Delta EL W Series Manual
Delta EL W Series Manual
Delta EL W Series Manual
com
Asia EMEA
China: Delta Electronics (Shanghai) Co., Ltd. EMEA Headquarters: Delta Electronics (Netherlands) B.V.
No.182 Minyu Rd., Pudong Shanghai, P.R.C. Sales: [email protected]
Post code : 201209 Marketing: [email protected]
TEL: +86-21-6872-3988 / FAX: +86-21-6872-3996 Technical Support: [email protected]
Customer Service: 400-820-9595 Customer Support: [email protected]
Service: [email protected]
Japan: Delta Electronics (Japan), Inc. TEL: +31(0)40 800 3900
Industrial Automation Sales Department
2-1-14 Shibadaimon, Minato-ku BENELUX: Delta Electronics (Netherlands) B.V.
Tokyo, Japan 105-0012 Automotive Campus 260, 5708 JZ Helmond, The Netherlands
TEL: +81-3-5733-1155 / FAX: +81-3-5733-1255 Mail: [email protected]
TEL: +31(0)40 800 3900
Korea: Delta Electronics (Korea), Inc. DACH: Delta Electronics (Netherlands) B.V.
1511, 219, Gasan Digital 1-Ro., Geumcheon-gu,
Coesterweg 45, D-59494 Soest, Germany
Seoul, 08501 South Korea
Mail: [email protected]
TEL: +82-2-515-5305 / FAX: +82-2-515-5302
TEL: +49(0)2921 987 0
Singapore: Delta Energy Systems (Singapore) Pte Ltd. France: Delta Electronics (France) S.A.
4 Kaki Bukit Avenue 1, #05-04, Singapore 417939 ZI du bois Challand 2, 15 rue des Pyrénées,
TEL: +65-6747-5155 / FAX: +65-6744-9228 Lisses, 91090 Evry Cedex, France
Mail: [email protected]
India: Delta Electronics (India) Pvt. Ltd. TEL: +33(0)1 69 77 82 60
Plot No.43, Sector 35, HSIIDC Gurgaon,
PIN 122001, Haryana, India Iberia: Delta Electronics Solutions (Spain) S.L.U
TEL: +91-124-4874900 / FAX: +91-124-4874945 Ctra. De Villaverde a Vallecas, 265 1º Dcha Ed.
Hormigueras – P.I. de Vallecas 28031 Madrid
Thailand: Delta Electronics (Thailand) PCL. TEL: +34(0)91 223 74 20
909 Soi 9, Moo 4, Bangpoo Industrial Estate (E.P.Z), Carrer Llacuna 166, 08018 Barcelona, Spain
Pattana 1 Rd., T.Phraksa, A.Muang, Mail: [email protected]
Samutprakarn 10280, Thailand Digitized Automation for a Changing World
TEL: +66-2709-2800 / FAX: +66-2709-2827 Italy: Delta Electronics (Italy) S.r.l.
Via Meda 2–22060 Novedrate(CO)
Australia: Delta Electronics (Australia) Pty Ltd.
Unit 2, Building A, 18-24 Ricketts Road,
Mount Waverley, Victoria 3149 Australia
Piazza Grazioli 18 00186 Roma Italy
Mail: [email protected]
TEL: +39 039 8900365
Delta Sensorless Vector Control
Mail: [email protected]
TEL: +61-1300-335-823 / +61-3-9543-3720
Russia: Delta Energy System LLC
Vereyskaya Plaza II, office 112 Vereyskaya str.
Compact Drive
VFD-EL-W Series
17 121357 Moscow Russia
Americas Mail: [email protected]
TEL: +7 495 644 3240
USA: Delta Electronics (Americas) Ltd.
5101 Davis Drive, Research Triangle Park, NC 27709, U.S.A. Turkey: Delta Greentech Elektronik San. Ltd. Sti. (Turkey)
TEL: +1-919-767-3813 / FAX: +1-919-767-3969 Şerifali Mah. Hendem Cad. Kule Sok. No:16-A
34775 Ümraniye – İstanbul
Brazil: Delta Electronics Brazil Ltd. Mail: [email protected]
Estrada Velha Rio-São Paulo, 5300 Eugênio de TEL: + 90 216 499 9910
Melo - São José dos Campos CEP: 12247-004 - SP - Brazil
TEL: +55-12-3932-2300 / FAX: +55-12-3932-237 MEA: Eltek Dubai (Eltek MEA DMCC)
OFFICE 2504, 25th Floor, Saba Tower 1,
Mexico: Delta Electronics International Mexico S.A. de C.V. Jumeirah Lakes Towers, Dubai, UAE
Gustavo Baz No. 309 Edificio E PB 103 Mail: [email protected]
Colonia La Loma, CP 54060 TEL: +971(0)4 2690148
Tlalnepantla, Estado de México
TEL: +52-55-3603-9200
*We reserve the right to change the information in this manual without prior notice.
DELTA_IA-MDS_VFD-EL-W_UM_EN_20230221 www.deltaww.com
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Copyright notice
©Delta Electronics, Inc. All rights reserved.
All information contained in this user manual is the exclusive property of Delta Electronics Inc.
(hereinafter referred to as "Delta ") and is protected by copyright law and all other laws. Delta retains the
exclusive rights of this user manual in accordance with the copyright law and all other laws. No parts in
this manual may be reproduced, transmitted, transcribed, translated or used in any other ways without
the prior consent of Delta.
Limitation of Liability
The contents of this user manual are only for the use of the AC motor drives manufactured by Delta.
Except as defined in special mandatory laws, Delta provides this user manual “as is” and does not offer
any kind of warranty through this user manual for using the product, either express or implied, including
but not limited to the following: (i) this product will meet your needs or expectations; (ii) the information
contained in the product is current and correct; (iii) the product does not infringe any rights of any other
person. You shall bear your own risk to use this product.
In no event shall Delta, its subsidiaries, affiliates, managers, employees, agents, partners and licensors
be liable for any direct, indirect, incidental, special, derivative or consequential damages ( including but
not limited to the damages for loss of profits, goodwill, use or other intangible losses) unless the laws
contains special mandatory provisions to the contrary.
Delta reserves the right to make changes to the user manual and the products described in the user
manual without prior notice and afterwards.
I
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Table of Contents
Introduction............................................................................................................................................. 1
1-1 Receiving and Inspection ................................................................................................................................... 3
1-2 Preparation for Installation and Wiring ............................................................................................................... 8
1-3 Dimensions....................................................................................................................................................... 11
Installation and Wiring ......................................................................................................................... 15
2-1 Wiring ............................................................................................................................................................... 17
2-2 External Wiring ................................................................................................................................................. 21
2-3 Main Circuit ...................................................................................................................................................... 22
2-4 Control Terminals ............................................................................................................................................. 25
2-5 NPN / PNP Mode ............................................................................................................................................. 28
Keypad and Start-up ............................................................................................................................ 29
3-1 Description of the Digital Keypad ..................................................................................................................... 31
3-2 Operation Method ............................................................................................................................................ 34
3-3 Trial Run ........................................................................................................................................................... 35
Parameters ............................................................................................................................................ 37
4-1 Summary of Parameter Settings ...................................................................................................................... 39
4-2 Parameter Settings for Applications ................................................................................................................. 60
4-3 Description of Parameter Settings ................................................................................................................... 64
00 User Parameters ......................................................................................................................................... 64
01 Basic Parameters ........................................................................................................................................ 71
02 Operation Method Parameters .................................................................................................................... 79
03 Output Function Parameters ....................................................................................................................... 87
04 Input Function Parameters .......................................................................................................................... 91
05 Multi-step Speed Operation ......................................................................................................................103
06 Protection Parameters ..............................................................................................................................104
07 Motor Parameters ..................................................................................................................................... 110
08 Special Parameters ................................................................................................................................... 115
09 Communication Parameters .....................................................................................................................121
10 PID Control Parameters ............................................................................................................................133
4-4 Adjustment and Application ............................................................................................................................145
Troubleshooting .................................................................................................................................159
5-1 Over-Current (oc) ...........................................................................................................................................160
5-2 Over-Voltage (ov) ...........................................................................................................................................161
5-3 Low Voltage (Lv) ............................................................................................................................................162
5-4 Overheat (oH1) ..............................................................................................................................................163
5-5 Overload (oL) .................................................................................................................................................164
5-6 Keypad Display is Abnormal ..........................................................................................................................165
5-7 Phase Loss (PHL) ..........................................................................................................................................166
5-8 Motor Does Not Run ......................................................................................................................................167
Issued Edition: 00
Firmware Version: V2.04 (Refer to Pr.00-06 on the product for the firmware version.)
Issued Date: 2023/02
Introduction
Keep the AC motor drive in the shipping carton or crate before installation. In order to retain the warranty
coverage, properly store the AC motor drive when it is not to be used for an extended period of time. The
proper storage conditions are listed below.
Store in a clean and dry location without any direct sunlight or corrosive fumes.
Store in an ambient temperature range between -20°C to +60°C.
Store in a relative humidity range between 0% to 90% and non-condensing
environment.
DO NOT store in the environment with corrosive gas or liquid.
DO NOT place directly on the ground. If the surrounding environment is humid, you
should put a desiccant in the carton or crate.
DO NOT store in an area with rapid changes in temperature that may cause
condensation or frost to form.
If the AC motor drive is stored for more than three months, the temperature should
not be higher than 30°C. Storage for longer than one year is not recommended; it
could result in the degradation of the electrolytic capacitors.
When the AC motor drive is not used for long time after installation in an
environment with humidity and dust, it is the best to move the AC motor drive to a
better environment as stated above.
Model Name
Serial Number
choose NPN/PNP
RS485 terminal
(RJ45)
output terminals
grounding terminals
Frame A2
digital keypad
input terminals
NPN/PNP
choose 选择 PNP
NPN/
control terminals
digital keypad
RS485 terminal
(RJ45)
output terminals
grounding terminals
Frame B
digital keypad
input terminals
choose 选择 PNP
NPN/
NPN/PNP
output terminals
grounding terminals
NOTE:
RFI jumper of Frame A1, A2 and B is near the input terminals (R/L1, S/L2, T/L3), as the red circle shows in the
figure above. You can remove the RFI jumper by loosening the screws.
RFI Jumper
1. The drive contains Varistors / MOVs that are connected from phase to phase and from phase to
ground to prevent the drive from unexpected stop or damage caused by main surges or voltage
spikes. Because the Varistors / MOVs from phase to ground are connected to ground with the RFI
jumper, removing the RFI jumper disables the protection.
2. In models with a built-in EMC filter, the RFI jumper connects the filer capacitors to ground to form a
return path for high frequency noise in order to isolate the noise from contaminating the main power.
Removing the RFI jumper strongly reduces the effect of the built-in EMC filter. Although a single
drive complies with international standards for leakage current, an installation with several drives
with built-in EMC filters can trigger the RCD. Removing the RFI jumper helps, but the EMC
performance of each drive is no longer guaranteed.
If you remove the RFI jumper, you remove the reliable electrical isolation. In other words, all controlled
inputs and outputs become low-voltage terminals with basic electrical isolation. Also, when you remove
the internal RFI jumper, the motor drive is no longer electromagnetic compatible (EMC).
Do not remove the RFI jumper if the main power is a grounded power system to make EMC filter
effective
You must remove the RFI jumper when conducting high voltage tests. When conducting a high
voltage test for the entire facility, disconnect the main power and the motor if the leakage current is
too high.
To prevent damage to the drive, you must remove the RFI jumper connected to ground if the AC
motor drive is installed on an ungrounded power system or a high resistance-grounded (greater
than 30 Ω) power system or a corner grounded TN system.
Step 1
Step2
Minimum Distance
Temperature °C
Installation (mm)
Model Name
Method Max.(Derating is not Max.(Derating is
A B C Note 1
required) required) Note 3
Single Drive 120 50 - 40 50
Side-by-Side
VFD007EL21W(-1) 120 50 30 40 50
Horizontal
Zero-stack Note 2 - - - - -
Single Drive 120 50 - 50 60
VFD007EL43W(-1) Side-by-Side
120 50 30 50 60
VFD015EL43W(-1) Horizontal
Zero-stack - - - - -
VFD015EL21W(-1) Single Drive 150 50 - 50 60
VFD022EL21W(-1) Side-by-Side
150 50 30 50 60
VFD022EL43W(-1) Horizontal
VFD040EL43W(-1)
Zero-stack 150 50 0 40 50
VFD055EL43W(-1)
NOTE:
1. Due to a small protruding part of the heat sink at the bottom of the Frame A1/ A2, we calculate the distance C
for the side-by-side horizontal installation according to the main part of the motor drive only.
2. Frame A1 and A2 does not support zero-stack installation, whereas Frame B supports zero-stack installation.
3. Running the drive continuously with full load by the ambient temperature listed in the “Max. (derating)” column
reduces the drive’s life span.
4. Install the drive vertically to achieve the optimal heat dissipation performance.
5. The back surface of the drive for installation must be a metal material with higher temperature endurance and
good heat dissipation.
Mount the AC motor drive vertically on a flat vertical surface with screws. Other mounting directions
are not allowed.
