Delta Ia-Mds Vfd-El-W Um en 20200729

Download as pdf or txt
Download as pdf or txt
You are on page 1of 197

Industrial Automation Headquarters

Delta Electronics, Inc.


Taoyuan Technology Center
No.18, Xinglong Rd., Taoyuan District,
Taoyuan City 33068, Taiwan
TEL: 886-3-362-6301 / FAX: 886-3-371-6301

Asia EMEA
Delta Electronics (Shanghai) Co., Ltd. Headquarters: Delta Electronics (Netherlands) B.V.
No.182 Minyu Rd., Pudong Shanghai, P.R.C. Sales: [email protected]
Post code : 201209 Marketing: [email protected]
TEL: 86-21-6872-3988 / FAX: 86-21-6872-3996 Technical Support: [email protected]
Customer Service: 400-820-9595 Customer Support: [email protected]
Service: [email protected]
Delta Electronics (Japan), Inc. TEL: +31(0)40 800 3900

Industrial Automation Sales Department BENELUX: Delta Electronics (Netherlands) B.V.


2-1-14 Shibadaimon, Minato-ku De Witbogt 20, 5652 AG Eindhoven, The Netherlands
Tokyo, Japan 105-0012 Mail: [email protected]
TEL: 81-3-5733-1155 / FAX: 81-3-5733-1255 TEL: +31(0)40 800 3900

DACH: Delta Electronics (Netherlands) B.V.


Delta Electronics (Korea), Inc.
Coesterweg 45, D-59494 Soest, Germany
Mail: [email protected]
1511, 219, Gasan Digital 1-Ro., Geumcheon-gu,
TEL: +49(0)2921 987 0
Seoul, 08501 South Korea
TEL: 82-2-515-5305 / FAX: 82-2-515-5302 France: Delta Electronics (France) S.A.
ZI du bois Challand 2, 15 rue des Pyrénées,
Delta Energy Systems (Singapore) Pte Ltd. Lisses, 91090 Evry Cedex, France
4 Kaki Bukit Avenue 1, #05-04, Singapore 417939 Mail: [email protected]
TEL: 65-6747-5155 / FAX: 65-6744-9228 TEL: +33(0)1 69 77 82 60
Delta Electronics (India) Pvt. Ltd. Iberia: Delta Electronics Solutions (Spain) S.L.U
Plot No.43, Sector 35, HSIIDC Gurgaon, Ctra. De Villaverde a Vallecas, 265 1º Dcha Ed.
PIN 122001, Haryana, India Hormigueras – P.I. de Vallecas 28031 Madrid
TEL: 91-124-4874900 / FAX : 91-124-4874945 TEL: +34(0)91 223 74 20
Carrer Llacuna 166, 08018 Barcelona, Spain
Delta Electronics (Thailand) PCL.
909 Soi 9, Moo 4, Bangpoo Industrial Estate (E.P.Z), Mail: [email protected]
Pattana 1 Rd., T.Phraksa, A.Muang, Italy: Delta Electronics (Italy) S.r.l.
Samutprakarn 10280, Thailand Via Meda 2–22060 Novedrate(CO)
TEL: 66-2709-2800 / FAX : 662-709-2827 Piazza Grazioli 18 00186 Roma Italy
Mail: [email protected]
Delta Electronics (Australia) Pty Ltd. TEL: +39 039 8900365
Unit 20-21/45 Normanby Rd., Notting Hill Vic 3168, Australia
TEL: 61-3-9543-3720 Russia: Delta Energy System LLC

Americas 17 121357 Moscow Russia


Mail: [email protected]
Delta Electronics (Americas) Ltd.
TEL: +7 495 644 3240
P.O. Box 12173, 5101 Davis Drive, Turkey: Delta Greentech Elektronik San. Ltd. Sti. (Turkey)
Research Triangle Park, NC 27709, U.S.A. Şerifali Mah. Hendem Cad. Kule Sok. No:16-A
TEL: 1-919-767-3813 / FAX: 1-919-767-3969 34775 Ümraniye – İstanbul
Mail: [email protected]
Delta Greentech (Brasil) S/A TEL: + 90 216 499 9910

