Product HIMHART IM 1.us
Product HIMHART IM 1.us
Product HIMHART IM 1.us
November 2005
224-778-00C
Smart HART ® Loop
Interface and Monitor
HIM
Smart HART® Loop
HIM
Table of Contents
Provides Process and Diagnostic Alarms • A “Caution” provides information on steps to take
Relay alarm trips (optional) can be individually user-set to avoid procedures and practices that could risk
either to trip when unwanted high/low process condi- damage to the HIM or other equipment.
tions occur, or provide a diagnostic health warning to
• A “WARNING ” provides information on steps to
alert of loop or instrument fault conditions. take to avoid procedures and practices that could
pose safety risks to personnel.
Figure 1. The HIM Accepts a Digital HART Signal and Outputs Both Analog Signals and Alarm Relays
Control System
HART Communicator can (DCS or PLC)
be connected anywhere
along the 4-20mA loop
(HART Secondary Master)
Smart HART
Multivariable
Mass Flow
Transmitter
Flow
Specifications
Performance Input Accuracy: Reflects Performance +TX Power Supply: 24.0Vdc Indicators Format: Top row is five
the accuracy of the HART (Continued) ±10%@24mA (Continued) alphanumeric characters,
field device ALARM OUTPUTS plus sign and decimal point;
Input Impedance: Transmit Digital Response Time: bottom row is five
Mode: 150 ohms; Defined by HART protocol as alphanumeric characters
Receive Mode: Less than 500msec maximum in Normal Decimal Points: User-
5kohms HART Mode; 333msec selectable for 0, 1, 2 or 3
Input Over-Range maximum in HART Burst places after the decimal point
Protection: ±5Vdc Mode or automatically adjusting with
Alarm Response Time: a four decimal point maximum
ANALOG OUTPUTS Digital Response Time + Range: -99999 to 99999
Output Accuracy: ±0.015% 150msec (Defined as time Minimum Display Span:
of maximum output span from the field instrument’s 1.00
(20mA). Includes the reporting a fault until the HIM Display Update Rate:
combined effects of linearity, alarm is tripped) 100msec
hysteresis, repeatability and Alarm Trip Delay: LED Type: Dual color
adjustment resolution. Programmable from 0-120sec red/green indicate:
Output Response Time: INPUT LED: Whether (green)
<120ms, 10-90% MODBUS OUTPUTS or not (red) the HART input is
Isolation: 500Vrms channel- Type: Standard MODBUS connected and functioning
to-channel isolation; RTU protocol interface over properly
1000Vrms between case, RS485 (parameters as READY LED: Whether
input, outputs and power specified in U.S. Standard (green) or not (red) the HIM is
terminals, and will withstand EIA-RS485) initialized and operating
1500Vac dielectric strength Address Range: properly
test for one minute with no Configurable from 1 to 247. TRIP 1 and 2 LED: Shows the
breakdown Unit will assume a MODBUS status of alarm off (green) or
Ripple: Less than 10mV address of 01 by default alarm on (red)
peak-to-peak when Baud Rate: Interface
measured across a supports the following: 300, Ambient Operating & Storage
250 ohm resistor 600, 1200, 4800, 9600, 19.2k. Conditions Range:
Output Limiting: 130% of MODBUS interface will -40°C to +85°C
span maximum; 125% of support even, odd and no (-40°F to +185°F)
span typical parities. Unit will assume a Display Range:
Output Protection: baud rate of 9600 and no -25°C to +85°C
Transient protection on parity by default (-13°F to +185°F)
output Character Format: One start Relay Range:
Load Capability: bit, 8 data bits and one stop -25°C to +70°C
0-20mA, 1100 ohms bit (-13°F to +158°F)
maximum Data Format: User- Relative Humidity:
Load Effect: ±0.01% of span selectable Standard LSW 0-95%, non-condensing
from 0 to maximum load (Least Significant Word) or Ambient Temperature
resistance Swapped MSW (Most Effect: ±0.0065% of
Line Voltage Effect: Significant Word). Unit will span/°C maximum
±0.005% of output span for a assume Standard LSW by RFI/EMI Immunity
1% change in line voltage default (Standard):
Input Fail Modes: PC Power Consumption: 20V/m@20-1000MHz, 1kHz
programmable to fail high, fail 2-3.5W, nominal; 4.5W AM, when tested according to
low, hold last, hold last then @24Vdc maximum for units IEC1000-4-3-1995
fail high, or hold last then fail using transmitter excitation to RFI/EMI Immunity (with
low (configurable hold time, 0- supply loop power a 2-wire -RF Option): 30V/m@
60 seconds) instrument 20-1000MHz, 1kHz AM, when
Output Limits on Input tested according to IEC1000-
Failure: 0-20mA: Fail Low to Indicators LCD Type: Two-line LCD; 4-3-1995
0mA or Fail High to 23.6mA; Top Row, 10mm (0.4 in) high Noise Rejection: Common
4-20mA: Fail Low to 3.6mA black digits on a reflective Mode: 100dB@50/60Hz
or Fail High to 23.6mA; background; Bottom Row,
X-20mA (0<X<4): Fail Low to 6mm (0.225 in) high digits Weight 567 grams (16 ounces)
90% of XmA or Fail High to on a reflective background;
23.6mA two-digit HART address
indicator
Specifications and information subject to change without notice.