The AC motor drive generates heat during operation. Allow sufficient space around the unit for heat
dissipation. When you install the AC motor drive in a confined space (for example a cabinet), the
surrounding temperature must be meet specifications of operation (as shown in chapter 1.2.1) with
good ventilation. DO NOT install the AC motor drive in a space with poor ventilation.
The heat sink temperature may rise to 90°C when running. The metallic material on which the AC
motor drive is mounted must be noncombustible, be excellent at thermal dissipation and be able to
withstand this high temperature.
When installing multiple AC motor drives in the same cabinet, mount them in a row with enough
space between for ventilation. When installing one AC motor drive below another one, use a metal
separator between the AC motor drives to prevent mutual heating.
120mm 150mm
120mm 150mm
A B
120mm 150mm
Air flow
120mm 150mm
NOTE:
1. Prevent fiber particles, scraps of paper, shredded wood, sawdust, metal particles, etc. from
adhering to the heat sink.
2. Install the AC motor drive in a metal cabinet to prevent the risk of fire accident.
1-3 Dimensions
Frame A1
VFD002EL21W(-1), VFD004EL21W(-1), VFD004EL43W(-1), VFD007EL21W(-1), VFD007EL43W(-1)
See A
(mounting hole)
Unit: mm (inch)
Frame W W1 H H1 D D1 S1
92.0 82.0 162.0 152 128.7 5.4 5.4
A1
(3.62) (3.23) (6.38) (5.98) (5.07) (0.21) (0.21)
Frame A2
VFD015EL43W(-1)
See A
(mounting hole)
Unit: mm (inch)
Frame W W1 H H1 H2 D D1 S1
92.0 82.0 180.5 162.0 152 128.7 2.0 5.4
A2
(3.62) (3.23) (7.11) (6.38) (5.98) (5.07) (0.08) (0.21)
Frame B
VFD015EL21W(-1), VFD022EL21W(-1), VFD022EL43W(-1), VFD040EL43W(-1), VFD055EL43W(-1)
See A
See B
(mounting hole)
(mounting hole)
Unit: mm (inch)
Frame W W1 H H1 D D1 S1 S2
100.0 89.0 174.0 162.9 136.0 4.0 5.9 5.4
B
(3.94) (3.50) (6.86) (6.42) (5.36) (0.16) (0.23) (0.21)
2-1 Wiring
2-2 External Wiring
2-3 Main Circuit
2-4 Control Terminals
2-5 NPN / PNP Mode
After removing the covers of input/ output side terminals and control board terminals, verify the main
circuit terminals and control circuit terminals are clear. Be sure to observe the following precautions
when wiring.
Turn off the AC motor drive power before installing any wiring. A hazardous charge
may still remain in the DC bus capacitors after the power has been turned off. For
your safety, wait until the digital keypad indictor turns off and measure the DC
voltage with the voltmeter. Makes sure the voltage drops to a safe level < 25 VDC
before wiring. Performing a wiring installation while voltage remains may cause
sparks and short circuits.
Only qualified personnel familiar with AC motor drives are allowed to do the wiring.
Make sure the power is turned off before wiring to prevent electric shock.
Make sure that power is only applied to the R/L1, S/L2, and T/L3 terminals. Failure
to comply may result in damage to the equipment. The voltage and current should
be in the range on the AC motor drive nameplate.(refer to Section 1-1 Receiving
and Inspection for details)
The grounding terminals must be well-grounded to prevent electric shock or fire
accidents and to reduce noise interference.
Make sure that you correctly tighten the main circuit terminal screws to prevent
sparks that can be caused by screws loosened due to vibration.
When wiring, choose wires that comply with local regulations for your safety.
Check following items after finishing the wiring:
1. Are all connections correct?
2. Are there any loose wires?
3. Are there any short circuits between the terminals or to ground?
2-1 Wiring
There are wirings for main circuits and control circuits. You must wire according to the following wiring
diagrams.
230V One-phase
VFD002EL21W(-1), VFD004EL21W(-1), VFD007EL21W(-1), VFD015EL21W(-1),
VFD022EL21W(-1)
Fuse/NFB
(No Fuse Breaker)
Motor
L R(L1) U(T1)
N S(L2) IM
V(T2)
3~
W(T3)
E E
+24V
Run/Stop
MI1 NPN
Multi-step1
Factory MI2 Switch
Setting Multi-step2
MI3 PNP
Multi-step3 MI4
Digital signal common
DCM
RA
Multi-function contact output
E RB
Factory setting is
AVI +10V RC
3 malfunction indication
2
Switch AVI/ACI
1
ACI ACM PIN3:GND
PIN4:SG-
SG- PIN5:SG+
SG+
Main circuit (power) terminals Control circuit terminals Shielded leads & cable
Terminal SG+,SG- are joined to PIN5,PIN4 of RJ45 Connector
460V Three-phase
VFD004EL43W(-1), VFD007EL43W(-1), VFD015EL43W(-1), VFD022EL43W(-1), VFD040EL43W(-1),
VFD055EL43W(-1)
Fuse/NFB
(No Fuse Breaker)
Motor
R R(L1) U(T1)
S S(L2) IM
V(T2)
3~
T T(L3) W(T3)
E E
+24V
Run/Stop
MI1 NPN
Multi-step1
Factory MI2 Switch
Setting Multi-step2
MI3 PNP
Multi-step3 MI4
Digital signal common
DCM
RA
Multi-function contact output
E RB
Factory setting is
AVI +10V RC
3 malfunction indication
2
Switch AVI/ACI
1
ACI ACM PIN3:GND
PIN4:SG-
SG- PIN5:SG+
SG+
Main circuit (power) terminals Control circuit terminals Shielded leads & cable
Terminal SG+,SG- are joined to PIN5,PIN4 of RJ45 Connector
Separate the main circuit and control circuit wiring to prevent erroneous actions.
Use shielded wire for the control wiring and do not expose the peeled-off shield in front of
the terminal.
Use shielded wire or conduit for the power wiring and ground the two ends of the shielded
wire or conduit.
Damaged insulation of wiring may cause personal injury or damage to circuits and
equipment if it comes in contact with high voltage.
The AC motor drive, motor and wiring may cause interference. To prevent equipment
damage, take care of interference between the surrounding sensors and the equipment.
Connect the AC drive output terminals U/T1, V/T2, and W/T3 to the motor terminals U/T1,
V/T2, and W/T3, respectively. To permanently reverse the direction of motor rotation, switch
over any of the two motor leads.
With long motor cables, high capacitive switching current peaks can cause over-current,
high leakage current or lower current readout accuracy. To prevent this, the motor cable
should be less than 20 m for 4.0 kW models and below. The cable should be less than 50 m
for 5.5 kW models and above. For longer motor cables, use an AC output reactor.
The AC motor drives, electric welding machines and the larger horsepower motors should
be grounded separately.
Use ground leads that comply with local regulations and keep them as short as possible.
The VFD-EL-W series does not have a built-in brake unit,and no support for external brake
unit and brake resistor.
When grounding, choose wires that comply with local regulations for your safety.
To prevent lightning strike and electric shock, the metal grounding wire of electrical
equipment should be thick and short, and connected to the dedicated grounding terminal of
the inverter system.
You can install multiple VFD-EL-W units in one location. All the units should be grounded
directly to a common ground terminal, as shown in the figure below. Ensure that there are
no ground loops.
Good
Not allowed
Items Explanations
Please follow the specific power supply
Power supply
requirements in Appendix A.
There may be an inrush current during power-
Fuse/NFB up. Please check the chart in Appendix B and
(optional) select the correct fuse for the rated current. Use
of an NFB is optional.
Magnetic Do not use a magnetic contactor as the I/O
contactor switch for the AC motor drive, as it will reduce
(optional) the operating life of the AC drive.
Use to improve the input power factor, reduce
harmonics and provide protection from AC line
disturbances (such as surges, switching spikes,
Input AC Line
short interruptions). Install an AC line reactor
Reactor
when the power supply capacity is 500 kVA or
(optional)
more, or advanced capacity is activated. The
wiring distance should be 10m. Refer to
Appendix B for details.
No Fuse Breaker
(NFB) MC
R Motor
R(L1) U(T1)
S S(L2) IM
V(T2)
T T(L3) 3~
W(T3)
E
E
U/T1, V/T2, W/T3 Motor drive output terminals for connecting three-phase induction motor
When it is necessary to install the filter at the output side of terminals U/T1, V/T2,
W/T3 on the AC motor drive, use an inductance filter. Do not use phase-
compensation capacitors or L-C (Inductance-Capacitance) or R-C (Resistance-
Capacitance), unless approved by Delta.
DO NOT connect phase-compensation capacitors or surge absorbers at the
output terminals of AC motor drives.
Use a well-insulated motor, suitable for inverter operation.
VFD015EL21W(-1)
10 mm2
(8 AWG)
VFD022EL21W(-1)
M4 screw
10 mm2 13 kgf-cm
B VFD022EL43W(-1)
(8 AWG) (11.4 in-lbf)
2.5 mm2 (1.3 Nm)
VFD040EL43W(-1)
(14 AWG)
VFD055EL43W(-1)
NOTE:
1. For installation at an ambient temperature of 50°C, select copper wires with temperature resistance of
75°C or 90°C. For installation at an ambient temperature over 50°C, select copper wires with temperature
resistance of 90°C or above.
2. For VFD007EL21W(-1) model: when install at Ta 40°C environment, use copper wires that are temperature
resistance to 75°C or 90°C; when install at Ta 40°C above environment, use copper wires that are
temperature resistance to 90°C or above.
3. When installing VFDxxxEL21W(-1), use wires that have a voltage rating of 300 VAC or above. When
installing VFDxxxEL43W(-1), use wires that have a voltage rating of 600 VAC or above.
Terminal
Terminal Function Defaults (NPN mode) ON: Connect to DCM
Symbol
Inductive Load:
1.5 A (N.O.) / 0.5 A (N.C.) 240 VAC
RC Multi-function Relay Common
1.5 A (N.O.) / 0.5 A (N.C.) 24 VDC
Refer to Pr.03.00 for programming
+10V Potentiometer Power Supply +10 VDC 3 mA (Variable resistor 3–5 kΩ)
Analog Voltage Input
Impedance: 47 kΩ
+10V
AVI circuit
Resolution: 10 bits
Range: 0–10 VDC /4–20 mA =
AVI AVI
0–maximum output frequency (Pr.01.00)
Selection: Pr.02.00, Pr.02.09, Pr.10.00
ACM Setting: Pr.04.14–Pr.04.17
internal circuit
AVI
C
ACM
ferrite core
MI..
MI..
NPN .
.
PNP
DC 24V
SWITCH
NPN PNP NPN PNP Max:20mA
Max:20mA
NPN/Sink
+24V
+24V DC 24V
Switch-NPN DC 24V
DCM
DCM
MI..
MI..
NPN .
.
PNP
SWITCH
DC 24V NPN PNP
NPN PNP Max:20mA
Max:20mA
PNP/Source
+24V
+24V DC 24V
Switch-PNP DC 24V
DCM
DCM
NOTE:
1. The +24V-DCM internal 24V power capacity is 60 mA. For the output capacity of other external loads, the
current consumption of the corresponding number of MI terminals should be deducted (6 mA for each MI
terminal).
2. For VFD007EL21W(-1) model, if you need to install fan kit, the fan power supply is powered by +24V-DCM.
Except for the normal use of the MI terminal, do not use other external loads in the same time to prevent the
+24V terminal from being overloaded and the drive damaged.
Make sure that the wiring is correct. In particular, ensure that the output terminals
U/T1, V/T2, W/T3 are NOT connected to power and that the drive is well grounded.
Verify that no other equipment is connected to the AC motor drive.
Do NOT operate the AC motor drive with wet hands.
Please check if the digital keypad displays F60.0 or F50.0 is ON when power is
applied.
Stop the motor when a fault occurs during running and refer to Chapter 6 Fault Code
Information and Maintenance for solutions. DO NOT touch output terminals U, V, W
when power is still applied to L1/R, L2/S, L3/T, even when the AC motor drive is
stopped to prevent electric shock.
FWD command.
REV command.
Displays “End” for approximately one second (as shown in the left figure) if the
data has been accepted and automatically stored in the register.
Displays if the setting data is not accepted or data value exceeds the allowed
range.
Setting Mode
S TART
GO START
Setting parameters
or
NOTE:In the parameter setting mode, you can press MODE to return the selecting mode.
To shift data
3-1-4 Reference Table for the Seven-segment LED Display of the Digital Keypad
Digit 0 1 2 3 4 5 6 7 8 9
Led Display
English Alphabet A b Cc d E F G Hh Ii Jj
Led Display
English Alphabet K L n Oo P q r S Tt U
Led Display
English Alphabet v Y Z
Led Display
Operate through
external signals
Figure 3-2
Set MI1-DCM as Run / Stop.
MI3-DCM (Set Pr.04.05 = d10) Refer to the parameter descriptions in
MI4-DCM (Set Pr.04.06 = d11) Chapter 04 for details of FWD/REV
operations.
If the results of trial run are normal, increase the operating frequency to continue the trial run. If the trial
run still goes normally, then you can start the formal run.
