T110D
Air Conditioning Study Unit


Users Manual
and Exercise Guide











Didacta Italia



T110D
Air Conditioning Study Unit


Users Manual
and Exercise Guide











Didacta Italia Srl - Strada del Cascinotto, 139/ 30 - 10156 Torino
Tel. +39 011 273.17.08 273.18.23 - Fax +39 011 273.30.88
http:/ / www.didacta.it/ - e-mail:[email protected]





















The information contained in this manual has been selected and verified with the
greatest care. However, no responsibility stemming from its use can be ascribed to the
Authors or to Didacta Italia or any person or company involved in its preparation.
The information contained in this manual can be modified at any time and without
warning on account of technical or educational needs.
Copyright Didacta Italia 2004
Reproduction by any means, including photocopying of this test or parts thereof, or the
figures contained therein, is strictly prohibited.
Printed in Italy - 26/ 07/ 04
Code 01610E0704 Edition 01 - Revision 01
table of contents
T110D User' s Manual v
Table of Contents

1. General .................................................................................... 1

2 Composition and description................................................. 3
2.1 Composition............................................................................................... 3
2.2 Description ................................................................................................. 4
2.2.1 General synoptic ..........................................................................................................4
2.2.2 Control panel ................................................................................................................6
2.2.3 Transducer and signal conditioning unit ...................................................................7
2.2.4 Data acquisition and analysis software .....................................................................8

3. Starting .................................................................................. 11
3.1 Starting the unit ....................................................................................... 11
3.2 Starting the data ac quisition system .................................................... 11
3.3 Taking the Measurements with Data Acquisition System .................. 11
3.4 Preparing the system for a prolonged period of inactivity................ 12

4. Experimental Exercises......................................................... 13
4.1 Introduction to the exercises................................................................. 13
4.2 Basic Exercises......................................................................................... 13
Exercise 4.1 Air sensitive heat variation ...........................................................................13
Exercise 4.2 Variation in the latent heat of the air.........................................................16
Exercise 4.3 Defrosting (Evaporation Cooling) ...............................................................21
Exercise 4.4 Condensed Cooling .....................................................................................22
Exercise 4.5 Valutation of the efficiency of a frigorific machine .................................24
4.3 Advanced Exercises.................................................................................. 27
Exercise 4.6 - Full Air Conditioning Plant .............................................................................27
Exercise 4.7 - R22 Compression Refrigeration Cycle.........................................................36

table of contents
vi Didacta Italia
5. Exercises with SAD/ T110D Automatic data acquisition
system ...................................................................................53
5.1 Formulas used for air conditioning tests (Test 01) ................................ 53
5.2 Formulas used in cooling tests (Test 02) ................................................ 56
5.3 Experimental exercises............................................................................ 57
Exercise 5.1 - Air conditioning test (Test 01) ...................................................................... 57
Exercise 5.2 - Air conditioning test (Test 01) with pre-heater .......................................... 61
Exercise 5.3 - Air conditioning test (Test 01) with heater.................................................. 65
Exercise 5.4 - Air conditioning test (Test 01) with cooler .................................................. 69
Exercise 5.5 - Air conditioning test (Test 01) with humidifier and water......................... 73
Exercise 5.6 - Air conditioning test (Test 01) with steam humidifier ................................ 77
Exercise 5.7 - Cooling test (Test 02) .................................................................................... 81
Exercise 5.8 - Conditioning Cycle in the Wet Air Mollier Diagram (Test 03) ................. 84

6. Annex 1 - Table for the collection of test data ...................85

7. Annex 2 - Psychrometric diagrams.....................................87
7.1 Enthalpy diagram of Freon R22 ............................................................. 87
7.2 Psychrometric diagrams of air ............................................................... 89

8. Annex 3 - Table for the air speeds in m/ s............................95

9. Appendix 4 - T110D/ 1 .........................................................97

Chapter 1.
T110D User s Manual 1
1. General
The air conditioning and climate control study unit T110D has been specially
designed to serve as a highly advanced teaching tool: simplicity and clarity are the basic
features enabling the teacher and the students to carry out a variety of experiments
without having to acquire complex utilisation procedures.
The operating principle of this unit is as follows: a stream of air generated by a
centrifugal fan is made to pass through a tunnel via a fluid thread rectifier. As it goes
through the tunnel the air undergoes a series of treatments until it reaches a final
chamber representing the environment to be conditioned. The air, in fact, is initially pre-
heated, then humidified by means of steam diffusers, then cooled by means of the R22
evaporator and finally conveyed into the end chamber.
Before this last step, the air can be heated and humidified again by means of water
diffusers, enabling the students to become familiar with the heating processes and to
vary the greatest possible quantity of parameters, for a thorough understanding of
climate control. The study unit is self-sufficient in terms of the instrumentation
necessary to perform all the tests which are described in a theoretical-practical manual.
The T110D has a testing section entirely made of stainless steel and mounted on a
wheeled frame that also carries part of the cooling circuit, a small steam boiler, the
power supply, adjustment and control module, and a panel with a scheme of the entire
circuit silk-screen printed on.
The variety of tests that are possible with this study unit encompasses all the
problems of air conditioning, such as:
determination of the thermal balance
determination and study of the effects of removing/adding heat and humidity
from/to the air, and the relative air conditioning system techniques
study of the influence of air velocity and flow on the temperature and humidity of
the air
conditioning of ambient air in summer
conditioning of ambient air in winter
air conditioning for industrial processes
execution of psychrometric conversions on Mollier's diagrams for wet air
execution of enthalpy and matter balances
study of the principles governing the simultaneous transport of heat and matter
evaluation of the efficiency of the cooling cycles employed in air conditioning
processes
general
2 Didacta Italia
measurement of pressure drops in the air going through a channel
An automatic data acquisition and analysis system for personal computer is
available. This unit, called SAD/T110D, makes it possible to perform the
measurements, plot the characteristic curves on screen or print them out, file the data on
a disk or print them out entirely automatically.

Chapter 2.
T110D User s Manual 3
2. Composition and description
2.1 Composition
The T110D study unit (Code 954000) shown in fig. 2.1 consists of a truck mounted
structure housing the following elements:

Fig. 2.1 - Overview of the system
1. Testing tunnel of stainless steel;
2. Centrifugal fan;
3. Control panel;
4. R22 sealed compressor;
5. Condenser;
6. Steam generation boiler;
7. Centrifugal pump;
8. Manometer panel;
9. Differential micro-manometer.
composition and description
4 Didacta Italia
The automatic data acquisition system (SAD/T110D) includes:
a kit of electronic transducers for the conversion of the quantities to be measured
into the corresponding electric signals (code 914321);
a signal conditioning and A/D conversion unit (code 914320);
data acquisition and analysis software for Windows (code 914324).
2.2 Description
2.2.1 General synoptic

Fig. 2.2 - General synoptic scheme
Fig. 2.2 shows the overall scheme of study unit T110D.
The basic components are:
Variable speed (0 to 1450 rpm) centrifugal fan
No. 2 fluid threads rectifiers
Set of pre-heating resistors, with power continuously adjustable up to 3 kW
Steam generation boiler (1.3 kg/h)
Set of heat diffusers
R22 air evaporator
R22 air condenser with 3.8 l capacity tank
1.2 HP sealed compressor
Chapter 2.
T110D User s Manual 5
Drier filter
Thermostat controlled expansion valve
Set of heating resistors, with power continuously adjustable up to 3 kW
Set of water diffusers in a closed circuit fed by a pump from a 2 litre calibrated
container
No. 2 chambers with inspection windows.
The system includes the following control and measuring instruments:
Digital temperature indicator, connected to 4 thermal resistors selected by means
of a switch
No. 4 PT100's T1; T2; T3; T4 from -100 to +100 C
No. 2 ammeters connected to the heating sets
Low pressure manometer, 15 bar
Electronic pressure transducer Pe (Capacity 0 to 10 bar) (only in conjunction
with SAD/T110D)
High pressure manometer, 24 bar
Electronic pressure transducer Pc (Capacity 0 to 25 bar) (only in conjunction
with SAD/T110D)
No. 2 dry bulb thermometers, - 10 to 50C, 1/5C accuracy
No. 3 dry bulb PT100's Tad; Tcd; Tod, 0 to 150C (only in conjunction with
SAD/T110D)
No. 2 wet bulb thermometers, - 10 to 50C, 1/5C accuracy
No. 3 wet bulb PT100's Taw; Tcw; Tow, 0 to 150C (only in conjunction with
SAD/T110D)
No. 1 psychrometer
Tilting scale micro-manometer, 0 to 200 mm H
2
O
Differential electronic pressure transducer to measure air flow rate, deltap
(capacity 0 to 50 mm H
2
0) (only in conjunction with SAD/T110D)
Calibrated diaphragm, 100 mm
7 to 30 bar pressure switch, differential pressure adjustable between 2.5 and 3.8
Electronic thermostat with pre-selector, 0 to 99.9 C.
composition and description
6 Didacta Italia
The SAD/T110D automatic data acquisition system makes it possible to acquire
automatically the following quantities:
Taw: wet bulb ambient temperature
Tad: dry bulb ambient temperature
Tcw: wet bulb testing chamber temperature
Tcd: dry bulb testing chamber temperature
Tow: wet bulb output temperature
Tod: dry bulb output temperature
T1 Condenser input temperature
T2 Condenser output temperature
T3 evaporator input temperature
T4 evaporator output temperature
Pe low pressure (intake)
Pc high pressure (compression)
p differential pressure
2.2.2 Control panel
The control panel consists of the following 6 modules, which can be recognised in
the front view shown in fig. 2.3:
Fan module
Makes it possible to turn on and off the fan and adjust its speed
Power supply module
Makes it possible to turn on the auxiliary circuits by means of the start key or turn
them off by pressing the emergency button
Pre-heater module
This is used to select the preheating power, 1000W, 2000W or 3000W, and to read
the current absorption value on the ammeter.
Temperature module
Makes it possible to select the operating set-point and to display the cooling circuit
temperatures.
Chapter 2.
T110D User s Manual 7
Compressor module
This is used to start the compressor and determine whether or not the thermostat or
the pressure switch have been triggered
Heater module
This is used to select the heating power, 1000W, 2000W or 3000W, and to read the
current absorption value on the ammeter.