Rua Itapeva, 26 – 3˚ Andar - Bela Vista GCC: Delta Energy Systems AG (Dubai BR)
CEP: 01332-000 – São Paulo – SP - Brasil P.O. Box 185668, Gate 7, 3rd Floor, Hamarain Centre
TEL: 55-11-3530-8643 / 55-11-3530-8640 Dubai, United Arab Emirates
Mail: [email protected]
Delta Electronics International Mexico S.A. de C.V. TEL: +971(0)4 2690148

Egypt + North Africa: Delta Electronics


Colonia La Loma, CP 54060 Unit 318, 3rd Floor, Trivium Business Complex, North 90 street,
Tlalnepantla, Estado de México New Cairo, Cairo, Egypt
TEL: 52-55-3603-9200 Mail: [email protected]

DELTA_IA-MDS_VFD-EL-W_UM_EN_20200729
*We reserve the right to change the information in this catalogue without prior notice.
Copyright notice
©Delta Electronics, Inc. All rights reserved.
All information contained in this user manual is the exclusive property of Delta Electronics Inc.
(hereinafter referred to as "Delta ") and is protected by copyright law and all other laws. Delta retains the
exclusive rights of this user manual in accordance with the copyright law and all other laws. No parts in
this manual may be reproduced, transmitted, transcribed, translated or used in any other ways without
the prior consent of Delta.

Limitation of Liability
The contents of this user manual are only for the use of the AC motor drives manufactured by Delta. Except
as defined in special mandatory laws, Delta provides this user manual “as is” and does not offer any kind
of warranty through this user manual for using the product, either express or implied, including but not
limited to the following: (i) this product will meet your needs or expectations; (ii) the information contained
in the product is current and correct; (iii) the product does not infringe any rights of any other person. You
shall bear your own risk to use this product.

In no event shall Delta, its subsidiaries, affiliates, managers, employees, agents, partners and licensors
be liable for any direct, indirect, incidental, special, derivative or consequential damages ( including but
not limited to the damages for loss of profits, goodwill, use or other intangible losses) unless the laws
contains special mandatory provisions to the contrary.

Delta reserves the right to make changes to the user manual and the products described in the user
manual without prior notice and afterwards.
Preface

Thank you for choosing DELTA’s sensorless vector control compact drive VFD-EL-W series. The VFD-EL-W series
are manufactured with high-quality components and materials and incorporate the latest microprocessor
technology available.
Use this manual for the AC Motor Drive installation, parameter setting, troubleshooting, and daily maintenance. To
guarantee safe operation, read the following safety guidelines before connecting power to the AC motor drive.
Keep this user manual at hand and distribute to all users for reference.
To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor drive are to do
installation, start-up and maintenance. Always read this manual thoroughly before using VFD-EL-W series AC
Motor Drive, especially the DANGER ,WARNING and CAUTION notes. Failure to comply may result in personal
injury and equipment damage. If you have any questions, please contact your dealer.

PLEASE READ PRIOR TO INSTALLATION FOR SAFETY.

 Disconnect AC input power before connecting any wiring to the AC motor drive.
 Even if the power has been turned off, a charge may still remain in the DC-link
capacitors with hazardous voltages before the indicator on the digital keypad is
OFF. Do NOT touch the internal circuits and components.
 There are highly sensitive CMOS IC components on the motor drive’s printed
circuit boards. These components are especially sensitive to static electricity.
Take anti-static measure before touching these components or the circuit boards.
 Never modify the internal components or wiring.
 Ground the AC motor drive by using the ground terminal. The grounding method
must comply with the laws of the country where the AC motor drive is to be
installed.
 Use the VFD-EL-W series to control only variable speed three-phase induction
motors. The VFD-EL-W is NOT for controlling one-phase motors or for other
purposes.
 Do NOT use the VFD-EL-W series for life support equipment or any life safety
situation.
 To prevent personal injury, keep children and unqualified people away from the
equipment.

