Delta Ia-Plc As MDM en 20210820
Delta Ia-Plc As MDM en 20210820
Delta Ia-Plc As MDM en 20210820
Asia EMEA
China: Delta Electronics (Shanghai) Co., Ltd. EMEA Headquarters: Delta Electronics (Netherlands) B.V.
No.182 Minyu Rd., Pudong Shanghai, P.R.C. Sales: [email protected]
Post code : 201209 Marketing: [email protected]
TEL: +86 -21- 6872-3988 / FAX: +86 -21- 6872-3996 Technical Support: [email protected]
Customer Service: 400 - 820 - 9595 Customer Support: Customer- [email protected]
Service: [email protected]
Japan: Delta Electronics (Japan), Inc. TEL: +31(0) 40 800 3900
Industrial Automation Sales Department
2-1-14 Shibadaimon, Minato - ku BENELUX: Delta Electronics (Netherlands) B.V.
Tokyo, Japan 105 - 0012 Automotive Campus 260, 5708 JZ Helmond, The Netherlands
TEL: +81- 3 - 5733 -1155 / FAX: +81-3 - 5733 -1255 Mail: [email protected]
TEL: +31(0) 40 800 3900
Korea: Delta Electronics (Korea), Inc. DACH: Delta Electronics (Netherlands) B.V.
1511, 219, Gasan Digital 1- Ro., Geumcheon - gu,
Coesterweg 45, D - 59494 Soest, Germany
Seoul, 08501 South Korea
Mail: [email protected]
TEL: +82-2- 515 - 5305 / FAX: +82-2- 515 - 5302
TEL: +49(0)2921 987 0
Singapore: Delta Energy Systems (Singapore) Pte Ltd. France: Delta Electronics (France) S.A.
4 Kaki Bukit Avenue 1, #05 - 04, Singapore 417939 ZI du bois Challand 2, 15 rue des Pyrénées,
TEL: +65 - 6747- 5155 / FAX: +65 - 6744 - 9228 Lisses, 91090 Evry Cedex, France
Mexico: Delta Electronics International Mexico S.A. de C.V. MEA: Eltek Dubai (Eltek MEA DMCC)
Gustavo Baz No. 309 Edificio E PB 103 OFFICE 2504, 25th Floor, Saba Tower 1,
Colonia La Loma, CP 54060 Jumeirah Lakes Towers, Dubai, UAE
Tlalnepantla, Estado de México Mail: [email protected]
TEL: +52- 55 -3603 - 9200 TEL: +971(0) 4 2690148
AS-0249820-10
*We reserve the right to change the information in this catalogue without prior notice. 2021/08/20 www.deltaww.com
AS Series Module Manual
Revision History
Ve r s i o n Revision Date
1st The first version was published. 2 0 1 6 / 11 / 3 0
1. Chapter 1: Added information concerning new models
AS08AD-B and AS08AD-C.
2. Chapter 2: Added information concerning new models
AS08AD-B andAS08AD-C.
3. Chapter 3: Updated information concerning CR#23-24
and software ne w screenshots.
4. Chapter 4: Updated information concerning CR#35-
2nd 54/CR#210-225 and software ne w screenshots. 2017/07/07
5. Chapter 5: Updated information concerning CR#1-
4/CR#210-217 and software ne w screenshots.
6. Chapter 6: Updated information concerning CR#210-
217 and software new s creenshots.
7. Chapter 7: Updated information concerning theoretical
calibration and software new screenshots
8 . C h a p t e r 8 : U p d a t e d i n f o r m a t i o n c o n c e r n i n g n e w FW 2 . 0 .
1. Chapter 1: Added information concerning new models
AS06RTD-A and AS08TC-A and installation information
updated in section 1.3.1.
3rd 2. Chapter 5: Added information concerning new model 2018/02/09
AS06RTD-A.
3. Chapter 6: Added information concerning new models
AS08TC-A.
1. Chapter 1: Added information concerning ambient air
temperature-barometric pressure-altitude.
2. Chapter 2: Added information concerning filter average,
cable length and resistance. Updated section 2.2.4
CR#23-38 and section 2.2.5 CR#43-74.
3. Chapter 3: Added information concerning cable length
and resistance. Updated section 3.2.1 analog to digital
conversion range, output impedance and section 3.2.4
CR17-20 and CR#21-36.
4. Chapter 4: Added information concerning filter average,
cable length and resistance. Updated section 4.2.1
analog to digital conversion range, output impedance
4th and 4.2.4 CR#31-21. 2 0 1 8 / 11 / 2 6
5. Chapter 5: Updated section 5.2.1 JPt100 range, section
5.2.4-5.2.5 added notes on CR, updated section 5.2.6
PID information, revised section 5.2.7 control mode.
6. Chapter 6: Section 6.2.1 revised type B range, added a
note, section 6.2.4-6.2.5 added notes on CR, revised
CR# for the records, updated section 6.2.6 PID
information and revised section 6.2.7 control mode.
7. Chapter 7: Section 7.2.4 added notes on CR.
8 . C h a p t e r 8 : N e w f u n c t i o n s i n n e w FW 2 . 0 2 .
9. Chapter 9: Updated section 9.2.5 output impedance
information and added sections 9.2.7.1-9.2.7.9 for new
f u n c t i o n s a d d e d a n d o p e r a t i o n a l e xa m p l e s .
1. Chapter 7: Revised contents of CR#0 and #59 in
5th section 7.2.4. 2019/1/29
2. Chapter 8: Deleted a note in section 8.6.4.
6th 1. Chapter 5: Updated wiri ng information in section 5.2.8. 2019/5/10
Ve r s i o n Revision Date
1. Chapter 1: Added model information including AS02PU-
A, AS04PU-A, AS02HC-A, AS04SIL-A and AS-FPFN02
2. Chapter 2: Updated section 2.2.1 specification, 2.2.4
and 2.2.5 CR table, and 2.4 adding a new error code.
3. Chapter 3: Updated section 3.2.4 CR table and 3.4
adding a new error code.
4. Chapter 4: Updated section 4.2 specification, 4.2.4 CR
table and 4.4 adding a new error code.
5. Chapter 5: Updated section 5.2 specification, 5.2.4 and
5.2.5 CR table, and 5.4 adding a new error code.
6. Chapter 6: Updated section 6.2.4 and 6.2.5 CR table.
7th 2 0 1 9 / 11 / 2 9
Added D MPID instruction supporting firmware versions
and section 6.4 adding a new error code.
7. Chapter 7: Updated section 7.2.4 and 7.2.5 CR table
and 7.5 adding a new error code.
8. Chapter 8: Added a new error code in section 8.7.2.2.
9. Chapter 9: Updated AS-F2AD specifications in sections
9 . 2 . 4 a n d 9 . 2 . 5 . D e l e t e d S M 111 0 a n d S R 1 5 4 0 i n
section 9.2.7. Added AS-FPFN02 information in
sections 9.2.8 and 9.3.5.
1 0 . C h a p t e r 11 : N e w c h a p t e r i n t r o d u c i n g p o s i t i o n i n g
modules AS02PU-A and AS04PU-A.
1. Chapter 1: Updated section 1.1 to include software
information for new AX series PLC, updated AS02HC-A
specifications and added AS-FOPC02 information.
Added an installation note in section 1.3.4.
2. Chapter 2: New chapter introducing digital input/output
modules.
3. Chapter 3 – 7: Added DIADesigner+ and Hardwa re
Configuration information.
4. Chapter 8: Updated CR#120 default value and input
values 100 to 105 of CR200 command set in section
8.2.4.
5. Chapter 9: Added AS-FPEN02 and AS04SIL-A
information, added LED indicator information of
8th EtherNet/IP in section 9.4.2, and added error LED 2020/04/30
indicator information of AS00SC M- A in section 9.7.2.2.
6. Chapter 10: Updated software images in section 10.2.7
and 10.2.7.2, updated section 10.2.7.7, added AS-
FPFN02 installed on AS00SC M-A information in section
10.2.8, added AS-FOPC02 product information in
sections 10.2.9 and 10.3.6, updated LED indicator
information of AS-FEN02 in section 10.3.4.
7. Chapter 12: Updated response time and input isolation
specifications in section 12.2.1.
8. Chapter 13: New chapter introducing IO link
communication module, AS04SIL-A.
9. Chapter 14: New chapter introducing high speed
counter modules AS02PU and AS04PU.
1. Chapter 1: Updated AS02/04PU-A module descriptions
2. Chapter 3-8: Added DIADesigner-AX software o peration
3. Chapter 9: Updated sections 9.7.2.2 and 9.7.2.3
9th 2020/10/30
AS00SCM Error LED Indicators
4. Chapter 10: Deleted EtherNet/IP Adapter information in
section 10.2.9.
Ve r s i o n Revision Date
5. Chapter 13: Added filter time in section 13.2.1 and
added 13.3.2.5 Application-specific API for
Communications of IO-Link Devices.
6. C h a p t e r 1 4 : A d d e d t h e p r o c e s s i m a g e s o f t h e Ti m i n g t o
Count in section 14.2.5 Pulse Input Counting.
1. Chapter 1: Added new product information for AS02ADH-A
and AS-FFTP01.
2. Chapter 6: Added Ma xi mum Measurable Range in
functional specifications and Conversion Details in
section 6.21. Added a label description in profile in
section 6.2.2.
3. Chapter 7: Added more applicable sensor types in,
including C, U, L and TXK. Added Conversion Details in
section 7.2.1. Added a label description in Profile in
section 7.2.2 Added compatible firmware versi ons and
more descriptions on control mode in section 7.2.7.
4. Chapter 8: Added W eight in functional specifications in
section 8.2.1. Added a label description in Profile in
section 8.2.2. Added new CRs, CR#400 to #479 in section
8.2.4. Added a new illustration for zero point tracking in
section 8.2.5. Updated the software images in section
8.3.2, 8.3.3 and 8.4. Added troubleshooting for diver
board failure in section 8.6.2.
5. Chapter 9: Updated Introduction and added applicable
PLC CPU for AS00SCM-A in RTU mode in section 9.1.
10th Updated Knob Function in section 9.2.3. Updated Modbus 2021/08/20
information and added software images in sections 9.3.1,
9.3.1.1 and 9.3.1.2. Updated UD Link information, added
software images in section 9.3.2, and added new
description for SC MSoft in section 9.3.2.2. Added more
d e s c r i p t i o n s a n d e xa m p l e f o r a p p l i c a t i o n s o f A S 0 0 S C M - A
in RTU mode in section 9.4.2. Deleted software image
from manufacturer R in section 9.4.2.6. Added Network
Security information in section 9.4.2.7. Added error code
16#1304 in section 9.7.2.1, updated error codes 16#1506
in section 9.7.2.2 and updated 16#1502 in section
9.7.2.1.
6. Chapter 10: Updated supported firmware and software
versions in section 10.2.7.1. Updated Features in
section 10.2.7.2. Added a new section for IP Setting in
section 10.2.7.4. Updated information in Data Mapping
through EtherNet/IP Adapter in section 10.2.7.6. Updated
software images (from manufacturer R) and descriptions
i n E xa m p l e o f C o n n e c t i n g t o 3 r d P a r t y P L C S c a n n e r
through EIP Builder in section 10.2.7.7. Updated
supported firmware and software ve rsions in section
10.2.8.1. Updated Features in section 10.2.8.2. Updated
Ve r s i o n Revision Date
information in Configuring the Data Length for I/O
M o d u l e (W o r k s w i t h A S 3 0 0 ) i n s e c t i o n 1 0 . 2 . 8 . 4 . U p d a t e d
applicable modules in section 10.2.8.6. Updated
software images (from manufacturer S) and PROFINET
D e v i c e E xa m p l e ( A d a p t e r ) i n s e c t i o n 1 0 . 2 . 8 . 8 . U p d a t e d
features for AS-FOPC02 in section 10.2.9.2. Added
Modbus TCP Specifications and OPC UA Specifications
in section 10.2.9.3. Added SR information for AS300 in
s e c t i o n 1 0 . 2 . 9 . 4 . A d d e d S e t t i n g U T C Ti m e i n O P C U A
Slave information in section 10.2.9.6. Added Network
Security information in section 10.2.9.7. Added The
C o p y r i g h t I n f o r m a t i o n a b o u t t h e U s e d E xt e r n a l S o f t w a r e
Sources in 10.2.9.8. Added a new section 10.2.10 for
AS-FFTP01. Updated AS-FPFN02 LED information in
section 10.3.5.
7. Chapter 12: Updated information in Special Features in
section 12.2.4. Updated software images in section 12.3.
8. Chapter 13: Updated AS PLC CPU firm ware vers ion in
section 13.1. Updated application-specific API
information in section 13.3.2.5. Updated 16#FF21~
16#FF25 in IO-Link Event Code table in section 13.5.
9. Chapter 14: Updated the receiving data length to 32 bits
in section 14.1.1. Move the input/output information to
section 14.3. Updated software images in section 14.4.
10.Chapter 15: Added a new chapter for High-speed analog
module AS02ADH.
AS Series Module Manual
Table of Contents
Chapter 1 Introduction
i
3.3.2 Checking the Version of a Module....................................................3-27
3.3.3 Online Mode .................................................................................3-28
3.3.4 Importing/Exporting a Parameter File ..............................................3-29
3.3.5 Parameters ..................................................................................3-30
ii
4.5 Troubleshooting .............................................................................. 4-30
4.5.1 Error Codes ............................................................................. 4-30
4.5.2 Troubleshooting Procedure ........................................................ 4-30
iii
Chapter 6 Temperature Measurement Module AS04/06RTD
iv
Chapter 7 Temperature Measurement Module AS04/08TC
v
Chapter 8 Load Cell Module AS02LC
vi
Chapter 9 Serial Communication Module AS00SCM
9.1 Introduction ...................................................................................... 9-3
vi i
Chapter 10 Function Cards
viii
Chapter 11 DeviceNet Master Scanner Module AS01DNET-A
11.6 How to Call DeviceNet Builder through ISPSoft (AS-Series PLC) ... 11-97
ix
Chapter 12 Positioning Modules AS02/04PU
x
13.4.5 Application of CANopen DS301 Mode ............................................. 13-33
xi
Chapter 15 High Speed Analog Input Moudle AS02ADH
xi i
1
Chapter 1 Introduction
Table of Contents
1.1 Overview ........................................................................................... 1-2
1-1
A S S er i es Mo d u le Ma n ua l
1.1 Overview
_1 This manual introduces the use of special modules. The special modules are the analog input/output modules,
temperature measurement modules, load cell modules, and network modules. For software operation, you
need to use ISPSoft, if you are using AS Series PLC CPU. Refer to ISPSoft User Manual for more information.
The new software DIADesigner-AX only supports AX Series PLC CPU and AS Series modules now, refer to
AX-3 User Manual for more information on software operation. Refer to Section 1.1.2 of AX-3 Operation
Manual for more information on modules that are supported for AX-3 Series PLC.
1-2
Ch a pt er 1 In tr od uc t i o n
1-3
A S S er i es Mo d u le Ma n ua l
1.2 Specifications
_1 1.2.1 General Specifications
Item Specifications
Ingress protection
IP20
(IP ratings)
EMC (electromagnetic
Refer to Chapter 7 for more information.
compatibility)
Tested with:
5 Hz ≦ f ≦ 8.4 Hz, constant amplitude 3.5 mm
1-4
Ch a pt er 1 In tr od uc t i o n
1.2.2.1 EMI 1_
(radiated)
(measured at a
230-1000 MHz 47 dB (μV/m) quasi-peak
distance of 10
1.2.2.2 EMS
Environmental
Reference Standard Test Test Level
Phenomenon
Electrostatic Contact ±4 kV
IEC 61000-4-2
Discharge Air ±8 kV
1-5
A S S er i es Mo d u le Ma n ua l
Shielded cable 1 kV 1 kV CM 10 V
Data communication
Unshielded cable 1 kV 1 kV CM 10 V
2 kV CM
AC I/O (unshielded) 2 kV 10 V
1 kV DM
2 kV CM
AC power 2 kV 10 V
1 kV DM
Equipment power
0.5 kV CM
DC power 2 kV 10 V
0.5 kV DM
1-6
Ch a pt er 1 In tr od uc t i o n
1.3 Installation
1.3.1 Installing a Module 1_
1. Push the clip rings if they are out as the image 1 shown. Push the module to the desire position until you
hear a click to finish installation.
2. Link the I/O modules on the right side of the PLC and make sure they are hooked together. Push the
modules into the DIN rail until you hear a click.
3. After you installed the module, fasten the screws on the modules to secure the module on the DIN rail.
1 2
If there is a vibration source near the installation site, install anti-vibration baffles on the sides of the AS Series
modules for better stabilization, such as the gray baffles show below.
1-7
A S S er i es Mo d u le Ma n ua l
1-8
Ch a pt er 1 In tr od uc t i o n
Installation
Align the terminal block at the port, and press it into the CPU.
Removal
Push the clips inward as the arrow 1 shown to release the terminal block and then pull it up as the arrow
2 shown.
1 1
1-9
A S S er i es Mo d u le Ma n ua l
1-10
Ch a pt er 1 In tr od uc t i o n
Installation 1_
Push the extension card into the extension card slot until you hear a click.
Note: before the installation begin, you need to check if the pin arrangement and appearance are normal. If
there is any bent or missing pin, you need to change to a new card. You should also check the PLC card slot
Removal
Press the tab labeled PUSH to release the extension card, and then remove the extension card.
1 - 11
A S S er i es Mo d u le Ma n ua l
Installation
2. Press the driver board in the direction indicated by arrow 1, and make sure that the groove is
Removal
1-12
2
Chapter 2 Digital Input/Output Modules
Table of Contents
2.1 Digital Input/Output Module Specifications....................................... 2-2
2.1.1 General Specifications .................................................................... 2-2
2.1.2 Digital Input/Output Module Profiles ................................................. 2-4
2.1.3 Digital Input/Output Module Terminals ........................................... 2-12
AS Series Module Manual
_2 Number of inputs 8 16 32 64 8 8 8
Removable terminal
Connector type MIL connector Removable terminal block
block
Input type Digital input
Input form Direct current (sinking or sourcing)
24 VDC
Input voltage/ current 24 VDC,5 mA 24 VDC,5 mA
3.2 mA
Input impedance 4.7 k Ω 7.5k Ω 4.7 k Ω
OFF→ON >15 VDC
Action level
ON→OFF <5 VDC
Response OFF→ON < 20 us
time ON→OFF < 200 us
Software filter time Setting range: 0 ~ 25 ms; default: 10 ms
Varies according to the filter time; for example when the filter is 1 ms, the
Maximum input
maximum input frequency is 500 Hz, when 2 ms, 250 Hz.
frequency
Note: CPU scan time also affects the maximum input frequency.
Voltage input
Sinking: The inputs are NPN transistors whose collectors are open
Input signal collectors.
Sourcing: The inputs are PNP transistors whose collectors are open
collectors.
Input Isolation 500 VDC
Input display When the optocoupler is driven, the input LED indicator is ON.
Weight 100 g 117 g 100 g 140 g 138 g 120 g 120 g
2-2
Ch a pt er 2 D ig i ta l I np ut /O ut pu t M od u l es
Model 08AN01 16AN01 16AP11 08AN01 16AN01 16AP11 08AN01 16AN01 16AP11
Item R-A R-A R-A T-A T-A T-A P-A P-A P-A
output Inductance 0.5 Hz 0.5 Hz 0.5 Hz
frequency*1
Bulb 1 Hz 10 Hz 10 Hz
OFF→ON 10 ms 0.5 ms 0.5 ms
Maximum
Response ON→OFF 10 ms 0.5 ms 0.5 ms
time 2_
Output Isolation 1350 VAC 500 VDC
Weight 120 g 158 g 138 g 100 g 122 g 120 g 100 g 123 g 120 g
Model
32AN02T-A 64AN02T-A
Item
Number of outputs 32 64
Connector type MIL connector
Output type Digital output
Output form Transistor-T (sinking)
Output voltage 5–30 VDC
Leadage current <10uA
Resistance 0.1A/output, 3.2A/COM
Maximum
Inductance N/A
load
Bulb N/A
120VAC Resistive
3000
30VDC Inductive(t=7ms)
2000
240VAC Inductive(cosψ = 0.4)
1000
120VAC Inductive(cosψ =0.4)
Operation(X10 )
3
500
300
200
100
30VDC
50 Inductive
(t=40ms )
30
20
2-3
AS Series Module Manual
08AM 1
7
7
IN
_2
S/S
PWR
S/S
IN
0 0
1
2
98.3
1 2
88
3
2 4
5
3
6
7
4
3
5
6
4
7
8 5
6 75
25
C0 C0 C0
PWR PWR PWR
C0 C0 C0
OUT OUT OUT
0 0 0 0 0 0
1 1 1
1 2 1 2 1 2
3 3 3
2 4 2 4 2 4
5 5 5
3 3 3
6 6 6
7 4 7 7
4 4
5 5 5
6 6 6
7 7 7
Unit: mm
2-4
Ch a pt er 2 D ig i ta l I np ut /O ut pu t M od u l es
AS16AM10N-A/AS16AN01P-A/AS16AN01R-A/AS16AN01T-A/AS16AP11P-A/AS16AP11R-A/
AS16AP11T-A
38.2 95
16AM 1
7
7
IN IN
S/S S/S
PWR
S/S
2_
S/S
IN
0 1 0 2
98.3
1
88
2 3 2
3
4 5 4
5
6 7
8 9
6
7 3
10 11 8
9
12 13 10
14 15
11
12
4
13
8 14
15 5
6 75
35
C0 C0 C0 C0 C0 C0 C0 C0 C0
Unit: mm
2-5
AS Series Module Manual
AS32AM10N-A
28.2 92
32AM 1
X0 LED
X1 LED
7 2
7
39
3
PWR
IN
0
4
1
_2
98.3
88
2
3
4
5
6
7
5
8
9
10
11
12
1
8 13
14
15
6 75
25
Unit: mm
AS32AN02T-A
28.2 92
32AN 1
Y0 LED
Y1 LED
7 2
7
39
3
PWR
OUT
0
4
1
98.3
88
2
3
4
5
6
7
5
8
9
10
11
12
1
13
8 14
15
6 75
25
Unit: mm
2-6
Ch a pt er 2 D ig i ta l I np ut /O ut pu t M od u l es
AS64AM10N-A
38.2
92
64AM 1
0 1 0 1
0 1
2
8
3 8
40 2
P WR
4
IN
X1 X2
0
1 5
98.3
88
2
3
4
5
6
7
6
X0 X3 8
9
10
11
12
2 40
13
9 14
15
7 75
35
Unit: mm
2-7
AS Series Module Manual
AS64AN02T-A
38.2 92
64AN 1
0 1 0 1
0 1
2
8
3 8
40 2
P WR
4
O UT
Y1 Y2
0
1 5
_2
98.3
2
88
3
4
5
6
7
6
Y0 Y3 8
9
10
11
12
2 40
13
9 14
15
7 75
35
Unit: mm
Number Name Description
1 Model name Model name of the module
LED indicator
2 Switches the LED indicators to their represented outputs.
switch 1
LED indicator
3 Switches the LED indicators to their represented outputs.
switch 2
For the external I/O connecting cables UC-ET010-24D, UC-ET020-24D,
4 ML connector
UC-ET030-24D
Power LED
5 Indicates the power status of the module
indicator
Output LED
6 If there is an output signal, the output LED indicator is ON.
indicator
7 DIN rail clip Secures the DIN rail
External module
8 Connects the modules
port
9 Label Nameplate
Length
19 2 0
#1
3 9 40 2
1 2
1
39 40
#2
1 2 2
21 2 2
500 -
+10m m
Unit: mm
2-8
Ch a pt er 2 D ig i ta l I np ut /O ut pu t M od u l es
39 40 39 40
1 2 1 2
2_
Number Name Description
Connects an external terminal module and a wiring module UB-10-
1 IDC 40-pin terminal
ID32A, and UB-10-OT32A
UB-10-ID16A
67.0
4
87.0
3
2
53.6
Unit: mm
UB-10-ID32A
113
1
87
2
4 53.6
Unit: mm
Number Name Description
UB-10-ID16A: 20-pin ML connector Connects the external terminal module and a
1
UB-10-ID32A: 40-pin ML connector wiring module
2 Terminals Input/Output terminals for wiring
3 Clip Hangs the external terminal module on a DIN rail
4 Set screw Fixes the base
2-9
AS Series Module Manual
4. AS332T-A/AS64AN02T-A and the external terminal modules UB-10-ID16A, UB-10-OR16A, and UB-
10-OT32A.
UB-10-ID16A
67.0
_2 6
87.0
7
2
53.6
Unit: mm
UB-10-OR16A
113
1
3
4
87
5
55.3
7
2
6
Unit: mm
UB-10-OT32A
113
1
87
2
7 53.6
Unit: mm
2-10
Ch a pt er 2 D ig i ta l I np ut /O ut pu t M od u l es
2_
1
101
2 26.9
33.7
Unit: mm
2 - 11
AS Series Module Manual
08AM 08AN
_2
IN OUT
C0
PWR PWR
C0
IN OUT
0 0 0 0
1 1
1 2 1 2
3 3
2 4
2 4
5 5
3 3
6 6
4 7 4 7
5 5
6 6
7 7
AS08AN01R-A AS08AN01T-A
08AN 08AN
OUT OUT
C0 C0
PWR PWR
C0 C0
OUT OUT
0 0 0 0
1 1
1 2 1 2
3 3
2 4 2 4
5 5
3 3
6 6
4 7 7
4
5 5
6 6
7 7
2-12
Ch a pt er 2 D ig i ta l I np ut /O ut pu t M od u l es
AS16AM10N-A AS16AN01P-A
16AM 16AN
IN IN
2_
OUT OUT
C0 C0
PWR PWR
0 1
IN OUT
0 1 0 2 3 0
1 1
2 3 2 4 5 2
3 3
4 5 4 6 7 4
5 5
6 7 C1 C1
6 6
7 7
8 9 8 9
8 10 8
10 11 11
9 9
12 13 10 12 13 10
11 11
14 15 12 14 15 12
13 13
14 14
15 15
AS16AN01R-A AS16AN01T-A
16AN 16AN
C0 C0 C0 C0
PWR PWR
C0 C0 0 1
OUT OUT
0 1 0 2 3 0
1 1
2 3 2 4 5 2
3 3
4 5 6 7 4
4
5 5
6 7 C1 C1
6 6
7 7
8 9 8 9
8 10 11 8
10 11
9 9
12 13 10 12 13 10
11 11
14 15 12 14 15 12
13 13
14 14
15 15
2-13
AS Series Module Manual
AS16AP11P-A AS16AP11R-A
16AP 16AP
IN OUT IN OUT
_2 C0 C0
PWR PWR
C0 C0
IN IN
0 0 0 0 0 0
1 1
1 1 2 1 1 2
3 3
2 2 2 2 4
4
5 5
3 3 3 3
6 6
7 7
4 4 4 4
OUT OUT
0 5 5 0
5 5
1 1
2 6 6 2
6 6
3 3
7 7 7 7 4
4
5 5
6
6
7
7
AS16AP11T-A AS32AM10N-A
- -
S/S S/S
32AM 1.15 1.14
16AP X0 LED
X1 LED
1.13 1.12
1.11 1.10
1.9 1.8
IN OUT
39 1.7 1.6
C0 PWR
PWR 1.5 1.4
C0
IN
IN 0 1.3 1.2
0 0 0 1
1 2 1.1 1.0
1 1 2
3
3
4
- -
2 2 4 5
5 6
S/S S/S
3 3
6
7
7 0.15 0.14
4 4
OUT
0
8 0.13 0.12
5 5 9
1
6 2
10 0.11 0.10
6 11
7
3
1
12 0.9 0.8
4
13
5
14 0.7 0.6
6
15
7 0.5 0.4
0.3 0.2
0.1 0.0
2-14
Ch a pt er 2 D ig i ta l I np ut /O ut pu t M od u l es
AS32AN02T-A AS64AM10N-A
- - - - 2.0 2.1
C0 C0 S/S0 S/S0 2.2 2.3
32AN 1.15 1.14 64AM 1.15 1.14 2.4 2.5
Y0 LED 0 1 01
Y1 LED 1.13 1.12 0 1 1.13 1.12 2.6 2.7
1.11 1.10 1.11 1.10 2.8 2.9
1.9 1.8 1.9 1.8 2.10 2.11
2_
40 2
39
1.7 1.6 PWR 1.7 1.6 2.12 2.13
PWR
1.5 1.4 IN 1.5 1.4 2.14 2.15
OUT 0
X1 X2
0
1
1.3 1.2 1 1.3 1.2 S/S S/S
2
2 1.1 1.0 3 1.1 1.0 - -
3 4
4 - - 5 - - 3.0 3.1
5 6
6 C0 C0 7 S/S0 S/S0 3.2 3.3
7
0.15 0.14 X0 X3 8 0.15 0.14 3.4 3.5
8 9
9
0.13 0.12 10 0.13 0.12 3.6 3.7
10 11
11
0.11 0.10 12 0.11 0.10 3.8 3.9
2 40
13
1
12 0.9 0.8 14
0.9 0.8 3.10 3.11
13
15
14 0.7 0.6 0.7 0.6 3.12 3.13
15
0.5 0.4 0.5 0.4 3.14 3.15
0.3 0.2 0.3 0.2 S/S1 S/S1
0.1 0.0 0.1 0.0 - -
AS64AN02T-A
- - 2.0 2.1
C0 C0 2.2 2.3
64AN 1.15 1.14 2.4 2.5
0 1 01
2-15
AS Series Module Manual
1. AS32AM10N-A/AS64AM10N-A
_2 TB1
TB2
#1
#2
AS32AM10N-A/ AS64AM10N-A
TB1 X0.0 X0.2 X0.4 X0.6 X0.8 X0.10 X0.12 X0.14 S/S -
#2
TB2 X0.1 X0.3 X0.5 X0.7 X0.9 X0.11 X0.13 X0.15 S/S -
AS series terminals:
Upper
X0.0 X0.2 X0.4 X0.6 X0.8 X0.10 X0.12 X0.14 X1.0 X1.2 X1.4 X1.6 X1.8 X1.10 X1.12 X1.14 S/S S/S
row
Lower
X0.1 X0.3 X0.5 X0.7 X0.9 X0.11 X0.13 X0.15 X1.1 X1.3 X1.5 X1.7 X1.9 X1.11 X1.13 X1.15 S/S S/S
row
2-16
Ch a pt er 2 D ig i ta l I np ut /O ut pu t M od u l es
UB-10-ID16A
TB1
TB2 2_
#1
#2
AS332T-A
TB1 Y0.0 Y0.2 Y0.4 Y0.6 Y0.8 Y0.10 Y0.12 Y0.14 C0 -
#1
TB2 Y0.1 Y0.3 Y0.5 Y0.7 Y0.9 Y0.11 Y0.13 Y0.15 C0 -
UB-10-OT32A
AS series terminals:
Upper
Y0.0 Y0.2 Y0.4 Y0.6 Y0.8 Y0.10 Y0.12 Y0.14 Y1.0 Y1.2 Y1.4 Y1.6 Y1.8 Y1.10 Y1.12 Y1.14
row
Lower
Y0.1 Y0.3 Y0.5 Y0.7 Y0.9 Y0.11 Y0.13 Y0.15 Y1.1 Y1.3 Y1.5 Y1.7 Y1.9 Y1.11 Y1.13 Y1.15 C0 C0
row
UB-10-OR16A
Terminals:
GND +24
V
C0 Y0 Y1 Y2 Y3 C1 Y4 Y5 Y6 Y7 C2 Y10 Y11 Y12 Y13 C3 Y14 Y15 Y16 Y17
AS series terminals:
GND +24V
C0 Y0.0 Y0.1 Y0.2 Y0.3 C1 Y0.4 Y0.5 Y0.6 Y0.7 C2 Y0.8 Y0.9 Y0.10 Y0.11 C3 Y0.12 Y0.13 Y0.14 Y0.15
2-17
AS Series Module Manual
UB-10-IO32D
_2
2-18
3
Chapter 3 Analog Input Module
AS04/08AD
Table of Contents
3.1 Overview ........................................................................................ 3-2
3.1.1 Characteristics ............................................................................... 3-2
3.2 Specifications and Functions .......................................................... 3-3
3.2.1 Specifications ................................................................................ 3-3
3.2.2 Profile........................................................................................... 3-5
3.2.3 Arrangement of Terminals ............................................................... 3-6
3.2.4 AS04AD Control Register ................................................................ 3-6
3.2.5 AS08AD Control Registers ............................................................. 3-11
3.2.6 Functions .................................................................................... 3-17
3.2.7 Wiring ........................................................................................ 3-20
3.2.8 LED Indicators ............................................................................. 3-24
3.3 HWCONFIG in ISPSoft .................................................................. 3-24
3.3.1 Initial Setting .............................................................................. 3-24
3.3.2 Checking the Version of a Module................................................... 3-27
3.3.3 Online Mode ................................................................................ 3-28
3.3.4 Importing/Exporting a Parameter File ............................................. 3-29
3.3.5 Parameters ................................................................................. 3-30
3.4 DIADesigner-AX (Hardware Configuration) .................................. 3-34
3.4.1 Initial Setting .............................................................................. 3-34
3.4.2 Checking the Version of a Module................................................... 3-37
3.4.3 Online Mode ................................................................................ 3-38
3.4.4 Parameters ................................................................................. 3-39
3.5 Troubleshooting ........................................................................... 3-41
3.5.1 Error Codes ................................................................................. 3-41
3.5.2 Troubleshooting Procedure ............................................................ 3-42
A S S er i es Mo d u le Ma n ua l
3.1 Overview
This chapter describes the specifications for analog-to-digital modules, their operation, and their programming.
In this chapter, “module” refers to the analog-to-digital modules AS04AD-A, AS08AD-B, and AS08AD-C.
3.1.1 Characteristics
(1) Select a module based on its practical application.
AS04AD-A: Has four channels. A channel can receive either voltage or current input.
Conversion accuracy: The error range for both voltage input and current input is ±0.2% at ambient
is 100.
The HWCONFIG utility software is built into ISPSoft. You can set modes and parameters directly in
HWCONFIG without spending time writing programs to set registers to manage functions.
3-2
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
Number of Inputs 4 8 8
Analog-to-Digital
Voltage input/Current input Voltage input Current input
Conversion
optocoupler, but the analog channels are not isolated from one another.
Weight 145g
Functional specifications
Analog-to-Digital
Voltage Input
Conversion
Absolute Input
±15 V
Range*3
3-3
A S S er i es Mo d u le Ma n ua l
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the
input signal is below the lower limit, it only shows the minimum value.
*2: If the input signal exceeds the hardware input limit, it also exceeds the digital conversion limit and a
conversion limit error appears. For example in the voltage input mode (-10 V to +10 V), when the input
signal is 10.15 V, exceeding the hardware upper limit, it also exceeds the conversion upper limit. The
module uses the upper limit value (32387) as the input signal and a conversion limit error appears.
*3: If an input signal exceeds the absolute range, it might damage the channel.
_3
Analog-to-Digital
Current Input
Conversion
Hardware Input
-20.24 mA ~ 20.24 mA -0.24 mA ~ 20.24 mA 3.81 mA ~ 20.19 mA
Limit*1
K-32384 K-384 K-384
Conversion Limit*2 ~ ~ ~
K32384 K32384 K32384
Absolute Input
±32 mA
Range*3
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the
input signal is below the lower limit, it only shows the minimum value.
*2: If the input signal exceeds the hardware input limit, it also exceeds the digital conversion limit and a
conversion limit error appears. For example in the voltage input mode (4 mA to 20 mA), when the input
signal is 0 mA, exceeding the hardware upper limit, it also exceeds the conversion upper limit. The
module uses the upper limit value (-384) as the input signal and a conversion limit error appears.
*3: If an input signal exceeds the absolute range, it might damage the channel.
3-4
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3.2.2 Profile
AS04AD-A
38.2 95
04AD 1
7
7
V 1+ V 2+
P WR
I1 + I2 +
V I1- V I2- E RR 2
98.3
A D
88
V 3+ V 4+
I3 + I4 +
V I3- V I4-
3
8 S LD S LD
AG 2 4V
4
3_
0V
9 5
6 75
35
Unit: mm
Arrangement of the
4 Arrangement of the terminals
Input/Output Terminals
6 DIN Rail Clip Secures the module onto the DIN rail
8 Ground Clip
9 Label Nameplate
3-5
A S S er i es Mo d u le Ma n ua l
V I2-
_3
V I1- E RR V3+ V4+ ERR I3+ I4+ ERR
A D A D A D
V 3+ V 4+ V3- V4- I3- I4-
AG 2 4V AG 24V AG 24V
0V 0V 0V
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
1: floating point format
0: closed
1 Channel 1 mode setup
1: -10 V to +10 V
3-6
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
8: -20 mA to +20 mA
5 Channel 1 offset
6 Channel 2 offset
Range: -32768 to +32767 R/W 0
7 Channel 3 offset
8 Channel 4 offset
9
3_
Channel 1 gain
10 Channel 2 gain
Range: -32768 to +32767 R/W 1000
11 Channel 3 gain
12 Channel 4 gain
Channel 1 average
13
times
Channel 2 average
14
times
Range: 1–100 R/W 10
Channel 3 average
15
times
Channel 4 average
16
times
Channel 1 filter
17
average percentage
Range: 0–3
Channel 2 filter
18 Unit: ±10%
average percentage
1: ±10% R/W 1
Channel 3 filter
19 2: ±20%
average percentage
3: ±30%
Channel 4 filter
20
average percentage
0: 2 ms
Channel sampling 1: 4 ms
cycle 2: 10 ms
21 R/W 0
(sampling/integration 3: 15 ms
time) 4: 20 ms
5: 30 ms
3-7
A S S er i es Mo d u le Ma n ua l
6: 40 ms
7: 50 ms
8: 60 ms
9: 70 ms
10: 80 ms
11: 90 ms
12: 100 ms
_3 0: open channel alarm
bit0: channel 1
bit1: channel 2
bit2: channel 3
bit3: channel 4
22 Channel Alarm Setup R/W 0
0: warning
1: alarm
33 The maximum scale maximum value is +10.0 V and the minimum value
10.0
34 range for channel 2 is -10.0 V.
35 The maximum scale If the scale range for an analog to digital input
10.0
36 range for channel 3 channel is 4 mA ~ 20 mA. It indicates the maximum
3-8
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
edit.
1
3_
16#0102: record the peak value again for channel
channels 1–4
201 Instruction Set W 0
16#0201: enable recording for channel 1
3-9
A S S er i es Mo d u le Ma n ua l
3-10
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
3_
1: floating point format
AS08AD-B
2 Channel 2 mode setup
0: closed
1: -10 V to +10 V
3 Channel 3 mode setup 2: 0 V–10 V
3: -5 V to +5 V
5: 1 V–5 V R/W 1
1: -20 mA to +20 mA
2: 0 mA–20 mA
7 Channel 7 mode setup
3: 4 mA–20 mA
9 Channel 1 offset
10 Channel 2 offset
11 Channel 3 offset
12 Channel 4 offset
Range: -32768 to +32767 R/W 0
13 Channel 5 offset
14 Channel 6 offset
15 Channel 7 offset
16 Channel 8 offset
3 - 11
A S S er i es Mo d u le Ma n ua l
17 Channel 1 gain
18 Channel 2 gain
19 Channel 3 gain
20 Channel 4 gain
Range: -32768 to +32767 R/W 1000
21 Channel 5 gain
22 Channel 6 gain
23 Channel 7 gain
_3
24 Channel 8 gain
3-12
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
percentage
0: 2 ms
1: 4 ms
2: 10 ms
3: 15 ms
4: 20 ms
41 (Sampling/Integration 6: 40 ms R/W 0 3_
Time) 7: 50 ms
8: 60 ms
9: 70 ms
10: 80 ms
11: 90 ms
12: 100 ms
bit0: channel 1
bit1: channel 2
bit2: channel 3
bit3: channel 4
bit4: channel 5
bit5: channel 6
42 Channel Alarm Setup R/W 0
bit6: channel 7
bit7: channel 8
0: warning
1: alarm
3-13
A S S er i es Mo d u le Ma n ua l
58 for channel 8
Note: You can use PLC instruction DSCLP
59 The maximum scale range
(API0217) and set SM685 to ON to use
60 for channel 1
floating-point operations when a conversion
61 The maximum scale range range needs to edit.
62 for channel 2
64 for channel 3
66 for channel 4
R 10.0
67 The maximum scale range
68 for channel 5
70 for channel 6
72 for channel 7
74 for channel 8
3-14
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
channel 1
channel 2
channel 3
channels 1-4
201 Instruction Set W 0
16#0201: enable recording for channel 1
3-15
A S S er i es Mo d u le Ma n ua l
3-16
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3.2.6 Functions
Disconnection Disconnection detection only operates when the analog range is 4 mA–
4
3_
Detection 20 mA or 1 V–5 V.
If an input signal exceeds the range of inputs that the hardware can
Channel Detect and
5 receive, the module produces an alarm or a warning. You can disable
Alarm
this function.
Records for
Channels
7 Save the analog curves for channels
(Applicable for
AS04AD)
8 Scale Range When the format is floating-point, you can set the scale range.
1. Enable/Disable a channel
An analog signal is converted into a digital signal at a rate of 2 ms per channel. The total conversion time is
2 ms X (the number of channels). If a channel is not used, you can disable it to decrease the total
conversion time.
2. Calibration
To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The
calibration range depends on the range of inputs that the hardware can receive. The formula is:
Example:
A channel receives voltage inputs between -10.0 V to +10.0 V. The gain is 1000, and the offset is 0. The
corresponding value for the original signal -10.0 V to +10.0 V is -32000 to +32000. If you change the offset to -
100, the calibrated value for the original signal -10.0 V to +10.0 V becomes -31900 to +32100.
3-17
A S S er i es Mo d u le Ma n ua l
Original signals
1 0V S igna ls aft er t he ca libration
3200 0 32100
Digita l v alue (X)
-10V
Voltag e (Y)
Analog s ig nal
_3
3. Average
You can set the average value between 1–100. It is a steady value obtained from the sum of the recorded
values. If the recorded values include an acute pulse due to unavoidable external factors, however, you
may observe violent changes in the average value. Use the filtering function to exclude acute pulses from
the sum-up and equalization, so that the computed average value is not affected by the acute recorded
values. Set the filter percentage to the range 0–3, where the unit is 10%. If you set the filter range to 0, the
system sums up all the recorded values and divides them to obtain the average value, but if you set the
filter range to 1, for example, the system excludes the bottom 10% and top 10% of the values and
averages only the remaining values to obtain the average value. For instantance, set the average value to
100 and set the filter percentage to 3. When there are 100 pieces of data collected, the system arranges
the collected data according to their values from large to small and then excludes the bottom 30% and top
30% of the values (60 pieces of data) and averages only the remaining values (40 pieces of data) to
4. Disconnection detection
Disconnection detection only operates when the analog range is 4–20 mA or 1–5 V. If a module that can
receive inputs between 4–20 mA or from 1–5 V is disconnected, the input signal exceeds the range of
3-18
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
5. Channel detection
If an input signal exceeds the allowable range of inputs, an error message appears. You can disable this
function so that the module does not produce an alarm or a warning when the input signal exceeds the
input range.
This function saves the maximum and minimum values for channels so that you can determine the peak to
peak values.
Maximum valu e
Mini mu m va lue
Time
Record the input values of the cyclic sampling for each channel. The system saves up to 500 data
Ti me
Instru cti on for recordi ng Recordin g e nds
8. Scale range
You can set the scale range when the format is floating-point. The analog output mode of a channel has
a corresponding digital range. Digital values correspond to analog outputs sent by the module. For
example, if the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0,
and the LSP scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to
+10 V, as the example below shows.
3-19
A S S er i es Mo d u le Ma n ua l
Analog value
10 V
-10 V
Digital value
-10.0 10.0
_3 Scale range
3.2.7 Wiring
Precautions
To ensure the analog-to-digital module functions well and reliably, the external wiring must prevent noise.
(1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the
(2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load that is
not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable, or a cable
(4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the
(5) Use single-core cables or twin-core cables in a diameter of 24 AWG–22 AWG with pin-type connectors
smaller than 1 mm. Use only copper conducting wires that can resist temperatures above 60° C-75° C.
Four-wire connection (active transducer): the transducer uses an independent power supply so
do not connect it to the same power circuit as the analog input module.
