Koeltorenboekje Engels Zonder Logo
Koeltorenboekje Engels Zonder Logo
Koeltorenboekje Engels Zonder Logo
Section page
1. Cooling tower operation 2. Cooling tower types 3. Cooling tower notions 4. Heat exchange 5. Dynamic cooling tower functioning 6. Water consumption 7. Cooling tower regulation 8. Measuring the cooling tower capacity 9. Cooling tower components 10. Sound of the cooling tower
2 4 5 6 9 14 16 18 23 27
Version 1
Cooling towers
Thermometer
Air flow
Put differently, for the wet bulb temperature of the wet cover the passing unsaturated air emits just enough sensible heat to support the latent heat flow (evaporation) of the water. The wet bulb temperature is also called the adiabatic saturation temperature.
MOLLIER-CHART
Air B Tnb2 A Tw2 Tnb1 Water Tw1
the air absorbs more heat. For this reason the condition of the air moves to the right and follows the curve A-B. In the point B, with a matching wet bulb temperature Tnb2, is a curve directed to the point Tw1. The air flow absorbs more and more water and will eventually be saturated. The force behind the total enthalpy increase of the air is the enthalpy difference between the air in the border layer air-water and the passing air. In short, in the cooling tower the cooling water is cooled from temperature Tw1 to Tw2. The drawn-in air with condition Tnb1 is heated and humidified to a condition Tnb2, where the air is almost saturated. A rule of thumb is that the wet bulb temperature of the air leaving the cooling tower almost equals the average of the cooling waters in and outlet temperatures. This depends on the cooling towers efficiency.
Warm water
The most well known examples of this category of cooling towers are the counter flow and the cross flow cooling towers. In a counter flow cooling tower the water falls down in a vertical manner and the air rises in opposite direction. In a cross flow cooling tower the water falls in a vertical manner, crossed by the air flow in horizontal direction.
4. Heat exchange
4.1 Cooling fills
The most important part of the heat and mass exchange between water and air takes place in the cooling fill of the cooling tower. As a contact body the cooling fill exists in many constructions. We have waved synthetic foils (film fills), which exist of manageable blocks and the well-known wooden splash bars. When the water is slightly polluted, nowadays synthetic splash fills are used as well. In order to achieve a maximum heat exchange in the cooling fill, the following points must be considered: The cooling water should cover a maxi mally large surface with respect to the air stream. Therefore, a thin water film and a large exchange surface (m2 surface per m3 contents) of the cooling fill are of great importance. The speed of the heat exchange is enlarged by a more turbulent air stream (among others a high air speed). The rougher the surface of the cooling fill, the more turbulent is the air/water stream. A longer stay or contact period of the cooling water in the cooling fill enhances the heat exchange between water and air. Usually, the stay is stretched by enlarging the depth/ height of the cooling fill (in the direction of the air). A good water distribution above the cooling fill due to a correctly designed water distribution system in the cooling tower. An equal distribution of air speed in the cooling fill due to an aerodynamic cooling tower.
Film fill
In the modern synthetic film fill (figure 4b) the water is distributed over a large surface in a thin, levelled film of water. For this type of cooling fill it is necessary to have a good water distribution system. Film fills are available for counter flow as well as for cross flow cooling towers. Due to the crossed channel structure of the film cooling fill, which usually has a mesh width of 12 to 19 mm. and a building height of 600 to 1500 mm., the air stream is very
turbulent. Therefore, the film fill is a very efficient cooling fill and it is used frequently. The term efficient can be explained in the following way: A large exchange surface (ca. 250 m2/ m3) in a compact block shape with a relatively low airside resistance. In other words: a lot of cooling capacities per m3 cooling fill against low energy costs (of the fan).