 Never connect the AC motor drive output terminals U/T1, V/T2, and W/T3 directly
to the AC mains circuit power supply.
 DO NOT use a Hi-Pot test for internal components. The semiconductors used in
the AC motor drive are easily damaged by high-voltage.
 Even if the three-phase AC motor is stopped, a charge with hazardous voltages
may still remain in the main circuit terminals of the AC motor drive
 Only qualified persons are allowed to install, wire and maintain the AC motor
drives.
 When the AC motor drive uses the external terminal as the source of the
operation command, the motor may run immediately after applying power. At this
time, it is dangerous if people are at the scene.

i
 DO NOT install the AC motor drive in a location subject to high temperature, direct
sunlight, high humidity, or splash of water droplets.
 Use the AC motor drives only within specification. Failure to comply may result in
fire, explosion or electric shock.
 When the motor cable between AC motor drive and motor is too long, the
insulation layer of the motor may be damaged. Use a frequency inverter-duty
motor or add an AC output reactor to prevent damage to the motor. Refer to
Appendix B “Reactor” for details.
 The rated voltage of power system to install motor drives is listed below. Ensure
that the installation voltage is in the correct range when installing a motor drive.
1. For 230V models, the range is between 180V~264V
2. For 460V models, the range is between 342V~528V
 The performance of electrolytic capacitor will degrade if it is not charged for a long
time. It is recommended to charge the drive which is stored in no charge condition
every 2 years for 3~4 hours to restore the performance of electrolytic capacitor in
the motor drive. Note: When power up the motor drive, use adjustable AC power
source (ex. AC autotransformer) to charge the drive at 70%~80% of rated voltage
for 30 minutes (do not run the motor drive). Then charge the drive at 100% of rated
voltage for an hour (do not run the motor drive). By doing these, restore the
performance of electrolytic capacitor before starting to run the motor drive. Do
NOT run the motor drive at 100% rated voltage right away.
 Pay attention to the following precautions when transporting and installing this
package (including wooden crate and wood stave)
1. If you need to deworm the wooden crate, do NOT use fumigation or you will
damage the drive. Any damage to the drive caused by using fumigation voids
the warranty.
2. Use other methods, such as heat treatment or any other non-fumigation
treatment, to deworm the wood packaging material.
3. If you use heat treatment to deworm, leave the packaging materials in an
environment of over 56°C for a minimum of thirty minutes.

 If the motor drive generates leakage current goes over AC 3.5 mA or over DC 10
mA on a protective earth (PE) conductor, the PE conductor must be a copper wire
with a cross section of minimum 10mm2 or an aluminum wire with a cross section
of at least 16mm2. You can also install an earth-leakage circuit breaker
(ELCB).

NOTE

 In order to explain the details of the product, the outer casing or the safety cover is removed and described as
a figure. During operation, it is necessary to install the casing and wiring in accordance with the regulations,
and operate according to the instructions to ensure safety.
 The figures shown in the manual, for the convenience of explanation, may be slightly different from the
product. This is normal and does not affect your customer rights.
 The content of this manual may be revised without prior notice. Please consult our distributors or download
the latest version at http://www.deltaww.com/iadownload_acmotordrive

ii
Table of Contents

Preface ……………………………………………………………………………………………………………………….. i

Table of Contents …………………………………………………………………………………………………………... iii

Chapter 1 Introduction …………………………………………………………………………………………………… 1-1


1.1 Receiving and Inspection ……………………………….…………………………………………….…………… 1-1
1.1.1 Nameplate Information ………………………………………………………………………….…...………. 1-1
1.1.2 Model Name …………………………………………………………………………..……………….……... 1-2
1.1.3 Serial Number ………………………………………………………………………………………………... 1-2
1.1.4 Drive Frames and Appearances …………………………………….…………………………….…..…… 1-3
1.2 Preparation for Installation and Wiring …………………………………………………………….……..………. 1-7
1.2.1 Ambient Conditions ………………………………………………………………………………...………… 1-7
1.3 Dimensions …………………………………………………………………….……………………….…………1-11