Fig. 2.3 - Front view of the control panel
2.2.3 Transducer and signal conditioning unit
The transducer and signal conditioning unit (only in conjunction with SAD/T110D)
consists of the following 3 modules, which can be recognised in the front view shown in
fig. 2.4:
Temperature module
Makes it possible to acquire the temperature values at the different points along the
circuit on a -100 to +100C scale by means of a selector.
Differential pressure module
Makes it possible to acquire the differential pressure of the output air stream on a
scale from 0 to 50 mm H
2
O.
composition and description
8 Didacta Italia
Pressure module
Makes it possible to acquire the delivery pressures (0 to 25 bar scale) and intake
pressures (0 to 10 bar) of the cooling compressor.
The upper part of this unit (see fig. 1.4) accommodates:
The general switch, called POWER
The ground socket, called GND.

Fig. 2.4 - Front view of the transducer and signal conditioning unit
2.2.4 Data acquisition and analysis software
The software has common characteristics that are described in detail in the "SAD -
Data Acquisition System - User's Manual" supplied with the system.
The installation procedure is also explained step by step in this manual.
Chapter 2.
T110D User s Manual 9

Fig. 2.5 - SAD/T110D software: working environment

Fig. 2.6 - SAD/T110D software: experimental diagram
composition and description
10 Didacta Italia

Chapter 3.
T110D User s Manual 11
3. Starting
3.1 Starting the unit
1. Make sure that the humid bulb thermostats are filled with water and that the gauze
is humid and also that the thermometer is hit by an air current and that it is not
immersed in the water container;
2. Check the availability of:
Electrical power supply: 380 V AC 3 ~ + N 50Hz; 220V AC 60Hz
Maximum power 9 kW
1. Set all the selectors on zero;
3. Fill the humidifier circuit tank and the steam generation boiler with water;
4. That the mater input valve of the boiler is open, while the exit one is closed; and
also that the seal clamps of the tubes are well closed.
5. Connect the special plug to the mains voltage 380V AC 3 ~ + N 50Hz or 220V AC
3 ~ 60Hz
3.2 Starting the data acquisition system
1. Connect the transducer to the signal conditioning and A/D conversion unit, by
exploiting the front connectors of the unit and the cables supplied with the system.
2. Connect the signal conditioning unit to the parallel or serial port of the Personal
Computer, by means of the cable supplied as standard.
3. Connect the signal conditioning unit to the 220V AC 50/60 Hz mains voltage.
4. Install the SAD/T110D software in the Personal Computer according to the
indications contained in the "SAD - Data Acquisition System - User's Manual".
3.3 Taking the Measurements with Data Acquisition System
1. Power the unit by means of the special safety switch.
2. Turn the start key in the control panel power module, so as to activate the auxiliary
circuits.
3. Start the fan and adjust fan speed by checking the flow rate on the differential
micro-manometer.
starting
12 Didacta Italia
4. Measure the values and enter them in the table shown in annex 1, or, if using the
SAD/T110D, proceed with the automatic acquisition of the data.
5. Use the heating and humidifying devices to vary the operating conditions of the
study unit.
3.4 Preparing the system for a prolonged period of inactivity
1. Set all the selectors on zero.
2. When using the SAD/T110D, turn off the signal conditioning unit.
3. If you don't use the unit for a certain period we suggest that you empty the boiler
for the vapour production, operation that must be done after having sent out all the
vapour.
Chapter 4.
T110D User s Manual 13
4. Experimental Exercises
4.1 Introduction to the exercises
Following here will be reported a series of guide exercises that have as their aim the
comprehension of the theoretical principles illustrated in the previous chapters and the
valuation of the possibilities of the air conditioning machines.
It is not considered in this treatment, the valuation of the problems tied with the
mixing of the air treated with the fraction untreated of a given environment, as also
phenomena tied with the filtration, purification and at times sterilization of air in certain
environments, very important factors in air conditioning, but specific and tied to the use
of air so of difficult generalization.
The use of the T110D unit is devoted to the comprehension of the principles and the
problems of the conditioning machines.
4.2 Basic Exercises
Exercise 4.1 Air sensitive heat variation
This exercise has as its aim the understading of the transformations that an air
undergoes without a variation in its absolute humidity.
The numerical values are examples introduced for a better comprehension of the
diagram of the exercise; in reality, depending on the environment in which the group
will be used, different couples of humid bulb and dry bulb temperatures will be found.
Suppose you have an environmental air with the following couples of temperatures:
T
s
= 20C
T
u
= 15C
Using the psychrometric diagram (reported in the appendix) the relative umidity is
found at the intersection of the humid bulb and dry bulb temperature; while the absolute
humidity is read on the ordinate axis drawing a horizzontal line from the point found:
U = 0.0088 Kg/kg d.a.
The temperatures T
u
and T
s
must be read with the hygrometer included in the group
(as reported in the general treatment); therefore the fan that inputs air into the channel is
turned on, choosing the work delivery, for example positioning the knob on 70 80%.
experimental exercises
14 Didacta Italia
At this point you turn on the heat of the resistance B (ref. to fig. complete diagram);
operating on the knob situated on the control panel, regulate the electrical current to
heat the air that flows into the channel at a temperature not higher than 50C, to be able
to use the psychrometric diagram.
U
r
60%
The control of the heating temperature is done manually operating on the control
panel and reading the value of the temperature with the thermometers Q.
Suppose you heat the air to T
s
35 C the value of T
u
must be of about 20 C.
Reporting these values on the psychrometric diagram, you will find that the air will
have a relative humidity of:
U
r
= 25% and U = 0.0088 kg/kg d.a.
Therefore the air will have absorbed only the sensitive heat with a measurement
found once again from the psychrometric diagram through the subtraction of the
enthalpy at the final point (after the heating) and the initial one:
. . / 4 . 15 1 . 42 5 . 57 s a Kg kJ h h h
i f
= = =
Measuring the air delivery in the channel with the differential micro-gauge,
according to what is reported in the general treatment; finding the value of the specific
volume of the at the final conditions from the psychrometric diagram
v 0.885 m
3
/kg a.s.
it is possible to find the value of the thermal power needed for the heating of the air:

(

h
kJ
h
v
V
Q
where V is the air delivery in m
3
/h.
The example now shown, is that of air that acquires sensitive heat; to make this
happen it is necessary to cool air to a temperature higher than the dew point, below it
would also lose laten heat. For our air it would correspond to:
T
r
11.5 C
that is the intersection of the horizontal pasing through the rapresentative point of the
air, on the psychrometric diagram, and the curve at U
r
= 100%.
Chapter 4.
T110D User s Manual 15
To carry out this other exercise, it is necessary first to turn off the heating B and then
wait for a certain period of time so that the air that flows through the channel cools the
resistences, to decrease this period you can increase the air delivery; then position the
thermostat of the frigorific cycle at the temperature wanted higher than 11.5 C, for
example 15 C.
This operation must be done by pressing the pushbutton of the digital regulator and
turning the knob to the value requested.
At this point you can insert the frigorific cycle and wait until the air is cooled.
Remember that the value indicated by the set-point is the value at that moment, so
through it is possible to check the actual cooling of the air itself.
Suppose that after a certain period the last couple of thermometers gives the
following values:
T
s
= 15 C T
u
13.00 C
Note
If the value read by the dry bulb is slightly different from the set-point it can depend
from various factors:
the measuring points are in different points along the channel;
the precision of the mercury thermometer is higher than that of the probe;
the two sensors can read at different heights along the section of the channel.
Differences between 1 C are acceptable, if not, check if the set-point sensor is
situated at the center of the channel.
The values reported on the humid air diagram give:
U
r
82% U = 0.0088 Kg/kg a.s
Therefore, also in this case the air has undergone a variation in sensitive heat
changing its U
r
but not the absolute humidity.
Similarly to before it is possible to find the value of the thermal power subtracted:

