Product HIMHART IM 1.us

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

Interface and Monitor

November 2005
224-778-00C
Smart HART ® Loop
Interface and Monitor
HIM
Smart HART® Loop
HIM
Table of Contents

The HIM .............................................................................................................. 3


About this Manual ............................................................................................................... 3
Specifications ..................................................................................................................... 4
HIM Dimensions ................................................................................................................. 5
Terminal Designations ........................................................................................................ 5
Configuring the HIM ......................................................................................... 6
Installing the HIM .............................................................................................. 7
Installing the HIM into the Loop ........................................................................................... 7
Bench Checking the HIM .................................................................................................... 9
PC Configuration Software............................................................................10
HART Parameters ............................................................................................................ 11
Display Parameters .......................................................................................................... 13
Alarms Parameters ........................................................................................................... 14
Analog Outputs Parameters .............................................................................................. 16
Custom Curve Parameters ................................................................................................18
Scaling Parameters .......................................................................................................... 19
Customer Service ...........................................................................................20
Appendix A: HIM MODBUS Feature .............................................................21

2 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

Takes Advantage of Legacy Instruments


The HIM The device lets you leave existing smart HART trans-
The Moore Industries HIM HART Interface Module mitters and valves in place, yet still take advantage of
unlocks the full potential of new and in-place HART all the information they have to offer.
multivariable transmitters, valves, meters and other
smart instruments. Works with every Smart HART Device
The instrument can be programmed in minutes to inter-
Converts HART to 4-20mA Signals face with every HART-compatible monitoring and con-
The HIM allows up to three additional analog process trol device.
variable measurements from a multivariable transmit-
ter or valve with no additional process penetrations.
Installed transparently across the 4-20mA instrument
About this Manual
loop, the HIM reads the HART digital process data that Wherever you see a “Note”, “Caution”, or “WARNING ”
rides on the loop wires. It converts the digital informa- pay particular attention.
tion for up to three isolated analog (4-20mA) process • A “Note” provides information to help you in
signals that are readily accepted by in-place control avoiding minor inconveniences during
systems, such as a DCS or PLC. calibration, installation or operation of the HIM.

Provides Process and Diagnostic Alarms • A “Caution” provides information on steps to take
Relay alarm trips (optional) can be individually user-set to avoid procedures and practices that could risk
either to trip when unwanted high/low process condi- damage to the HIM or other equipment.
tions occur, or provide a diagnostic health warning to
• A “WARNING ” provides information on steps to
alert of loop or instrument fault conditions. take to avoid procedures and practices that could
pose safety risks to personnel.

Figure 1. The HIM Accepts a Digital HART Signal and Outputs Both Analog Signals and Alarm Relays

Control System
HART Communicator can (DCS or PLC)
be connected anywhere
along the 4-20mA loop
(HART Secondary Master)

4-20mA Representing the


Primary Variable (Mass Flow)

HART Digital Signal Carrying Primary,


Second, Third, Fourth Variable Process Data,
and Instrument Diagnostic Information

4-20mA Proportional to 2nd Variable (DP)


HIM HART Interface Module
"Breaks Out" Data from 4-20mA Proportional to 3rd Variable (P)
Smart HART Instruments 4-20mA Proportional to 4th Variable (T)
(HART Primary Master) High Alarm in Response to 4th Variable (T)
HART Transmitter Fault Alarm

Smart HART
Multivariable
Mass Flow
Transmitter

Flow

The Interface Solution Experts 3


HIM
Smart HART Loop
Interface and Monitor

Specifications
Performance Input Accuracy: Reflects Performance +TX Power Supply: 24.0Vdc Indicators Format: Top row is five
the accuracy of the HART (Continued) ±10%@24mA (Continued) alphanumeric characters,
field device ALARM OUTPUTS plus sign and decimal point;
Input Impedance: Transmit Digital Response Time: bottom row is five
Mode: 150 ohms; Defined by HART protocol as alphanumeric characters
Receive Mode: Less than 500msec maximum in Normal Decimal Points: User-
5kohms HART Mode; 333msec selectable for 0, 1, 2 or 3
Input Over-Range maximum in HART Burst places after the decimal point
Protection: ±5Vdc Mode or automatically adjusting with
Alarm Response Time: a four decimal point maximum
ANALOG OUTPUTS Digital Response Time + Range: -99999 to 99999
Output Accuracy: ±0.015% 150msec (Defined as time Minimum Display Span:
of maximum output span from the field instrument’s 1.00
(20mA). Includes the reporting a fault until the HIM Display Update Rate:
combined effects of linearity, alarm is tripped) 100msec
hysteresis, repeatability and Alarm Trip Delay: LED Type: Dual color
adjustment resolution. Programmable from 0-120sec red/green indicate:
Output Response Time: INPUT LED: Whether (green)
<120ms, 10-90% MODBUS OUTPUTS or not (red) the HART input is
Isolation: 500Vrms channel- Type: Standard MODBUS connected and functioning
to-channel isolation; RTU protocol interface over properly
1000Vrms between case, RS485 (parameters as READY LED: Whether
input, outputs and power specified in U.S. Standard (green) or not (red) the HIM is
terminals, and will withstand EIA-RS485) initialized and operating
1500Vac dielectric strength Address Range: properly
test for one minute with no Configurable from 1 to 247. TRIP 1 and 2 LED: Shows the
breakdown Unit will assume a MODBUS status of alarm off (green) or
Ripple: Less than 10mV address of 01 by default alarm on (red)
peak-to-peak when Baud Rate: Interface
measured across a supports the following: 300, Ambient Operating & Storage
250 ohm resistor 600, 1200, 4800, 9600, 19.2k. Conditions Range:
Output Limiting: 130% of MODBUS interface will -40°C to +85°C
span maximum; 125% of support even, odd and no (-40°F to +185°F)
span typical parities. Unit will assume a Display Range:
Output Protection: baud rate of 9600 and no -25°C to +85°C
Transient protection on parity by default (-13°F to +185°F)
output Character Format: One start Relay Range:
Load Capability: bit, 8 data bits and one stop -25°C to +70°C
0-20mA, 1100 ohms bit (-13°F to +158°F)
maximum Data Format: User- Relative Humidity:
Load Effect: ±0.01% of span selectable Standard LSW 0-95%, non-condensing
from 0 to maximum load (Least Significant Word) or Ambient Temperature
resistance Swapped MSW (Most Effect: ±0.0065% of
Line Voltage Effect: Significant Word). Unit will span/°C maximum
±0.005% of output span for a assume Standard LSW by RFI/EMI Immunity
1% change in line voltage default (Standard):
Input Fail Modes: PC Power Consumption: 20V/m@20-1000MHz, 1kHz
programmable to fail high, fail 2-3.5W, nominal; 4.5W AM, when tested according to
low, hold last, hold last then @24Vdc maximum for units IEC1000-4-3-1995
fail high, or hold last then fail using transmitter excitation to RFI/EMI Immunity (with
low (configurable hold time, 0- supply loop power a 2-wire -RF Option): 30V/m@
60 seconds) instrument 20-1000MHz, 1kHz AM, when
Output Limits on Input tested according to IEC1000-
Failure: 0-20mA: Fail Low to Indicators LCD Type: Two-line LCD; 4-3-1995
0mA or Fail High to 23.6mA; Top Row, 10mm (0.4 in) high Noise Rejection: Common
4-20mA: Fail Low to 3.6mA black digits on a reflective Mode: 100dB@50/60Hz
or Fail High to 23.6mA; background; Bottom Row,
X-20mA (0<X<4): Fail Low to 6mm (0.225 in) high digits Weight 567 grams (16 ounces)
90% of XmA or Fail High to on a reflective background;
23.6mA two-digit HART address
indicator
Specifications and information subject to change without notice.