Bar fill
The dated use of wooden bars in a cooling tower is based on the principle of splashing (figure 5). The bars are mounted in alternating manner having vertical and horizontal distances of e.g. 150 mm. between them. Cooling fill heights up to 8 m. and depths up to 3 m. are no exceptions. The cooling water disperses on every bar so that small water drops emerge. The result of this is a more effective heat exchange surface. The splash effect also lengthens the stay of the cooling water. In general we can say that these splash bars are a moderately efficient cooling fill (a small exchange surface m2/ m3). Synthetic splash bars (figure 4c) are a good alternative for the wooden bars in older cooling towers. Using these, the cooling capacity and the efficiency of the cooling tower is usually enlarged. Splash bars are used more frequently in cross flow cooling towers than in counter flow cooling towers or than in a combination of these.
figure 5. Splashbars
Splash fill
The splash fill (figure 4a) is a good alternative of the film fill mentioned above. The mesh width is for example 40 mm. with a vertical splash distance of about 40 mm. The use of the splash fill is based on a combination of the splash effect of the splash bars
and a thin water film around the splash surface. The exchange surface is ca. 150 m2/ m3. Because of the good redistribution of the cooling water of this cooling fill, there is less demand on the water distribution system in the cooling tower. The splash fill is also used for extra redistribution of the water and as a mechanical protective layer on the film fills with a high nozzle pressure. In counter flow cooling towers the overall heights vary from 900 to 1500 mm. These splash fills are not very frequently used in cross flow cooling towers with bigger cooling fill heights. It should be clear that the splash fill is less efficient than the film fill, but more efficient than the splash bars. The most important advantage of the splash fill over the film fill is that it is less sensitive for pollution that is due to a lesser quality of the circulating cooling water in the cooling tower.
Water
Water distribution reservoir Fill
Water
Fill
Air Air
Counter flow
Cross flow
Tw1
Counter flow
The heat exchange in a counter flow cooling tower is schematically depicted in figure 7. The cooling fill is divided in 5 imaginary layers: Air-sided: In the bottom cooling fill layer the inlet wet bulb temperature Tnb1 increases when ascending. The outlet Tnb of the first layer is the inlet Tnb of the second cooling fill layer etc., until the final Tnb2 is reached. Water-sided: In the fifth cooling fill layer the inlet water temperature Tw1 decreases when descending. The outlet wet Tw of the fifth layer is the inlet Tw of the fourth cooling fill layer etc., until the final Tw2 is reached.
Tnb2
COUNTER FLOW
figure 7. Heat transfer principle
CROSS FLOW
Cross flow
For a cross flow cooling tower (figure 7) the heat exchange can be depicted in a similar way. Here we divide the cooling fill in 18 imaginary blocks: Air-sided: In the blocks 1-3 the inlet wet bulb temperature Tnb 1 increases. This is also true for the blocks 4-6, 7-9 etc. The final Tnb per horizontal layer (3 blocks) differs. The values of the outlet Tnb of the blocks 3-18 is averaged to Tnb2,
the outlet wet bulb temperature of the entire cooling fill. Water-sided: When the cooling water with an inlet water temperature Tw1 passed the blocks 1-16, 2-17 and 3-18 in vertical direction, an average can be taken of the water outlet temperature of the blocks 16, 17 and 18, the water outlet temperature Tw2 of the entire cooling fill.
Amplification
It may be clear that the air- and watersided heat balance should be in equilibrium in every cooling fill layer or block. So the increase in enthalpy of the air must be equal to the decrease of the heat content of the cooling water. With the help of modern calculation techniques the physical evaporation process in a counter flow or cross flow cooling tower is thus calculated. With the principle of the cross flow we may notice that the first block cools the water the most effective, because in here the warmest water comes into contact with the coldest air. Reasoning this way we can say that the water flowing from block 16 is colder than the water flowing from block 17 and 18 respectively. This could be a reason to moisten the cross flow fill asymmetrically on top (more cooling water on the air inlet side of the cooling fill). The blocks 3-18 do not cool the water to the same degree as the blocks 1-16 and 2-17 (in vertical direction). This tells us that it is not always useful to select a deeper cooling fill (air sided). Sometimes, an enlargement of for example 50% of the depth of the cooling fill only raises the cooling capacity with 15%. In vertical direction, on the other hand, it is more useful to choose a higher cooling fill, on the condition that this is not a problem for the whole construction or the internal water economy. As a rule the counter flow cooling fill is always more effective than the cross flow cooling fill, because in counter flow less m3 cooling fill is required (for example 30%) than in cross flow, assuming that the design data and cooling fill characteristics as type and mesh width are the same. Depending on the approach the turning point of the choice between counter flow and cross flow is more closely, as we will explain in a later article. We then will compare the advantages and disadvantages of these two cooling tower types in more depth.