(7) Note: use cables with the same length (less than 200 m) and use wire resistance of less than 100 ohm.
3-20
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
AG
*6
4-wir e: v ol tage inp ut
CHX
-10 V~ + 10 V Shi eld ed cabl e *1 1M
+ V I+
+ 2 4V 250 CH1
- *3 I1 +
0V 1M
VI 1-
*4
FE
*6 AG
4-wir e: c urr ent inp ut CHX
-20 mA ~ +2 0 mA Shi eld ed c abl e *1 1M
V 2+
+ *2 25 0 CH2
+ 24 V I2 +
- 1M
0V V I2 -
*4
+ 2 4V CH X
+ 1M
V4 +
25 0 CH4
0V - I 4+
1M
*4 V I4 -
FE
+ 15 V
0V D C /D C
24 VD C AG
24 V C on ve rt e r
-15 V
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–4) must be short-circuited.
*3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor
*6. Every channel can operate with the wiring presented above.
3-21
A S S er i es Mo d u le Ma n ua l
4 -w ire vo lt ag e inp u t AG
-10 V~ + 10 V Sh ield ed c ab le* 1 *5
CHX 1M
+ 2 4V +
V 1+
- *2 1M
0V V1 -
*3
FE
3 - wire v olt ag e in pu t
-1 0 V~ + 10 V S hie ld ed ca b le* 1 *5 AG
_3
CH X
+ 2 4V + 1M
V2 +
0V -
1M
V 2-
*3
FE
*4
+ 1 5V
0V D C / DC
2 4 VD C C on ve rte r AG
2 4V
-1 5V
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor
*5. Every channel can operate with the wiring presented above.
3-22
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
4 -w ire cu rren t in pu t AG
*4
-2 0m A~ + 2 0m A Sh ield ed cab le* 1
CHX
1M
+ 2 4V +
I1 +
- 2 50 1M
0V I1 -
*2
FE
2- w ire curre nt in pu t
4m A~ + 20 m A
+ 24 V
Sh ield ed cab le* 1 *4 AG
+
CHX
3_
- 1M
I2 +
250 1M
0V I2 -
*2
FE
+ 1 5V
0V D C /D C
2 4 VD C C on ve rt e r AG
2 4V
-1 5V
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*4. Every channel can operate with the wiring presented above.
3-23
A S S er i es Mo d u le Ma n ua l
3-24
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3_
(3) Double-click the module in the working area to open the Device Setting page.
3-25
A S S er i es Mo d u le Ma n ua l
_3
3-26
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
(5) Click Download on the toolbar to download the parameters. Note that you cannot download the
3_
3-27
A S S er i es Mo d u le Ma n ua l
(2) Double-click the module to open the Device Setting page. The versions of both the firmware and the
_3
3-28
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3_
3-29
A S S er i es Mo d u le Ma n ua l
(2) Click Import in the Device Settings dialog box and select a CSV file to import saved parameters.
_3
3.3.5 Parameters
(1) The input formats of the channels
3-30
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3_
3-31
A S S er i es Mo d u le Ma n ua l
_3
3-32
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3_
3-33
A S S er i es Mo d u le Ma n ua l
_3
3-34
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3_
3-35
A S S er i es Mo d u le Ma n ua l
(5) After setting is complete, select the module and click Login on the tool bar to download the settings to the
modules.
_3
3-36
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
(2) Select the module and click Login on the tool bar to go to Online Mode. You can find the Module Revision
from the Parameters tab.
3_
3-37
A S S er i es Mo d u le Ma n ua l
_3
(2) You can monitor the values, status, error codes in each channel from the I/O Mapping tab.
(3) You can monitor the current status and error codes from the Status tab.
3-38
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3.4.4 Parameters
(1) You can set up the value format to Integer or Floating for Channel 1 to 4.
3_
3-39
A S S er i es Mo d u le Ma n ua l
(6) You can set up the channel detect and alarm settings.
_3
3-40
Ch a pt er 3 A na l o g In pu t M od u l e A S0 4 /0 8 A D- A
3.5 Troubleshooting
3.5.1 Error Codes
Blinking once
or twice and
after 2
- When power-on, the module is not detected by CPU module. OFF
seconds, it
blinks
repeatedly
3-41
A S S er i es Mo d u le Ma n ua l
Description Procedure
Internal error
Contact the factory.
The factory calibration is abnormal.
When power-on, the module is not detected by Check if the connection between module and CPU
3-42
4
Chapter 4 Analog Output Module AS04DA
Table of Contents
4.1 Overview ........................................................................................ 4-2
4.1.1 Characteristics ........................................................................... 4-2
4.2 Specifications and Functions .......................................................... 4-3
4.2.1 Specifications ............................................................................. 4-3
4.2.2 Profile ....................................................................................... 4-5
4.2.3 Arrangement of Terminals ........................................................... 4-6
4.2.4 Control Registers ........................................................................ 4-6
4.2.5 Functions ................................................................................... 4-8
4.2.6 Wiring ..................................................................................... 4-12
4.2.7 LED Indicators .......................................................................... 4-14
4.3 HWCONFIG in ISPSoft .................................................................. 4-14
4.3.1 Initial Setting ........................................................................... 4-14
4.3.2 Checking the Version of a Module ............................................... 4-17
4.3.3 Online Mode ............................................................................. 4-18
4.3.4 Importing/Exporting a Parameter File .......................................... 4-19
4.3.5 Parameters .............................................................................. 4-20
4.4 DIADesigner-AX (Hardware Configuration) .................................. 4-23
4.4.1 Initial Setting ........................................................................... 4-23
4.4.2 Checking the Version of a Module ............................................... 4-26
4.4.3 Online Mode ............................................................................. 4-27
4.4.4 Parameters .............................................................................. 4-28
4.5 Troubleshooting ........................................................................... 4-30
4.5.1 Error Codes.............................................................................. 4-30
4.5.2 Troubleshooting Procedure ......................................................... 4-30
A S S er i es Mo d u le Ma n ua l
4.1 Overview
An analog output module receives four 12-bit blocks of digital data from a CPU module. The module converts
4.1.1 Characteristics
(1) Select a module based on its practical application.
AS04DA-A: Has four channels. A channel can send either voltage or current output.
_4 Conversion accuracy: The error range for both voltage output and current output is ±0.2% at ambient
temperature of 25° C.
The HWCONFIG utility software is built into ISPSoft. You can set modes and parameters directly in
HWCONFIG without spending time writing programs to set registers to manage functions.
4-2
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
Number of Outputs 4
Digital-to-Analog
Voltage input/Current input
Conversion
Weight 145 g
Functional specifications
Digital-to-Analog
Voltage Output
Conversion
Error Rate
±0.2%
(Room Temperature)
Linearity error
±0.05%
(Room Temperature)
4-3
A S S er i es Mo d u le Ma n ua l
Digital-to-Analog
Voltage Output
Conversion
Error Rate
±0.2%
(Room Temperature)
_4 Error Rate
±0.5%
(Full Temperature Range)
4-4
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
4.2.2 Profile
38.2 95
04DA 1
7
7
VO1 VO2
P WR
IO1 IO2
AG AG E RR 2
98.3
D A
88
SLD SLD
VO3 VO4
IO3 IO4
3
8 AG AG
SLD SLD
24V
0V
4
9 5
6 75
35
unit: mm
Removable Terminal
3 Outputs are connected to loads to be driven.
Block
Arrangement of the
4 Arrangement of the terminals
Input/Output Terminals
6 DIN Rail Clip Secures the module onto the DIN rail
8 Ground Clip
9 Label Nameplate
4-5
A S S er i es Mo d u le Ma n ua l
AS04DA-A
04DA
VO1 VO2
P WR
IO1 IO2
AG AG E RR
D A
SLD SLD
VO3 VO4
IO3 IO4
AG AG
SLD SLD
_4
24V
0V
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
1: floating-point format
0: closed
1 Channel 1 mode setup R/W
1: -10 V to +10 V (default)
2: 0 V–10 V
2 Channel 2 mode setup R/W
3: -5 V to +5 V
1
4: 0 V–5 V
3 Channel 3 mode setup R/W
5: 1 V–5 V
6: 0 mA–20 mA
4 Channel 4 mode setup R/W
7: 4 mA–20 mA
4-6
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
6 Channel 2 offset
7 Channel 3 offset
8 Channel 4 offset
9 Channel 1 gain
10 Channel 2 gain
Range: -32768 to +32767 R/W 1000
11 Channel 3 gain
12 Channel 4 gain
Retaining an output
13
sent by channel 1
Retaining an output 0: when the PLC stops, the value of the analog output
14
sent by channel 2 is reset to 0.
R/W 0
4_
Retaining an output 1: when the PLC stops, the value of the analog output
15
sent by channel 3 is retained.
Retaining an output
16
sent by channel 4
channel 4
21 When the format is set to integer in HWCONFIG, the R
The minimum scale
-10.0
range for channel 1
22 scale range is invalid. R
25 The minimum scale values for earier understanding. Here you can set the R
-10.0
26 range for channel 3 minimum and maximum scale ranges of corresponding R
4-7
A S S er i es Mo d u le Ma n ua l
28 range for channel 4 For example, if the scale range for an analog to digital R
31 The maximum scale If the scale range for an analog to digital input channel R
10.0
32 range for channel 2 is 4 mA ~ 20 mA. It indicates the maximum value is 20 R
mA and the minimum value is 4 mA.
33 The maximum scale R
10.0
34 range for channel 3 Note: You can use PLC instruction DSCLP (API0217) R
and set SM685 to ON to use floating-point operations
35 R
The maximum scale
range for channel 4 when a conversion range needs to edit. 10.0
36 R
0: warning
1: alarm
_4
37 Channel alarm setup bit0: error in the power supply R/W 0
4.2.5 Functions
When a module stops running, the system can retain the signal sent by the
3 Retain an Output
module.
Refresh Time for an Refresh the analog output value according to the value of the fixed slope.
4
Output
5 Scale Range You can set the scale range when the format is floating-point.
4-8
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
1. Enable/Disable a Channel
An analog signal is converted into a digital signal at a rate of 2 ms per channel. The total conversion time is
2 ms X (the number of channels). If a channel is not used, you can disable it to decrease the total
conversion time.
2. Calibration
To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The
calibration range depends on the range of inputs that the hardware can receive. The formula is:
Example:
A channel receives voltage inputs between -10.0 V to +10.0 V. The gain is 1000, and the offset is 0. The
4_
corresponding value for the original signal -10.0 V to +10.0 V is -32000 to +32000. If you change the offset to -
100, the calibrated value for the original signal -10.0 V to +10.0 V becomes -31900 to +32100.
Original signals
1 0V S igna ls aft er t he ca libration
3200 0 32100
Digita l v alue (X)
-10V
Voltag e (Y)
Analog s ig nal
4-9
A S S er i es Mo d u le Ma n ua l
3. Retain an Output
When a module stops running, the system can retain the signal sent by the module.
Input si gnal
Output signal
Anal og si gnal
Output signal
4-10
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
Set the refresh time for an output and the system updates the value of the slope (m) accordingly.
Anal og si gnal
4_
When the analog output signal changes, the system updates the value of the analog output according to the
Analog si gnal
Time
4 - 11
A S S er i es Mo d u le Ma n ua l
5. Scale Range
You can set the scale range when the format is floating-point. The analog output mode of a channel has a
corresponding digital range. Digital values correspond to analog outputs sent by the module. For example, if
the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0, and the LSP
scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to +10 V, as the
Analog value
10 V
_4 -10 V
Digital value
-10.0 10.0
Scale range
4.2.6 Wiring
Precautions
To ensure the digital-to-analog module functions well and reliably, the external wiring must prevent noise.
(1) To prevent a surge and induction, the AC cable and the output signal cables that are connected to the
(2) Do not install or bound the cable to a main circuit, a high-voltage cable, or a cable connected to a
load that is not a PLC.
(4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the
(5) Connect 24 to 22 AWG (1 mm) wires to the input/output terminals. The plastic jackets that are
removed from the cables should be 8 mm to 10 mm long. The specifications for the terminals and the
wiring of the terminals are shown below. Use only copper leads that can resist temperatures above
60° C /75° C.
ohm.
4-12
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
External wiring
Voltage output
- 10V~+1 0V *4
CHX
VO1 CH1
*2
IO1
AC m otor driv e, Shielded c able* 1 AG
AG
recorder, SL D
proportioning v alv e
Current output *4
CHX
0 mA ~20 mA
VO4 CH4
IO4
AG
AG
AC motor driv e, Shielded cable*1 SLD
recorder,
proporti oni ng v al ve *3
FE
+15 V 4_
0V DC/DC
24VDC AG
2 4V C on ve rte r
-15V
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor
*3. Connect the SLD to FE, and connect both the FE and the terminal to the ground terminal.
*4. Every channel can operate with the wiring presented above.
4-13
A S S er i es Mo d u le Ma n ua l
_4
Conversion Indicator
OFF: conversion has stopped.
4-14
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
4_
(3) Double-click the module in the working area to open the Device Setting page.
4-15
A S S er i es Mo d u le Ma n ua l
_4
(4) Choose a parameter, set the values, and click OK.
4-16
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
(5) Click Download on the toolbar to download the parameters. Note you cannot download the parameters
cannot be downloaded.
4_
4-17
A S S er i es Mo d u le Ma n ua l
(2) Double-click the module to open the Device Setting page. The versions of both the firmware and the
hardware are displayed.
_4
4-18
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
4_
4-19
A S S er i es Mo d u le Ma n ua l
(2) Click Import in the Device Settings dialog box and select a CSV file to import save parameters.
_4
4.3.5 Parameters
(1) The output formats of the channels
4-20
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
4_
4-21
A S S er i es Mo d u le Ma n ua l
_4
4-22
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
4_
4-23
A S S er i es Mo d u le Ma n ua l
_4
(4) Module parameter setting page:
4-24
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
(5) After setting is complete, select the module and click Login on the tool bar to download the settings to the
modules.
4_
4-25
A S S er i es Mo d u le Ma n ua l
(2) Select the module and click Login on the tool bar to go to Online Mode. You can find the Module Revision
from the Parameters tab.
_4
4-26
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
4_
(2) You can monitor the values, status, error codes in each channel from the I/O Mapping tab. You can also
set a new value in the colum of Prepared Value and press Ctrol+F7 on the keyboard to write the new
values in.
(3) You can monitor the current status and error codes from the Status tab.
4-27
A S S er i es Mo d u le Ma n ua l
4.4.4 Parameters
(1) You can set up the value format to Integer or Floating for Channel 1 to 4.
_4
4-28
Ch a pt er 4 A na l o g O u tp ut M o du l e A S 0 4D A
(6) You can set up the channel detect and alarm settings.
4_
4-29
A S S er i es Mo d u le Ma n ua l
4.5 Troubleshooting
4.5.1 Error Codes
_4 Blinking once
or twice and
after 2
- When power-on, the module is not detected by CPU module. OFF
seconds, it
blinks
repeatedly
Description Procedure
Internal error
Contact the factory.
The factory calibration is abnormal.
When power-on, the module is not detected by Check if the connection between module and CPU
4-30
5
Chapter 5 Analog Input/Output Module
AS06XA
Table of Contents
5.1 Overview ....................................................................................... 5-2
5.1.1 Characteristics ........................................................................... 5-2
5.2 Specifications and Functions ......................................................... 5-3
5.2.1 Specifications ............................................................................ 5-3
5.2.2 Profile ...................................................................................... 5-6
5.2.3 Arrangement of Terminals ........................................................... 5-7
5.2.4 Control Registers ....................................................................... 5-8
5.2.5 Functions .................................................................................5-13
5.2.6 Wiring .....................................................................................5-20
5.2.7 LED Indicators ..........................................................................5-22
5.3 HWCONFIG in ISPSoft ................................................................. 5-23
5.3.1 Initial Setting ...........................................................................5-23
5.3.2 Checking the Version of a Module ...............................................5-26
5.3.3 Online Mode .............................................................................5-27
5.3.4 Importing/Exporting a Parameter File ..........................................5-28
5.3.5 Parameters ..............................................................................5-29
5.4 DIADesigner-AX (Hardware Configuration) ................................. 5-34
5.4.1 Initial Setting ...........................................................................5-34
5.4.2 Checking the Version of a Module ...............................................5-37
5.4.3 Online Mode .............................................................................5-38
5.4.4 Parameters ..............................................................................5-39
5.5 Troubleshooting .......................................................................... 5-41
5.5.1 Error Codes ..............................................................................5-41
5.5.2 Troubleshooting Procedure .........................................................5-42
A S S er i es Mo d u le Ma n ua l
5.1 Overview
This chapter describes the specifications for the analog input/output module, its operation, and its
programming. On the analog input/output module, four channels receive analog signals (voltage or current),
and converts those signals into 16-bit digital signals. In addition, the analog input/output module receives two
blocks of 16-bit digital data from a CPU module, and converts the digital data into analog signals (voltage or
current). The analog input/output module sends the analog signals by two channels
5.1.1 Characteristics
(1) Use the AS06XA-A analog input/output module, based on its practical application.
Input: The error range for both voltage and current input is ±0.2%.
Output: The error range for both voltage and current output is ±0.02%.
The HWCONFIG utility software is built into ISPSoft. You can set modes and parameters directly in
HWCONFIG without spending time writing programs to set registers to manage functions.
5-2
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
Analog-to-Digital
Voltage input/Current input/Voltage output/Current output
Conversion
Weight 145 g
Analog-to-Digital
Voltage Input
Conversion
5-3
A S S er i es Mo d u le Ma n ua l
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the
input signal is below the lower limit, it only shows the minimum value.
*2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a conversion
limit error appears. For example in the voltage input mode (-10 V to +10 V), when the input signal is 10.15 V,
exceeding the hardware upper limit, it also exceeds the conversion upper limit. The module uses the upper
limit value (32384) as the input signal and a conversion limit error appears.
*3: If an input signal exceeds the absolute range, it might damage the channel.
Analog-to-Digital
Current Input
Conversion
Hardware Input
_5 Limit*1
-20.24 mA ~ 20.24 mA -0.24 mA ~ 20.24 mA 3.81 mA ~ 20.19 mA
Absolute Input
±32 mA
Range*3
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the
input signal is below the lower limit, it only shows the minimum value.
*2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a conversion
limit error appears. For example in the voltage input mode (4 mA to 20 mA), when the input signal is 0 mA,
exceeding the hardware upper limit, it also exceeds the conversion upper limit. The module uses the upper
limit value (-384) as the input signal and a conversion limit error appears.
*3: If an input signal exceeds the absolute range, it might damage the channel.
5-4
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
Digital-to-Analog
Voltage Output
Conversion
Error Rate
±0.2%
(Room Temperature)
Error Range
±0.5%
(Full temperature range)
Linearity Error
±0.05%
(Room Temperature)
Linearity Error
±0.05% 5_
(Full Temperature Range)
Permissible load
≧1kΩ ≧500Ω
impedance
Digital-to-Analog
Current Output
Conversion
Error Range
±0.2%
(Room Temperature)
Error Range
±0.5%
(Full Temperature Range)
Linearity Error
±0.03%
(Room Temperature)
5-5
A S S er i es Mo d u le Ma n ua l
Permissible Load
≦550 Ω
Impedance
5.2.2 Profile
38.2 95
1
7
7
2
98.3
88
8 3
4
9
5
6 75
35
_5 Unit: mm
Conversion status
Analog-to-Digital
Blinking: conversion is in process.
Conversion Indicator
OFF: conversion has stopped.
Arrangement of the
4 Arrangement of the terminals
Input/Output Terminals
5-6
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
6 DIN Rail Clip Secures the module onto the DIN rail
8 Ground Clip
9 Label Nameplate
06X A
V1+ V2+
P WR
5_
I1+ I2+
VI1- VI2- E RR
A D
V3+ V4+
I3+ I4+
VI3- VI4 -
VO1 VO2
IO1 IO2
AG 24V
0V
5-7
A S S er i es Mo d u le Ma n ua l
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
1: floating point format
0: closed
1 Input channel 1 mode setup
1: -10 V to +10 V (default)
2: 0–10 V
2 Input channel 2 mode setup
3: -5 to +5 V
R/W 1
4: 0–5 V
3 Input channel 3 mode setup
5: 1–5 V
6: 0–20 mA
_5 4 Input channel 4 mode setup 7: 4–20 mA
8: -20 mA to +20 mA
5 Input channel 1 offset
5-8
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
average percentage
0: 2 ms
1: 4 ms
2: 10 ms
3: 15 ms
4: 20 ms
(sampling/integration time)
7: 50 ms 5_
8: 60 ms
9: 70 ms
10: 80 ms
11: 90 ms
12: 100 ms
bit0: channel 1
bit1: channel 2
bit2: channel 3
bit3: channel 4
22 Input channel alarm setup R/W 0
0: warning
1: alarm
5-9
A S S er i es Mo d u le Ma n ua l
0: closed
Output channel 1 mode 1: -10 V to +10 V (default)
23
setup
2: 0–10 V
3: -5 V to +5 V R/W
1
4: 0–5 V
Output channel 2 mode 5: 1–5 V
24
setup 6: 0–20 mA
7: 4–20 mA
Retain the output sent by 0: When the PLC stops, the value of the
29
channel 1 analog output is reset to 0.
_5 R/W 0
Retain the output sent by 1: When the PLC stops, the value of the
30
channel 2 analog output is retained.
41 The minimum scale range For example, if the scale range for an analog
-10.0
42 for output channel 1 to digital input channel is ±10.0 V, it indicates
5-10
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
45 The maximum scale range If the scale range for an analog to digital input
10.0
46 for input channel 1 channel is 4 mA ~ 20 mA. It indicates the
49 The maximum scale range Note: You can use PLC instruction DSCLP
10.0
for input channel 3 (API0217) and set SM685 to ON to use
50
floating-point operations when a conversion
51 The maximum scale range
range needs to edit. 10.0
52 for input channel 4
channel 1
5_
16#0102: record the peak value again for
channel 2
channel 3
channel 4
channels 1–4
201 Instruction Set W 0
16#0201: enable recording for channel 1
5 - 11
A S S er i es Mo d u le Ma n ua l
_5
The minimum peak value
217
for channel 4
5-12
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5.2.5 Functions
Set modes of operation and parameters with HWCONFIG utility software built into ISPSoft.
Analog input
Disconnection Disconnection detection only operates when the analog range is 4–20
4
Detection mA or 1–5 V. 5_
If an input signal exceeds the range of inputs that the hardware can
Channel Detect and
5 receive, the module produces an alarm or a warning. You can disable
Alarm
this function.
Records for
7 Save the analog curves for channels.
Channels
8 Scale Range When the format is floating-point, you can set the scale range.
1. Enable/Disable a Channel
An analog signal is converted into a digital signal at a rate of 2 ms per channel. The total conversion time
is 2 ms X (the number of channels). If a channel is not used, you can disable it to decrease the total
conversion time.
2. Calibration
To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The
calibration range depends on the range of inputs which can be received by the hardware. The formula is:
5-13
A S S er i es Mo d u le Ma n ua l
Example:
A channel receives voltage inputs between -10.0 V to +10.0 V. The gain is 1000, and the offset is 0. The
corresponding value for the original signal -10.0 V to +10.0 V is -32000 to +32000. If you change the offset to
-100, the calibrated value for the original signal -10.0 V to +10.0 V becomes -31900 to +32100. When the
input voltage is 0 V, the digital value becomes -100. When the input voltage is 10.0 V, the digital value
becomes 32100.
-10V
10V Voltage (X)
(X1, Y1) Input analog v alue
(0V, 100)
_5 -10
(Y)
Digital value
3. Average
You can set the average value between 1–100. It is a steady value obtained from the sum of the recorded
values. If the recorded values include an acute pulse due to unavoidable external factors, however, you may
observe violent changes in the average value. Use the filtering function to exclude acute pulses from the
sum-up and equalization, so the computed average value is not affected by the acute recorded values. Set
the filter percentage to the range 0–3, where the unit is 10%. If you set the filter range to 0, the system sums
up all the recorded values and divides them to obtain the average value, but if you set the filter range to 1, for
example, the system excludes the bottom 10% and the top 10% of the values and averages only the
remaining values to get the average value. For instantance, set the average value to 100 and set the filter
percentage to 3. When there are 100 pieces of data collected, the system arranges the collected data
according to their values from large to small and then excludes the bottom 30% and top 30% of the values
(60 pieces of data) and averages only the remaining values (40 pieces of data) to obtain the average value.
5-14
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
Quantity
Range for filter percentage
4. Disconnection detection
Disconnection detection only operates when the analog range is 4–20 mA or 1–5 V. If a module which can
receive inputs between 4–20 mA or between 1–5 V is disconnected, the input signal exceeds the range of
5. Channel Detection
If an input signal exceeds the allowable range of inputs, an error message appears. You can disable this 5_
function so that the module does not produce an alarm or a warning when the input signal exceeds the
input range.
This function saves the maximum and minimum values for channels so that you can determine the peak to
peak values.
Maximum valu e
Mini mu m va lue
Time
5-15
A S S er i es Mo d u le Ma n ua l
Record the input values of the cyclic sampling for each channel. The system saves up to 500 data
Ti me
Instru cti on for recordi ng Recordin g e nds
8. Scale range
When the format is floating-point, you can set the scale range. The analog output mode of a channel
has a corresponding digital range. Digital values correspond to analog outputs sent by the module. For
example, if the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0,
_5
and the LSP scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to
Analog value
-10 V
Digital value
-10.0 10.0
Scale range
5-16
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
Analog Output
When a module stops running, the system retains the signal sent by the
3 Retain an Output
module.
Refresh Time for an Refresh the analog output value according to the value of the fixed slope.
4
Output
5 Scale Range You can set the scale range when the format is floating-point.
1. Enable/Disable a Channel
An analog signal is converted into a digital signal at a rate of 2 ms per channel. The total conversion time
is 2 ms X (the number of channels). If a channel is not used, you can disable it to decrease the total
conversion time.
2. Calibration 5_
To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The calibration
range depends on the range of inputs which can be received by the hardware. The formula is:
Example:
A channel receives voltage inputs between -10.0 V to +10.0 V. The gain is 1000, and the offset is 0. The
corresponding value for the original signal -10.0 V to +10.0 V is -32000 to +32000. If you change the offset to
200 and the gain to 1000, the calibrated value for the original signal -10.0 V to +10.0 V is -31800 to +32200.
Original signals
1 0V S igna ls aft er t he ca libration
-10V
Voltag e (Y)
Analog s ig nal
5-17
A S S er i es Mo d u le Ma n ua l
3. Retain an Output
When a module stops running, the system retains the signal sent by the module.
Analog signal
Output signal
Time
_5
4. Refresh Time for an Output
Set the refresh time for an output and the system updates the value of the slope (m) accordingly.
Anal og si gnal
5-18
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
When the analog output signal changes, the system updates the value of the analog output according to
Analog si gnal
Time
*The output conversion time and the input channel sampling cycle are the same.
5. Scale Range
You can set the scale range when the format is floating-point. The analog output mode of a channel has
a corresponding digital range. Digital values correspond to analog outputs sent by the module. For
5_
example, if the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0,
and the LSP scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to
Analog value
10 V
-10 V
Digital value
-10.0 10.0
Scale range
5-19
A S S er i es Mo d u le Ma n ua l
5.2.6 Wiring
Precautions
To ensure the analog-to-digital module functions well and reliably, the external wiring must prevent noise.
(1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the
(2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load that
is not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable, or a
(4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the
(5) Use single-core cables or twin-core cables with a diameter of 24–22 AWG and with pin-type
_5 connectors smaller than 1 mm. Only use copper conducting wires which can withstand temperatures
(6) Note: use cables with the same length (less than 200 m) and use wire resistance of less than 100
ohm.
Four-wire connection (active transducer): the transducer uses an independent power supply, so
do not connect it to the same power circuit as the analog input module.
5-20
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
External wiring
(1) AS06XA-A
AG
4-wire: vo lt ag e inp ut *8
-10 V~ +1 0V
Sh ield ed cabl e *1 C HX -I
1M
+ V1 +
+2 4V 25 0 CH 1
- *3 I1+
0V 1M
VI1 -
*6
FE
*8 AG
4-wire: cu rrent i np ut C HX -I
-20 mA~ + 20 mA Sh ield ed cabl e *1 1M
V 2+
+ *2 25 0 CH2
+ 24 V I2 +
- 1M
0V VI 2-
*6
2-wi re: cur rent in put FE
4 mA ~+ 20 mA
*8 AG
+ 24V Sh ield ed cabl e *1 CH X-I
+ 1M
V 3+
- *2
25 0 CH3
I3 +
1M
0V VI 3-
*6
FE
3-wir e: vol tage in put
-10 V~ +1 0V Sh ield ed cabl e *1 *8 AG
C HX -I
5_
+2 4V + 1M
V4 +
2 50 C H4
0V - I 4+
1M
*6 V I4 -
FE
3-wire: cu rrent i np ut
*8 AG
-2 0m A~ +2 0m A Sh ield ed cabl e *1 C HX -I
+ 2 4V 1M
+ *2 V 1+
2 50 C H1
I1 +
0V - 1M
V I1 -
*6
FE
AC motor dr ive,
rec order, Vol tage o utput
-10 V~+ 1 0V *8
proportioning v alv e C HX-O
VO1 C H5
*5
IO1
AG
Sh ield ed cabl e *4 * 6 AG
FE
AC motor dr ive, *8
rec order, Current output CH X-O
proportioning v alv e 0m A~2 0m A
VO2 CH6
IO2
AG
AG
Sh ield ed cabl e *4 * 6
FE
*7
+1 5V
0V D C /D C
24 VD C AG
24 V C o nv ert er
-15 V
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–4) must be short-circuited.
*3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor
5-21
A S S er i es Mo d u le Ma n ua l
*4. Connect the shielded cable to the terminal FE and to the ground terminal.
*6. The wording “CHX-I” indicates that you can use those five wiring methods for every input channel. The
wording “CHX-O” indicates that you can use those two wiring methods for every output channel.
5-22
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5_
5-23
A S S er i es Mo d u le Ma n ua l
(3) Double-click the module in the working area to open the Device Setting page.
_5
5-24
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
(4) Choose the parameter, set the values, and click OK.
(5) Click Download on the toolbar to download the parameters. Note that you cannot download the
5-25
A S S er i es Mo d u le Ma n ua l
_5
(2) Double-click the module to open the Device Setting page. The versions of both the firmware and the
5-26
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5_
(2) Right-click the module and click Module Status.
5-27
A S S er i es Mo d u le Ma n ua l
_5
(2) Click Import in the Device Settings dialog box and select a CSV file to import saved parameters.
5-28
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5.3.5 Parameters
(1) The input modes of the channels
5-29
A S S er i es Mo d u le Ma n ua l
_5
5-30
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5_
5-31
A S S er i es Mo d u le Ma n ua l
_5
5-32
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5_
5-33
A S S er i es Mo d u le Ma n ua l
_5
5-34
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5_
(4) Module parameter setting page:
5-35
A S S er i es Mo d u le Ma n ua l
(5) After setting is complete, select the module and click Login on the tool bar to download the settings to
the modules.
_5
5-36
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
(2) Select the module and click Login on the tool bar to go to Online Mode. You can find the Module
Revision from the Parameters tab.
5_
5-37
A S S er i es Mo d u le Ma n ua l
_5 (2) You can monitor the values, status, error codes in each channel from the I/O Mapping tab. You can also
set a new value in the colum of Prepared Value and press Ctrol+F7 on the keyboard to write the new
values in.
(3) You can monitor the current status and error codes from the Status tab.
5-38
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5.4.4 Parameters
(1) You can set up the value format to Integer or Floating for Channel 1 to 4.
5-39
A S S er i es Mo d u le Ma n ua l
(6) You can set up the channel detect and alarm settings.
_5 (7) You can set up the output channel mode for Channel 1 and 2.
(8) You can set up the calibrations for output Channel 1 and 2.
(9) You can set up the output settings for output Channel 1 and 2.
5-40
Ch a pt er 5 An a l og I n pu t/O ut p ut M o du l e A S0 6 X A
5.5 Troubleshooting
5.5.1 Error Codes
Blinking once
or twice and
after 2
- When power-on, the module is not detected by CPU module. OFF
seconds, it
blinks
repeatedly
5-41
A S S er i es Mo d u le Ma n ua l
Description Procedure
Internal error
Contact the factory.
The factory calibration is abnormal.
When power-on, the module is not detected by Check if the connection between module and CPU
5-42
6
Chapter 6 Temperature Measurement
Module AS04/06RTD
Table of Contents
6.1 Overview ............................................................................................ 6-2
6.1.1 Characteristics ............................................................................... 6-2
6.2 Specifications and Functions .............................................................. 6-3
6.2.1 Specifications ................................................................................. 6-3
6.2.2 Profile ........................................................................................... 6-6
6.2.3 Arrangement of Terminals ................................................................ 6-7
6.2.4 AS04RTD Control Registers .............................................................. 6-8
6.2.5 AS06RTD Control Registers ............................................................ 6-12
6.2.6 Functions..................................................................................... 6-17
6.2.7 Control Mode ............................................................................... 6-20
6.2.8 Wiring ......................................................................................... 6-20
6.2.9 LED Indicators .............................................................................. 6-22
6.3. HWCONFIG in ISPSoft ..................................................................... 6-23
6.3.1 Initial Setting ............................................................................... 6-23
6.3.2 Checking the Version of a Module .................................................... 6-26
6.3.3 Online Mode ................................................................................. 6-27
6.3.4 Importing/Exporting a Parameter File .............................................. 6-28
6.3.5 Parameters .................................................................................. 6-29
6.4 DIADesigner-AX (Hardware Configuration) ...................................... 6-32
6.4.1 Initial Setting ............................................................................... 6-32
6.4.2 Checking the Version of a Module .................................................... 6-34
6.4.3 Online Mode ................................................................................. 6-35
6.4.4 Parameters .................................................................................. 6-36
6.5 Troubleshooting ............................................................................... 6-38
6.5.1 Error Codes.................................................................................. 6-38
6.5.2 Troubleshooting Procedure ............................................................. 6-39
6.5.3 State of the Connection ................................................................. 6-40
AS Ser ies M od ul e Man ua l
6.1 Overview
This section describes the specifications for temperature measurement modules, their operation, and their
programming. The AS04/06RTD is a temperature measurement module that converts the temperatures
received from four/six thermocouples into digital signals. You can select either Celsius or Fahrenheit as the
unit of measurement.
6.1.1 Characteristics
(1) Select a sensor based on its practical application.
Conversion accuracy: The error range of the input is ±0.1% at ambient temperature of 25° ±5° C.)
_6
An object’s temperature can be maintained through PID control actions.
The HWCONFIG utility software is built into ISPSoft. You can set modes and parameters directly in
HWCONFIG without spending time writing programs to set registers to manage functions.
6-2
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
Number of Analog
4 6
Inputs
300 Ω/0–3000 Ω
LG-Ni1000
Cu50/Cu100
Pt100/Ni100/Pt1000/Ni1000/JPt100
Cu50; 25° C/77° F: The allowed error range is ±4% of full scale.
Cu100; 25° C/77° F: The allowed error range is ±2% of full scale.
optocoupler, and the analog channels are isolated from one another by
optocouplers.
Isolation Isolation between a digital circuit and the ground: 500 VDC
Isolation between an analog circuit and the digital circuit: 500 VDC
6-3
AS Ser ies M od ul e Man ua l
Functional specifications
Analog-to-Digital
Centigrade (°C) Fahrenheit (°F) Input Impedance
Conversion
*1: If any of these limits are exceeded, device functionality should not be assumed, damage may occur and
*2: If the to be measured temperature exceeds the upper/lower limit, it only shows the maximum / minimum
value.
_6 Conversion details
Centigrade (°C)
6-4
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
Fahrenheit (°F)
6_
6-5
AS Ser ies M od ul e Man ua l
6.2.2 Profile
38.2 95
04RT D 1
7 7
98.3
88
8 3
4
9
5
6 75
35
Unit: mm
Conversion status
Analog-to-Digital
Blinking: conversion is in process.
Conversion Indicator
OFF: conversion has stopped.
6 DIN Rail Clip Secures the module onto the DIN rail
8 Ground Clip
6-6
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
AS04RTD-A AS06RTD-A
0 4R T D 06RTD
S LD I 3- I 56- I34-
S LD I 4- L6+ L6-
0V 0V
6_
6-7
AS Ser ies M od ul e Man ua l
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
1: floating point format
0: closed
1 Channel 1 mode setup 1:0–300 Ω (default)
2:0–3000 Ω
3:Pt100
2 Channel 2 mode setup
4:JPt100
5:Pt1000 R/W 1
6:Ni100
3 Channel 3 mode setup
7:Ni1000
8:LG-Ni1000
_6
10:Cu100
5 Channel 1 offset
6 Channel 2 offset
Range: -32768 to +32767 R/W 0
7 Channel 3 offset
8 Channel 4 offset
9 Channel 1 gain
10 Channel 2 gain
Range: -32768 to +32767 R/W 1000
11 Channel 3 gain
12 Channel 4 gain
6-8
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
0: Fahrenheit
21 Units of temperature R/W 0
1: Celsius
bit0: channel 1
bit1: channel 2
bit2: channel 3
bit3: channel 4
22 Channel alarm setup R/W 0
0: warning
1: alarm
channel 1
channel 2
channel 3
6-9
AS Ser ies M od ul e Man ua l
channel 4
channels 1–4
channel 1
channel 2
channel 3
channel 4
channels 1–4
211 The maximum peak value for channel 2 Integer format; the maximum -
R
212 The maximum peak value for channel 3 peak value for analog inputs -
215 The minimum peak value for channel 2 Integer format; the minimum peak -
225 The time to record for channel 4 value for the channels 1
241 The number of records for channel 2 Range: 0–500, display the current 0
R
242 The number of records for channel 3 records 0
4000-
Records for channel 1 500 records for channel 1 R --
4499
6-10
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
4999
5000-
Records for channel 3 500 records for channel 3 R --
5499
5500-
Records for channel 4 500 records for channel 4 R --
5999
6_
6 - 11
AS Ser ies M od ul e Man ua l
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
1: floating point format
0: closed
1 Channel 1 mode setup
1:0–300 Ω (default)
2 2:0–3000 Ω
Channel 2 mode setup
3:Pt100 1
5:Pt1000 R/W
7:Ni1000
5 Channel 5 mode setup 8:LG-Ni1000
9:Cu50
6 Channel 6 mode setup
_6
10:Cu100
7 Channel 1 offset
8 Channel 2 offset
9 Channel 3 offset
Range: -32768 to +32767 R/W 0
10 Channel 4 offset
11 Channel 5 offset
12 Channel 6 offset
13 Channel 1 gain
14 Channel 2 gain
15 Channel 3 gain
Range: -32768 to +32767 R/W 1000
16 Channel 4 gain
17 Channel 5gain
18 Channel 6 gain
6-12
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
0: Fahrenheit
31 Units of temperature
1: Celsius
R/W 0
6_
0: open channel alarm
bit0: channel 1
bit1: channel 2
bit2: channel 3
bit3: channel 4
bit4: channel 5
32 Channel alarm setup R/W 0
bit5: channel 6
0: warning
1: alarm
6-13
AS Ser ies M od ul e Man ua l
channel 1
channel 2
channel 3
channel 4
channels 5
channels 6
channels 1-6
6-14
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
219
The minimum peak value for analog inputs
-
6_
channel 4
6-15
AS Ser ies M od ul e Man ua l
4000
4199
4500
4699
5000
5199
5500
5699
6000
6199
6500
6699
6-16
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
6.2.6 Functions
Use the HWCONFIG utility software built into ISPSoft to set modes of operation and parameters.
Analog input
Disconnection If the channel is open, the module can detect when it is disconnected. If
5
Detection the input is open-circuited, the module produces an alarm or a warning.
If an input signal exceeds the range of inputs that the hardware can
Channel Detection
6 receive, the module produces an alarm or a warning. You can disable
and Alarm
this function.
Records for 6_
8 Save the analog curves for channels.
Channels
1. Enable/Disable a Channel
An analog signal is converted into a digital signal at a rate of 200 ms per channel. If a channel is not used,
2. Unit of Measurement
3. Calibration
To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The
calibration range depends on the range of inputs that the hardware can receive. The formula is:
(𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼 × 𝐺𝐺𝐺𝐺𝐺𝐺𝐺𝐺)
𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂 = + 𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂
1000
6-17
AS Ser ies M od ul e Man ua l
Example:
If the gain is 1000 and the offset is 0, the corresponding value for the original signal 0° C to 100° C is 0–1000.
If you change the offset to 100, the calibrated value for the original signal 0° C to 100° C becomes 100–1100.
O
Original signals
100 C Signals af ter the calibration
-320 00
0 100 1000 110 0
D igital v alue (X)
4. Average
You can set the average value between 1–100. It is a steady value obtained from the sum of the recorded
values. If the recorded values include an acute pulse due to unavoidable external factors, however, you
may observe violent changes in the average value. Use the filtering function to exclude the acute pulses
from the sum-up and equalization, so the computed average value is not affected by the acute recorded
values. Set the filter percentage to the range 0–3, where the unit is 10%. If you set the filter range to 0, the
system sums up all the recorded values and divides them to obtain the average value, but if you set the
_6 filter range to 1, for example, the system excludes the bottom 10% and the top 10% of the values and
5. Disconnection Detection
If the channel is open, the module can detect when it is disconnected. If the input is open-circuited, the
6-18
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
6. Channel Detection
If an input signal exceeds the allowable range of inputs, an error message appears. You can disable this
function so that the module does not produce an alarm or a warning when the input signal exceeds the
input range.
This function saves the maximum and minimum values for channels so that you can determine the peak to
peak values.
Maximum valu e
Mini mu m va lue
Time
Record the input values of the cyclic sampling for each channel. The system saves up to 500 data
points for AS04RTD-A and up to 200 data points for AS06RTD-A and the recording time is 100 ms. The
6_
following uses AS04RTD-A as an example to demonstrate.
Ti me
Instru cti on for recordi ng Recordin g e nds
9. PID control
PID algorithm is available for every channel. With its auto tuning function, parameters such as Kp, Ki, Kd
and more can be calculated and therefore temperature control can be achieved. You can also use
DMPID instruction to calculate relative parameters by entering the parameters in the endpoints of
corresponding instruction image and you can then obtain the output values from the output endpoints.
Note: DMPID instruction is availbe for AS04RTD-A (V1.04 or later), AS06RTD-A (V1.00 or later), AS
Series PLC (V1.06 or later) and AS-SCM (V2.04 or later).
6-19
AS Ser ies M od ul e Man ua l
2. When using PID parameters to set up control registers: PID control registers of AS04RTD-A are
retainable; however PID control registers of AS06RTD-A are not retainable.
6.2.8 Wiring
Precautions
To ensure the analog-to-digital module functions well and reliably, the external wiring must prevent noise.
(1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the
ASRTD Series must be separate cables.
(2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load
which is not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable,
(5) Note: use cables with the same length (less than 200 m) and use wire resistance of less than 20
_6
ohm.
External wiring
(1) AS04RTD-A
0~ 300Ω, 0~ 3000Ω
N i100 /Ni1000/ Pt 100/ Pt 1000 Ni 10 0 Pt1 00 ,J Pt1
, 00 ,
C u50/C u100/ J Pt 100/ LG -Ni1000 Cu 5 0, C u 1 00 /
Ni 10 0 0, P t1 0 00 ,
C H1 L G -N i 10 00 * 3
L1 +
L 1- ADC
*2 INA
I1-
S hielded cab le * 1 S LD
2 -Wi re AG
C H2
L2+
L2-
I2-
S hielded cab le * 1 AG
3 -Wi re
6-20
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
*1. Use shielded twisted pair cables for temperature sensors, and keep them away from power cables
*2. If using two-wire temperature sensors, Ln- and In- must be short-circuited (where n is between 1–4).
*3. There are two different internal excitation currents. If you are using a Ni100 temperature sensor, a
Pt100 sensor, a JPt100, a Cu50/Cu100, or a 0~300 Ω resistance sensor, the internal excitation
current is 1.5 mA. If you are using a Ni1000 temperature sensor, a Pt1000 temperature sensor, a LG-
Ni1000 sensor, or a 0~3000 Ω resistance sensor, the internal excitation current is 0.2 mA.