Chapter 2 Installation and Wiring ………………………………………………………………….…………………… 2-1


2.1 Wiring ………………………………………………………………………………………………………………… 2-2
2.2 External Wiring ……………………………………………………………………………………………………… 2-6
2.3 Main Circuit …………………………………………………………………………………………………………. 2-7
2.3.1 Main Circuit Connection …………………………………………………………………………………….. 2-7
2.3.2 Main Circuit Terminals ………………………………………………………………………………………. 2-8
2.4 Control Terminals ………………………………………………………………………………………………….. 2-9
2.5 NPN / PNP Mode …………………………………………………………………………………………………. 2-12

Chapter 3 Keypad and Start Up ………………………………………………………………………………………… 3-1


3.1 Description of the Digital Keypad …………………………………………………………………………………. 3-2
3.2 Operation Method …………………………………………………………………………………………………... 3-5
3.3 Trial Run ……………………………………………………………………………………………………………... 3-7

Chapter 4 Parameters …………………………………………………………………………………………………….. 4-1


4.1 Summary of Parameter Settings ………………………………………………………………………………….. 4-2
4.2 Parameter Settings for Applications …………………………………………………………………………….. 4-23
4.3 Description of Parameter Settings ………………………………………………………………………………. 4-27

Chapter 5 Troubleshooting ……………………………………………………………………………………………… 5-1


5.1 Over-Current (oc) …………………………………………………………………………………………………… 5-2
5.2 Over-Voltage (ov) …………………………………………………………………………………………………… 5-3
5.3 Low Voltage (Lv) ……………………………………………………………………………………………………. 5-4
5.4 Overheat (oH1) ……………………………………………………………………………………………………… 5-5
5.5 Overload (oL) ……………………………………………………………………………………………………….. 5-6
5.6 Keypad Display is Abnormal ………………………………………………………………………………………. 5-7
5.7 Phase Loss (PHL) ………………………………………………………………………………………………….. 5-7
5.8 Motor Does Not Run ……………………………………………………………………………………………….. 5-8
5.9 Motor Speed Cannot be Changed ……………………………………………………………………………….. 5-9
iii
5.10 Motor Stalls During Acceleration ………………………………………………………………………………. 5-10
5.11 The Motor Does Not Run as Expected ………………………………………………………………………... 5-10
5.12 Electromagnetic/Induction Noise ………………………………………………………………………………. 5-11
5.13 Operating Environment Condition ……………………………………………………………………………… 5-11
5.14 Affecting Other Machines ……………………………………………………………………………………….. 5-12

Chapter 6 Fault Code Information and Maintenance ……………………………………………………………….. 6-1


6.1 Fault Code Information …………………………………………………………………………………………….. 6-2
6.2 Maintenance and Inspections ……………………………………………………………………………………... 6-6

Appendix A Specifications ……………………………………………………………………………………………… A-1

Appendix B Accessories ………………………………………………………………………………………………… B-1


B.1 Non-fuse Circuit Breaker Chart …………………………………………………………………………………… B-1
B.2 Reactor ……………………………………………………………………………………………………………… B-2
B.2.1 AC Reactor …………………………………………………………………………………………………… B-2
B.2.2 Zero Phase Reactor ………………………......................…………………………………………………. B-4
B.3 Digital Keypad ……………………………………………………………………………………………………… B-5
B.3.1 VFD-PU06 ……………………………………………………………………………………………………. B-5
B.3.2 VFD-PU08 and VFD-PU08V…………………………………………………………………………………B-8
B.4 Optional Fan Kit ……………………………………………………………………………………………………B-10