So far, we gave a first theoretical onset in explaining the functioning of the (evaporative) cooling tower. In this chapter, the cooling fill is given extra attention, because this actually is the heart of the cooling tower. In the following chapters we will explain the functioning of several other cooling tower components in more detail. In the following article we will try to clarify several misunderstandings concerning the operation and business operation.
T=7
T=4
18,0
figure 8. Performance curve
20,0
22,0
Tnb ( C)
APPROACH (C)
18 16
14
12
10
2 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
air speed and the wet bulb temperature are assumed to be constant. Obviously, this is also the case with an unvarying choice of the cooling tower and the cooling fill.
10
Example:
approach [C]: [%]: [m2]: [%]: 8 (100) 5 (100) 4 (50) 10 (200)
Temp. ( C)
28.5
Tw1
From the above example we can conclude that when the approach is divided into two, the required cooling tower surface must be twice as big. This shows us that every increase or decrease in degrees Celsius of the approach is of direct influence on the required cooling tower surface. One needs to be aware of this when selecting a cooling tower. When a higher selection water outlet temperature of the cooling tower is not acceptable, maybe a slight decrease of the wet bulb temperature in the selection is (see question 6). An economical guide value with the selection of a cooling tower is an approach of 4 to 5 C. With this, we yet again point to the fact that an approach increase of 4 C with 1 C to 5 C results in a decrease of the cooling tower surface of 20%. 3. What happens to the approach (Tw2-Tnb) when the wet bulb temperature changes? The cooling range (delta T) is taken as a constant value. When the wet bulb temperature increases, the cooling water temperature and the outlet temperature will increase as well. The entire cooling range Tw1-Tw2 then changes to a higher temperature. A decrease of the wet bulb temperature, on the other hand, results in a decrease of the entire cooling range. Herewith it is incorrect to suppose that when the wet bulb temperature increases with 1 C, the cooling range also increases with 1 C. As a rule of thumb we can assume that when the wet bulb temperature increases with 1 C the cooling range does so with 0,6 C. The cooling water outlet temperature then is 0,6 C higher and the approach is 0,4 C lower.
R = 13
R=8
Time
Example:
Tw1 Cooling range Tw2 Approach Tnb efficiency [C]: [C]: [C]: [C]: [C]: [-]: 30,8 7,0 23,8 5,8 18,0 0,55 32,0 7,0 25,0 5,0 20,0 0,58 33,2 7,0 26,2 4,2 22,0 0,63
In spring, autumn and winter the outside temperature, and therefore the wet bulb temperature, usually is lower than in summer. This means that the cooling tower can reach the required outlet temperature most of the year, because then the approach is bigger. Put differently, the cooling towers dimensions are actually too large for the most of the year, unless the user wants to reach a colder water temperature than the temperature for which the tower is selected. In the above example it is apparent that the cooling tower works less efficient with a lower wet bulb temperature and somewhat more efficient with a higher wet bulb temperature. With this we assume standard water/ air debit proportions in the cooling tower.