(

=
h
kJ
h
v
V
Q
The minus sign is to indicate that the heat is subtracted and not given out by the air.
experimental exercises
16 Didacta Italia
Exercise 4.2 Variation in the latent heat of the air
There is a variation in the latent heat of the air when not only its dry bulb
temperature changes, but also its absolute humidity; this can happen not only with
humidification heating but also with de-humidification cooling.
Humidification heating
To do this exercise, vapour will be used, so it is better to make sure that all the
contacts of the boiler with the entrance and exit of the water have been well done,
checking if the electrovalve for the vapour input into the channel and the two needle
valves are closed, verifying if the opening for the water in the boiler is open and that the
exit is closed, turn on the boiler.
At this point it is necessary to have cold water (to see better the phenomena),
obtainable using the frigorific group G.
Then, after having turned on the fan and set the air delivery, position the thermostat
of the fridge at a low value (for ex. 5 C) and turn on the compressor.
After a certain period read the temperatures of the last couple of thermometers and,
for example, you will have:
T
s
= 5 C T
u
= 4.5 C
therefore, using the psychrometric diagram you have (similarly to what shown in the
previous exercise):
U
r
= 97% U = 0.0052 kg/kg a.s.
At this point open the steam solenoid valve (starting its own switch) to heat the air up
to a given temperature.
Switch off the boiler, close the solenoid valve when the temperature aims to increase
too much preventing the use of the psychrometric diagram.
During this heating, obviously, the frigorific group must be left in function; suppose
that the air is heated and gives the following values:
T
s
= 35 C; T
u
= 32 C
that correspond to:
U
r
= 72%; U = 0.0256 kg/kg a.s.
Therefore the air has taken in:
0.0295 0.0052 = 0.0243 kg/kg a.s.
Chapter 4.
T110D User s Manual 17
of water at vapour state.
If you want to calculate the latent and sensitive heat the following method is used:
from the point representing the initial air A (fig. 4.1) draw a horizontal line,
while from point B, final point draw a vertical line; the point C, intersection of
the two lines, represents an imaginary point that lets us find the sensitive and
latent enthalpy.
This can be done reading from the points AB and C their enthalpies on the axis
slanted leftwards of the curve U
r
= 100%.
h
A
= 18 kJ/kg; h
B
= 101 kJ/kg; h
c
= 49 kJ/kg a.s.

As a matter of fact, it's as if the air were heated with a constant U in the section A C
and humidified in the section B C, so the sensitive heat will be:
h
C
h
A
= 49 18 = 31 k J/kg a.s.
while the latent one is:
h
B
h
C
= 111 49 = 62 kJ/kg a.s.
The thermal powers will be, knowing the delivery V and the specific volume v of the
air:
experimental exercises
18 Didacta Italia
( )
(

h
kJ
h h
v
V
Q
A C s

( )
(

h
kJ
h h
v
V
Q
C B 1

The umidification heating is a typical case of air treatment in winter conditions or for
industrial applications that request hot air with a certain degree of humidity.
In fact, we must say that in the case of winter conditioning (quite rare) in civil
environments, the air is heated and not humidified, leaving the humidity control to the
hourly renewals of the air in the environment for health purposes.
A very common application is, instead of changing the latent heat given by the
cooling, the conditioning and control of the humidity of the air in a frigorific room for
the preservation of foods; we will go back to this after having described the exercise.
To subtract water from an air and therefore subtract sensitive heat it is necessary to
cool the air to a temperature lower than that of the frost point.
To execute this exercise operate in the following manner:
turn on the fan and set the knob on a given position, suppose the air has the same
values of T
s
e T
u
of the previous exercises:
T
s
= 20 C; T
u
= 15 C: U
r
= 60%; U = 0.0088 Kg/kg a.s.
At this point the thermostat of the frigorific group must be set at a temperature lower
than frost point of the given air, in this case 11.5 C; so suppose you set the thermostat
at 5 C.
At this point turn on the frigorific group; after a certain period the last couple of
thermometers will show the conditions that the air has reached, suppose the following
values are read:
T
s
= 6 C; T
u
5.5 C
so:
U
r
95%; U = 0.0054 kg/kg a.s.
At this point the air will have undergone a change of the type reported in fig. 4.2
exagerating to better visualize the phenomena.
Chapter 4.
T110D User s Manual 19

In fig. 4.2 the full line with the arrow represents the real thermodynamic
transformation that the air has undergone, that is, a cooling A A', a de-humidification A'
B' along the saturation line, a slight heating B' B.
To find the value of the enthalpies of the case, similarly to what done in the previous
exercise, draw the horizontal through B and the vertical through A, the intersection
point C permits us to find the values of the enthalpies on the axis on the left of the
saturation curve:
h
A
= 42 kJ/kg a.s.; h
B
= 19.5 kJ/kg a.s.; h
C
= 33 kJ/kg a.s.
Therefore it is as if the air had undergone an imaginary transformation A C and C B;
in which in the section A C it is de-humidified by subtraction of the latent heat:
h
A
h
C
= 42 33 = 9 kJ/kg a.s.
and in the section C B it is cooled by the subtraction of the sensitive heat:
h
C
h
B
= 33 19.5 = 13.5 kJ/kg a.s.
The quantity of the water that the air has lost is:
U
A
U
B
= 0.0088 0.0054 = 0.0034 kg/kg a.s.
It is possible to collect the condensed water and verify that the calculations are
correct to certain limits: to do so it is necessary, once reached the standard conditions
(for a certain air delivery, constant T
s
and T
u
in point B), to measure the air delivery in
the channel (through the micro-gauge) V, and then in point B (with the psychometric
experimental exercises
20 Didacta Italia
diagram) the specific volume of the air v, then if the experiment is done for a period of
time T (in hours) you will have:
( ) | | O H kg P U U
v
V
T
B A 2
=
that represents the quantity of water subtracted from the air by cooling.
The experiment ends by stopping at the time T, measured with a watch (or stop-
watch), the air flow into the channel; at this point it is necessary to collect the water in
the container M.
Obviously part of the water can be in frost form at the evaporator; to collect it it's
necessary to defrost the evaporator.
Chapter 4.
T110D User s Manual 21
Exercise 4.3 Defrosting (Evaporation Cooling)
The defrosting operation is done periodically on environmental conditioning plants,
when the plants are continually used; in case non-continuous functioning, it is done only
in rest conditions of the plant.
The evaporator is defrosted by contact with hot air, or at least hotter than the
previous so also the environmental one.
In the case being examined, the defrosting is done by sending hot air on the
evaporator.
During the defrosting operation the frigorific group must be kept still.
At the end of the defrosting that must go on for a certain period of time, the water is
collected during the condensing cooling.
The quantity of total water thus obtained must be compared with the value of P
calculated, the value measured will be lower because, not considering the sperimental
errors, during the defrosting the defrosting air humidifies itself adiabatically in contact
with the evaporators frost.
The quantity of air acquired can be measured knowing the conditions of the air at the
beginning.
After having positioned the knob of the fan on a given position, and having measured
the air delivery, you will read the values with the couples of thermometers before the
evaporator, for example:
T
s
= 20 C; T
u
= 15 C; U
r
= 60%; U
1
= 0.0088 kg/kg a.s.
suppose that at the exit of the evaporator the air has the following values:
T
s
= 15 C; T
u
= 14 C; U
r
= 90%; U
2
= 0.0097 kg/kg a.s.
The defrosting must be protracted until the temperature of the air starts to rise again
and return to the value of 20 C; let's call t this defrosting time.
The air then has gone from a relative humidity of 60% to one of 90% and from an
absolute humidity of 0.0008 to another of 0.0097 taking in
(U
2
U
1
) = 0.0097 0.0088 = 0.0009 kg/kg a.s.
Therefore the
( )
s
P U U
v
V
t =
1 2

experimental exercises
22 Didacta Italia
The main experimental errors in this experience are that it is practically impossible to
drain all the evaporator's water and that the transitions in which the air and the water are
brought into equilibrium are not considered. However operating with a certain accuracy
these errors can be minimised; that is, working with the same air delivery both in the
frost formation stage than in the defrosting stage, and interrupt only the compressor to
indicate the end of the condensing cooling from the defrosting one.
Naturally the two experiences can be done separately one from the other and the
effects amplified for a better comprehension.
For example, you can start with an air containing more humidity and than sending to
the evaporator air heated with vapour in C.
Exercise 4.4 Condensed Cooling
The practical execution of this exercise has already been described in the chapter
dedicated to the latent heat variations in an air, here we only want to describe the
application of this principle to the humidity control in a refrigerating room.
Consider the variations in humidity (both absolute and relative) that the air
undergoes inside the room going from 0 C to -5 C.
Why this cooling of the air?
It is evident that if you want to maintain in the room a standard temperature of 0 C
and at the same time take away the heat brought in by the foods that are introduced, we
have to make the air go out from the evaporator at a lower temperature for ex. 5 C.
Consequently the temperature of the Freon must be even lower for ex. 10 C.
In this case is implemented a periodical cooling of the room's air from 0 C to 5 C
and therefore its heating Freon 5 C to 0 C.
This determines a cycle that presents the following phases:
cooling without de- humidification from 0 C to the frosting point. If
hypothetically the cycle is started with the air containing 90% relative humidity,
the frost points of 1.4 C/ref fig. 4.3) but we advise to follow the tracing of the
cycle on the psychrometric diagram;
cooling with de-humidification (along the saturation line) to the temperature
wanted of 5 C;
heating of the air from 5 C to 0 C, as a consequence of the taking away of the
heat from the room. U
r
65%. In this phase there can be a passage of humidity
from the foods to the air of the room and therefore a drying of the foods or a loss
in freshness caused by the decrease of U
r
.
The diagram shows that during this cycle the air has been de-humidified, because it
has gone from an absolute humidity of about 0.0034 kg/kg d.a.; at to 0.0025 kg/kg d.a.;
so it has lost about 0.9 gr of steam for every kg of air.
Chapter 4.
T110D User s Manual 23
The control of humidity is then done by changing the temperature of the air at the
exit of the evaporator, decreasing in the case you want to dry out, and increasing in the
case you want to keep the food fresh for a short preservation.
In the example given, making the air some out from the evaporator at 3 you have U
r