Figure 3-3
Parameters
The VFD-EL-W parameters are divided into 11 groups by property for easy setting. In most applications,
users can complete all parameters settings before starting-up according to the relevant parameters
settings in the parameter group. The 11 parameter groups are as following:
00: User Parameters
01: Basic Parameters
02: Operation Method Parameters
03: Output Function Parameters
04: Input Function Parameters
05: Multi-Step Speed Parameters
06: Protection Parameters
07: Motor Parameters
08: Special Parameters
09: Communication Parameters
10: PID Control Parameters
01 Basic Parameters
You can set this parameter during operation.
Pr. Parameter Name Setting Range Default
60.00/
01.00 Max. Operation Frequency 50.00–400.0 Hz
50.00
60.00/
01.01 Motor Rated Frequency 0.10–400.0 Hz
50.00
220.0/
230V models: 0.1–255.0 V
230.0
01.02 Motor Rated Voltage
380.0/
460V models: 0.1–510.0 V
400.0
Mid-Point Frequency
01.03 0.10–400.0 Hz 1.50
Setting
230V models: 0.1–255.0 V 10.0
01.04 Mid-Point Voltage Setting
460V models: 0.1–510.0 V 20.0
Min. Output Frequency
01.05 0.10–400.0 Hz 1.50
Setting (Hz)
Min. Output Voltage 230V models: 0.1–255.0 V 10.0
01.06
Setting 460V models: 0.1–510.0 V 20.0
Output Frequency Upper
01.07 0.1–120.0% 110.0
Limit
Output Frequency Lower
01.08 0.0–100.0% 0.0
Limit
01.09 Acceleration Time 1 0.1–600.0 sec./ 0.01–600.00 sec. 10.0
01.10 Deceleration Time 1 0.1–600.0 sec./ 0.01–600.00 sec. 10.0
01.11 Acceleration Time 2 0.1–600.0 sec./ 0.01–600.00 sec. 10.0
01.12 Deceleration Time 2 0.1–600.0 sec./ 0.01–600.00 sec. 10.0
01.13 JOG Acceleration Time 0.1–600.0 sec./ 0.01–600.00 sec. 1.0
01.14 JOG Deceleration Time 0.1–600.0 sec./ 0.01–600.00 sec. 1.0
01.15 JOG Frequency Setting 0.10–400.0 Hz 6.00
0: Linear acceleration and deceleration
1: Auto-acceleration and linear deceleration
2: Linear acceleration and auto-deceleration
Auto-Acceleration / Auto-
01.16 3: Auto-acceleration and auto-deceleration (set by 0
Deceleration Setting
loads)
4: Auto-acceleration and auto-deceleration (set by
acceleration/ deceleration time setting)
S-Curve Acceleration Time
01.17 0.0–10.0 sec./ 0.00–10.00 sec. 0.0
Setting
06 Protection Parameters
You can set this parameter during operation.
Pr. Parameter Name Setting Range Default
0: Disable
Over-Voltage Stall
06.00 230V models: 330.0–410.0 V 390.0
Prevention
460V models: 660.0–820.0 V 780.0
Over-Current Stall
06.01 Prevention during 20–250% (0: Disable) 170
Acceleration
Over-Current Stall
06.02 Prevention during 20–250% (0: Disable) 170
Operation
0: No function
1: After over-torque detection during constant speed
operation, continues operation until oL1 or oL
protection activate
2: After over-torque detection during constant speed
Over-Torque Detection operation, stops and shows oL2 fault
06.03 0
Selection 3: After over-torque detection during acceleration and
constant speed operation, continues operation
until oL1 protection activates
4: After over-torque detection during acceleration and
constant speed operation, stops and shows oL2
fault
Over-Torque Detection
06.04 10–200% 150
Level
Over-Torque Detection
06.05 0.1–60.0 sec. 0.1
Time
0: Standard motor
Electronic Thermal Relay
06.06 1: Inverter Motor 2
Selection
2: Disabled
Electronic Thermal Relay
06.07 30–600 sec. 60
Action Time
06.08 Fault Record 1 0: No fault record 0
06.09 Fault Record 2 1: Over-current (oc) 0
06.10 Fault Record 3 2: Over-voltage (ov) 0
06.11 Fault Record 4 3: IGBT over-heat (oH1) 0
06.12 Fault Record 5 4: Reserved 0
06.21 Fault Record 6 5: Drive over-load (oL) 0
06.22 Fault Record 7 6: Electronics thermal relay 1 protection (oL1) 0
06.23 Fault Record 8 7: Motor overload (oL2) 0
07 Motor Parameters
You can set this parameter during operation.
Pr. Parameter Name Setting Range Default
30–120% FLA 100%
07.00 Motor Rated Current
(FLA: drive’s rated current) FLA
40%
07.01 No-Load Current for Motor 0–99% FLA
FLA
07.02 Auto-Torque Compensation 0.0–10.0 0.0
07.03 Torque Compensation Gain 0.00–10.00 0.00
0: Disabled
1: Auto-tuning R1 (motor does not run)
07.04 Motor Parameter Auto-Tuning 0
2: Auto-tuning R1 + no-load current (motor
runs)
Motor Resistance R1 (Line to
07.05 0–65535 mΩ 0
Line)
07.06 Motor Rated Slip 0.00–20.00 Hz 3.00
07.07 Slip Compensation Limit 0–250% 200
Torque Compensation Low Pass
07.08 0.01–10.00 sec. 0.10
Filter Time
Slip Compensation Low Pass
07.09 0.05–10.00 sec. 0.20
Filter Time
Accumulated Motor Operation
07.10 00–1439 min. 0
Time (Minutes)
Accumulated Motor Operation
07.11 00–65535 days 0
Time (Days)
Motor PTC Overheating 0: Disable
07.12 0
Protection 1: Enable
Motor PTC Overheating
07.13 0–9999 (unit: 2ms) 100
Protection Input Filter Time
Motor PTC Overheating
07.14 0.1–10.0 V 2.4
Protection Level
Motor PTC Overheating Warning
07.15 0.1–10.0 V 1.2
Level
Motor PTC Overheating Warning
07.16 0.1–5.0 V 0.6
Reset Level Difference
0: Warn and ramp to stop
07.17 Motor PTC Overheating Action 1: Warn and coast to stop 0
2: Warn and continue operation
08 Special Parameters
You can set this parameter during operation.
Pr. Parameter Name Setting Range Default
08.00 DC Brake Current Level 0–100% 0
08.01 DC Brake Time at Start-up 0.0–60.0 sec. 0.0
08.02 DC Brake Time at STOP 0.0–60.0 sec. 0.0
08.03 DC Brake Frequency at STOP 0.00–400.0 Hz 0.00
0: Stop operation
1: Operation continues after momentary power
loss, speed search starts with the last
08.04 Momentary Power Loss Action frequency 0
2: Operation continues after momentary power
loss, speed search starts with the minimum
frequency
Maximum Allowable Power
08.05 0.1–20.0 sec. 2.0
Loss Time
0: Disable
1: Speed search starts with the last speed before
08.06 Base Block Speed Search 1
B.B.
2: Speed search starts with the minimum speed
08.07 Speed Tracking Delay Time 0.1–5.0 sec. 0.5
08.08 Speed Tracking Action Level 30–200% 150
08.09 Skip Frequency 1 Upper Limit 0.00–400.0 Hz 0.00
08.10 Skip Frequency 1 Lower Limit 0.00–400.0 Hz 0.00
08.11 Skip Frequency 2 Upper Limit 0.00–400.0 Hz 0.00
08.12 Skip Frequency 2 Lower Limit 0.00–400.0 Hz 0.00
08.13 Skip Frequency 3 Upper Limit 0.00–400.0 Hz 0.00
08.14 Skip Frequency 3 Lower Limit 0.00–400.0 Hz 0.00
Number of Times of Restart
08.15 0–10 0
after Fault
08.16 Auto-restart Interval of Fault 0.1–6000.0 sec. 60.0
Auto-Energy Saving 0: Disable
08.17 0
Operation 1: Enable
0: Enable AVR
Automatic Voltage Regulation 1: Disable AVR
08.18 0
(AVR) Function 2: Disable AVR during deceleration
3: Disable AVR at STOP
08.19 Reserved
08.20 Oscillation Suppression 0.0–5.0 0.0
09 Communication Parameters
You can set this parameter during operation.
Pr. Parameter Name Setting Range Default
09.00 Communication Address 1–254 1
0: Baud rate 4800 bps
Communication 1: Baud rate 9600 bps
09.01 1
Transmission Speed 2: Baud rate 19200 bps
3: Baud rate 38400 bps
0: Warn and continue operation
Communication Fault 1: Warn and ramp to stop
09.02 3
Treatment 2: Warn and coast to stop
3: No treatment and no fault
Communication Time-Out 0.0: No function
09.03 0.0
Detection 0.1–120.0 sec.
0: 7, N, 2 for ASCII
1: 7, E, 1 for ASCII
2: 7, O, 1 for ASCII
3: 8, N, 2 for RTU
4: 8, E, 1 for RTU
5: 8, O, 1 for RTU
09.04 Communication Protocol 0
6: 8, N, 1 for RTU
7: 8, E, 2 for RTU
8: 8, O, 2 for RTU
9: 7, N, 1 for ASCII
10: 7, E, 2 for ASCII
11: 7, O, 2 for ASCII
09.05 Reserved
09.06 Reserved
Communication Response
09.07 0–200 (unit: 2ms) 1
Delay Time
Communication Keypad 0: PU06
09.08 0
Selection 1: PU08
Energy-Saving Operation
Save energy according to the set proportion when the AC motor drive runs at constant speed, yet has full
power during acceleration and deceleration. Applicable for vibration reduction of precision machine tools.
Applications Purpose Related Parameters
Punch press, precision machine
Save energy, reduce vibration 08.17
tools
Overheat warning
When an AC motor drive overheats, a thermal sensor triggers the overheating warning.
Applications Purpose Related Parameters
Air conditioners Safety measure Pr.03.00, Pr.04.06–04.08
Operation Command
Select the AC motor drive control by external terminals or digital keypad
Applications Purpose Related Parameters
General application Select the control signal source Pr.02.01, Pr.04.06–04.08
Frequency Hold
Hold the output frequency during acceleration and deceleration
Applications Purpose Related Parameters
General application Acceleration/ deceleration pause Pr.04.06–04.08
Over-torque Setting
Set the internal motor or mechanical over-torque detection level. When over-torque occurs, the drive
automatically adjusts the output frequency.
It is suitable for machines like fans and pumps that require continuous operation.
Applications Purpose Related Parameters
To protect machines and enhance
Pumps, fans and extruders Pr.06.00–06.05
continuous/ reliable operation
460V Models
Power (kW) 0.4 0.75 1.5 2.2 4.0 5.5
Power (HP) 0.5 1.0 2.0 3.0 5.5 7.5
Identity Code 3 5 7 9 11 13
Rated current 1.5 2.5 4.2 5.5 9.0 13
Carrier Frequency 12 kHz
In the flow control occasions such as constant pressure water pumps using PID control, set
Pr.00.03 = 3 and Pr.00.04 = 8. When the drive reboots after powered off, the start-up screen
displays 00:00 (as shown in the figure above). The displayed value on the left of “:” is the
physical quantity of PID target value; on the right of “:” shows the sensor output value (0–10V/
4–20 mA) corresponding to the actual physical quantity.
Refer to Pr.10.00 to set the target value; and Pr.10.18 to set the feedback value.
If the set and displayed target value directly correspond to physical quantities such as pressure,
temperature, flow, etc., you also need to set Pr.00.13 and Pr.00.14 at the same time.
settings, you must enter the correct password in Pr.00.08 to deactivate the password
temporarily, and this would make Pr.00.09 become 0.
NOTE:
If you set Pr.00.09 to 0, you deactivate the password protection function. There will be no
password protection when you reboot the drive. On the contrary, when Pr.00.09 is not set to 00,
the password protection is activated permanently, and is always reactivated after you reboot the
motor drive. At this time, if you want to change any of the parameter settings, you must enter the
correct password in Pr.00.08 to deactivate the password temporarily, and then you can set all
parameters.
Pr.00-07 and Pr.00-08 are used to prevent personnel from setting other parameters by accident.
Step 1: Enter the original password in Pr.00.09 again (or you can set a new password; be sure to
record it).
Step 2: Reboot the drive to enable the password protection.
Step 3: Enter any value that is not the password in Pr.00.08). (Pr.00.08 displays End regardless
of whether the password is entered correctly.)
Password Decode Flow Chart
00.11 Reserved
00.12 50 Hz Power System Base Voltage Setting
Default: 0
Settings 0: 230V/ 400V
1: 220V/ 380V
Determines the base voltage initial value when the motor drive resets with 50 Hz power system.
01 Basic Parameters
You can set this parameter during operation.
01.00 Max. Operation Frequency
Default: 60.00 / 50.00
Settings 50.00–400.00 Hz
01.01 Motor Rated Frequency
Default: 60.00 / 50.00
Setting 0.10–400.00 Hz
Set this parameter according to the rated voltage on the motor nameplate.
01.08 01.07
Output Frequency Output Frequency
Voltage Lower Limit Upper Limit
01.02
Maximum
Output
Voltage
01.04
Mid-point
Voltage
The limit of
Output
Frequency
01.06 Frequency
Minimum
Output
01.05 01.03 01.01 01.00
Mid-point Maximum Voltage Maximum
Voltage Minimum Frequency Output
Output Freq.