11
4. What is the influence of a variation in the cooling water debit (with equal cooling load) on the cooling water temperatures? As a starting point we take the example given in figure 10. In the starting situation a constant water load (R) of 13 m3 /m2/hr on the cooling tower, a constant wet bulb temperature and a water inlet temperature of 22,5 C with a corresponding cooling load value of (13*4=) 52 are assumed. When the water load in the cooling tower is suddenly decreased to 8 m3/ m2/hr, the delta T will increase from 4 to 6,5 C. The cooling load remains constant with a value of (8* 6,5=) 52. It should be noted that the water outlet temperature Tw2 is decreased with 0,5 C. In this example it is thus possible to obtain somewhat colder water from the cooling tower by lessening the water debit over the cooling tower. It must be remarked that the corresponding increase of the water inlet temperature in the cooling process can be unacceptable. Furthermore, the water distribution system is in many cases not designed for great variation in the cooling water flow. 5. Is a cooling tower able to cool a larger cooling load than it was originally designed for? The answer to this question is yes. This is illustrated by figure 8. In our example a constant wet bulb temperature of 20 C is chosen. With a delta T of 7 C, the water outlet temperature Tw2 of the cooling tower is 25,0 C. When the cooling load of the cooling process increases to a delta T of 10 C, the water outlet temperature of the cooling tower increases to about 26,7 C. An increase of the cooling load of 43% results in an increase of the Tw2 of the cooling tower of 1,7 C. In this example the approach increases from 5 C with 1,7 C to 6,7 C; this is an increase of 34%. In practice we sometimes hear a remark of the kind: the cooling tower only cools for half its capacity. The cooling tower then is designed for a capacity of 300 kW, but cools 150 kW. It will now be clear that this is not the responsibility of the cooling tower. It is possible for the cooling tower to cool 300 kW as long as this is indicated by the cooling process or the factorys adjustment. The only
correct way of measuring the functioning of the cooling tower is by means of the cold water temperature (Tw2), or the range (Tw2Tnb), as already explained in question 2. 6. What is the preferable wet bulb temperature for the selection of a cooling tower? As already mentioned the choice of the wet bulb temperature (Tnb) is important for determining the size of the of the cooling tower surface. For the choice of the cooling tower we start from a selection Tnb that is adjusted to the climatological circumstances of the environment in which the cooling tower is placed. With this we also take the possible recirculation of blown out air of the cooling tower into consideration, because this can increase the Tnb with the air inlet of the cooling tower. For a correct choice of the Tnb it is also important to consider the number of working hours and the part of day in which the cooling tower is used. During winter, the Tnb is as good as similar to the dry bulb temperature (Tdb), but during summer a large difference between these two may exist. With higher surrounding temperatures the relative humidity of air is often lower. For example, an air condition of Tdb = 27 C with a corresponding R.V. = 60% accords to Tnb = 21 C. The graph that is depicted in figure 11 shows the upper and lower limits of the wet bulb temperature in the Netherlands, measured in De Bilt, in the period 1961- 1980 on the basis of 24 hours a day. With the help of this graph we can trace approximately how many hours per year the cooling tower will not reach the desired (selected) cooling water temperature. From this it is clear that an average Tnb of 21 C is only exceeded in 0,18% of the time looking at one year on a yearly basis. In the table below we give a short survey of the most common Tnb with the corresponding upper limits.
12
For cooling towers that are situated on the coast of the Netherlands, a wet bulb temperature of 19 C can be taken. This has to do with the slightly lower outside temperature
Tnb C Exceeding in the Netherlands % Exceeding in the Netherlands hours/year
3 11 25 47 84
on the coast. For climate installations in the inland of the Netherlands a Tnb of 20-21 C is usually taken.
13
6. Water consumption
The water consumption of an evaporative cooling tower exists of three components, i.e. evaporative losses, splash and drain water losses.
14
As a rough indication we use figure 12. In this figure we can see the average required amount of supplied water as a percentage of the circulating water debit for several delta Ts.
(%)
(i=2) 6 5 4 3 2 1 0 0 5 10 15 20
Range ( C)
15
warm
cold
Example
As an example we take a cooling tower that exists of three separate cells, which have a cooling water debit of 33 m3/ h each. The three cooling tower cells are placed above a shared cold water basin (see figure 13). The total (steady) cooling load on the three cell cooling tower is 3* 384 = 1152 kW and the desirable cold water temperature is 25 C. For several indicated wet bulb temperatures the cooling tower is able to cool the cooling water from 35 C to a Tw2 that is indicated in table 1. The first of the three cooling cells can be switched off when the other two can give a
cooling capacity of 1152/ 2 = 576 kW each. This is the case with a wet bulb temperature of about 10 C and lower. In the next section it will become clear that it is not very useful to choose a multiple cell cooling tower with a one speed fan / motor for the sake of energy saving. For this, a two speed regulation is definitely preferred. Then, the energy use will be indicated, using the (limited) example below. The amount of mentioned Tnb hours is chosen on a yearly basis (24 hours a day) (see table 2). If the used capacity of the three fans on high speed is set on15 kW in total, the energy consumption will be: 1.591* 15 = 23.865 kWh.