4 The Interface Solution Experts


Smart HART Loop
HIM
Interface and Monitor

Figure 2. HIM Dimensions

138mm
65mm (5.45 in)
133mm
(2.56 in) (5.25 in)

T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12

INPUT READY TRIP 1 TRIP 2

ADDR
60.278 100mm
0 DEG C (3.94 in)

COM
HIM HART INTERFACE
MODULE

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12

Table 1. Terminal Designations


INPUT / OUTPUT T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12

+TX +IN –IN No Label +I Source –I Source –I Sink +I Source –I Source –I Sink
(AO2) or (AO2) (AO1) or (AO1)
HART Input, 2 Analog Outputs (2AO) +I Sink +I Sink
(AO2) (AO1)

+TX +IN –IN +I –I Source –I Sink +I Source –I Source –I Sink +I Source –I Source –I Sink
Source or (AO3) (AO2) or (AO2) (AO1) or (AO1)
HART Input, 3 Analog Outputs (3AO) (AO3) +I Sink +I Sink +I Sink
(AO3) (AO2) (AO1)

HART Input, 2 MODBUS Oututs A B S A B S


+TX +IN –IN +I –I Source –I Sink
and 1 Analog Output (MB1AO) MODBUS MODBUS MODBUS MODBUS MODBUS MODBUS
Source or (AO) 2 2 1
2 1 1
(AO) +I Sink
(AO)

A B S A B S
HART Input, 2 MODBUS Outputs (MB) +TX +IN –IN No Label MODBUS MODBUS MODBUS MODBUS MODBUS MODBUS
2 2 2 1 1 1

ALARM RELAYS / POWER B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12

No Alarm No Label DC DCC Ground


No Label

NO1 CM1 NC1 NO2 CM2 NC2 DC


Single Alarm (–1PRG) DCC Ground
Relay 1

Dual Alarm (–2PRG) NO1 CM1 NC1 NO2 CM2 NC2


DC DCC Ground
Relay 1 Relay 2

KEY: NOTES:
+IN/–IN = Current input to HIM from HART device +TX = Transmitter Excitation Current 1. The standard Single Alarm unit (1PRG) utilizes a DPDT relay.
+I/–I Source = Analog Source Output +I/–I Sink = Analog Sink Output 2. Terminal blocks can accommodate 14-22 AWG solid wiring
A/B = MODBUS Output NO/NO# = Normally Open (torque to 4 inch-pounds, maximum).
NC/NC# = Normally Closed CM/CM# = Common
DC/DCC = 24VDC Connection (AO#) = Analog Output

The Interface Solution Experts 5


HIM
Smart HART Loop
Interface and Monitor

Table 2. Assembling the Necessary Equipment


Configuring the HIM
One of the benefits of the HIM is that there are no Device Specifications
internal or external controls to adjust or settings to
Precision Load
change. All operating parameters are set using the PC Resistor
250 ohms, ±0.01%
Configuration software.
Multimeter or Accurate to ±0.009% of span;
Ammeter e.g. HP Model 3487A
Once these software settings are made, they are
downloaded to the monitor in the form of a Configuration Power
24Vdc, ±10%
File and stored in the unit’s non-volatile memory. You Supply
can choose to save a backup copy of the file on your
80386-based(or faster) IBM PC, or 100%
PC hard drive or external media. The HIM communi- compatible; (Pentium recommended)
cates with the PC through a proprietary communica- Personal Computer
CD Drive
4Mb free RAM; 16Mb recommended
tions cable to the PC’s serial (COM) port.
20Mb free disk space on hard drive
1 (one) serial port (COM 1, 2, 3 or 4)
Begin by installing the PC Configuration Software.
Microsoft Windows® 95, 98, 2000, ME, or
NT with Internet Explorer 4.0+
PC Operating
or
Installing the PC Configuration Software System
Microsoft Windows® NT with
Refer to Table 2 for the equipment needed. Service Pack 3 or greater
Moore Industries
1. Insert the Moore Industries Interface Solution Version 1.0 or higher, successfully
PC Configuration
installed to the hard drive
PC Configuration Software CD into the CD drive Software
of the PC. Access the CD and open the HIM
Communication
PC Configuration Software folder. Cable
Part Number: 803-053-26, or equivalent
2. Double-click the installation program located in
the folder. Follow the prompts to correctly
install the program.

Once the Configuration Program is installed on the PC,


the unit can be connected either into the loop or to test
equipment to simulate input and monitor output. With
the PC program, the user can then view and/or change
its operating parameters. To begin the process, connect
the HIM either into the loop (see Installing the HIM into
the Loop) or into a configuration setup (see Bench
Checking the HIM).

