Lightning Protection System-Layout

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

10 MM DIA COPPER BONDED STEEL ROUND CONDUCTOR

TERRACE FLOOR PLAN 8MM DIA ALUMINIUM ROUND CONDUCTOR

CROSS CONNECTOR

EXPANSION PIECE WITH CONNECTOR

TEST JOINT WITH ENCLOSURE

CONDUCTOR HOLDER

LIGHTNING COUNTER

PARAPET CONDUCTOR HOLDER

3MTR VAT WITH WALL CLAMP

2 MTR VAT WITH WALL CLAMP

EXOTHERMIC WELDING

EXPANSION PIECE WITH CONNECTOR NOTE:-

AIR TERMINATION :

1) Level IV Protection based on the risk


assessment.
2) Vertical air terminal is considered at the top
of the building covering all corners & edges
based on angle of protection method.
3) Fixing support for the conductor considered
at every 1 mtr.
4) 8mm Round Solid Aluminium alloy
considered as conductor.
TERRACE HOLDER 5) Expansion joints as well as accessories such
as cross connectors, straight connectors
included confirming IS/IEC 62305.

DOWN CONDUCTOR:

6) 1No of down conductor shown as sample.


Totally 26 nos of down conductors are
considered peripheral of building.
7) Conductor holder for fixing Aluminium
conductor vertically at every 1 mtr.
8) Test joint with Polycarbonate Enclosure
required for every down conductor.
9) 1No of Lightning counter is used.

CROSS CONNECTOR
EARTHING:

9) 10mm copper bonded steel round conductor


is used for ring earthing.
cross connector (ccss)
10) Ring earthing with exothermic welding is
considered.
3MTR VAT WITH WALL CLAMP

8 mm aluminium round
conductor (src-8al)

DOWN CONDUCTOR
lightning counter

Test joint with enclosure

Polycarbonate enclosure

10 mm copper coated steel


round conductor
Ground level
soil level

CROSS CONNECTOR 2 MTR VERTICAL AIR


TERMINAL (VAT-2)
TERRACE HOLDER

CONNECTOR FOR
10 MM SS CONDUCTOR EXPANSION PIECE WALL CLAMP

EXPANSION PIECE DRAWN

CHECKED
CONDUCTOR HOLDER FOR 8-10MM TEST JOINT 1.5M ABOVE GROUND TERRACE HOLDER AT EVERY
CONDUCTOR AT EVERY DOWN 1M DISTANCE FOR FLAT SURFACE DATE
LEVEL AT EVERY DOWN
CONDUCTOR CONDUCTOR DIM