Note: When using a three-wire temperature sensor, the cables should be the same length (less than 200
(2) AS06RTD-A
0~ 300Ω, 0~ 3000Ω
N i100 /Ni1000/ Pt 100/ Pt 1000 Ni 10 0 Pt1 00 ,J Pt1
, 00 ,
C u50/C u100/ J Pt 100/ LG -Ni1000 Cu 5 0, C u 1 00 /
Ni 10 0 0, P t1 0 00 ,
C H1 L G -N i 10 00 * 3
L1 +
L 1- ADC
S LD INA
CH2
L2+ 6_
L2 -
I12- *2
*1. Use shielded twisted pair cables for temperature sensors and keep them away from power cables and
*2. Terminal “I12-“ indicates “ I1- & I2-“, terminal “I34-“ indicates “ I3- & I4-“, and terminal “I56-“ indicates
“ I5- & I6-“. If you use two-wire temperature sensors, Ln- and In- must be short-circuited (where n is
between 1–6).
*3. There are two different internal excitation currents. If you are using a Ni100 temperature sensor, a
Pt100 sensor, a JPt100, a Cu50/Cu100, or a 0~300 Ω resistance sensor, the internal excitation
current is 1.0 mA. If you are using a Ni1000 temperature sensor, a Pt1000 temperature sensor, a LG-
Ni1000 sensor, or a 0~3000 Ω resistance sensor, the internal excitation current is 0.2 mA.
Note: When using a three-wire temperature sensor, the cables should be the same length (less than 200
6-21
AS Ser ies M od ul e Man ua l
_6
6-22
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
6_
6-23
AS Ser ies M od ul e Man ua l
(3) Double-click the module in the working area to open the Device Setting page.
_6
6-24
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
(4) Choose the parameter, set the values, and click OK.
(5) Click Download on the toolbar to download the parameters. Note that you cannot download the
parameters while the CPU module is running.
6_
6-25
AS Ser ies M od ul e Man ua l
(2) Double-click the module to open the Device Setting page. The versions of both the firmware and the
_6
6-26
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
6_
6-27
AS Ser ies M od ul e Man ua l
(2) Click Import in the Device Setting dialog box and select a CSV file to import saved parameters.
_6
6-28
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
6.3.5 Parameters
(1) The input modes of the channels
6_
6-29
AS Ser ies M od ul e Man ua l
_6
6-30
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
6_
6-31
AS Ser ies M od ul e Man ua l
6-32
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
6_
6-33
AS Ser ies M od ul e Man ua l
(5) After setting is complete, select the module and click Login on the tool bar to download the settings to the
modules.
_6
(2) Select the module and click Login on the tool bar to go to Online Mode. You can find the Module Revision
from the Parameters tab.
6-34
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
(2) You can monitor the values, status, error codes in each channel from the I/O Mapping tab.
6_
(3) You can monitor the current status and error codes from the Status tab.
6-35
AS Ser ies M od ul e Man ua l
6.4.4 Parameters
(1) You can set up the value format to Integer or Floating for Channel 1 to 4.
_6
6-36
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
(6) You can set up the channel detect and alarm settings.
6_
6-37
AS Ser ies M od ul e Man ua l
6.5 Troubleshooting
6.5.1 Error Codes
Blinking once
or twice and
after 2
- When power-on, the module is not detected by CPU module. OFF
seconds, it
blinks
repeatedly
6-38
Ch ap te r 6 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 6RTD
Description Procedure
Internal error
Contact the factory.
The factory calibration is abnormal.
6-39
AS Ser ies M od ul e Man ua l
State of connection
Channel value
L+ L- I-
●: Disconnection
*1: for AS06RTD Series: in the modes of 0-300Ω and 0-3000Ω, it cannot detect I- state of connection.
_6
6-40
7
Chapter 7 Temperature Measurement
Module AS04/08TC
Table of Contents
7.1 Overview ........................................................................................... 7-2
7.1.1 Characteristics .............................................................................. 7-3
7-1
AS Ser ies M od ul e Man ua l
7.1 Overview
This chapter describes the specifications for the ASTC-A module, its operation, and its programming. The
AS04TC-A is a temperature measurement module that converts temperatures received from thermocouples
(type J, K, R, S, T, E, N, B, C, U, L, or TXK with ±100 mV voltage inputs) into digital signals. You can select
either Celsius (resolution: 0.1° C) or Fahrenheit (resolution: 0.1° F) as the unit of measurement.
An introduction to thermocouples
A thermocouple uses the Seebeck effect to measure differences in temperature. Generally speaking, a
thermocouple consists of two conductors of different materials that produce a voltage at the point where the
two conductors contact. The voltage produced depends on the difference of temperature between the
junctions with other parts of those conductors, and it ranges from several dozen microvolts to several
Differential operations are used to eliminate external noise. Thermocouples are more stable than thermistors,
resistance thermometers, and thermal resistors, so thermocouples are widely used in industrial applications.
A thermocouple consists of a circuit having two wires of different metals or metal alloys welded together or
joined at both ends. One of the junctions—normally the cold junction—is maintained at a known reference
temperature, and the other junction is at the temperature to be sensed. A temperature gradient across the
junction of the wires gives rise to an electric potential according to the Seebeck effect. The voltage produced
is proportional to the difference of temperature between the junctions with other parts of those conductors.
(Q A − QB )dT
T2
V =∫
T1
(A)
_7
where QA and QB are the thermopowers (Seebeck coefficient) of the metals A and B, and T1 and T2 are the
temperatures of the two junctions.
Principle of operation
Because QA and QB are almost unrelated to temperature, formula (A) above can be approximated as in
equation (B).
7-2
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
There are two types of thermocouple thermometers: wrapped thermocouples and bare thermocouples. A
wrapped thermocouple is wrapped in protective metal, and is similar to an electric spoon in appearance.
Wrapped thermocouples are used to measure temperature of liquid, and bare thermocouples are used to
7.1.1 Characteristics
(1) Select a sensor based on its practical application.
Conversion accuracy: the error range is ±0.5% of the input at ambient temperature of 25° C ±5° C.
The HWCONFIG software is built into ISPSoft. You can set modes and parameters directly in
HWCONFIG without spending time writing programs to set registers to manage functions.
7-3
AS Ser ies M od ul e Man ua l
Functional specifications
Analog-to-Digital
Centigrade (°C) Fahrenheit (°F) Voltage Input
Conversion
_7 Type J: -100° C to +1,200° C Type J: -148° F to +2,192° F
Type K: -100° C to +1,350° C Type K: -148° F to +2,462° F
Type R: 0° C to 1,750° C Type R: 32° F to 3,182° F
Type S: 0° C to 1,750° C Type S: 32° F to 3,182° F
Type T: -150° C to +400° C Type T: -238° F to +734° F
Rated Input Range*1 Type E: -150° C to +980° C Type E: -238° F to +1,796° F ±100 mV
Type N: -150° C to +1,300° C Type N: -238° F to +2,372° F
Type B: 200° C to +1,800° C Type B: 392°F to 3,272°F
Type C: 0°C to 2,320°C Type C: NA
Type U: -200°C to 600°C Type U: -328°F~1,112°F
Type L: -200°C to 900°C Type L: -328°F~1,652°F
Type TXK: -200°C~800°C Type TXK: -328°F~1,472°F
*1 If the measured temperature exceeds the upper limit, it only shows the maximum value. If the measured
temperature is below the lower limit, it only shows the minimum value.
7-4
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
Conversion details
Centigrade (°C)
Fahrenheit (°F)
Sensor Integer value range Floating point value range
Rated input range
type after digital conversion after digital conversion
J -148°F ~ 2,192°F K-1480 ~ K21920 -148.0 ~ 2192.0
K -148°F ~ 2,462°F K-1480 ~ K24620 -148.0 ~ 2462.0
R 32°F ~ 3,182°F K320 ~ K31820 32.0 ~ 3182.0
S 32°F ~ 3,182°F K320 ~ K31820 32.0 ~ 3182.0
T -238°F ~ 752°F K-2380 ~ K7520 -238.0 ~ 752.0
E -238°F ~ 1,796°F K-2380 ~ K17960 -238.0 ~ 1796.0
N -238°F ~ 2,372°F K-2380 ~ K23720 -238.0 ~ 2372.0
B 392°F ~ 3,272°F K3920 ~ K32720 392.0 ~ 3272.0
C NA NA NA 7_
U -328°F ~ 1112°F K-3280 ~ K11120 -328.0 ~ 1112.0
L -328°F ~ 1652°F K-3280 ~ K16520 -328.0 ~ 1652.0
TXK -328°F ~ 1472°F K-3280 ~ K14720 -328.0 ~ 1472.0
±100mV -100mV ~ 100mV K-10000 ~ K10000 -100.00 ~ 100.00
7-5
AS Ser ies M od ul e Man ua l
7.2.2 Profile
38.2 95
04TC 1
7
7
98.3
88
3
8
4
9 5
6 75
35
Unit: mm
Conversion status
Analog-to-Digital
_7 Conversion Indicator
Blinking: conversion is in process.
Arrangement of the
4 Arrangement of the terminals
Input/Output Terminals
6 DIN rail clip Secures the module onto the DIN rail
8 Ground clip
9 Label Nameplate
7-6
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
0 4 TC 08 TC
I1 + I1+ I 1-
PWR PWR
SLD I1- I2+ I 2-
I3 + I5+ I 5-
I4 + I7+ I 7-
2 4V SLD 24V
0V 0V
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
1: floating point format
0: closed
1 Channel 1 mode setup 1: -100 mV to +100 mV 7_
2: J-Type
3: K-Type
2 Channel 2 mode setup
4: R-Type
5: S-Type
3 Channel 3 mode setup 6: T-Type
R/W 1
7: E-Type
8: N-Type
9: B-Type
10: C-Type
4 Channel 4 mode setup
11: U-Type
12: L-Type
13: TXK-Type
7-7
AS Ser ies M od ul e Man ua l
5 Channel 1 offset
6 Channel 2 offset
Range: -32768 to +32767 R/W 0
7 Channel 3 offset
8 Channel 4 offset
Channel 1 average
13
times
Channel 2 average
14
times
Range: 1–100 R/W 10
Channel 3 average
15
times
Channel 4 average
16
times
0: Fahrenheit
21 Units of temperature R/W 0
1: Celsius
bit0: channel 1
bit1: channel 2
bit3: channel 4
0: warning
1: alarm
7-8
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
channel 2
channel 3
channel 4
channels 1–4
7-9
AS Ser ies M od ul e Man ua l
4000
Records for channel 1 500 records for channel 1 R -
~4499
_7 4500
Records for channel 2 500 records for channel 2 R -
~4999
5000
Records for channel 3 500 records for channel 3 R -
~5499
5500
Records for channel 4 500 records for channel 4 R -
~5999
7-10
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
1: floating point format
1: -100 mV to +100 mV
2 Channel 2 mode setup
2: J-Type
3 Channel 3 mode setup
3: K-Type
5: S-Type
5 Channel 5 mode setup
6: T-Type
6 Channel 6 mode setup R/W 1
7: E-Type
7 Channel 7 mode setup 8: N-Type
9: B-Type
10: C-Type
12: L-Type
13: TXK-Type
9 Channel 1 offset
10 Channel 2 offset
11 Channel 3 offset
7_
12 Channel 4 offset
Range: -32768 to +32767 R/W 0
13 Channel 5 offset
14 Channel 6 offset
15 Channel 7 offset
16 Channel 8 offset
17 Channel 1 gain
18 Channel 2 gain
19 Channel 3 gain
Range: -32768 to +32767 R/W 1000
20 Channel 4 gain
21 Channel 5 gain
22 Channel 6 gain
7 - 11
AS Ser ies M od ul e Man ua l
23 Channel 7 gain
24 Channel 8 gain
0: Fahrenheit
41 Units of temperature R/W 0
1: Celsius
bit0: channel 1
bit1: channel 2
42 Channel alarm setup R/W 0
bit2: channel 3
bit3: channel 4
bit4: channel 5
bit5: channel 6
7-12
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
bit6: channel 7
bit7: channel 8
0: warning
1: alarm
channel 1
channel 2
channel 3
channel 4
channel 5
channel 6
channels 1-8
7-13
AS Ser ies M od ul e Man ua l
7-14
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
The time to record for The time to record the digital value for the
230 R/W 1
channel 5 channels
7-15
AS Ser ies M od ul e Man ua l
4000
Records for channel 1 100 records for channel 1 R -
~4099
4500
Records for channel 2 100 records for channel 2 R -
~4599
5000
Records for channel 3 100 records for channel 3 R -
~5099
5500
Records for channel 4 100 records for channel 4 R -
~5599
6000
Records for channel 5 100 records for channel 5 R -
~6099
6500
Records for channel 6 100 records for channel 6 R -
~6599
7000
Records for channel 7 100 records for channel 7 R -
~7099
7500
_7 ~7599
Records for channel 8 100 records for channel 8 R -
7-16
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
7.2.6 Functions
Disconnection If the channel is open, the module can detect when it is disconnected. If
5
Detection the input is open-circuited, the module produces an alarm or a warning.
If an input signal exceeds the range of inputs that the hardware can
Channel Detection
6 receive, the module produces an alarm or a warning. You can disable
and Alarm
this function.
Records for
8 Save the analog curves for channels.
Channels
1. Enable/Disable a Channel
An analog signal is converted into a digital signal at a rate of 200 ms per channel. If a channel is not used,
2. Unit of Measurement
3. Calibration
To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The
calibration range depends on the range of inputs that the hardware can receive. The formula is:
(𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼 × 𝐺𝐺𝐺𝐺𝐺𝐺𝐺𝐺)
𝑂𝑂𝑢𝑢𝑢𝑢𝑢𝑢𝑢𝑢𝑢𝑢 = + 𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂
1000
7-17
AS Ser ies M od ul e Man ua l
Example:
If the gain is 1000 and the offset is 0, the corresponding value for the original signal 0° C to 100° C is 0–1000.
If you change the offset to 100, the calibrated value for the original signal 0° C to 100° C becomes 100–1100.
O
Original signals
100 C Signals af ter the calibration
-320 00
0 100 1000 110 0
D igital v alue (X)
4. Average
You can set the average value between 1–100. It is a steady value obtained from the sum of the recorded
values. If the recorded values include an acute pulse due to unavoidable external factors, however, you may
observe violent changes in the average value. Use the filtering function to exclude the acute pulses from the
sum-up and equalization, so the computed average value is not affected by the acute recorded values. Set the
filter percentage to the range of 0–3, where the unit is 10%. If you set the filter range to 0, for example, the
system sums up all the recorded values and divides them to obtain the average value, but if you set the filter
range to 1, the system excludes the bottom 10% and the top 10% of the values and averages only the
_7
Quantity
5. Disconnection Detection
If the channel is open, the module can detect when it is disconnected. If the input is open-circuited, the
7-18
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
6. Channel Detection
If an input signal exceeds the allowable range of inputs that the hardware can receive, an error message
appears and the Error LED blinks. You can disable this function so that the module does not produce an
alarm or warning and the Error LED also does not blink when the input signal exceeds the input range.
This function saves the maximum and minimum values for channels so that you can determine the peak to
peak values.
Maximum valu e
Mini mu m va lue
Time
8. Records for channels
Record the input values of the cyclic sampling for each channel. For AS04TC-A, the system saves up to
500 data points and the recording time is 10 ms. For example, if the conversion time is 2 ms and 4
channels are open, the recording time is 8 ms x 500 data points = 4 seconds in total. And the system
saves up to 100 data points for AS08TC-A and the recording time is 100 ms. The following uses
Ti me
Instru cti on for recordi ng Recordin g e nds
9. PID control
PID algorithm is available for every channel. With its auto tuning function, parameters such as Kp, Ki, Kd
and more can be calculated and therefore temperature control can be achieved. You can also use
DMPID instruction to calculate relative parameters by entering the parameters in the endpoints of the
corresponding instruction image and then you can then obtain the output values from the output
endpoints. Note: DMPID instruction is available for AS04TC-A (V1.04 or later), AS08TC-A (V1.00 or
7-19
AS Ser ies M od ul e Man ua l
AS04TC-A (V1.04 or later), AS08TC-A (V1.00 or later), AS Series PLC (V1.06 or later) and AS-
SCM (V2.04 or later). Refer to AS Series Programming Manual for more details.
2. If the device you have does NOT support DMPID instruciton, you can use the following PID
CR#
Operand Function Description Defaults
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
1: the PID
algorithm is
implemented.
algorithm is not
implemented.
601 631 661 691 721 751 781 811 SV SV Target value 0
0: automatic
control
_7 When PID_MAN
is switched from
1 to 0, the
output value
(MV) is included
PID control
602 632 662 692 722 752 782 812 PID_MODE in the automatic 0
mode
algorithm.
1: the parameters
are tuned
automatically for
the temperature
control. When
the tuning is
7-20
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
CR#
Operand Function Description Defaults
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
complete, the
device is
automatically
reset to 0, and
the parameters
Kc_Kp, Ti_Ki,
Td_Kd, and Tf
are set
appropriately.
0: auto; the MV is
output based
on the PID
algorithm.
1: manual; the MV
PID A/M is output based
603 633 663 693 723 753 783 813 PID_MAN 0
mode on the MOUT.
When
PID_MODE is
also set to 1,
this setting is
ineffective.
0: normal; the
7_
MOUT does not
MOUT
vary with the
automatic
604 634 664 694 724 754 784 814 MOUT_AUTO MV. 0
change
1: auto; the MOUT
mode
varies with the
MV.
Range: 0–32000,
mode.
7-21
AS Ser ies M od ul e Man ua l
CR#
Operand Function Description Defaults
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Kc_Kp are
floating-point
numbers. If the P
Calculated
coefficient is less
proportional
606 636 666 696 726 756 786 816
Kc_Kp than 0, the Kc_Kp 3.846
607 637 667 697 727 757 787 817 coefficient
is 0.
(Kc or Kp)
Independently, if
Kc_Kp is 0, it is
not controlled by P.
point numbers. If
Integral the calculated
608 638 668 698 728 758 788 818 coefficient
Ti_Ki coefficient I is less 0.013
609 639 669 699 729 759 789 819
(Ti or Ki) than 0, Ti_Ki is 0.
If Ti_Ki is 0, it is
not controlled by I.
Td_Kd are
floating-point
numbers. If the
Derivative calculated
610 640 670 700 730 760 790 820 coefficient
Td_Kd coefficient D is 190.078
611 641 671 701 731 761 791 821
_7 (Td or Kd) less than 0, Td_Kd
is 0. If Ti_Ki is 0, it
is not controlled by
D.
If the derivate-
action time
constant is less
612 642 672 702 732 762 792 822 Derivate-action than 0, Tf is 0 and
Tf 4.941
613 643 673 703 733 763 793 823 time constant it is not controlled
by the derivate-
action time
constant.
7-22
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
CR#
Operand Function Description Defaults
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
0: independent
formula
0: use the
variations in the
error (E) to
calculate the
control value of
the derivative
The
(derivative of
calculation of
E).
615 645 675 705 735 765 795 825 PID_DE the PID 0
1: use the
derivative
variations in the
error
PV to calculate
the control
value of the
derivative
(derivative of
PV).
0: heating action
PID forward/
(E=SV-PV) 7_
616 646 676 706 736 766 796 826 PID_DIR reverse 0
1: cooling action
direction
(E=PV-SV)
is the difference
between the SV
Range within and the PV. When
which the this setting is 0,
617 647 677 707 737 767 797 827 ERR_DBW 0
error value is the function is not
counted as 0 enabled. When
this setting is
module checks
7-23
AS Ser ies M od ul e Man ua l
CR#
Operand Function Description Defaults
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
whether the
present difference
absolute value of
ERR_DBW, and it
checks whether
the present
difference meets
condition. If the
present difference
absolute value of
ERR_DBW and it
status condition,
counted as 0, and
is implemented.
Otherwise the
present error is
_7 brought into the
PID algorithm
normally.
618 648 678 708 738 768 798 828 α value Integral sum Range: 0–100 31
619 649 679 709 739 769 799 829 β value Integral sum Unit: 0.01 0
When PID_MAN is
set to 1, the MV
MV_MAX and
MV_MIN.
7-24
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
CR#
Operand Function Description Defaults
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Range: 0–1000
(0%–100%)
Feedforward
feedforward
A floating-point
Unit: %
Floating-point
format.
The accumulated
integral value is
temporarily stored
for reference.
624 654 684 714 744 774 804 834 Accumulated
I_MV When the MV is --
625 655 685 715 745 775 805 835 integral value
out of the range
0%–100%, the
accumulated
integral value in
I_MV is 7_
unchanged.
When this
instruction is read,
is implemented
according to the
Sampling
626 656 686 716 746 776 806 836 CYCLE sampling time, and 1
time (TS)
the MV is
refreshed.
If TS is less than 1,
it is read as 1. If TS
is larger than
7-25
AS Ser ies M od ul e Man ua l
CR#
Operand Function Description Defaults
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
1,000, it is read as
1,000.
Unit: 100 ms
Note: PID control registers of AS04TC-A and RTD-A are retainable; however PID control registers of
AS06RTD-A and AS08TC-A are not retainable. But you can use the data registers that are retainable to store
the set PID parameters so that the PID parameters can be retainable.
PID formula:
2. When you set the PID_MODE to 1, auto tuning mode is enabled. When auto tuning is complete, the value
7-26
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
ERR_DBW
Kc_Kp
PID-P
>0 PID_MAN
BIAS
+ 0
<=0 +
0 +
Kc_Kp MV_LIMIT
1
MV
Ti_Ki
PID-I
>0
MV_MAX, MV_MIN
+
<=0 +
0 +
Ti_Ki MOUT_AUTO
+ MOUT
0
Td_Kd MOUT
PID-D PID_MAN
>0 1
0
<=0
0 1
Td_Kd, Tf MOUT
Kc_Kp
ERR_DBW Kc_Kp
>0
<=0
0 7_
PID_MAN
BIAS
+ 0
+
+
MV_LIMIT
1
Ti_Ki MV
PID-I
>0
MV_MAX, M V_MIN
<=0
0
Ti_Ki MOUT_AUTO
MOUT
0
Td_Kd MOUT PID_MAN
PID-D
>0 1
0
<=0
0 1
Td_Kd, Tf MOUT
7-27
AS Ser ies M od ul e Man ua l
ERR_DBW
When the PV (present value) is in the range of ERR_DBW, at the beginning, the present error is brought
into the PID algorithm according to the normal processing, and then the CPU module checks whether the
present error meets the cross status condition: PV (present value) goes beyond the SV (target value).
Once the condition is met, the present error is counted as 0 when applying the PID algorithm. After the PV
(present value) is out of the ERR_DBW range, the present error is brought into the PID algorithm again. If
PID_DE is true, that means it uses the variations in the PV to calculate the control value of the derivative,
and after the cross status condition is met, the PLC treats Δ PV as 0 to apply the PID algorithm. (Δ PV=
current PV – previous PV). In the following example, the present error is brought into the PID algorithm
according to the normal processing in section A ,and the present error or Δ PV is counted as 0 to apply
the PID algorithm in the section B.
α、β Value
To reduce overshoot, you can use parameters of ALPHA or BETA in the beginning of the PID
operation or while SV (target value) varies to compensate initial value of integral calculus (for
_7 heating up or cooling down). See the images below. Use ALPHA parameter to reduce overshoot while the
temperature is climbing up. Use BETA parameter to reduce overshoot while the temperature is dropping.
Temperature ( 0 C) Temperature ( 0 C)
Time Time
7-28
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
Execute the general pulse with modulation instruction (GPWM) to set pulse output width and output cycle
Example:
If the output cycle is 2000 ms, then the output value is 50% after the PID algorithm is implemented.
In other words, the GWPM instruction can be set to pulse output width = 1000 and output cycle = 2000.
t =10 0 0 ms
Ou tp u t Y 1 0
T =2 00 0 ms
Note:
1. When tuning the parameters Kc_Kp, Ti_Ki, and Td_Kd (PID_MODE=0), set the Kc_Kp value first, and
then set the Ti_Ki and Td_Kd values to 0. In a controlled environment, you can increase the values of
Ti_Ki (from smaller to bigger) and Td_Kd (from bigger to smaller). When the value of Kc_Kp is 1, the
proportional gain is 100%. That is, the error values increase by a factor of one. When the proportional
gain is less than 100%, the error values decrease. When the proportional gain is greater than 100%, the
7_
2. The parameters which have been automatically tuned are not necessarily suitable for every controlled
environment. You can, therefore, further modify the automatically-tuned parameters, but it is
3. The operand CYCLE is to set the sampling time to use the PID algorithm and refresh MV.
4. When the number of the channel for measurement is changed, the time to refresh the
measured value also changes. For example, the measured value is refreshed every 200 ms
when there is only 1 channel for measurement. The measured value is refreshed every 800 ms
when there are 4 channels for measurement. The Kc_Kp, Ti_Ki, Td_Kd parameters may differ
when the number of channel for measure is different.
7-29
AS Ser ies M od ul e Man ua l
7.2.8 Wiring
Precautions
To ensure the analog-to-digital module functions well and reliably, the external wiring must prevent noise.
(1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the
ASTC-A Series must be separate cables.
(2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load
which is not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable,
(7) Note3: TC modules must run for 30 minutes before they start to take any temperature measurement.
External wiring
J,K ,R ,S ,T,E ,N , B,
C, U, L an d T X K CH1
+ I 1+
- A DC
I1-
SL D I NA
Shi el ded cable*1
_7 - 1 00 mV ~1 0 0m V CH 3
+
I3 +
-
I3 - Cold - junction
SL D compensati on
*1. Use shielded twisted pair cables for Type J, K, R, S, T, E, N, B, C, U, L and TXK thermocouples, and
keep them separate from power cables and other cables which generate noise.
7-30
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
7_
7-31
AS Ser ies M od ul e Man ua l
_7
7-32
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
(3) Double-click the module in the working area to open the Device Setting page.
7_
7-33
AS Ser ies M od ul e Man ua l
(4) Choose the parameter, set the values, and click OK.
(5) Click Download on the toolbar to download the parameters. Note that you cannot download the
parameters while the CPU module is running.
_7
7-34
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
(2) Double-click the module to open the Device Setting page. The versions of both the firmware and the
7_
7-35
AS Ser ies M od ul e Man ua l
_7
7-36
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
(2) Click Import in the Device Setting dialog box, and select a CSV file to import saved parameters.
7_
7-37
AS Ser ies M od ul e Man ua l
7.3.5 Parameters
(1) The input modes of the channels
_7
7-38
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
7_
7-39
AS Ser ies M od ul e Man ua l
_7
7-40
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
7_
7-41
AS Ser ies M od ul e Man ua l
_7
7-42
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
(5) After setting is complete, select the module and click Login on the tool bar to download the settings to the
modules.
7_
7-43
AS Ser ies M od ul e Man ua l
(2) Select the module and click Login on the tool bar to go to Online Mode. You can find the Module Revision
from the Parameters tab.
_7
7-44
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
(2) You can monitor the values, status, error codes in each channel from the I/O Mapping tab.
(3) You can monitor the current status and error codes from the Status tab.
7_
7-45
AS Ser ies M od ul e Man ua l
7.4.4 Parameters
(1) You can set up the value format to Integer or Floating for Channel 1 to 4.
_7
(4) You can set up the average filtering for Channel 1 to 4.
7-46
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
(6) You can set up the channel detect and alarm settings.
7_
7-47
AS Ser ies M od ul e Man ua l
7.5 Troubleshooting
7.5.1 Error Codes
Blinking once
or twice and
after 2
- When power-on, the module is not detected by CPU module. OFF
seconds, it
blinks
repeatedly
7-48
Ch ap te r 7 Te mper a tu re Me asur eme n t Mod ul e AS0 4/0 8TC
Description Procedure
Internal error
Contact the factory.
The factory calibration is abnormal.
When power-on, the module is not detected by Check if the connection between module and CPU
7-49
AS Ser ies M od ul e Man ua l
MEMO
_7
7-50
8
Chapter 8 Load Cell Module AS02LC
Table of Contents
8.1 Overview ........................................................................................... 8-2
8-1
AS Ser ies M od ul e Man ua l
8.1 Overview
This chapter describes the specifications for load cell modules, their operation, and their programming. You
can use the AS02LC load cell module with four-wire or six-wire load cells with various eigenvalues, so you
can adjust its response time according to your requirements. In addition, the AS02LC-A can read and write
data via the AS Series PLC units using the FROM/TO instructions. To ensure that the product is correctly
installed and operated, read the manual carefully before use. This manual provides functional specifications,
and it also introduces installation, basic operation, and settings. Refer to load cell related literature for more
8.2 Specifications
8.2.1 Specifications
Item Description
Rated Supply Voltage/Power
24 VDC (-15% to +20%) / 3 W
Consumption
Minimum/Maximum Voltage 18–31.2 VDC
Maximum Current Consumption 150 mA
Input Signal Range ±40 mVDC
Sensibility +5 VDC +/-10%
Highest Accuracy 0.04 % of full scale
Communication Interface RS-232, RS-485
Applicable Sensor Type 4-wire or 6-wire load cell
Expanding a Temperature
≤ ±50 ppm/K v. E
Coefficient
Reducing a Temperature
≤ ±0.4 μV/K
Coefficient to Zero
Linearity Error ≤0.02%
Response Time 2.5, 10, 16, 20, 50, 60, 100, 200, and 400 ms
Eigenvalue Applicable to a Load
0–1, 0–2, 0–4, 0–6, 0–20, 0–40 and 0–80 mV/V
Cell
Maximum Distance for
100 meters
Connecting a Load Cell
_8 Maximum Output Current 5 VDC x 160 mA
Allowable Load 40–4010 Ω
Common-mode Rejection Ratio
≥100 dB
(CMRR @50/60 Hz)
Dynamic Filter K1–K5
Average Weights K1–K100
Between a digital circuit and the ground: 500 VAC
Isolation Between an analog circuit and the ground: 500 VAC
Between an analog circuit and a digital circuit: 500 VAC
Weight 147 g
8-2
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
8.2.2 Profile
38.2 95
02LC 1
7
7
EX C+ EX C -
SI G+ SI G -
CH1
SE N+ SE N- 2
98.3
88
SL D
EX C+ EX C-
3
SI G+ SI G-
CH2
8 SE N+ SE N-
SL D
2 4V
0V
4
9
5
6 75
35
Unit: mm
Conversion status
Analog-to-Digital
Blinking: conversion is in process.
Conversion Indicator
OFF: conversion has stopped.
6 DIN Rail Clip Secures the module onto the DIN rail
8 Ground Clip
9 Label Nameplate
8-3
AS Ser ies M od ul e Man ua l
02LC
EX C+ EX C -
SI G+ SI G -
C H1
SE N+ SE N-
SL D
EX C+ EX C-
SI G+ SI G-
C H2
SE N+ SE N-
SL D
2 4V
0V
_8
8-4
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: disabled
3: raw data
0: 1 mV/V
1: 2 mV/V
2: 4 mV/V
4: 20 mV/V
5: 40 mV/V
6: 80 mV/V
0: 2.5ms
1: 10ms
2: 16ms
3: 20ms
5: 60ms
6: 100ms
7: 200ms
8: 400ms
8_
Weight measured times in a
3 Range: K1–K500 R/W 5
stability range for CH1
4 Floating-point format
Stability range for CH1 R/W 10
5 Range: 0–100000
Floating-point format
6 Maximum weight for CH1 R/W 100,000
Maximum measuring weight; when the
8-5
AS Ser ies M od ul e Man ua l
greater than 1.
0: no filter (default)
11 Floating-point format
Upper limit of the zero return
Determines the current weight as the zero R/W 10
for CH1
12
point in the upper/lower range; when the
Floating-point format
19–58 Calibrated weight for CH1 Calibrated weight of the calibration points R/W -
_8 1–20
0: disabled
1: gross weight
59 Display options for CH2 R/W 1
2: net weight
3: raw data
0:1 mV/V
2:4 mV/V
8-6
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
3:6 mV/V
4:20 mV/V
5:40 mV/V
6:80 mV/V
0:2.5 ms
1:10 ms
2:16 ms
3:20 ms
5:60 ms
6:100 ms
7:200 ms
8:400 ms
63 Floating-point format
Stability range for CH2 R/W 10
64 Range: 0–100000
Floating-point format
65
Maximum measuring weight; when the
Maximum weight for CH2 weight measured exceeds the limit, an R/W 100,000
0: no filter (default)
8-7
AS Ser ies M od ul e Man ua l
Floating-point format
78–117 Calibrated weight for CH2 Calibrated weight of the calibration points R/W -
1–20
0: warning
1: alarm
channels
240 The number of records for CH1 Range: 0–500; display the current records R -
8-8
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
604 -
Tare weight measured by CH1 Display the tare weight measured by CH1 R/W
605 -
606 -
Tare weight measured by CH2 Display the tare weight measured by CH2 R/W
607 -
8_
8-9
AS Ser ies M od ul e Man ua l
Explanation
You can view the error code, the channel value, and the state code, as well as the data registers that
correspond to their commands under the Normal Exchange Area tab of the Device Setting dialog box in the
Explanation
b0 16#0001 Error exists in the power supply. b1 16#0002 Error exists in the module hardware.
_8 b6 16#0040
exceeds the maximum weight that
b7 16#0080
exceeds the maximum weight that
b8 16#0100 exceeds the maximum weight that b9 16#0200 exceeds the maximum weight that
b10 16#0400 CH1 has been adjusted incorrectly. b11 16#0800 CH2 has been adjusted incorrectly.
b12 16#1000 CH1 is not measuring any weight. b13 16#2000 CH2 is not measuring any weight.
b14 16#4000 The weight measured by CH1 is in b15 16#8000 The weight measured by CH2 is in
8-10
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
Note: The state is determined by the corresponding bit and it is possible to have more than 2 states at the
same time.
C R # 2 0 1 : Command set
Explanation
Input
Description Input value Description
value
Commands for calibrating the calibration Start a new recording of the peak value
1–20 16#0102
points 1–20 on CH1 for CH2.
Commands for calibrating the calibration Start a new recording of the peak value
21–40 16#010F
points 1–20 on CH2 for CH1 - CH2.
98 Activate the weight calibration. 16#0201 Start a new recording for CH1.
99 Deactivate the weight calibration. 16#0202 Start a new recording for CH2.
(DWORD).
102 zero. You might need to execute this 16#0212 Stop recording for CH2.
(DWORD).
8 - 11
AS Ser ies M od ul e Man ua l
Input
Description Input value Description
value
Start a theoretical calibration for CH1 - Restore default settings and clear
16#030F 16#0501
CH2. settings in Flash.
_8
8-12
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
8.2.5 Functions
When an object is put on a load cell, you can check whether the
2 Stability check
present weight of the object is in a specified stability range.
3 Determining zero point If an object is removed from the load cell, no weight is measured.
You can choose to measure either the net weight or the gross weight of an object. Net weight is the actual
weight of a product without its package. The weight of a package is the tare weight. Gross weight is the total
Net weight: the weight of a product, that is, the actual weight of a product without its package
Gross weight: the total weight, that is, the net weight of a product plus the tare weight of its package
8_
Gross weight=Net weight+Tare weight
Example: a product weighs 10 kg, and the carton in which the product is packed weighs 0.2 kg. The
Net weight = 10 kg
8-13
AS Ser ies M od ul e Man ua l
2. Checking stability
When an object is placed on a load cell, you can check whether the present weight of the object is in a
If the weight measured is in the specified stability range, the corresponding bit is set to 1.
If the weight measured exceeds the specified stability range, the corresponding bit is set to 0 until the
Example: the measurement time set is 10 ms, the number of weights measured in a stability range is 10, and
the stability range is 1000 g. If a variation exceeds 1000 g, the corresponding bit is set to 0. If the variations
within 100 ms (10×10 ms) are within 1000 g, the corresponding bit is set to 1. You should determine whether
the present weight measured is in the stability range before you perform control actions.
△ : Va ri a ti on s in a ve ra g e we ig h ts
t
t: Me a su r em en t tim e se t by use rs
k
k: Sta b il i ty ra ng e se t by use r s
m <k
< kk △<
△< k
m: Num be r o f we i gh ts me a su re d i n <kk
△<
a sta bi l ity ra n g e >k
△> k
A ve r ag e we i gh t >k
△> k
>k
△> k
△> k
>k
△> k
>k
△> k
△
△> k
>k
T ime
B it in th e sta b il it y ran g e t m
b it
_8 If an object is removed from the load cell, the corresponding bit is set to 1, and you can perform the next
control action. If a weight measured is in the specified zero range, the corresponding bit is also set to 1.
No o b je ct
Ch 1
L oa d ce ll
CH 2
8-14
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
Average weight
Zero range
Time
Zero weight
Filtering out the maximum/minimum weight measured: If there is a maximum weight or a minimum
weight, you can filter out the maximum weight or the minimum weight. The larger the value, the more
Averaging weights: The values recorded are averaged so that a steady value is obtained. There may be
peak values due to unavoidable external factors, and the average value obtained may change
Make adjustments to get the weight measured by a cell to correspond to the digital value displayed by the
load cell module. Generally, two points are adjusted. After a system is set up, put no load on the scale. The
weight measured is 0 grams when there is no load. Then place an object of a given weight on the scale, and
set a digital value corresponding to the weight. At that point, two points have been adjusted. For example, if
you have a load cell sensor which can measure a maximum weight of 10 kg, and if 1 kg corresponds to
Weight
8_
10 kg
Point
1 kg
Digital value
K0 K1000 K10000 (LSB)
8-15
AS Ser ies M od ul e Man ua l
In addition to this two-point adjustment, the load cell also supports adjustments of up to 20 points. A
Weight
Point 5
10 kg
Point 3
Point 4
Point 1
1 kg
Point 2
Digital value
K0 K1000 K10000 (LSB)
Theoretical calibration is determined according to the sensor specification in order to input the voltage values
corresponding to various weights. The registers for storing the voltage values are CR#700–739 for CH1 and
CR#740–779 for CH2. After entering the voltage values into the registers, you can use the command set
Example: the sensor specification is 10 kg and its eigenvalue is 2 mV/V. When the sensor is loaded with a 10
Step 2: set the 2-point adjustment; when the sensor is loaded with a 1 kg weight, set the value to 1000.
_8
Step 3: set the voltage calibration for the zero point to 0 (0 mV) in the CR#700/701 registers, and to 1.0 (1
Step 4: enable the calibration function and enter 98 into the command set CR#201.
8-16
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
Step 5: enter 16#0301 into the command set CR#201 to execute a theoretical calibration for channels 1.
Step 6: do not put any load on the sensor and enter 16#102 into the command set CR#201 to reset the value
to 0 for CH1.
Step 7: disable the calibration function to prevent inappropriate changes. To complete the theoretical
calibration, enter 99 into the command set CR#201. Put a 1 kg weight on the sensor and the load cell should
show 1000.
Weight
Point
D igita l v alue
2 -point a djustme nt
Step 8: write 16#6001 in CR#201 to disable the calibration function to write the current settings into Flash and
Zero point tracking refers to resetting the current value to 0. You can reset the value to 0 within a certain
duration or at a certain weight. This is especially useful when the sensor is no longer as accurate as it was
before.
8_
8-17
AS Ser ies M od ul e Man ua l
Save the maximum and minimum values for channels so you can determine the peak to peak values.
Maximum valu e
Mini mu m va lue
Time
9. Recording channels
Record the input values of the cyclic sampling for each channel. The system saves up to 500 data points and
Ti me
Instru cti on for recordi ng Recordin g e nds
_8
8-18
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
8.2.6 Wiring
External wiring
EX C+ A+5V
EX C- AGND
F our -wir e
SIG+
SIG-
CH 1
SE N+
SE N-
EX C+ A+5V
Six- wire EX C- AGND
SIG+
SIG-
CH 2
SE N+
SE N-
Connected to
on a power supply m odule *1 A+5V
System 0V DC/DC
ground 24V conver ter
AGND
T hir d gr ound
( Im pedance: Less than 100 )
8_
8-19
AS Ser ies M od ul e Man ua l
Multiple load cells connected in parallel are connected to a single load cell module.
Lo ad c ell
Lo ad c ell
Lo ad c ell
CH1
Lo ad c ell
Lo ad c ell
CH2
Lo ad c ell
Lo ad c ell
Loa d ce ll
Note 1: Please connect on the power supply module and on the load cell module to a system
ground, and then ground the system ground or connect the system ground to a distribution box.
Note 2: If multiple load cells are connected in parallel, the total impedance should be greater than 40 Ω.
_8
8-20
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
load cell module. You can make adjustments by following the commands below or by setting up the
No weight
YES
Writing an ad ju st ment enabled A djust ing th e nex t point
ins truc tion
NO
8_
8-21
AS Ser ies M od ul e Man ua l
Step 3: Set the number of adjustments and their corresponding values. The example below shows a 2-point
_8
8-22
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
Step 4: After the configuration is complete, download the parameters to the module.
Step 6: Leave no load on the load cell (adjustment point 1) and click Next Step to proceed.
8_
8-23
AS Ser ies M od ul e Man ua l
Step 7: Put a load on the load cell (adjustment point 2). For multi-point adjustment, repeat this step. This
_8
8-24
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
Weig ht
1 0 kg
Po int
1 kg
Step 2: Set the number of adjustments and their corresponding values. The example below shows a 2-point
8_
8-25
AS Ser ies M od ul e Man ua l
Step 3: After the configuration is complete, download the parameters to the module.
Step 4: Double-click on the module to see the settings and verify that the corresponding address the
_8
8-26
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
Step 5: Enter the command for activating the weight calibration 98 into D28007.
Step 6: Leave no load on the load cell (adjustment point 1) and enter 1 into D28007. 1 represents CH1 and 2
represents CH2.
Step 7: Put a load on the load cell (adjustment point 2). For multi-point adjustment, repeat this step. This
Step 8: to complete the adjustment, enter the command for deactivating the weight calibration 99 into
D28007.
Weig ht 8_
1 0 kg
Po int
1 kg
8-27
AS Ser ies M od ul e Man ua l
_8
8-28
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
8_
8-29
AS Ser ies M od ul e Man ua l
(3) Right-click on the module and then click LC Wizard to go to the settting page.
_8
8-30
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
(5) Click Download on the toolbar to download the parameters in HWCONFIG. Note that you cannot
download the parameters while the CPU module is running.)
8_
8-31
AS Ser ies M od ul e Man ua l
(2) Double-click the module to open the Device Setting page. The versions of both the firmware and the
_8
8-32
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
8_
8-33
AS Ser ies M od ul e Man ua l
(2) Click Import in the Device Settings dialog box and select a dep file to import saved parameters.
_8
8-34
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
8.4.5 Parameters
(1) Settings for CH1
8_
8-35
AS Ser ies M od ul e Man ua l
_8
8-36
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
8_
8-37
AS Ser ies M od ul e Man ua l
Double-click the DIADesigner-AX icon to open DIADesigner-AX. Click New Project on the Start
Page or select File > New Project (Ctrl+N) to create a new project.
Next you will see a window with two sections, Categories and Templates. Click Projects in the Categories
section and click Standard project in the Templates section. After that create a Name and specify a location
for the project and then click OK.
_8
8-38
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
And a Standard Project dialog appears. You can select the device and the programming language from the
drop-down list. Click OK, the system generates a cyclic task with a default PLC_PRG.
After a new project is successfully created, you can see a project management area in the left side of the
window. All the options are listed in nodes. Click View -> Devices (Alt+0) on the tool bar, if nothing appears in
the project management area.
8_
8-39
AS Ser ies M od ul e Man ua l
With AX-3 Series PLC backplaneless design, the extension module can install on the right-side of AX-3
Series PLC directly. Double-click or drag and drop the extension module that you’d like to add from the
Product List. Newly added extension modules will apper on the right-side of the AX-3 Series PLC. And the
_8
8-40
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
Method 2
If the AX-3 Series PLC and its connected extension module are powered on and the gateway is correctly set,
you can use the icon to scan and add the modules in. Newly added extension modules will apper on
the right-side of the AX-3 Series PLC. And the device names will also show up on the left-side under
Delta_LocalBus_Master.
8_
8-41
AS Ser ies M od ul e Man ua l
Method 1
Find and double-click Hardwre Configuration in the tree view to open the Hardware Configuration.
Double-click the image of the module you’d like to configure to open the parameter setting page.