138mm
65mm (5.45 in)
133mm
(2.56 in) (5.25 in)
ADDR
60.278 100mm
0 DEG C (3.94 in)
COM
HIM HART INTERFACE
MODULE
+TX +IN –IN No Label +I Source –I Source –I Sink +I Source –I Source –I Sink
(AO2) or (AO2) (AO1) or (AO1)
HART Input, 2 Analog Outputs (2AO) +I Sink +I Sink
(AO2) (AO1)
+TX +IN –IN +I –I Source –I Sink +I Source –I Source –I Sink +I Source –I Source –I Sink
Source or (AO3) (AO2) or (AO2) (AO1) or (AO1)
HART Input, 3 Analog Outputs (3AO) (AO3) +I Sink +I Sink +I Sink
(AO3) (AO2) (AO1)
A B S A B S
HART Input, 2 MODBUS Outputs (MB) +TX +IN –IN No Label MODBUS MODBUS MODBUS MODBUS MODBUS MODBUS
2 2 2 1 1 1
KEY: NOTES:
+IN/–IN = Current input to HIM from HART device +TX = Transmitter Excitation Current 1. The standard Single Alarm unit (1PRG) utilizes a DPDT relay.
+I/–I Source = Analog Source Output +I/–I Sink = Analog Sink Output 2. Terminal blocks can accommodate 14-22 AWG solid wiring
A/B = MODBUS Output NO/NO# = Normally Open (torque to 4 inch-pounds, maximum).
NC/NC# = Normally Closed CM/CM# = Common
DC/DCC = 24VDC Connection (AO#) = Analog Output
Mounting
Installing the HIM The HIM is designed to snap easily onto 32mm, G-type
There are two methods for connecting the HIM for (EN50035) or 35mm Top Hat (EN50022) DIN rails.
configuration. The recommended method requires you
to install the instrument into the loop before it is Electrical Connections
configured. The secondary method allows you to bench After mounting, you are ready to connect the HIM to
check the HIM by attaching it to test equipment that the loop. Each unit comes equipped with a transmitter
will simulate the input and monitor the output. excitation terminal which allows it to supply power to
the monitored HART instrument, if necessary. Figures
Installing the HIM into the Loop 2 and 3 show the connection diagrams for an HIM with
Installation consists of physically mounting the unit, or without using the transmitter excitation current.
grounding the instrument, and completing the electrical
connections. To install the HIM into the loop for CE Conformity
configuration, use the equipment in Table 2 to hookup Installation of any Moore Industries products that carry
the HIM into the loop as shown in Figure 3 (without the CE certification (Commission Electrotechnique)
using the HIM to power a transmitter) or Figure 4 (using must adhere to the guidelines in Installing the HIM in
the TX terminal to power a transmitter). If you need a order to meet the requirements set forth in applicable
complete terminal description, refer to Table 1.
Figure 3. Installing a HIM Into the Loop Without Using the Transmitter Excitation (+TX) Terminal
HART Communicator
can be connected
anywhere on the loop
➤ ➤
➤
7 ➤
4 8
5 9
1
0
.
2
3
6
—
➤
24Vdc ➤
Power
+ –
Sensor +
Input
4-20mA R
–
+IN –IN
HART Multivariable
Field Instrument INPUT READY TRIP 1 TRIP 2 DCS
(Temperature
Pressure, Level
and Flow)
Analog Output tied to
ADDR
COM
Event Recorder
DCC
GND
NO
NC
DC
COM
NC (normally closed)
EMC (Electromagnetic Compatibility) directives • All input signals to, and output signals
(EN55011, EN 50082-1, EN50082-2, etc.). Consult the from, Moore Industries’ products should be
factory for the most current information on products wired using a shielded, twisted pair
that have been CE certified. technique. Shields are to be connected to an
earth or safety ground at the unit itself.