6 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

Mounting
Installing the HIM The HIM is designed to snap easily onto 32mm, G-type
There are two methods for connecting the HIM for (EN50035) or 35mm Top Hat (EN50022) DIN rails.
configuration. The recommended method requires you
to install the instrument into the loop before it is Electrical Connections
configured. The secondary method allows you to bench After mounting, you are ready to connect the HIM to
check the HIM by attaching it to test equipment that the loop. Each unit comes equipped with a transmitter
will simulate the input and monitor the output. excitation terminal which allows it to supply power to
the monitored HART instrument, if necessary. Figures
Installing the HIM into the Loop 2 and 3 show the connection diagrams for an HIM with
Installation consists of physically mounting the unit, or without using the transmitter excitation current.
grounding the instrument, and completing the electrical
connections. To install the HIM into the loop for CE Conformity
configuration, use the equipment in Table 2 to hookup Installation of any Moore Industries products that carry
the HIM into the loop as shown in Figure 3 (without the CE certification (Commission Electrotechnique)
using the HIM to power a transmitter) or Figure 4 (using must adhere to the guidelines in Installing the HIM in
the TX terminal to power a transmitter). If you need a order to meet the requirements set forth in applicable
complete terminal description, refer to Table 1.
Figure 3. Installing a HIM Into the Loop Without Using the Transmitter Excitation (+TX) Terminal

HART Communicator
can be connected
anywhere on the loop
➤ ➤

7 ➤
4 8
5 9
1
0
.
2
3
6

R must be > 250 and <1100 Ohms



24Vdc ➤

Power
+ –
Sensor +
Input
4-20mA R

+IN –IN

HART Multivariable
Field Instrument INPUT READY TRIP 1 TRIP 2 DCS
(Temperature
Pressure, Level
and Flow)
Analog Output tied to
ADDR

0 Any Process Variable

COM

25.1 80.1 50.7


deg-c 20.3

Event Recorder
DCC

GND
NO

NC

DC
COM

NO (normally open) 24Vdc


Power
Source
COMMON

NC (normally closed)

The Interface Solution Experts 7


HIM
Smart HART Loop
Interface and Monitor

EMC (Electromagnetic Compatibility) directives • All input signals to, and output signals
(EN55011, EN 50082-1, EN50082-2, etc.). Consult the from, Moore Industries’ products should be
factory for the most current information on products wired using a shielded, twisted pair
that have been CE certified. technique. Shields are to be connected to an
earth or safety ground at the unit itself.
Recommended Ground Wiring Practices
Moore Industries recommends the following ground • The maximum length of unshielded input
wiring practices: and output signal wiring should be 2 inches.

Power Sourcing Parameters for General


• Any Moore Industries product in a metal Locations, Intrinsically Safe, and
case or housing should be grounded. Non-Incendive/Type N applications
In accordance with IEC 1010.1 Annex H
• The protective earth conductor must be
(all models), the input terminals must be
connected to a system safety earth ground
connected to and/or supplied from a certified
before making any other connections.
energy limiting Class 2 or a Separate Extra Low
Voltage (S.E.L.V.) power supply separated from
all mains by double/reinforced insulation.

Figure 4. Installing a HIM Into the Loop Using the Transmitter Excitation (+TX) Terminal
HART Communicator
can be connected
anywhere on the loop
➤ ➤

7 ➤
4 8
5 9
1
2 6
0
3
.
R must be > 250 and <1100 Ohms



Sensor
Input
4-20mA
+IN
R
+
+TX –IN
HART Multivariable
Field Instrument
(Temperature, INPUT READY TRIP 1 TRIP 2 DCS
Pressure, Level
and Flow)

Analog Output tied to


ADDR

0 Any Process Variable

COM

Event Recorder
DCC

GND
NO

NC

DC
COM

NO (normally open) 24Vdc


Power
Source
COMMON

NC (normally closed)

8 The Interface Solution Experts


Smart HART Loop
HIM
Interface and Monitor

Bench Checking the HIM Figure 6. Bench Checking the HIM Without Using the
Transmitter Excitation (+TX) Terminal to Power a Transmitter
If you would like to configure the HIM before
attaching it to the loop, you need to hook it up For a HART Transmitter, the
with the equipment listed in Table 1. Refer to resistor must be >250 and <1100 ohms.
For a HART Receiver, such as a
Figures 5 and 6 for instructions on how to bench 24Vdc valve positioner, no resistor is necessary.
Power
check the HIM either with or without taking + –

advantage of the Transmitter Excitation (+TX) Sensor


HART +
Input +
terminal. If you need further descriptions of the Field Device
or
R
Multimeter
terminals, see Table 2. Simulator –
+IN –IN – –

Figure 5. Bench Checking the HIM Using the Transmitter +


Optional
Excitation (+TX) Terminal to Power a Transmitter
INPUT READY TRIP 1 TRIP 2

R must be > 250 and <1100 Ohms ADDR

– 0
Sensor HART
Input Field Device +
R COM

or Multimeter
+IN
Simulator +
+TX –IN –
+ –
Equipment Hook-Up

GND
DCC
NO

NC

DC
for HART field device using INPUT READY TRIP 1 TRIP 2

COM
Transmitter Excitation
Multimeter 24Vdc
ADDR
Power
0
Checks for
COM
continuity
Optional
GND
DCC
NO

NC

DC
COM

Multimeter 24Vdc
Power

Checks for
continuity
Optional

The Interface Solution Experts 9


HIM
Smart HART Loop
Interface and Monitor

PC Configuration Software
Figure 7. HIM PC Configuration Software Screen

3
2

The HIM PC Configuration Software can be used to HIM Device Status–Displays how the HIM is function-
program all of the HIM’s parameters. Once the default ing, giving a brief summary of any errors or displaying
configuration has been saved, it is safe to program OK if it is operating normally.
other parameters. The PC Software is made up of
these sections: HIM Displayed Data–this display mirrors what the at-
tached HIM is displaying.
1. HIM Status and Information Section–The left
side of the screen includes seven boxes that display Progress–This bar stays in motion any time the HIM
the different settings of the attached HIM. is monitoring, uploading or downloading.