Method 2
Find and double-click the module you’d like to configure under Delta_LocalBus_Master (Delta LocalBus
_8
8-42
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
Max Weight, Filter Mode, Filter Ratio, Filter Average Times, Zero Upper Range, Zero Lower Range, Zero
Tracking Time and Zero Tracking Range for channel 1 and channel 2.
Channel 1:
Channel 2:
8_
8-43
AS Ser ies M od ul e Man ua l
Channel 1:
Channel 2:
_8
8-44
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
under the Parameter Tab when the system is in the Online Mode, but editing is NOT accessible in the Online
Mode.
8-45
AS Ser ies M od ul e Man ua l
8.5.5 Status
You can monitor the status and error message of the module under the Status Tab.
8.5.6 Information
You can check the module information, including Name, Vendoro, Categories, Type, ID, Version, Order
_8
8-46
Ch ap te r 8 Lo ad Ce ll Mo du le AS02 LC
8.6 Troubleshooting
8.6.1 Error Codes
Blinking once
or twice and
Upon power-on, the module does NOT receive any detecting after 2
- OFF
request from the PLC CPU. seconds, it
blinks
repeatedly
8_
8-47
AS Ser ies M od ul e Man ua l
Description Procedure
Diver board failure short-circuit (check EXC+ and EXC-). If the problem
The signal received by channel 1 exceeds the Check the value input to channel 1 and the maximum
The factory calibration in channel 1 is incorrect. Check the weight calibration in channel 1.
The signal received by channel 2 exceeds the Check the value input to channel 2 and the maximum
The factory calibration in channel 2 is incorrect. Check the weight calibration in channel 1.
Upon power-on, the module does NOT receive Check the connection between the CPU and the module
any detecting request from the PLC CPU. or reconnect them again.
_8
8-48
9
Chapter 9 Serial Communication Module
AS00SCM
Table of Contents
9.1 Introduction
Thank you for using the AS00SCM-A, a serial communication module. To ensure that your AS00SCM-A is installed
and operated correctly, read this manual carefully before using the module.
The AS00SCM-A is a serial communication module, supporting AS series communication extension modules (COM)
as well as the remote modules (RTU) and the followings:
COM mode (AS series communication extension modules installed on the right side of the AS CPU and no
external power supply)
Serial communication cards: AS-F232, AS-F422, and AS-F485 support Modbus and UD Link (user-defined
format).
AS00SCM-A with serial communication card installed can be used only in COM mode.
AS00SCM-A with CANopen communication card (AS-FCOPM) installed can be used in COM mode.
CANopen communication card ( AS-FCOPM) supports AS remote mode and CANopen DS301 (Slave).
AS00SCM-A with CANopen communication card (AS-FCOPM) installed can be used in RTU mode
(without connecting to AS CPU).
AS00SCM-A with Ethernet communication card (AS-FEN02) installed ca be used only in RTU mode.
AS00SCM-A with PROFINET communication card (AS-FPFN02) installed ca be used only in RTU mode.
Refer to Chapter 10 of AS Module Manual for more information.
V1.00 V - - - - -
V2.00 V V V - - -
_9 V2.02 V V V V V -
V2.06 V V V V V V
9-2
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
When AS00SCM-A is used as a remote module, its right side supports the followings AS Series IO modules.
When AS00SCM-A acts as a CANopen remote module, the followings are supported.
AS08AM10N-A, AS16AM10N-A, AS32AM10N-A, AS64AM10N-A, AS08AN01P-A,
Digital Module AS08AN01R-A, AS08AN01T-A, AS16AN01P-A, AS16AN01R-A, AS16AN01T-A,
AS32AN02T-A , AS64AN02T-A , AS16AP11P-A, AS16AP11R-A, AS16AP11T-A
AS04AD-A, AS08AD-B, AS08AD-C, AS02ADH-A, AS04RTD-A, AS06RTD-A, AS04TC-A,
Analog Module
AS08TC-A, AS04DA-A, AS06XA-A, AS02LC-A
Network Module AS04SIL-A (for AS00SCM-A FW V2.06 or later)
When AS00SCM-A acts as an EtherNet/IP remote module, the followings are supported.
AS08AM10N-A, AS16AM10N-A, AS32AM10N-A, AS64AM10N-A, AS08AN01P-A,
Digital Module AS08AN01R-A, AS08AN01T-A, AS16AN01P-A, AS16AN01R-A, AS16AN01T-A,
AS32AN02T-A , AS64AN02T-A , AS16AP11P-A, AS16AP11R-A, AS16AP11T-A
AS04AD-A, AS08AD-B, AS08AD-C, AS02ADH-A, AS04RTD-A, AS06RTD-A, AS04TC-A,
Analog Module
AS08TC-A, AS04DA-A, AS06XA-A, AS02LC-A
When AS00SCM-A acts as a PROFINET remote module, the followings are supported.
AS08AM10N-A, AS16AM10N-A, AS32AM10N-A, AS64AM10N-A, AS08AN01P-A,
Digital Module AS08AN01R-A, AS08AN01T-A, AS16AN01P-A, AS16AN01R-A, AS16AN01T-A,
AS32AN02T-A , AS64AN02T-A , AS16AP11P-A, AS16AP11R-A, AS16AP11T-A
AS04AD-A, AS08AD-B, AS08AD-C, AS04RTD-A, AS06RTD-A, AS04TC-A, AS08TC-A,
Analog Module
AS04DA-A, AS06XA-A
When AS00SCM-A acts as a serial communication extension module or a CANopen remote module, it should
work with AS PLC CPU for configuration. Download ISPSoft V3.13 or later versions from Delta’s official website
to configure AS00SCM-A.
If you use UD Link, configure it through SCMSoft, which is embedded in HWCONFIG of DCISoft. Download
DCISoft V1.24 or later from Delta’s official website.
When AS00SCM-A acts as an Ethernet remote module, you can set up the EtherNet/IP via EIP Builder and
HWCONFIG of ISPSoft. Download ISPSoft V3.13 or later versions and EIP Builder V1.08 or later from Delta’s
official website.
9_
9-3
AS Ser ies M od ul e Man ua l
Item Specifications
Connector type 5- pin European-style terminal block, spring-clip connector
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800 115200 and
Transmission speed
230400 bps
Stop bit: 1 bit and 2 bits
Communication
Parity bit: none, an odd parity bit, and an even parity bit
format
Data bit: 7 bits and 8 bits
Communication Modbus ASCII/RTU
protocol UD Link
Item Specifications
Connector type RJ45*2
Transmission speed 10k, 20k, 50k, 125k, 250k, 500k, and 1000k bps
Communication AS remote mode (RTU mode)
protocol CANopen (firmware V2.00 or later)
Item Specifications
Connector type RJ45*2
Transmission speed 10M, 100Mbps
Communication
EtherNet/IP (firmware V2.02 or later), PROFINET (firmware V2.06 or later)
protocol
Electrical specifications
Item Specifications
Supply voltage 24 VDC
Electric energy
0.6 W
consumption
Weight Approximately 169 g
_9
9-4
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
1 SCM
PO WER
7 2
ER RO R
CA RD 1 7
CA RD 2
98 .3
ID 1
88
3
FOR M AT 1
4
8
ID 2
F OR MA T 2
9
5
C OM . RTU
6 75
10 56
Unit: mm
9-5
AS Ser ies M od ul e Man ua l
1. When the setting range is 0x01–0x0F, you can use the knob to set the node ID1 and ID2. (The settings in the
ISPSoft is ignored here.)
2. When the setting range is NOT between 0x01–0x0F, you can turn the knob to 0 and use ISPSoft
(HWCONFIG) to set up the node ID. Follow the descriptions shown on the HWCONFIG for node ID setting
range.
COM. RTU
3. When the FORMAT knob is NOT set to 0, use the FORMAT1 AND FORMAT2 knobs to set the communication
mode. Refer to the following table. (The settings in the ISPSoft is ignored here.)
4. When the FORMAT knob is set to 0, you can use ISPSoft (HWCONFIG) to set up the communication mode.
COM. RTU
9-6
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
1. When the setting range is 0x01–0x0F, you can use the knob to set the node ID1 and ID2. (The settings in the
ISPSoft is ignored here.)
2. When the setting range is NOT between 0x01–0x0F, you can turn the knob to 0 and use ISPSoft
(HWCONFIG) to set up the node ID. Follow the descriptions shown on the HWCONFIG for node ID setting
range.
3. When in RTU mode, the setting varies according to different CANopen communication mode; refer to section
9.4.1 for more details.
COM. RTU
Refer to the following table and use FORMAT 2 knob to set up the communication. You can NOT use ISPSoft
(HWCONFIG) to set up the communication mode in this format.
FORMAT 2 1 2 3 4 5 6 7 8-F
Bit rates (bps) 10K 20K 50K 125K 250K 500K 1000K NA
Distance (m) 5000 2500 1000 500 250 100 25 NA
When using the communication card AS-FEN02, you need to set ID1 and FORMAT1 to 0. Refer to the following
methods to edit the IP address and settings of AS-FEN02.
1. When both knobs ID2 and FORMAT 2 are set to 0, IP address is set through EIP Builder (ISPSoft ->
HWCONFIG).
Open EIP Builder and add AS00SCM (RTU) + AS-FEN02 to your network. Double-click HWCONFIG to
set up.
Open EIP Builder and select IP Setting Tool from the Tool on the tool bar to scan for the device IP
address for setup.
2. When both ID2 and FORMAT 2 are set to F, IP setting mode is in DHCP mode. After setting is complete, you
need to turn the power OFF and then ON to make sure the modules are sending DHCP requests. Check the 9_
sticker on the AS-FEN02 communication card for the MAC address. After that open EIP Builder and select IP
Manager from the Tool on the tool bar and click Start the Server to set up the correspondences between MAC
address and IP address.
3. When either ID2 or FORMAT 2 is Neither 0 nor F, IP address is set by knobs ID2 and FORMAT 2. Hexadecimal
format is used and ID2 corresponds to x161 and FORMAT 2 to x160. The possible IP address is 192.168.1.x,
x=1~FE (1~254).
9-7
AS Ser ies M od ul e Man ua l
_9
9-8
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9.2.4 Wiring
Turn the work mode to COM. Install the module on the right hand side of the AS Series CPU. To avoid problems, do
not use an external power supply for AS00SCM-A.
Turn the work mode to RTU. This module is equipped with an independent DC power connecter.
To ensure the serial communication module functions well and reliably, the external wiring must prevent noise. Before
you install cables, follow the precautions below.
(1) To prevent a surge and induction, the DC cable and other power cables that are connected to the AS00SCM-
A must be separate cables. An independent power supply is recommended for the AS00SCM-A.
SCM AS Series IO
D C Power Supply
24VD C
Min 1.5A
0V 2 4V
Ground
Ground
24V
DC Power Supply
24VD C
0V
Ground
Ground
24V
DC Power Supply Ot her
24V D C devices
0V
Ground
(2) The 24 VDC cable should be twisted pair, and the shorter end should be connected to the module.
(3) The cable (110 VAC, 220 VAC, and 24 VDC) must not be installed near a main circuit, a high-voltage cable,
or a cable connected to a load that is not a PLC. In addition, the cable must not be bound to a main circuit, a
high-voltage cable, or a cable connected to a load that is not a PLC. All the cables should be wired at least
100 mm apart.
9-9
AS Ser ies M od ul e Man ua l
This module comes with two function card slots, supporting AS-F232, AS-F422, and AS-F485 communication cards.
The Card 2 slot also supports the AS-FCOPM communication card (firmware V2.00 or later). Refer to Chapter 10 for
more information on wiring the cards.
The Card 2 slot supports the AS-FCOPM communication card (firmware V2.00 or later), AS-FEN02 (firmware V2.02
or later) and AS-FPFN02 (firmware V2.06 or later). Refer to Chapter 10 for more information on wiring the cards.
_9
9-10
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9.3.1 Modbus
The AS00SCM-A supports standard communication protocols such as Modbus RS232, RS422, and RS485. Once
you create a data exchange table, you can exchange data with slave modules.
You can set up communication format and node ID via HWCONFIG. Refer to section 9.2.3 for more details.
9_
9 - 11
AS Ser ies M od ul e Man ua l
Set up the node ID and communication format. Go to Edit Area -> Function Card1 / Card 2 Setting.
Retry times: set the times for the AS00SCM to retry communication. If no response after the set retry
times, a slave timeout alarm will be triggered.
Received Data Timeout Alarm Enable: available for FW V2.06 or later, you can enable this function so
that if a timeout occurs, an alarm will be triggered. Default: disable.
Select a mode to start. Go to Data Exchange -> Function Card1 / Function Card 2 -> Mode (Program
Control, PLC Run, or Always Enable)
_9
9-12
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Program Control: PLC decides whether the set data exchange is performed. Function Card 1
and Function Card 2 are independent; you can set them up differently.
PLC Run: The set data exchange will be executed automatically when PLC is in RUN state. If
the PLC is in STOP state, the communication will stop.
Always Enable: The data exchange will be executed constantly after PLC is powered on.
9_
Select the Slave Address and the Remote Device Type from their drop-down list.
The Shortest Update Cycle (ms): You can set the shortest update cycle in ms. If a timeout error occurs
too often, you can increase the value here, 10 ms as a unit to find out the best setting value.
Connection Timeouts (ms): You can set the connection timeout time in ms. If for a period of time that
you have set, there is no response from the slave device, this is considered as a timeout. The value here
cannot be set too large, otherwise the PLC will need to wait for the time set for the slave device to
9-13
AS Ser ies M od ul e Man ua l
respond, and this will affect and prolong the data exchange time.
Support Read/Write Synchronization (Function Code: 0x17): the master PLC CPU can use MODBUS
function code to complete read and write synchronization at one operation. However you need to make
sure all the devices support MODBUS function codes; otherwise, the slaves devices may NOT recognize
the function code and fail to complete read/write synchronization.
After the setting is done, click Download. And you can find the Address of Card 1 / 2 Data Exchange
State under the tab of Normal Exchange Area. If the address value is 1 here, it indicates the data
exchange is a success one.
Note: When you use HWCONFIG to scan the modules, the data exchange table of AS00SCM-A can NOT be
copied back to HWCONIG. If you need the data exchange table of AS00SCM-A, you can use Upload on the
tool bar to send the data exchange table of AS00SCM-A back to HWCONFIG.
You can find the corresponding registers in HWCONFIG, after setting up AS00SCM-A as the right-side module of AS
CPU. As the image shown below, you can see the input device range (to write) for Card 1 is from D26000 to D26099
and the output device range (to read) is from D26100 to D26199.
_9
9-14
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9_
9-15
AS Ser ies M od ul e Man ua l
9.3.2 UD Link
The UD Link provides communications with devices that communicate via RS232, RS422 or RS485. You can edit a
packet according to its communication format to send and receive packets. This section introduces the use of UD
Link communications in COM mode.
Notes:
1. Make sure the knob of SCM module is turned to 0 before operation.
Set up the function card. -> Set the communication protocol to UD Link. -> Set up the communication format and
baud rate. -> Download to HWCONFIG. -> Use data length 8 byte as the communication format, 8E1, 8N1, 8O2 and
so forth to ensure a complete transmission. After setting, you need to download HWCONFIG parameters.
_9
9-16
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
2. Opening SCMSoft
Right-click any AS00SCM module if there is more than one AS00SCM module to see the context menu, click
Communication Software and then double-click SCMSoft to open it.
AS00SCM modules can upload UD Link parameters through SCMSoft. Select one slot as one SCM module and one
AS00SCM module at one time.
9.3.2.2 SCMSoft
COM PORT Settings: Here is the parameters set in HWCONFIG and it is a read-only page. If you need to edit the
parameters, close SCMSoft first and then go to HWCONFIG to edit.
9_
9-17
AS Ser ies M od ul e Man ua l
Upload the module parameters to UD Link. -> Right-click Group List to create a group list. -> Double-click the Group
List 1 to set up the slot number on the editing window on the right -> Right-click the created group list on the node to
create groups for data mapping. -> Define the Group ID and Group Name on the editing window on the right.
Group List: One group list corresponds to one slot, do NOT use the same group list on other slots repeatedly. The
slot number in the group list is the actual placement order of AS00SCM-A on the right-side of the PLC. For example,
the slot number 2 in the group list corresponds to the second module on the right-side of the PLC. Once the group list
is assigned to a certain slot, the CARD 1 and CARD 2 of its corresponding module can trigger the group list of the
selected slot.
_9
9-18
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Group List under the Group List: Every group has its Group ID and this number will be used in PLC program as
AS00SCM uses to call for the group to take orders.
Group: Right-click anywhere on the blank area of the Group to create commands. When the Group ID is called,
AS00SCM executes the commands in their numerical order of the called Group ID.
After the group list is created, you can edit packets for transmission.
Send packet / Receive packet: use the packets to be sent or to be received but they can only be used in the
group where they belong. Commands can be used to execute all kinds of packets.
Send: to send packets
Receive: to receive packets
Send & Receive: to send packets and to receive packets 9_
1. COM PORT History: Right-click this node to upload the COM Port History. You can obtain the data stored in the
communication port by selecting the slot (CARD 1 indicating COM 1 and CARD 2 indicating COM2). The data
here include TX and RX packets and the data is included not only AS00SCM data but also other kinds of data as
long as they are from the same communication port.
9-19
AS Ser ies M od ul e Man ua l
Refer to the next section for the settings on packets and commands. After the setting is done, download the
parameters from SCMSoft to PLC. And once a group number is trigger, the function card starts to send and receive
packets according to the command order. Make sure you add the group number in the UD Link group address in the
Normal Exchange area. Refer to section 9.6.2 for more details on operation.
_9
Packet Name: enter the packet name.
Packet Segment Edit: adjust the sequence of segments and add or delete segments.
No.: the segment number. You can create no more than 64 segments.
9-20
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Class: the segment class. The available classes are Message, Address, Length, and Checksum.
Format: the data format of the segment. The available data formats are Hex (hexadecimal), ASCII, and Code.
Message: a message may be either Constant or Variable. Messages can be applied to a header segment, a start
bit segment, an end bit segment, and a data segment. There can be several messages in a packet.
Address: an address may be either Constant or Variable. There can be only one address segment in a packet.
Length: enter the length of a packet. There can be only one length segment in a packet.
Value: enter a value for the length according to the format; unit: byte
Checksum: edit the checksum. There can be only one checksum segment in a packet.
Format: Select Hex, ASCII, or Code in the Format box. If you select Code, the data is a control code.
9_
9-21
AS Ser ies M od ul e Man ua l
Variable: a variable data to read or write. Specify either an internal register in AH10SCM-A or a register in a CPU
module.
Hex: ASCII data is converted into hexadecimal data. ASCII data that cannot be converted into hexadecimal data is
converted into 0.
ASCII: Hexadecimal data is converted into ASCII data. Hexadecimal data that cannot be converted into ASCII
data is converted into 0.
Reverse: the high byte of a one-word checksum which is calculated, and the low byte of the checksum are
reversed.
Variable Property:
Function: for a TX packet, select Read R() for the Function. For an RX packet, select Read R(), Write W(), or *
for the Function.
Length Property:
Function: It is suggested to select to determine the length (*) automatically. The data length can be specified
between the packet interval (around 4 character time length) and should receive all data. Select Read R ( ) for a
variable. And then you can select its corresponding register. The value here is the length. Select Constant and
then you can define the data length.
_9 For a TX packet, you can select the variable and the constant length. For a RX packet, you can select a variable,
constant and determine the length (*) automatically.
9-22
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9.3.2.4 Command
After creating several TX and RX packets, create commands to select packets to be sent and packets to be received.
Also create a sequence to execute the commands.
Command No.: every command has a number. The Command Number indicates the execution order. You can
also use this Command Number to appoint a certain packet for transmission when using Goto function.
Command Type: select Send, Receive, or Send & Receive for the Command Type. Once the type Send is
selected, when the packet is sent, the transmission is considered successful. Once the type Send & Receive is
selected, AS00SCM-A checks if the received data met the definition of RX packet. When they are matched, the
transmission is considered successful.
Success: specify the action to follow the successful execution of the command: Next, Goto, or End.
Next: the next command is executed based on Command Number. If the command that is being executed
is command 1, the next command that will be executed is command 2.
Fail: specify the action to follow the failure of the command: Next, Goto, or Abort.
Next: the next command is executed based on Command Number. If the command that is being
executed is command 1, the next command that will be executed is command 2.
Retry: set the number of times the command will be retried after a failure.
9_
Repeat: set the number of times the command will be repeated after successful execution.
Send Wait: set an interval in milliseconds for the sequence to wait between commands. The default is 0
milliseconds, which causes the next command to be executed immediately after a reply is received.
Timeout: set the amount of time in milliseconds for the system to wait for the command to be executed before
the system reports a communication timeout. The default is 50 milliseconds. When it is set to 0, there
is no timeout message and the module is at the status of waiting to receive.
9-23
AS Ser ies M od ul e Man ua l
9.3.3.1 Features
When using the AS00SCM-A as a slave module, it has the following features:
Supports PDO; up to 8 TxPDO and 8 RxPDO can be configured for every slave.
Supports SDO:
Server: 1
User: 0
Supports SDO (expedited SDO) transmission mode
_9
9-24
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9_
9-25
AS Ser ies M od ul e Man ua l
FORMAT1 Description
0 AS Remote Communication
4 CANopen DS301
8 Delta Special Driver & AS Remote Mode
ID1: 0 (recommended)
ID2: 0 (the knob is no function; set up through ISPSoft); see the table below for the knob setting
range.
Use the knob for setting. You cannot use ISPSoft (HWCONFIG) to set up the communication mode in this
format.
FORMAT2 1 2 3 4 5 6 7 8-F
Byte (bps) 10K 20K 50K 125K 250K 500K 1000K NA
Distance (m) 5000 2500 1000 500 250 100 25 NA
_9
9-26
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Turn the FORMAT1 knob to 0 and it is in AS Remote Communication Mode. In AS Remote Communication mode, an
AS series CPU PLC can connect to as many as 15 AS00SCM-A modules, as long as they are all in RTU mode. The
RTU station number should be set from 1 to 15 in numerical order. RTU mode and baud rate cannot be set via
ISPSoft (HWCONFIG). Use the knob ID2 to set up Node ID and use the knob FORMAT2 to set up the baud rate.
(The baud rate should be the same as the PLC’s baud rate.)
9_
9-27
AS Ser ies M od ul e Man ua l
1. Set up the PLC: AS Remote Communication mode, number of the device: 1; baud rate: 1000kbps; download the
parameters.
2. Set up AS00SCM-A; set the ID1 knob to 0 and FORMAT1 to 0; ID2 knob to 1 and FORMAT2 to 7.
3. Supply power to AS00SCM-A and connect AS00SCM-A to the PLC with a CANopen cable.
4. Resupply power to the PLC and the indicator of CARD2 should keep blinking. That indicates AS00SCM-A and
the PLC are connected. The PLC error indicator should be blinking too, since the setting is not done yet.
6. Download the parameters and check if the PLC error indicator has stopped blinking. Then the setting of one RTU
device is complete.
_9
9-28
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Turn the FORMAT1 knob to 8, and it is in Delta Special Driver & AS Remote Mode. In this mode, an AS series
CPU PLC can connect to as many as 7 AS00SCM-A modules, as long as they are all in RTU mode. The RTU
station number should be set from 9 to 15 in numerical order. RTU mode and baud rate cannot be set via
ISPSoft (HWCONFIG). Use the knob ID2 to set up Node ID and use the knob FORMAT2 to set up the baud
rate. (The baud rate should be the same as the PLC’s baud rate.)
9_
9-29
AS Ser ies M od ul e Man ua l
1. Set up the PLC: Delta Special Driver & AS Remote Modem mode, number of the device: 1; baud rate: 1000kbps;
download the parameters.
2. Set up AS00SCM-A; set the ID1 knob to 0 and FORMAT1 to 8; ID2 knob to 9 and FORMAT2 to 7.
3. Supply power to AS00SCM-A and connect AS00SCM-A to the PLC with a CANopen cable.
4. Resupply power to the PLC and the indicator of CARD2 should keep blinking. That indicates AS00SCM-A and
the PLC are connected. The PLC error indicator should be blinking too, since the setting is not done yet.
6. Download the parameters and check if the PLC error indicator has stopped blinking. Then the setting of one RTU
device is complete.
_9
9-30
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Before using a 3rd party PLC, use AS Series PLC as the CPU and select the AS Remote Communication Mode.
Before connecting to CANopen DS301, turn the AS00SCM-A FORMAT1 knob to 4, and the adjustable range for
station knob ID2 becomes 0x1h~0xFh. This mode is used to communicate with a Master PLC from other brand.
See the detail in section 9.6.3. when the PDO data is mapped, AS00SCM-A can control the IO modules from its
right side.
Double-click the AS Series PLC, then in Device Setting click Function Card 2 Setting and set the function card
2 to AS-FCOPM, set to working mode to CANopen DS301.
1. Set up the PLC: in AS Remote Communication Mode, connect AS series PLC to AS00SCM-A, refer to section
9.4.1.1 for more details.
2. Use AS series PLC to scan the I/O modules installed on the right-side of AS00SCM-A and download the
parameters.
3. If using HWCONFIG to set up the node ID, you can use COM mode to connect AS00SCM-A to the right-side of
AS series PLC directly and no I/O module behind it. Use AS series PLC’s HWCONFIG to scan and add
AS00SCM-A in and then double-click the module to set up its node ID and then download the parameters. After
that, knob ID2 to 0.
4. Install the I/O module to the right side of AS00SCM-A and turn the working mode to RTU.
5. Turn FORMAT1 to 4 and use the CANopen cable to connect to the PLC, and then supply power to AS series
PLC.
Refer to section 9.6.3 PDO examples, if you are using AH10COPM-5A as the CPU.
9_
9-31
AS Ser ies M od ul e Man ua l
It is suggested to use ISPSoft V3.13 or later versions when AS00SCM-A+AS-FEN02 is used in remote mode with AS
or AH PLC CPU. Use HWCONFIG V4.0 to set up EtherNet/IP for AS PLC CPU and use EIP Builder to set up
EtherNet/IP for AH PLC CPU.
When AS00SCM-A+AS-FEN02 is used with the 3rd party EtherNet/IP Scanner, you need to set up the remote IO
modules in EIP Builder (V1.06 or later). Go to Delta Official Website Delta | Download Center (deltaww.com)
(steps: Select Product Category: Industrial Automation; Select Product Sub-Category: PLC- Programmable Logic
Controllers; Select Series: AS Series; Filter: Electrical Parameter and click Submit and then find the EtherNet/IP EDS
File: AS00SCM-RTU (AS-FEN02)) to download the EDS file and then install the downloaded EDS file in the
EtherNet/IP software. Refer to the user manual of the 3rd party EtherNet/IP Scanner for more information.
Refer to section 10.2.7 for more details on the operations of AS-FEN02 installed on AS Series PLC.
9-32
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Using knobs: Highly suggested. You can use ID2 and FORMAT2 knobs to set up the IP address.
Hexadecimal format is used and ID2 corresponds to x161 and FORMAT 2 to x160. The possible IP address is
192.168.1.x, x=1~FE (1~254).
Using IP Manager Tool: You can find IP Manager Tool in HWCONFIG (V4.0 or later). If you need to use an IP
address that is NOT part of 192.168.1.x, you can use IP Manager Tool to set up the IP address. This tool uses
MAC address to recognize the identities of different devices and thus the IP duplication is allowed. It is very
useful when you need to edit the IP addresses of multiple devices at the same time, as long as you know the
MAC address of each device. Check the sticker on the AS-FEN02 communication card for the MAC address.
1. Open EIP Builder and add AS00SCM (RTU) + AS-FEN02 to your network. Make sure all four knobs on the
AS00SCM-A (remote module) are turned to 0. And then connect to your computer via Ethernet.
2. AS-FEN02 (FW V1.02.40 or later) supports IP Manager Tool from the Tool on the tool bar to scan for the
device for IP address setup. You can also edit the devices in different network segments. For example, the
IP address of the device by default is 192.168.1.3 but the IP address of the computer is 192.168.10.5. You
can use IP Setting Tool to edit the device IP address.
9_
9-33
AS Ser ies M od ul e Man ua l
3. If you are using a non Delta EtherNet/IP device as a scanner (master), you need to use EIP Builder. Open
EIP Builder and select IP Manager from the Tool on the tool bar.
4. Select the adapter type and click IP Search or Broadcast Search and then you can edit the parameters.
After the editing is complete, select the device you’d like to download and then click Download.
5. Using IP Setting Tool to change the IP setting mode to DHCP. And after that you can go to IP Manager to
set up the correspondences between the specific MAC address and specific IP address. Follow the steps
below for DHCP setup.
_9
9-34
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Using DHCP: Besides using IP Manager Tool to set the IP setting mode to DHCP mode, you can also use knob
to set the mode to DHCP.
1. When both ID1 and FORMAT 1 are set to 0 and both ID2 and FORMAT 2 are set to F, IP setting mode is in
DHCP mode. And then use Ethernet to connect to your computer.
2. Open EIP Builder and select IP Manager from the Tool on the tool bar.
3. Click Stop the Server and then select a suitable Network Interface. Click Start the Server to complete
the setting. After that, you need to turn the power OFF and then ON so that the devices will send DHCP
requests to the computer.
4. Check the device in the DHCP request form to assign the IP address to its corresponding MAC address.
You can also export the corresponding table. After the assignment is complete, you can see the result in
the status section.
5. After IP setting is complete, you can decide whether to disable DHCP function or not. If the system is in the
absence of a DHCP server (or use IP Setting Tool only for once), it is suggested to use IP Setting Tool to
change the IP setting mode to static mode. If the system includes a DHCP server, it is suggested to keep
the IP setting mode in DHCP mode. Whenever the power of the remote module is OFF, the system clears
all the IP parameters and sends DHCP request out whenever the power of the remote module is ON to
make sure the DHCP server is working.
9_
9-35
AS Ser ies M od ul e Man ua l
1. Connect your AS PLC CPU, ASRTU and computer through EtherNet/IP. Set up the IP addresses for AS PLC
CPU and ASRTU and make sure they are in the same network.
2. Open Project: Open HWCONFIG through ISPSoft and click AS PLC CPU to see the EtherNet/IP setting option.
Click it to open the setting page.
_9
9-36
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
4. Establish a connection: Right-click anywhere on the blank area to see the Fast Connect option and then click it
to open the setting page. Click OK to connect. When ASRTU is connected to AS PLC CPU, its right side IO
modules are also connected.
5. Set up module: Go back to HWCONFIG and Click ASRTU to see the RTU Configuration (Dev_0) option and then
click it to open the setting page for the right-side modules, ASRTU and the handlings after the connection lost.
Refer to section 9.4.3 for more information on Remote Module Setting.
9_
6. Data Exchange: Go to EtherNet/IP setting page and click Show Data Exchange option to see the setting page.
9-37
AS Ser ies M od ul e Man ua l
7. Download: Use the function button Download under the Communication tab in EtherNet/IP setting page to
download the EtherNet/IP parameters. Make sure you are in the setting page of EtherNet/IP.
8. Check the connection: Click the function button On-line Mode under the Communication tab in EtherNet/IP
setting to check the EtherNet/IP connection status.
9. HWCONFIG Table Synchronization: After setting is complete, you can synchronize the devices used by ASRTU
with ISPSoft.
1) Open HWCONfIG Table.
_9 2) You can edit the identifier one by one or click Set All Identifiers to set all identifiers at one time.
9-38
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
3) Go to ISPSoft -> Global Symbols -> HWCONFIG Table: right-click anywhere on the blank area to see and click the
option Synchronize with HWCONFIG. After the synchronization is complete, ASRTU devices are shown in array and
available to be used in PLC program.
9_
9-39
AS Ser ies M od ul e Man ua l
1. Connect your AH PLC CPU, ASRTU and computer through EtherNet/IP. Set up the IP addresses for AH PLC
CPU and ASRTU and make sure they are in the same network.
2. Open Project: Open HWCONFIG through ISPSoft and click AH PLC CPU to see the EtherNet/IP setting option.
Click it to open the setting page.
3. Scan the network to add ASRTU in EIP Builder. Drag the red block and drag it to the same network (Network_0)
as the AH Series PLC does. Double-click ASRTU to open HWCONFIG and set the parameters for ASRTU.
_9
9-40
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
4. Data Mapping
5. You can drag and drop ASRTU from the Product List on the right to add it into the Network View even when it is
in off-line mode.
9_
9-41
AS Ser ies M od ul e Man ua l
6. After the settings are complete, click the Downloader icon and then select the parameters that you’d like to
download. Parameters include:
RTU parameters: all the parameters set in RTU-HWCONFIG in the previous step
Data Exchange: data mapped from the RTU right-side modules of AS00SCM-A to the PLC
_9
9-42
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
1. You can manually or scan the network to add the AS00SCM (RTU) + AS-FEN02 to the network. Click the remote
module to open RTU-HWCONFIG to scan and download the parameters of the right side modules of AS00SCM-
A.
9_
9-43
AS Ser ies M od ul e Man ua l
2. Write down the information in Normal Exchange Area. This is the working order for the 3rd party device to
perform the data exchange. Use AS04DA-A as an example, the first input value is the error code. (all of the
module error codes are the input values; the exchange direction is from remote module inputs to scanner) the 1st
value is the value in channel 1; the 2nd value is the value in channel 2 and so forth. The unit is the length of 2
words.
1. Use EDS Hardware Installation Tool to install the EDS file of ASCPU (AS-FEN02).
2. Right-click Ethernet to see the context menu and click New Module to add a new device in. After that, you
can set up the parameters, including instance for input and output, data length and more. For AS-FEN02
with firmware V1.03 or later, you can open the ASRTU webpage to check the data.
3. After the setting is complete, you can use the module data according to the offset values shown in the
webpage. Input data 0-29 and output data 0-19 are the parameters of AS00SCM-A. Refer to the Normal
Data Exchange area from RTU-HWCONFIG for more corresponding data information.
9-44
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
2. For AS00SCM-A with firmware V2.04 or previous versions, parameter-downloading for ASRTU is connection lost.
If the handling of lost connection is all the I/O modules stop running (default), you need to turn the power off and
then on again after downloading is complete.
For the following four situations, you can either stop I/O module (all I/O modules stop running) or keep I/O module
running (all I/O modules keep the same state).
1) When a Scanner (Master) connection is lost
I/O modules keep the same state: all modules keep running
I/O modules keep the same state: all modules keep running
I/O modules stop running: all I/O modules stop running (after resupply power to resume running)
I/O modules keep the same state: all modules keep running
I/O modules stop running: all I/O modules stop running (after resupply power to resume running)
I/O modules keep the same state: all modules keep running 9_
9-45
AS Ser ies M od ul e Man ua l
No change to
I/O module stops Output value
Master Output value = 0 the output
running Cannot update data =0
connection value
on the master
lost
I/O module keeps
No change to the output value
the same state
_9
9-46
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
The examples above shows that AS00SCM-A is installed as the first module on the right side of AS PLC CPU;
note that the Normal Exchange Area shows the corresponding data registers of the module and the PLC.
Card 1 & Card 2 Data Exchange State: occupies 4 data registers (32-bit data); each bit 1–32 represents the
state of the corresponding data point 1–32 to be exchanged: 0 = none/fail, 1 = success.
Card 1 & Card 2 Data Exchange Mode Control: set the data register to 0: none, 1: once, 2: always.
Card 1 & Card 2 Data Exchange Trigger: occupies 4 data registers; each bit 1–32 represents the state of the
corresponding data point 1–32 to be exchanged: 0 = no trigger, 1 = trigger.
Card 1 & Card 2 UD Link Group ID Trigger: set the group ID to be triggered.
9_
9-47
AS Ser ies M od ul e Man ua l
I/O Module Error Code: refer to the I/O module manual for more information.
RTU State: 0 = communication module is working fine, 1 = communication module is NOT working fine.
I/O Module State: each I/O module uses 1 bit to show its status (0 = normal , 1 = not running normally)
I/O Module Error Code: refer to the I/O module manual for more information.
_9
9-48
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9.6 Application
9.6.1 Modbus
This section introduces how to use the Modbus protocol to connect the AS00SCM-A to other Delta industrial products
such as human-machine interfaces, temperature controllers, programmable logic controllers, AC motor drives, and
servo motors.
0x03 16#0100–16#0163
Read
0x04 16#0200–16#0263
16#0300–16#0363
0x06 16#0000–16#0063
Write
0x10 16#0200–16#0263
16#0000–16#0063
16#0100–16#0163
Read
16#0200–16#0263
0x17
16#0300–16#0363
16#0000–16#0063
Write
16#0200–16#0263
The structures:
Example of a slave structure: HMI (master station) AS-F485 + AS00SCM-A COM1 (slave station)
9_
9-49
AS Ser ies M od ul e Man ua l
If the AS00SCM-A functions as a Modbus slave, you need to set a slave ID and baud rate.
1) Drag to add AS00SCM-A in the system configuration area. Make sure the knob of AS00SCM-A is turned to COM
mode and no power connected to it.
2) Click the I/O Scan button to make the system read the module’s current configuration. The PLC assigns the input
and output device ranges.
_9
Device from which Register in the Device into which Register in the
Function card
data is read CPU module data is written CPU module
Function card 1 16#0000 D26000 16#0100 D26100
Function card 2 16#0200 D26200 16#0300 D26300
9-50
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
4) Set the communication protocol values for COM1 using the HMI settings.
9_
NOTE: Double-click the module to open the Device Setting dialog box to configure the parameters.
9-51
AS Ser ies M od ul e Man ua l
The structures:
Example of a master structure: AS-F485 + AS00SCM-A COM2 (master station) VFD, ASDA, and DVP series PLC
If the AS00SCM-A is functioning as a Modbus master, you need to set a slave ID and baud rate.
1) Drag to add AS00SCM-A in the system configuration area. Make sure the knob of AS00SCM-A is turned to COM
mode and no power connected to it.
_9
9-52
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
2) Double-click COM2 Setting and set the Function Card Type to AS-F485.
3) Click the I/O Scan button to make the system read the module’s current configuration. The PLC assigns the input
and output device ranges.
9_
9-53
AS Ser ies M od ul e Man ua l
_9
9-54
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
6) Set up the data exchange table: select Data Exchange – COM2 and click Add to create a new Data Exchange
Setup table.
7) In the Data Exchange Setup table double-click an item to edit its settings.
Select Standard Modbus Device as the Remote Device Type, enter the parameters, and check Enable.
9-55
AS Ser ies M od ul e Man ua l
Select Standard Modbus Device as the Remote Device Type, enter the ASDA parameters, and check
Enable.
Select PLC devices as the Remote Device Type, enter the PLC parameters, and check Enable.
9-56
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
NOTE: If the Data Exchange Mode Control is set by the program, you can check and control the register address
on the Normal Exchange Area page. The following example shows when writing “2: always” to D28021, it
indicates Card 2 is always the one to perform data mapping.
9_
9-57
AS Ser ies M od ul e Man ua l
If you set Mode to Always Enable, the data exchange begins immediately after downloading the parameters.
If you set Mode to Program Control, the program starts the data exchange after downloading the parameters.
9.6.2 UD Link
This section introduces how to use a non-Modbus RS485 communication port on the AS00SCM-A to connect to other
industrial products.
RS 485 9600, 7, E, 1
Communication with a slave
POS, xxx, yyy POS, ACT xxx and yyy are coordinates (0–999)
1) Drag to add AS00SCM-A in the system configuration area. Make sure the knob of AS00SCM-A is turned to COM
mode and no power connected to it.
_9
9-58
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9_
9-59
AS Ser ies M od ul e Man ua l
4) Select UD Link as the Protocol, set the Baud Rate and Format, and click OK.
5) Right-click the AS00SCM-A and click Communication Software and then click SCMSoft.
_9
9-60
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
6) Right-click Group List and then click Create Group List to create a group list.
7) You can find a created Group List1. Double-click it to open an editing window to edit the Group List Name and
the Slot.
Give the group list a Name (this example uses “Slave_Simulation”) and select 1 (COM1) as the Slot number.
9_
9-61
AS Ser ies M od ul e Man ua l
8) Right-click Slave_Simulation and click Create Group List to create a group list for the Slave_Simulation group.
9) You can find a created Group List1. Double-click it to open an editing window to edit the Group List Name and
the Slot.
_9
9-62
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9_
9-63
AS Ser ies M od ul e Man ua l
12) Give the Packet a Name (This example uses “TX POS Send”)
_9
9-64
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
13) Edit the TX packet, “POS, xxx, yyy” (The example below uses POS, 123, 123)
Enter “POS” in the Value area. Click OK and verify the packet contents in the Packet View.
9_
9-65
AS Ser ies M od ul e Man ua l
15) [xxx] is a variable, so click Variable in the Message area to edit it. Use ISPSoft to get the value from data
registers D26100–D26101. The example below uses D26100: 16#3132 and D26101: 16#3300 and the value is
123.
16) Enter the data register that contains the value you want to find. The example below uses D26100 and the value
returned is 3. Use ISPSoft to get the value from data registers D26100–D26199.
_9
9-66
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Click OK and verify the values (”POS,”+(R(D Register [26100], 3))in the Packet View.
17) [,]: Use Address Constant to enter this Value and set the Format to ASCII.
Click OK and verify the values (”POS,”+(R(D Register [26100], 3))in the Packet View.
18) [yyy] is a variable, so click Variable in the Message area to edit it. Use ISPSoft to get the value from data
registers D26102–D26103. The example below uses D26102: 16#3132 and D26103: 16#3300 and the value is
123.
9_
9-67
AS Ser ies M od ul e Man ua l
19) Enter the data register that contains the value you want to find. The example below uses D26102 and the value
returned is 3. Use ISPSoft to get the value from the data registers D26100–D26199.
Click OK and verify the values (”POS,”+(R(D Register [26102], 3))in the Packet View.
20) Edit the packet: Create a packet and name it “RX Result”. Double-click it to open the editing window.
_9
9-68
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Enter the sending packet into the D26000 register of the AS300 CPU. “*” indicates that the length is not
specified.
21) Create a command: Right-click Master Send and click the Create Command.
9_
9-69
AS Ser ies M od ul e Man ua l
22) Double-click the new command on the list to open the Command Edit window.
23) Set Send Packet to “TX POS Send” and set Recv Packet (received contents) to “RX Result”.
_9
9-70
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
25) Click the Download button to download the parameters to the AS00SCM.
9_
9-71
AS Ser ies M od ul e Man ua l
26) Set up the devices for the UD Link Group ID Trigger in HWCONFIG. Once you create the AS00SCM-A module,
the system automatically assigns the corresponding addresses.
27) Double-click AS00SCM-A to open the Device Setting page. Verify that the Card 1 UD Link Group ID Trigger is set
to D28030. Use ISPSoft to enter 1 into register D28030 to start the data exchange.
_9
9-72
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
28) Use the monitor function in ISPSoft to verify that the transmission is working correctly.
29) In SCMSoft, right-click the item COM PORT History on the left and click the option “Upload COM History Data” to
see the transmission history of COM1 and COM2 respectively. Under the item COM1 and COM2, you can view
recent transmission history; however the shown recent history cannot be deleted or saved.
30) Select Tools -> Return to Default to clear the previous settings and have all the settings back to defaults. After
this, turn the power off and on again.
Device Function
Scan and download AS00SCM-A (RTU mode),
AS300
right side module configurations
AS00SCM-A + AS-FCOPM CANopen Slave
AHCPU530-EN + AH10COPM-5A CANopen Master
AS16AN10R-A 16 Digital outputs
AS16AM01N-A 16 Digital inputs
AS04DA-A 4 Analog channels for output
AS04AD-A 4 Analog channels for input
9_
9-73
AS Ser ies M od ul e Man ua l
Step 1
Use AS300 to connect to AS00SCM-A through AS Remote Communication (RTU mode) and then use HWCONFIG to
scan and download the parameters. If the Card 2 LED is blinking normally, with no error messages, and no need to
download the PLC programs, the device power can be turned off. Refer to Section 9.4.1.1 for reference.
_9
9-74
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Step 2
Turn the Format 1 of AS00SCM-A to 4 (using CANopen DS301 mode) and turn Format 2 to 7 (setting the bit rate to
1000kbps) and then turn the power off and on again. After that wiring AH10COPM-5A and set the node ID to 2 and
set the bit rate to 1000kbps. Use ISPSoft (V3.04 or later) and HWCONFIG to scan and download the parameters to
AH500. Right click AH10COPM-5A and open Intelligent Module Configuration (CANopen Builder) from the menu.