Recommended Ground Wiring Practices
Moore Industries recommends the following ground • The maximum length of unshielded input
wiring practices: and output signal wiring should be 2 inches.
Figure 4. Installing a HIM Into the Loop Using the Transmitter Excitation (+TX) Terminal
HART Communicator
can be connected
anywhere on the loop
➤ ➤
➤
7 ➤
4 8
5 9
1
2 6
0
3
.
R must be > 250 and <1100 Ohms
➤
—
➤
–
Sensor
Input
4-20mA
+IN
R
+
+TX –IN
HART Multivariable
Field Instrument
(Temperature, INPUT READY TRIP 1 TRIP 2 DCS
Pressure, Level
and Flow)
COM
Event Recorder
DCC
GND
NO
NC
DC
COM
NC (normally closed)
Bench Checking the HIM Figure 6. Bench Checking the HIM Without Using the
Transmitter Excitation (+TX) Terminal to Power a Transmitter
If you would like to configure the HIM before
attaching it to the loop, you need to hook it up For a HART Transmitter, the
with the equipment listed in Table 1. Refer to resistor must be >250 and <1100 ohms.
For a HART Receiver, such as a
Figures 5 and 6 for instructions on how to bench 24Vdc valve positioner, no resistor is necessary.
Power
check the HIM either with or without taking + –
– 0
Sensor HART
Input Field Device +
R COM
or Multimeter
+IN
Simulator +
+TX –IN –
+ –
Equipment Hook-Up
GND
DCC
NO
NC
DC
for HART field device using INPUT READY TRIP 1 TRIP 2
COM
Transmitter Excitation
Multimeter 24Vdc
ADDR
Power
0
Checks for
COM
continuity
Optional
GND
DCC
NO
NC
DC
COM
Multimeter 24Vdc
Power
Checks for
continuity
Optional
PC Configuration Software
Figure 7. HIM PC Configuration Software Screen
3
2
The HIM PC Configuration Software can be used to HIM Device Status–Displays how the HIM is function-
program all of the HIM’s parameters. Once the default ing, giving a brief summary of any errors or displaying
configuration has been saved, it is safe to program OK if it is operating normally.
other parameters. The PC Software is made up of
these sections: HIM Displayed Data–this display mirrors what the at-
tached HIM is displaying.
1. HIM Status and Information Section–The left
side of the screen includes seven boxes that display Progress–This bar stays in motion any time the HIM
the different settings of the attached HIM. is monitoring, uploading or downloading.
seconds. In this example, we will use seven seconds. To convert HEX to Decimal code, perform the
The HIM then sees its slave device speak and waits following steps:
seven seconds for it to speak again. As long as the
HIM sees a new message from its slave device its Access the Calculator feature in Microsoft
outputs are updated based upon the measured vari- Windows® by opening the Start menu. Next,
ables. If the slave device does not speak within the select Programs then Accessories and finally
seven second period, the HIM declares a “No HART” Calculator.
situation and sends its outputs to the failed communi-
Ensure that the Calculator is in Scientific mode.
cations values.
To do this, select the View dropdown menu
To use this feature, proceed with the following steps: and choose Scientific.
1. Select the Listen (Specified Slave) button. Click the Hex radio button and enter the HEX
code value.
2. Enter your desired value into the Timeout Period(s)
text box. Next, click the Dec button and the value will be
converted into the Decimal value.
Factory default is 5 seconds. The maximum Timeout
Period is 30 seconds. Enter the converted value into the proper param
eter.
3. Set the exact slave address of the instrument you
wish to monitor. Click the Set Slave Address button. The Device ID Number is the serial number of
This brings up the HART Slave Device Long Format the exact device to which the HIM will listen.
Address Settings screen (Figure 8). Enter the required
4. Once complete, press OK.
information into the appropriate text boxes.
Download the information to your instrument once you
Figure 8. HART Slave Device Long Format Address Settings are finished.
Screen
Auto Clear Status Bit
Most HART instruments indicate when a device's
configuration has been changed. This indication
(status bit) can be reset by sending HART command
38–reset configuration changed. Checking the Auto
Clear Status Bit box causes the HIM to issue this
command whenever the HART instrument it is
monitoring has its configuration changed. However,
The Manufacturer’s ID and Device Type ID for the the HIM can also be set to alarm on this bit (see
instrument that the HIM will listen to are available from Programming the Alarm Parameters). If the HIM is
the HART Foundation website at www.hartcomm.org both set to alarm and to auto clear, then it will do
and/or the instrument manufacturer. both–going into alarm mode and resetting that
indication.