Program Status–Displays the activity of the Communication Status–monitors the PC Software’s


connected HIM. It will show you if the unit is Idle, ability to communicate with the HIM.
Uploading, Downloading, Monitoring or Searching.
2. HART/Display/ Alarms/Analog Outputs/Custom
HIM Device Info–Displays the individual charac Curve/ Scaling Tabs–These tabs change the right
teristics of the attached HIM, such as its Identifi- side of the screen to allow you to set the appropriate
cation, Hardware and Software Revisions, and the part of the HIM’s configuration. Refer to the associ-
last date that the device was configured. ated pages in this document for additional information
on these tabs.
HIM Tag–A phrase used to identify a HIM.
3. Menu Bar/Tool Bar– Dropdown menus and corre-
sponding icons allow you to perform various functions
throughout the PC Configuration Program.

10 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

HART Parameters The HART protocol allows for two communications


To program the HART parameters, change the settings masters on the loop, a Primary and a Secondary.
in the Communications Settings box, then press Quick Setting the HIM to function as the Primary HART
Set. See the descriptions below of the various Master in the application means that any other HART
sections of the screen. device in the loop must be configured either as a HART
Secondary Master (1 per loop) or as a HART Slave (up
HART Address to 16 per loop). Conversely, setting the HIM to function
The HART Address is the address of the HART device as the Secondary HART Master allows other HART
that the HIM will be monitoring. devices to function either as a Primary Master or as
slaves. Configuring more than one device on a single
Number of Retries loop as a Primary or Secondary HART Master will
The Number of Retries can be set between 1 and 9, cause a communications failure.
and will determine how many times the HIM will
attempt to poll the HART transmitter (without success), Listen (Specified Slave)
before it indicates a HART Fault condition. When multiple HART instruments are present, the
Listen (Passive) mode cannot be used because data
Normal/Burst/Listen (Passive) Modes returned from one instrument will overwrite the data
The HIM can operate in one of four modes: Normal, previously stored in the HIM. If multiple HART slave
Burst, or Listen (Passive) and Listen (Specified Slave). instruments are communicating on the loop, the HIM
In each of these modes, the HIM attempts to find a will overwrite its internal HART data sets with the latest
HART transmitter. device read from the bus, no matter where the data
originates. To allow selective monitoring on a multi-
In Normal mode, the HIM polls the HART loop for a instrument loop, and to allow multiple HIMs to be used
transmitter, then polls the HART instrument twice per on a digital loop, the Listen (Specified Slave) feature is
second, requesting the current process status and the used.
HART instrument’s diagnostic status. The HART
instrument responds with the requested data. If the HIM is in “Listen” mode it is not a HART commu-
nication master and therefore is not in control of
In Burst mode, the monitored HART instrument is
communication. Other HART masters are controlling
programmed to continuously transmit its process
the polling of slaves and the HIM can only “Listen”.
variable and health status. The HIM samples the
continuous HART data three times per second. The HIM must be able to detect when it has not heard
from its assigned slave device so that it can declare a
Listen (Passive) mode allows the HIM to operate on a
“No HART” input and force outputs to the values
loop that already has primary and secondary HART
masters. In Listen (Passive) mode, the monitor specified by the user. The HIM must therefore be told
connects passively, continuously sampling HART data to wait an appropriate amount of time for the slave
from a smart instrument without affecting normal loop device to send its message before the HIM declares
operation. When using this mode, either the monitored “No HART”. This timing coordination is accomplished
smart HART instrument must be set in Burst Mode or a with Timeout Period.
HART master must be continuously polling the smart
HART slave device. Timeout Period is a value between 1 and 30sec and
must be greater than the period between polls by the
HART master of the Specified Slave. For example,
assume that there are five HART transmitters on the
same multi-drop loop as the HIM. The HART master is
configured to poll each device every second. It then
takes the HART master five seconds to repeat the poll
to the one device being monitored by the HIM. the HIM
Timeout Period must be set at a value greater than five

The Interface Solution Experts 11


HIM
Smart HART Loop
Interface and Monitor

seconds. In this example, we will use seven seconds. To convert HEX to Decimal code, perform the
The HIM then sees its slave device speak and waits following steps:
seven seconds for it to speak again. As long as the
HIM sees a new message from its slave device its Access the Calculator feature in Microsoft
outputs are updated based upon the measured vari- Windows® by opening the Start menu. Next,
ables. If the slave device does not speak within the select Programs then Accessories and finally
seven second period, the HIM declares a “No HART” Calculator.
situation and sends its outputs to the failed communi-
Ensure that the Calculator is in Scientific mode.
cations values.
To do this, select the View dropdown menu
To use this feature, proceed with the following steps: and choose Scientific.

1. Select the Listen (Specified Slave) button. Click the Hex radio button and enter the HEX
code value.
2. Enter your desired value into the Timeout Period(s)
text box. Next, click the Dec button and the value will be
converted into the Decimal value.
Factory default is 5 seconds. The maximum Timeout
Period is 30 seconds. Enter the converted value into the proper param
eter.
3. Set the exact slave address of the instrument you
wish to monitor. Click the Set Slave Address button. The Device ID Number is the serial number of
This brings up the HART Slave Device Long Format the exact device to which the HIM will listen.
Address Settings screen (Figure 8). Enter the required
4. Once complete, press OK.
information into the appropriate text boxes.
Download the information to your instrument once you
Figure 8. HART Slave Device Long Format Address Settings are finished.
Screen
Auto Clear Status Bit
Most HART instruments indicate when a device's
configuration has been changed. This indication
(status bit) can be reset by sending HART command
38–reset configuration changed. Checking the Auto
Clear Status Bit box causes the HIM to issue this
command whenever the HART instrument it is
monitoring has its configuration changed. However,
The Manufacturer’s ID and Device Type ID for the the HIM can also be set to alarm on this bit (see
instrument that the HIM will listen to are available from Programming the Alarm Parameters). If the HIM is
the HART Foundation website at www.hartcomm.org both set to alarm and to auto clear, then it will do
and/or the instrument manufacturer. both–going into alarm mode and resetting that
indication.
Values obtained from the HART website are in HEX
code. The HIM does not use HEX code; you must Quick Read/Set
convert this value to Decimal code. The Quick Read button causes the PC Configuration
Software to read the communications information from
the attached HIM; the Quick Set button causes the
software to configure the HIM’s communications
settings to match those of the PC Software.