Step 3
Use CANopen Builder to scan the network. You should find Node ID 1 and its name to be AS00SCM-A RTU.
If not, check if you follow the first two steps right. And repeat the previous steps. Recommended to set the value in
cycle period to 50 ms to ensure a more complete module functions. Double click the module to open the Node
Configuration window and set up the PDO manually. RPDO is for DO/AO and TPDO is for DI/AI and error codes of
RTU/IO.
9_
9-75
AS Ser ies M od ul e Man ua l
Step 4
Here uses a first right side digital output module (16 points) as an example.
1. Since it is the first one, here it corresponds to Receive PDO1 (index: 1400), indicating RTU receives data from
Master through CANopen communication. (If this is an input module, it sends data to Master through CANopen
communication.) Double click to add it in the table. Double click the table to open the PDO setting window.
2. Since it is the first one, here it corresponds to Rx_Module 1. It is a 16-point digital output module so that only
the object of one word Rx_Module1_EDO0 (Index: 2000) should be selected. Click the arrow to add it into the
data mapping parameter table and you have set up a PDO for the first module. If t is a 32-point digital output
module, objects of 2 words Rx_Module1_EDO0 and Rx_Module1_EDO1 should be selected in numerical
order.
_9
9-76
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Mapping
Device Function PDO PDO Mapping
Registers
AS16AN01R-A 16 digital outputs RxPDO1 Rx_Module1_EDO0 D6000
AS16AM01N-A 16 digital inputs TxPDO2 Tx_Module2_EDI0 D5000
4 Analog Rx_Module3_EDO0 D6001
channels for Rx_Module3_EDO1 D6002
AS04DA-A RxPDO3
output Rx_Module3_EDO2 D6003
(Integer format)* Rx_Module3_EDO3 D6004
4 Analog Tx_Module4_EDI0 D5001
channels for Tx_Module4_EDI1 D5002
AS04AD-A TxPDO4
input Tx_Module4_EDI2 D5003
(Integer format)* Tx_Module4_EDI3 D5004
Tx_Module1_error_code D5005
IO Module Tx_Module2_error_code D5006
- TxPDO5
Error Code Tx_Module3_error_code D5007
Tx_Module4_error_code D5008
RTU Error Code - TxPDO6 Tx_RTU_error_code D5009
* Here the analog module uses integer format; if you need to use floating point format, two PDOs will be used per
channel.
* Index 2002 to Index 200d are for system internal use only. Avoid using this range, when PDO is used.
Step 5
Double click the PLC icon and select Node ID 001 from the available nodes and then use the Right arrow to add the
selected one into the Node List. Output and Input tables are mapping registers for PDOs.
9_
9-77
AS Ser ies M od ul e Man ua l
Step 6
Double click the module icon and the Node Configuration window appears. Click Error Control Protocol and then
Error Control Setting windows appears. Select Heartbeat and set values for the Master Consumer Timeout and
Node Heartbeat Producer Timer. Select AH10COPM Master from the Node List and click the Down arrow to add it
to the list of Heart Consumer and then disconnection detection is now available for AS00SCM-A (RTU mode).
_9
9-78
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Click OK to confirm the setting. Download the parameters to the PLC. And then PLC can control the input/output of
the IO module remotely.
Start ISPSoft and download the program from AH series PLC. Switch digital output module between 1 and 0 in every
0.5 seconds; change output values of the analog output module. Wire DI/DO modules to AI/AO modules and then
you can see the changes of D6000 from D5000 and D6001-D6004 from D5001-D5004 as the example below shown.
The module error codes are stored in D5005-D5009. Refer to relevant module manuals for error code definitions.
9_
9-79
AS Ser ies M od ul e Man ua l
Here use EIP Builder to demonstrate. For ISPSoft V3.13 or later, there is no need to use EIP Builder, you can
complete the settings in HWCONFIG. Refer to section 9.4.2.3 for more information.
Step 1
After setting up AS300 in ISPSoft and HWCONFIG. Open EIP Builder and scan the network to add AS00SCM-A
(RTU) + AS-FEN02 to the Network. Double-click RTU module to open HWCONFIG and scan to obtain the
configuration and mapped register addresses of the I/O module on the right side of AS00SCM-A. You can also edit
the module configurations and write down the mapped register addresses. After saving, close HWCONFIG.
_9
9-80
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Step 2
You can see the IP address and the data length from the data mapping table in EIP Builder. The data mapping table
can be downloaded and upload the mapped data to the device.
Step 3
Start ISPSoft and switch digital output module between 1 and 0 in every 0.5 seconds and shift output values of the
analog output module between 10 V and 5V. Wire DI/DO modules to AI/AO modules. Refer to Chapter 2, 3 and 4 in
this manual for more details on module operation.
9_
9-81
AS Ser ies M od ul e Man ua l
The following example shows how to add multiple AS00SCM-A (RTU) + AS-FEN02 (hereafter referred to as the
“RTU”) to an AS Series PLC in EIP connection. All IP addresses of RTU are set by the software.
Turn all the knobs of the FORMAT 2 of the 3 new RTUs to 0. The default IP addresses are 192.168.1.3. Refer to
section 9.4.2.2 for more information on using IP Setting Tool to set up the IP address.
Step 2
After the IP addresses of the 3 new RTUs are set, you can scan and add them in the network and connect to the AS
Series PLC. Do not download the project before uploading the already set RTU values to the network.
Now you can set up the right-side module of RTU. Refer to section 9.6.4 for more details. Scan all the RTU and save
the parameters. Make sure the data mapping table is updated and then download the project, including the
parameters, configurations, and data mapping table to the AS Series PLC and the RTUs.
_9
9-82
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
9_
9-83
AS Ser ies M od ul e Man ua l
Error
Description Solution
Code
1. Check that the module is securely installed.
16#1605 Hardware failure
2. Install a new AS00SCM-A or contact the factory.
1. Check if the function card is securely installed.
2. Install a new function card or contact the factory.
16#1606 The function card setting is incorrect. 3. Check if the setting in HWCONFIG is consistent
with the function card setting.
4. Install a new AS00SCM-A or contact the factory.
The following error codes identify possible errors when the AS00SCM-A module is installed on the right side of the
CPU module and acts as a communication module.
Error
Description Solution
Code
Check the parameter in HWCONFIG. Download the
16#1802 Incorrect parameters
parameter again.
1. Check whether the communication cable is
properly connected.
2. Check if the station number and the
16#1803 Communication timeout
communication format are correctly set.
3. Check if the connection with the function card is
working correctly.
1. Check the settings of the UD Link.
16#1804 The UD Link setting is incorrect.
2. Check the warning settings in the PLC.
The following error codes can only be viewed with SCMSoft; when the following errors occur, they are not shown on
the LED indicators and the system does not send the error messages to the CPU module.
Error
Description Solution
Code
The settings in HWCONFIG and manual Check the settings in HWCONFIG and manual
16#0107 settings are not consistent with function settings for function card 1.
card 1.
The settings in HWCONFIG and manual Check the settings in HWCONFIG and manual
16#0108 settings are not consistent for function card settings for function card 2.
_9 2.
Check the parameter in HWCONFIG. Download the
16#0201 Incorrect parameters
parameter again.
1. Check if the station number and the
communication format are correctly set.
16#0301 Function card 1 communication timeout
2. Check if the connection with the function card is
working correctly.
9-84
Ch ap te r 9 Ser ia l C om mu nic a ti on Mod ul e AS00 SC M
Error
Description Solution
Code
1. Check if the station number and the
communication format are correctly set.
16#0302 Function card 2 communication timeout
2. Check if the connection with the function card is
working correctly.
Invalid UD Link Group ID for function card 1. Check the UD Link settings.
16#0400
1 2. Check the warning settings in the PLC.
Invalid UD Link Group ID for function card 1. Check the UD Link settings.
16#0401
2 2. Check the warning settings in the PLC.
Invalid UD Link Command for function card 1. Check the UD Link settings.
16#0402
1 2. Check the warning settings in the PLC.
Invalid UD Link Command for function card 1. Check the UD Link settings.
16#0403
1 2. Check the warning settings in the PLC.
Error
Description Solution
Code
1. Check if the module is securely installed.
16#1301 Hardware failure 2. Change and install a new AS00SCM-A or contact
the factory.
1. Check if the function card is securely installed with
the AS-FCOPM card.
2. Change and install a new function card or contact
16#1302 The function card setting is incorrect. the factory.
3. Check if the setting in HWCONFIG is consistent
with the function card setting.
4. Install a new AS00SCM-A or contact the factory.
More than eight remote modules on Check the total number of remote modules on the right
16#1304 side of the CPU module (maximum is 8).
the right side of the CPU module.
9-85
AS Ser ies M od ul e Man ua l
Error
Description Solution
Code
16#1500 Remote module communication timeout Make sure the communication cable is well connected
Check the parameter in HWCONFIG. Download the
16#1502 Incorrect parameters parameter again. Or use the knob to restore the
modules to the default settings.
Make sure the communication cable is well connected
Remote extension module communication
16#1503 and the module is properly connected to the CPU
timeout
module and turn the modules on again.
The actual placement of the extension Check if the parameter in HWCONFIG is the same as
16#1505
modules is NOT the same as it is set. the actual placement.
1. Make sure the module is properly connected to the
Extension module communication CPU module and turn the modules on again.
16#1604
timeout 2. If the problem persists, contact the local authorized
distributors.
This happens when the 24 VDC power supply for the remote module is not sufficient. Check the power supply. If the
power supply is normal, remove the extension module from the CPU module and then check if the SCM remote
module is out of order. Error codes:
Error
Description Solution
Code
24VDC power supply had not been Check whether the 24 V power supply to the module is
16#1303 sufficient before and then recovered from normal.
low-voltage that was less than 10 ms.
_9
9-86
10
Chapter 10 Function Cards
Table of Contents
10-1
A S S er i es Mo d u le Ma n ua l
10.1 Introduction
Function cards are extension cards such as analog input/output (AI/AO) and communication cards for the AS Series
PLC.
Wiring example
AS-F232
(DB9 female) + + Superior
machine
10.2.2 AS-F422
Use the AS-F422 extension card to communicate with Delta HMI devices or other devices that use an RS-422
communication port. Other than the different communication interface, the communication functions remain the same as
the built-in ones. You can set the communication port as either a slave or a master node. After installing the extension
card, use HWCONFIG in ISPSoft to configure the communication.
Wiring example for communication with Delta HMI DOPA series via COM2
AS-F422 Delta HMI DOPA series
1 R+ Tx+ 3 6 RT S-
2 R- Tx- 4 7 RT S+
3 T+ Rx+ 2 8
4 T- Rx- 1 9 CT S+
CT S-
COM2/DB-9
10.2.3 AS-F485
With its own standalone communication port, the AS-F485 card can work independently and can be either a slave or a
master node. After installing the extension card, use HWCONFIG in ISPSoft to configure the communication.
Wiring example
Master node Slave node Slave node
D+ D- SG D+ D- SG SG D+ D-
Terminal Terminal
resistor resistor
(120 ohm) (120 ohm)
Shielded Shielded
10 cable cable
10-2
Ch a pt er 1 0 F unc t i on C ar ds
10.2.4 AS-F2AD
2 DC analog signal input channels:
Conversion Time*3 3 ms / CH
Digital Value Output
4000
Characteristic Curve
0 10V 4 20mA
Curr ent input
Voltage input
*2: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the input signal is
below the lower limit, it only shows the minimum value. If the input signal exceeds the hardware input limit, it also
exceeds the digital conversion limit and a conversion limit error appears. For example in the current input mode (4 mA to
20 mA), when the input signal is 0 mA, exceeding the hardware lower limit, it also exceeds the conversion lower limit.
The module uses the lower limit value (-48) as the input signal. If a disconnected analysis is required, you can check if
the digital conversion value is -48.
*3: The conversion time is the time for each channel to convert signals to hardware input signals. If you need to calculate
a complete conversion time, you need to add the PLC scan time.
*4: Use the program to read the values in SR to obtain the corresponding A/D conversion value for the channel.
Refer to section 2.2.16 from AS Programming Manual for more information on SM27 and SR27.
10
10-3
A S S er i es Mo d u le Ma n ua l
10.2.5 AS-F2DA
2 DC analog signal output channels:
Analog Signal 0 V - 10 V 4 mA - 20 mA
10V
Voltage Output
20mA
0 4 4000
4000 Digital Value Input
Di gital Value Input
*2: Use the MOV instruction to move the value to the SR to obtain the corresponding voltage output value.
10.2.6 AS-FCOPM
With its own standalone communication port, the AS-FCOPM card can work independently and can be either a slave or a
master node. After installing the extension card, use HWCONFIG in ISPSoft to configure the communication.
Wiring example
Terminal Terminal
resistor Shielded resistor
(120 ohm) cable (120 ohm)
10
10-4
Ch a pt er 1 0 F unc t i on C ar ds
10.2.7 AS-FEN02
This communication card can work independently and does NOT occupy the communication port of PLC CPU. It can act
as Modbus TCP Server or Client and EtherNet/IP Adapter. After AS-FEN02 is installed, you can go to HWCONFIG from
ISPSoft to do the editing in the Function Card 2 section.
All the AS-FEN02 parameters are stored in AS300 PLC CPU or AS00SCM-A. If you need the IP address of AS-FEN02,
you need to go to HWCONFIG from ISPSoft to check its IP address in the Function Card 2 section. You can also use
COMMGR to see the IP address of this device.
The firmware of AS00SCM-A module should be V2.02 or later for AS-FEN02 to be installed on it. AS00SCM
should be in RTU mode only, not supported when installed on the right-side of the AS PLC CPU.
AS-FEN02 AS00SCM-A
V1.00 V2.02
Compatible firmware
V1.02 V2.04
versions
V1.03 V2.06
If using Delta AS/AH PLC CPU in RTU mode, it is suggested to use ISPSoft V3.13 or later. Use HWCPNFIG
V4.0 to set up EtherNet/IP for AS PLC CPU and use EIP Builder to set up EtherNet/IP for AH PLC CPU.
If using the 3rd party EtherNet/IP Scanner in RTU mode, it is suggested to use EIP Builder V1.06 or later to
set up the remote IO modules.
10.2.7.2 Features
AS-FEN02 can be installed on AS300 Series PLC and AS00SCM-A (in RTU mode). But the firmware of
AS00SCM-A module should be V2.02 or later for AS-FEN02 to be installed on it. AS00SCM should be in
RTU mode only, not supported when installed on the right-side of the AS PLC CPU.
This section introduces the operations when it is installed on AS300 Series PLC. For the operations when it
is installed on AS00SCM-A, refer to Chapter 9 for more details.
When AS-FEN02 is installed on AS300 Series PLC, it acts as a Scanner or an Adapter for Modbus TCP
connection. Go to HWCONFIG and click AS300 PLC CPU. Select Data Exchange in the editing area and if
the AS-FEN02 is installed, you can find FEN02 in the function card section. Click it to edit the data exchange
table. The rest is the same as using the built-in connection port for communication. Refer to Chapter 8 from
AS Series Hardware and Operation Manual for more details.
10
10-5
A S S er i es Mo d u le Ma n ua l
When AS-FEN02 is installed on AS300 Series PLC, it acts as an EthernNet/IP Adapter but not EtherNet/IP
Scanner for EtherNet/IP connection. When using Delta PLC CPU, you can use EtherNet/IP software to scan
and add the device in.
When AS00SCM-A+AS-FEN02 is used with the 3rd party EtherNet/IP Scanner, you need to set up the
remote IO modules in EIP Builder (V1.06 or later). Go to Delta Official Website Delta | Download Center
(deltaww.com) (steps: Select Product Category: Industrial Automation; Select Product Sub-Category: PLC-
Programmable Logic Controllers; Select Series: AS Series; Filter: Electrical Parameter and click Submit and
then find the EtherNet/IP EDS File: AS00SCM-RTU (AS-FEN02)) to download the EDS file and then install
the downloaded EDS file in the EtherNet/IP software. Refer to the user manual of the 3rd party EtherNet/IP
Scanner for more information.
10.2.7.3 Specifications
System Specifications
Item Specification
Scanner, Adapter, and RTU communication
Device type
interface
Topology Star and linear topologies are supported.
When installed on AS300 PLC CPU, you can
only use HWCONFIG from ISPSoft for editing.
When installed on AS00SCM-A and used for
RTU application, you can edit via software
or hardware.
Software: Set the ID2 and FORMAT2 to
IP Settings
General 0x000 and use HWCONFIG from EIP Builder
for editing.
Hardware: Use the ID2 and FORMAT2 to set
IP address to 192.168.1.X (X=1~254) or turn
ID2 and FORMAT2 to 0xFF to make it in
DHCP mode.
AS300 Series PLC
AS00SCM-A (available only for RTU mode; NOT
Availability
supported when installed on the right-side of the AS
PLC CPU.)
Max. connection number 8
View device information
Account management
Web
Functions AS-FEN02 firmware update
When installed in AS00SCM-A and in RTU mode,
10 the module monitoring is supported.
10-6
Ch a pt er 1 0 F unc t i on C ar ds
EtherNet/IP Specifications
Item Specification
General Device type Adapter
CIP connection number 8
TCP connection number 8 (Servers)
CIP Network I/O
Requested Packet Interval (RPI) 1 ms~1000ms
Connection
Max. Transmission Speed 10,000 pps
Max. data length/per transmission 200 bytes
Class 3
(Connected Type) Total 8 (Servers)
UCMM (for both class 3 and UCMM connection
(Non-Connected Type, only uses types)
TCP connections)
Identity Object (16#01)
CIP Network
Message Router Object (16#02)
Explicit Message
Assembly Object (16#04)
Connection Manager Object (16#06)
CIP Objects
Port Object (16#F4)
TCP/IP Interface Object (16#F5)
Ethernet Link Object (16#F6)
Not supporting self-defined objects
10
10-7
A S S er i es Mo d u le Ma n ua l
10.2.7.4 IP Setting
The IP address of AS-FEN02 is not stored on the function card. When you install AS-FEN02 onto AS300 PLC CPU
or AS00SCM-A, the IP settings of AS-FEN02 will be obtained automatically.
When installed on AS300 PLC CPU, you can go to ISPSoft -> HWXONFIG -> Function Card 2 Setting -> Ethernet
Port Basic Setting to edit the parameters.
AS-FEN02 can be installed on AS00SCM-A (firmware V2.02 or later) so that AS00SCM-A can act as a remote
module. When the knob is set to 0, the IP address is 192.168.1.3 by default. Before setting up the remote IO
module, you need to set up the IP settings. Two methods for you to set up the IP addresses for AS-FEN02 installed
on AS00SCM-A.
Using knobs: Highly suggested. You can use ID2 and FORMAT2 knobs to set up the IP address.
Hexadecimal format is used and ID2 corresponds to x161 and FORMAT 2 to x160. The possible IP address is
192.168.1.x, x=1~FE (1~254). (DHCP mode)
Using IP Manager Tool: You can find IP Manager Tool in HWCONFIG (V4.0 or later). If you need to use an IP
address that is NOT part of 192.168.1.x, you can use IP Manager Tool to set up the IP address.
1. Open EIP Builder and add AS00SCM (RTU) + AS-FEN02 to your network. Make sure all four knobs on the
AS00SCM-A (remote module) are turned to 0. And then connect to your computer via Ethernet.
10
2. AS-FEN02 (FW V1.02.40 or later) supports IP Manager Tool from the Tool on the tool bar to scan for the
device for IP address setup. You can use IP Search to search for one specific IP Search or use Broadcast
10-8
Ch a pt er 1 0 F unc t i on C ar ds
Search to scan all the AS-FEN02 in the network. This tool can be used when there is IP duplications, the IP
addresses are in various network segments, or you need to edit the IP addresses of multiple devices at the
same time.
3. Steps:
1) Select an Adapter.
2) Search for the function card you’d like to add through IP Search or Broadcast Search.
3) This tool uses MAC address to recognize the identities of different devices and you can use the MAC
address of each device to edit the IP addresses of multiple devices at the same time.
4) Select one or multiple devices at the same time and click Download. After downloading, you can scan the
devices again to check if the parameters are correct.
Note: You can use IP Manager Tool, when AS-FEN02 is installed on AS300 PLC CPU, but do not use it to set up the IP
address to avoid conflicts with the parameters of AS300 PLC CPU project.
10
10-9
A S S er i es Mo d u le Ma n ua l
10.2.7.5 SM/SR
Special Auxiliary Relays (SM)
AS300 Series
AS200 Series
Attribute
Latched
OFF STOP RUN
Default
SM Function
ON RUN STOP
SM1006 Data exchange through AS-FEN02 enabled by ISPSoft. ○ – OFF – OFF N R/W OFF
Connection 1 for data exchange through AS-FEN02
SM1008 ○ – OFF – – N R/W OFF
started
Connection 2 for data exchange through AS-FEN02
SM1009 ○ – OFF – – N R/W OFF
started
Connection 3 for data exchange through AS-FEN02
SM1010 ○ – OFF – – N R/W OFF
started
Connection 4 for data exchange through AS-FEN02
SM1011 ○ – OFF – – N R/W OFF
started
Connection 5 for data exchange through AS-FEN02
SM1012 ○ – OFF – – N R/W OFF
started
Connection 6 for data exchange through AS-FEN02
SM1013 ○ – OFF – – N R/W OFF
started
Connection 7 for data exchange through AS-FEN02
SM1014 ○ – OFF – – N R/W OFF
started
Connection 8 for data exchange through AS-FEN02
SM1015 ○ – OFF – – N R/W OFF
started
Successful data exchange connection 1 through AS-
SM1016 ○ – OFF – – N R OFF
FEN02
Successful data exchange connection 2 through AS-
SM1017 ○ – OFF – – N R OFF
FEN02
Successful data exchange connection 3 through AS-
SM1018 ○ – OFF – – N R OFF
FEN02
Successful data exchange connection 4 through AS-
SM1019 ○ – OFF – – N R OFF
FEN02
Successful data exchange connection 5 through AS-
SM1020 ○ – OFF – – N R OFF
FEN02
Successful data exchange connection 6 through AS-
SM1021 ○ – OFF – – N R OFF
FEN02
Successful data exchange connection 7 through AS-
SM1022 ○ – OFF – – N R OFF
FEN02
Successful data exchange connection 8 through AS-
SM1023 ○ – OFF – – N R OFF
FEN02
Error in data exchange connection 1 through AS-
SM1024 ○ – OFF – – N R OFF
FEN02
Error in data exchange connection 2 through AS-
SM1025 ○ – OFF – – N R OFF
FEN02
Error in data exchange connection 3 through AS-
SM1026 ○ – OFF – – N R OFF
FEN02
Error in data exchange connection 4 through AS-
SM1027 ○ – OFF – – N R OFF
FEN02
Error in data exchange connection 5 through AS-
SM1028 ○ – OFF – – N R OFF
10 FEN02
Error in data exchange connection 6 through AS-
SM1029 ○ – OFF – – N R OFF
FEN02
10-10
Ch a pt er 1 0 F unc t i on C ar ds
AS300 Series
AS200 Series
Attribute
Latched
OFF STOP RUN
Default
SM Function
ON RUN STOP
Special auxiliary
Refresh time
relay
SM1006 After the parameters of data exchange are downloaded, you set the flag to ON or OFF.
SM1008~SM1015 After the parameters of data exchange are downloaded, you set the flag to ON or OFF.
SM1016~SM1031 The flag is ON, when the system is refreshed automatically.
Attribute
Latched
OFF STOP RUN
Default
AS300
AS200
Series
Series
SR Function
ON RUN STOP
1 0 - 11
A S S er i es Mo d u le Ma n ua l
Attribute
Latched
OFF STOP RUN
Default
AS300
AS200
Series
Series
SR Function
ON RUN STOP
Special data
Refresh time
register
SR1520~SR1535 Refresh after AS-FEN02 communication is done.
SR1536~SR1539 The flag is ON, when the system is refreshed automatically.
10
10-12
Ch a pt er 1 0 F unc t i on C ar ds
The below example uses PLC 1 and PLC 2 (with AS-FEN02) to connect to each other and perform data mapping through
EtherNet/IP connection. When AS PLC CPU acts as a Scanner, you need to set the network to EtherNet/IP in ISPSoft.
Refer to Chapter 9 in AS Series Hardware and Operation Manual for more details on AS Series PLC acting as
EtherNet/IP Scanner.
Steps
(1) Right-click AS PLC CPU of the PLC1 project in HWCONFIG and then select Communication Software ->
EtherNet/IP.
(2) Scan the network or to add ASCPU(ASFEN02) (the latest version) manually. After adding the function card in,
drag and drop it to the red dot of Network_0 to add it to the same network as the scanner’s. Click Data
Exchange tab to open the data exchange table and to edit the data mapping table, including Scanner Start
Address, Adapter Starter Address, and Length for data mapping between the scanner and adapter; the unit for
data length is word.
(3) Click the Download on the tool bar and then start data exchange. Click the On-line Mode to check the
connection status. 10
10-13
A S S er i es Mo d u le Ma n ua l
(1) Right-click Ethernet to see the context menu and click New Module to add a new device in.
(2) Set up the parameters including device name, IP address and many more. For basic operation, you can use the
default EDS file directly. No need to edit the EDS file. But you should change the data type to meet the system
format. Click Change in the section of Module Definition on the General tab to change the data type according to
your needs. Here the data type is INT, meaning when monitoring, data in each deice is shown in one word (a D
device).
I: Input data (TO), The Scanner reads data from the Adapter.
Ex. Connection 1 is corresponding to PLC D3000~D3099.
C: here corresponds to the configurations. You can edit the corresponding PLC addresses of input and output. After
editing, you need to download the parameters to the 3rd party PLC and establish a connection to make the changes
become effective.
10-14
Ch a pt er 1 0 F unc t i on C ar ds
The following example shows two AS Series PLCs (one with AS-FEN02) to connect each other and one as Master and
the other as Slave (AS-FEN02) to perform data mapping through the Modbus TCP connection. For the support function
codes and corresponding addresses, refer to AS Series Operation Manual for more details.
Step 1
Double click AS Series PLC in HWCONFIG and the Device Setting window appears. Set up the IP Address of the A to
192.168.1.3 and then connect Master and Slave AS-FEN02.
10
10-15
A S S er i es Mo d u le Ma n ua l
Step 2
Create a data mapping table in the Master and then perform data mapping with the Slave (AS-FEN02).
Step 3
Click the Downloader icon and then select the parameters that you’d like to download.
10
10-16
Ch a pt er 1 0 F unc t i on C ar ds
10
10-17
A S S er i es Mo d u le Ma n ua l
c. The menu shows data based on the permission of the current user.
Permission
Nodes
Administrator Read
Device information V V
Account management V X
Firmware update V X
Save configuration V X
d. Account Management: You can set 2 kinds of access types, Administrator and Read. After the setting is done,
click Apply and save the settings in Save configuration.
e. Firmware Update: You can update the firmware of AS-FEN02 via the webpage.
f. Save Configuration: After any setting is done, save the settings in Save Configuration to reflect the changes.
b. The menu shows data based on the permission of the current user. When it is installed on AS00SCM-A, you
10 can monitor the right-side module (Hardware Status) and check the EtherNet/IP connection information.
10-18
Ch a pt er 1 0 F unc t i on C ar ds
Permission
Nodes
Administrator Read
Device information V V
Account management V X
Firmware update V X
Hardware status* V V
EtherNet/IP information** V V
Save configuration V X
Note:
* AS00SCM-A is recognizable for AS-FEN02 FW V1.13 or later, AS00SCM-A FW V2.06 or later.
** AS-FEN02 firmware V1.13 supports webpage monitoring function.
c. Hardware Status: you can monitor the connected right-side I/O modules, including their module names, the
current values, statuses and error codes. You can edit the values in the Refresh Cycle to update the cycle.
d. EtherNet/IP Information: when using a 3rd party device as an EtherNet/IP Scanner, you can check this page for
more information on connection parameters. Refer to Chapter 9 for more information on AS00SCM-A.
10-19
A S S er i es Mo d u le Ma n ua l
10.2.8 AS-FPFN02
When AS-FPFN02 is installed on AS300 PLC CPU, this communication card can work independently and does NOT
occupy the communication port of PLC CPU. AS-FPFN02 can act as a PROFINET adapter and connect to a PROFINET
scanner to exchange data on the PROFINET Network (PN). When AS-FPFN02 is installed on AS00SCM-A, Delta AS
Series I/O modules can be used remotely, and only available in RTU mode; NOT supported when installed on the right-
side of the AS PLC CPU). Delta software does NOT support PN network configuration, you can use software from the PN
scanner for editing the PN parameters. After editing, you need to download the updated parameters to the scanner and
then the scanner transfers the settings to AS-FPFN02.
It can work with Siemens PLC CPU: S7-1500, S7-1200, S7-300 and so forth. (TIA Portal V15.1 or later)
10.2.8.2 Features
When AS-FPFN02 is installed on AS300 PLC CPU or AS00SCM-A in RTU mode, it acts as a PROFINET
device and exchanges data with PROFINET (PN) Controller. But AS00SCM-A that can be installed on the
right-side of AS PLC CPU is not supported.
Architecture: you can use software from the PN scanner for editing the PN parameters. After editing, you
need to download the updated parameters to the scanner and then the scanner transfers the settings to AS-
FPFN02.
10
10-20
Ch a pt er 1 0 F unc t i on C ar ds
10.2.8.3 Specifications
Item Specification
Installed on PLC AS300 AS00SCM-A
Communication Protocol PROFINET RT
EtherNet/IP Interface 100 Mbit with 2 x RJ45
Fieldbus PROFINET Devices
Network Cable Length 100 meter
Error Indicator System Fail (SF): Red; Bus Fail (BF): Red
Max. IO Slot Supported 17 9
Devices to Read and Write AS300 series data registers RTU IO modules
10.2.8.4 Configuring the Data Length for I/O Module (Works with AS300)
The module and IO module mentioned in here and later sections indicates a unit of PN controller and AS300 for data
exchange. When AS-FPFN02 communication card is installed on AS300 Series PLC, up to 500/500 bytes of I/O address
area are available. From the following table you can create various kinds of data exchanges – different data length and
functions (e.g. 32 word in- and output) and to set up the corresponding I/O module addresses to the AS300 data register
addresses. Refer to Section 10.2.8.8 for more reference.
The total data size and the number of modules used are relevant. The total usage of I/O address area should also
include IO Production Status (IOPS), IO Consumption Status (IOCS) of each module, also Device Access Point (DAP)
and the bytes for information.
10
10-21
A S S er i es Mo d u le Ma n ua l
From the following table, you can see that users need to count the module information in, otherwise, if exceeding the
total size, PLC editing software would prompt an error message while compiling.
In (byte) Out (byte)
Slot Module IOPS & IOPS &
Data Size Total Data Size Total
IOCS IOCS
0 AS300-CPU (DAP)* 0 4 4 0 4 4
1 Status Register** 8 1 9 0 0 0
2 100 Word In- and Output_1 200 2 202 200 2 202
3 100 Word In- and Output_2 200 2 202 200 2 202
4 16 Word In- and Output_1 32 2 34 32 2 34
5 16 Word In- and Output_2 32 2 34 32 2 34
6 04 Word Output 0 0 0 8 1 9
Total Size 485 485
Note:
* DAP should be counted in the data of input and output module.
** Status Register is counted as the data of input module.
Status
Register
Name Description
(Siemens
S7-1500)
Input Data If the value is TRUE, the input data to be sent to PN Controller is valid.
%I0.0
Available If the value is 0, the input data to be sent to PN Controller is invalid.
You can check the first bit of the bytes %I0.0 (device register) to see if the data exchange is started; this can be
used when the PN device starts to work. You can determine if the input data is valid by checking %I0.0 (device
register); if it says TRUE, the input data is valid and data exchange can begin.
You can check the corresponding registers %I4.0~%I4.7 and %I5.0~%I5.7 to see if the Slot 2~17 is with a working
PN connection.
The following example shows the values in the corresponding registers %I4.0~14.22 are TRUE and that indicates
Slot 2~4 are with PN connections respectively.
10
10-22
Ch a pt er 1 0 F unc t i on C ar ds
10
10-23
A S S er i es Mo d u le Ma n ua l
Example
Use S7-1500 as a Scanner and AS remote module as the 1st Adapter. The address starts from 0. The actual used
address for the module is from the starting address of each module shown on the software. For those unused
addresses are reserved by the system. The unit is byte. For example, 20 to 21 is seen as a word and for the next
word, it will be 22 to 23. The image shown below is the grouped module.
Status Register
Name Description
(Siemens S7-1500)
0: STOP
%IW0 Operation Status
1: RUN
%IW2 For AS00SCM-A; refer to AS00SCM-A for more information
Error Code
%IW4 - %IW18 For Slot 2 to slot 9; refer to its corresponding module chapter
The unit for the address series is byte. The data size for each status register is one word; %IW0 indicates from the
address of 0 byte to read a length of word (%IB0 & %IB1) and the next word is %IW2 (%IB2 & %IB3) and so forth.
Select Slot 1 to set up when to Stop I/O module remotely. Double-click AS00SCM-A -> AS remote module in Device
Setting and click AS Serial Remote Module in HWCONFIG. Refer to Section 9.4.3 from AS Module Manual for more
information.
When the extension module is disconnected, the error code shown on AS00SCM-A is 16#1503. The address of the
10-24
Ch a pt er 1 0 F unc t i on C ar ds
5. Establish a connection
Click the S7-15XX image and go to Online-> Download to device. The IP address of AS-FPFN02 will be set as what
you have set in the previous step. Compile and download the project.
10-25
A S S er i es Mo d u le Ma n ua l
7. Data Exchange
The range of data registers in AS300 PLC CPU that an AS-FPFN02 can read/write is between D0 and D29999. The
data to be outputted is from PN controller to PN device. The data to be inputted is from PN device to PN controller.
8. Configuring the data length for I/O module
Select a right-side module and then configure the data length for it. Up to 250 bytes of data length is available for
input and output respectively. Double click to add in order or drag and place it to the preferable position to add. If
exceeding the limit, the parameters cannot be used. Refer to Section 10.2.8.4 for more details.
9. Setting up the starting address of the data register to exchange data.
Select an added module and enter the starting address in Module Parameters for data exchange. For example set
the value “08 Word In- and Output_1” in Slot 2 and click the name in the Module to set the starting register address
of the corresponding AS300: Properties -> General-> Module parameters-> IO Address.
When entering 100 in Input D Register and 200 in Output D Register and using a 8 Word In/Out module, the PN
Controller reads values starting from D100 to D107 and writes the values in the data register starting from D200 to
D207.
PN Controller transmits 8 Words of data (Q0~Q15) to the data register D200~D207 in AS300 PLC CPU.
AS-FPFN02 transmits 8 Words of data (D100~D107) to the data register I8~I23 in S7-15XX.
The data exchange can only begin when the Bit Input Data Available is TRUE. Refer to Section 10.2.8.5 for more
details.
Apply the same setting procedure when AS-FPFN02 is installed in AS00SCM-A in RTU mode. But you need to pay
attention on the IO modules in the software that should be consistent to the actual placement of the right-side of
AS00SCM-A in RTU.
10
10-26
Ch a pt er 1 0 F unc t i on C ar ds
10.2.9 AS-FOPC02
AS-FOPC02 can be installed on AS300 PLC CPU. Communication can be done independently and that does NOT
occupy the communication port of PLC CPU. It can act as an OPC UA Server. After AS-FOPC02 is installed, you can go
to HWCONFIG from ISPSoft to do the editing in Ethernet Port Basic Setting and Ethernet Port IP Filter.
All the AS-FOPC02 parameters are stored in AS300 PLC CPU. Go to HWCONFIG from ISPSoft to check AS-FOPC02 IP
address in the Function Card 2 section. You can also use COMMGR to see the IP address of this device.
AS00SCM-A does NOT support AS-FOPC02. You can NOT install AS-FOPC02 on AS00SCM-A.
10.2.9.2 Features
When AS-FOPC02 is installed on AS300 Series PLC, it can act as OPC UA Server. The tag settings are the
same as the network communication settings for AS Series; refer to Chapter 9 from AS Series Hardware and
Operation Manual for more information.
Before scanning to add AS-FOPC02 in, remerber to change the setting “Setting delay time to detect I/O
Module” to 3 seconds and then download the settings to PLC CPU.
10
10-27
A S S er i es Mo d u le Ma n ua l
10.2.9.3 Specifications
System Specifications
Item Specification
Device type Slave
Topology Star and linear topologies are supported.
General When installed on AS300 PLC CPU, you can use
IP Settings
HWCONFIG from ISPSoft for editing
Availability AS300 Series PLC
Max. connection number 8
View device information
Web
Functions Account management
AS-FOPC02 firmware update
OPC UA Specifications
Item Specification
General Device type Server (TCP port: 4840)
OPC UA Max. sessions 6 (Clients)
Server Max. tags 1000
Security policy None
Authentication Anonymous
Default endpoint/port opc.tcp://192.168.1.5:4840/
Transport protocol / encoding opc.tcp / binary
Supported profiles UA v1.03 Nano Embedded Device Server Profile
Sampling rate (ms) 100, 200, 300(default), 400, 500, 600…50000
Publish interval (ms) 100, 200, 300, 400, 500(default), 600…50000
Supported data type Int16, Uint16, Int32, Uint32, Float, Boolean
Max. subscription per session 2
Max. monitored items 3000 (including all sessions)
Session timeout (ms) 5000 ~ 30000
Subscription keep alive count 1~1000ms
1) Maximum data size of monitor items for all sessions < 50000bytes
Monitor Items Total Data size of Sampling and
monitor items Publish interval
(Bytes) time (second)
1~500 1~10000 1
10001~20000 2
20001~30000 3
Restrictions
30001~40000 4
40001~50000 5
501~1000 1~10000 2
10001~20000 3
10
20001~30000 4
30001~40000 5
40001~50000 6
10-28
Ch a pt er 1 0 F unc t i on C ar ds
Item Specification
1001~1500 1~10000 3
10001~20000 4
20001~30000 5
30001~40000 6
40001~50000 7
1501~2000 1~10000 4
10001~20000 5
20001~30000 6
30001~40000 7
40001~50000 8
2001~2500 1~10000 5
10001~20000 6
20001~30000 7
30001~40000 8
40001~50000 9
2501~3000 1~10000 6
10001~20000 7
20001~30000 8
30001~40000 9
40001~50000 10
2) Maximum tag array elements = 512 or data size < 400Bytes
3) Maximum tag name length = 40bytes
Attribute
Latched
OFF STOP RUN
Default
AS300
AS200
Series
Series
SR Function
ON RUN STOP
Special data
Refresh time
register
SR913, SR914,
The flag is ON, when the system is refreshed automatically.
SR1430, SR1537
10
10-29
A S S er i es Mo d u le Ma n ua l
(1) Open ISPSoft and create a new project and then double-click Global OPC UA Variables under the Global
Symbols node to open the Global OPC UA Variables setting table.
10
10-30
Ch a pt er 1 0 F unc t i on C ar ds
(2) Right-click on the Global OPC UA Variables setting table to see the context menu. Click Add a Symbol to open the
setting page.
(3) Set up the OPC UA tag. See the following example for reference.
Supported data types are: WORD, DWORD, INT, DINT, REAL, and ARRAY; supported data types in ARRAY are
BOOL, WORD, DWORD, INT, DINT, and REAL.
(4) After the settings are complete, download the settings to PLC. After that devices can read/write the Tag. The way to
connect to the Tags varies in different brands. Refer to the specific device manual for more information on using tags
to connect.
10
10-31
A S S er i es Mo d u le Ma n ua l
10
10-32
Ch a pt er 1 0 F unc t i on C ar ds
Redistribution and use in source and binary forms, with or without modification, are permitted provided that the
following conditions are met:
1. Redistributions of source code must retain the above copyright notice, this list of conditions and the following
disclaimer.
2. Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following
disclaimer in the documentation and/or other materials provided with the distribution.
3. The name of the author may not be used to endorse or promote products derived from this software without
specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE AUTHOR ``AS IS AND ANY EXPRESS OR IMPLIED WARRANTIES,
INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR BE LIABLE FOR ANY DIRECT,
INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT
LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS;
OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN
CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY
OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
10
10-33
A S S er i es Mo d u le Ma n ua l
10.2.10 AS-FFTP01
AS-FFTP01 can only be installed on AS300 PLC CPU. Communication can be done independently and that does NOT
occupy the communication port of PLC CPU. It supports IIoT related protocols. After AS-FFTP01 is installed, you can go
to HWCONFIG from ISPSoft to do the editing.
For the AS-FFTP01 basic parameters (IP address and other parameters) are stored in AS300 PLC CPU. IIoT related
parameters are stored in the communication card (AS-FFTP01). After AS-FFTP01 is installed on AS300 PLC CPU, you
can use the following steps to obtain and make sure the IP address of AS-FFTP01 is correct.
1. Go to HWCONFIG from ISPSoft to upload the AS300 parameters to obtain the IP address of AS-FFTP01.
AS00SCM-A does NOT support AS-FFTP01. You can NOT install AS-FFTP01 on AS00SCM-A.
10
10-34
Ch a pt er 1 0 F unc t i on C ar ds
10.2.10.3 Specifications
System Specifications
Item Specification
Device type IIoT module
Availability AS300 Series PLC
Topology Star and linear (end point) topologies are supported.
When installed on AS300 PLC CPU, you can use HWCONFIG from ISPSoft for
IP Settings
editing
Supported Protocols
Name Description
It can act as an OPC UA Client. AS-FFTP01 and AS-FOPC02 share the same OPC
OPC UA Server UA symbols table in ISPSoft.
File Transfer Protocol (FTP); enter the IP address or the network name and the port
number (default 21) in FTP Client and then enter username and password to log in.
FTP Server
The read/write permission varies according to different users. You can set up the
parameters and the user permission in HWCONFIG.
You can save data in .csv file format, save user-defined contents in a table, and
design triggering conditions. The data log will be saved in the SD card on AS-
Data Log
FFTP01 and which can be retrieved from the SD card or obtained through FTP
Server.
You can create a connection with Amazon Web Services (AWS) through API of PLC
MQTT Client
to publish and subscribe messages.
Web page function is supported. (AS300 PLC CPU has its own independent web
page.) You can monitor the communication card and Nod-RED Dashboard through
Web Server
the webpage. Read/write data from the AS300 registers are also available on the
web page.
It can act as the slave of the Modbus TCP communication; up to 8 connections are
Modbus TCP Server
supported.
10
10-35
A S S er i es Mo d u le Ma n ua l
OPC UA Specifications
Item Specification
Device Type OPC UA Server
TCP Port 4840
Maximum Sessions 6 (Clients)
Maximum Tags 1000
None,
Basic128Rsa15 – Sign,
Security policy Basic128Rsa15 - Sign & Encrypt
Basic256 – Sign
Basic256 - Sign & Encrypt
Anonymous
Authentication
Sign
Default endpoint/port opc.tcp://192.168.1.5:4840/
Transport protocol / encoding opc.tcp / binary
Supported profiles UA v1.03 Nano Embedded Device Server Profile
Sampling rate (ms) 100, 200, 300(default), 400, 500, 600…50000
Publish interval (ms) 100, 200, 300, 400, 500(default), 600…50000
Supported data type Int16, Uint16, Int32, Uint32, Float, Boolean
Max. subscription per session 2
Max. monitored items 3000 (including all sessions)
Session timeout (ms) 5000 ~ 30000
Subscription keep alive count 1~1000ms
Maximum data size of monitor items for all sessions <
50000bytes
Total Data size of Sampling and
Monitor Items monitor items Publish interval
(Bytes) time (second)
1~10000 1
10001~20000 2
1~500 20001~30000 3
30001~40000 4
40001~50000 5
1~10000 2
10001~20000 3
Restrictions 501~1000 20001~30000 4
30001~40000 5
40001~50000 6
1~10000 3
10001~20000 4
1001~1500 20001~30000 5
30001~40000 6
40001~50000 7
1~10000 4
10001~20000 5
10 1501~2000
20001~30000 6
30001~40000 7
10-36
Ch a pt er 1 0 F unc t i on C ar ds
Item Specification
40001~50000 8
1~10000 5
10001~20000 6
2001~2500 20001~30000 7
30001~40000 8
40001~50000 9
1~10000 6
10001~20000 7
2501~3000 20001~30000 8
30001~40000 9
40001~50000 10
Maximum tag array elements = 512 or data size < 400Bytes
Maximum tag name length = 40bytes
Use FTP Client from your computer to connect to AS-FFTP01 and upload/download data on the SD card. Enter the
followings:
IP address of the communication or the network name
Port number (default: 21)
User account and password
FTP Specifications
Item Specifications
Device type FTP Server
Communication port 21
Maximum connection number 1
Maximum user accounts 4
Data storage SD card
10
10-37
A S S er i es Mo d u le Ma n ua l
After the connection is established, you can use the PLC APIs, including, MQTT_Connect, MQTT_Publish and
MQTT_Subscribe to manage MQTT for IoT messaging. Refer to AS Programming Manual for more details.