16
speed able to cool the cooling water from 35 C to a Tw2 indicated in the table for the indicated several wet bulb temperatures. The three cell cooling tower is, with the 2/ 3 revolution speed, able to give a desired cold water temperature of 25 C with a wet bulb temperature that is lower or equal to 16 C. For this temperature we could simultaneously switch the three fans back to a lower revolution speed. The theoretical energy consumption of a 2/ 3 revolution electric motor can be calculated with the help of the capacity formula: P = (n1/ n2)3; this gives P = (2/ 3)3 = 8/ 27 = 30% Energy consumption (high revolution speed) = 53* 15 = 795 kWh Energy consumption (low revolution speed) = 1896* 0,30* 15 = 8.532 kWh Total 9.327 kWh The energy saving of the two speed regulation in relation to the on/ off regulation is in this (limited) example: (23.865 9.327 =) 14.538 kWh, this is 61%.
35 25 20 384
35 22 15 499
35 19,5 10 595
35 17 5 691
( C) ( C) ( C) (kW)
Tnb C
Tnb hours
High speed %
off hours
0 10 46 108 165 183 195 707 (31%)
off cells
0 0 0 0 0 1 1
20 18 16 14 12 10 8 total
100 88 80 74 69 64 61
Tabel 2.
35 26,6 20
35 26,1 19
35 25,7 18
35 25,3 17
35 24,8 16
35 24,4 15
( C) ( C) ( C)
Tnb
Tnb
%
High speed
hours 25 28 0 0 0 0 0 53 (2%) cells 3 1 0 0 0 0 0 % 0 67 98 91 85 80 75
Low speed
hours 0 57 227 378 453 407 374 1.896 (83%) cells 0 2 3 3 3 3 3 % 0 0 2 9 15 20 25
Switched off
hours 0 0 5 37 80 102 125 349 (15%) cells 0 0 0 0 0 0 0
C 20 18 16 14 12 10 8 total
100 33 0 0 0 0 0
Tabel 4.
17
T nb T db
u u
OC OC ABS
T w1
Qw pump
T nb T db
OC OC
T w2
T nb T db T nb T db
o o u
ambient wet bulb ambient dry bulb exhaust wet bulb exhaust dry bulb pump head absorbed power fan airvolume watervolume
u pump ABS QL Qw
pipe to the cooling tower or in the water distribution system. The water outlet temperature (Tw2) of the cooled water from the cooling tower that goes to the cooling process. This temperature is preferably measured in the drain of the cooling tower because in there the water temperature is average. The influence of the supplied water needs to be fixed because sometimes the water supply cannot be switched off during measuring.
Temperatures
The water inlet temperature (Tw1) of the water supply that needs to be cooled. This temperature is measured in the supply
18
The wet bulb temperature of the surrounding air of the cooling tower. This temperature is measured before the air inlets of the cooling towers with the help of an Assman psychrometer. These temperature measurements are preferably registered by a computer so that possible fluctuations in the system can be tracked down. For this, PT100-recorders are often used because of their stable functioning.
RD 910
1/3 H
cooling tower
Water flow
In order to fix the water flow (Qw) several methods can be used. Preferable methods are standard measurements such as orifice plate covering (which usually is not very suitable for cooling towers) or measurement by Pitots tube. The measuring points, then, need to be included in the design of the installation. Points to consider are a straight length of pipes before and after the measuring point and the location of the measuring points. The advantage of the measurement by Pitots tube is that the user of the cooling tower can assemble two simple ball- or push cranes per pipe (a free culvert is required), in which the Pitots tube can be shoved (see figure 15). Other possible water flow measurements are electro-magnetic or inductive flow methods or turbine meters, which obviously need to be fixed as well.
mP = position of the pitot-tube connections
2/3 H = 2/3 L = min. 10x the duct dimension detail pitot-tube connection
female thread 3/4" B.S.P. minimum lenght ball or butterfly (valve min. 16 mm. access) welded socket 3/4" B.S.P.
duct diameter
1500 mm.
19
used as a coarse indication to check whether the measurement is reliable. Deviations up to 20% can be prevented because the air sided capacity is hard to be determined more accurately.