12 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

HART Device Info Toggle, Variable List


This box displays the identification and revision The Toggle checkbox causes the HIM to sequentially
information of the monitored HART instrument. display two HART variables in five second increments.
Directly below the Toggle checkbox are two list boxes
HART Device Status to select the variables that you would like to be
The HART Device Status box displays the current displayed. Notice that if you select a scaled variable,
status of the monitored HART transmitter. In a small it is important to check on the Scaling page to verify
double-box, the software displays the code (hex that you have set all of the scaling parameters.
number) associated with the status.
Use Custom Label
Variables The Custom Label is used to display a calculated or
The device will monitor up to the first four HART scaled variable. Clicking the Use Custom Label box
variables sent by your transmitter. This portion of the causes the HIM to always display the custom label as
screen displays those variables and the Loop Current. Engineering Units (EGUs).

Precision
HART Device Range & Limits The Precision buttons allow you to change the number
This portion of the screen displays the range and the of decimal places displayed by the HIM.
sensor limits of the monitored HART transmitter.
Quick Set
The Quick Set button programs the HIM with the
information on the Display page.
Display Parameters
The Display tab configures the HIM’s LCD display. To Display Format
program the Display parameters, change the settings in The HIM reads the dynamic process variable supported
the Display Source box, then press Quick Set. See by HART sensors. Generally, the HIM’s LCD displayed
the following descriptions of the various sections of the values range from -99999 to 99999. Occasionally,
screen. these process variable values may extend past this
range. To improve the displayed readings, values
Figure 9. Display Tab below -XXXXX and above XXXXX are translated into
exponential form. Below is an example of the appear-
ance of the display when certain values are sensed.

Value Display
12345 12345
1234500 1.23E06
-500000 -5.00E05

The Interface Solution Experts 13


HIM
Smart HART Loop
Interface and Monitor

Alarms Parameters Device Malfunction (Bit 7)


The Alarms tab controls the programmable alarm Relay trips whenever it detects that a hardware error or
trip(s) option. This screen will be grayed out if the failure has occurred in the connected HART device.
attached HIM is not equipped with at least one alarm
trip. To program the Alarm parameters, change the Configuration Changed (Bit 6)
settings in the Alarm1 and/or Alarm2 box, then press Relay trips whenever it detects that the connected
Quick Set. The sections of the screen are described HART device has had its configuration changed.
below.
Cold Start (Bit 5)
Figure 10. Alarms Tab Relay trips whenever the power to the HART device is
interrupted. It will also trip during a HART Master
Reset or Self Test Command.

Additional Status (Bit 4)


Relay trips whenever the connected HART device
reports a condition requiring HART Command #48,
which is Read Additional Information. This indicates
that the instrument needs attention from a device with
full HART command capability.

Output Current Fixed (Bit 3)


Relay trips whenever the HIM detects that the
connected HART device’s output is no longer
responding to changes in its input, and is being held at
a predefined level.

PV Analog Output Saturated (Bit 2)


Trip/Fault Alarms Relay trips whenever it detects that both its analog and
A Trip Alarm monitors a selected variable and trips digital representations of the Primary Variable are
either when the variable exceeds a set value (Trip outside rated operating limits, and no longer reflect the
High) or when the variable falls below a selected value true sensor input.
(Trip Low). The Source specifies which variable will be
monitored, while the Trip Point sets the point at which Non-PV Out of Limits (Bit 1)
the alarm will trip. After the alarm trips, the Dead Relay trips whenever one of the HART ancillary
Band determines how far past the trip point the variables (second, third or fourth), is operating outside
variable will have to go before the alarm condition the limits that can be effectively measured.
returns to normal.
PV Out of Limits (Bit 0)
There are two types of Fault Alarms. A HIM Fault Relay trips whenever the HART Primary Variable is
Alarm monitors the health of the HART monitor. It will operating outside the limits that can be effectively
trip whenever the internal error status word is set. For measured.
example, if the HIM’s configuration file becomes
corrupt, this alarm will trip and the monitor will display Delay & Fail Safe
BAD_CONFIG. A Field Device Fault Alarm monitors By entering a value in the Delay box, you can specify
the health of the HART transmitter. This fault alarm how long (in seconds) the alarm condition needs to
will trip for any of these eight malfunctions: exist before the alarm trips. Failsafe alarms (box
checked) de-energize when in alarm condition;
Non-Failsafe alarms energize when tripped.

14 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

HART Additional Status Alarm Bits Read & Quick Set Buttons
HART Additional Status also called “More Status” and The Read button causes the PC Configuration Software
to read the alarm information from the attached HIM;
“Command 48” is where device manufacturers install
The Quick Set button causes the software to configure
the custom diagnostics for the specific device. For
the HIM's alarm settings to match those currently
your particular application, you may choose all of these entered in the PC Software.
diagnostics to cause the HIM relay to trip or just one
diagnostic bit to trip the HIM relay (or any combination
in between). The manufacturer of the HART device will
be the source for the specific diagnostic information.

Selecting the Field Device Fault Alarm function in the


Alarms screen allows you to enable the HIM to set
alarm states, when in fault mode, based on the bit
settings of the additional status information returned by
certain HART instruments. This provides flexibility to
the requirement of alarming on additional status infor-
mation.

Choosing this feature, you are given the ability to


specify the bit(s) on which to alarm. To access this
feature, check the Additional Status box. The Edit
button will appear in the HART Additional Status Bits
section of the screen. Clicking the Edit box brings up
the Additional HART Status Alarm Bits Settings window
(Figure 11). Check the box(es) that correspond to the
bits you wish to use; click OK.

Download the information to your instrument once you


are finished.