MQTT Specifications
Item Specifications
Device type MQTT Client
Supported platform Amazon Web Service
Communication port 8883
Maximum connection number 1
Maximum connection number to be
1
recorded
Quality of Service (QoS)* 0, 1
Section to be read D Register
Maximum data length in Publish 1000 words
Maximum data length in Subscribe 1000 words
MQTT_Connect
Application command MQTT_Publish
MQTT_Subscribe
*Note: QoS levels in MQTT:
QoS=0, at most once: No guarantee of delivery.
QoS=1, at least once: It guarantees that a message is delivered at least one time to the receiver. If no confirmation
is received or the packet went missing, the message will be resent until it receives a confirmation.
10
10-38
Ch a pt er 1 0 F unc t i on C ar ds
1. After the setting IP address in HWCONFIG of ISPSoft. Open your browser and enter AS-FFTP01 IP address in the
search bar to connect to AS-FFTP01. After the webpage appears, enter “Admin” in the User section and click Login
without entering any password. You can set up the password after login.
10
10-39
A S S er i es Mo d u le Ma n ua l
2. The menu shows data based on the permission of the current user.
Permission
Nodes
Administrator Read
Device information V V
Account management V X
Save configuration V X
Node-Red editor V X
Node-Red dashboard V X
3. Account Management: You can set 2 kinds of access types, Administrator and Read. After the setting is done, click
Apply and save the settings in Save configuration.
4. Save Configuration: After any setting is done, save the settings in Save Configuration to reflect the changes.
5. Node-RED editor: click to open a new webpage to add nodes and save PLC registers in this browser-based flow
editor.
6. Node-RED dashboard: click to open a new webpage to see the visualized data in a dashboard created through
Node-RED editor.
10
10-40
Ch a pt er 1 0 F unc t i on C ar ds
1. Log Setting
On the Log Setting page, click +Add to create a row in the .csv file and up to 60 rows can be added. One row is
corresponding to one register. The following parameters can be set here on the Log Setting page.
Name: user-defined, the maximum length is 64 characters.
Register Type: Register D and M
Register Address: Register number
Data Type: INT16, UINT16, INT32, UINT32, Float, INT64, UINT64, and Double Float can be used. After the file
is saved in the log, the corresponding data type and acceptable data length will be applied.
Decimal Places: Up to 5 decimal places can be used for the use of floating-point data type.
B. Archive Settings
(1) Path – Log Path Setting
Data log can only be saved on the SD card. You can define the directory and the file name. If
Date or Date + Time is selected, the date or date + time will be added right after your set
filename. Make sure you have set up the real time setting correctly in AS300 PLC CPU before
selecting Date or Date + Time option.
(2) Directory Creating Timing
Do not create a new directory: When selecting this option, the system will NOT create a new
directory but to save the data in the original directory when the saving condition is met.
Daily, Weekly, or Monthly: When selecting the cycle unit, the system will create a new directory
10
and save the data in the new directory when the saving condition is met.
10-41
A S S er i es Mo d u le Ma n ua l
10
10-42
Ch a pt er 1 0 F unc t i on C ar ds
10
10-43
A S S er i es Mo d u le Ma n ua l
10
10-44
Ch a pt er 1 0 F unc t i on C ar ds
66.3
59.3
37 23.9
Unit: mm
10.3.2 AS-F422/AS-F485/AS-F2AD/AS-F2DA
59.3
60.8
37 23.9
Unit: mm
10.3.3 AS-FCOPM
61.3
59.3
37 23.9
10
Unit: mm
10-45
A S S er i es Mo d u le Ma n ua l
10.3.4 AS-FEN02
42 25.2
1
2
88
3
4
5
61.5 6
Unit: mm
1 TX+
2 TX-
3 RX+
4 N/C
5 N/C
6 RX-
7 N/C
10
8 N/C
10-46
Ch a pt er 1 0 F unc t i on C ar ds
10.3.5 AS-FPFN02
42 25.2
1
2
88
3
4
61.5 6
Unit: mm
10
10-47
A S S er i es Mo d u le Ma n ua l
10.3.6 AS-FOPC02
42 25.2
1
2
88
3
4
5
61.5 6
Unit: mm
1 TX+
2 TX-
3 RX+
4 N/C
5 N/C
6 RX-
7 N/C
10 8 N/C
10-48
Ch a pt er 1 0 F unc t i on C ar ds
10.3.7 AS-FFTP01
42 25.2
A S- FF TP0 1
MS
NS 1
88
4 3
61.5 6
Unit: mm
1 TX+
2 TX-
3 RX+
4 N/C
5 N/C
6 RX-
7 N/C
8 N/C
10
10-49
A S S er i es Mo d u le Ma n ua l
10.4 Wiring
10.4.1 AS-F2AD
2-wi re : curre nt i np ut
3-wire: c urre nt i np ut
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–2) must be short-circuited.
*3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor having a
capacitance in the range of 0.1–0.47 μF and a working voltage of 25 V.
*5. The wording “CHX” indicates that you can use the five wiring methods listed above for every input channel.
10
10-50
Ch a pt er 1 0 F unc t i on C ar ds
10.4.2 AS-F2DA
C urre nt o utp ut *4
CHX
4mA ~20mA
V O2 CH2
IO2
COM
AG
AC motor driv e,
recorder, Sh iel de d ca ble *1 *3
propor tioning v al ve
FE
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor having a
capacitance in the range of 0.1–0.47 μF and a working voltage of 25 V.
*4. The wording “CHX” indicates that you can use the two wiring methods listed above for every input channel.
10
10-51
A S S er i es Mo d u le Ma n ua l
Star Topology
Star Topology
10
10-52
Ch a pt er 1 0 F unc t i on C ar ds
10
10-53
A S S er i es Mo d u le Ma n ua l
(3) Double-click the function card to open the Device Setting page.
Card1 Detect mode: select Auto Detect or choose the function card model.
(a) When the function card is an AS-F232, AS-F422, or AS-F485, configure the communication settings in the red
box.
(b) Function card AS-FCOM can only be installed in function card slot 2.
10
10-54
Ch a pt er 1 0 F unc t i on C ar ds
(d) When the function card is an AS-F2AD or AS-F2DA, configure the communication settings in the red box.
(e) When the function card is an AS-FEN02, configure the communication settings in the red box.
10
10-55
A S S er i es Mo d u le Ma n ua l
(4) Click Download on the toolbar to download the parameters. Note that you cannot download the parameters while
the CPU module is running.
10
10-56
11
1
Chapter 11 DeviceNet Master Scanner Module
AS01DNET-A
Table of contents
11.1 Introduction o AS01DNET-A ............................................................ 11-3
11.1.1 Feature ..................................................................................... 11-3
11.1.2 Specifications ............................................................................. 11-3
11 - 1
AS Ser ies M od ul e Man ua l
11.6 How to Call DeviceNet Builder through ISPSoft (AS-Series PLC) 11-97
11 - 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
The instruction is simply a guideline for operation of the product and the details on the DeviceNet protocol is 11
excluded here. Please refer to relevant articles and literatures for more details on the DeviceNet protocol.
AS01DNET-A, a DeviceNet network module can work in two modes: master /slave and RTU. The RTU-
Master/Slave switch is used for selecting one of the two modes. When AS01DNET-A works in master/slave mode,
it makes up the DeviceNet master or slave with AS-series PLC together. When working in RTU mode, AS01DNET-
A needs an external 24VDC power supply and can connect AS-series I/O modules onits right side.
Refer to Section 11.4 and 11.5 for details about master/slave mode and RTU mode.
11.1.1 Feature
Supports the Group 2 server slave and Group 2 only servers.
Supports the explicit connection in the predefined master/slave connection and I/O polling connection.
Able to work as a DeviceNet master or slave as well as a remote RTU connecting AS series I/O modules.
The network configuration software DeviceNet Builder offers the graphical configuration interface.
Supports the EDS file configuration in the DeviceNet network configruation tool.
11.1.2 Specifications
DeviceNet Connector
Item Specifications
DeviceNet Communication
Item Specifications
Electrical Specification
Item Specifications
11 - 3
AS Ser ies M od ul e Man ua l
Environment
Item Specifications
International standard IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 &
Vibration/Shock resistance
IEC 68-2-27 (TEST Ea)
11 - 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11.2.2 Components
01DNET 1
MS
7 2 9
11
NS
1
x10
3
IN 0
IN 1 Node Address
0
x10
8 5
6
RTU Master/ Slave
10
Mode toggle
① Model name ⑥
(RTU-Master/Slave)
⑤ DeviceNet communication port ⑩ 24V DC power input port for RTU mode
Note:
The power input port of the network module is required to connect an external 24VDC power supply only when the toggle
(RTU- Master/Slave) is switched to RTU mode. Otherwise, the port does not need an external 24VDC power supply
connected when the toggle (RTU- Master/Slave) is switched to Master/Slave mode.
11 - 5
AS Ser ies M od ul e Man ua l
11
Switch setting Description 2 3
4
0 1
x10
1
5 6
9
7 8
0 … 63 Valid DeviceNet node address Node Address
2 3
4
0 1
x10
0
5 6
9
64…99 Invalid DeviceNet node address
7 8
Example: If users need to set the node address of AS01DNET-A to 26, simply switch the corresponding switch of
x101 to 2 and the corresponding switch of x100 to 6.
Note:
While AS01DNET-A is working, changing the setting of the node address is invalid.
Rotate the switch carefully with a slotted screwdriver to prevent damage to the switch.
After the setup of the function switch is completed during power off, repower AS01DNET-A.
While AS01DNET-A is working, changing the setting of the node address is invalid.
Adjust the DIP switch carefully with a slotted screwdriver to prevent any damage to the switch.
11 - 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11 - 7
AS Ser ies M od ul e Man ua l
11
1. AS01DNET-A, a DeviceNet module running on
the right of AS PLC can work as a DeviceNet
master or slave.
AS01DNET-A 2. AS01DNET-A can also be used as AS series
remote IO module for connecting AS series
DI/DO modules and AI/AO modules to DeviceNet
network.
11 - 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
IFD9502
electromechanical equipment such as AC motor 11
drive, PLC, temperature controller, servo drive, HMI,
user-defined device.
11 - 9
AS Ser ies M od ul e Man ua l
11
Used for the connection of DeviceNet network and
DVPDT02-H2
DVP-EH2 series PLC.
11 - 1 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
A DeviceNet network requires two terminal resistors of 121 Ω connected at both ends of the trunk cable respectively.
The thick cable represents the trunk cable, the thin cable represents the branch cable and the yellow boxes at the two
11
ends are terminal resistors in the following figure.
The terminal resistor is used for eliminating the signal reflection in the communication cable.
All signal transmission cables have the characteristic impedance. The characteristic impedance of Delta DeviceNet
communication cable is about 121 Ω.
When being transmitted to the end of the communication cable, because the impedance of the end is different from the
characteristic impedance, the signal will be reflected, which will interfere with the new signal and the signal wave form
distortion will happen.
The phenomenon of the signal wave form distortion is not obvious in the short-distance transmission. But the wave form
distortion will become severer in the increasingly long communication cable. Therefore, the two ends of the trunk cable
must be installed with the terminal resistors respectively.
The DeviceNet communication cable consists of five wires such as red wire, blue wire, white wire, black wire and shielded
wire as below.
The terminal resistors must be installed to the two ends of the trunk cable only. Since the blue wire and white wire are
for signal transmission, both of the terminal resistors must be installed between blue wire and white wire at the two ends
of the main cable.
11 - 11
AS Ser ies M od ul e Man ua l
11 Delta DeviceNet communication cable consists of five wires, among which the power cable and signal cable occupy two
wires respectively and the one on the left is the shielded wire as the above figure shows.
The supply power for the bus is optional and could be a single supply power or multiple supply powers according to the
actual demand.
11 - 1 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
The network configuration software DeviceNet Builder provides graphic configuration interface.
Sending explicit messages to read and write the data in slave through the explicit message instruction
DNETRW.
Automatically performing data exchange with the PLC module; users just need write a program for D register
in the PLC without using FROM/TO instructions.
Offering 190 bytes of output data area and 190 bytes of input data area for exchanging data with the master.
Polling connection;
Offering 200 bytes of input data area and 200 bytes of output data area for exchanging data with master;
Automatically exchanging data with the PLC. The user just need to write a program for D register in the PLC
without using FROM/TO instruction.
11 - 1 3
AS Ser ies M od ul e Man ua l
11.4.2 Installation
11.4.2.1. Connecting AS01DNET-A Module to AS series PLC
For the details on how AS01DNET-A (in Master/slave mode) is connected to AS series PLC, refer to Section 1.3.1
Installing a Module in AS Series Module Manual.
Make sure that the color marks for the PINs of the DeviceNet connection port match the colors of the connection
cables and the cable should be connected to the right PIN.
11 - 1 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Up to four AS01DENT modules can be connected to the right side of AS PLC at most. After AS01DNET modules and
PLC are connected, PLC will assign data mapping areas to each module. 11
POWER
01DNET 01DNET 01DNET 01DNET
RUN MS MS MS MS
ERROR
BAT. LOW NS NS NS NS
COM1
COM2
AS324MT 40
IN 0
x10
IN 0
x10
IN 0
x10
IN 0
x10
0 8
1 9
Ethernet
2 10
3 11
OUT
4 2 1
5
6
7
RTU Master/ Slave RTU Master/ Slave RTU Master/ Slave RTU Master/ Slave
AS01DNET modules are connected to the right of the PLC. The position of the first module on the right of AS PLC is 1, the
second module is 2, the third module is 3 and the fourth module is 4. The position is only defined for network modules such
as AS01DNET and AS00SCM, instead of digital modules, analog modules, temperature modules, and weight-
measurement modules. The positions of AS01DNET modules on the right of the PLC are shown in the following table
where there are two arrangement ways of module connections.
Example 1 Example 2
AS PLC AS PLC
1 AS01DNET 1 AS01DNET
AS04AD AS04AD
2 AS01DNET AS00SCM
3 AS01DNET
11 - 1 5
AS Ser ies M od ul e Man ua l
When AS01DNET is at different positions of the right of the PLC, the input and output mapping areas for the AS01DNET
module in AS PLC are listed in the following table.
Position of
AS01DNET on
11 the right of the
Output mapping area Input mapping area
PLC
1 D26100 – D26199 D26000 – D26099
2 D26500 – D26599 D26400 – D26499
3 D26900 – D26999 D26800 – D26899
4 D27300 – D27399 D27200 – D27299
When AS01DNET works in master mode, the input and output mapping areas for AS01DNET at different
positions of the right of AS PLC are listed in the following table.
Position of Output mapping area (for sending data to Input mapping area (for receiving data from
AS01DNET the slave) the slave)
on the right Data Data
D register Mapping area D register Mapping area
of the PLC size size
Scan-list node
Bit-strobe 4 4
D26100~D26103 D26000~D26003 status indication
command area words words
area
Module status
1 D26104 Reserved 1word D26004 1 word
indication area
DeviceNet
95 DeviceNet input 95
D26105~D26199 output data D26005~D26099
words data area words
area
Scan-list node
Bit-strobe 4 4
D26500~D26503 D26400~D26403 status indication
command area words words
area
Module status
2 D26504 Reserved 1word D26404 1 word
indication area
DeviceNet
95 DeviceNet input 95
D26505~D26599 output data D26405~D26499
words data area words
area
Scan-list node
Bit-strobe 4 4
D26900~D26903 D26800~D26803 status indication
command area words words
area
Module status
3 D26904 Reserved 1word D26804 1 word
indication area
DeviceNet
95 DeviceNet input 95
D26905~D26999 output data D26805~D26899
words data area words
area
Scan-list node
Bit-strobe 4 4
D27300~D27303 D27200~D27203 status indication
command area words words
area
4
Module status
D27304 Reserved 1word D27204 1 word
indication area
D27305~D27399 DeviceNet 95 D27205~D27299 DeviceNet input 95
11 - 1 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Position of Output mapping area (for sending data to Input mapping area (for receiving data from
AS01DNET the slave) the slave)
on the right Data Data
D register Mapping area D register Mapping area
of the PLC size size
output data words data area words 11
area
Note: See Section 11.4.5 for further explanation of scan-list node status indication areas and module status indication
areas. The input and output mentioned here are defined in the perspective of the master of the entire fieldbus system.
When AS01DNET works in slave mode, the input and output mapping areas for AS01DNET at different positions
of the right of AS PLC are listed in the following table.
Position of Area for sending data to the master Area for receiving data from the master
AS01DNET on
the right of the
D register Data length D register Data length
PLC
1 D26100~D26199 100 words D26000~D26099 100 words
When the values of bit0 and bit1 of D26100 are both 0, node 0 and node 1 are selected and they need return data to the
master.
D6283 D6282
b31 b30 b18 b17 b16 b15 b14 b2 b1 b0
Node 0
Node 1
Node 2
Node 14
In the bit-strobe method, the master does not send control data to the slave node. However, the slave node need return
I/O data to the master if the corresponding bit is set to 0. If the corresponding bit is set to 1, the slave node does not need
to return I/O data to the master.
11 - 1 7
AS Ser ies M od ul e Man ua l
Register in Description
the PLC b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Module status
D26004 Error code in the module
(0:Normal,1:Initializing,2:error)
11.4.6 Setting the Time for Data Exchange between Master and
Slaves
When AS01DNET works in master mode, the period of time for a data exchange between master and all slaves need be
set. Master and all salves will periodically perform the data exchange based on the set time. See the following explanation
for details. Click menu Network >> Scanner Setting on the DeviceNet Builder software page. The Scanner Setting
window appears as below.
11 - 1 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
The explanation of Scan Interval Time and Expected Packet Rate is shown in the following table.
The period of time needed for a data exchange between master and all slaves.
Scan Interval Time
Master and all salves will periodically exchange data based on the set interval time.
Sets the timeout time for connection of master and slaves. The calculation method:
4 X EPR with the unit: ms. The default EPR is 75. The EPR for the connection of 11
Expected Packet Rate master and slaves is 4 X 75 = 300ms. The value indicates that the IO data exchange
(EPR) should be achieved once at least within 300 ms. Otherwise, the connection will fail
due to communication timeout and then the connection will have to be re-made so
that the IO data exchange can proceed.
Since most DeviceNet slaves only support polled IO data exchange, the EPR value is related to the value of Scan
Interval Time. Make sure that the actual setting must meet the following condition.
We suggest users refer to the following condition while setting the value of Scan Interval Time.
Click the Calculate Time button. The Calculate Scan Interval Time dialog box comes out. Clicking the Calculate button,
the values of Total input size, Total output size and Scan Interval Time are calculated. The value of Scan Interval Time
is a value in theory. We suggest users should set the scan interval time to a value slightly greater than the actually
calculated time. The scan interval time calculated here will not be filled in the Scan Interval Time box automatically and
so users need enter the value manually.
Control requirement: AS PLC remotely monitors D26105~D26108 and D26005~D26008 in AS module through
DeviceNet network to achieve the data exchange as AS01DNET-A works as master and slave respectively.
11 - 1 9
AS Ser ies M od ul e Man ua l
This section describes how to construct a DeviceNet network configuration through an application example. Before
constructing a DeviceNet network, users should understand the control requirement of the network; plan the data for
11 exchange in advance such as maximum communication distance, slaves, total data length for exchange as well as the
requreiment for response time during data exchange.
The information above will determine whether the constructed network is reasonable and able to meet the demand. Even
it will directly affect the future maintenance and convenience of network capacity expansion and upgrade.
Connection Figure
Note: Both of the ends of the DeviceNet Bus cable must connect one 121Ω terminal resistor respectively. The terminal
resistor is connected between CAN_H and CAN_L.
Modules Setting
Prepare two AS PLCs and two AS01DNET-A modules for constructing one DeviceNet network. The setups for two
AS01DNET-A modules are shown in the follwing table.
11 - 2 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
1. Set the driver for the connection of AS PLC and PC. Clicking Add, the Driver Properties dialog box appears.
Select the connection type for AS PLC and PC in the Type field. In this example, select Ethernet as the 11
connection type. Click Search to search the PLC and then click OK after searching is finished.
11 - 2 1
AS Ser ies M od ul e Man ua l
11
11 - 2 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
3. Selecting Setup>> Communication Setting, the following dialog box appears. Select the driver for
connection of AS PLC and PC as below. Click OK to finish the selection of Driver.
11
11 - 2 3
AS Ser ies M od ul e Man ua l
6. After scanning is finished, all node icons and device names which have been scanned in the network will
appear on the following interface. The node address of AS01DNET-A is 00 in this example.
11
7. Double click the icon of AS01DNET Slave. Then the Node Configuration… dialogue box appears. Input Size
and Output Size are both set to 8 bytes. Click OK to finish the setting.
11 - 2 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
8. Right click the icon of AS01DNET Slave and click Parameter Edit… on the drop-down menu. The Parameters
Edit… dialog box appears and Polled Input Length and Polled Output Length are both set to 8 bytes as
shown in the following red box. Then click Write button. Click OK after writing is finished. Afterwards, repower
AS01DNETSlave.
11
11 - 2 5
AS Ser ies M od ul e Man ua l
Configuring AS01DNET-A
1. Double click the icon of AS01DNET Scanner (node 0). The Scanner Module Configuration… dialog box
appears. The left list shows the current available node AS01DNET Slave and the right Scan List is empty as
below.
11
11 - 2 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
2. Move the DeviceNet slaves from the left list to Scan List of the right side. Follows the steps: Select one
DeviceNet slave node and then click > . Then the DeviceNet slave nodes are moved to the Scan List one
by one.
11
3. Click OK to finish the configuration above. Then download the configuration data to AS01DNET-A. During
the download, the Warning dialog box will pop out if AS PLC is in RUN mode. Click OK to continue the
download.
11 - 2 7
AS Ser ies M od ul e Man ua l
Configure the DeviceNet network by following the steps above. The IO data mappings between
AS01DNET-A and the slave are shown in the following tables.
AS01DNET-A → Slave
Slave → AS01DNET-A
This section describes how to write a ladder program to achieve the control requirement of the DeviceNet network.
PLC Programs
Program Explanation:
The contents in D26000~D26003 are the data received from the master and the contents in D26100~D26103
are the data transmitted to the master. SM400 is a normally open contact. The program above can make the
contents in D26000~D26003 move to D26100~D26103.
11 - 2 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
Program Explanation:
1. When M0 changes to ON, the value 16#5555 is written to D26105~D26108 in AS PLC. The data are
transmitted to the slave cyclically via DeviceNet Bus.
2. The contents in D26005~D26008 are the data which the master receives from the slave via DeviceNet
Bus. When M1 changes to ON, the data in D26005~D26008 are moved to D0, D1, D2 and D3.
1. AS PLC transmits the explicit request message to AS01DNET-A master according to the user program.
2. AS01DNET-A transmits the explicit request message to the slave according to the user program.
3. The slave sends back the response message to AS01DNET-A master after handling data.
4. AS PLC gets back the response message from AS01DNET-A master. Then the explicit message transmission of this
time is finished.
11 - 2 9
AS Ser ies M od ul e Man ua l
DNETRW instruction:
STRING
LWORD
WORD
LREAL
BOOL
REAL
UINT
DINT
LINT
TMR
CNT
INT
Data type
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
D1
D2
D3
D4
D5
11 - 3 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Symbol:
DNETRW
S1 D1
S2 D2
S3 D3 11
S4 D4
S5 D5
S6
S7
S8
S9
S 10
S3 Service Code
S4 Class ID
S5 Instance ID
S6 Attribute ID
S7 Written-data size
D1 Completion flag
D2 Error flag
D3 Error code
D4 Read-data size
Explanation:
S1 is the sequence number of the module on the right of the PLC. The number of the first module is 1; the
second module is 2 and so on. Any type of module need be numbered within the range of 1~32. If the number
is out of the range, the instruction will take the minimum (1) or maximum (32) for operation.
S2 is a DeviceNet node address within the range of 0~63. Users can specify the node address of a slave
which the master is to read and write. It also can be the node address of the master, which means to read and
write the data in the master.
11 - 3 1
AS Ser ies M od ul e Man ua l
S8 is the start device where written data are stored. The data are arranged in the order from low byte to high
byte.
S9 is the communication timeout time within the range: 1~100 and with the unit: 0.1 second.
S10 is the times of re-transmission within the range: 0~3. When communication timeout occurs, the
communication will be resent
Error Code
Explanation
Code 1 (High Byte) Code 2 (Low Byte)
XX FF Not conform to the DeviceNet standard
20 01 The target slave does not exist.
20 02 Unable to make the connection with the slave
20 03 Sending explicit message failed.
16 00 Explicit message response timeout.
D4 is the read-data size with the unit: Byte.
D5 is the start device where read data are stored. The data are arranged in the order from low byte to high
byte.
Application Example 1
Control requirement: when M0=ON, read the data of class1>>instance1>>attribute1 of the DeviceNet function
card CMC-DN01.
Connection Figure
POWER
01DNET
RUN MS
ERROR
BAT. LOW NS
COM1
COM2
AS324MT 40
IN 0
x10
IN 1 Node Address
0 8 x10
1 9
2 10
3 11
IN
4
5
6
DeviceNet
7
0 8
1 9
Ethernet
2 10
3 11
OUT
4 2 1
5
6
7
RTU Master/ Slave
11 - 3 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
PLC Program
S1: The number of the module sending DeviceNet communication. The first one of the right side is 01.
S7:Write data size. When DNETRW instruction is used to read data, the value in S7 can be set to any
data.
S8:The start device where the written data are stored. When DNETRW instruction is used to read data,
the value in S8 can be set to any data.
D1:Completion flag
11 - 3 3
AS Ser ies M od ul e Man ua l
D2:Error flag
D3:Error code
Program Explanation
When M0 changes to ON, execute the explicit message instruction DNETRW to read Class 1 >> Instance
1 >> Attribute 1 of the target equipment with node ID: 01. If the explicit message communication succeeds,
the completion flag M1 changes to ON.
When M0 changes to ON, AS01DNET-A sends out the request message only once. If the request
message is to be resent, the instruction DNETRW need be re-triggered.
If the data reading succeeds, the content of Class 1>> Instance1 >> Attribute 1 of CMC-DN01 will be
stored in D5. In this example, the content in D5 should be 031FHex.
Application Example 2
Control requirement: When M1 changes to ON, set the content of Class ID: 0x05>> Instance 1>>Attribute ID:
09 of CMC-DN01 to 000AHex.
Connection figure
POWER
01DNET
RUN MS
ERROR
BAT. LOW NS
COM1
COM2
AS324MT 40
IN 0
x10
IN 1 Node Address
0 8 x10
1 9
2 10
3 11
IN
4
5
6
DeviceNet
7
0 8
1 9
Ethernet
2 10
3 11
OUT
4 2 1
5
6
7
RTU Master/ Slave
11 - 3 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
PLC Program
11
S1:The number of the module sending DeviceNet communication. The first one of the right side is 01.
S7:Write data size with the unit: Byte. The written-data size is 2 in this example.
D1:Completion flag.
D2:Error flag.
D3:Error code.
D4:Read data size. When DNETRW instruction is used to write data, the value in D4 can be set to any
data.
D5:The start device where read data are stored. When DNETRW instruction is used to write data, the
value in D5 can be set to any data.
11 - 3 5
AS Ser ies M od ul e Man ua l
Program Explanation
When M0 changes to ON, AS01DNET-A sends the request message and 000AHex is written to Class
ID: 05>> Instance 1 >> Attribute ID: 09 of the target equipment with node ID: 01. If explicit message
communication succeeds, the completion flag M1 changes to ON.
11
When M0 changes to ON, AS01DNET-A sends out the request message only once. If the request
message is to be resent, the instruction DNETRW need be re-triggered.
01DNET
MS
NS
11.4.9.1. NS LED
11 - 3 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11.4.9.2. MS LED
LED status
Indication Correction
NS LED MS LED
OFF OFF No power Check if the power supply for AS01DNET-A is normal.
Make sure that the baud rate of at least one node in the
Green light Duplicate ID check has
OFF network is the same as that of the module and their
ON not been completed.
communication is normal.
Green light Duplicate ID check failed 1. Ensure that the node ID of AS01DNET is unique.
Red light ON
ON or Bus-OFF. 2. Repower the module.
Red light
blinking
1. Check if the network cable connection is proper.
Red light ON (ON:0.5s and No network power
2. Check if the network power supply is normal.
OFF: 0.5s
alternately)
Red light ON Red light ON Hardware error Return the module to the factory for repair.
11 - 3 7
AS Ser ies M od ul e Man ua l
11 - 3 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Under standard mode, AS01DNET-A supports three baud rates: 125K, 250K and 500K. Under non-standard mode,
AS01DNET-A supports eight baud rates: 10K, 20K, 50K, 125K, 250K, 500K, 800K and1M.
Refer to Section 2.4 Communication Setting in the ISPSoft User Manual for more details.
11 - 3 9
AS Ser ies M od ul e Man ua l
4. Selecting Setup>> Communication Setting, the following dialog box appears. Select the driver for connection of
AS PLC and PC as below. Click OK to finish the selection of Driver.
11
6. Click Project List>>Properties. Then the Properties dialog box appears. Select Slave mode and then click OK.
11 - 4 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
7. Click Network >> Download. If the PLC is in STOP state, the following dialog box will exist during the download.
The dialog box will disappear automatically after the download is finished. AS01DNET-A will be in slave mode after
repower ON.
8. If the PLC is in RUN state, the Warning dialog boxes will pop out before and after the download. Users can click
OK or Cancel according to actual situation.
11 - 4 1
AS Ser ies M od ul e Man ua l
Refer to Section 2.4 Communication Setting in the ISPSoft User Manual for more details.
11
2. Call the DeviceNet Builder software through the ISPSoft software.
4. Selecting Setup>> Communication Setting, the following dialog box appears. Select the driver for connection of
AS PLC and PC as below. Click OK to finish the selection of Driver.
11 - 4 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
6. Click Project List>>Properties as below. Then the Properties dialog box appears. Select Master mode and
then click OK.
11 - 4 3
AS Ser ies M od ul e Man ua l
11
7. Click Network >> Download. If the PLC is in STOP state, the following dialog box will exist during the download.
The dialog box will disappear automatically after the download is finished. AS01DNET-A will be in master mode
after repower ON.
8. If the PLC is in RUN state, the Warning dialog boxes will pop out before and after the download. Users can click
OK or Cancel according to actual situation.
11 - 4 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
2. Selecting Setup>> Communication Setting, the following dialog box appears. Select the driver for connection of
AS PLC and PC as below. Click OK to finish the selection of Driver.
11 - 4 5
AS Ser ies M od ul e Man ua l
11
4. Clicking Network>> Scan DeviceNet Network, the DeviceNet Builder software starts to scan the whole network.
5. After scanning is finished, all node icons and device names which have been scanned in the network will appear
on the following interface. The node address of AS01DNET-A is 01 in this example.
11 - 4 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
6. Right-click AS01DNET(Slave), select Parameter Edit… on the drop-down menu to enter the Parameter Edit
page.
11
7. Set Extend Baudrate Enable to Enable and then select the desired baud rate. Click Write button after setting is
finished.
8. After the download is completed, switch DR0 and DR1 of AS01DNET to ON. Finally, repower AS01DNET-A.
11 - 4 7
AS Ser ies M od ul e Man ua l
11
2. Selecting Setup>> Communication Setting, the following dialog box appears. Select the driver for connection of
AS PLC and PC as below. Click OK to finish the selection of Driver.
11 - 4 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
4. Clicking Network>> Scan DeviceNet Network, the DeviceNet Builder software starts to scan the whole network.
5. After scanning is finished, all node icons and device names which have been scanned in the network will appear
on the following interface. The node address of AS01DNET-A is 00 in this example.
11 - 4 9
AS Ser ies M od ul e Man ua l
6. Click Network >> Scanner Setting. The Scanner Setting dialog box appears. Select Enable under Extension
Baudrate and the desired baud rate as below. Click OK after the setting is finished.
11
7. Click Network >> Download to download the extension baud rate setting to the master. After the download is
completed, switch DR0 and DR1 of AS01DNET-A to ON. Finally, repower AS01DNET-A.
11 - 5 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
The network configuration software DeviceNet Builder provides graphic configuration interface, and supports
auto scan and recognition of I/O modules, free mapping of special module parameters as I/O exchange data
as well as the setting of exception handling and diagnosis of module error states.
Users can choose to retain the data in registers or not when the network is disconnected according to actual
need.
AS01DNET (in RTU mode) can connect max. 8 AS-series extension modules including digital modules, analog
modules, temperature modules and etc. The mapping length of digital modules is determined by number of
digital points. The max. length of mapping parameters for input of other module is 20 words and the max.
length of mapping parameters for output of other module is 20 words.
Max lengths for output data and input data of AS01DNET (in RTU mode) are both 100 bytes.
AS01DNET (in RTU mode) needs the external 24VDC power supply.
11 - 5 1
AS Ser ies M od ul e Man ua l
AS08AM10N-A None 1
AS16AM10N-A None 1
AS32AM10N-A None 2
AS64AM10N-A None 4
AS08AN01T-A 1 None
AS08AN01R-A 1 None
AS08AN01P-A 1 None
AS16AN01T-A 1 None
AS16AN01R-A 1 None
AS16AN01P-A 1 None
AS32AN02T-A 2 None
AS64AN02T-A 4 None
AS16AP11T-A 1 1
AS16AP11R-A 1 1
AS16AP11P-A 1 1
The model and specification of AS-series special modules connectable to AS01DNET (in RTU mode):
AS04AD-A 6 None
AS04DA-A 2 4
AS06XA-A 10 4
AS02LC-A 7 1
AS04RTD-A 10 None
AS06RTD-A 14 None
AS04TC-A 10 None
AS08TC-A 18 None
AS08AD-B 18 None
AS08AD-C 18 None
Note:
The length of mapping data of the I/O modules connected to AS01DNET (in RTU mode) is fixed. The default mapping
parameters of special modules must be chosen.
Besides default mapping parameter configuration, you can also choose other parameters for I/O mapping according to
need when special modules are connected to AS01DNET (RTU). The max. input length and max. output length of
default parameters and user-added mapping parameters of each special module are both 20 words.
11 - 5 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11.5.3 Installation
11.5.3.1. Installing AS01DNET (in RTU Mode)
11.5.3.1.1. Connecting AS01DNET-A (in RTU Mode) and Extension Module on DIN Rail
Please push the clips of AS01DNET-A (RTU) in the directions indicated by arrow ① until hearing a click. That 11
means the DIN clips are interlocked each other. Then insert the module hooks at the bottom into the DIN rail
mounting slot until hearing a click. That means AS01DNET-A (RTU) is connected to the DIN rail.
To install the second module AS16AP11T, push the clips of AS16AP11T in the direction indicated by arrow ①.
Then aim the left-side slot of AS16AP11T at the right-side slot of AS01DNET-A (RTU) and push AS16AP11T in
the direction as illustrated by arrow ② until hearing a click. That means the module is on the DIN rail and is
connected to AS01DNET-A (RTU). In the same way, install more IO modules on the right side of AS01DNET-A
(RTU) and DIN rail one by one.
1 DI N ra il clip
2
01DNET
MS
NS
x101
IN 0
IN 1 Node Address
0
x10
RTU Mas te r/ Sl a ve
Tighten the screws on the top of the module at the end of installing.
11 - 5 3
AS Ser ies M od ul e Man ua l
The color marks on the communication connector match the colors of the connection cables. During the wiring,
please check whether the colors of the connection cable and the color mark are same.
Peel off the metallic shielded net and foil, and you
will see 2 power cables (red and black), 2 signal
cables (blue and white) and 1 shielded cable.
11 - 5 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11.5.4.1. Terms
The first WORD for output data that the master assigns to AS01DNET is
the control word of AS01DNET for setting the work mode of AS01DNET.
1 Control word WORD When the content in the control word is set to 2, AS01DNET is in STOP
mode. When the content in the control word is set to 1, AS01DNET is in
RUN mode.
The first WORD for input data that the master assigns to AS01DNET is
the status word of AS01DNET for displaying the operation state of
2 Status word WORD
AS01DNET.
Refer to section 11.5.4.3.4 for more about status word.
Range of input data Determined by start input address and input mapping parameter length
5 WORD
in modules of each module.
Range of output data Determined by start output address and output mapping parameter
6 WORD
in modules length of each module.
The sum of the size of status word of AS01DNET and the size of input
data of the modules connected to it. The status word occupies one word.
Digital input module takes 16 bits as one word. The input data length of
7 Input data size WORD
analog I/O modules and temperature modules are determined by the
default mapping parameter length and user-added parameter length, no
more than 20 words.
The sum of the size of control word of AS01DNET and the size of output
8 Output data size WORD data of the modules connected to it. The control word occupies one word.
Digital output module takes 16 bits as one word. The output data length
11 - 5 5
AS Ser ies M od ul e Man ua l
Before the new version of DeviceNet Builder software is used for making a connection with PLC, make sure that the
communication manager COMMGR has been installed.
Before making a normal connection between DeviceNet Builder and PLC, you have to do relevant setup for COMMGR
software.
Refer to Section 2.4 Communication Setting in the ISPSoft User Manual for more details.
11 - 5 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
5. The master module AS01DNET-A which has been scanned is shown in the left-side Project List.
11 - 5 7
AS Ser ies M od ul e Man ua l
11
7. After online is implemented, click the Scan DeviceNet Network button to start scanning the nodes in the network.
11 - 5 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
1. After scanning is finished, double click the AS01DNET (RTU) node in the network. Then the Node Configuration…
window comes out. The polled transmission is supported with default input data size of 2 bytes and output data size of
2 bytes which are mapping address lengths of control word and status word of AS01DNET (RTU) respectively.
11
Input Size and Output Size under Polled Setting mean the lengths of AS01DNET (RTU) parameters which are
mapped in the master.
11 - 5 9
AS Ser ies M od ul e Man ua l
2. Click the I/O Configure… button in the Node Configuration… window. Then the main configuration page appears
as below.
11
Item Description
All I/O modules currently connected to the right side of AS01DNET (RTU) are scanned. The
Scan existing modules in the software will be compared with the actually connected I/O module. The
mismatched one will be displayed in an abnormal icon.
Upload and show the configuration data including I/O list, I/O configuration, parameter mapping
Upload
and basic control information in AS01DNET (RTU) in the software.
Download current AS01DNET (RTU) configuration including I/O list, I/O configuration, parameter
Download mapping and basic control information to AS01DNET (RTU), which is retained when the power is
turned off.
Reset Make the connected AS01DNET (RTU) restart.
Clear the configuration data stored in the latched area and automatically reset the configuration.
Clear config
Then the indicator displays F1.
11 - 6 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Item Description
Watch and set in real time the configured exchange data in current system; change output data,
Start
watch input data and use control word to control the operation state of AS01DNET (RTU) in real
Monitor
time.
Name Name of each module 11
Firmware version of each module. Choosing corresponding version of firmware, download the
Firmware
module parameter information which matches the firmware version.
Description The description of basic information of each module.
The mapping range of input data of each module, determined by start address offset of mapping
Input
input data and the size.
The mapping range of output data of each module, determined by start address offset of mapping
Output
output data and the size.
Comment Add a comment for each I/O modules
The current configuration data will not be saved until you click the OK button to finish the
OK
configuration.
Clicking the Cancel button to exit AS01DNET (RTU) configuration page, current configuration data
Cancel
will not be saved.
3. Clicking the Scan button on the page, the main AS01DNET (RTU) configuration page changes as below.
11 - 6 1
AS Ser ies M od ul e Man ua l
After the I/O modules connected to AS01DNET (RTU) are scanned, abnormal icons may appear.
11 The I/O module configured in the software does not match the current I/O module
actually connected, e.g. the software configuration is AS32AM, but the actually
connected module is AS16AP. So the abnormal icon such as left-side icon will appear
after the scan. You can change it into current configuration icon with double clicks on it.
The I/O module in the software configuration does not exist in the actual connection,
e.g. the software configuration is AS32AM, but it has not been connected actually. So
the abnormal icon such as left-side icon will appear after the scan. You can change it
into current configuration icon with double clicks on it.
AS01DNET (RTU) scans an unknown module. Right click current icon to select Change
from the menu which appears to change it into a module icon which can be recognized
for configuration.
After I/O modules are scanned, the main configuration interface changes as follows.
11 - 6 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Double click AS01DNET (RTU) icon on the far left of the configuration page. Then the parameter setting interface of
AS01DNET (RTU) comes out for setting the error handling method as follows.
11
Chooses the extension baud rate of AS01DNET (RTU) after ticking the
checkbox of it. The selected baud rate is stored in AS01DNET (RTU) after the
Software baud
download and it will not take effect until the hardware switch of AS01DNET None
rate
(RTU): DR1 and DR0 are both ON.
Refer to Section 11.2.6 for details on function switch.
Firmware version Displays the firmware version of AS01DNET (RTU). None
11 - 6 3
AS Ser ies M od ul e Man ua l
The mapping parameters of each module can be set through double clicks on the selected I/O module icon on the
following interface.
11
11 - 6 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Double click the 08AD icon. Then the AS08AD-C configuration interface appears as below for configuration of parameter
mapping of AS08AD-C module.
11
Item Description
Displays module name, MDS version and creation date. The module parameters will be shown
MDS information in the left-side window based on the MDS file. For explanation of module parameters, refer to the
relevant module manual.
Displays all module parameters read from the MDS file of the module. Set up these parameters
I/O parameter list
to control the operation of the module.
Exception The error handling of AS01DNET (RTU) when AS01DNET (RTU) detects that an error occurs in
handling the module. “RTU keep running” or “RTU stop” can be selected as the solution to the error.
11 - 6 5
AS Ser ies M od ul e Man ua l
Generally, the settings for I/O module parameters and device mappings can be made in the following three cases.
Case 1: Select one appropriate parameter value from the drop-down list in the Initial column, e.g. select -20Ma~+20mA
11 as channel 1 input mode of AS08AD-C.
Case 2: Manually enter the value for the parameter to change in the Initial column, e.g. write 100 for CH1 Cal.Offset of
AS08AD-C).
11 - 6 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Case 3: For the module parameter which need be monitored in real time or need be modified in its value, tick the desired
parameter in the Mapping to Device column and then the corresponding value of the parameter will map to the
bus data for exchange i.e. the D registers in PLC. After the values of the ticked parameters in the Mapping to
Device column go to the software monitor page, the current values of parameters can be monitored and
modified in real time. 11
Double click the icon of AS08AD-C module. Then the Module Configuration: AS08AD-C dialog box comes out as
below.
11 - 6 7
AS Ser ies M od ul e Man ua l
11
11 - 6 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
11 - 6 9
AS Ser ies M od ul e Man ua l
CH1~CH8 Calibration【16】
11
11 - 7 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Sampling time
11
11 - 7 1
AS Ser ies M od ul e Man ua l
When the software is in online mode and current configuration in AS01DNET (RTU) is the same as that stored in the
software, click the Start Monitor button to enter the monitor interface and start to monitor the operation states of
AS01DNET (RTU) and I/O modules in real time.
11
11 - 7 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Indicates that the module is in the warning or error state. For details on errors, refer to
explanation of error codes in the related product manual.
Indicates that the actually connected module does not match the module configured in the
software or currently configured module has been disconnected.
On the following interface, right click the selected module icon and select RUN or Stop from the drop-down box to
change the operation state of the I/O module.
11 - 7 3
AS Ser ies M od ul e Man ua l
The model of the entire mapping data exchange is displayed below and eventually data will map to the registers in the
PLC of the master.
11
PLC AS 01DNET Dev ic eNET AS0 1DNE T IO modules
(RTU)
Note: All mapping addresses mentioned below means the D registers in the PLC.
The start input address and start output address of AS01DNET (RTU) are assigned automatically by the master when
AS01DNET (RTU) is added to the master. The input mapping address length and output mapping address length of
AS01DNET (RTU) are determined by the configuration of modules connected to AS01DNET (RTU).