Air speed
The speeds of air near the cooling tower that occur during the measurement need to be measured as well. The speed of air is checked because an air speed that is too high influences the air flow throughout the cooling tower.
20
high throughout the measurement. - Further deviating conditions concerning the functioning of the cooling tower should be discussed with the user and before the measurement agreements should be made. - Obviously, the cooling tower should be checked for its mechanical functioning. This includes the functioning of the nozzles, pollution or damage to the fill and the condition of the fan and the drive.
At the moment the European cooling tower manufacturers, in co-operation within Eurovent, are drawing up a completely renewed measuring protocol that can be realised in practice without difficulty.
8.5 Evaluation of the functioning of the cooling tower in relation to the design
In order to be able to evaluate the measuring results in connection with the design data, the measured values need to be compared to the cooling towers design data. There are several methods that can be used to evaluate the measurement. Nowadays, the following evaluations are commonly used: Firstly, the comparison between the measured KAV/L (this is the cooling towers code) and the design KAV/L. This method, however, is not a practical evaluation for the users conceptualisation of the cooling tower. Another frequently used evaluation is the comparison between the design water outlet temperature and the water outlet temperature that is calculated from the measuring data and that the cooling tower reaches in practice. In fact, this method reflects a practical deviation of the present functioning of the cooling tower with respect to the design. Obviously, calculations by computer enable fast calculation of the measuring values of the design and can easily reflect deviations in the water outlet. However, curves that show the influence of an entity that is to be measured with respect to the Tw2 are still being used. Examples are the two curves displayed in figure 16. By means of these curves one is able, with the help of certain calculation basics, to identify the present water outlet temperature (Tw2-ist). The design data reveal what the water outlet temperature (Tw2-soll) should be. We can also determine a total inaccuracy of the measuring tolerances of the measuring instruments and the uncertainties of fluctuations in the system (*Tw inaccuracy).
21
The formula then is: Tw2-soll + *Tw inaccuracy Tw2-ist In other words, the measured and recalculated water outlet temperature should be lower than the design water outlet temperature heightened with the total measuring inaccuracy. When this condition is met, we could say that at the moment of measuring the cooling tower complies with its design, within the active measuring tolerances.
25
Tw2
design
19 12 Tnb 22
+1,0
change of Tw2 0
-1,0 90% 100% % Q w (m3/h) Q w T w2 water flow (m3 /h) cold water temperature ( C) 110%
22
6. fan section
motor
geared motor
motor
6.The fan section. For an induced draft cooling tower (see figure 18) this consists of an induced draft fan, driven by an electromotor. For bigger cooling towers the revolution speed of the electro motor needs to be reduced by means of a reduction component. This because of the maximum tip speeds that, for e.g. synthetic fans lie between 50 and 70 m/ s., depending on the construction and the choice of materials. This reduction component can exist of a geared motor that
drives the fan directly or of a right angle gearbox with an intermediate shaft and a foot mounted motor, where this electromotor usually is outside of the fan stack (see figure 18).
23
Obviously, a good technical adjustment of these components and the optimal functioning of the cooling tower deserve extra attention. The following points are taken into consideration: - The relative proportion of the fans diameter compared to the drift eliminators surface and the cooling fills surface. We choose a large enough fan, so that no extreme air speeds occur in the fan cone while there is a correct air speed in the cooling fill and the drift eliminator (the air speeds in the fan cone vary from 1-15 m/ sec). - The distance between the fan and the drift eliminator should be large enough to prevent local differences in air speed in the drift eliminator. - The inlet shape of the fan cone and the fans tip space in the cone are important to the ultimate fan profits and therefore for the energy consumption of the cooling tower as well. - The nozzles should be distributed in such way that the water streams through the cooling fill instead of along the sides of the casing, for water streaming along the sides will not be in sufficient contact with the drawn-in air. This portion of water will then reduce the cooling capacity.
24
drops X
plastic profiles
air flow
air flow
water drain
carried back from the bottom of the drift eliminator to the basin. The air speed of this type of drift eliminator may be between 2 and 8 m/ sec, dependent on the design and construction.