Figure 11. Additional HART Status Alarm Bits Settings Window

The Interface Solution Experts 15


HIM
Smart HART Loop
Interface and Monitor

Analog Outputs Parameters For example, you have a vortex flow meter with an
The HIM comes with either two (–2AO) or three (–3AO) imbedded RTD that measures the process
analog outputs. The Analog Outputs tab allows you to temperature, and that temperature is assigned to the
specify which HART variable is to be monitored as the HART Secondary Variable. The full range of the RTD
source of the analog output, the input range and output sensor is from –400°F to +1760°F, but your flow
range, and how the output will react when the variable stream will always be between 0° and 400°F. To scale
input is out of range. To program the Analog Outputs the analog output, for Output 1, set the Source as SV.
parameters, change the settings in the Output1/2/3 Set the Input Range to 0° and 400°F, and the Output
boxes, then press Quick Set. See the descriptions Range to 4mA to 20mA. Click Quick Set to download
below of the various sections of the screen. the new configuration file to the HIM.

Output Current Box


Figure 12. Analog Outputs Tab The Output Current Box on the Analog Outputs Tab
displays up-to-the-second information on the value, in
mA, of the analog output.

Fail Mode
The Fail Mode setting determines how the HIM will
respond when its monitored input fails. If Fail Mode is
set to High and the measured input goes out of range,
or any detected error occurs in the HART transmitter,
the analog output will output a 23.6mA signal. If Fail
Mode is set to Low and the measured input goes out of
range, or any detected error occurs in the HART
transmitter, the analog output will output a signal that
is 90% of the lower range value below 4mA; it will
output 0mA if the lower range is set to 0mA.

If Fail Mode is set to Hold Last, the HIM will continue


Source to output the last value it recorded before the input
Source defines the variable that the analog output will failed. If Fail Mode is set to Hold Last Then High or
monitor. Notice that selecting one of the scaled Hold Last Then Low, the HIM will continue to output the
outputs will require you to make changes to the last value recorded for a set amount of time (according
Scaling tab, and selecting the Custom Curve option will to Hold Last Duration box), then either fail high or fail
require you to make changes to the Custom Curve tab. low, respectively.

Input/Output Range Quick Set Button


The Input or Output Range defines the range of the The Quick Set button causes the software to configure
source input and the range of the analog output. the instrument’s analog output settings to match those
These two sets of fields can be used to scale the currently entered in the PC Software.
HIM’s output.
Trim Button
The Trim button brings up the Trim Menu, allowing you
to set the device’s output to match the reading of the
loop. Refer to the Programming the Trimming
Parameters section of this manual for more
information.

16 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

Configuring Analog Output Trimming Fix Current Utility


The Analog Output Trimming section of the software The Fix Current Utility allows you to force the HIM to
allows you to match the HART monitors analog output output any current value from 0-20mA. This can be
to the output measured by a calibration device. This used to match the calibration of your other equipment.
will require a calibrated multimeter, such as a HP Model To fix the current, simply enter the value in the Current
3478A or equivalent, accurate to ±0.009%. box (in mA) that you want the HIM to output, and click
Fix Output. When you are finished, make sure to
press the Unfix Output button so that the HIM can
return to normal operation.
Note:
Trimming the analog output of the monitor
nullifies any scaling that may have been
performed in the Scaling tab.

Figure 13. Trimming Window

User Trimming
To trim the device, attach a multimeter to the analog
output, then click the Fix Output at Low Point button.
Read the value on the multimeter, enter it into the
Measured Output Loop Current portion of the Trimming
box, and press Trim. Repeat this sequence until the
analog output matches the minimum point (4mA for a
4-20mA output) when you click the Fix Output at Low
Point button.

After the low point is trimmed, press the Fix Output at


High Point button. Read the value on the multimeter,
enter it into the Measured Output Loop Current portion
of the Trimming box, and press Trim. Repeat this
sequence until the analog output matches the
maximum point (20mA for a 4-20mA output) when you
click the Fix Output at High Point button.

When finished, press the Unfix Output button.

The Interface Solution Experts 17


HIM
Smart HART Loop
Interface and Monitor

Custom Curve Parameters Custom Curve Variable


The custom curve tab allows you to set up a custom The Custom Curve Variable displays up-to-the-second
curve of up to 128 points. A custom curve can either information on the value of the Custom Curve. Press
be created from scratch or loaded from a previously the Monitor button to display the variable information.
created comma separated value (.csv) file. To
program the Analog Outputs parameters, change the Custom Curve
settings in the Custom Curve tab, then press Download The middle section of the screen displays the custom
Table. See the descriptions below of the various curve table. After enabling custom curve mode and
sections of the screen. setting the variable to be monitored, continue by
selecting the number of points for the curve. Enter the
actual linearization points into the custom curve table,
Figure 14. Custom Curve Tab
inserting the source variable into the X Column, and
the corresponding data (i.e. the °C, °F, Gallons, PSIG,
Millimeters, etc.) into the Y Column.

Note:
When entering data in the linearization table, make
sure that you enter a number into every open cell.

Custom Curve File


These buttons allow you to manipulate custom curve
files, including the important Save Table command that
will save a table to your hard drive.

Upload Table
Moves a custom curve file from the connected HIM to
the PC Software for editing or storage.

Download Table
Configures the HIM by downloading the custom curve
table from the PC Software to the HIM.
Mode
Check the Enabled box to begin programming the Save Table
custom curve. Saves a displayed custom curve table to memory on
your computer’s hard drive.
Source Variable
The Source Variable defines the variable that the Load Table
custom curve will calculate. Notice that if you select a Loads a previously saved custom curve table.
scaled variable, you may need to click on the Scaling
tab and verify the settings for your scaled variable. Clear Table
Clears the displayed custom curve table.
Quick Set
The Quick Set button causes the software to configure When you have finished changing all your settings,
the HIM’s custom curve settings to match those download the information to the HIM using the
currently entered in the PC Software. Download Table button. If you have selected a scaled
variable, you should also click on the Scaling tab and
set the scaling parameters.

18 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

Figure 15. Scaling Tab


Scaling Parameters
The Scaling tab allows you to configure the values for
scaled variables. To scale the selected variable, enter
the values into the appropriate boxes, then click on the
Transfer menu and click Download to transfer the new
scaled values to the HIM. (If any scaled variable was
selected in the Display, Alarm or Analog Outputs tabs,
then the corresponding scaled variable section will
become active for editing).

The HIM’s versatile scaling feature has many possible


applications, as is shown in the illustration below.