Freq. (Base Frequency) Frequency
V/f Curve
maximum output frequency will not be larger than 60 Hz even executing slip compensation. If
the output frequency must be larger than 60 Hz, adjust the output frequency upper limit or
increase the maximum operation frequency.
Frequency
01.00
Max. output
Frequency
setting
operation
frequency
01.05
Min. output
frequency
0 Hz
Accel. Time Decel. Time Time
01.09 01.11 01.10 01.12
The definition of
Accel./Decel. Time
Resulting Resulting
Accel. Time Decel. Time
Resulting Accel./Decel. Time
Frequency
01.15
JOG
Frequency
01.05
Min. output
frequency
0 Hz
JOG Accel. Time JOG Decel. Time
Time
01.13 01.14 01.12
The definition of JOG Accel./Decel. Time01.21
parameter is set to 4, the actual acceleration/deceleration time vary with the setting for Pr.01.09–
Pr.01.12. Therefore, the actual acceleration/ deceleration time are equal to or greater than
Pr.01.09–Pr.01.12.
Using auto-acceleration and auto-deceleration can avoid complicated adjustment procedures. It
does not stall during acceleration and does not need a brake resistor during deceleration to stop.
It can also improve operation efficiency and save energy.
1 2
3
4
1 2
3
4
1 2
3 4
Disable S curve
Enable S curve
Acceleration/deceleration Characteristics
t t x t2 nf
120
S n x p
2
(revolution/second) motor
As shown in the figure below, assume that the radius of the four-pole motor is r and rotation
speed is n (rpm).
n
Example 1:
When the motor swivel table rotates at 50 Hz, and Pr.02.02 = 4 (Simple positioning stop; E.F.:
Coast to stop), and Pr.01.26 = 50 Hz (Simple Positioning Stop Frequency 6), and its
corresponding Pr.01.34 = 2 sec. (Simple Positioning Stop Delay Time 6), then the deceleration
time from 50 Hz to 0 Hz is 10 seconds. After executing the stop command, Simple Positioning
Stop activates, its rotation speed is n = 120 x 50 / 4 (revolution / minute) = 25 (revolution/
second)
The number of revolution of the swivel table = (25 × (2 + 12)) / 2 = 175 (revolutions)
Therefore, the motor’s operation distance after executing the stop command = number of
revolutions × circumference = 175 × 2 πr. It also means that the swivel table goes back to the
top after 175 revolutions.
Example 2:
Assume that the motor swivel table rotates at 1.5 Hz, and Pr.01.22 = 10 Hz [Simple Positioning
Stop Frequency 2], and Pr.01.30 = 10 sec. [Simple Positioning Stop Delay Time 2], then the
deceleration time from 60 Hz to 0 Hz is 40 seconds.
The delay time at stop for 1.5 Hz is 1.5 second; the deceleration time from 1.5 Hz to 0 Hz is 1
second.
After executing the stop command, Simple Positioning Stop activates, its rotation speed is n =
120 × 1.5 / 4 (revolution / minute) = 1.5/2(revolution / second)
The number of revolution of the swivel table = (1.5/2 × (1.5 + 2.5)) ÷ 2 = 1.5 (revolutions)
Therefore, the motor’s operation distance after executing the stop command = number of
revolutions × circumference = 1.5 × 2 πr. It also means that the swivel table stops after running
1.5 revolutions.
Frequency Frequency
output
output
frequency
frequency
motor
motor
speed
speed
Time Time
stops according to free run to stop
operation decel eration time operation
command RUN STOP command RUN STOP
Frequency Frequency
frequency output
motor
speed
frequency
motor output
speed
stops according to
operation decel eration time free run to stop
operation
command command
EF EF
When Pr.02.02 is set to 2 or 3 When Pr.02.02 is set to 0 or 1
8kHz
From the table, you see that the PWM carrier frequency has significant influences on the
electromagnetic noise, the AC motor drive heat dissipation, and the motor acoustic noise.
Therefore, if the surrounding noise is greater than the motor noise, lower the carrier frequency to
reduce the temperature rise. Although the motor has quiet operation in the higher carrier
frequency, consider the entire wiring and interference.
With default carrier frequency:
(1) Take VFD007EL21W(-1) (need to install cooling fans) as an example, assume that the
ambient temperature is 40°C, the drive output current must be controlled within 100% of the
rated current. If the ambient temperature is 50°C, the drive output current should be within
80% of the rated current.
(2) When model VFD007EL21W(-1) works without cooling fans, assume that the ambient
temperature is 40°C, the drive output current must be controlled within 100% of the rated
current. If the ambient temperature is 50°C, the drive output current should not exceed 80%
of the rated current.
Rated current (%)
(3) Take VFD007EL21W(-1) (need to install cooling fans) as an example, assume that the
ambient temperature is 40°C and the default carrier frequency is 8 kHz, the drive output
current reaches 100% of the rated current. If the carrier frequency is 12 kHz, the drive
output current should be controlled within 80% of the rated current.
(4) When model VFD007EL21W(-1) works without cooling fans, assume that the ambient
temperature is 40°C and the default carrier frequency is 8 kHz, the drive output current
reaches 100% of the rated current. If the carrier frequency is 12 kHz, the drive output
current should be controlled within 80% of the rated current.
(5) For model VFD055EL43W, when that the ambient temperature is 50°C and the default
carrier frequency is 4 kHz, the drive output current reaches 100% of the rated current. If the
carrier frequency is 12 kHz, the drive output current should be controlled within 40% of the
rated current.
(6) When the ambient temperature is 25°C, the drive is installed independently and the carrier
frequency is 12 kHz, the drive output current reaches 100% of the rated current.
Rated current (%)
When you set Pr.02.05 = 1 or 3, it does not guarantee that the drive will never run. Be careful
when using this function because the switch may bounce due to mechanical vibration or
defective switch parts.
Pr.02.07 = 0: Use the Up/ Down keys on the digital keypad to increase or decrease the
frequency command.
Pr.02.07 = 1: The increasing or decreasing Frequency command (F) operates according to the
setting for acceleration or deceleration time, only valid during operation.
Pr.02.07 = 2: Increase and decrease the frequency command according to the setting for
Pr.02.08.
Pr.02.07 = 3: Increase and decrease the frequency command according to the setting for
Pr.02.08 (unit: pulse input). Every ON after OFF is regarded as one input pulse.
Time
run/stop ON OFF
03.01 Reserved
03.03 Reserved
03.04 Reserved
03.05 Count Value Reached
Default: 0
Settings 0–9999
Sets the count value of the internal counter. You can use the external multi-function input
terminals on the control terminals to trigger the counter. When the count reaches the setting
value, the specified output terminal activates by setting one of the multi-function input terminals
(the count value resets after reaching the setting for Pr.03.05).
NOTE:
When the display shows c555, the drive has counted 555 times. If the display shows c555•, it
means that the actual counter value is between 5,550 and 5,559.
2msec
Display
(Pr.00.04=1)
TRG
Counter Trigger
2msec
The width of trigger signal
Preliminary Count Value should not be less than
(Pr. 03.00=11) Ex:03.05=5,03.06=3 2ms(<250 Hz)
03.09 Reserved
03.10 Reserved
Frequency
Output
Case 1: Pr.03.12
Pr. 03.11
Case 2: Pr.03.12
Time
Run/Stop
Case 1: Pr.03.00=21
Case 2: Pr.03.00=21
Pr.03.00 multi-function output terminal 21: Mechanical brake control: When the output frequency
reaches Pr.03.11 (Mechanical brake release frequency), this terminal is closed (ON); when the
output frequency reaches Pr.03.12 (Mechanical brake active frequency), this terminal is OFF.
Frequency/Hz
Pr.01.00 60Hz
Max. Default:
operation Pr.01.00=60 Hz Max. operation frequency
frequency Pr.04.00=0 % Bias adjustment
Pr.04.01=0 Bias direction adjustment
Pr.04.02=100 % Gain of frequency adjustment
Pr.04.03=0 No negative bias command
0Hz
Min.(0V) Max.(5V) Potentiometer
(voltage/V)
Example 2:
If you want the corresponded minimum value to be 12 Hz when the keypad potentiometer is
turned to the minimum position (Min.), you need to adjust other frequencies manually. From the
diagram below, you can see that the correspondence between the keypad potentiometer
(voltage) and setting frequency has been changed from 0–5 V (min.–max.) / 0–60 Hz to 0–4 V /
0–60 Hz. Therefore, the 4 V and above from the keypad potentiometer all correspond to 60 Hz.
To use the full potentiometer range, refer to Example 3.
Frequency/Hz
Default:
Pr.01.00 60Hz
Pr.01.00=60 Hz Max. operation frequency
Max.
operation Pr.04.00=20 % Bias adjustment
frequency Pr.04.01=0 Bias direction adjustment
Pr.04.02=100 % Gain of frequency adjustment
Pr.04.03=0 No negative bias command
12Hz
Bias 0Hz To count the bias (See α in the formula)
adjustment Potentiometer 60-0 Hz 12-0 Hz
-1V Min.(0V) = → α= 1V
4V Max.(5V) (voltage/V) 5V αV
Bias 1V
∴ Pr.04.00 = ×100 %=20 %
5V
Example 3:
As shown in this example, the keypad potentiometer can be used for all ranges of 0–5 V / 0–60
Hz settings. This increases flexibility.
Frequency/Hz
Default:
Pr.01.00 60Hz
Pr.01.00=60 Hz Max. operation frequency
Max.
Pr.04.00=20 % Bias adjustment
operation
frequency Pr.04.01=0 Bias direction adjustment
Pr.04.02=83.3 % Gain of frequency adjustment
Pr.04.03=0 No negative bias command
10Hz
Bias To count the bias (See α in the formula)
adjustment 0Hz Potentiometer 60-10H z 10-0 Hz
= → α=1V
-1V Min.(0V) Max.(5V) (voltage/V) 5V αV
1V
Bias α ∴ 04.00 = 5V×100 %=20 %
Example 4:
This example shows how to use the first half range 0–2.5 V (min.–1/2 × max.) from the keypad
potentiometer to set 0–60 Hz frequency settings. You can achieve the same results by either
adjusting Pr.04.02 gain or setting Pr.01.00 to 120 Hz.
Frequency/Hz
Pr.01.00 60Hz Default:
Max. Pr.01.00=60 Hz Max. operation frequency
operation Pr.04.00=0.0 % Bias adjustment
frequency Pr.04.01=0 Bias direction adjustment
Pr.04.02=200 % Gain of frequency adjustment
Pr.04.03=0 No negative bias command
Example 5:
Using negative bias to set the frequency greatly reduces the noise interference. In a noisy
environment, do NOT use signals less than 1V to set the drive’s operation frequency.
Frequency/Hz
Default:
Pr.01.00 60Hz Pr.01.00=60 Hz Max. operation frequency
Max. Pr.04.00=20.0 % Bias adjustment
48Hz
operation Pr.04.01=1 Bias direction adjustment
frequency
Pr.04.02=100 % Gain of frequency adjustment
Pr.04.03=0 No negative bias command
Min.
(0V) 0Hz
Frequency 1V Max.(5V)
Potentiometer
bias 12Hz (voltage/V)
Bias
Example 6:
This example is an extension application of Example 5. In addition, it uses the gain correction to
set to the maximum operating frequency. This type of application is extremely extensive, you can
apply it flexibly.
Frequency/Hz
Default:
Pr.01.00 60Hz Pr.01.00=60 Hz Max. operation frequency
Bias
Max. Pr.04.00=20.0 % Bias adjustment
48Hz adjustment
operation
frequency Pr.04.01=1 Bias direction adjustment
Pr.04.02=125 % Gain of frequency adjustment
Pr.04.03=0 No negative bias command
To count the gain value
5V
0Hz Pr.04.02 = ×100 %=125 %
Potentiometer (5-1)V
Frequency Min. 1V Max.(5V)
(0V) (voltage/V)
bias 15Hz
Bias
Example 7:
This example is the culmination of all potentiometer applications. With the application of forward
and reverse rotation areas, it can be easily combined with the system to make various complex
applications. When this application is set, the forward and reverse commands of the external
terminals will automatically fail, pay extra attention.
Frequency/Hz Default:
Pr.01.00
Max. 60Hz Pr.01.00=60 Hz Max. operation frequency
operation Pr.04.00=50.0 % Bias adjustment
frequency FWD Pr.04.01=1 Bias direction adjustment
30Hz
Pr.04.02=200 % Gain of frequency adjustment
Pr.04.03=1 No negative bias command
Min.(0V) 0Hz
Potentiometer To count the bias (See α in the formula)
2.5V Max.(5V)
(voltage/V) 60-(-60)Hz 60-0Hz
= → α=2.5V
5V αV
2.5V
30Hz ∴ Pr.04.00 = ×100%=50%
5V
REV
To count the gain value
60Hz 5V
Pr.04.02 = ×100%=200%
[5-(2.5)]V
Example 8:
This example uses negative slope.
The rotate direction of this application cannot be changed, and the drive can only operates in a
reverse direction. Pay extra attention when using this application.