85% so the drying effects resulting on the food will be diminished.
experimental exercises
24 Didacta Italia
Exercise 4.5 Valutation of the efficiency of a frigorific machine
Before reading the parameters for the study of the cycle and the balances it is better
to let the group run for a couple of minutes to permit the machine to go at full standard.
First it is necessary to find on the diagram log P, h (in the appendix is reported the
diagram for R22) the real functioning on the cycle.
To do so it is necessary to find the temperatures in the various points of the cycle
(t1t4) and the drawing in and compression pressures that are indicated with P
v
and P
c
,
that are not the same of the evaporation and compression ones, because of the loss in
charge that the frigorific fluid undergoes in the heat exchangers.
For example, let the values found be the following for a certain air delivery at the
evaporator:
t
1
= 65 C condenser entrance
t
2
= 25 C condenser exit
t
3
= -15 C after the expansion valve
t
4
= 6 C exit evaporator
P
e
= 12 bar compressor pressure
P
c
= 16 bar evaporator pressure
The construction of the cycle is made up of the following phases:
you set on the bell of the state diagram for x = 1, the points correspondent to the
pressures P
e
and P
c
;
prolonging the isobaric P
e
until it intersects the isothermal of 65 C, in the field
of the overheated vapour, you will obtain point 4 (ref. fig.4.4); similarly for the
isobaric P
c
, to the intersection with the isotherm 6 C you obtain point 3;
prolonging the isobaric P
c
until it intersects t
2
= 25 C position point 1 on the bell
for x = 0. In this case the liquid R22 go overcooling, because point 1 is in the
liquid area, in this area the isotherms can be considered; to a good
approximation, vertical. The state of point 1 depends on the charge losses that the
R22 undergoes in the condenser, that given the specification adopted in the
group, results always very limited;
point 2 is found going vertically from point 1 to the isotherm/isobar
correspondent to t
3
= -15 C.
Collecting the various points found (14) the working characteristics of the cycle are
found.
Chapter 4.
T110D User s Manual 25
The difference in pressure between point 2 and point 3 P
2,3
is the loss of charge that
the frigorific fluid undergoes in the evaporator, this loss in an air evaporator is always
big enough because of the winding paths that the fluid must follow.
After having traced the cycle, the enthalpies can be measured in the various points;
remember that the enthalpic values read on the diagram are for mass unit of the
refrigerating fluid (kJ/kg).
For example in the case considered we have:
h
1
= h
2
= 230 kJ/kg
h
3
= 415 kJ/kg
h
4
= 440 kJ/kg
Having built the cycle on the diagram log P/h, it is possible to give a valuation to the
efficiency of the frigorific machine.
Referring to fig. 4.4 the values of the enthalpies in points 1, 2, 3, 4, and the quantities of
heat d
1
and d
2
exchanged one with the other at the condenser and the evaporator, and
the work of the cycle given by the compressor l
ciclo
are given.
For the hypothesised working conditions they result:
q
1
= h
4
h
1
= 215 kJ/kg
q
2
= h
3
h
2
= 185 kJ/kg
l
cicle
= h
4
h
3
= 25 kJ/kg
since they derive from the measurement of the real conditions of the frigorific fluid,
these values consider the various performances at the compressor (mechanic, electric),
so:
04 . 7
25
185
2
= = =
ciclo
q

experimental exercises
26 Didacta Italia

We advise you to calculate with sir at different temperatures, heating with the
resistance B at various humidities, heating with C and with different air deliveries in the
channel as stated in general port in order to understand the mass as well as energy
balances in psichrometry technique.



Chapter 4.
T110D User s Manual 27
4.3 Advanced Exercises
Exercise 4.6 Full Air Conditioning Plant
a - Aim
Focusing on the experimental air conditioning apparatus present in the T110D
assembly, analysed in the laboratory, this chapter describes the function of the system,
highlighting the thermodynamic role played by the various parts.
The temperature measurements made in the laboratory are used to calculate the
transformations undergone by the air, plotting them on a Mollier diagram for wet air.
The following are also calculated:
Thermal powers exchanged in the pre-heater, cooling set and post-heater;
The flow rate of water vaporised by the steam humidifier;
The flow rate of water vapour condensed in the cooling plant.
Note
It is assumed:
that water vapour from the humidifier is saturated steam at 1 bar;
that the water vapour present in the air at the outlet of the cooling set is in a
saturated condition.
b Instructions for the teacher
Conditions to be set on the apparatus:
The following conditions are suitable for exercises relating to a room temperature of
16 20 C.
Fan: 50 %
Pre-heater: position 2 4-5 A
Post-heater: position 2 4 A
Refrigerating cycle thermostat: 12 C
Notes
The flow rate of steam produced by the boiler is quite high. It is therefore
important to open the steam inlet valve only when readings are taken (just before,
experimental exercises
28 Didacta Italia
make sure that steady state conditions have been reached), otherwise water may run
out.
If dehumidification occurs in the cold plant do NOT give the student the
temperature of the air measured downstream of the plant itself (value shown on the
display of the thermostat sensor of the fridge cycle). For the calculations it is
sufficient to assume that air has a relative humidity of 100%.
c Carrying out the test
c1 Main points of the summer air conditioning cycle
This exercise consists in the realisation of a summer air conditioning cycle. This
cycle did not use the room air directly, aspirated through the fan, but pre-heated and
humidified it (using steam) in order to reproduce particularly severe summer
conditions (high temperatures, high water vapour content). A schematic diagram of the
plant, highlighting the areas in which the various transformations occur, is shown in
Figure 4.5.

Batteria di refrigerazione
Batteria di post riscaldamento
Nebulizzatore
Batteria di preriscaldamento
As mentioned earlier, in order to simulate a case of summer conditioning, air is taken
in from the room at the following conditions T
abs
= 16.5 C and T
abu
= 11 C (point a)
and is treated in the pre-heating set where it is heated (transformation a-a) and then
humidified (trasformation a-1) using a steam diffuser.
The output consists of a flow of hot and wet air (conditions in point 1) to be used by
the summer transformation cycle.
Chapter 4.
T110D User s Manual 29
The summer conditioning cycle includes:
Cooling and dehumidification in the cooling set (transformation 1-1), supplied
with an appropriate refrigerant (see refrigerating cycle exercise). This
transformation brings the air to = 100 % in point 1.
Heating of the air using the post-heating set (transformation 1-2).
The data measured during the course of a typical exercise are summarised in Table
4.1:


a 16.5 11
1 42 28
2 28 18
.
Using these values it is possible to assess the representative state of thermodynamic
conditions of wet air. In fact, if we remember that the wet-bulb temperature corresponds
to the adiabatic saturation point temperature, it is possible to identify points a, 1 and 2
using the Mollier wet air diagram.
To do this, we must identify the isoenthalpic curves passing through the intersection
between the respective wet bulb isotherms and the saturation curve = 100 %.
Having drawn these straight lines, the points representing the thermodynamic state of
the air are identified in correspondence with the intersection between the isoenthalpic
lines and the respective dry-bulb isotherms.
The following can then be measured: relative humidity, titres and enthalpy. These
data are set out in Table 4.2

a 7.63 31.92 50 6.0


1 21.50 90.00 35 18.5
2 12.10 50.65 38 9
.
experimental exercises
30 Didacta Italia
In order to identify the remaining points (a and 1) it is necessary to calculate energy
and mass balances for the various parts making up the plant.
c2 Balances for pre-heater + humidifier (sections a-1)

Energy balance:
& &
Q Q
pre risc 1
=



& &
Q L
i 1
= & m h =>
( )
&
& & Q m h h m h
a a v v 1 1
=
q h h h
m
m
a v
v
a
1 1
=
&
&

The enthalpy h
v
of steam corresponds to saturated steam at 1 bar:
From the table we find: h
v
= 2676 kJ/kg.
Mass balance for steam:
& & & m x m x m
a a a v
=
1
0
&
&
m
m
x x
v
a
a
=
1

By replacing the values in Table 4.2, we obtain:

&
&
m
m
v
a
= 18.5 - 6 = 12.5 g/kg
kg kJ q / 63 . 24 10 5 . 12 2676 92 . 31 90
3
1
= =


kg kJ q / 63 . 24
1
=
Chapter 4.
T110D User s Manual 31
In order to identify point a, the end of pre-heating, it is necessary to define the mass
and energy balance of the thermodynamic system included between sections a and a
(pre-heater) (the same results could also be obtained by writing the balances the
humidifier alone, system a-1) (see Figure 4.5).
c3 - Balance for pre-heater (sections a-a)


