Chapter 2 Psychrometric Chart
Chapter 2 Psychrometric Chart
Chapter 2 Psychrometric Chart
PSYCHROMETRIC CHART
DR HAMID YUSOFF MEC 351
9/3/2014
CHAPTER 2 CONTENTS
2.1 Atmosphere presure and moisture 2.2 What is a Psychrometric Chart? 2.3 Psychrometric Processes: Sensible Cooling and Sensible Heating of Air 2.4 Psychrometric Processes: Heating & Humidification 2.5 Psychrometric Processes: Cooling with dehumidification 2.6 Psychrometric Processes: Cooling with Adiabatic humidification (Water injection) 2.7Psychrometric Processes: Heating with Adiabatic dehumidification (sorbent/desiccants) 2.8 Psychrometric Processes: mixing of two streams of air
9/3/2014
9/3/2014
Taking 0OC as reference temperature, enthalpy and enthalpy change of dry air can be determined from
hdry air C PT 1.005kJ / kg.O C T
kJ kg
The atmospheric air can be treated as a n idealgas mixture whose pressure is the sum of the partial pressure of dry air Pa and that of water vapor Pv. P Pa Pv kPa where p = total pressure of air (Pa, N/m2) pa = partial pressure dry air (Pa, N/m2) pw = partial pressure water vapor (Pa, N/m2 ) Vapor Pressure: The partial pressure of water vapor is usually referred to as the vapor pressure. It is the pressure water vapor would exert if it existed alone at the temperature and volume of atmospheric air.
Absolute or specific humidity: The mass of water vapor present in a unit mass of dry air. [Note: Also called humidity ratio]
mv ma
(kg water vapor / kg dry air)
Saturated Air: There is a limit on the amount of vapor the air can hold at a given temperature. Air that is holding as much moisture as it can at a given temperature is called saturated air. Any moisture introduced into saturated air will condense.
Relative Humidity (): The amount of moisture the air holds relative to the maximum amount of moisture the air can hold at the same temperature.
mv P V RvT Pv v mg PgV RvT Pg
where
Pg Psat @ T
0.622 Pg Pgdr y air to 1 for The relative humidity ranges from P 0 for saturated air.
0.622Pg
Total enthalpy of atmospheric air is the sum of the enthalpies of dry air and water vapor:
H H a H v ma ha mv hv (kJ/kg dry air)
h ha hg
Dry bulb temperature (Tdb): The ordinary temperature of the atmospheric air is refereed to as the dry bulb temperature. Dew point temperature (Tdp): The temperature at which condensation begins when the air is cooled at constant pressure.
Tdp Tsat @ Pv
When the temperature of a cold drink is below the dew-point temperature of the surrounding air, it sweats.
Relative humidity and Sp. Humidity of air can be determined by measuring the adiabatic saturation temperature of air, which is the temperature air attains after flowing over water in a long adiabatic channel until it is saturated
C P T2 T1 2 h f g hg1 h f 2
0.622Pg 2 P2 Pg 2
Wet bulb temperature (Twb): A thermometer whose bulb is covered with a cotton wick saturated with water and to blow air over the wick as shown in figure. The temperature measure in this manner is called wet bulb temperature.
Sling Psychrometer: The wet bulb temperature can also be measured by placing the wet wicked thermometer in a holder attached to a handle and rotating the holder rapidly. A device that works on this principle is called Sling Psychrometer.
Enthalpy F
For a saturated air, the dry bulb, wet bulb and dew point temperature are identical.
Air Conditioning Processes Air-conditioning processes include: Simple heating (raising the temperature), Simple cooling (lowering the temperature) Humidifying (adding moisture), and Dehumidifying (removing moisture).
9/3/2014
20
2.3 Psychrometric Processes: Sensible Cooling Observable features of a sensible cooling process the dry bulb temperature decreases the relative humidity increases the enthalpy decreases the wet bulb temperature decreases the specific volume decreases the humidity ratio, vapor pressure and dew point remains constant
= = =
9/3/2014 21
CHAPTER 2 PSYCHROMETRIC CHART 2.3 Psychrometric Processes: Sensible heating In HVAC systems, air is typically heated by passing it over a heating coil or use of electrical strip heaters. A schematic of a cooling coil is shown below.
Observable features of a sensible heating process The dry bulb temperature increases the relative humidity decreases the enthalpy increases the wet bulb temperature increases the specific volume increases the humidity ratio, vapor pressure and dew point remains constant
= = =
9/3/2014 22
CHAPTER 2 PSYCHROMETRIC CHART 2.3 Psychrometric Processes: Governing Equation for Sensible Heating and Cooling The heat transfer is given by;
= = ( ) = 1.005 + 1.888 ( ) = 1.005 + 1.88 = 1.005 + (2501 + 1.88) is the ratio of volume flow rate to the specific volume
3 3
= () = 1 , = 2 , = ( ) = is the enthalpy of stream 1, (kJ/kg) = is the enthalpy of stream 2, (kJ/kg) = specific heat of moist air =
9/3/2014 23
9/3/2014
24
25
9/3/2014
26
9/3/2014
28
9/3/2014
29
Example
Solved Problem 1 - Assume that the outside air temperature is 32C with a relative humidity = 60%. Use the psychrometric chart to determine the specific humidity [18 gmmoisture/kg-air], the enthalpy h [78 kJ/kg-air], the wet-bulb temperature Twb [25.5C], the dew-point temperature Tdp [23C], and the specific volume of the dry air v [0.89m3/kg]. Indicate all the values determined on the chart.
9/3/2014 30
Solved Problem 2: Assume that the outside air temperature is 8C. If the air in a room is at 25C with a relative humidity = 40%, use the psychrometric chart to determine if the windows of that room which are in contact with the outside will become foggy.
9/3/2014
The air in contact with the windows will become colder until the dew point is reached. Notice that under the conditions of 25C and 40% relative humidity the dew point temperature is slightly higher than 10C, At that point the water vapor condenses as the temperature approaches 8C along the saturation line, and the windows will become foggy.
31
Solved Problem 3: One of the major applications of the Psychrometric Chart is in air conditioning, and we find that most humans feel comfortable when the temperature is between 22C and 27C, and the relative humidity between 40% and 60%. This defines the "comfort zone" which is portrayed on the Psychrometric Chart as shown below. Thus with the aid of the chart we either heat or cool, add moisture or dehumidify as required in order to bring the air into the comfort zone.
9/3/2014 32
Solved Problem 4: Outside air at 35C and 60% relative humidity is to be conditioned by cooling and heating so as to bring the air to within the "comfort zone". Using the Psychrometric Chart neatly plot the required air conditioning process and estimate (a) the amount of moisture removed [11.5gH20/kg-dry-air], (b) the heat removed [(1)-(2), qcool = 48kJ/kg-dry-air], and (c) the amount of heat added [(2)(3), qheat = 10kJ/kg-dry-air].
9/3/2014 33
Solved Problem 5: Hot dry air at 40C and 10% relative humidity passes through an evaporative cooler. Water is added as the air passes through a series of wicks and the mixture exits at 27C. Using the psychrometric chart determine (a) the outlet relative humidity [45%], (b) the amount of water added [5.4gH20/kg-dry-air], and (c) the lowest temperature that could be realized [18.5C].
9/3/2014
34
9/3/2014
35
9/3/2014
36
9/3/2014
37
9/3/2014
38
9/3/2014
39
9/3/2014
40
9/3/2014
41