25
not get wet. In order to wet every fill, the nozzles must overlap one another. In general, the water distribution with splash nozzles is not as good as with low pressure nozzles. However, for the bigger cooling towers with somewhat coarser fill types the splash nozzles suffice.
re-distribution fill
fill
26
Lw = Current sound capacity w0 = Reference sound capacity (10-12 Watt) This value is independent of the distance and cannot be measured directly with the measuring equipment. The sound capacity is frequently used to characterise the force of a specific sound source. We can calculate the sound capacity and the sound pressure (on a specific distance) with the help of for example the formula mentioned below. This formula only accounts for a point source in an acoustically free field without influence from the soil or reflections: Lw = Lp+10log(4**R2) R = distance to the source, the radius (m).
What is sound?
Sound is a vibration of air that is caused by movement of an object. This movement causes differences in pressure that move through the air in the form of vibrations. Human beings sense these vibrations by means of sound. Humans can sense sound pressures that range from 20Pa (audibility threshold) to 200 Pa (pain threshold). The force of the sound pressure is defined in decibels in the following manner: Lp = 20*log P P (dB)
P = occurring sound pressure Po = sound pressure of the audibility threshold (20uPa) The value of the sound pressure always needs to be given together with the distance to the source. In our formula the sound pres-
27
comparison- a number of middle frequencies are used, for which the total spectrum is divided into ranges that are shown in the table below. Additionally, in order to reflect the sound with a simple number, a filter spectrum that is in accordance with the human audibility can be used. For this spectrum, it is researched which pitches are the most annoying for human beings. The commonly used dB(A) filter is also shown in the table below:
Medium frequency 63 125 250 500 1000 2000 4000 8000 Band limits 45 - 90 90 - 180 180 - 355 355 - 710 710 - 1400 1400 - 2800 2800 - 5600 5600 - 11200 dB(A) filter -26 -16 -9 -3 0 1 1 -1
the sound pressures of the sources in a measuring point can be added logarithmically using the following formula: Lptotal = 10 log[10
(Lp source 1 )
+10
(Lp
source 2
+10
(Lp
source 3
...]
10
10
10
For several equal sources for the sound pressure increase in the example counts the following: -For 2 equal sources = 10 log(2) = +3 dB -For 3 equal sources = 10 log(3) = +5 dB -For 4 equal sources = 10 log(4) = +6 dB When the distance from measuring point to source changes, counts theoretically, preserving air- and ground dampening, a resonance of other influences: LPnew = LPold -20log (
distance new distance old
From the A-spectrum can be concluded that high pitches especially are experienced as annoying. In order to determine the value from the dB(A) spectrum, the middle frequency values are added logarithmically according to the formula below: In practice, the sound meter is provided with a dB(A) filter, so that the dB(A) sound pressure level can be read directly. dB(A) = 10log[10 +10 +10
(value - correction value) 10 (value - correction value) 10 (value - correction value) 10
For rotating machines it counts that when the revolutions are changed, it can be stated (theoretically) that LPnew can become LPold following the following formula: LPnew = LPold -50log (
original speed new speed
An example for electrically driven machines is: - 2/3 rotations = +50log(0.67)= -9 dB - 1/2 rotations = +50log(0.5) = -15 dB We must note here that for fans more influences are of importance, which we will examine in due course of this booklet.
+ + +
+........................)