Values obtained from the HART website are in HEX
code. The HIM does not use HEX code; you must Quick Read/Set
convert this value to Decimal code. The Quick Read button causes the PC Configuration
Software to read the communications information from
the attached HIM; the Quick Set button causes the
software to configure the HIM’s communications
settings to match those of the PC Software.
Precision
HART Device Range & Limits The Precision buttons allow you to change the number
This portion of the screen displays the range and the of decimal places displayed by the HIM.
sensor limits of the monitored HART transmitter.
Quick Set
The Quick Set button programs the HIM with the
information on the Display page.
Display Parameters
The Display tab configures the HIM’s LCD display. To Display Format
program the Display parameters, change the settings in The HIM reads the dynamic process variable supported
the Display Source box, then press Quick Set. See by HART sensors. Generally, the HIM’s LCD displayed
the following descriptions of the various sections of the values range from -99999 to 99999. Occasionally,
screen. these process variable values may extend past this
range. To improve the displayed readings, values
Figure 9. Display Tab below -XXXXX and above XXXXX are translated into
exponential form. Below is an example of the appear-
ance of the display when certain values are sensed.
Value Display
12345 12345
1234500 1.23E06
-500000 -5.00E05
HART Additional Status Alarm Bits Read & Quick Set Buttons
HART Additional Status also called “More Status” and The Read button causes the PC Configuration Software
to read the alarm information from the attached HIM;
“Command 48” is where device manufacturers install
The Quick Set button causes the software to configure
the custom diagnostics for the specific device. For
the HIM's alarm settings to match those currently
your particular application, you may choose all of these entered in the PC Software.
diagnostics to cause the HIM relay to trip or just one
diagnostic bit to trip the HIM relay (or any combination
in between). The manufacturer of the HART device will
be the source for the specific diagnostic information.
Analog Outputs Parameters For example, you have a vortex flow meter with an
The HIM comes with either two (–2AO) or three (–3AO) imbedded RTD that measures the process
analog outputs. The Analog Outputs tab allows you to temperature, and that temperature is assigned to the
specify which HART variable is to be monitored as the HART Secondary Variable. The full range of the RTD
source of the analog output, the input range and output sensor is from –400°F to +1760°F, but your flow
range, and how the output will react when the variable stream will always be between 0° and 400°F. To scale
input is out of range. To program the Analog Outputs the analog output, for Output 1, set the Source as SV.
parameters, change the settings in the Output1/2/3 Set the Input Range to 0° and 400°F, and the Output
boxes, then press Quick Set. See the descriptions Range to 4mA to 20mA. Click Quick Set to download
below of the various sections of the screen. the new configuration file to the HIM.
Fail Mode
The Fail Mode setting determines how the HIM will
respond when its monitored input fails. If Fail Mode is
set to High and the measured input goes out of range,
or any detected error occurs in the HART transmitter,
the analog output will output a 23.6mA signal. If Fail
Mode is set to Low and the measured input goes out of
range, or any detected error occurs in the HART
transmitter, the analog output will output a signal that
is 90% of the lower range value below 4mA; it will
output 0mA if the lower range is set to 0mA.
User Trimming
To trim the device, attach a multimeter to the analog
output, then click the Fix Output at Low Point button.
Read the value on the multimeter, enter it into the
Measured Output Loop Current portion of the Trimming
box, and press Trim. Repeat this sequence until the
analog output matches the minimum point (4mA for a
4-20mA output) when you click the Fix Output at Low
Point button.
Note:
When entering data in the linearization table, make
sure that you enter a number into every open cell.
Upload Table
Moves a custom curve file from the connected HIM to
the PC Software for editing or storage.
Download Table
Configures the HIM by downloading the custom curve
table from the PC Software to the HIM.
Mode
Check the Enabled box to begin programming the Save Table
custom curve. Saves a displayed custom curve table to memory on
your computer’s hard drive.
Source Variable
The Source Variable defines the variable that the Load Table
custom curve will calculate. Notice that if you select a Loads a previously saved custom curve table.
scaled variable, you may need to click on the Scaling
tab and verify the settings for your scaled variable. Clear Table
Clears the displayed custom curve table.
Quick Set
The Quick Set button causes the software to configure When you have finished changing all your settings,
the HIM’s custom curve settings to match those download the information to the HIM using the
currently entered in the PC Software. Download Table button. If you have selected a scaled
variable, you should also click on the Scaling tab and
set the scaling parameters.