The start input and output mapping addresses of one I/O module are assigned automatically by the software. Its input
mapping address length and output mapping address length are determined by the configuration of the module. The range
of input / output mapping address is limited by the input / output mapping address range of AS01DNET (RTU).
11 - 7 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11.5.4.3.2. The Rule for Assignment of Mapping Addresses for AS01DNET (RTU)
The start input and start output mapping addresses of AS01DNET (RTU) are assigned automatically by the master when
AS01DNET (RTU) is added to the master. The master assigns mapping addresses of AS01DNET (RTU) according to input
mapping address length and output mapping address length. Input mapping address length and output mapping address
length are determined by the configuration parameters of all modules connected to AS01DNET (RTU). The start addresses
of AS01DNET (RTU) will not be assigned until AS01DNET (RTU) is added to the master and they are related to the order
of adding slaves to the master.
When there are two slaves of AH10DNET and AS01DNET (RTU), the input size and output size of AH10DNET are both 4
bytes and the input size and output size of AS01DNET (RTU) are both 4 bytes. If AS01DNET (RTU) is added to the master
before AH10DNET is added to the master, then the input mapping addresses and output mapping addresses of AS01DNET
(RTU) are respectively D26005~D26006 and D26105~D26106 as below. D26005 and D26105 are respectively the start
input mapping address and start output mapping address, i.e. status word and control word of AS01DNET (RTU). The
registers after start input mapping address and start output mapping address are for mapping the configuration parameters
of I/O modules.
11 - 7 5
AS Ser ies M od ul e Man ua l
If AS01DNET (RTU) is added to the master after AH10DNET is added to the master, then the input mapping addresses
and output mapping addresses of AS01DNET (RTU) are respectively D26007~D26008 and D26107~D26108 as below.
D26007 and D26107 are respectively the start input mapping address and start output mapping address, i.e. status word
and control word of AS01DNET (RTU). The registers after start input mapping address and start output mapping address
11 are for mapping the configuration parameters of I/O modules.
11 - 7 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11.5.4.3.3. The Rule for Assignment of Mapping Addresses for I/O Modules
Each module has two forms of data mapping. When DeviceNet master has not assigned the start input mapping address
and start output mapping address to AS01DNET (RTU), the contents in Input and Output in the following figure represent
offsets based on start input or start output mapping address of AS01DNET (RTU). After DeviceNet master has assigned
the start input mapping address and start output mapping address to AS01DNET (RTU), the contents in Input and Output 11
in the following figure represent mapping addresses of parameters in the modules on the right of AS01DNET (RTU).
When AS01DNET (RTU) is added to Scan List on the page of Scanner Module Configuration…, DeviceNet master
assigns start input and output mapping addresses to AS01DNET (RTU). When AS01DNET (RTU) is removed from Scan
List on the page of Scanner Module Configuration…, the start input and start output mapping addresses of AS01DNET
(RTU) are unknown.
Before the master assigns mapping addresses to AS01DNET (RTU), the device mappings of modules connected to the
right side of AS01DNET (RTU) are displayed as below.
11 - 7 7
AS Ser ies M od ul e Man ua l
After AS01DNET (RTU) is pulled into Scan List, the mapping addresses that the master assigns to AS01DNET (RTU) are
shown as below.
11
11 - 7 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
After the master assigns mapping addresses to AS01DNET (RTU), the mapping devices of the modules connected
to the right side of AS01DNET (RTU) are shown as below.
11
The software automatically assigns mapping addresses of module parameters in the arrangement order of modules
connected to the right side of AS01DNET (RTU) from left to right.
Below is the table of configuration of one master AS01DNET and one slave AS01DNET (RTU) and mapping addresses
that the software automatically assigns to each module. D26005 and D26105 are the control word and status word of
AS01DNET (RTU).The input mapping address and output mapping address of AS16AP are D26006 and D26106
respectively. The input mapping addresses and output mapping addresses of AS04DA are D26007~D26008 and
D26107~D26114 respectively. The input mapping addresses of AS04AD are D26009~D26018.
Auto Assignment Input Output
AS01DNET(RTU) D26005 status word D26105 control word
AS04AD D26009~D26018
The input and output mapping addresses of AS01DNET (RTU) are D26005~D26018 and D26105~D26114.
11 - 7 9
AS Ser ies M od ul e Man ua l
The start input address and start output address in the mapping areas of AS01DNET (RTU) are used as the status word
and control word of AS01DNET (RTU) respectively with the detailed explanation in the following table.
11
Control word of AS01DNET(RTU)
Bit Status value Description
000 Make no control setting for the operation of AS01DNET(RTU)
bit0
001 Set AS01DNET(RTU) to RUN mode
~
010 Set AS01DNET(RTU) to STOP mode
bit2
Other Reserved
0 Reserved
bit3
1 Restart AS01DNET (RTU)
bit4 0/1 Reserved
bit5 0/1 Reserved
bit6 0/1 Reserved
bit7 0/1 Reserved
bit8 0/1 Reserved
bit9 0/1 Reserved
bit10 0/1 Reserved
bit11 0/1 Reserved
bit12 0/1 Reserved
bit13 0/1 Reserved
bit14 0/1 Reserved
bit15 0/1 Reserved
11 - 8 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
To configure AS01DNET (RTU) successfully and make it work normally in the network, the following steps should be
taken for the setup.
Hardware wiring
During hardware wiring, notice that the standard cable should be used and two terminal resistors of 121Ω should be
connected respectively to the two ends of the main line in the DeviceNet network. The node IDs of all nodes in the network
bus can not be repeated and their baud rates should be consistent.
Online scan
The online scan consists of two parts: scanning online network nodes and scanning I/O modules of AS01DNET (RTU).
Before the scan, make sure that the communication channel selected is proper and the communication setup is normal in
the communication manager COMMGR.
Configuration setting
The configuration setting includes the master configuration and AS01DNET (RTU) configuration settings. The master
configuration contains the master scanner module setting (configuration of master) and the scan list configuration setting.
AS01DNET (RTU) configuration contains AS01DNET (RTU) setting and other I/O modules setting.
Configuration Download
Configuration download consists of master configuration download and AS01DNET (RTU) configuration download. During
the master configuration download, the seven-segment displayer of AS01DNET (RTU) shows 80 and its node ID alternately.
During the AS01DNET (RTU) configuration download, the seven-segment displayer of AS01DNET (RTU) shows 83 and
its node ID alternately.
11 - 8 1
AS Ser ies M od ul e Man ua l
Control Requirement:
1. Connect the output point of AS16AP to the input point; turn on the output point to make the input point ON.
2. Write one value for channel 1 of AS04DA to change into analog signal and then convert the analog signal to
digital signal to output via AS04AD.
POWER 01DNET
DeviceNet RUN
ERROR
MS
COM1
COM2
AS324MT 40
IN 0
x1 0
IN 1 N o d e A d d re ss
0 8 x1 0
1 9
AS01DNET
2 10
3 11
IN
4
5
6
RTU Mode
7
0 8
1 9
Ethernet
2 10 01DNET 16AP 04DA 04AD
Ethernet OUT
3
4
11
2 1
MS
5 NS
6
IN OUT
7
R TU M ast er/ Sla ve 1
IN 0
x1 0 S/S C0 VO1 VO2 V1+ V2+
IN 1 N o d e A d d re ss PWR P WR PWR
C0 IO1 IO2 I1+ I2+
x1 0
0
IN
0 0 0 AG AG E RR VI1 VI2- ERR
1 D A A D
1 1 2 SLD SLD V3+ V4+
3
2 2 4 VO3 VO4 I3+ I4+
5
DeviceNet
3 3 IO3 IO4 VI3 VI4-
6
4 4 7 AG AG SLD SLD
OUT
5 5 0 SLD SLD
1
6 6 2 24V AG 24 V
3
7 7 4 0V 0V
5
6
7
R TU M ast er/ Sla ve
Note:
1. During the wiring, connect the voltage output of channel 1 of AS04DA to the voltage input of channel 1 of
AS04AD. And add the 24 V power to AS04DA and AS04AD respectively.
2. Make sure that the baud rates of AS01DNET and AS01DNET (RTU) match.
3. Connect the 24V network power module between V+ and V- and a terminal resistor of 121Ω between CAN_H
and CAN_L.
Refer to Section 2.4 Communication Setting in the ISPSoft User Manual for more details.
11 - 8 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11 - 8 3
AS Ser ies M od ul e Man ua l
11
The AS01DNET-A master module which has been scanned is shown in the left-side Project List.
11 - 8 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
11 - 8 5
AS Ser ies M od ul e Man ua l
6. Double click AS01DNET (RTU). Then the Node Configuration… dialog box appears. Click the IO Configure…
button to make the AS01RTU-DNET interface appear, where to configure the modules connected to AS01DNET
(RTU).
11
11 - 8 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
7. Click the Scan button to scan the I/O modules connected to the right side of AS01DNET (RTU).
11
11 - 8 7
AS Ser ies M od ul e Man ua l
8. After the module is scanned, configure module parameters. Double click AS04DA module and select “-10V~+10V”
for channel 1 mode setting. Click the OK button to finish the setting. Use the same setting way for channel 1 mode
setting of AS04AD and set it to “-10V~+10V” as well.
11
9. After the configuration of modules is finished, click the Download button to download the configuration of I/O
modules connected to the right side of AS01DNET (RTU) to AS01DNET (RTU).
11 - 8 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
10. After the download, click the OK button to go back to the main page of the software. Double click AS01DNETScanner
icon and then move the slave in Available Nodes to Scan List on the Scanner Module Configuration dialog box.
Click the OK button to finish the setting.
11
11 - 8 9
AS Ser ies M od ul e Man ua l
11. Click menu Network >> Download to download AS01DNET (RTU) configuration to the master.
The input mapping address D26005~D26018 and output mapping address D26105~D26114 are for AS01DNET
(RTU). The start input address D26005 and start output address D26105 are respectively used as the status word
and control word of AS01DNET (RTU). The parameter mappings of all modules connected to AS01DNET (RTU) are
11 displayed below.
11 - 9 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
Program Explanation:
1. In network 1, write a value for the output of AS16AP and for the output of channel 1 of AS04DA when M0 changes
to ON.
2. In network 2, move the input value of AS16AP to D0 and the input value of channel 1 of AS04AD to D1 when M1
changes to ON.
AS01DNET (RTU) provides four diagnosis methods such as LED indicator, seven-segment displayer, status word
diagnosis and software diagnosis.
11 - 9 1
AS Ser ies M od ul e Man ua l
NS indicator
1. Ensure that the IDs of all nodes are unique on the bus.
Network trouble; 2. Check if the network installation is normal.
Repeated node ID; 3. Check if the baud rate of AS01DNET (RTU) is the same
Red light ON
No network power; as that of the bus.
Or BUS-OFF. 4. Check if the node ID of AS01DNET (RTU) is valid.
5. Check if the network power supply is normal.
MS indicator
11 - 9 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Red light
1. Check if the network power supply is normal;
blinking No network power supply;
2. Reset the internal parameters in AS01DNET (RTU);
(ON:0.5s and Configuration error;
OFF: 0.5s Module alarms.
3. Check if there is an error or alarm in the I/O modules 11
connected to the right side of AS01DNET (RTU).
alternately)
Return the product to factory for repair if the error still exists
Red light ON Hardware error
after re-power on.
No I/O module is configured to Add I/O modules in AS01DNET (RTU) in the DeviceNet
F1 AS01DNET (RTU) in the Builder software and download the configuration data to
DeviceNet Builder software. AS01DNET (RTU) after the configuration is finished.
The work voltage of AS01DNET Check if the power supply for AS01DNET (RTU) works
F2
(RTU) is too low. normally.
AS01DNET (RTU) enters the
F3 Repower AS01DNET (RTU).
test mode.
1. Check if the network communication cable is normal and
the shielded cable is grounded.
AS01DNET (RTU) is the Bus- 2. Ensure the baud rates of all network nodes are same.
F4
Off state. 3. Check if the two ends of the network are both connected
with a 120Ω terminal resistor.
4. Repower the scanner module.
Internal error;
Return the product to factory for repair if the error still exists
F6 An error in the internal storage
after re-power on.
units of AS01DNET (RTU)
Internal error;
Return the product to factory for repair if the error still exists
F7 An error in the data exchange
after re-power on.
units of AS01DNET (RTU)
Return the product to factory for repair if the error still exists
F8 Manufacture error
after re-power on.
11 - 9 3
AS Ser ies M od ul e Man ua l
Internal error;
Return the product to factory for repair if the error still exists
F9 An error in the access of the
after re-power on.
11 Flash of AS01DNET (RTU)
When multiple errors exist, the seven-segment displayer of AS01DNET (RTU) will display error codes cyclically. For
example, the error codes: E4 03 80 02 are displayed cyclically. See the detailed meaning as below.
E4 03 80 02
1.
2.
3.
4.
E4 indicates a module error or offline. For details, see the explanation of codes above.
03 indicates the position of the module where an error occurs. The position of the first module connected to the right
side of AS01DNET (RTU) is 1 and that of the second module is 2. Maximum 8 I/O modules are connectable to
AS01DNET (RTU) within the range of 1~8.
11 - 9 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Status
Bit Description Disposal
value
0 AS01DNET (RTU) is in RUN state No correction needed
bit0
1 AS01DNET (RTU) is in STOP state. Restart AS01DNET(RTU)
Valid configuration data in
0 No correction needed
AS01DNET(RTU)
bit1 Re-download the configuration data to
Invalid configuration data in AS01DNET
1 AS01DNET (RTU) by using the DeviceNet
(RTU)
Builder software.
bit2 Reserved —— ——
bit3 Reserved —— ——
Currently connected module matches the
0 No correction needed
configuration in the software.
1. Check if currently connected module is
consistent with the configuration in the
bit4 Currently connected module is software.
1 inconsistent with the configuration in the 2. Change current module to match the
software. configuration in the software or change the
configuration in the software to match
currently connected module.
0 AS01DNET(RTU) in normal operation No correction needed
bit5 Check if the power supply for AS01DNET (RTU)
1 AS01DNET(RTU) in low voltage
is normal.
bit6 Reserved —— ——
0 AS01DNET(RTU) in normal operation No correction needed
bit7
Reserved —— ——
bit8 Reserved —— ——
bit9 Reserved —— ——
bit10 Reserved —— ——
bit11 Reserved —— ——
bit12 Reserved —— ——
bit13 Reserved —— ——
bit14 Reserved —— ——
bit15 Reserved —— ——
11 - 9 5
AS Ser ies M od ul e Man ua l
11
Note: For details on more error codes, refer to the explanation of Error ID in AS-series product manual.
Remark:
The software diagnosis function can not be enabled until the DeviceNet Builder software is online.
11 - 9 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Network structure
11
Connect the devices according to the following figure. PC accesses AS-series PLC through Ethernet.
11 - 9 7
AS Ser ies M od ul e Man ua l
Operation of Software
1. Open the ISPSoft software and then select menu File>> New>> New. In the following dialog box which appears,
select corresponding PLC type AS marked in the red box below.
11
11 - 9 8
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
2. Click the OK button. Then the main interface of the ISPSoft software appears as below.
11
3. Set up COMMGR communication. Refer to Section 2.4 Communication Setting in the ISPSoft User Manual for
more details.
11 - 9 9
AS Ser ies M od ul e Man ua l
4. After the setup of COMMGR communication is finished, select menu Tools>> Communication settings…
11
5. The following dialog box appears. Select one desired driver which has been created and then click the OK button.
11 - 1 0 0
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
7. Select menu Option>> I/O Scan in the following window which pops up. Then the AS01DNET-5A icon will show
up.
11 - 1 0 1
AS Ser ies M od ul e Man ua l
8. Select menu Option>> Download in the HWCONFIG window. Then the following dialog box appears. Select the
checkbox of Download All Items or select the checkboxes of the items which are needed for download.
Afterwards, click the OK button.
11
9. Then the following two dialog boxes of HWCONFIG and PC=>AS appear. Click Yes to perform the PC=>AS status.
10. When the download is finished, the progress bar is shown as below.
11 - 1 0 2
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
Meanwhile the following dialog box pops out. Click the Yes button.
11
11. The following dialog box appears to show that the download has been finished.
12. Return to the HWCONFIG window and right-click AS01DNET module to make the drop-down menu pop out. Select
Communication Software >> DeviceNet Builder from the menu.
11 - 1 0 3
AS Ser ies M od ul e Man ua l
13. The following dialog box pops out. Click the Yes button there.
11
14. The DeviceNet Builder software is opened as below, which means the DeviceNet Builder software has been
opened through the ISPSoft software.
11 - 1 0 4
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
11
11 - 1 0 5
AS Ser ies M od ul e Man ua l
17. Right-click the master module AS01DNET-A under the left-side Project List. Then a drop-down list pops up. Click
the option Scan DeviceNet Network from the list.
11
11 - 1 0 6
Ch ap te r 11 De viceNe t M as ter Sca nner Mo du le AS01DN ET-A
19. The master and slave which have been scanned both show up in the network.
11
11 - 1 0 7
AS Ser ies M od ul e Man ua l
MEMO
11
11 - 1 0 8
12
Chapter 12 Positioning Module AS02/04
Table of Contents
12.1 Overview .............................................................................................. 12-2
12.1.1. Characteristics ................................................................................. 12-2
12.2 Specifications and Functions ................................................................ 12-3
12.2.1. Specifications ................................................................................... 12-3
12.2.2. Profile ............................................................................................. 12-5
12.2.3. Arrangement of Terminals .................................................................. 12-6
12.2.4. Special Features ............................................................................... 12-8
12.2.5. Wiring ............................................................................................. 12-8
12.3 HWCONFIG in ISPSoft ........................................................................ 12-11
12.3.1. Initial Setting .................................................................................. 12-11
12.3.2. Checking the Version of a Module ...................................................... 12-13
12.3.3. Online Mode .................................................................................... 12-15
12.3.4. Importing/Exporting a Parameter File ................................................. 12-16
12.3.5. Parameters ..................................................................................... 12-18
12.3.6. Normal Exchange Area ..................................................................... 12-20
12.4 Troubleshooting ................................................................................. 12-21
12.4.1. Error Codes .................................................................................... 12-21
12.4.2. Troubleshooting Procedure ................................................................ 12-21
12.4.3. State Codes (Axis 1 - 4) ................................................................... 12-21
12-1
A S S er i es Mo d u le Ma n ua l
12.1 Overview
This chapter describes the specifications for the positioning module, its operation, and its programming. On
the analog input/output module, four channels receive analog signals (voltage or current), and converts those
signals into 16-bit digital signals. In addition, the analog input/output module receives two blocks of 16-bit
digital data from a CPU module, and converts the digital data into analog signals (voltage or current). The
12 12.1.1. Characteristics
(1) Use the AS02/04 PU-A module, based on its practical application.
AS02PU-A: high speed output frequency at 200 k Hz (A/B/Z phase) and 2-axis 200 k HZ differential
output
(3) Input/output
The HWCONFIG utility software is built into ISPSoft. You can set modes and parameters directly in
HWCONFIG without spending time writing programs to set registers to manage functions.
You can use specially designed instructions to control the modules without spending too much time to
12-2
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
3 5 12
Number of Input Points 6
(A+/A-, B+/B-, Z+/Z-) (X0.0-X0.4)
Direct current
(sinking or sourcing)
collectors.
Input display When the optocoupler is driven, the input LED indicator is ON.
Weight 120 g
12-3
A S S er i es Mo d u le Ma n ua l
Model
AS02PU-A AS04PU-A
Item
Resistance 10 mA 0.1A
Maximum
Inductance N/A
load
Bulb N/A
Weight 120 g
*1: Acutal output: 4 VDC (high input impedance) to 3.3 VDC (10 mA)/output
12-4
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
12.2.2. Profile
38.2 95
1
7
7
98 .3
88
8 2 3
12
4
9
5
6 75
35
Unit: mm
Arrangement of the
4 Arrangement of the terminals
input/output terminals
6 DIN rail clip Secures the module onto the DIN rail
12-5
A S S er i es Mo d u le Ma n ua l
9 Label Nameplate
02PU
04PU
IN IN
IN OUT
A+ A-
C0
B+ B- PWR
0 PWR
Z+ Z- RUN
ERR 0 1 RUN
0 A ERR
B 1 2 0
1 2 Z 1
0 2 3 2
3 4 IN
IN 1 3
OUT OUT 3 C1
2
0+ 0- 4
5
3 4 4
1+ 1-
4 0
5 5
2+ 2- 1
●
6 2
3+ 3- 0 3
1 OUT
●
7 4
OUT
2 5
3 6
7
12-6
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
AS02PU-A AS04PU-A
Wordings with the same indications that are used Wordings with the same indications that are used
on the terminal block and manual on the terminal block and manual
A+ A+ A- A- S/S S/S C0 C0
12
B+ B+ B- B- S/S S/S Y0.0 0
Z+ Z+ Z- Z- X0.0 0 Y0.1 1
12-7
A S S er i es Mo d u le Ma n ua l
output control parameters, reading output status, pulse output (no acceleration), relative position output (with
acceleration and deceleration), absolute addressing output (with acceleration and deceleration), homing, jog
output, MPG output, and high-speed counter function. Refer to section 6.15 (API 14) in AS Programming
12
12.2.5. Wiring
Precautions
To ensure the positioning module functions well and reliably, the external wiring must prevent noise.
(1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the
(2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load that
is not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable, or a
(4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the
(5) Use single-core cables or twin-core cables with a diameter of 24–22 AWG and with pin-type
connectors smaller than 1 mm. The plastic jackets that are removed from the cables should be 8
mm to 10 mm long. Only use copper conducting wires which can withstand temperatures of 60° C
/75° C or higher.
(6) Note: use cables with the same length (less than 200 m) and use wire resistance of less than 100
ohm.
Four-wire connection (active transducer): the transducer uses an independent power supply, so
do not connect it to the same power circuit as the analog input module.
12-8
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
External wiring
(1) AS02PU-A
X0.4
X0.1
Y0.1- /SIGN 37 12
X0.0
5 ~2 4V *4
A+
R* 6
A-
B+
R*6
B-
Z+
R*6
Z-
*5
A+
R* 6
A-
B+
R* 6
B-
Z+
R* 6
Z-
5 ~2 4V
*1. Sinking
*2. Souring
*6. Open collector sinking/sourcing to conncet to phase A/B/Z and if the input frequenct is higher than 100
kHz, add a 3W/470 ohm resistor between + the positive end and – the negative end.
*7. Refer to API1402 in AS Series Programming Manual and Delta Servo Drive Manual for more
12-9
A S S er i es Mo d u le Ma n ua l
(2) AS04PU-A
9 1kΩ
PU L L_ HI_ P 339 Ma x.
2 00Kpps
PUL SE 43
X0.5 51Ω
Y0.0 /PU L SE 41
51Ω
C0 COM- 45
X0.4
12
*3 0V
X0.2 5 1 kΩ
PU LL _ HI_ S 339 Max.
200 Kp ps
SIGN 36
51Ω
X0.1 Y0.1 /S IGN 37
51Ω
C0 C OM- 45
*3 0V
X0.0
5~30VD C, 0.1A
*4 Y0.4
S/S
C1
*2
+24V
*5 *3
*1. VDD and COM are seen as a group and its power is provided by Delta servo drive.
*3. Use the same power supply for the same COM group.
*4. Sinking
*5. Sourcing
12-10
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
12
1 2 - 11
A S S er i es Mo d u le Ma n ua l
(3) Double-click the module in the working area to open the Setting page.
12
(4) Choose the parameter, set the values, and close the setting page.
12-12
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
(5) Click Download on the toolbar to download the parameters. Note that you cannot download the
parameters while the CPU module is running.
12
12-13
A S S er i es Mo d u le Ma n ua l
(2) Double-click the module to open the Setting page. The versions of both the firmware and the hardware
are displayed.
12
12-14
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
12
12-15
A S S er i es Mo d u le Ma n ua l
12
12-16
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
12
(2) Click Import in the Device Settings dialog box and select a .dep file to import saved parameters.
12-17
A S S er i es Mo d u le Ma n ua l
12.3.5. Parameters
The input point settings
You can set values in the input points as the triggering conditions (phase Z, DOG, LSN, LSP) for the
axis1 and axis 2 to position. Rising-edge and falling-edge can also be specified in the triggering
conditions.
12
12-18
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
The default setting is 10 ms; the system filters out distortion and noises in a pulse width modulated
You can set values in the output points (single pulse output, pulse + direction, CW+CCW, A phase + B
phase). Refer to API1402 in AS Series Programming Manual for more information on output modes.
12
Axis settings
You can set up the axis in HWCONFIG or through positioning instructions. Use API1402 to set up the
followings starting speed, accelation time, deceleration time, max. speed, seeking the set number of Z phase
after homing, output the offset position after homing. Use API1407 to setup homing mode. Refer to API1402 –
1410 in AS Series Programming Manual for more information on the settings of axis.
12-19
A S S er i es Mo d u le Ma n ua l
parameters.
AS02PU-A
12
AS04PU-A
12-20
Ch a pt er 1 2 Pos i t io n i ng M o d ul e A S 0 2/ 04 P U
12.4 Troubleshooting
12.4.1. Error Codes
12
12.4.2. Troubleshooting Procedure
Description Procedure
0 Error flag
8 Error flag
12-21
A S S er i es Mo d u le Ma n ua l
MEMO
12
12-22
13
12
Chapter 13 IO-Link Communication Module
AS04SIL
Table of Contents
13.1 Overview .................................................................................................. 13-2
13.1.1 Firmware and Software Versions ............................................................. 13-2
13.2 Specification and Wiring .......................................................................... 13-3
13.2.1 Specifications ....................................................................................... 13-3
13.2.2 Profile ................................................................................................. 13-5
13.2.3 Wiring ................................................................................................. 13-6
13.3 Functions ................................................................................................. 13-8
13.3.1 Basic Functions .................................................................................... 13-8
13.3.2 Application Functions ........................................................................... 13-14
13.4 Application Examples ............................................................................. 13-16
13.4.1 Using AS Series CPU as Upper Device .................................................... 13-16
13.4.2 Using AH Series CPU or Non-Delta Master PLC as Upper Device ................. 13-17
13.4.3 Application of AS Special Remote Mode .................................................. 13-18
13.4.4 Application of Delta Special Driver & AS Remote Mode ............................. 13-30
13.4.5 Application of CANopen DS301 Mode ..................................................... 13-32
13.5 IO-Link Event Code Table ....................................................................... 13-39
13.6 Module Status Codes .............................................................................. 13-41
A S S er i es Mo d u le Ma n ua l
13.1 Overview
Thank you for using the IO-Link master module AS04SIL-A. To ensure that your AS04SIL-A is installed and operated
correctly, read this manual carefully before using the module.
The AS04SIL-A module is an AS series IO-Link communication module (hereafter referred to as “SIL” module) connected
on the right side of AS CPU module or AS00SCM-A (RTU mode). When the communication card AS-FCOPM is being used
together, they serve as a CAN remote device. SIL provides 4 channels, which can be separately configured in IO-Link
master or standard I/O (SIO) mode. IO-Link master can freely connect with IO-Link devices and supports the hybrid use of
IO-Link sensors and traditional sensors. Digital I/O of the SIL module can be extended with IO-Link hubs so that the sensors
which do not support IO-Link can be connected to. Therefore it is pretty flexible to use the SIL module.
The setup software for AS04SIL-A is HWCONFIG 4.0 which is built in ISPSoft. Go to Delta official website to download
and install ISPSoft.
_13
13.1.1 Firmware and Software Versions
Firmware
Model AS series CPU AS00SCM-A AS04SIL-A
Version V1.08.50 and later V2.06 and later V1.00 and later
Software
AS00SCM-A CANopen EDS file
Model ISPSoft HWCONFIG 4.0
(Remote DS301 Mode)
Version V3.12 and later V4.02 and later V2.06 and later
13-2
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
Item Specifications
13-3
A S S er i es Mo d u le Ma n ua l
Electrical Specifications
Item Specifications
13-4
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13.2.2 Profile
38.2 95
04 SI L 1
7
7
CQ 1 L1+
PWR
DI 1 L1-
CQ2 L2+ MS 2
98.3
NS
88
DI2 L2- C1
Q1
CQ3 L3+
E1
C2
DI3 L3 -
CQ4 L4+
Q2
E2 3
DI4 L4- C3
Q3
24 V E3
4
●
C4
0V Q4
E4
8 5
6 75
35 13
Unit: mm
Number Name Description
1 Model name Model name of the module
13-5
A S S er i es Mo d u le Ma n ua l
13.2.3 Wiring
13.2.3.1 IO-Link Mode Wiring for Power and Communication
Precautions:
1. Keep the input cables, output cables and power cable separate from one another. It is suggested to use independent
_13 power for AS04SIL-A. See the example below.
IO-Link Sens or
(w it h DI )
I O-Link Mast er
A S 04S I L-A 1 B rown
C Q1 . L1+ . 2 Whit e
D I1
. L1- . 3 B lue
4 Black
C Q2 L2+
D I2 L2-
C Q3 . L3+ . 1 B rown
D I3 L3- .
C Q4 L4+ 3 Blue
4 Black
D I4 L4-
0V 24V
DC Power S upply
24V D C
2. The 24 VDC cable should be twisted and connected to a module within a short distance.
3. Do not bundle 110 VAC cable, 220 VAC cable, 24 VDC cable, the (high-voltage high-current) main circuit, and the I/O
signal cable together and keep the power cables away from the earth cable. It is suggested that the distance between
adjacent cables should be more than 100 millimeters.
5. Use single-wire cables or two-wire cables with a diameter of 20 AWG to 14 AWG. Only use copper conducting wires
with a temperature rating of 60/75°C.
13-6
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
CQn CQn
Ln- Ln-
0V 0V
2 4V 2 4V
0V 0V
13
Note: n= 1~4
0V 0V
2 4V 2 4V
0V 0V
Note: n= 1~4
When the connected device is a PNP type When the connected device is a NPN type
DI n DI n
Ln- Ln-
0V 0V
2 4V 2 4V
0V 0V
Note: n=1~4
13-7
A S S er i es Mo d u le Ma n ua l
13.3 Functions
AS04SIL-A supports the IO-Link devices when it works as the IO-Link master. Between the master and the devices is the
point-to-point connection adopting the reliable 3-wire technology and the unshielded standard cable to connect intelligent
sensors/actuators which function as IO-Link devices. AS04SIL-A is compatible with traditional digital sensors/actuators.
The designs for circuit status and data channels are both based on the reliable 24VDC technology.
13-8
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
A mixture of IO-Link communication and digital I/O can apply to the same AS04SIL-A module.
13-9
A S S er i es Mo d u le Ma n ua l
_13 communicate with them. Thus there is no need to set the baud rate at communication ports for connected devices.
The real-time data can be monitored through Port 1- 4 Pin2 value of Normal Exchange Area. See the following figure as
an example.
13-10
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
The mapped register for Port 1- 4 Pin2 value of Normal Exchange Area is D29029. For the pin2 input value, the
addresses D29029.0~ D29029.3 correspond to port 1~ port 4 respectively.
Communication Port Address
Port 1 D29029.0
Port 2 D29029.1
Port 3 D29029.2
Port 4 D29029.3
DI1-DI4 of AS04SIL-A can also be used separately as standard inputs.
The device status for each port should be set to 3 bytes in length. See the following table of above device addresses
corresponding to ports in order.
Description Address
Port 1 D29022_H, D29022_L, D29023_H
Port 2 D29023_L, D29024_H, D29024_L
Port 3 D29025_H, D29025_L, D29026_H
Port 4 D29026_L, D29027_H, D29027_L
1 3 - 11
A S S er i es Mo d u le Ma n ua l
Value Definition
0 Unknown
1-3 Reserved
4 Application
5-7 Reserved
Bit 3: SOURCE
Value Definition
0 Device (Remote)
1 Master (Local)
Value Definition
0 Reserved
1 Notification
2 Warning
3 Error
Value Definition
0 Reserved
1 Event single shot
2 Event disappears
3 Event appears
Whether the input data is invalid or not can be monitored by Port1 – 4(IO-Link Process Data) Input Invalid Flag of the
Normal Exchange Area section. If the flag is 1, then the input data is invalid. If it is 0, the input data is valid.
See the example in the following figure.
The mapped register for Port1 – 4(IO-Link Process Data) Input Invalid Flag is D29028 and for the input invalid flag,
D29028.0~ D29028.3 correspond to Port 1~Port 4 respectively as shown in the following table.
13-12
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
You can also select any AS04SIL-A module and then click Scan All Device to scan all the IO-Link devices connected to
the communication port of AS04SIL-A.
While SIL is auto-identifying devices, all IO-Link devices connected to IO-Link master need be restarted and therefore
the devices will probably stop running for a short time.
13-13
A S S er i es Mo d u le Ma n ua l
_13 For example, the IO-Link device configured for Port 1 supports four work modes in the following figure. The default work
mode is Segment mode (0).
When Level mode (1) is switched to, a Confirm dialog box will appear to alert that the Process Data content will be
changed.
13-14
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
Clicking Yes button, the Process Data content will be refreshed in the software.
Click menu Communication > Download. The switch is completed once the download is done.
13
The V1.1 IO-Link devices support the Backup and Restore functions which are not necessary functions and are
determined by their IODD files.
IO-Link device parameter settings are backed up to the IO-Link master or restored to IO-Link devices. When IO-Link
devices are replaced, the communication can be resumed according to original settings instead of setting parameters
once again. See the setting page below.
Option Description
Disable The backup function is disabled and the backed up process data is cleared.
The backup file is empty if no data exists. It is allowed to back up the parameters read from
Backup/Restore
the connected device to the master and write the parameters to the connected device.
Restore To write parameters to the connected device is allowed.
13-15
A S S er i es Mo d u le Ma n ua l
I O-Link
_13 Input
S ensor/A ctuat or
Hub
I OD D file
Connect to US B port
or E thernet port 16x DI / DO
of A S series CP U ….. …..
Soft ware:
HW CO NFI G 4 .0
CA N open Builder
I O-Link
S ensor/Actuat or
Hub
CA N
I O-Link
B inary
E thernet / U S B
An AS04SIL-A module can connect with 4 IO-Link devices at most. If the hybrid use of the IO-Link devices and multiple
traditional sensors (binary sensors) is needed, there are two connection methods based on the number of traditional
sensors on site.
1. If there is only a small number of traditional sensors to be connected, each of AS04SIL-A module’s ports can connect
with one traditional sensor by using the DI function of Pin2 for each port.
2. If there are many traditional sensors to be connected, use the IO-Link hub from other brand to extend the connectable
digital I/O devices.
13-16
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
I mport
I OD D file
C on nect t o U SB p ort
o r Ethe rn et p o rt
o f AS Series C PU IO-Link
Sens or /Act uat or
:
Software: Hub
H WCON FIG4 . 0
CA Nopen Builder 16x D I/ DO
… .. …..
I O-Link
Sens or /Act uat or
Hub
C AN
IO-Lin k
Bina ry
Etherne t / U SB
Pin2 DI funct ion
13-17
A S S er i es Mo d u le Ma n ua l
According to the description on CANopen DS301 Mode in section 13.4.1, connect the AS00SCM-A module to AS CPU in
AS special remote mode, configure all extension modules and IO-Link devices in HWCONFIG 4.0 and then switch the
mode back to the CANopen DS301 mode.
If the upper device is an AH series CPU, the CANopen Builder software can be opened. Configure the PDO mapping list
according to the EDS file of the AS00SCM-A module. See the details in section 13.4.5.
If the upper device is a master PLC from other brand, use the software from the brand to configure the CANopen slaves
and PDO mapping.
First of all, open the HWCONFIG 4.0 software and import the IODD files of IO-Link devices which can be downloaded from
vendors’ official websites. Follow the steps here to import the IODD files through the Device Description File Manager
tool.
13-18
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
Put all IODD files in the same folder so as to import multiple IODD files at a time.
13-19
A S S er i es Mo d u le Ma n ua l
_13
Check the following setups before the AS00SCM-A module is powered on.
1. The AS-FCOPM card is inserted to AS00SCM-A via Card 2. (The 120Ω terminal resistor is enabled.)
2. Use Delta standard cables to connect to AS CPU and the mode switch is turned to RTU mode.
3. Four switches are set to ID1: 0/ FORMAT1: 0/ ID2: 1/ FORMAT2: 7 and the status is set to AS Remote Communication,
node ID 1 and baud rate 1Mbps.
4. AS04SIL-A is connected on the right side of AS00SCM (RTU). Ensure that IO-Link devices are connected to the four
ports according to the wiring in section 13.2.3.
13-20
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
Switch the power on after the AS-FCOPM card is inserted to AS332T-A via Card 2. (The 120Ω terminal resistor is enabled.)
Open the HWCONFIG 4.0 software, set up function card 2 for AS CPU and then download the settings as follows.
13
13-21
A S S er i es Mo d u le Ma n ua l
_13
Ensure that the CANopen cables are connected properly and the AS00SCM-A module is already powered on. Check if the
Card2 LED indicator of AS00SCM-A keeps blinking after the configuration of AS332T-A is downloaded so as to make sure
the communication works normally.
13-22
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
Once any AS04SIL-A module is detected through the software scan, the software will ask whether to scan the connected
IO-Link device.
13-23
A S S er i es Mo d u le Ma n ua l
Perform the scan of IO-Link devices. If some configured devices are in communication during the scan, they will fail to be
used temporarily. Restart the devices after the scan is over and restore the original work mode.
_13
Click the IO-Link module and then select the IO-Link page where each device model and related information are can be
seen and the parameters to be set up are all default values.
If no matched IODD file can be found out for the scanned device, Unknown Device will be shown in the device name field.
Users need download the IODD file of the device from the coporate website of the device product according to the scanned
device details such as Vendor Name, Vendor ID, Device ID and Device Name and then import the file into the HWCONFIG
software.
13-24
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
Under the Process Data tab, you can find the supported register addresses of each port. Since ISPSoft V3.11 supports
using tags in PLC programming, it is very useful to set up the tags and its corresponding register addresses.
Follow the steps 1~3 below to set up the tabs.
Step 1: Click Set All Tag
Step 2: A confirmation shows up asking you if you want to overwrite the set tags and comments. Click Yes to proceed.
13-25
A S S er i es Mo d u le Ma n ua l
Step 3: All the editable tags show up. Double-click the tags in blue to edit if you need to use a different name other than
the default ones.
Note: One register address coresponds to one tag, and it shows on the first group of address.
_13
13-26
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
13-27
A S S er i es Mo d u le Ma n ua l
_13
13-28
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
Click the On-line Mode button on the IO-Link page and then see the connection status of all devices and the real time
monitored values of input and output process data.
13
The Status of Port 1~ Port 4 above can also be known through the parsing in the Normal Exchange Area of the
AS04SIL-A module below.
13-29
A S S er i es Mo d u le Ma n ua l
With a click on any device, only the input and output process data of the clicked single device will be displayed.
_13
13.4.4 Application of Delta Special Driver & AS Remote Mode
The device list in the following example is the same as that in section12.4.3.
Model name Device type
AS332T-A PLC
AS00SCM-A RTU
AS04SIL-A IO-Link Master
AI-B100 3rd IO-Link Device
E3S-DCP21-IL3 3rd IO-Link Device
MAXREFDES27# 3rd IO-Link Device
MAXREFDES36# 3rd IO-Link Device
Complete the following setups before the AS00SCM-A module is powered on.
1. The AS-FCOPM card is inserted to AS00SCM-A via Card 2. (The 120Ω terminal resistor is enabled.)
2. Use Delta standard cable to connect to AS CPU and the mode switch is turned to RTU mode.
3. Four switches are set to ID1: 0 / FORMAT1: 8 / ID2: 9 / FORMAT2: 7and the status is set to Delta Special Driver &
AS Remote Communication, node ID 9 and baud rate 1Mbps.
4. AS04SIL-A is connected on the right side of AS00SCM (RTU). Ensure that IO-Link devices are connected to the four
ports according to the wiring in section 13.2.3.
Switch the power on after the AS-FCOPM card is inserted to AS332T-A via Card 2. (The 120Ω terminal resistor is
enabled.) Open the HWCONFIG 4.0 software, set up function card 2 for AS CPU and then download the settings as
follows.
13-30
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
The following steps are the same as the operation in section 13.4.3.
13-31
A S S er i es Mo d u le Ma n ua l
The device list in the following example is the same as that in section12.4.3.
AS332T-A PLC
AS00SCM-A RTU
The CANopen Builder does not support the configuration of extension modules on the right of the AS00SCM-A module
and connected IO-Link devices.
First make the connection in AS Special Remote mode, configure all extension modules and IO-Link devices in the
HWCONFIG 4.0 software (see the example in section 13.4.3) and then switch back to the CANopen DS301 mode.
Please complete the following setups before the AS00SCM-A module is powered on.
1. The AS-FCOPM card is inserted to AS00SCM-A via Card 2. (The 120Ω terminal resistor is enabled.)
2. Use Delta standard cables to connect to AS CPU and the mode switch is turned to RTU mode.
3. Four switches are set to ID1: 0 / FORMAT1: 4 / ID2: 2 / FORMAT2:7and the status is set to CANopen DS301, node
ID 2 and baud rate 1Mbps.
4. AS04SIL-A is connected on the right side of AS00SCM (RTU). Ensure that IO-Link devices are connected to the four
ports according to the wiring in section 13.2.3.
Switch the power on after the AS-FCOPM card is inserted to AS332T-A via Card 2. (The 120Ω terminal resistor is
enabled.) Open the HWCONFIG 4.0 software, set up function card 2 for AS CPU and then download the settings as
follows.
13-32
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
Right-click the AS332T-A symbol and open the CANopen Builder software as below.
13-33
A S S er i es Mo d u le Ma n ua l
Click the Scan button. Then the AS00SCM-A RTU module can be detected.
_13
Double-click the detected AS00SCM-A RTU module and ensure that it is with EDS file V2.06 or later. If the EDS file is not
matched, check if the V2.06 EDS file has been imported to the left-side device list and the firmware of AS00SCM-A is
V2.06 or later.
13-34
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
13-35
A S S er i es Mo d u le Ma n ua l
Each object in the EDS file is 1 word (2 bytes) in size and thus one PDO corresponds to one mapped register. Assign all
input parameters to available TxPDOs according to the parameters in the Normal Exchange Area of AS04SIL-A in
section 13.4.3. The mapped PDO object of the input process data is Tx_ModuleX_EDIY (Exchanging Data Input which is
referred to as EDI).
In this example, the AS04SIL-A module is the first one on the right of the RTU module. Therefore the value of X is 1 and
the PDO mapped object for error codes is Tx_Module1_error_code. The corresponding objects starts from
Tx_Module1_EDI0 as below.
_13
Based on all communication port address information in the HWCONFIG 4.0 software in section 13.4.3, assign all input
process data to available TxPDOs, which corresponds to the mapped object Tx_NIOX_PD_InputZ and assign all output
process data to available RxPDOs, which corresponds to the mapped object Rx_NIOX_PD_OutputY.
In this example, the AS04SIL-A module is the first one on the right of the RTU module. Therefore the value of X is 1, the
input objects starting from Tx_NIO1_PD_Input0 correspond to IO-Link Port1~ Port4 in Process Data- Input respectively
and the output objects starting from Rx_NIO1_PD_Output0 correspond to IO-Link Port1~ Port4 in Process Data- Output
respectively.
Configure all parameters which need to be updated continuously (which are called objects in CANopen Builder) to one
TxPDO or RxPDO according to the steps described above. Add AS00SCM-A RTU to the slave list (Node List) and then the
real addresses of mapped registers in AS CPU show up immediately as below.
13-36
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13
According to the Normal Exchange Area page in HWCONFIG in section 13.4.3, the PDO mapped objects correspond to
the mapped registers assigned by CANopen Builder as follows.
