Schedule of Loads Panelboard Ante Tata
Schedule of Loads Panelboard Ante Tata
Schedule of Loads Panelboard Ante Tata
TOTAL K SPECIFIC
CIRCUIT RATED CONDUIT RESISTIVITY
MAGNETIC POWER AMPS PHASE GND WIRE VOLTAGE %VOLTAG
NO. L.O C.O OTHERS S1 S2 S3 VOLTAGE AT AF POLE KAIC LINE(MM²) TYPE TYPE (MMØ) AREA(CM) STRANDED LENGTH(FT.) REMARKS
STARTER (WATTS) (MM²) DROP E DROP
PVC/EMT COPPER OHM-
CM/FT
1 12 480 230 2.09 1 30 50 2 10 2-2.00MM² THHN 2-2.00MM² THHN 20 4,110 11 295 3.30 1.43 SAFE
2 7 1260 230 5.48 1 30 50 2 10 2-3.50MM² THHN 2-3.50MM² THHN 20 6,530 11 165 3.05 1.32 SAFE
3 ACU-1HP 944 230 4.10 1 30 50 2 10 2-5.50MM² THHN 2-5.50MM² THHN 20 10,400 11 98 0.85 0.37 SAFE
4 SPARE
5 SPARE
6 SPARE
MAIN TOTAL 2,684 230 11.67 1 MAIN BREAKER SIZE MAIN VOLTAGE DROP CALCULATIONS
K SPECIFIC RESISTIVTY %
VOLTAGE END
CALCULATION MAIN CONDUCTOR SIZE AT AF POLE LENGTH AREA(CM) STRANDED COPPER OHM- VOLTAGE REMARKS
DROP VOLTAGE
(FT) CM/FT DROP
IW(MAIN SERVICE ENTRANCE CONDUCTOR) = TOTAL CURRENT +25% (LARGEST MOTOR FLA)
=11.67+25%(10)=14.17A USE 2-8.00MM² THHN WIRE +3.50 THHN GROUNDING
40 50 2 100 16,500 11 1.56 228.44 0.68 SAFE
CONDUCTOR IN 25MMØ WITH 6 BRANCES PANELBOARD
I(OCPD) = IW+LARGEST MOTOR(FLA) = 14.17+10=14.17A