Figure 16. The HIM’s Scaling feature works to get the most out of your existing process instruments
Control
level
range
(50% to 100%
of total level) Full
Controller maintaining
Primary
Loop Display control from 50-100% of full scale
Variable
(reads 0-100% 4-20mA (60-120 inH 2 0/2.15-4.3 PSI).
range
of control Signal 4-20mA from HART Monitor
(in PSI)
level) should represent 60-120
inH 2 0.
4-20mA
Signal
Digital
Pressure HART HART Monitor
Transmitter Signal (120 PSI)
Customer Support
Moore Industries is recognized as the industry leader
in delivering top quality to its customers in products
and services. We perform a battery of stringent quality
assurance checks on every unit we ship. If any Moore
Industries product fails to perform up to rated specifi-
cations, call us for help. Our highly skilled staff of
trained technicians and engineers pride themselves on
their ability to provide timely, accurate and practical
answers to your process instrumentation questions.
Parity
The HART monitor supports even, odd and no Parity.
The data format is one start bit, 8 data bits and one
stop bit.
MODBUS Registers
The HART Monitor outputs a MODBUS signal to the
attached controller. To access the MODBUS registers
for variable, input/output or error information, refer to
Table A-1 (MODBUS Register Definitons table) and/or
Table A-2 (System Status Registers table).
Figure A-2. Installing a HIM with MODBUS output into the loop using the Transmitter Excitation (+TX) terminal
HART Communicator
can be connected
anywhere on the loop
Sensor –
Input
4-20mA +IN R
+ A
+TX –IN B
S
HART
Field Instrument
(Temperature, INPUT READY TRIP 1 TRIP 2 DCS
Pressure,
Level,
Flow Multivariable)
ADDR
60.278
0 DEG C
RS485 / RS232
Converter
COM TO serial
(COM) port
MODBUS output MODBUS Host
of PC
(with MODBUS option)
DCC
GND
NO
NC
DC
COM
NC (normally closed)
4 PV scaled
5 SV scaled
6 TV scaled
7 FV scaled
8 Linearized variable
18 Device ID MSW
19 Device ID LSW
Bit 0 HW fail
* Indicates any input, output, power, option and housing as listed on the product data sheet
• Supplementary Information:
None
European Contact: Your Local Moore Industries Sales and Service Office
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair –
If you are unsure if your unit is still under warranty, we can use the unit’s serial number
to verify the warranty status for you over the phone. Be sure to include the RMA
number on all documentation.
Non-Warranty Repair –
If your unit is out of warranty, be prepared to give us a Purchase Order number when
you call. In most cases, we will be able to quote you the repair costs at that time.
The repair price you are quoted will be a “Not To Exceed” price, which means that the
actual repair costs may be less than the quote. Be sure to include the RMA number on
all documentation.
3. Use sufficient packing material and carefully pack the equipment in a sturdy shipping
container.
The returned equipment will be inspected and tested at the factory. A Moore Industries
representative will contact the person designated on your documentation if more information is
needed. The repaired equipment, or its replacement, will be returned to you in accordance with
the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THE
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WARRAN- COMPANY SHALL BE BARRED UNLESS THE COMPANY RECEIVES
TIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT OR
FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SER- BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THE
VICES SOLD BY THE COMPANY. THE COMPANY DISCLAIMS ALL WARRAN- BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DE-
TIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, AND FECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WAR-
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWL- RANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THAN
EDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM OR TWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYER
USAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THAT COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR
ANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IM- BREACH.
PLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANY
WAY. RETURN POLICY
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREES For a period of thirty-six (36) months from the date of shipment, and under
WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REMEDIES FOR normal conditions of use and service, Moore Industries ("The Company") will
BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES at its option replace, repair or refund the purchase price for any of its manu-
SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACE factured products found, upon return to the Company (transportation charges
THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THE prepaid and otherwise in accordance with the return procedures established
COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CONSEQUENTIAL OR by The Company), to be defective in material or workmanship. This policy
INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPT extends to the original Buyer only and not to Buyer's customers or the users
TO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASE of Buyer's products, unless Buyer is an engineering contractor in which case
THE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALL the policy shall extend to Buyer's immediate customer only. This policy shall
MONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THE not apply if the product has been subject to alteration, misuse, accident, ne-
GOODS OR SERVICES. glect or improper application, installation, or operation. THE COMPANY
SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSE-
QUENTIAL DAMAGES.
© 2005 Moore Industries-International, Inc. Specifications and Information subject to change without notice.