Energy balance:

( )
&
&
'
Q m h h
a a a 1
=
Mass balance of steam:
& &
'
m x m x
a a a a
= 0 x
a
= x
a

by replacing the numeric values you obtain:
kg g x
a
/ 6
'
=
( ) h + q = /
a 1 ' ' 1 1 a a a a
h h h q m Q = = &
&

and therefore
h
a
= 24.63 + 31.92 = 56.55 kJ/kg = 13.51 kcal/kg
Having calculated the enthalpy for point a, it is identified on the Mollier diagram as
the intersection between isoenthalpic h
a
and the isotitre straight line x
a
= x
a

corresponding to point a.
In order to calculate heat q
2
removed by the refrigeration set and the heat q
3
provided
by the post-heater, a balance of mass and energy must first be calculated for the system
consisting of the refrigeration set plus post-heating set. In this way, you calculate the
overall thermal flow exchange by the system.
experimental exercises
32 Didacta Italia
Subsequently, using a balance for the post-heater alone, the separate contributions of
q
2
and q
3
can be calculated.
c4 - Balance for the refrigerator system + post-heater (sections 1-2):


Energy balance:

& &
Q L
i
= & m h =>
( )
+ = +
& &
& & Q Q m h h m h
a l l 3 2 2 1

If we consider the enthalpic flow issued with the flow of condensed steam to be
negligible, & m h
l l
0, this relation can be written as:

( )
+
= +
& &
&
Q Q
m
q q h h
a
3 2
3 2 2 1

by replacing the numeric values: + q q
3 2
= 50.65 - 90 = -39.35 kJ/kg
Balance of water vapour mass:
& & & m x m x m
a a l
+ =
2 1
0
from which:

&
&
m
m
x x
l
a
=
1 2

by replacing the numeric values:
Chapter 4.
T110D User s Manual 33

&
&
m
m
l
a
= 18.5 - 9 = 9.5 g/kg
In order to make a separate calculation of the contribution provided by q
2
and that by
q
3
, and to find the thermodynamic state of point 1, we must lastly define the energy and
steam mass balance for the post-heater alone (or, equivalently, the cooling set alone).
c5 - Balance for post-heater (sections 1-2):



Energy balance:

( )
&
&
'
Q m h h
a 3 2 1
=
Steam mass balance:
& &
'
m x m x
a a
=
2 1
0 x
2
= x
1

point 1 is the most representative point for the thermodynamic conditions of air
output from the cooling set. As indicated in the text, this point will lie on the curve =
100%. Moreover, the balance of the steam mass is used to calculate that the titre of 1 is
equal to the title of 2.
It is therefore possible to determine, univocally, point 1 on the Mollier diagram as
the intersection of the isotitre passing through 2 and the curve = 100%.
Having fixed 1, it is possible to read the corresponding enthalpy from the Mollier
diagram:
h
1
8.3 kcal/kg = 34.75 kJ/kg
experimental exercises
34 Didacta Italia
by developing the calculations and replacing the numeric values, you obtain:
x
1
= 9 g/kg

( )
&
/ &
'
Q m q h h
a 3 3 2 1
= =
q
3
= 50.65 - 34.75 = 15.90 kJ/kg
and therefore:
q
2
= q
3
+ 39.35 = 15.90 + 39.35 = 55.25 kJ/kg
q
3
= 15.90 kJ/kg e q
2
= -55.25 kJ/kg
Using these data, it is possible to report the fixed points (a, a, 1, 1, 2) and the
relative transformations on the Mollier wet air diagram. The trend from a typical
experience is shown in the diagram below (Fig. 3).
c6 Calculating the air flow rate
The air flow rate is measured using a calibrated diaphragm that detects a fall in
pressure. Using this finding and the characteristic tables for the diaphragm (enclosed) it
is possible, using linear interpolation, to determine the speed of air flow.
Values measured:
p = 6.35 mmH
2
O
T
air
= T
2
= 28 C
Diameter of diaphragm = 0.1 m
The following is shown by the table:
v
air
= 10.5 m/s
and therefore:
4
2

= =


a air air a
vI Sez v m& = 1.29(273/308)10.57.8510
-3
= 0.0942
kg/s 339 kg/h
Chapter 4.
T110D User s Manual 35
Once the flow of treated air is known, it is then possible to calculate the thermal
power exchanged, the flow rate of vaporised water and condensed water.
c7 Calculation of the thermal powers exchanged and the flow rates of
condensed and vaporised water

& &
& Q Q q m
pre risc a
= =
1 1
= 24.630.0942 = 2.32 kW

a refrig
m q Q Q &
& &
= =
2 2
= (-55.25)0.0942 = -5.20 kW

a heat post
m q Q Q &
& &
= =
3 3
= 15.900.0942 = 1.50 kW
&
&
&
& m
m
m
m
l
l
a
a
= 9.50.0942 = 0.895 g/s 3.22 kg/h
&
&
&
& m
m
m
m
v
v
a
a
= = 12.50.0942 = 1.18 g/s 4.25 kg/h
To sum up:

&
Q
pre risc
= 2.32 kW

&
Q
raff
= -5.20 kW

&
Q
post risc
= 1.50 kW
& m
l
= 0.895 g/s 3.22 kg/h
& m
v
= 1.18 g/s 4.25 kg/h
Exercise 4.7 R-22 Compression Refrigeration Cycle
a - Aim
Focusing on the compression refrigerating machine, operating with R22 in the
T110D assembly, this chapter describes the function of the refrigerating assembly,
highlighting the thermodynamic function of the various parts.
experimental exercises
36 Didacta Italia
By measuring pressure and temperature in the laboratory, it is also possible to
calculate:
1. The main points of the thermodynamic cycle, plotting the cycle itself on the
equilibrium diagram (h, log p) and (T,s). (To carry out this part, the following
hypotheses are used to make the calculations: slight falls in pressure in exchangers,
condensation end points to give a saturated liquid),
2. The energy exchanged by the system during the various transformations (heat and
work),
3. The refrigerating efficiency of the cycle,
4. The flow rate of R22 in circulation. For this calculation, it is supposed that all the
heat removed from the air during cooling is transmitted to R22 running inside the
evaporator,
5. The electrical power absorbed by the electric motor (assuming that the compressor
has a mechanical output of 0.8 and the motor an electrical output of 0.9).
Lastly, calculate the efficiency of the refrigerating cycle in the event that this
consists of an inverse Carnot cycle between:
The same evaporation and condensation pressures of the real cycle.
The pressures of condensation and evaporation corresponding, respectively to
room temperature and the temperature of refrigerated air.
In both cases determine the mechanical powers and the flow rates of refrigerating
fluid required to remove a head from the refrigerated environment equivalent to that
measured experimentally.
b Instructions for the teacher
The T110D unit is used to adjust the refrigerating cycle automatically. This creates a
few problems during the test given that the assembly tends to make adjustments both
through the laminar valve (controlled by bellows by the end evaporation temperature)
(continuous fine regulation) and the on-off function of the compressor (approximate
regulation), controlled by a thermostat that detects air temperature after the evaporator
(extent of regulation, set-point set by user).
If the set-points are not chosen appropriately, the system makes continuous
adjustments, preventing stationary operating conditions from being obtained. This
means that the equipment has to be put in crisis by setting parameter values that
cannot be met even if the system works at full head (in this way the cycle will operate in
stable conditions at full power).
In order to achieve this, the following adjustments are valid for room temperatures of
approximatley 20C (small adjustments may be required for other values):
fan ON with potentiometer at 75%;
Chapter 4.
T110D User s Manual 37
set-point of compressor thermostat (in air channel downstream of the evaporator)
set at about 12 C;
electrical air preheater (upstream of evaporator) ON 2 with approx. 78 amperes of
absorbed power (adjust using potentiometer).
Using these measurements, the value of the parameters will be as follows, in order of
size:
air temperature upstream of the evaporator 43 C
air temperature downstream of the evaporator 16 C
pressure at start of compression 3 bar
pressure at end of compression 10.4 bar (10.5 atm)
temperature at end of compression = T
1
70.6 75.4 C
temperature at start of compression (evaporator outlet) = T
4
11.8 12.4 C
temperature at end of condensation (condenser outlet) = T
2
28.3 C
temperature at end of lamination (evaporator input) = T
3
5.7 C
p of air astride the diaphragm = 11 20 Pa
It is important to observe that the pressure at the start and end of compression does
not coincide with the corresponding evaporation and condensation pressures of the
cycle owing to the loss of head. These are relatively small for the condenser, but are
much greater for the evaporator. This means that if all the above values were to be
detected and plotted on the R22 equilibrium diagram, they would produce a strongly
distorted cycle (see Figure 4.6).
For teaching purposes it is not appropriate to use this real cycle, but it is clearer and
more instructive to use an ideal cycle and overlook the losses of head in the condenser
and evaporator, also given that the various energie involved (q
2
, q
1
, l
i,comp
, efficiency) do
not change as they pass from one cycle to another (they are differences of enthalpy and
they stay the same if point 3 is set in the real cycle, or it is set as 3 as in the ideal
cycle).
Errore. Non stato specificato un argomento.
It follows that students must solely be given the following measured parameters:
pressure at start of compression coinciding with evaporation pressure (supposed
constant along the entire evaporator);
pressure at end of compression coinciding with condensation (supposed constant
along the entire evaporator);
experimental exercises
38 Didacta Italia
temperature at start of compression (T
4
);
temperatura at end of compression (T
1
).
It is therefore necessary to hypothesise that the end point of condensation provides a
saturated liquid (lower curve).
Using these data students can plot the complete ideal cycle on the equilibrium
diagram (NOT provide values for T
2
and, above all, T
3
because they are not compatible
with the ideal cycle).
c - Performing the test
c1 Main points of the refrigeration cycle
During the course of the experimental exercise, analysis is focused on the
refrigerating cycle used for the cooling set in an air conditioning plant, for laboratory
purposes, of the full air type. Figure 2.8 shows a detail of the refrigerating system
operating on R22.
Chapter 4.
T110D User s Manual 39