13-37
A S S er i es Mo d u le Ma n ua l
Mapped register in
Parameter Configured PDO PDO mapped object
AS CPU
Error code Tx_Module_error_code D24032
Tx_Module1_EDI0 D24033
Port 1-2 Device TxPDO1
Tx_Module1_EDI1 D24034
Status
Tx_Module1_EDI2 D24035
Tx_Module1_EDI3 D24036
Port 3-4 Device
Tx_Module1_EDI4 D24037
Status
Tx_Module1_EDI5 D24038
TxPDO2
Port1-4 (IO-Link
Process Data) Tx_Module1_EDI6 D24039
Input Invalid Flag
Tx_NIO1_PD_Input0 D24040
Port 1 Process
Tx_NIO1_PD_Input1 D24041
Data- Input TxPDO3
_13 Tx_NIO1_PD_Input2 D24042
Port 2 Process Tx_NIO1_PD_Input3 D24043
Data- Input Tx_NIO1_PD_Input4 D24044
Tx_NIO1_PD_Input5 D24045
TxPDO4
Tx_NIO1_PD_Input6 D24046
Tx_NIO1_PD_Input7 D24047
Port 3 Process Tx_NIO1_PD_Input8 D24048
Data- Input Tx_NIO1_PD_Input9 D24049
TxPDO5
Port 4 Process Tx_NIO1_PD_Input10 D24050
Data- Input Tx_NIO1_PD_Input11 D24051
Port 1 Process Rx_NIO1_PD_Output0 D25032
Data- Output Rx_NIO1_PD_Output1 D25033
Port 2 Process No parameter need
No parameter need be output
Data- Output be output
RxPDO1
Port 3 Process
Rx_NIO1_PD_Output2 D25034
Data- Output
Port 4 Process
Rx_NIO1_PD_Output3 D25035
Data- Output
13-38
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
13-39
A S S er i es Mo d u le Ma n ua l
13-40
Ch a pt er 1 3 IO - Li nk C o m m unic a t io n M o du l e A S 04 S IL
Error
Description Solution
Code
16#1800 Error occurs in IO-Link Master See section 13.5 for more information.
16#1801 Error occurs in IO-Link device See section 13.5 for more information. 13
16#1802 No external power supply Check the external power supply
Error in the download of IO-Link
16#1803 Redownload the configuration by the software
device mapping tables
Failure to switch the process data Check if the connected device is the same as that configured in
16#1804
parameter set the software.
Error occurs in the communication
16#1805
port 1 of IO-Link connection
Error occurs in the communication 1. Cut the external power off for 3 seconds and power-on
16#1806
port 2 of IO-Link connection again
Error occurs in the communication 2. Download the configurations again
16#1807
port 3 of IO-Link connection
Error occurs in the communication
16#1808
port 4 of IO-Link connection
1. Cut the external power off for 3 seconds and power-on
Error occurs in scan device and
16#1809 again
force to stop scanning
2. Scan all devices again
13-41
A S S er i es Mo d u le Ma n ua l
MEMO
_13
13-42
14
10
Chapter 14 High Speed Counter Module
AS02HC
Table of Contents
14-1
A S S er i es Mo d u le Ma n ua l
Overview
The AS02HC-A module is a high-speed counter module with two built-in channels. It performs counting through receiving
the pulse signal input or SSI encoder signal input. It is only connected to the right side of AS series CPU modules.
Configuring it to the right side of the remote modules is not allowed. This chapter mainly introduces the specifications,
functions and operation of the module.
Characteristics
1. Pulse signal / SSI signal input interface selection
Pulse input: Supports single-phase pulse input, two-phase pulse input (multiplication x2/4) and CW / CCW pulse input,
5V differential signal and 5-24VDC single-ended signal. The counting speed can reach up to 200kHz
(for single-phase input).
SSI input: The data transmission frequency can reach up to 1.25 MHz; the received data length can be up to 32 bits;
supports multi-turn and single-turn SSI encoders as well as the conversion of gray and binary codes.
2. 32-bit counter
The two channels of AS02HC-A are both 32-bit counters with the counting range of -2147483648 to 2147483647.
3. Counter type setting
Ring counter: cyclical counting between -2147483648 and 2147483647.
14 Linear counter: The upper and lower limit values need be set. When the counter value is out of the allowed range,
the module can detect that the upper or lower limit is exceeded.
4. High-speed comparison
Preset a comparison value and compare it with the present value of the counter. When they are equal, the external
output point actions can be controlled, the interrupt program can be executed or the counter value can be cleared at
the same time.
5. Phase-Z function selection
Each of the two channels is configured with a phase Z which can be used as the external input point for Reset,
Capture or Gate control.
6. External output points
Four external output points. They can be controlled individually or be used for the output together with high-speed
comparison function.
7. Counter value capture
The counting value is captured through a phase Z input trigger or channel comparison-matched trigger.
8. Pulse rate and rotation rate (RPM) measurement
The function measures the input pulse rate and position change rate of the SSI encoder. And the rotation speed
(RPM) can be calculated automatically.
9. Use the tool software for easy settings
HWCONFIG built in ISPSoft can be used to create the hardware module configuration so that users can directly
select the mode and parameters without spending time programming to set up the registers corresponding to a
variety of functions.
10. Miscellaneous API instructions
The functions such as counter control, counter value capture, high-speed comparison output and measurement can
be achieved via dedicated API instructions.
14-2
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
Item Description
Number of channels 2
SSI Input
250 kHz → 150 m 14
500 kHz → 50 m
Max. transmission
625 kHz → 40 m
distance
1 MHz → 20 m
1.25 MHz → 10 m
Counter control Reset, preset, gate, capture offset correction for absolute position
Counter
Count direction, counting overflow/underflow, linear counting beyond the
lower and upper limit values, SSI feedback, SSI position exceeding the
State check
protection limit, SSI parity checking, SSI communication status, a zero
point is set beyond SSI encoder resolution
Input point
2 (one point per channel)
number
Function Counter reset, gate control, counting value capture
External input
point (phase Z) Digital filtering Disabled, 100 us, 200 us …20 ms
Min. software
interrupt response 20 us (hardware response time included)
time
Output point
External output 4
number
point
Output type NPN transistor (sinking)
General comparison output instruction, table comparison output
Comparison Instruction instruction
function Interrupt Using comparison to achieve the interrupt function
14-3
A S S er i es Mo d u le Ma n ua l
Action OFF→ON 3V
level ON→OFF 1V
Maximum input
200 kHz 20 kHz
frequency
Input impedance 4.7 kΩ
Input signal Single-ended signal: 5 ~ 24 VDC (sinking or sourcing); differential signal: 5 V
Electrical isolation 500 VDC
Input display When the optocoupler is driven, the input LED indicator is ON.
Weight 138 g
Model
SSI input SSI output
14 Item
Number of inputs /
2 (DATA+/DATA-) 2 (CLK+/CLK-)
outputs
Connector type D-sub15
Voltage / Current 5 VDC, 1 mA 5 VDC, ±60 mA (Max)
14-4
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
Model
AS02HC-A
Item
Number of outputs 4
Connector type D-sub15
Output type NPN transistor (sinking)
Voltage / Current 5~30 VDC, 0.1 A
Resistance 0.1 A
Maximum -
load Inductance
Bulb -
Resistance 10 kHz
Maximum
output Inductance -
frequency
Bulb -
Maximum
Response OFF→ON 25 us
time
14
Electrical specifications for the +5 V encoder power supply
Model AS02HC-A
Item
Number of outputs 2 (+5VO/GND)
Connector type D-sub15
Voltage / Current 5 VDC (±5%), 100 mA (Max)
14-5
A S S er i es Mo d u le Ma n ua l
Profile
7 5
1
5
98.3
88
2
6
4 75
35
7 Label Nameplate
14-6
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
Terminals
3 A1- A2-
PWR
7 B1+ B2+
ERR
CH1 Act.
CH1 A 2 B1- B2-
CH1 B
CH2
CH1 Z
Y0.0
Y0.1 6 Z1+ Z2+
CH2 Act.
CH2 A
CH2 B
CH2 Z
1 Z1- Z2-
Y0.2
Y0.3
10 CLK1+ CLK2+
5 CLK1- CLK2-
9 DATA1+ DATA2+
14
D-sub15 pin
4 DATA1- DATA2-
14 +5VO1 +5VO2
15
5
10
15 GND1 GND2
12 Y0.0 Y0.2
11
1
6
11 Y0.1 Y0.3
13 COM0 COM1
14-7
A S S er i es Mo d u le Ma n ua l
Wiring
Pulse Input
• The NPN output encoder wiring
A S02HC-A
COM
14
0V +24V
Phase B A-
OUT B+
Phase Z B-
OUT
Z+
Z-
COM
+24V 0V
14-8
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
S SI encoder
Isolation
circu it +5V
+V
0V GND
CL K+ CLK+
CL K- CL K-
DATA+ DATA +
DATA- DATA-
Note:
If the power supply to the SSI encoder is non-5 VDC power supply, please supply corresponding external power based
on SSI encoder specifications of different vendors.
14-9
A S S er i es Mo d u le Ma n ua l
External Output
AS02 HC-A
14
*1:Loads or input points
*2:Use one single power supply for each COM port.
14-10
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
LED Indicators
Ch1 phase-A input ON: The phase-A input for channel 1 is active.
CH1 A Red
indicator OFF: The phase-A input for channel 1 is not active.
Ch1 phase-B input ON: The phase-B input for channel 1 is active. 14
CH1 B Red
indicator OFF: The phase-B input for channel 1 is not active.
1 4 - 11
A S S er i es Mo d u le Ma n ua l
Operation
Parameter Settings
Before using AS02HC-A to count, you need to set the following shown settings in ISPSoft-HWCONFIG. Set the
parameters and download the settings to AS02HC-A. Refer to section 14.4. for detailed ISPSoft-HWCONFIG operations.
Input
Tab Setting Value Setting Option
Interface
• 250 KHz
• 500 KHz
Clock Rate • 625 KHz
• 1 MHz (default)
• 1.25 MHz
CH 1 Setting Data Length 7~32 (default: 5)
Multi-Turn Length 0~32 (default: 12)
Multi-Turn MSB Location b0~b31 (default: b24)
Single-Turn Length 1~32 (default: 13)
Single-Turn MSB Location b0~b31 (default: b12)
SSI Input Status Length 0~15 (default: 0)
Status MSB Location b0~b31 (default: b0)
• None (default)
Parity Check • Even Parity Check
• Odd Parity Check
14-12
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
Input
Tab Setting Value Setting Option
Interface
• Reset Counter (default)
• Reset Counter + clear Yno
(Reset the current counter value and the
Z-Phase CH1 Z-Phase Function assigned Y output points from DHCCMP and
Function DHCCMPT instructions.)
Setting • Capture
• Gate Control
CH2 Z-Phase Function Same as CH1 Z-Phase Function
Filter Time 0~200; unit: 100us; default: 0
CH1 Ring Counter Overflow /
Default: disabled
Underflow Detect
CH1 SSI Zero Crossing Detect Default: disabled
Alarm Setting
CH2 Ring Counter Overflow /
Default: disabled
Underflow Detect
CH2 SSI Zero Crossing Detect Default: disabled
1. Pulse Type
Specify the pulse input type which can be A/B phase (2x), A/B phase (4x), CW/CCW or pulse + direction.
Parameter Setting Unit Default
A/B phase (2x),
A/B phase (4x),
Pulse Type - A/B phase (2x)
CW/CCW,
Pulse + direction
ϕA
ϕB
14-13
A S S er i es Mo d u le Ma n ua l
ϕA
ϕB
Counting
Value
ϕA
ϕB
CW/CCW
ϕA
ϕB
Pulse +
direction
14-14
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
2,147,483,647
-2,147,483,648
When the count value is beyond the allowed range, the counting persists internally in the hardware. The counter
returns to normal and the count value is refreshed when the internal count value comes back within the valid range.
But when the internal count value in the hardware is beyond the valid range of -2,147,483,648 to 2,147,483,647, the
counter state shows linear counter overflow or linear counter underflow, the counting stops and the internal count
value stops at 2,147,483,647 or -2,147,483,648. The counting can not continue until the count value overflow state of
the counter is cleared.
The methods to clear the states include resetting the counter through phase-Z inputs, executing Reset/Preset via
DHCCNT instruction, disabling DHCCNT instruction or changing the CPU from RUN to STOP.
Parameter Setting Unit Default
Max. counter value
0 ~ 2147483647 - 2147483647
(upper limit)
Min. counter value
-2147483648 ~ 0 - -2147483648
(lower limit)
Linear counter
overflow
2,147,483,647
Maximum
counter value
Minimum
counter value
-2,147,483,648
Linear counter
underflow
14-15
A S S er i es Mo d u le Ma n ua l
231-1 231-1
Ring counter
overflow
Counter
0 0
value
Ring counter
underflow
Counting up Counting down
-231 -231
There are two coding methods, Binary Code and Gray Code for SSI absolute encoder. The Binary Code is the
default coding method. If the Gray Code is selected, the gray-code position data (multi-turn and single-turn data)
transmitted back from the SSI encoder will be converted into the binary-code position data.
2. Clock Rate
The HWCONFIG software provides 5 clock rates for option including 250 kHz, 500 kHz, 625 kHz, 1 MHz and 1.25
MHz. Default: 1 MHz.
Set Multi-turn, Single-turn and Status Data start bit & length as well as Parity Check based on the specifications of
the used SSI absolute encoder. For SSI data format, 12ST, 13ST, 12 MT+13ST and User-Defined are provided for
option. See the descriptions as below for details.
MSB LSB
b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Single-turn data
14-16
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
MSB LSB
b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Single-turn data
MSB LSB
b24 b23 b22 b21 b20 b19 b18 b17 b16 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Users can define all parameters based on the illustration in the following diagram.
Data length
14-17
A S S er i es Mo d u le Ma n ua l
Note: For a multi-turn encoder, the multi-turn data and single-turn data should be next to each other without
additional data placed between them.
Item Setting Default
Data Length (bits) 7 ~ 31 25
Multi-Turn Data Length (bits) 0 ~ 31 12
Multi-Turn Data Start Bit B0 ~ b30 B24
Single-Turn Data Length (bits) 1 ~ 31 13
Single-Turn Data Start Bit B0 ~ b30 B12
Status Data Length (bits) 0 ~ 15 0
Status Data Start Bit B0 ~ b30 B0
No check, odd parity check, even
Parity Check No check
parity check
Parity Check Bit B0 ~ b30 B0
Parity Check Start Bit B0 ~ b30 B0
Parity Check Length (bits) 0 ~ 30 0
14 MSB LSB
b24 b23 b22 b21 b20 b19 b18 b17 b16 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Single-turn data
MSB LSB
b27 b26 b25 b24 b23 b22 b21 b20 b19 b18 b17 b16 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Status
Multi-turn data Single-turn data
data
14-18
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
MSB LSB
b17 b16 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
4. Monoflop Time
The Monoflop Time parameter determines the interval time between two SSI data frames. The correct position data
can be received as long as the setting value is greater than that specified for the connected encoder. The range is
set as follows. 14
Monoflop
Time
CLK
DATA
The parameter is used to prevent sudden errors occurring in reading absolute position values due to noise interference.
You can set the limit value for the variation between two consecutive SSI positions.
When the position change exceeds the set limit, the read position value is discarded, the present count value is not
refreshed and the error code is displayed in the counter status. When the position change is back within the set range,
the counting returns to normal and the error code is cleared.
When the maximum position variation limit is set to 0, the function is disabled and no check on the position change
will be done.
Parameter Setting Unit Default
Maximum Variation
0 ~ 2147483647 - 0 (Disabled)
Limit
14-19
A S S er i es Mo d u le Ma n ua l
6. Absolute Position
When the Absolute Position option is selected as the counter type, the counter value will show the absolute position
of the SSI absolute encoder within the range of 0 to 2resolution . The data information including single-turn data, multi-
turn data status, data and counting direction can be displayed independently based on the set data format. The offset
setting of the SSI absolute encoder can be modified as well. Refer to DHCCNT instruction for more.
7. Ring Counter
When Ring Counter is chosen as the counter type, AS02HC-A is used as a 32-bit ring counter by making two read
absolute position variations added up and the count value is changing cyclically in the range of -2147483648 to
2147483647. The counting value changes cyclically within the range of -2147483648 to 2147483647. The ring counter
value can be cleared to zero through phase Z. The DHCCNT instruction can also be used to clear and preset the
counter value. Refer to DHCCNT instruction for details.
The SSI Zero Crossing Detect function is enabled on the Alarm Setting tab page of the HWCONFIG software. The
alarm will appear if the absolute position of the SSI encoder crosses the zero position. The detection function can be
used for both the absolute position and ring counters. The timing for the zero crossing is illustrated in the following
table.
14
2R es ol utio n 2R es ol utio n
Zero Zero
crossing crossing
Counter
Absolute value
Position
counting up counting down
0 0
The absolute position of SSI encoder (original data)
The absolute position of SSI encoder (after offsetting)
14-20
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
231-1 231-1
2R es ol utio n 2R es ol utio n
Ring counter
31 31
-2 -2
14
9. Ring Counter Overflow / Underflow Detection
The Ring Counter Overflow/Underflow Detection function is enabled on the Alarm Setting tab page of the
HWCONFIG software. The alarm will appear as the counter value overflow/underflow occurs.
231-1 231-1
Ring counter
Counter overflow
value
0 0
Ring counter
underflow
Counting up
-231 -231
Counting down
For the SSI input counting, the rotation rate restriction is influenced by the SSI encoder resolution and monoflop time.
Use the corresponding formula in the following table to calculate the rotation speed of the SSI encoder.
Encoder type Rotation rate (RPM)
60
Single-turn encoder ± (tp: monoflop time, unit: us)
2×tp×10−6
60×2MT data length
Multi-turn encoder ± (tp: monoflop time, unit: us)
2×tp×10−6
14-21
A S S er i es Mo d u le Ma n ua l
See the reference values for the formula above in the following table.
Max. rotation rate Max. rotation rate
Monoflop time
of single-turn encoders of multi-turn encoders
(us)
(RPM) (RPM)
64 468750 468750 ✕ 2MT data length
4000 7500 7500 ✕ 2MT data length
8000 3750 3750 ✕ 2MT data length
12000 2500 2500 ✕ 2MT data length
16000 1875 1875 ✕ 2MT data length
20000 1500 1500 ✕ 2MT data length
24000 1250 1250 ✕ 2MT data length
28000 1071 1071 ✕ 2MT data length
32000 938 938 ✕ 2MT data length
36000 833 833 ✕ 2MT data length
40000 750 750 ✕ 2MT data length
14-22
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
DHCCAP
Set a capture method 14
(Count vlaue
Show captured count values
capture)
14-23
A S S er i es Mo d u le Ma n ua l
14
The impact of AS CPU Status on AS02HC-A
The following table lists the module execution states corresponding to AS CPU operation states of poweroff, and Run ->
Stop. After the AS CPU state switches from Stop to Run, the operation state of AS02HC-A module is controlled by the PLC
program.
Item Poweroff, CPU Run -> Stop
Y0.0~Y0.3 Reset to OFF
Phase Z Disabled
Counter The counting stops and counter state is cleared.
DHCCNT The instruction is disabled.
HCDO The instruction is disabled.
DHCCAP The instruction is disabled.
DHCCMP The instruction is disabled; MATCH1 and MATCH2 are cleared.
DHCCMPT The instruction is disabled and CurNo is cleared.
DHCMEAS The instruction is disabled.
14-24
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
14
14-25
A S S er i es Mo d u le Ma n ua l
3. After the scanning is completed, AS02HC-A will appear in the following window.
14
14-26
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
14
6. Click Download to download the configuration data. (The download can not be performed if the CPU is in RUN
state)
14-27
A S S er i es Mo d u le Ma n ua l
2. Double-click AS02HC module to check the firmware version and hardware version.
14
14-28
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
Online Mode
1. Click On-line Mode to enter the online mode.
2. Right-click AS02HC module and select Hardware Configuration or Module State from the context menu. Then the
error code information can be seen in the module state window and module error log can be seen in the diagnosis
area. 14
14-29
A S S er i es Mo d u le Ma n ua l
14
2. Click Import in the dialog box and select a dep file to save parameters.
14-30
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
Parameters
1. Select one input interface in CH1 Setting / CH2 Setting.
14
14-31
A S S er i es Mo d u le Ma n ua l
5. Alarm Setting
14
14-32
Ch a pt er 1 4 H i g h S pe ed C o un te r Mo d u le A S 02 HC
Troubleshooting
Error Codes
Error ERR
Description Counter action Remark
code LED
Counted result in the latched
16#1605 area is not retainable (major
error)
The counter The error alarm makes the CPU
Module settings in the latched
module stops stop the system. (The module need
16#1606 area is not retainable. (major ON
operating and be set to keep counting or stop for
error)
counting when an error occurs in the module:)
Module setting error
16#1607
(major error)
Linear counter:
Counter value overflow inside the
Counter overflow / underflow
16#1800 Linear counter: hardware
on CH1
Counting stops. Ring counter:
After the Ring Counter
Blinking
Ring counter: Overflow/Underflow Detect function
Counting is enabled in the Alarm Setting of
Counter overflow / underflow
16#1801
on CH2
continues. HWCONFIG, the alarm will appear
when the overflow or underflow
14
occurs.
Linear count exceeding the set The counting value The counting inside the hardware
16#1802
upper/lower limit on CH1 is fixed at the set persists. When the internal counter
Blinking max. counter value value is back within the valid range,
Linear count exceeding the set or the set min. the counter returns to normal and
16#1803
upper/lower limit on CH2 counter value. the counting value is refreshed.
The variation in relation to an
16#1804 SSI encoder position The counting value
The variation between two
exceeding the limit on CH1 is fixed at the most
Blinking consecutive SSI positions exceeds
The variation in relation to an recent correct count
the setting value.
16#1805 SSI encoder position value.
exceeding the limit on CH2
Encoder disconnection/ wiring
Abnormal SSI communication error/no power supply to the
16#1806 The counting value
on CH1 encoder/ data format error/parity
is fixed at the most
Blinking check setting error
recent correct count
Abnormal SSI communication (Error log will not appear unless five
16#1807 value.
on CH2 consecutive abnormal situations
occur.)
SSI absolute position cross After the SSI Zero Crossing Detect
16#1808
zero point on CH1 function is enabled on the Alarm
Setting tab page of the HWCONFIG
Blinking Counting continues.
SSI absolute position cross software, the alarm will appear as
16#1809
zero point on CH2 the absolute position of the SSI
encoder crosses the zero position.
14-33
A S S er i es Mo d u le Ma n ua l
Troubleshooting Procedure
Description Solution
Counted data is lost. Switch the module power OFF and ON again. The
Counted result in the latched area is not
error code is cleared by the system. Contact the factory if the problem
retainable (major error)
persists.
Module setting data is lost. Switch the module power OFF and ON
Module settings in the latched area is not
again. Download the HWCONFIG settings again to clear the error code.
retainable. (major error)
Contact the factory if the problem persists.
Module setting error Check if the setting in HWCONFIG is consistent with the actual
(major error) placement. Contact the factory if the problem persists.
Counter overflow / underflow on CH1 Check the counter result. If the alarm is not required, disable the alarm
output function in HWCONFIG. Use any of the followings to clear the
error code: clear, reset, preset the counter, restart the module, or
Counter overflow / underflow on CH2
execute DHCCNT instruction again.
Linear count exceeding the set upper/lower
Check the signal received by channel 1 and 2.
limit on CH1
Hardware counter is still counting; when the number is back within the
Linear count exceeding the set upper/lower
range of the maximum to the minimum, the error code will be cleared.
limit on CH2
The variation in relation to a SSI encoder
position exceeding the limit on CH1 Check if there is any interruption and check the device specification to
14 The variation in relation to a SSI encoder see if the offset setting is matching with the actual placement.
position exceeding the limit on CH2
Abnormal SSI communication on CH1 Check the execution of DHCCNT instruction. If it is parity check, check if
there is any interruption and check if the data format is correct. Check if
Abnormal SSI communication on CH2 the device wiring is secure, and if the encoder power supply is normal.
SSI absolute position cross zero point on Check the SSI absolute encoder specification and modify the setting
CH1 accordingly. If the alarm is not required, disable the alarm output function
in HWCONFIG. Use any of the followings to clear the error code: clear,
SSI absolute position cross zero point on
reset, preset the counter, restart the module, or execute DHCCNT
CH2
instruction again.
14-34
15
Chapter 15 High-Speed Analog Input
Module AS02ADH
Table of Contents
15.1 Overview
The AS02ADH module is a high-speed analog-to-digital module with two built-in channels. The conversion rate
of analog to digital signals can be as fast as 20 µs per channeI. Its two built-in channels are capable of sampling
simultanelously. The channels are designed as isolated to reduce interferences and ensure the accuracy of the
measured results. This chapter mainly introduces the specifications, functions and operation of the module.
15.1.1 Characteristics
(1) High-speed conversion
The conversion rate of analog to digital signals can be as fast as 20 µs per sampling cycle for two
channels simulanelously.
Conversion accuracy: The error range for both voltage input and current input is ±0.1% at ambient
temperature of 25° C.
Apart from the design of separating the digital and analog signals, the insulation between channels is
At the speed of 20 µs, high-speed recording works with external input points triggering to activate
recording the log continuously or just the execution points in real time.
ISPSoft with built-in HWCONFIG can be used to create the hardware module configuration so that users
can directly select the mode and parameters without spending time programming to set up the registers
The functions including recording log and peak value can be achieved through dedicated API
instructions.
15-2
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
Voltage: ≧2 MΩ
Input resistance value
Current: 250 Ω
Voltage: ±15 V
Absolute input range*1
Current: ±32 mA
Channel sampling
20 µs, 40 µs and 80 µs
Cycle*2
*1: If an input signal exceeds the absolute range, it might damage the channel.
*2: Two channels are in A/D conversion simulanelously.
*3: Logging function should be used with API instructions.
*4: Disconnecton detecton can only be used in the modes of 4 mA to 20 mA and 1V to 5 V.
15-3
A S S er i es Mo d u le Ma n ua l
Analog-to-Digital
Voltage Input
Conversion
Hardware Input
-20.24 mA to 20.24 mA -0.24 mA to 20.24 mA 3.81 mA to 20.19 mA
Limit*1
K-32384 K-384 K-384
Conversion Limit*2 to to to
K32384 K32384 K32384
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the
input signal is below the lower limit, it only shows the minimum value.
*2: If the input signal exceeds the hardware input limit, it also exceeds the digital conversion limit and a
conversion limit error appears. For example in the voltage input mode (4 mA to 20 mA), when the input
signal is 0 mA, exceeding the hardware upper limit, it also exceeds the conversion upper limit. The
module uses the upper limit value (-384) as the input signal and a conversion limit error appears.
15-4
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
Electrical specifications
An analog circuit is isolated from a digital circuit. The analog channels are
Rated voltage of
24 VDC
external input point
Rated currentof
5 mA
external input point
Resistance value of
3.9 kΩ
external input point
Hardware response
Weight 154g
15-5
A S S er i es Mo d u le Ma n ua l
15.2.2 Profile
38.2 95
02A DH 1
7 7
X0 .0
X0 .1 PWR
● ● ERR
2
98.3
X0.0
V1 + AG1 X0.1
88
I1 + VI1- AD1
SL D SL D
3
8 V2 + AG2
I2 + VI2-
AD2
● 2 4V
0V
4
9 5
6 75
35
Unit: mm
6 DIN Rail Clip Secures the module onto the DIN rail
8 Ground Clip
9 Label Nameplate
15-6
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
S/S X0.0
● ●
X0.0
V1+ AG1
X0.1 PWR
ERR
● ●
X0.0
I1+ VI1-
V1+ AG1 X0.1
V2+ AG2
V2+ AG2
I2+ VI2-
AD2
24V
I2+ VI2-
●
0V
● 24V
0V
15_
15-7
A S S er i es Mo d u le Ma n ua l
the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after
0: integer format
0 Format Setup R 0
1: floating point format
0: closed
1: -10 V to +10 V
1 Channel 1 mode setup
2: 0 V to 10 V
3: -5 V to +5 V
4: 0 V to 5 V
5: 1 V to 5 V
R/W 1
6: 0 mA to 20 mA
7: 4 mA to 20 mA
2 Channel 2 mode setup
8: -20 mA to +20 mA
_15 Note: when the format is set as floating point
TO instruction.
3 Channel 1 offset
Range: -32768 to +32767 R/W 0
4 Channel 2 offset
5 Channel 1 gain
Range: -32768 to +32767 R/W 1000
6 Channel 2 gain
7 0: moving average
Channel 1 filtering method
1: time average
2:50 Hz low-pass filter
3:60 Hz low-pass filter
4:1 kHz low-pass filter (for sampling cycle 40
µs and 80 µs only)
5:3 kHz low-pass filter (for sampling cycle 40 R/W 0
8 Channel filtering method µs and 80 µs only)
6:5 kHz low-pass filter (for sampling cycle 40
µs and 80 µs only)
7:7 kHz low-pass filter (for sampling cycle 40
µs only)
8:9 kHz low-pass filter (for sampling cycle 40
µs only)
15-8
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
0: 20 µs
2: 80 µs
Channel 1 maximum digital When the digital output value is out of the
12
output value range (-32384 to 32384), the digital clipping is
R/W 32384
Channel 2 maximum digital used to fix the exceeding value to the
13
maximum digital output value.
15_
output value
Channel 1 minimum digital When the digital output value is out of the
14
output value range (-32384 to 32384), the digital clipping is
R/W -32384
Channel 2 minimum digital used to fix the exceeding value to the
15
output value minimium digital output value.
15-9
A S S er i es Mo d u le Ma n ua l
value is -10.0 V.
25
The maximum scale range If the scale range for an analog to digital input
10.0
for channel 1 channel is 4 mA to 20 mA. It indicates the
26
maximum value is 20 mA and the minimum
value is 4 mA.
15-10
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
15.2.5 Functions
3 Average function Conversion values are averaged and filtered for each channel.
When the digital output value is out of the range (-32384 to 32384), the
Digital output value
7 digital clipping is used to fix the exceeding value to the maximum /
range
minimum digital output value.
Channel detection If an input signal exceeds the input hardware range, the module
8
and alarm produces an alarm or a warning. You can disable this function. 15_
Used with instruction ADLOG and DADLOG (API 1424) to save the
9 Logging function
analog curves for channels.
Peak records for Used with instruction ADPEAK and DADPEAK (API 1425) to save the
10
channels maximum and minimum value for channels.
Disconnection Disconnection detection only operates when the analog range is 4 mA–
11
Detection 20 mA or 1 V–5 V.
1 5 - 11
A S S er i es Mo d u le Ma n ua l
You can choose integer (16-bits, binary format) or floating-point format for the digital output format. If you
set the format to floating-point, you can set the scale range. The analog output mode of a channel has a
corresponding digital range. Digital values correspond to analog outputs sent by the module. For example,
if the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0, and the LSP
scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to +10 V, as the
Analog value
10 V
-10 V
Digital value
-10.0 10.0
Scale range
2. Calibration
_15 To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The
calibration range depends on the range of inputs that the hardware can receive. The formula is:
(𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼 × 𝐺𝐺𝐺𝐺𝐺𝐺𝐺𝐺)
𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂 = + 𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂
1000
Example:
A channel receives voltage inputs between -10.0 V to +10.0 V. The gain is 1000, and the offset is 0. The
corresponding value for the original signal -10.0 V to +10.0 V is -32000 to +32000. If you change the offset to -
100, the calibrated value for the original signal -10.0 V to +10.0 V becomes -31900 to +32100.
Original signals
1 0V S igna ls aft er t he ca libration
-10V
Voltag e (Y)
Analog s ig nal
15-12
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
3. Average function
There are two kinds of averages, including moving average and time average; the setting range is 1 to 1000.
When the setting value (sampling value) is 1, averaging is not executed. Moving average is to use the lastest
N number of read values to perform averaging and thus the latest digital output values can be obtained. Thus
in moving average, digital value updating cycle = sampling cycle. For time average, it is to accumulate
sampling cycle for a time set and then perform averaging on the total value. Thus in time average, digital value
updating cycle = sampling cycle x times. For example, when the sampling cycle is 20 µs and set the time to
4. Digital filtering
AS02ADH-A comes with various digital filters. You can use low-pass filter to screen out some specific
frequency or use band-pass filter to perform filtering on some specific range of frequency. According to the
sampling cycle, you choose an apporiate digital filter; refer the table below.
Sampling cycle
20 µs 40 µs 80 µs
Filter
15_
50 Hz low-pass filter ● ● ●
60 Hz low-pass filter ● ● ●
15-13
A S S er i es Mo d u le Ma n ua l
50 Hz low-pass filter
Magnitude(dB)
0 dB
-30 dB
-60 dB
50 100 150
Frequency(Hz)
60 Hz low-pass filter
Magnitude(dB)
0 dB
_15
-30 dB
-60 dB
60 120 180
Frequency(Hz)
15-14
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
Low-pass filter
Magnitude(dB)
-46 dB
15-15
A S S er i es Mo d u le Ma n ua l
Band-pass filter
0
Magnitude(dB)
Band-pass
Cutoff section section Cutoff section
-46 dB
Sampling Realization
fstop1 fpass1 fpass2 fstop2
cycle time
band-pass filter 80 µs 0.75 kHz 1.5 kHz 3 kHz 3.75 kHz 2.56 ms
_15 band-pass filter 80 µs 2.25 kHz 3 kHz 5.5 kHz 6.25 kHz 2.56 ms
band-pass filter 80 µs – – – – –
band-pass filter 80 µs – – – – –
15-16
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
5. Sampling cycle
The conversion rate of analog to digital signals can be set to 20 µs, 40 µs or 80 µs per sampling cycle for two
Hardware Firmware
Channel 1
Channel 1 Average /
CH1 ADC Digital output
Analog signal Digital filtering
value
Sampling
cycle setup
for channels
Channel 2
Channel 2 Average /
CH2 ADC Digital output
Analog signal Digital filtering
value
15_
CH2 ADLOG
X0.1 Input point Record data
Digital input point Digital filtering instruction
Example:
The conversion rate of analog to digital signals used in this example is 20 µs per sampling cycle for two
channels simultaneously.
20us
0 t
CH1 Ana log input CH2 Ana log input
CH1 ADC re sul t CH2 ADC re sul t
15-17
A S S er i es Mo d u le Ma n ua l
Input point filtering is available to reduce the chance of being triggered by mistake or interferences: you can
set the digital filtering cycle to 0 (disabled), 100 µs, 200 µs, 500 µs according to your requirement.
Digital filtering /
sampling cycle
(20 µs)
Digital input
point –
pin signal
After filtered,
the positioning
of digital input
point
When the digital output value is out of the range (-32384 to 32384), the digital clipping is used to fix the
_15
Digital
output value
-upper limit
Digital
output value
-lower limit
If an input signal exceeds the allowable hardware input range, an error message appears and error LED starts
to blink. You can disable this function in the setting of Channel Detect and Alarm so that the module does not
produce an alarm or a warning when the input signal exceeds the input range.
15-18
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
9. Logging function
AS02ADH can record 10000 piece of data, if used with instructions ADLOG and DADLOG (API 1424), you
can set up the parameters, enable or disable recording for channels. Refer to section 6.15 (API14 Module
DADLOG
En
Group Datalog
Module CurNo When the output value is in floating-point format, you
DADLOG ChNo Cmplt need to use this 32-bit instruction.
(32-bit) The fuctions for 32-bit instruciton are the same as they
Mode Error
are stated for 16-bit instruction above.
Period ErrCode
Points
15_
Postrig
AS02ADH-A can record the shortest time (20 µs) of data and the longest time (2.56 s) of data. It can also
record by external input point triggering or as every single log recording. Up to 2000 pieces of data can be
recorded. And there are four recording modes are available.
(1) Fixed period mode: Set Mode=0, the data recording would be performed according to the pre-defined
record period when EN switches to ON. After the recording of a specified number of log points is
complete, the Cmplt flag would be set to High automatically.
Example:
Set Points = 2000
1 2
0 t
EN
CurNo 0 1~1999 2000 0~1999 2000
Cmplt
15-19
A S S er i es Mo d u le Ma n ua l
(2) Fixed period + Trigger start mode: Set Mode=1 and switch instruction EN to ON before the recording
starts. When a trigger signal is detected at the external input point, start recording based on the pre-
defined record period. And the Cmplt flag is set to High automatically when completed. Before the
recording is complete, any operation at the external input points does NOT affect the proceeding of
record. When the recording of log points is complete and the Cmplt flag is High, trigger the external
input points again to start a new cycle of recording; the instruction EN does NOT required to be
turned OFF and then ON again to start another new recording.
Example:
Set Points = 2000, the trigger timing for the external input point is set to rising-edge triggered.
1 2
0 t
_15 EN
External input trigger
The feature of Fixed period + Trigger Start is similar to Fixed period. But the start timing of recording
in Fixed period mode would be delayed as a result of PLC scan time and module communication
time, which is shown in the following illustration. It is assumed that M0 is the device to control EN of
ADLOG instruction. We can see when M0 switches from OFF to ON, the module does not start
recording immediately but with a slight delay.
0 t
Fixed period
M0
Recording Starts
15-20
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
(3) Point Logging mode: Set Mode=2, turn the instruction EN to ON before the recording starts. One log
point would be recorded for each triggering at external input point until it reaches the pre-defined
point number, Cmplt flag would set to High automatically. If you need to the recording to be continued
after the Cmplt flag is set to High, execute the instruction again.
Record The signal source corresponding to the external input points
Example:
Set Points = 2000, the trigger timing for external input point is set to rising-edge triggered.
2000 th point
2nd poin t 1999 th point
1st point rd
3 poin t 3rd poin t
1st poin t
0 t
EN
Exte rnal input trig ger
(4) Fixed period + Trigger position Assign mode: Set Mode=3 and set parameters Points and PostTrg 15_
according to your requirements. This mode is to trigger at the external input point and record the pre-
defined number of log points before and after the triggering occurs. When using EN to turn on this
mode, AS02ADH-A would start waiting for signals to be triggered at external input. And the sampling
would start right after, until it reaches the pre-defined point number, and then Cmplt flag would set to
High automatically. The value in CurNo is 0 before triggered, and after triggered, the modules start
to send the before-triggered data log to the PLC CPU . Therefore the value of CurNo would catch up
to the number of accumulated log points.
Record The signal source corresponding to the external input points
15-21
A S S er i es Mo d u le Ma n ua l
Example
Set Mode=3, Points = 2000, and PostTrg = 1500 so the position of point 501 (Points – PostTrg)would be the
first record after an external trigger signal is detected.
1 2
The number of all records(Points):2000 The number of all records(Points):2000
DADPEAK
En
When the output value is in floating-point format, you
Group MAX
DADPEAK need to use this 32-bit instruction.
(32-bit) Module MIN The fuctions for 32-bit instruciton are the same as they
ChNo Error are stated for 16-bit instruction above.
ErrCode
15-22
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
15.2.6 Wiring
Precautions
To ensure the analog-to-digital module functions well and reliably, the external wiring must prevent noise.
(1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the
(2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load that is
not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable, or a cable
(4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the
(5) Use single-core cables or twin-core cables in a diameter of 24 AWG–22 AWG with pin-type connectors
smaller than 1 mm. Use only copper conducting wires that can resist temperatures above 60° C-75° C.
Four-wire connection (active transducer): the transducer uses an independent power supply so
do not connect it to the same power circuit as the analog input module.
(7) Note: use cables with the same length (less than 200 m) and use wire resistance of less than 100 ohm.
S /S X0.0
24VD C 24VD C
5 mA 5 mA
X 0 .0
S/ S
15-23
A S S er i es Mo d u le Ma n ua l
+2 4V
+ V1+ 25 0Ω CH1
*3 I1 + INA 1 A DC1
0V
- VI1 -
AG 1 1 MΩ
SL D *5
AG 1
A G1
Current input
*4
-20mA ~+ 20 mA Sh ielded c able *1 CHX A G2
1 MΩ
+ *2 V 2+ 250 Ω
+ 24 V CH2
I 2+ INA 2 A DC2
- VI 2-
0V AG 2
1 MΩ
SL D *5
A G2
A G2
+1 5V
24 V DC/ DC
0V Co nv erte r 1 -15V AG 1
+1 5V
DC/ DC
Conv ert er 2
-1 5V A G2
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–2) must be short-circuited.
_15
*3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor
*4. The wording “CHX” indicates that very channel can operate with the wiring presented above.
*5. If the environment is severe or there is interferences in 24 V pwer supply, short-circuit AGn (n=1-2) and the
input signal.
15-24
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
3-wired
Voltage input
-10V~ +10 V Sh ielde d cable *1
*4
+ 24V CHX A G1
+ 1MΩ
V1+
- 2 50 Ω CH1
0V I 1+ INA 1 ADC1
VI 1-
AG 1
1MΩ
S LD *5
A G1 A G1
Current input
-20mA ~+2 0mA Sh ielde d cable *1 *4
CHX A G2
1MΩ
+ 24V *2 V2+
+ 25 0Ω CH2
I2+ I NA2 A DC2
0V
- V I2-
A G2
*5 1MΩ
S LD
A G2
AG 2
+ 15V
2 4V DC/DC
0V Conv ert er 1 -15V AG 1
+ 15V
DC/DC
Con ve rter 2
-15V AG 2
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–2) must be short-circuited.
15_
*3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor
*4. The wording “CHX” indicates that very channel can operate with the wiring presented above.
*5. If the environment is severe or there is interferences in 24 V pwer supply, short-circuit AGn (n=1-2) and the
input signal.
15-25
A S S er i es Mo d u le Ma n ua l
2-wired
Current inp ut
+ 24V 4mA ~+2 0mA
+ S hield ed ca ble *1 *4
CHX A G1
1MΩ
V1+
- *2 2 50 Ω CH1
I 1+ I NA1 ADC1
VI 1-
A G1
0V S LD *5 1MΩ
A G1 A G1
Current inp ut
+ 24V 4mA~ +2 0mA
+ *4
S hield ed ca ble *1 CHX A G2
1MΩ
*2 V2+
- I2+
25 0Ω
A DC2
CH2
I NA2
V I2-
A G2
0V S LD *5 1MΩ
A G2
AG 2
+ 15V
2 4V DC/DC
0V Conv ert er 1 -15V A G1
+ 15V
DC/DC
Con ve rter 2
-15V AG 2
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–2) must be short-circuited.
_15
*3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor
*4. The wording “CHX” indicates that very channel can operate with the wiring presented above.
*5. If the environment is severe or there is interferences in 24 V pwer supply, short-circuit AGn (n=1-2) and the
input signal.
15-26
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
Printed
Function Description
as
15-27
A S S er i es Mo d u le Ma n ua l
_15
15-28
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
(3) After the scanning is completed, AS02ADH will appear in the following window.
15_
15-29
A S S er i es Mo d u le Ma n ua l
(6) Click Download to download the configuration data. (The download can not be performed if the CPU is in
RUN state)
_15
15-30
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
(2) Double-click AS02ADH module to check the firmware version and hardware version.
15_
15-31
A S S er i es Mo d u le Ma n ua l
(2) Right-click the module and click Module State or Diagnosis. You can find digital output value and error
_15 codes in Module State and the error log can be found in Diagnosis.
15-32
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
15_
15-33
A S S er i es Mo d u le Ma n ua l
(1) Click Export in the dialog box to save the current parameters as a dep file (.dep).
_15
(2) Click Import in the dialog box and select a dep file to save parameters.
15-34
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
15.3.5 Parameters
(1) Set up the parameters.
15_
15-35
A S S er i es Mo d u le Ma n ua l
_15
15-36
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
15_
15-37
A S S er i es Mo d u le Ma n ua l
_15
15-38
Ch a pt er 1 5 H i g h- s p e ed I n pu t M od u le A S 0 2 AD H
15.4 Troubleshooting
15.4.1 Error Codes
Run: Blinking
16#1605 Hardware failure ON
Stop: OFF
Run: Blinking
16#1606 The parameter setting is not consistent. (alarm) ON
Stop: OFF
Run: Blinking
16#1608 The factory calibration is abnormal. (alarm) ON
Stop: OFF
Run: Blinking
16#1802 Hardware failure Blinking
Stop: OFF
Run: Blinking
16#1804 The factory calibration is abnormal. Blinking
Stop: OFF
15_
The signal received by channel 1 exceeds the range of inputs
16#1808
that the hardware can receive. Run: Blinking
Blinking
The signal received by channel 2 exceeds the range of inputs Stop: OFF
16#1809
that the hardware can receive.
Blinking once
or twice and
after 2
- When power-on, the module is not detected by CPU module. OFF
seconds, it
blinks
repeatedly
15-39
A S S er i es Mo d u le Ma n ua l
Description Procedure
Internal error
Contact the factory.
The factory calibration is abnormal.
When power-on, the module is not detected by Check if the connection between module and CPU
_15
15-40