Frequency/Hz Default:
FWD
Pr.01.00=60 Hz Max. operation frequency
Min.(0V) Max.(5V) Potentiometer Pr.04.00=100 % Bias adjustment
0Hz (voltage/V)
Pr.04.01=1 Bias direction adjustment
Pr.04.02=100 % Gain of frequency adjustment
Pr.04.03=1 No negative bias command
REV
60Hz
Pr.04.04 = 0
Mode 1
Single-wire operation
Pr.04.19 = 0
control
FWD / STOP
Pr.04.04 = 0
Two-wire operation
Mode 2
control
Pr.04.19 = 1
FWD / STOP, REV /
STOP
Pr.04.04 = 1
Two-wire operation
control
RUN / STOP, REV /
Mode 2 FWD
Pr.04.19 = 1
Pr.04.04 = 2
Three-wire Operation
Control
04.05 Reserved
Acceleration /
6 deceleration speed
inhibit
You can select the acceleration and deceleration time of the drive with
this function, or from the digital status of the terminals; there are two
acceleration and deceleration selections.
The JOG operation executes when the drive stops completely. While
running, you can still change the operation direction; and the STOP key
8 JOG operation
on the keypad is valid. When the external terminal is OFF, the motor
stops in the JOG deceleration time. Refer to Pr.01.13–01.15 for details.
ON: the output of the drive stops immediately and the motor is in free
run status. When Base Block control is deactivated, the drive starts its
speed search function and synchronizes with the motor speed, and then
accelerates to the set frequency. Even if the motor has completely
stopped after the Base Block, it executes the speed tracking as soon as
the function is OFF. (NOTE: bb: Base block) (Refer to descriptions of
Pr.08.06–08.07)
External interrupt B.B.
9
input (Base Block)
ON: the frequency of the drive increases or decreases by one unit. If this
10 Digital up command function remains ON continuously, the frequency increases or decreases
according to Pr.02.07 / Pr.02.08. The Digital up command and Digital
down command are the same as the up/down key on the digital keypad,
the only difference is that they cannot be used to change parameter
11 Digital down command
settings. These two functions are only valid when the frequency
command source is digital keypad (Pr.02.00/ Pr.02.09 = 0).
ON: the current counter value is cleared and displays c0. The drive
13 Clear the counter
counts up when this function is disabled.
When the drive receives status change from the EF terminal, it stops
External Fault (EF) output immediately and shows EF on the digital keypad. The drive keeps
14
input running until the external fault is cleared after you press RESET on the
keypad (EF: External Fault). (EF: External Fault)
AC motor drive stops output and the motor coasts if one of these
16 Output stop settings is enabled. If the status of terminal is changed, AC motor drive
restarts from 0 Hz.
ON: all parameters are read as 0. Change the terminal status to OFF to
17 Parameter lock
read the parameter settings.
Second frequency ON: Pr.02.09 setting is valid. It is used to switch the first/ second
22
command source frequency command and the operation command source.
Simple positioning When the motor receives this signal while running in a forward direction,
23
FWD stop limit it stops running forward.
Simple positioning REV When the motor receives this signal while running in a reverse direction,
24
stop limit it stops running reverse.
25: Multi-pump manual/ When this function is enabled, switch to HAND or AUTO mode through
25
auto switch this terminal.
Prohibit Write
29 ON: determines whether to enable the Prohibit write EEPROM function
EEPROM Function
3 2 1 0
Weight 2 2 2 2
Bit 3 2 1 0
0=N.C. MI1
1=N.O. MI2
MI3
MI4
Start-up/ Stop Mode MI4 MI3 MI2 MI1 MI Terminal Status Setting
Terminals Occupied
Multi-function Input
Mode Pr.04.19 Pr.04.04 bit 3 bit 2 bit 1 bit 0 by the Start-up/
Terminal
Stop Function
Single-
MI4, MI3 and MI2 MI1 is only
wire
0 0 0/1 0/1 0/1 - can be set as N.O. controlled by
operation
or N.C. external terminals
control
Two-wire MI1 and MI2 are
MI4 and MI3 can be
operation 1 0 or 1 0/1 0/1 - - only controlled by
set as N.O. or N.C.
control external terminals
Three- MI1, MI2 and MI3
wire MI4 can be set as are only controlled
1 2 0/1 - - -
operation N.O. or N.C. by external
control terminals
Setting method:
When setting this parameter, covert bit3–bit0 that represent the status of MI4–MI1 from binary
to decimal.
For example: setting MI3 and MI4 to be 1 = N.C.; setting MI1 and MI2 to be 0 = N.O.
Pr.04.09 should be set to 12.
3 2 1 0
Weight 2 2 2 2 Setting value
3 2 1
Bit 1 1 0 0 =bit3× 2 +bit2× 2 +bit1× 2
0
0=N.C. MI1 +bit0× 2 =8+4+0+0=12
1=N.O. MI2
MI3
MI4
100
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
For example, if you set MI2 and MI3 to ON, Pr.04.26 displays 57 (63-2-4=57, decimal)
When setting this parameter, covert bit3–bit0 that represent the status of MI4–MI1 from binary to
decimal, and then set this parameter. Set MI3 and MI4 as internal terminals; set MI1 and MI2 as
external terminals. Pr.04.27 should be set to 12.
3 2 1 0
Weight 2 2 2 2
Bit 3 2 1 0
0=External MI1
terminal is OFF MI2
1=Internal
MI3
terminal is ON
MI4
Setting method: set Pr.04.28 to 12 to activate MI3 and MI4.
3 2 1 0
Weight 2 2 2 2 Setting value
设定值
Bit 1 1 0 0 3 2 1
=bit3× 2 +bit2× 2 +bit1× 2
0
0=External MI1 +bit0× 2 =8+4+0+0=12
terminal is OFF MI2
1=Internal MI3
terminal is ON
MI4
04.20
– Reserved
04.25
102
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
06 Protection Parameters
You can set this parameter during operation.
06.00 Over-voltage Stall Prevention
Default: 390.0 / 780.0
Settings 230V models: 330.0–410.0 V (0: Disable)
460V models: 660.0–820.0 V (0: Disable)
The default for 230V models is 390.0; the default for 460V models is 780.0.
Set Pr.06-01 to 0.0 disables the over-voltage stall prevention function (connected with braking
unit or brake resistor).
During deceleration, the DC bus voltage may exceed its Maximum Allowable Value due to motor
regeneration. When this function is enabled and the DC bus voltage detected is too high, the
drive stops decelerating (output frequency remains unchanged) until the DC bus voltage drops
below the setting value.
This parameter is suitable for uncertain load inertia. When stopping under normal load, the over-
voltage does not occur during deceleration and meet the deceleration time setting. Sometimes it
may not stop due to over-voltage during decelerating to STOP when the load regenerative
inertia increases. In this case, the AC motor drive extends the deceleration time automatically
until the drive stops. If the deceleration time affects your application, it is not recommended to
use this function. You can also install a brake resistor to absorb the excessive regenerative
voltage.
high voltage at DC side
over-voltage
detection level
time
output
frequency
Frequency Held
Deceleration characteristic
when Over-Voltage Stall
Prevention enabled
time
104
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
06.01
Over-Current output current
Detection
Level setting
frequency
Over-Current Stall
prevention during
Acceleration, Output
frequency held Frequency
time
Output
Frequency
the setting for Pr.06.05, the warning message “OL2” displays. If a multi-functional output terminal
is set to over-torque (OL2) detection (Pr.03.00), the output is ON. (Refer to Pr.03.00)
106
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
300
50Hz or more
250 10Hz
5Hz
200
150
100
50
Load
0 50 100 150 200 250 factor (%)
ID Descriptions
13 Reserved
14 Phase loss (PHL)
15 Reserved
16 Auto-acceleration/ auto-deceleration fail (cFA)
17 Software or password protection (codE)
18 Write error (CF1.0)
19 Read error (CF2.0)
20 Protection circuit error (HPF1)
21 Protection circuit error (HPF2)
22 Reserved
23 Protection circuit error (HPF4)
24 U-phase hardware error (cF3.0)
25 V-phase hardware error (cF3.1)
26 W-phase hardware error (cF3.2)
27 DC bus hardware error (cF3.3)
28 OH1 hardware error (cF3.4)
29 Reserved
30–31 Reserved
32 Analog feedback signal error (AErr)
33 Reserved
34 Motor PTC Overheating Protection (PTC1)
35 PID feedback fault (FbE)
36 PID feedback error (dEv)
37 OPHL
38-40 Reserved
108
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
07 Motor Parameters
You can set this parameter during operation.
07.00 Motor Rated Current
Default: 100%FLA
Settings 30.0–120.0% FLA
Sets this value according to the specification as indicated on the motor nameplate. Set the
default value according to the drive rated current, therefore, the default is 100% of the drive
rated current (FLA).
There will be a 0.1 error between the actual set value and the minimum value of the motor.
If the power of the drive and the motor do not match, the motor needs to be overloaded. Set
Pr.06.03, 06.04, and 06.05 motor over-torque protection related parameters.
110
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
Assume that the motor rated frequency is 60 Hz with 4 poles, and the rated motor speed is 1650
rpm. The rated slip calculated by the formula is 60 Hz – (1650 rpm × 4/ 120) = 5 Hz.
This parameter is related to Pr.07.03 Slip Compensation Gain. To get the best slip compensation
effect, you must enter the correct settings. The incorrect setting may cause invalid slip
compensation and even damage to the motor and to the AC motor drive.
Related Parameters: Pr.07.03 Torque Compensation Gain
112
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
Take the standard PTC thermistor as an example: if the protection level is 1330 Ω, the actual
voltage between +10V-ACM is 10.5 V and divider resistance R1 is 4.4k Ω.
resistor value(Ω)
1330
550
Tr temperature(℃)
Tr-5℃ Tr+5℃
Refer to the following calculation when Pr.07.14 is set to 2.4 and motor temperature
overheating protection level is 1330 Ω:
1330//47000 = (1330 × 47000) ÷ (1330 + 47000) = 1293.4
10.5 × 1293.4 ÷ (4400 + 1293.4) = 2.38 (V) ≒ 2.4 (V)
114
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
08 Special Parameters
You can set this parameter during operation.
08.00 DC Brake Current Level
Default: 0
Settings 0–100%
Sets the level of the DC brake current output to the motor at start-up and stop. When setting the
DC brake current, the rated current is 100%. Therefore, when you set this parameter, increase
the level slowly to reach the desired holding torque. The set value cannot exceed the motor
rated current.
Use the DC brake before running the motor when the load is movable at stop, such as with fans
and pumps. The motor is in free running status and in unknown rotation direction before the
drive starts up. Execute the DC brake before you start the motor.
Use the DC Brake at STOP when you need to brake the motor quickly or to control the
positioning. Such as cranes or cutting machines.
Time
FWD Run
B.B.
Fig 1:B.B. Speed Search with Last Output Frequency Downward Timing Chart
(Speed Search Current Attains Speed Search Level)
116
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
Output frequency
(H) Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
08.08 Current Limit A Speed Search
for Speed SearchSpeed
Synchronization speed detection
Time
FWD Run
B.B.
Fig 2: B.B. Speed Search with Last Output Frequency Downward Timing Chart
(Speed Search Current doesn't Attain Speed Search Level)
B.B.
Fig3: B.B. Speed Search with Minimum Output Frequency Upward Timing Chart
08.09
08.10
08.11
08.12
08.13
08.14
0
setting frequency
118
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
08.19 Reserved
120
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
09 Communication Parameters
6: 8, N, 1 for RTU
7: 8, E, 2 for RTU
8: 8, O, 2 for RTU
9: 7, N, 1 for ASCII
10: 7, E, 2 for ASCII
11: 7, O, 2 for ASCII
Computer Link: When using the RS-485 serial communication interface, you must specify each
drive’s communication address in Pr.09.00. The computer then implements control using the
drives’ individual addresses.
The VFD-EL-W series drive uses Modbus networks communication protocol. The Modbus uses
one of the following two modes: ASCII (American Standard Code for Information Interchange) or
RTU (Remote Terminal Unit). The ASCII mode transfers the data into corresponded ASCII code
before transmission; meanwhile, the RTU directly transmits the data without translation. The
followings are descriptions for ASCII mode:
The CPU delays about 1 second when using the communication reset; therefore, there is at
least 1 second delay time in the master station.
