Experiment Manual - Psychrometric Test Rig
Experiment Manual - Psychrometric Test Rig
Experiment Manual - Psychrometric Test Rig
The heating of air, without any change is its specific humidity is known as sensible heating.
Let air at temperature td1 passes over a heating coil of temperature td3. It may be noted that
the temperature of air leaving the heating coil (td2) will be less that td3. The process of
sensible heating on psychometric chart is shown by horizontal line 1-2, extending left to
right. The point 3 represents the surface temperature of the heating coil.
The heat absorbed by the air during sensible heating may be obtained from the
psychometric chart by the enthalpy difference (h2 - h1). It may be noted that the specific
humidity during the sensible heating remains constant (W1-W2). The dry bulb temperature
increases from td1 to td2 and relative humidity reduces from φ1 to φ2 and relative humidity
reduces from φ1 to φ2. The amount of heat added during sensible heating may also be
obtained from the relation.
Heat added: q = h2-h1
The cooling of air without any change in its specific humidity is known sensible cooling.
Let air at temperature td1 passes over a cooling coil of temperature td3 as shown.
1. It may be noted that the temperature of air leaving the cooling coil (td2)
will be more than td3. The process of sensible cooling is shown by horizontal line 1-
2 extending from right to left. The point 3 represents the surface temperature of the
cooling coil. The heat rejected by air during sensible cooling may be obtained from
the psychometric chart by the enthalpy difference (h1- h2). It may be noted that the
specific humidity during the sensible cooling remains constant. The dry bulb temperature
reduces from td1 to td2 and relative humidity increases from φ1 to φ2. The amount of heat
rejected during sensible cooling may also be obtained from the relation.
Heat rejected q = h1-h2
The term (Cpa+ W Cps) is called humid specific heat Cpm and its value is taken as
1.022 kJ / kg K.
Let one kg of air at temperature td1 is passed over the coil having its temperature (i.
e. coil surface temperature) td3. A little consideration will show that when air passes over a
coil, some of it (say x kg) just by-passes unaffected while the remaining (1-x) kg comes
in direct contact with the coil. This by-pass process of air is measured in terms of a by-
pass factor. The amount of air that by-passes or the by-pass factor depends upon the
following factors:
The no. of fins provided is a unit length i.e., pitch of cooling coil fins.
The no. of row in a coil in the direction of flow; and
Velocity of flow of air.
It may be noted that the by-pass factor of a cooling coil decreases with decrease infin
spacing and increase in number of rows.
Balancing the enthalpies; we get:x
Cpm td1+ (1-x) Cpm td3
= 1 x Cpm td2
x (td3 - td1) = td3 - td2
x = (td3 - td2) / (td3-td1)
Where x is called the by-pass factor of the coil and is generally written as BPF.Therefore,
by-pass factor for heating coil,
BPF = (td3 - td2) / (td3-td1) Similarly,
The addition of moisture to the air, without any change in its dry bulb temperature is
known as humidification. Similarly, removal of moisture from the air, without change in its
dry bulb temperature is known as dehumidification. The heat added during humidification
process and heat removed during dehumidification process is shown on the psychometric
chart.
It may be noted that in humidification, the relative humidity increasefrom φ1
to φ2 and specific humidity also increases from w1 to w2. Similarly, in dehumidification,
the relative humidity decreases φ1 to φ2 and specific humidityalso decreases from w1 to
w2. It may be noted that in humidification, change in enthalpy is shown by intercept (h2-h1)
on the psychometric chart. Since the dry bulb temperature of air during the humidification
remains constant, therefore its sensible heat also remains constant. It is thus obvious, that
the change in enthalpy per kg of dry air due to the increased moisture content equal to (w2-
w1) kg per kg of dry air is considered to cause a latent heat transfer (LH).
Mathematically,
Where hfg is the latent heat of vaporization at dry bulb temperature (td1)
When the air is passed through an insulated chamber having sprays of water (known as air
washer) maintained at a temperature (t1) higher than the dew point temperature of entering
air (tdp1), but lower than its dry bulb temperature (td1) of entering air (or equal the wet
bulb temperature of the entering air (tw1) then air issaid to be cooled and humidified.
Since no heat is supplied or rejected from the spray water as the same water is re-
circulated again and again, therefore, in this case, a condition of adiabatic saturation will be
reached.