28
Lwa = the sound capacity of the fan dB(A) Lwas = the specific sound capacity of the used fan dB(A) W = the fan capacity kW m U = rotation speed sec D = the fan diameter m From the above we can conclude, concerning an optimal fan-sound, the following: The rotation speed of the fan is the most influential factor. This rotation speed is equal to the rotation. A fan having the same amount of air and boosting with a lower rotation speed will therefore produce less sound. The diameter also influences the sound production of the fan. A fan with a large diameter with the same design conditions will bring about less sound. The used capacity of the fan is also an influence on the sound. Because the capacity is the same as the (air debit) boosting divided by the profit, starting from a given required debit and boosting, only the profit is relevant. Therefore, a fan with a higher profit will produce less sound. When the above technical design aspects are thoroughly examined but too much sound is produced anyway, we can check the outlet dampers on the cooling tower (see figure 21). The disadvantage of an outlet damper is that it causes additional air- sided resistance, which increases the fan capacity. The production of the sound source (the fan) then increases according to the formula above. It may now be clear that from a technical and economical viewpoint maximising the fan drive by a relatively more expensive fan and one that is as large as possible (with a maximised blade shape and more profit for lower rotation speeds) is preferred. Good reduced-sound fans are available these days, so that now the drive of the fan plays a part. For a cooling tower drive we pay attention to the electro-motor for electric sound and cooling fan sound. When, on top of that, a rotation-reduction by a gearbox or by a reductor is being used, we also pay attention to sound of the gear wheel. When this happens, a quickly rotating intermediate
discharge silencer
distance
figure 21. Cooling tower with discharge silencer
stage can cause problems. When the sound of the drive is significantly less than the fan sound in practice, a minimal difference of 10 dB is stated and the drive will, as a rule, not cause problems. It is advisable to compare this for the entire spectrum, so that possible peak sounds in specific frequencies are not annoying.
29
Every manufacturer of cooling towers will give a personally measured sound level that is determined by means of equal cooling tower types. As an example of a sound pressure level that can happen in practice, the following sound pressures are given for a CMC-type cooling tower of about 2.5 *2.5 meter:
Medium frequency Air intake Sound pressure level at 10 m.
25- 30 canting
plates
72 72 70 75 78 77 78 76 83
50 50 48 53 56 55 56 54 61
watersurface
In order to reduce the sound of the falling water, we can place side-wing dampers around the cooling tower or we can place a sound wall at some distance of the cooling tower (see figure 22). It is also possible to make sound facilities in the basin yourself. Slanting fences or especially constructed, floating mats that catch the drops and break them, causing less splash sound, could be placed in the basin. These dampers can reduce the sound about 10 to 11 dB(A).
lution of 501 rpm this fan suffices. For this fan counts a sound pressure release on 10 meters of:
Hz dB 63 125 53 56 250 58 500 56 1000 53 2000 49 4000 42 8000 35 dB(A) 58
For the falling water of this cooling tower counts, as already mentioned in the former section, a sound pressure release on 10 meters of:
Hz dB 63 125 50 50 250 48 500 53 1000 56 2000 55 4000 56 8000 54 dB(A) 62
Example of a sound-situation
As an example we choose a standard cooling tower of 2.5 * 2.5, with a height of 3.5 meters and with a standard fan. This fan should move 19 m3 /sec air with a boosting of 140 Pa. The used capacity of the fan is then 4.8 kW with a rotation of 720 rpm. For this fan counts on 10 meters a sound pressure release of:
Hz dB 63 125 61 63 250 64 500 62 1000 59 2000 54 4000 48 8000 42 dB(A) 64
When we consider the total sound pressure level of this cooling tower we will find as a sum of the water sound and the fan sound for the standard situation on 10 meters a sound pressure release of:
Hz dB 63 125 61 63 250 64 500 62 1000 61 2000 57 4000 56 8000 54 dB(A) 66
In the situation with a reduced-sound fan counts on 10 meters a sound pressure release of:
Hz dB 63 125 55 57 250 58 500 58 1000 58 2000 56 4000 56 8000 54 dB(A) 63,5
If we want to replace this type of fan by a reduced-sound type that can do with less revolutions, we can realise less sound release. For a used capacity of 4.9 Kw and a revo-
30
Considering the above, we see that especially in the reduced-sound situation the water sound plays a great part. In this situation we could with the help of for example floating dampers (sound attenuators) reduce the sound of falling water to a sound release from 10 meters of:
Hz dB 63 125 50 50 250 48 500 48 1000 44 2000 45 4000 45 8000 39 dB(A) 52
For the total sound of the combination reduced-sound fan with dampened water sound, counts on 10 meters:
Hz dB 63 125 55 57 250 58 500 57 1000 53 2000 50 4000 47 8000 40 dB(A) 59
Conclusion
We find that by the use of a sound-reduced fan and by dampening of the splash water sound a sound reduction from 66 dB(A) to 59 dB(A) of the standard fan and the sound of the water is possible at a distance of 10 meters. Obviously, this situation is just an example. Every situation should be considered separately.
31
Cooling towers 1.
32