Each 8-bit data is the combination of two ASCII characters. For example, one byte of data: 64
Hex, shown as ‘64’ in ASCII, consists of ‘6’ (36Hex) and ‘4’ (34Hex). The following table is the
ASCII characters:
Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’
ASCII code 30H 31H 32H 33H 34H 35H 36H 37H
7-data bits
10-bits character frame
(7, E, 1)
122
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
(7, O, 1)
(7, N, 1)
Start Stop
bit 0 1 2 3 4 5 6
bit
7-data bits
9-bits character frame
(7, E, 2)
(7, O, 2)
For RTU
(8, N, 2)
(8, E, 1)
Start Even Stop
bit 0 1 2 3 4 5 6 7
parity bit
8-data bits
11-bits character frame
(8, O, 1)
Start Odd Stop
bit 0 1 2 3 4 5 6 7
parity bit
8-data bits
11-bits character frame
(8, N, 1)
Start Stop
bit 0 1 2 3 4 5 6 7
bit
8-data bits
10-bits character frame
(8, E, 2)
(8, O, 2)
Communication Protocol
3.1 Communication Data Frame
ASCII mode:
STX Start character = ‘ : ’ (3AH)
Address High Communication address:
Address Low one 8-bit address consists of 2 ASCII codes
Function High Command code:
Function Low one 8-bit command consists of 2 ASCII codes
DATA (n-1) Contents of data:
……. n x 8-bit data consists of 2n ASCII codes
DATA 0 n ≤ 20, maximum of 40 ASCII codes (20 sets of data)
LRC Check High LRC checksum:
LRC Check Low one 8-bit checksum consists of 2 ASCII codes
END High End characters:
END Low END High = CR (0DH), END Low = LF (0AH)
RTU mode:
START A silent interval of more than 10 ms
Address Communication address: 8-bit binary address
Function Command code: 8-bit binary command
DATA (n-1)
Contents of data:
…….
n×8-bit data, n ≤ 40 (20 x 16-bit data).
DATA 0
LRC Check Low CRC checksum:
LRC Check High one 16-bit CRC checksum consists of 2 8-bit binary characters
END A silent interval of more than 10 ms
124
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
RTU mode:
Command Message Response Message
Address 01H Address 01H
Function 03H Function 03H
21H Number of data
Starting data address 04H
(count by byte)
Function code 06H: write single register (can write up to 20 data to the register at the same
time)
Example: Writing data 6000 (1770H) to register 0100H. AMD address is 01H.
ASCII mode:
Command Message Response Message
STX ‘:’ STX ‘:’
‘0’ ‘0’
Address Address
‘1’ ‘1’
‘0’ ‘0’
Function Function
‘6’ ‘6’
‘0’ ‘0’
‘1’ ‘1’
Data address Data address
‘0’ ‘0’
‘0’ ‘0’
‘1’ ‘1’
‘7’ ‘7’
Data content Data content
‘7’ ‘7’
‘0’ ‘0’
‘7’ ‘7’
LRC Check LRC Check
‘1’ ‘1’
CR CR
END END
LF LF
RTU mode:
Command Message Response Message
ADR 01H ADR 01H
CMD 08H CMD 08H
00H 00H
Data Data
00H 00H
17H 17H
Data Data
70H 70H
LRC Check Low 8EH LRC Check Low 8EH
LRC Check High 0EH LRC Check High 0EH
126
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
The following is an example of CRC generation using C language. The function takes two
arguments:
Unsigned char* data a pointer to the message buffer
Unsigned char length the quantity of bytes in the message buffer
The function returns the CRC value as a type of unsigned integer. Unsigned int
crc_chk(unsigned char* data, unsigned char length)
{
int j;
unsigned int reg_crc=0xffff;
while(length--){
reg_crc ^= *data++;
for(j=0;j<8;j++){
if(reg_crc & 0x01){ /* LSB(b0)=1 */
reg_crc=(reg_crc>>1) ^ 0xa001;
}else{
reg_crc=reg_crc >>1;
}
}
}
return reg_crc; // return register CRC
Address list
Content Parameter Function
address
AC motor drive GGnnH GG is the parameter group, nn is the parameter number. For
parameters example, the address of Pr.04-10 is 0401H.
Command write only 2000H bit0–1 00B: No function
01B: Stop
10B: Run
11B: JOG + RUN
bit2–3 Reserved
bit4–5 00B: No function
01B: FWD
10B: Direction reverse
11B: Change direction
bit6–7 00B: 1st step accel./decel.
01B: 2nd step accel./decel.
bit8–15 Reserved
2001H Frequency command
2002H bit0 1: EF ON
bit1 1: Reset command
bit2 1: Base Block (B.B) ON
bit3–4
Reserved
bit6–15
00B: No function
Enable Fire Mode bit5
01B: Start Fire Mode (without RUN command)
Status monitor read 2100H Error code
only
0: No fault record
1: Over-current (oc)
2: Over-voltage (ov)
3: IGBT overheat (OH1)
4: Reserved
5: Drive Over load (oL)
6: Motor over load (oL1)
7: Over-torque (oL2)
8: External fault (EF)
9: Over-current during acceleration (ocA)
10: Over-current during deceleration (ocd)
11: Over-current at constant speed (ocn)
12: Reserved
13: Low voltage (Lv)
14: Input phase loss (PHL)
128
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
Exception response:
When the drive is using the communication connection, if an error occurs, the drive responds to
the error code and sets the highest bit (bit 7) of the command code to 1 (function code AND
80H) then responds to the control system to signal that an error occurred. If the keypad
displays “CEXX” as a warning message, “XX” is the error code at that time. Refer to the table of
error codes for communication error for reference.
The following table shows some examples:
ASCII mode: RTU mode:
STX ‘:’ Address 01H
‘0’ Function 86H
Address
‘1’ Exception code 02H
‘8’ LRC Check Low C3H
Function
‘6’ LRC Check High A1H
‘0’
Exception code
‘2’
‘7’
LRC Check
‘7’
CR
END
LF
130
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
<7,E,1>=1AH
<7,O,1>=0AH,
<8,N,2>=07H,
<8,E,1>=1BH
<8,O,1>=0BH,
*/
for(i=0;i<=16;i++){
while(!(inportb(PORT+LSR) & 0x20)); /* wait until THR empty */
outportb(PORT+THR,tdat[i]); /* send data to THR */ }
i=0;
while(!kbhit()){
if(inportb(PORT+LSR) & 0x01){ /* b0==1,read data ready */
rdat[i++]=inportb(PORT+RDR); /* read data form RDR */
} } }
09.05 Reserved
09.06 Reserved
132
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
134
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
to improve the system state. Using a suitable differential time can reduce overshoot and shorten
adjustment time; however, the differential operation increases noise interference. Note that a too
large differential causes more noise interference. In addition, the differential shows the change
and the differential output is 0 when there is no change. Note that you cannot use the differential
control independently. You must use it with the other two controllers for the PD controller or PID
controller.
Sets the D controller gain to determine the deviation change response. Using a suitable
differential time reduces the P and I controllers overshoot to decrease the oscillation for a stable
system. A differential time that is too long may cause system oscillation.
The differential controller acts on the change in the deviation and cannot reduce the
interference. Do not use this function when there is significant interference.
Integral + Output
Setpoint
+ P I gain
limit
+ Freq.
Limit
Digital
filter Freq.
Command
- 10.02 10.03 10.05 + 10.07 10.06
D
10.04
Input Freq. PID
Gain feedback
10.10 10.01
136
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
When the PID function is enabled and the sleep mode is disabled:
If Pr.01.08 > Pr.01.05, the lower limit of the drive output frequency H is limited by Pr.01.08.
If Pr.01.08 ≤ Pr.01.05, the lower limit of the drive output frequency H is limited by Pr.01.05.
When it reaches Pr.01.05, the drive stops output and is in ready status.
Integral + Output
Setpoint
+ P I gain
limit
+ Freq.
Limit
Digital
filter Freq.
Command
- 10.02 10.03 10.05 + 10.07 10.06
D
10.04
Input Freq. PID
Gain feedback
10.10 10.01
138
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
Parallel connection
P
10.02
In teg ra l + O utp ut
Setpoint
+ I g ai n
l imi t
+ Fr eq .
L imi t
Di gi tal
fi lte r Fr eq .
Co mman d
- 10.03 10.05 + 10.07 10.06
D
10.04
In pu t Fre q. P ID
G ai n fe ed ba ck
10.10 10.01
set point
10.25
feedbac k v al ue
10.26
Example:
If the set point of constant pressure control of a pump is 4 kg, Pr.10.22 is set to 5%, Pr.10.23 is
set to 15 seconds, Pr.10.24 is set to 25%, Pr.10.25 is set to 3% and Pr.10.26 is set to 0.5
140
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
seconds, then the deviation is 0.2 kg (4 kg × 5% = 0.2 kg). It means when the feedback value is
higher than 3.8 kg for a time exceeding 15 seconds, the AC motor drive decelerates to stop, this
deceleration time acts according to Pr.01.12.
Case 1: Assume that when the AC motor drive does not run and is in a constant pressure status,
the variation of the feedback value is less than 0.12 kg (4 kg × 3% = 0.12 kg) within 0.5 second.
When the feedback value continues to decrease to make the deviation of the set point be less
than 1 kg (4 kg × 25% = 1 kg), that is, when the feedback value is less than 3 kg, the AC motor
drive starts to run.
Case 2: When the AC motor drive is in constant pressure status, it does not operate until the
feedback change value exceeds 0.12 bar within 0.5 seconds, which means the AC motor drive
starts operating when the feedback value is less than 3.88 bar within 0.5 seconds.
10.27 Reserved
10.28 Reserved
10.29 Reserved
10.30 Reserved
10.31 Reserved
10.32 Reserved
10.33 Reserved
10.36 Multi-Pump ID
Default: 0
Settings 0–4
0: Disable multi-pump function
1: Master
2–4: Slave
When using the multi-pump control mode, the settings of each pump for Pr.10.36 cannot be the
same.
Fixed quantity control (multi-pump operating at constant pressure): Assume that when the
master pump’s operating time is longer than the setting for Pr.10.37, the master pump and the
slave pump switch alternatively.
This parameter is only valid for master pump settings.
142
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
bit 0: When the operating pump is failed, whether it switches to an alternative pump or not
0: Stop all pump action
1: Switch to an alternative pump
Example: bit0 = 0, when an error occurs to the running pump, all pumps stop.
bit0 = 1, when an error occurs to the running pump, switch the erroneous pump to an
alternative one.
bit 1: During the operation, stop or standby after resetting from error
0: Set the erroneous pump to be in a standby status after reset (the pump receives the RUN
command)
1: Set the erroneous pump to be in a stop status after reset (the pump does not receive the
RUN command).
Example: bit1 = 0, after you reset the erroneous pump, it can be set running through the
controller
bit1 = 1, after you reset the erroneous pump, it cannot be set running through the controller
until the master pump gives a STOP command.
bit 2: Whether the master pump receives the RUN command or not when the pump has an error
0: The master pump does not receive RUN command when an error occurs to the running
pump
1: The master pump can choose an alternative pump to run when an error occurs to the
running pump
Example: bit 2 = 0: when an error occurs to Pump #2, the master pump does not accept the
RUN command.
bit 2 = 1: when an error occurs to Pump #2, the master pump receives the RUN command
and chooses to run with an alternative pump.
This parameter is only valid in AUTO mode.
10.46
– Reserved
10.48
144
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
Related parameters for PID set point and feedback value corresponds to the physical quantity
00.03 Start-up Display
Default: 0
Settings 0: F (frequency command)
1: H (output frequency)
2: A (output current)
3: U (user-defined)
4: FWD/REV command
Determines the start-up display page after power is applied to the drive.
Gets into the self-check state first when the drive starts-up, after displays “Pon” and flashes for 5
sec., the drive turns to start-up page.
146
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
In the flow control occasions such as constant pressure water pumps using PID control, set
Pr.00.03 = 3 and Pr.00.04 = 8. When the drive reboots after powered off, the start-up screen
displays 00:00 (as shown in the figure above). The displayed value on the left of “:” is the
physical quantity of PID target value; on the right of “:” shows the sensor output value (0–10V/
4–20 mA) corresponding to the actual physical quantity.
Refer to Pr.10.00 to set the target value; and Pr.10.18 to set the feedback value.
If the set and displayed target value directly correspond to physical quantities such as pressure,
temperature, flow, etc., you also need to set Pr.00.13 and Pr.00.14 at the same time.
temperature, flow, etc., you also need to set Pr.00.13 and Pr.00.14 at the same time. For
example, when the maximum range of the set point set as 16.0 bar, you also need to set
Pr.00.13 = 160, 00.14 = 1.
The target physical quantity corresponding to the frequency set by Pr.10.11 = (Pr.10.11/
Pr.01.00) × Pr.00.13 × 10-(Pr.00.14). For example, Pr.10.11 = 20 Hz, Pr.01.00 = 50 Hz, Pr.00.13 =
160, Pr.00.14 = 1, then the target physical quantity = 20 / 50 × 160 × 0.1 = 8.0.
The following table shows the set point physical quantity and the operating frequency of the
drive, sensor feedback value correspond to the physical quantity, set point setting method and
relationship.
Corresponded
Sensor Feedback Value
Corresponded Set Point Drive
Corresponding to the PID Set Point
Relation Physical Quantity Operation
Physical Quantity
Frequency
Pr.10.00 = 1
Parameter Pr.00.13 = 160 Pr.00.02 = 9 Pr.10.00 = 4
Pr.10.18 = 16.0 Keypad up/down
Setting Pr.00.14 = 1 Pr.01.00 = 50 Pr.10.11 = 50
keys
Lower Limit 0 0 0 0 0
Upper Limit 16.0 50 16.0 16.0 16.0
148
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
For example, the pressure sensor range is 0–16.0 bar, and the corresponding output range
is 4–20 mA. When the Pr.10.18 is set to 16.0 and the sensor's actual measurement output
is 12 mA, the actual feedback physical quantity = (12 - 4) ÷ (20 - 4) × 16.0 = 8.0 bar, the
corresponding relationship is shown in the table below.