Appendix C How to Select the Right AC Motor Drive ……………………………………………………………… C-1


C.1 Capacity Formulas ………………………………………………………………………………………………… C-2
C.2 General Precaution ………………………………………………………………………………………………... C-4
C.3 How to Choose a Suitable Motor ………………………………………………………………………………… C-5

Firmware V2.00
Application
Issue Date 2020/07

iv
This page intentionally left blank

v
Chapter 1 Introduction

1.1 Receiving and Inspection


1.2 Preparation for Installation and Wiring
1.3 Dimensions

Keep the AC motor drive in the shipping carton or crate before installation. In order to retain the warranty
coverage, properly store the AC motor drive when it is not to be used for an extended period of time. The proper
storage conditions are listed below.

CAUTION!

1. Store in a clean and dry location without any direct sunlight or corrosive fumes.
2. Store in an ambient temperature range between -20°C to +60°C.
3. Store in a relative humidity range between 0% to 90% and non-condensing environment.
4. DO NOT place directly on the ground. If the surrounding environment is humid, you should put a desiccant in
the carton or crate.
5. DO NOT store in an area with rapid changes in temperature that may cause condensation or frost to form.
6. If the AC motor drive is stored for more than three months, the temperature should not be higher than 30°C.
Storage for longer than one year is not recommended; it could result in the degradation of the electrolytic
capacitors.
7. When the AC motor drive is not used for long time after installation in an environment with humidity and dust,
it’s best to move the AC motor drive to a better environment as stated above.

1.1 Receiving and Inspection


This VFD-EL-W AC motor drive has gone through rigorous quality control tests at the factory before shipment.
After receiving the AC motor drive, please check for the following:
 Inspect the unit to ensure it was not damaged during shipment.
 Make sure that the part number indicated on the nameplate matches the part number of your order.
1.1.1 Nameplate Information
Example for 1 HP/0.75 kW three-phase 230V AC motor drive

1-1
Chapter 1 Introduction  VFD-EL-W

1.1.2 Model Name

VFD 007 EL 21 W -1
Type of packing
-1: Individual package
N/A: 12pcs/carton

W: Minimal and
Economic
Input voltage
21: 230V, 1-phase
43: 460V, 3-phase
EL series
Applicable motor capacity:
002: 0.25HP (0.2kW)
004: 0.5HP (0.4kW)
007: 1HP (0.75kW)
015: 2HP (1.5kW)
022: 3HP (2.2kW)
040: 5.5HP (4.0kW)

Product name
Variable Frequency Drive

1.1.3 Serial Number

007EL21W1 H 20 11 0001
Production number

Production week
20: year 2020
Production year
H: Hosur, W: Wujiang Production factory
230V, 1-phase, 1HP (0.75kW) Model name
Without 1: VFDxxxELxxW
With 1: VFDxxxELxxW-1

If the nameplate information does not match your purchase order or if there are any problems,
please contact your distributor.

1-2
Chapter 1 Introduction  VFD-EL-W

1.1.4 Drive Frames and Appearances

Frame A1

digital keypad
input terminals
R/L1, S/L2, T/L3 choose NPN/PNP

frequency control knob choose ACI/AVI

control terminals
digital keypad
RS485 terminal
(RJ45)

control board cover

output terminals
U/T1, V/T2, W/T3
grounding terminal

Frame A2

input terminals digital keypad


(R/L1, S/L2, T/L3)
choose NPN/ PNP
frequency control knob choose ACI/ AVI

control terminals
digital keypad
RS485 terminal
(RJ45)

