Air Washer
Air Washer
Air Washer
Fig.1 shows schematic representation of air washer. It involves the flow of air through a
spray of water. During the course of flow, the air may be cooled or heated, humidified or
dehumidified or simply adiabatically saturated depending on mean surface temperature of
water. The water is, accordingly, externally cooled or heated or simply recirculated by a pump.
Make up water is added for any loss in the case of humidification of air. Eliminator plates are
provided to minimize the loss of water droplets.
Fig.1
Fig.2
Fig.2 shows the thermodynamic changes of state of air along paths 1-2 in an air washer,
depending on the mean surface temperature of water droplets ts which is equal to the actual
temperature of water.
Thus, the droplets of water act as wetted surface, and both sensible and latent heat transfer take
place. Their directions depend on the temperature and vapour pressure potentials. The
following processes are possible:
Process 1-2A: Heating and humidification (ts > td1)
The mean surface temperature of water is greater than dry bulb temperature of air. The water
is externally heated.
Process 1-2B: Humidification (ts = td1)
The mean surface temperature of water is equal to dry bulb temperature of air. The enthalpy of
air increases. Hence the water is required to be externally heated.
Process 1-2C: Cooling and Humidification (tw1 < ts < td1)
The mean temperature of water is less than the dry bulb temperature of air but greater that the
wet bulb temperature of entering air. Though the air is cooled, its enthalpy increases as a result
of humidification. The water is, therefore, required to be externally heated.
Process 1-2D: Adiabatic saturation (ts=tw1)
This is the case of pumped recirculation of water without any external heating or cooling. There
is no heat gain or loss from the spray of water and the same water is circulated again and again.
The recirculated water reaches the equilibrium temperature which is equal to the wet bulb
temperature of entering air. The cooling and dehumidification of air occurs at constant
enthalpy.
Process 1-2E: Cooling and Humidification (tdp1 < ts < tw1)
The surface temperature of water is less than the wet bulb temperature of air but more than the
dew point temperature. The process is similar to 1-2C with the difference that the enthalpy of
air decreases in this case. Accordingly, water is required to be externally cooled.
Process 1-2F: Cooling (ts = tdp1)
The temperature of water is equal to the dew point temperature of air. Water is required to be
cooled.
Process 1-2G: Cooling and Dehumidification (ts < tdp1)
The mean water surface temperature is lower than the dew point temperature of air. Air is
simultaneously cooled and dehumidified. The process is exactly similar to that of a cooling and
dehumidifying coil.
It is thus seen that the air washer affords means for a year-round air-conditioning system.