Suppose you are using a digital pressure (DP)


transmitter to measure the level of a tank in either
centimeters/inches or PSI. Since the tank is only 300
centimeters (10 feet) high, the full range of the primary
variable (PV) output from the DP transmitter is 0-4.3
PSI. You want to display the full level range (in
centimeters/inches of water) on the HIM. You also 2. Go to the Scaling tab and set up the PV Zero and
need to control the level from 50% to 100%, since the PV Full values, and the Scaled PV Zero and Full
tank must be at least 50% full at all times. Finally, values. PV Zero would be 0 (PSI) and PV Full would
your existing loop indicator and level controller needs be 4.3 (PSI). Scaled PV would correlate to zero being
4-20mA to represent 150 to 300 centimeters (60 to 120 0 in H2O and full being 120 in H2O. The HIM should
inches) of water. How do you do this? now (after downloading) display the full range in
in H2O.
Scaling Illustration
1. Since you want to display the full level range in 3. To manipulate the HIM’s analog output, go to the
inches of water (in H2O) on the HIM, and the HIM is Analog Outputs tab. Select Scaled PV as the Output 1
reading PSI as the primary variable, first go to the source. Since you need to control the level from 50%
Display tab and select Scaled PV as your display to 100%, the Input Range should be 60 to 120 in H2O
source. and the Output Range should be 4mA to 20mA.

Figure 16. The HIM’s Scaling feature works to get the most out of your existing process instruments

Control
level
range
(50% to 100%
of total level) Full
Controller maintaining
Primary
Loop Display control from 50-100% of full scale
Variable
(reads 0-100% 4-20mA (60-120 inH 2 0/2.15-4.3 PSI).
range
of control Signal 4-20mA from HART Monitor
(in PSI)
level) should represent 60-120
inH 2 0.
4-20mA
Signal
Digital
Pressure HART HART Monitor
Transmitter Signal (120 PSI)

The Interface Solution Experts 19


HIM
Smart HART Loop
Interface and Monitor

Customer Support
Moore Industries is recognized as the industry leader
in delivering top quality to its customers in products
and services. We perform a battery of stringent quality
assurance checks on every unit we ship. If any Moore
Industries product fails to perform up to rated specifi-
cations, call us for help. Our highly skilled staff of
trained technicians and engineers pride themselves on
their ability to provide timely, accurate and practical
answers to your process instrumentation questions.

Factory phone numbers are listed on the back cover of


this manual.

If problems involve a particular instrument, there are


several pieces of information that can be gathered
before you call the factory that will help our staff get
the answers you need in the shortest time possible.
For fastest service, gather the complete model and
serial number(s) of the problem unit(s) and the job
number of the original sale.

20 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

Appendix A: HIM MODBUS Comms Settings


The Comms Settings include the following:
Feature
The HIM PC program allows you to configure the MODBUS Address
HART monitor. A HART Monitor with the MODBUS The MODBUS Address is the number that the HIM
option provides a digital MODBUS output to a con- monitor uses to identify itself on the MODBUS net-
nected MODBUS-based controller. Selecting the work. The MODBUS address is configurable from 1 to
MODBUS tab allows you to set the MODSBUS com- 247. By default, it will assume a MODBUS address of
munications parameters. Notice that the MODBUS tab 01.
will only be available in units with the MODBUS option.
Baud Rate
The Baud Rate is the speed of data transmission. It
Figure A-1. MODBUS Tab should be set to match the baud rate of the attached
controller. The interface supports the following baud
rates: 300, 600, 1200, 2400, 4800, 9600 and 19200.

Parity
The HART monitor supports even, odd and no Parity.
The data format is one start bit, 8 data bits and one
stop bit.

Floating Point Word Order


By default, the HART monitor will use the Standard
LSW (least significant word) floating point word order
format. This stores the most significant bits in the
second register and the least significant bits in the first
register. Selecting Swapped MSW (most significant
word) will reverse the order, storing the most signifi-
cant bits in the first register and the least significant
bits in the second register.

MODBUS Registers
The HART Monitor outputs a MODBUS signal to the
attached controller. To access the MODBUS registers
for variable, input/output or error information, refer to
Table A-1 (MODBUS Register Definitons table) and/or
Table A-2 (System Status Registers table).

The Interface Solution Experts 21


HIM
Smart HART Loop
Interface and Monitor

Figure A-2. Installing a HIM with MODBUS output into the loop using the Transmitter Excitation (+TX) terminal

HART Communicator
can be connected
anywhere on the loop

R must be > 250 ohms and <1100 ohms

Sensor –
Input
4-20mA +IN R
+ A
+TX –IN B
S
HART
Field Instrument
(Temperature, INPUT READY TRIP 1 TRIP 2 DCS
Pressure,
Level,
Flow Multivariable)
ADDR
60.278
0 DEG C
RS485 / RS232
Converter

COM TO serial
(COM) port
MODBUS output MODBUS Host
of PC
(with MODBUS option)
DCC

GND
NO

NC

DC
COM

NO (normally open) 24Vdc


Power
Source
COMMON

NC (normally closed)

22 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

Table A-1. MODBUS Register Definitions

Register Range Description

0 HART Primary variable

1 HART Secondary variable

2 HART Third variable

3 HART Fourth variable

4 PV scaled

5 SV scaled

6 TV scaled

7 FV scaled

8 Linearized variable

9 Analog Output 1 current x 100mA

10 Analog output 2 current x 100mA

11 Analog output 3 currentx 100mA

HIM Status Information


Bit 0 = hardware failure
Bit 1 = EEPROM fail
Bit 2 = EEPROM configuration checksum error
Bit 3 = EEPROM calibration checksum error
Bit 4 = EEPROM blank
Bit 5 = Out of range error
12 Bit 6 = Division by zero error
Bit 7 = Configuration data bad error
Bit 8 = COP SW fail
Bit 9 = RAM test fail
Bit 10-13 = not used
Bit 14 = HART device malfunction status bit set
Bit 15 = No HART communications status