control board cover

output terminals
(U/T1, V/T2, W/T3)
grounding terminal

1-3
Chapter 1 Introduction  VFD-EL-W

Frame B

digital keypad
input terminals
(R/L1, S/L2, T/L3) choose NPN/ PNP

frequency choose AVI/ ACI


control knob
control terminals
digital keypad
RS485 terminal
case (RJ45)

control board
cover

output terminals
(U/T1, V/T2, W/T3)

grounding terminal

1-4
Chapter 1 Introduction  VFD-EL-W

RFI Jumper Location

RFI jumper
R/L1
S/L2
T/L3
Grounding

NOTE
If it is required by the grounding system or the current leakage is too big and causes tripping, you can
remove RFI jumper which is near the input terminals (R/L1, S/L2, T/L3) by loosing screws. Once you
remove the RFI jumper, retighten the screws to keep good grounding to prevent electric shock.

Frame Power Range Models

0.25 - 1hp VFD002EL21W(-1), VFD004EL21W(-1) / 43W(-1),


A1
(0.2 - 0.75kW) VFD007EL21W(-1) / 43W(-1),

A2 2 HP (1.5 kW) VFD015EL43W(-1)

B 2–5.5 HP (1.5–4 kW) VFD015EL21W(-1), VFD022EL21W / 43W(-1), VFD040EL43W(-1)

RFI Jumper
(1) In the drive there are Varistor / MOVs, which are connected from phase to phase and from phase to ground, to
protect the drive against mains surges or voltage spikes.
Because the Varistors / MOVs from phase to ground are connected to ground via the RFI jumper, the
protection will be ineffective when the RFI jumper is removed.
(2) In the models with built-in EMC filter the RFI jumper connects the filer capacitors to ground to form a return
path for high frequency noise to isolate the noise from contaminating the main power. Removing the RFI
jumper strongly reduces the effect of the built-in EMC filter.
Isolating main power from ground:
When the power distribution system for the motor drive is a floating ground system (IT) or an asymmetric
ground system (TN), you must remove the RFI jumper. Removing the RFI jumper disconnects the
internal capacitors from ground to avoid damaging the internal circuits and to reduce the ground leakage
current.
Important points regarding ground connection
 Do not remove RFI jumper while the power is ON.
 Make sure that main power is OFF before removing the RFI jumper.
 Removing the RFI jumper also cuts off the built-in EMC filter capacitors. Compliance with the EMC
specifications is no longer guaranteed.
If you remove the RFI jumper, you remove the reliable electrical isolation. In other words, all controlled inputs and
outputs become low-voltage terminals with basic electrical isolation. Also, when you remove the internal RFI
jumper, the motor drive is no longer electromagnetic compatible (EMC).

 Do not remove the RFI jumper if the main power is a grounded power system to make EMC filter effective
 You must remove the RFI jumper when conducting high voltage tests. When conducting a high voltage test for
the entire facility, disconnect the main power and the motor if the leakage current is too high.
 To prevent damage to the drive, you must remove the RFI jumper connected to ground if the AC motor drive is
installed on an ungrounded power system or a high resistance-grounded (greater than 30 Ω) power system or a
corner grounded TN system.

1-5
Chapter 1 Introduction  VFD-EL-W

Remove the control board cover Remove cooling fan:


As shown in Step 1 below, gently press the control To remove the cooling fan of Frame B, gently release the
board cover. Then, clips on both sides of the cooling fan.
as shown in Step 2, pull it down slowly to remove it.