Valvola di laminazione
Condenser
Compressore
Evaporatore
This is a continuous flow system that operates in a steady condition. Each of the
transformations take place in a given device.
experimental exercises
40 Didacta Italia
These are:
4-1 Irreversible adiabatic compression Compressor
1-2 Reversible isobar condensation (until
saturated liquid condition)
Condenser
2-3 Isenthalpic leak Laminar valve
3-4 Reversible isobar evaporation (until
superheated steam conditions)
Evaporator
A thermodynamic diagram is required which is used to display the properties of the
refrigerant fluid in conditions of equilibrium: for example, the diagram (h, log p) known
as a Mollier diagram, shown in Figure 4.9.
The following values measured experimentally using laboratory aparatus are also
known:

Evaporation pressure (p
3
=p
4
) 3 bar
Condensation pressure (p
1
=p
2
) 10.5 atm
Compressor aspiration temperature (or
end of evaporation) (T
4
)
11.8 C
Compressor delivery temperature (or
start of condensation) (T
1
)
70.6 C
Air temperature above the evaporator 43 C
Air temperature below the evaporator 16 C
p on calibrated diaphragm 25.6 mm H
2
O
Point 1
Point 1 at the end of compression occurs in conditions of superheated steam. Given
that it has a known temperature T
1
= 70.6 C = 343.6 K and pressure p
1
= p
condensation
=
10.5 atm = 10.4 bar, it is possible to make a full definition of its thermodynamic state
using the Mollier diagram. Pressure, enthalpy and entropy are measured (see Table 4.3).
Chapter 4.
T110D User s Manual 41
Transformation 1-2 and point 2
This consists of an isobar transformation consisting of two parts: one takes the form
of overheating from point 1 to the condensation temperature corresponding to the
pressure of 1, and the other, inside the limit curve, of isotherm condensation. Given that
the final conditions are saturated liquid, point 2 is competely determined and both
enthalpy and entropy can be determined from the Mollier diagram.
The transformation will obviously be a straight horizontal line in the diagram (h, log
p) whereas in Gibbs diagram it will be a straight horizontal line in the isotherm tract
(inside the limit curve) and in the superheated steam part the intermediate points of the
transformation can again be determined using the Mollier diagram.

Trasformation 2-3 and point 3
The 2-3 transformation take the form of a leak, in other words an isenthalpic
transformation (without producing work or thermal exchange); it is irreversible and
takes place to reduce the pressure of refrigerant fluid to the pressure of evaporation.
Point 3, marking the end of expansion, can be determined as the intersection between
the isenthalpic line passing through 2 and the isobar/isotherm passing through point 4
(evaporation isobar-isotherm at 3 bar). The other thermodynamic values for point 3 can
be read on the Mollier diagram.
Given that this is an irreversible transformation, the intermediate stages of the
transformation are not known: strictly speaking, it is only known that final enthalpy is
equal to the initial stage, but it does not necessarily remain constant throughout the
transformation. However, it is usual to consider enthalpy as remaining constant
throughout the course of transformation in order to plot the quality of transformation.
This will result in a vertical segment in the diagram (h, log p), whereas it will create a
decreasing curve in the diagram (T, s).
experimental exercises
42 Didacta Italia

Point 4
Point 4 marking the start of compression occurs in conditions of superheated steam.
Given that its temperature T
4
= 11.8 C = 284.8 K and pressure p
4
= p
evaporation
= 3 bar
are known, it is possible to make a complete definition of its thermodynamic state using
the Mollier diagram. In particular, pressure, enthalpy and entropy are determined (see
Table 4.3).
Transformation 3-4 and point 4
Transformation 3-4 is the transformation involving the evaporation of fluid. It will
lie, partly (up to point 3), inside the limit curve (where it coincides with an isobar-
isotherm) and the last part consists of a tract of isobar inside the zone of superheated
steam. The main points of 4 have already been determined earlier and the plotting of
the transformation 3-4 does not present any difficulty either on the diagram (h, log p) or
the diagram (T, s) because the two ends need only be joined by a straight segment.


Chapter 4.
T110D User s Manual 43
Transformation 4-1
Transformation 4-1 is an irreversible adiabatic compression. Strictly speaking, only
the initial and final stages of balance are known. It therefore cannot be plotted on the
equilibrium diagrams; however, by convention it is indicated using a fictitious
transformation (using a dashed line to recall that it is irreversible).


1 10.4 70.6 450 1.830
2 10.4 25.5 231 1.105
3 3 -14.7 h
3
=h
2
=231 1.123
4 3 11.8 417 1.830
Main
Based on these values, it is possible to trace the cycle on the enclosed equilibrium
diagram (Figure 4.9 shows the general trade of the cycle on the plane (h,log p).

experimental exercises
44 Didacta Italia
In order to plot the trend of the cycle on the diagram (T, s), it is important to measure
the assumed values for temperature and entropy in correspondence with some points
along the curve representing the cycle on the diagram (h, log p) plotted earlier. It is also
necessary to plot the limit curve, using the values of entropy and temperature shown in
Table form. Fig. 4.10 shows the cycle on the plane (T, s) in qualitative terms.
A realistic example of cycle on (T,s), obtained using MS-Excel, is shown in Figure
4-11.

Chapter 4.
T110D User s Manual 45
-
Temperatura =
Entropia
Note for the teacher only
In the same experimental conditions used in this exercise, if the temperatures T
2
and
T
3
had been measured, the following results would have been obtained:
T
2
= 28.3 C
T
3
= 5.7 C
It can be seen that the value of T
2
is very close to the value obtained by supposing
point 2 on the C.L.I., namely approximately 26C. What changes most is the
temperature of point 3. The real point 3 is at 5.7C, which corresponds to an
evaporation pressure of approximately 6 bar. Given that the pressure at the outlet of the
evaporator is 3 bar (corresponding to an evaporation temperature of 14.7C), this
means that the loss of pressure while crossing the evaporator is approximately 3 bar.
The trend of the real cycle is shown in red on the enclosed equilibrium diagram.
experimental exercises
46 Didacta Italia
c2 Calculating the energy exchanged
The energy exchanged is calculated by resorting to the first principle of
thermodynamics in the open-system form, by adopting the following hypotheses:
Steady condition
A single input and output
Negligible changes in kinetic and potential energy
The following formula can be proposed using these hypotheses:
q - l
i
= dh
Heat yielded to the outside environment (q
1
)
Heat is only yielded to the outside in isobar transformation 1-2 in which there is no
exchange of work. This can be expressed as:
q
1
= h
2
- h
1
= 231 - 450 = - 219 kJ/kg
Heat substacted from outside environment (q
2
)
Heat is only absorbed from the outside in isobar transformation 3-4 in which there is
no exchange of work. This can be expressed as:
q
2
= h
4
- h
3
= 417 - 231 = 186 kJ/kg
Inside work absorbed by the system (l
ic
)
Work is only exchanged in transformation 4-1: this is work carried out on the system
and given that transformation 4-1 is adiabatic, this produces
l
ic
= - (h
1
- h
4
) = - (450 - 417) = - 33 kJ/kg
Having calculated the energy exchanged, it is important to check that the first
principle of thermodynamics has been complied with, namely that:
q
i
=

l
or also:
q
1
+ q
2
= l
ic
(quantity taken with sign)
Chapter 4.
T110D User s Manual 47
In fact, given that: - 219 + 186 = - 33 the identity will be checked.
c3 Calculating the efficiency of the refrigerating cycle
The following is obtained on the basis of the above calculations:
= q
2
/ ,l
ic
, = 186/33 = 5.64
c4 Calculating the powers exchanged and the flow rate of R22
The flow rate of the refrigerating fluid carrying out the cycle is not known.
However, the sensitive heat removed from the air as it passes through the evaporator
can be determined If the channel through which air is ducted is supposed to be
adiabatic towards the outside, the following formula can be used to express the first
principle of thermodynamics:

air sensitive
Q Q
, 2
& &
=
from which:

