7.1. Overview
HART Field Communications Protocol extends this 4 ~ 20 mA standard to enhance
communication with smart field instruments. The protocol preserves the 4 ~ 20 mA
signal and enables two-way digital communications to occur without disturbing the
integrity of the 4 ~ 20 mA signal. Unlike other communication technologies, the
HART protocol can maintain compatibility with existing 4 ~ 20 mA systems with a
uniquely backward compatible solution. Here are two main operational modes of HART
instruments:
analog/digital mode, and multi-drop mode.

h Peer-to-Peer mode
The analog and digital signals can be communicated in this mode. Here the digital signals are overlaid on the 4 ~ 20 mA loop current.
Both the 4 ~ 20 mA current and the digital signal are valid output values from the instrument. The polling address of the instrument is
set to "0". Only one instrument can be put on each instrument cable signal pair.

h Multi-drop mode (digital)


In this mode, only the digital signals are used. The analog loop current is ¿xed at 4 mA. In multi-drop mode it is possible to have up to
15 instruments on one signal cable. The polling addresses of the instruments will be in the range 1 ~ 15. Each meter needs to have a
unique address.

7
1
h HART Features
HART Products

  Relatively easy to understand and use, the HART protocol provides access to the wealth of additional information (variables,
diagnostics, calibration, etc.)
  HART is a no risk solution for enhanced ¿eld communication
  Compatibility with standard 4 ~ 20 mA wiring
  Simultaneous transmission of digital data
  Risk reduction through a highly accurate and robust protocol
  Increase plant Availability
  Improve regulatory compliance

ł HART Series Selection Guide

Product Interface Description


I-7567 HART master <--> USB USB to HART master converter
HART Converters
I-7570 HART master <--> RS-232/RS485/RS422 HART to RS-232/RS-485/RS-422 converter

HART-710 HART master <--> RS-232/RS485/RS422 HART master to Modbus RTU/ASCII slave gateway
HART Gateways
GW-7557 HART master <--> PROFIBUS DP slave PROFIBUS slave to HART master gateway

I-87H17W HART master, 8 current inputs 8-ch current input HART master module
HART Modules
I-87H24W HART master, 4 current outputs 4-ch current output HART master module

7-1-1 ICP DAS CO., LTD. Professional Provider of High Quality Industrial Computer Products and Data Acquisition Systems Vol. RIO 2.0.00
Remote I/O Modules and I/O Expansion Units

ł HART Converters

USB to HART Master Converter

I-7567 CR The USB interface is comprehensive applied in PCs and notebooks. In order to touch the users' requirements more
closely, the I-7567 is presented. It is a USB to HART converter specially designed as the master device of HART
protocol. Through it, users can easily to access the HART network via USB port which is implemented as a virtual
COM port on PCs or notebooks. Because the I-7567 is powered by the USB interface, the external power is not
necessary. Moreover, the I-7567 provides the Utility tool which is helpful for diagnosing and con¿guring the HART
network. If you would like to develop a HART network, the I-7567 will be a good tool to reduce your setup costs.

Utility Features
Features   Easily transmit/receive HART command for testing
  Provide HART device diagnostic information
  Support HART Short/Long frame
  Provide module parameter con¿guration
  Support HART Burst mode
  Allow two HART masters
  Support the in point-to-point or multi-drop HART network mode
  Allow to connect with max. 15 HART modules
  Provide selectable 250 ƻ load resistor
  Compatible with USB 1.1 and 2.0 standards
  Powered by USB (external power is not necessary)
  Support ¿rmware update via USB
  Provide utility tool for module con¿guration
  Built-in watchdog
  4 kV ESD protection
  3000 VDC intra-module isolation

7
HART to RS-232/RS-485/RS-422 Converter

I-7570 CR The I-7570 is a Serial to HART converter specially designed as the master device of HART protocol. By using I-7570, 1
the HART devices, such transmitters, actuators, gauges, meters, and the current output devices, can be easily
integrated into the HMI/PLC/PC devices via serial port which may be RS-232/RS-422/RS-485 interface. In order to

HART Products
diagnose and con¿gure the HART network more easily, the I-7570 Utility tool with friendly con¿guration interface
is given. It is helpful for diagnosing and con¿guring the HART network. Through it, you can build a HART network
more easily and quickly.