Set Pr.00.03 = 3 and Pr.00.04 = 8 to display the actual feedback physical quantity on the digital
keypad. And the physical quantity correspond to the feedback value displayed on the right side
of ":". Refer to Pr.00.04 description for more details.
Corresponded Feedback Value
Sensor Feedback Value
Relation Corresponds to the Physical
Parameter ACI AVI Quantity
Setting Pr.10.01 =- 2 or 3 Pr.10.01 =- 0 or 1 Pr.10.18 = 16.0
Lower Limit 4 mA 0V 0 bar
Medium value 12 mA 5V 8.0 bar
Upper Limit 20 mA 10V 16.0 bar
150
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
User's User’s
Pr. Function Setting Range Default Note
Master Slave
Max. Operation
01.00 50.00–400.0 Hz 60.00 60.00 60.00
Frequency Set the parameters
Motor Rated according to the
01.01 0.10–400.0 Hz 60.00 60.00 60.00
Frequency specifications of
Motor Rated 230V models: 0.1–255.0 V 220.0 220.0 220.0 pumps.
01.02
Voltage 460V models: 0.1–510.0 V 400.0 400.0 400.0
Acceleration Time Adjust the parameter
01.09 0.1–600.0 sec./ 0.01–600.00 sec. 10.0 0.5 0.5
1 according to
Deceleration Time customer’s
01.10 0.1–600.0 sec./ 0.01–600.00 sec. 10.0 5.0 5.0
1 applications
The time for the drive
decelerating to stop
Deceleration Time
01.12 0.1–600.0 sec./ 0.01–600.00 sec. 10.0 3.0 3.0 when the pressure
2
reaches the setting
value.
0: Digital keypad
1: External terminal AVI analog
signal DC 0–10V Adjust the parameter
First Master
2: External terminal ACI analog according to
02.00 Frequency 0 2 2
signal DC 4–20 mA customer’s
Command Source
3: RS-485 communication input applications
4: Digital keypad potentiometer
knob
0: Digital keypad
1: External terminals, STOP key is
valid
Adjust the parameter
2: External terminals, STOP key is
Operation according to
02.01 invalid 0 0 0
Command Source customer’s
3: RS-485 communication, STOP
applications
key is valid
4: RS-485 communication, STOP
key is invalid
0: Disable
1: Fixed time circulation
Multi-Pump (alternative operation)
10.35 0 1 1
Operation Mode 2: Fixed quantity control (multi-
pump operating at constant
pressure)
0: Disable multi-pump function
10.36 Multi-Pump ID 1: Master 0 1 2
2–4: Slave
Multi-Pump Fixed
10.37 Time Circulation 1–65535 min. 60 1 1
Period
Pump’s Frequency
10.42 at Time-Out 0.0–Fmax 0.00 60 60
(Disconnection)
Pump Fault
Treatment
bit 0: When the
0: Stop all pump action
operating pump is
1: Switch to an alternative pump
failed, whether it 000 = 0
switches to an 001 = 1
alternative pump 010 = 2
or not 011 = 3
10.43 1 1 1
bit 1: During the 100 = 4
operation, stop or 101 = 5
0: Standby after resetting
standby after 110 = 6
1: Stop after resetting
resetting from 111 = 7
error
bit2 Whether the 0: 0: The system cannot activate
system can run or 1: The system selects another
not when the pump to operate
User's User’s
Pr. Function Setting Range Default Note
Master Slave
pump has an error
152
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
User's User’s
Pr. Function Setting Range Default Note
Master Slave
motor drive starts to
decelerate to stop.
The deceleration time
is according to the
Deceleration Time 2
set in Pr.01.12. When
the feedback value is
less than 2.85 kg, the
drive starts to run.
Deviation Level of Liquid Leakage:
10.24 0–50% 0 33 33
Liquid Leakage Assume that when
Liquid Leakage 0: Disable the drive does not run
10.25 0 4 4
Change Detection 0–100% and is in a constant
pressure status, the
variation of the
feedback value is
less than 0.12 kg (3
kg × 4% = 0.12 kg)
within 2 second.
When the feedback
value continues to
decrease to make the
deviation of the set
point be less than
0.99 kg (3 kg × 33%
Liquid Leakage = 0.99 kg), that is,
0: Disable
10.26 Change Detection 0.5 2 2 when the feedback
0.1–10.0 sec.
Time value is less than
2.01 kg, the drive
starts to run.
Liquid Usage after
Liquid Leakage:
When the drive does
not run and is in a
constant pressure
status, the variation
of the feedback value
is higher than 0.12 kg
within 2 seconds, the
drive starts to run.
154
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
User's User’s
Pr. Function Setting Range Default Note
Master Slave
0: Digital keypad
1: External terminals, STOP key
is valid
2: External terminals, STOP key Adjust the parameter
Operation
02.01 is invalid 0 0 0 according to customer’s
Command Source
3: RS-485 communication, STOP applications
key is valid
4: RS-485 communication, STOP
key is invalid
0: Disable
1: Fixed time circulation
Multi-Pump (alternative operation)
10.35 0 2 2
Operation Mode 2: Fixed quantity control (multi-
pump operating at constant
pressure)
0: Disable multi-pump function
10.36 Multi-Pump ID 1: Master 0 1 2
2–4: Slave
Multi-Pump Fixed
10.37 Time Circulation 1–65535 min. 60 1 1
Period
Pump’s Frequency
10.42 at Time-Out 0.0–Fmax 0.00 60 60
(Disconnection)
Pump Fault
Treatment
bit 0: When the
0: Stop all pump action
operating pump is 000 = 0
1: Switch to an alternative pump
failed, whether it 001 = 1
switches to an 010 = 2
alternative pump or 011 = 3
not 100 = 4 (bit2: 1, bit1:
10.43 1 1 1
bit 1: During the 0, bit0: 0)
operation, stop or 0: Standby after resetting 101 = 5
standby after 1: Stop after resetting 110 = 6
resetting from error 111 = 7
bit2 Whether the (bit 2 <-- bit 1 <-- bit 0)
0: The system cannot activate
system can run or
1: The system selects another
not when the pump
pump to operate
has an error
Pump Start-Up Adjust the parameter
0: By pump ID
10.44 Sequence 0 1 1 according to customer’s
1: According to the operating time
Selection applications
Pump Alternative Adjust the parameter
10.45 Operation Time 0.0–360.0 sec. 60.0 60.0 60.0 according to customer’s
Setting applications
0: PID function disabled
1: Digital keypad
Adjust the parameter
PID Set Point 2: Reserved
10.00 0 1 1 according to customer’s
Selection 3: Reserved
applications
4: PID reference target value
(Pr.10.11)
0: Positive PID feedback from
external terminal AVI (0–10
VDC)
1: Negative PID feedback from
external terminal AVI (0–10
Input Terminal for
10.01 VDC) 0 3 3
PID Feedback
2: Positive PID feedback from
external terminal ACI (4–20
mA)
3: Negative PID feedback from
external terminal ACI (4–20
User's User’s
Pr. Function Setting Range Default Note
Master Slave
mA)
Proportional Gain
10.02 0.0–10.0 1.0 1.2 1.2
(P) Adjust the parameter
10.03 Integral Time (I) 0.00–100.0 sec. 1.00 0.7 0.7 according to customer’s
Differential Time applications
10.04 0.00–1.00 sec. 0.00 - -
(D)
PID Feedback
10.12 Signal Error 1.0–50.0% 10.0 5 5
When the pressure
Deviation Level
feedback is < 0.5 kg and
PID Feedback
time > 15 sec., follow the
Signal Error
10.13 0.1–300.0 sec. 5.0 15 15 settings for Pr.10.20.
Deviation Detection
Time
Sets the maximum
PID Feedback feedback of PID physical
10.18 1.0–99.9 99.9 10 10
Physical Quantity quantity value to be 10
kg.
The parallel PID
PID Calculation 0: Serial connection calculation mode applies
10.19 0 1 1
Mode Selection 1: Parallel connection for the constant pressure
water supply control.
0: Warn and continue operation When there is water
(no treatment) shortage or unusual
PID Error Deviation 1: Coast to stop pressure feedback, the
10.20 0 3 3
Treatment 2: Ramp to stop pump stops running for
3: Ramp to stop and restart after 1800 sec. (30 minutes)
Pr.10.21 delay time until the pressure
PID Error Deviation feedback is back to
10.21 1–9999 sec. 60 1800 1800
Restart Delay Time normal.
Set Point Deviation If the feedback value
10.22 0–100% 0 5 5
Level and the set point
deviation are both is
0.15 kg (3 kg × 5% =
0.15 kg), that is, when
feedback value is ≥ 2.85
kg and time > 10
seconds, the AC motor
Set Point Stop drive starts to decelerate
10.23 1–9999 sec. 10 10 10
Detection Time to stop. The deceleration
time is according to the
Deceleration Time 2 set
in Pr.01.12. When the
feedback value is less
than 2.85 kg, the drive
starts to run.
Deviation Level of Liquid Leakage:
10.24 0–50% 0 33 33
Liquid Leakage Assume that when the
Liquid Leakage 0: Disable drive does not run and is
10.25 0 4 4
Change Detection 0–100% in a constant pressure
status, the variation of
the feedback value is
less than 0.12 kg (3 kg ×
4% = 0.12 kg) within 2
second. When the
feedback value
Liquid Leakage
0: Disable continues to decrease to
10.26 Change Detection 0.5 2 2
0.1–10.0 sec. make the deviation of
Time
the set point be less
than 0.99 kg (3 kg ×
33% = 0.99 kg), that is,
when the feedback value
is less than 2.01 kg, the
drive starts to run.
156
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 4 Parameters|VFD-EL-W
User's User’s
Pr. Function Setting Range Default Note
Master Slave
Liquid Usage after Liquid
Leakage:
When the drive does not
run and is in a constant
pressure status, the
variation of the feedback
value is higher than 0.12
kg within 2 seconds, the
drive starts to run.
RMKE-HUB01 VFD-CMD04
RS-485 RJ11 Four-port communication
RS-485 One-wire to Two-wire
breakout box
158
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 5 Troubleshooting VFD-EL-W
Troubleshooting
160
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 5 Troubleshooting VFD-EL-W
162
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 5 Troubleshooting VFD-EL-W
164
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 5 Troubleshooting VFD-EL-W
166
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 5 Troubleshooting VFD-EL-W
168
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 5 Troubleshooting VFD-EL-W
170
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 5 Troubleshooting VFD-EL-W
172
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 5 Troubleshooting VFD-EL-W
serial reactor
174
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 6 Fault Code Information and MaintenanceVFD-EL-W
The AC motor drive has various warnings and protections against errors such as over-voltage, low
voltage, or over-current. Once an error occurs, the protections activate, the AC motor drive stops output,
activates the error contacts, and the motor coasts to stop. Please refer to the error display from the AC
motor drive and look up the corresponding causes and solutions. The fault record is stored in the AC
motor drive internal memory and can store the five most recent error messages. You can read it from the
digital keypad or through the communications by accessing the parameters.
The AC motor drive includes a large number of electronic components, including ICs, resistors,
capacitors, transistors, and cooling fans. These components do not last forever. Even under normal
circumstances, they will eventually become error-prone if used past their lifespans. Therefore, you must
perform periodic preventive maintenance to identify defective and worn out parts, and eliminate the
causes of malfunctions in the AC motor drive at an early stage. At the same time, parts that have
exceeded their product life should be replaced whenever possible to ensure safe operation.
Visual checks should be done regularly to monitor the AC motor drive's operation, and to make sure
nothing unusual happens. Check the situations listed in the following table.
Wait five seconds after a fault has been cleared before pressing RESET with the
input terminal keypad.
The drive must first be switched off for at least five minutes for ≤ 22 kW models
until the charging indicator turns off before it is safe to open the cover to begin
maintenance operations.
Only qualified personnel can work on maintenance or replace parts. (Remove
metal items such as watch, rings, and other metal items before operation, and use
only insulated tools.)
Never modify internal components or wiring.
The performance and the surrounding environment should meet the standard
specifications. There should be no abnormal noise, vibration, or odor.
Verify if the keypad displays normally. Check if there is any abnormality such as
overheating or color change. Prevent the drive from electronic shock and
equipment accident.
176
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 6 Fault Code Information and MaintenanceVFD-EL-W
OV hardware fault
OC hardware fault
178
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 6 Fault Code Information and MaintenanceVFD-EL-W
Wiring detection fault U-phase error, return the unit to the factory.
Wiring detection fault V-phase error, return the unit to the factory.
Wiring detection fault W-phase error, return the unit to the factory.
Wiring detection fault DC bus wiring detection error, return the unit to the factory.
Wiring detection fault Temperature sensor error, return the unit to the factory.
Reset
Press the “RESET” key (as shown in the figure below) to reset the external terminal after the fault is
cleared, and set this terminal to be ON or send the Reset command through communication, then the
trip is cleared. Make sure the RUN command or signal is OFF before executing RESET to prevent
damage to the drive or personal injury due to immediate operation after reset.
180
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 6 Fault Code Information and MaintenanceVFD-EL-W
Ambient environment
Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check the ambient temperature, Visual inspection and measurement
humidity, vibration and for any dust, with equipment with standard
gas, oil or water drops. specifications
Check for any dangerous objects in
Visual inspection
the environment.