13 HART status information (as per HART specification)

The Interface Solution Experts 23


HIM
Smart HART Loop
Interface and Monitor

14 HART instrument PV EGU (MSB = 0, LSB = HART EGU code)

15 HART instrument SV EGU (MSB = 0, LSB = HART EGU code)

16 HART instrument TV EGU (MSB = 0, LSB = HART EGU code)

17 HART instrument QV EGU (MSB = 0, LSB = HART EGU code)

18 Device ID MSW

19 Device ID LSW

20 HART Device Manufacturer ID

21 HART Device, device type code

22 HART device, device ID MSW

23 HART Device, device ID LSW

24 HIM Alarm Status (Bit 0 = alarm 1, Bit 2 = alarm 2)

256-257 HART Primary variable (float format)

258-259 HART Secondary variable (float format)

260-261 HART Third variable (float format)

262-263 Hart Fourth variable (float format)

264-265 Scaled Primary variable (float format)

266-267 Scaled Secondary variable (float format)

268-269 Scaled Third variable (float format)

270-271 Scaled Fourth variable (float format)

272-273 Linearized varialbe (float format)

274-275 Analog output 1 current x 100mA

276-277 Analog output 2 current x 100mA

278-279 Analog output 3 current x 100mA

24 The Interface Solution Experts


HIM
Smart HART Loop
Interface and Monitor

Table A-2. System Status Registers

MSB/LSB Bit Position Description


Int 16
(16 bit integar)

Bit 7 HART device no comms


MSB = device status
Bit 6 HART device malfunction

Bit 0 HW fail

Bit 1 EEPROM fail

Bit 2 EEPROM checksum error

LSB = device error code Bit 3 EEPROM calib data error

Bit 4 EEPROM blank

Bit 5 out of range value

Bit 6 division by zero

Bit 7 bad configuration

The Interface Solution Experts 25


Declaration of Conformity
EMC Directive 89/336/EEC

• Manufacturer’s Name: Moore Industries-International, Inc.


• Manufacturer’s Address: 16650 Schoenborn Street
North Hills, CA 91343-6196
USA

Declares that the product(s):

• Product Name: HIM

MODEL / INPUT / OUTPUT / POWER / OPTIONS / HOUSING

• Model Number(s): HIM * * * * *

* Indicates any input, output, power, option and housing as listed on the product data sheet

• Conforms to the following EMC specifications:


EN 61326-1, 1998, Electromagnetic Compliance (EMC) requirements for electrical equipment for control use.

• Supplementary Information:
None

June 20, 2003


Date Fred Adt Robert Stockham
Quality Assurance Director Moore Industries-Europe General Mgr.

European Contact: Your Local Moore Industries Sales and Service Office

United States • [email protected] Belgium • [email protected] China • [email protected]


Tel: (818) 894-7111 • FAX: (818) 891-2816 Tel: 03/448.10.18 • FAX: 03/440.17.97 Tel: 86-21-62491499 • FAX: 86-21-62490635
Australia • [email protected] The Netherlands • [email protected] United Kingdom • [email protected]
Tel: (02) 8536-7200 • FAX: (02) 9525-7296 Tel: (0)344-617971 • FAX: (0)344-615920 Tel: 01293 514488 • FAX: 01293 536852
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:

1. Call Moore Industries and request a Returned Material Authorization (RMA) number.

Warranty Repair –
If you are unsure if your unit is still under warranty, we can use the unit’s serial number
to verify the warranty status for you over the phone. Be sure to include the RMA
number on all documentation.

Non-Warranty Repair –
If your unit is out of warranty, be prepared to give us a Purchase Order number when
you call. In most cases, we will be able to quote you the repair costs at that time.
The repair price you are quoted will be a “Not To Exceed” price, which means that the
actual repair costs may be less than the quote. Be sure to include the RMA number on
all documentation.

2. Provide us with the following documentation:


a) A note listing the symptoms that indicate the unit needs repair
b) Complete shipping information for return of the equipment after repair
c) The name and phone number of the person to contact if questions arise at the factory

3. Use sufficient packing material and carefully pack the equipment in a sturdy shipping
container.

4. Ship the equipment to the Moore Industries location nearest you.

The returned equipment will be inspected and tested at the factory. A Moore Industries
representative will contact the person designated on your documentation if more information is
needed. The repaired equipment, or its replacement, will be returned to you in accordance with
the shipping instructions furnished in your documentation.

WARRANTY DISCLAIMER ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THE
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WARRAN- COMPANY SHALL BE BARRED UNLESS THE COMPANY RECEIVES
TIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT OR
FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SER- BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THE
VICES SOLD BY THE COMPANY. THE COMPANY DISCLAIMS ALL WARRAN- BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DE-
TIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, AND FECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WAR-
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWL- RANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THAN
EDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM OR TWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYER
USAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THAT COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR
ANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IM- BREACH.
PLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANY
WAY. RETURN POLICY
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREES For a period of thirty-six (36) months from the date of shipment, and under
WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REMEDIES FOR normal conditions of use and service, Moore Industries ("The Company") will
BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES at its option replace, repair or refund the purchase price for any of its manu-
SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACE factured products found, upon return to the Company (transportation charges
THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THE prepaid and otherwise in accordance with the return procedures established
COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CONSEQUENTIAL OR by The Company), to be defective in material or workmanship. This policy
INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPT extends to the original Buyer only and not to Buyer's customers or the users
TO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASE of Buyer's products, unless Buyer is an engineering contractor in which case
THE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALL the policy shall extend to Buyer's immediate customer only. This policy shall
MONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THE not apply if the product has been subject to alteration, misuse, accident, ne-
GOODS OR SERVICES. glect or improper application, installation, or operation. THE COMPANY
SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSE-
QUENTIAL DAMAGES.

United States • [email protected] Belgium • [email protected] China • [email protected]


Tel: (818) 894-7111 • FAX: (818) 891-2816 Tel: 03/448.10.18 • FAX: 03/440.17.97 Tel: 86-21-62491499 • FAX: 86-21-62490635
Australia • [email protected] The Netherlands • [email protected] United Kingdom • [email protected]
Tel: (02) 8536-7200 • FAX: (02) 9525-7296 Tel: (0)344-617971 • FAX: (0)344-615920 Tel: 01293 514488 • FAX: 01293 536852

© 2005 Moore Industries-International, Inc. Specifications and Information subject to change without notice.

You might also like