T c V T c m Q
p air p air air sensitive
= =
&
&
&
,

The volumetric displacement of air can be calculated based on the characteristics of
the calibrated diaphragm. The volumetric displacement of air can be determined using
the characteristics of the calibrated diaphragm. If the p between upstream and
downstream is known, using the enclosed tables, air speed can be calculated:
T
aria
= 16 C, p = 14.4 mmH
2
O da tabelle v 15.2 m/s
Given that the diameter of the diaphragm is: = 10 cm the following is obtained:
A = D
2
/4 = 7.85410
-3
m
2

experimental exercises
48 Didacta Italia
= = A v V
air
&
0.119 m
3
/s = 428.4 m
3
/h
and therefore
=
air
m& 0.1191.29273/289 = 0.145 kg/s
( ) = = = 16 43 1004 145 . 0
,
T c m Q
p air air sensitive
&
&
3931 W
and lastly:

&
Q
2
=3931 W
the maximum deplacement of R22 can therefore be calculated as:
&
&
. / / m
Q
q
s h
R
= =

=
22
2
2
3931
186 1000
0 0211 76 kg kg
It is now possible to calculate the mechanical power supplied by the fluid and the
electric power absorbed (assuming the value of 0.8 as the mechanical output of the
compressor and 0.9 as the electrical output of the motor):

&
&
, ,
L l m
i c i c R
= =
22
696 W

&
&
,
L
L
e
i c
el
=

=

967 W
c5 Carnots inverse cycle
The refrigerating efficiency, mechanical power and flow rate of the refrigerant in
Carnots inverse cycle can now be calculated, considering the thermal load to be
removed from the air as constant.
1st Case
On the basis of a cycle with an evaporation and condensation cycle equal to those
calculated experimentally ( p
ev
= 10.4 bar; p
cond
= 3 bar. These values correspond to a
condensation temperature of 25.5 C and an evaporation temperature Tevap. equal to -
14.7 C. The corresponding ideal Carnots cycle plotted on the diagram (h,log p) is
shown in the following figure.
Chapter 4.
T110D User s Manual 49

The following efficiency and energies are exchanged:
= Tevap. / (Tcond. - Tevap.) = 258.3 / (298.5 - 258.3) = 6.4
q1 = h2 - h1 = ( 231 - 412.3 ) = - 181.3 kJ/kg
q2 = h4 - h3 = (385 - 228) = 157 kJ/kg
mR-22 = [ma c
pa
(Tai -Tao)] / q2 = 0,025 kg/s

&
L
ic
=
&
Q
2
/ = 3931/ 6.4 = 614 W
2nd Case
The second case considers:
condensation temperature Tcond equivalent to room temperature, 20 C,
evaporation temperature Tevap. equal to the cold air temperature,16 C.
experimental exercises
50 Didacta Italia

The following efficiency and energies are exchanged:
= Tevap. / (Tcond. - Tevap.) = 289 / (293 - 289) = 72.3
q1 = h2 - h1 = ( 224.1 - 411.4 ) = - 187.3 kJ/kg
q2 = h4 - h3 = (407.5 - 223 ) = 184.5 kJ/kg
mR-22 = [ma c
pa
(Tai -Tao)] / q2 = 0,0213 kg/s

&
L
ic
=
&
Q
2
/ = 3931/ 6.4 = 54.4 W
c6 analysis (only theoretical, not numeric)
It is possible to demonstrate that there is a relationship between minimum power (or
work), power effectively requested and changes in entropy of the universe during each
cycle:

& & &
min
L L T S
tot
= +
0

The change in the entropy of the universe is only caused by an increase in the overall
entropy of the two heat sources (cold namely the air treated and hot namely the
outside environment), given that the system operates cyclically we can suppose:

&
& &
S
Q
T
Q
T
tot
aria amb
= +


2 1

Chapter 4.
T110D User s Manual 51
Air treated by the system changes its temperature during the course of transformation
passing from the value of T
a1
upstream of the evaporator (in our case 43 C) to the value
T
a2
downstream (16 C). In the same way, even in the condenser, the cooling air passes
from room temperature to a higher temperature. For this reason, it can be said
(supposing the isobar of the air cooling/heating process):

&
& & &
ln ln
S
Q
T
Q
T
m c dT
T
c dT
T
c
T
T
c
T
T
tot
aria aria
aria p
aria Ta
T
aria p
aria T a
T
p
a
a
p
a
a
aria
a
aria
a
aria aria
= +

=

+

=
=
|
\

|
.
|
|
+

|
\

|
.
|
|

2 1
1
2
1
2
2
1
2
1
m

It is not possible to proceed with the numeric calculation because we have no data
relating to flow rate and the temperature of air in the condenser.
experimental exercises
52 Didacta Italia




Chapter 5.
T110D User' s Manual 53
5. Exercises with SAD/ T110D Automatic Data
Acquisition System
5.1 Formulas used for air conditioning tests (Test 01)
Enthalpy
The automatic data acquisition system enables the enthalpy values at 3 characteristic
system points to be determined automatically on the basis of the temperatures and the
wet air titre.
The formulas for the determination of enthalpy at the various points are:

W bu bu
T X X h ) 9 . 1 1 ( 2501 + + =
where:
T
w
= t
w
+ 273.16 (K)
t
w
= wet bulb temperature
air titre wet
101325
622 . 0
ws
ws
bu
P
P
X

+ + + + +
=
) ( ln
6
3
5
2
4 3 2
1
T C T C T C T C C
T
C
ws
e P
C
1
= -5800.2206
C
2
= 1.3914993
C
3
= -0.04860239
C
4
= 0.000041764768
C
5
= -0.000000014452093
C
6
= 6.5459673
T = T
w

Wet air titre
The air titre at the 3 system points is determined on the basis of temperature of dry
bulb temperature. The air titre is calculated through the following formula:
Exercises with SAD/ T110D Automatic Data Acquisition System
54 Didacta Italia

d
d
T
T h
X
+

=
9 . 1 2501

where:
h = enthalpy
T
d
= t
d
+ 273.16 (K)
t
d
= dry bulb temperature
Relative humidity
The relative humidity at the 3 system points is determined through the following
formula:

ws
P X
X
Hr

=
622 . 0
101325

where:
X = air titre

+ + + + +
=
) ( ln
6
3
5
2
4 3 2
1
T C T C T C T C C
T
C
ws
e P
T = T
d
= temperature of the dry bulb
Air flow-rate
The flow-rate of the output air is calculated on the basis of the differential pressure
before and after the special calibrated diaphragm.
Flow-rate (Q) may therefore be obtained through the following formula:
Q
C
d p =
1
4
2
4
1
2
1


Where:
Q is the air flow-rate expressed in m
3
/s
C is the discharge coefficient
Chapter 5.
T110D User' s Manual 55
C
D
= + + 0 5959 0 0312
2 1
0 1840
8
0 0029
2 5
10
6
0 75
. .
.
. .
.
(
Re
)
.

Re
D
is Reynolds number relative to diameter D

1
is the expansion factor

1
4
1
1 0 0 35 = + ( .41 . )
p
k

k is the iso-entropic exponent; for air it is 1.4
is the ratio between the diameter of the diaphragm (d) and the pipe diameter (D)
expressed in m.
=
d
D

d = 0.1 m; D = 0.3 m
p is the differential pressure before and after the diaphragm
1 mmH
2
O = 9.797 Pa
is the specific weight of air in kg/m
3

therefore we can say that:
1
p K Q =
Where:
K = 0.007853
Exercises with SAD/ T110D Automatic Data Acquisition System
56 Didacta Italia
5.2 Formulas used in cooling tests (Test 02)
Efficiency of C.O.P. cooler

3 4
1 3
h h
h h

=
where:
h
1
, h
3
and h
4
are the enthalpy values at the relative points in the cycle on the diagram
of Freon R22.
For the air flow-rate which is cooled, use the same formulas as in Test 01.
Experimental procedure for Test 02
adjust the SP of the cooler and the air flow-rate
acquire the temperature and the pressure
from the Freon 22 diagram, determine the enthalpy values at points 1,3,4; enter
then via the keyboard and save the tests.
modify air flow-rate and following the same procedure.
Chapter 5.
T110D User' s Manual 57
5.3 Experimental exercises
Exercise 5.1 - Air conditioning test (Test 01)
Execution of the test
1. Set a Set Point of 18C
2. Set an air flow-rate corresponding to a pressure difference at the diaphragm of 1.5 -
2 mm H
2
O.
3. Wait for the flow-rate to become stable.
4. Acquire the data automatically by means of the Read and Input commands.
5. Gradually increase the flow-rate and repeat steps 3 and 4.
6. After a certain number of acquisition processes, examine the working file and/or the
experimental diagrams; print them out if you wish to.
Test results
The following page shows a table with the results of test 1809199801: Test 01,
followed by the following diagrams:
Sensible heat - air flow-rate
Dry temperature - air flow-rate
Wet temperature - air flow-rate
Relative humidity - air flow-rate
Exercises with SAD/ T110D Automatic Data Acquisition System
58 Didacta Italia

Table 5.1
Chapter 5.
T110D User' s Manual 59

Fig. 5.1 Enthalpy vs air flow rate

Fig. 5.2 Dry temperature trend vs air flow rate
Exercises with SAD/ T110D Automatic Data Acquisition System
60 Didacta Italia