The temperature of spray water will reach the thermodynamic wet bulb temperature
of the air entering the spray water. This process is shown by line 1-3 on the
psychometric chart and follows the path along the constant wet bulb temperature line or
constant enthalpy line. In an ideal case when the humidification is perfect (or the
humidifying efficiency of the spray chamber is 100%). In actual practice, perfect
humidification is never achieved. Therefore, the final condition of air at outlet in
represented by point 2 on the line 1-3.
Let water at a temperature t1 is injected into the flowing steam of dry air (a). The final
condition of air depends upon the amount of water evaporation. When the water is
injected at a temperature equal to the wet bulb temperature of the entering air (tw1), then the
process follows the path of constant wet bulb temperature line.
Let,
Mw = Mass of water supplied,
ma = Mass of dry air,
W1 = Specific humidity of entering air, W2
= Specific humidity of leaving air, and
Hw = Enthalpy of water injected into the air.
= W1+ mw / ma
h2 = h1+ mw / ma x hfw
= h1+ (W2 - W1) hfw.
Since (W2-W1) hfw is very small as compared to h1 and h2, therefore it may be neglected.
Thus the water injection process is a constant enthalpy process, irrespective of the
temperature of water injected (i.e. whether the temperature t1< tw or t1 > tw ).
This process is generally used in winter air conditioning to warm and humidify the air. It is
the reverse process of cooling & humidity. When air is passed through a humidifier having
spray water temperature higher than the dry bulb temperature of the entering air, the
unsaturated air will reach the condition of saturation and thus the air becomes hot. The
heat of vaporization of water is absorbed from the spray water itself and hence it gets
cooled. In this way, the air becomes heated andhumidified. The process of heating and
humidification is shown by line 1-2 on the psychometric chart. The air enters at condition 1
and leaves at condition 2. In this process, the dry bulb temperature as well as specific
humidity of air increases. The final relative humidity of the air can be lower or higher than
that of the entering air.
Let,
mw1 and mw2 = Mass of spray water entering and leaving the humidifier in kg, hfw1 and
The temperatures ts1 and ts2 denote the temperatures of entering and leaving spray water
respectively. The temperature t3 is the mean temperature of the spray water which the
entering air may be assumed to approach.
Actually, the heating and humidification process follows the path as shown by dotted
curve, but for the calculation of psychometric properties, only the end points are important.
Thus, the heating and humidification process shown by a line 1-2 on the psychometric chart
may be assumed to have followed the path 1- A and A – 2. We see that the total heat added
to the air during heating and humidification is,
Total heat added to the air during heating humidification:q
The stream is normally injected into the air in order to increase its specific humidity. This
process is used for the air conditioning of textile industries where high humidity is
maintained. The dry bulb temperature of air changes very little during the process.
Let
ms = Mass of steam supplied, ma
= Mass of dry air entering,
W1 = Specific humidity of air entering,W2
= Specific humidity of air leaving, h1 =
Enthalpy of air entering,
h2 = Enthalpy of air leaving, and
hs = Enthalpy of steam injected into the air.
m1 h1 + m2 h2 = m3 h3
= (m1 + m2) h3 = m1 h3 + m2 h3
or m1 h1 – m1 h3 = m2 h3 – m2 h2m1 (h1 –
m1 / m2 = h3 – h2 / h1 – h3
Similarly, substituting the value of m3 from equation (i) in equation (iii), we have m1 / m2 = W3
- W2 / W1 - W3
m1 / m2 = h3 – h2 / h1 – h3 = W3-W2 / W1-W3
The adiabatic mixing process is represented on the psychometric chart as shown in fig. The final
condition of the mixture (point 3) lies on the straight line 1-2. Thepoint 3 divides the line1-2
in the inverse ratio of the mixing masses. By calculating the value of W3 from equation (vi), the
point 3 is plotted on the line 1-2.
It may be noted that when warm high humidity air is mixed with cold air, the resulting mixture
will be a fog and the final condition (point 3) on the psychometric chart will lie to the left or
above the saturation curve which represents the fogregion. The temperature of the fog is that
of the extended wet bulb line passing through point 3.
The fog may also result when steam or a very fine water spray is in injected into air in a
greater quantity that required saturate the air. Even lesser quantity of steam,if not mixed properly,
may result fog.
The fog can be cleared by heating the fog, mixing the fog with warmer unsaturated air or
mechanically separating the water droplets from the air.
______________________________________________________________________________________
Corporate Office: A - 192, Ashiana Colony, Moradabad, UP– 244001
Ph.: +91-591-3554004, Mob.: +91-9599583625
E-mail: [email protected]