Voltage
Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check if the voltages of the main Measure with multi-meter with
circuit and control circuit are correct. standard specifications.
Mechanical parts
Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check for any abnormal sounds or
Visual and auditory inspection
vibrations.
Check for any loose screws. Tighten the screws
Check for deformed or damaged
Visual inspection
parts.
Check for any color change due to
Visual inspection
overheating.
Check for any dust or dirt. Visual inspection
Main circuit
Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check for any loose or missing
Tighten or replace the screws.
screws.
Check for any deformed, cracked, or
damaged machinery or insulation and
Visual inspection
for any color change due to
overheating or ageing.
Check for any dust or dirt. Visual inspection
182
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Chapter 6 Fault Code Information and MaintenanceVFD-EL-W
184
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Appendix A SpecificationsVFD-EL-W
Appendix A. Specifications
The VFD-EL-W Series include the 230V and 460V models. The 230V model is one-phase; the 460V
model is three-phase. Refer to following specifications for details.
NOTE:
1. VFD-EL-W has two types of packaging: Individual Package [suffixed with (-1) at the end of the
model name] and 12 pcs/ carton.
2. The electrical specifications are the same for either packaging.
186
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Appendix A SpecificationsVFD-EL-W
Rated Output Current (A) 1.5 2.5 4.2 5.5 9.0 13.0
Maximum Output Voltage (V) Three-phase Proportional to Input Voltage
Output Frequency (Hz) 0.1–400
2–12 2–12
Carrier Frequency (kHz)
(default: 8) (default: 4)
Rated Input Current (A)
Input Rating
188
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Appendix A SpecificationsVFD-EL-W
Installation Location Altitude 1,000 m or lower, keep from corrosive gasses, liquid and dust.
Non-condensing, non-freezing
-10–50°C [40°C for side-by-side mounting, excluding VFD007EL21W(-1)]
Ambient Temperature
-10–40°C [VFD007EL21W(-1), ambient temperature exceeding 40°C may
reduce the service life of the drive]
Storage/ Transportation
-20–60°C
Temperature
Ambient Humidity Below 90% RH (non-condensing)
1.0 mm, peak to peak 2–13.2 Hz; 0.7–1.0 G, 13.2–55 Hz;
Vibration
1.0 G, 55–512 Hz; compliance with IEC 60068-2-6
Certifications CE, RoHS, GB 12668.3, KC (Only individually packaged)
190
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Appendix A SpecificationsVFD-EL-W
192
Send Quote Requests to [email protected]
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to [email protected] Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Appendix B. Accessories VFD-EL-W
Appendix B. Accessories
B-2 Reactor
B-2-1 AC Reactor
AC Input Reactor Recommended Value
230V, 50/60Hz, One-Phase
Fundamental Max. continuous Inductance (mH)
kW HP
Amps Amps 3–5% Impedance
0.2 0.25 4 6 6.5
0.4 0.5 5 7.5 3
0.75 1 8 12 1.5
1.5 2 12 18 1.25
2.2 3 18 27 0.8
0.75 1 8 12 3 5
1.5 2 8 12 1.5 3
2.2 3 12 18 1.25 2.5
0.75 1 4 6 9 12
1.5 2 4 6 6.5 9
2.2 3 8 12 5 7.5
4.0 5.5 12 18 3 5
5.5 7.5 18 27 1.5 2.5
Applications
Connected in input circuit
Application 1
When more than one AC motor drives are connected to the same mains power and are running, and one
of them is ON during operation.
Issues: When applying power to one of the AC motor drives, the charge current of the capacitors may
cause voltage dip. The AC motor drive may be damaged when over-current occurs during operation.
Correct wiring:
M1 reactor
AC motor drive motor
M2
AC motor drive motor
Mn
AC motor drive motor
Application 2
A silicon rectifier and AC motor drive are connected to the same power.
Issues: Switching spikes are generated when the silicon rectifier switches ON/OFF. These spikes may
damage the mains circuit.
Correct wiring:
Silicon Controlled Rectifier
power reactor
DC
AC motor drive
reactor
motor
Application 3
The power supply capacity is 10 or above times the AC motor drive capacity.
Issues: When the mains power capacity is too large, line impedance is small and the charge current is
too high. This may damage the AC motor drive due to the higher rectifier temperature.
Correct wiring:
large-capacity small-capacity
power reactor AC motor drive
motor
NOTE: Diagram B
600V Insulated Unshielded Cable Please put all wires through four cores in series without
winding.
1. The table above gives approximate wire size for
zero phase reactors, but the selection is ultimately Zero Phase Reactor
governed by the type and diameter of the cable;
that is, the cable must fit through the center hole Power R/L1 U/T1
of zero phase reactors. Supply
S/L2
T/L3
V/T2
W/T3
MOTOR
The actual operation frequency that the drive outputs to the motor.
Read parameters. Press PROG/DATA for 2–3 sec. until it is flashing. Then, you
can read four parameters from the AC motor drive to the digital keypad PU06
(read D0–read D3). Press UP or DOWN key to change to SAVE function.
Write parameters. Press PROG/DATA for 2–3 sec. until it is flashing. Then, you
can write the parameters from the digital keypad PU06 to the AC motor drive.
Press UP or DOWN key to change to READ function.
External Fault
“Err” displays if the input is invalid or the input exceeds the setting range.
Write Write
parameters parameters
failure success
VFD-PU08 Dimension
Unit: mm (inch)
W W1 W2 W3 H H1 H2 H3 D D1 D2 D3 D4 S1
68.0 63.8 59.9 8.1 46.8 42.0 26.3 7.5 35.6 22.7 7.6 2.2 1.3 M3*0.5
(2.68) (2.51) (2.36) (0.32) (1.84) (1.65) (1.04) (0.30) (1.40) (0.89) (0.30) (0.09) (0.05) (2X)
VFD-PU08V Dimension
Unit: mm [inch)
W1 W2 W3 W4 W H1 H2 H3 H4 H D1 D2 D
32.9 3.6 17.3 32.8 36.5 3.5 66.5 28.3 14.3 70.0 13.8 22.0 31.0
(1.30) (0.14) (0.68) (1.29) (1.44) (0.14) (2.62) (1.11) (0.56) (2.76) (0.54) (0.87) (1.22)
Items Description
Connector RJ45
NOTE:
The VFD-PU08 does not include the extension cord. Please choose the suitable extension cords as
needed. (Refer to the table below)
Communication cable
L
No. Model Name
mm inch
1 UC-CMC003-01A 300 11.8
2 UC-CMC005-01A 500 19.6
3 UC-CMC010-01A 1000 39.0
4 UC-CMC015-01A 1500 59.0
5 UC-CMC020-01A 2000 78.7
6 UC-CMC030-01A 3000 118.1
7 UC-CMC050-01A 5000 196.8
Status displayed
Status displayed Note
RUN: VFD is running
FWD: VFD is running forwardly
REV: VFD is running reversely
STOP: VFD is stopped
STOP Flashing: VFD is stopping
VR light on: VFD potentiometer function is enabled
VR light off: Direction function key (Up) and Direction function key
(Down & left) is enabled
Button functionality
Press MODE botton for 2 seconds, when “X” flashing:
1. When always on, you can press the + key combination to switch the up key
and <SHIFT> / down key to adjust the frequency command of the inverter, and will
MKEL-AFKM1 VFD007EL21W(-1)
Fan installation
The choice of the right AC motor drive for the application is very important and has a big influence on the
drive’s lifetime. If the capacity of the AC motor drive is too large, it cannot provide complete protection to
the motor and motor might be damaged. If the capacity of the AC motor drive is too small, it cannot
provide the required performance and the AC motor drive might be damaged due to overloading.
Simply selecting the AC motor drive with the same capacity as the motor cannot completely meet the
application requirements. Therefore, a designer should consider all the conditions, including load types,
load speeds, load characteristics, operation methods, rated output, rated speed, power and the change
in load capacity. The following table lists the factors you need to consider, depending on your
requirements.
Related Specification
Item Speed and
Time Overload Starting
Torque
Ratings Capacity Torque
Characteristics
Friction load and weight load
Liquid (viscous) load
Load type ● ●
Inertia load
Load with power transmission
Constant torque
Load speed and
Constant output
torque ● ●
Decreasing torque
characteristics
Decreasing output
Constant load
Shock load
Load
Repetitive load ● ● ● ●
characteristics
High starting torque
Low starting torque
Continuous operation
Short-time operation
Operation mode ● ●
Long-time operation at medium/low
speeds
Maximum output current
Rated output (instantaneous) ● ●
Constant output current (continuous)
Maximum frequency
Rated speed ●
Base frequency
Power supply transformer capacity
or percentage impedance
Voltage fluctuations and unbalance
Power supply ● ●
Number of phases, single phase
protection
Frequency
Load capacity Mechanical friction, losses in wiring ● ●
change Duty cycle modification ●
kN GD 2 N
TL 1.5 the _ capacity _ of _ AC _ motor _ drive(kVA)
973 cos 375 t A
kN
nT nsks 1 PC11 ns ks 1 the _ capacity _ of _ AC _ motor _ drive(kVA)
cos nT
The current should be less than the rated current of the AC motor drive (A).
Acceleration time ≤ 60 seconds
nT IM 1 nnTS kS 1 1.5 the _ rated _ current _ of _ AC _ motor _ drive( A)
nT IM 1 n
nS kS 1 the _ rated _ current _ of _ AC _ motor _ drive( A)
T
The motor capacity should be less than the capacity of the AC motor drive.
k 3 VM IM 103 the _ capacity _ of _ AC _ motor _ drive(kVA)
The current should be less than the rated current of the AC motor drive (A).
k IM the _ rated _ current _ of _ AC _ motor _ drive( A)
Symbol explanation
PM Motor shaft output for load (kW)
η Motor efficiency (normally approx. 0.85)
cos Motor power factor (normally approx. 0.75)
VM Motor rated voltage (V)
IM Motor rated current (A), for commercial power
k Correction factor calculated from the current distortion factor
(1.05–1.1, depending on PWM method)
PC 1 Continuous motor capacity (kVA)
kS Starting current/rated current of the motor
nT Number of motors in parallel
nS Number of simultaneously started motors
GD 2
Total inertia (GD2) calculated back to motor shaft (kg m2)
TL Load torque
tA Motor acceleration time
N Motor speed
Setting Parameters
1. You can set the AC motor drive to an output frequency up to 400 Hz (less for some models) with the
digital keypad. Setting errors may create a dangerous situation. For safety, setting an upper limit
frequency function is strongly recommended.
2. High DC brake operating voltages and long operation time (at low frequencies) may cause
overheating of the motor. In that case, forced external motor cooling is recommended.
3. Motor acceleration and deceleration time is determined by motor rated torque, load torque, and load
inertia.
4. If you activate the stall prevention function, the acceleration and deceleration time is automatically
extended to a length that the AC motor drive can handle. If the motor must decelerate within a
certain time with a higher load inertia than the AC motor drive can handle in the required time, either
use an external brake resistor and/or a brake unit (depending on the model) to shorten deceleration
time only, or increase the capacity of both the motor and the AC motor drive.
Load duty-cycle
25%
40% 60%
100
82
torque(%)
70
60
50 continuous
0 3 6 20 60
Frequency (Hz)
If 100% of continuous torque is required at low speed, it may be necessary to use a special inverter-
duty motor.
Motor dynamic balance and rotor endurance should be considered once the operating speed
exceeds the rated speed (60Hz) for a standard motor.
Motor torque characteristics vary when driving the motor with an AC motor drive instead of a
commercial power supply. Check the load torque characteristics of the machine connected to the
motor.
Because of the high carrier frequency PWM control of the VFD series, pay attention to the following
motor vibration problems:
Resonant mechanical vibration: use anti-vibration dampers to mount equipment that runs at varying
speed.
Motor imbalance: special care is required for operation at 60 Hz and higher frequencies.
The motor fan is very noisy when the motor speed exceeds 60 Hz or above.
Special Motors
Pole-changing (Dahlander) motor:
The rated current differs from that of a standard motor. Check before operation and carefully choose
the capacity of the AC motor drive. When changing the number of poles, stop the motor first. If over-
current occurs during operation or the regenerative voltage is too high, let the motor free run to stop
(coast).
Submersible motor:
The rated current is higher than that of a standard motor. Check before operation and carefully
choose the capacity of the AC motor drive. A long motor cable between the AC motor drive and the
motor reduces the available motor torque.
Explosion-proof (Ex) motor:
Must be installed in a safe place and the wiring should comply with the (Ex) requirements. Delta AC
Motor Drives are not suitable for (Ex) areas that require special precautions.
Gear reduction motor:
The lubricating method of the reduction gearbox and the speed range for continuous operation are
different and depend on the motor brand. Carefully consider the lubricating method when operating
for a long time at low speed and for high-speed operation.
Synchronous motor:
The rated current and the starting current are higher than those of standard motors. Check before
operation and carefully choose the capacity of the AC motor drive. When one AC motor drive
operates more than one motors, pay attention to starting and changing the motor.
Motor Torque
The motor torque characteristics operated by an AC motor drive depend on the motor model selection
and AC motor drive parameter settings.