Utility Features
  Easily transmit/receive HART command for testing
  Provide HART device diagnostic information
Features   Provide module parameter con¿guration

  Support HART Short/Long frame


  Support HART Burst mode
  Allow two HART masters
  Support the in point-to-point or multi-drop HART network mode
  Allow to connect with max. 15 HART modules
  Provide selectable 250 ƻ load resistor
  Isolated COM 1: 3-wire RS-232/RS-422/RS-485
  Support ¿rmware update via COM1
  Provide utility tool for module con¿guration
  Provide PWR/RUN/ERR LED indicators
  Built-in watchdog
  4 kV ESD protection
  Mountable on DIN Rail

Website: http://www.icpdas.com E-mail: [email protected] Vol. RIO 2.0.00 7-1-2


HART Introduction & Products

ł HART Gateways

HART Master to Modbus RTU/ASCII Slave Gateway PROFIBUS Slave to HART Master Gateway

HART-710 CR The HART-710 is a HART master to Modbus GW-7557 CR The GW-7557 is designed for the slave
slave gateway. It provides an economic device of PROFIBUS DP protocol. It allows
solution for Modbus master device to access the PROFIBUS master to access the HART
the HART slave devices. In order to diagnose slave devices. These HART devices may be
and configure the HART network more a transmitter, an actuator, a current output
easily, the HART-710 Utility tool with friendly device and so forth. Owing to the GW-7557,
con¿guration interface is given. you can put the HART slave devices into
PROFIBUS network very easily.

  Support HART Short/Long frame   Protocol: PROFIBUS DP-V0 slave


  Support HART Burst mode   Detect transmission rate (9.6 to 12000 kbps)
  Allow two HART masters on PROFIBUS automatically
  Support the in point-to-point or multi-drop HART network mode   240 bytes max. input data length
  Allow to connect with max. 15 HART modules   240 bytes max. output data length
  Support Modbus RTU and ASCII format   PROFIBUS address 0 ~ 126 set by DIP switch
  Modbus Function Code: 01, 02, 03, 04, 05, 06, 15 and 16   Support HART mode: point-to-point/multi-drop
  Isolated COM 1: 3-wire RS-232/RS-422/RS-485   Support 4 HART channels, each for max. 15 HART modules
  Built-in watchdog   Support HART Short/Long frame
  Mountable on DIN Rail   Network isolation protection: 2500 Vrms high speed iCoupler
  3000 VDC isolation
protection on
PROFIBUS side

7 ł HART Modules

1 8-ch Current Input HART Master Module 4-ch Current Output HART Master Module

I-87H17W CR The I-87H17W is an 8-ch HART analog I-87H24W CR The I-87H24W is a 4-ch HART analog
HART Products

input module. It can measure 4~20 mA output module. It can output 4~20 mA
current and act as a HART master, allowing current and be as a HART master, allowing
communication with HART field devices. communication with HART ¿eld devices. The
Users can measure current directly without I-87H24W supports DCON protocol defined
any external resistor. The I-87H17W adopts by ICP DAS, and can be used in WinPAC,
DCON protocol and can be used in WinPAC, ViewPAC, XPAC, LinPAC and iPAC series PAC.
ViewPAC, XPAC, LinPAC and iPAC series PAC.

  Support HART Short/Long frame   Support HART Short/Long frame


  Support HART Burst mode   Support HART Burst mode
  Allow two HART masters   Allow two HART masters
  Support the in point-to-point or multi-drop HART network mode   Support the in point-to-point or multi-drop HART network mode
  Allow to connect with max. 15 HART modules   Allow to connect with max. 15 HART modules
  Support 4 ~ 20 mA current input   Support 4 ~ 20 mA current output
  2-wire or 4-wire transmitters of HART   2-wire transmitters of HART
  Support DCON protocol   Support DCON protocol
  Open wire detection   Open wire detection
  4 kV ESD protection, and 2500 VDC intra-module isolation   4 kV ESD protection, and 2500 VDC intra-module isolation