Fig. 5.3 Wet temperature trend vs air flow rate

Fig. 5.4 Relative humidity vs air flow rate
Chapter 5.
T110D User' s Manual 61
Exercise 5.2 - Air conditioning test (Test 01) with pre-heater
Execution of the test
1. Set a Set Point of 18C
2. Turn on the pre-heater and position it on the value at which you wish to perform the
test.
3. Set an air flow-rate corresponding to a pressure difference at the diaphragm of 1.5 -
2 mm H
2
O.
4. Wait for the flow-rate to become stable.
5. Acquire the data automatically by means of the Read and Input commands.
6. Gradually increase the flow-rate and repeat steps 4 and 5.
7. After a certain number of acquisition processes, examine the working file and/or the
experimental diagrams; print them out if you wish to.
Test results
The following page shows a table with the results of test 1809199802: Test 01 with
pre-heater, followed by the following diagrams:
Sensible heat - air flow-rate
Dry temperature - air flow-rate
Wet temperature - air flow-rate
Relative humidity - air flow-rate
Exercises with SAD/ T110D Automatic Data Acquisition System
62 Didacta Italia

Table 5.2
Chapter 5.
T110D User' s Manual 63

Fig. 5.5 Enthalpy vs air flow rate

Fig. 5.6 Dry temperature trend vs air flow rate
Exercises with SAD/ T110D Automatic Data Acquisition System
64 Didacta Italia

Fig. 5.7 Wet temperature trend vs air flow rate

Fig. 5.8 Relative humidity vs air flow rate
Chapter 5.
T110D User' s Manual 65
Exercise 5.3 - Air conditioning test (Test 01) with heater
Execution of the test
1. Set a Set Point of 18C
2. Turn on the heater and position it on the value at which you wish to perform the test.
3. Set an air flow-rate corresponding to a pressure difference at the diaphragm of 1.5 -
2 mm H
2
O.
4. Wait for the flow-rate to become stable.
5. Acquire the data automatically by means of the Read and Input commands.
6. Gradually increase the flow-rate and repeat steps 4 and 5.
7. After a certain number of acquisition processes, examine the working file and/or the
experimental diagrams; print them out if you wish to.
Test results
The following page shows a table with the results of test 1809199803: Test 01 with
heater, followed by the following diagrams:
Sensible heat - air flow-rate
Dry temperature - air flow-rate
Wet temperature - air flow-rate
Relative humidity - air flow-rate
Exercises with SAD/ T110D Automatic Data Acquisition System
66 Didacta Italia

Table 5.3
Chapter 5.
T110D User' s Manual 67

Fig. 5.9 Enthalpy vs air flow rate

Fig. 5.10 Dry temperature trend vs air flow rate
Exercises with SAD/ T110D Automatic Data Acquisition System
68 Didacta Italia

Fig. 5.11 Wet temperature trend vs air flow rate

Fig. 5.12 Relative humidity vs air flow rate
Chapter 5.
T110D User' s Manual 69
Exercise 5.4 - Air conditioning test (Test 01) with cooler
Execution of the test
1. Set a Set Point lower than ambient temperature in the Keyboard Value window,
from the keyboard.
2. Turn on the cooler and adjust the Set Point of the instrument installed in the electric
panel located under the channel to the same value as set in the software.
3. Wait for the coolant temperature to approach the SP.
4. Set an air flow-rate corresponding to a pressure difference at the diaphragm of 1.5 -
2 mm H
2
O.
5. Wait for the flow-rate to become stable.
6. Acquire the data automatically by means of the Read and Input commands.
7. Gradually increase the flow-rate and repeat steps 3, 5 and 6.
8. After a certain number of acquisition processes, examine the working file and/or the
experimental diagrams; print them out if you wish to.
Test results
The following page shows a table with the results of test 1809199804: Test 01 with
coolant set point of 10C, followed by the following diagrams:
Sensible heat - air flow-rate
Dry temperature - air flow-rate
Wet temperature - air flow-rate
Relative humidity - air flow-rate
Exercises with SAD/ T110D Automatic Data Acquisition System
70 Didacta Italia

Table 5.4
Chapter 5.
T110D User' s Manual 71

Fig. 5.13 Enthalpy vs air flow rate

Fig. 5.14 Dry temperature trend vs air flow rate
Exercises with SAD/ T110D Automatic Data Acquisition System
72 Didacta Italia

Fig. 5.15 Wet temperature trend vs air flow rate

Fig. 5.16 Relative humidity vs air flow rate
Chapter 5.
T110D User' s Manual 73
Exercise 5.5 - Air conditioning test (Test 01) with humidifier and water
Execution of the test
1. Set a Set Point of 18C.
2. Start the pump located under the channel by means of the relative button.
3. Adjust the flow of the water coming out from the nozzle located inside the chamber
by working on the valve fitted to the pump.
4. Set an air flow-rate corresponding to a pressure difference at the diaphragm of 1.5 -
2 mm H
2
O.
5. Wait for the flow-rate to become stable.
6. Acquire the data automatically by means of the Read and Input commands.
7. Gradually increase the flow-rate and repeat steps 5 and 6.
8. After a certain number of acquisition processes, examine the working file and/or the
experimental diagrams; print them out if you wish to.
Test results
The following page shows a table with the results of test 1809199805: Test 01 with
pump delivery valve fully open, followed by the following diagrams:
Sensible heat - air flow-rate
Dry temperature - air flow-rate
Wet temperature - air flow-rate
Relative humidity - air flow-rate
Exercises with SAD/ T110D Automatic Data Acquisition System
74 Didacta Italia

Table 5.5
Chapter 5.
T110D User' s Manual 75

Fig. 5.17 Enthalpy vs air flow rate

Fig. 5.18 Dry temperature trend vs air flow rate
Exercises with SAD/ T110D Automatic Data Acquisition System
76 Didacta Italia

Fig. 5.19 Wet temperature trend vs air flow rate

Fig. 5.20 Relative humidity vs air flow rate
Chapter 5.
T110D User' s Manual 77
Exercise 5.6 - Air conditioning test (Test 01) with steam humidifier
Execution of the test
1. Set a Set Point of 18C.
2. Make sure that the boiler located under the channel is full of water.
3. Turn on the boiler by means of the button located on top of it and wait for the steam
to form.
4. Press the steam delivery button.
5. Set an air flow-rate corresponding to a pressure difference at the diaphragm of 1.5 -
2 mm H
2
O.
6. Wait for the flow-rate to become stable.
7. Acquire the data automatically by means of the Read and Input commands.
8. Gradually increase the flow-rate and repeat steps 6 and 7.
9. After a certain number of acquisition processes, examine the working file and/or the
experimental diagrams; print them out if you wish to.
Test results
The following page shows a table with the results of test 1809199806: Test 01,
followed by the following diagrams:
Sensible heat - air flow-rate
Dry temperature - air flow-rate
Wet temperature - air flow-rate
Relative humidity - air flow-rate
Exercises with SAD/ T110D Automatic Data Acquisition System
78 Didacta Italia

Table 5.6
Chapter 5.
T110D User' s Manual 79

Fig. 5.21 Enthalpy vs air flow rate

Fig. 5.22 Dry temperature trend vs air flow rate
Exercises with SAD/ T110D Automatic Data Acquisition System
80 Didacta Italia

Fig. 5.23 Wet temperature trend vs air flow rate

Fig. 5.24 Relative humidity vs air flow rate
Chapter 5.
T110D User' s Manual 81
Exercise 5.7 - Cooling test (Test 02)
Execution of the test
1. Make sure that option Calculate on command inside Option - Input mode of
SAD/T110D (test 02) is active.
2. Set a Set Point lower than ambient temperature in the Keyboard Value window,
from the keyboard.
3. Turn on the cooler and adjust the Set Point of the instrument installed in the electric
panel located under the channel to the same value as set in the software.
4. Wait for the coolant temperature to approach the SP.
5. Set an air flow-rate corresponding to a pressure difference at the diaphragm of 1.5 -
2 mm H
2
O.
6. Wait for the flow-rate to become stable.
7. Acquire the data automatically by means of the Read command.
8. Based on the pressure and temperature data for the 3 points, determine the enthalpy
value from the enthalpy diagram for Freon R22.
9. Enter from the keyboard the enthalpy values measured on the diagram and work on
the Calculate and Input commands.
10. Gradually increase the flow-rate and repeat steps 4, 5, 6, 7, 8 and 9.
11. After a certain number of acquisition processes, examine the working file and/or the
experimental diagrams; print them out if you wish to.
Test results
The following page shows a table with the results of test 2109199802: Test 02 with
coolant set point of 10C, followed by a diagram:
Efficiency - air flow-rate
Exercises with SAD/ T110D Automatic Data Acquisition System
82 Didacta Italia

Table 5.7

Chapter 5.
T110D User' s Manual 83

Fig. 5.25 Efficiency vs flow-rate
Exercises with SAD/ T110D Automatic Data Acquisition System
84 Didacta Italia
Exercise 5.8 Conditioning Cycle in the Wet Air Mollier Diagram (Test 03)
Execution of the test
1. Perform a conditioning test (for instance reproducing the exercise 4.6).
2. Every time it needs to have a conditioning cycle, acquire the data automatically by
means of the Read and Input commands.
3. Examine and in case print the conditioning test in the Mollier diagram.
Test results
The following page shows a plant conditioning cycle in the Air Wet Mollier Diagram

Fig. 5.26 Conditioning cycle in the wet air Mollier diagram