Step 1

Step2

1-6
Chapter 1 Introduction  VFD-EL-W

1.2 Preparation for Installation and Wiring


1.2.1 Ambient Conditions
Install the AC motor drive in an environment with the following conditions.
-10°C to 50°C (VFD007EL21W & VFD007EL21W-1,
fan required). After you install an optional cooling fan,
Temperature
you can increase the operating temperature of these
two models up to 50°C without derating.
Relative Humidity < 90%, non-condensing
Operation Atmospheric pressure 86–106 kPa
Installation Site Altitude <1000 m
1.0 mm, peak-to-peak value: from 2–13.2 Hz;
Vibration 0.7–1.0 G, from 13.2–55 Hz; 1.0 G, from 55–512 Hz;
compliance with IEC 60068-2-6 standard.
Temperature -20°C to 60°C (-4°F to 140°F)
Relative Humidity < 90%, non-condensing
Storage Atmospheric pressure 86–106 kPa
and
Transportation 1.0 mm, peak-to-peak value: from 2–13.2 Hz;
Vibration 0.7–1.0 G, from 13.2–55 Hz; 1.0 G, from 55–512 Hz;
compliance with IEC 60068-2-6 standard.
Pollution Degree 2: good for a factory type environment.

1-7
Chapter 1 Introduction  VFD-EL-W

Minimum Mounting Clearance

(Blue arrow)
(Red arrow) Outflow (Black) Distance
Inflow

Single Drive Installation Side-by-Side Horizontal Installation Zero-stack Installation

Minimum Distance (mm) Temperature °C


Installation
Model Name Max.(Derating is not Max.(Derating is
Method A B C Note 1
required) Note 3 required)

VFD002EL21W(-1) Single Drive 120 50 - 50 60

VFD004EL21W(-1) Side-by-Side
120 50 30 50 60
Horizontal

VFD004EL43W(-1) Zero-stack Note 2 - - - - -

Single Drive 120 50 - 50 Note 4 60

Side-by-Side
VFD007EL21W(-1) 120 50 30 50 Note 4 60
Horizontal

Zero-stack Note 2 - - - - -

Single Drive 120 50 - 50 60

VFD007EL43W(-1) Side-by-Side
120 50 30 50 60
VFD015EL43W(-1) Horizontal

Zero-stack - - - - -

VFD015EL21W(-1) Single Drive 150 50 - 50 60

VFD022EL21W(-1) Side-by-Side
150 50 30 50 60
VFD022EL43W(-1) Horizontal

VFD040EL43W(-1) Zero-stack 150 50 0 40 50

1-8
Chapter 1 Introduction  VFD-EL-W

NOTE

1. Due to a small protruding part of the heat-sink at the bottom of the Frame A1/ A2, we calculate the distance C

for the side-by-side horizontal installation according to the main part of the motor drive only.

2. Frame A1 and A2 does not support zero-stack installation, whereas Frame B supports zero-stack installation.

3. Running the drive continuously with full load by the ambient temperature listed in the “Max. ( Derating is not

requiered)” column reduces the drive’s life span.

4. After installing a cooling fan to VFD007EL21W(-1), the operating temperature of this model is as shown in the

table above. When VFD007EL21W(-1) doesn’t have cooling fan, its operating temperature should be 10 ºC

lower than the temperature shown above (See Cooling Fan Installation in Appendix B.4).

1-9
Chapter 1 Introduction  VFD-EL-W

CAUTION!

1. Mount the AC motor drive vertically on a flat vertical surface with screws. Other mounting directions are not
allowed.
2. The AC motor drive generates heat during operation. Allow sufficient space around the unit for heat
dissipation. When you install the AC motor drive in a confined space (for example a cabinet), the surrounding
temperature must be meet specifications of operation (as shown in chapter 1.2.1) with good ventilation. DO
NOT install the AC motor drive in a space with poor ventilation.
3. The heat sink temperature may rise to 90°C when running. The metallic material on which the AC motor
drive is mounted must be noncombustible, be excellent at thermal dissipation and be able to withstand this
high temperature.
4. When installing multiple AC motor drives in the same cabinet, mount them in a row with enough space
between for ventilation. When installing one AC motor drive below another one, use a metal separator
between the AC motor drives to prevent mutual heating.

Installation with Metal Separator Installation without Metal Separator

120mm 150mm

120mm 150mm
A B
120mm 150mm
Air flow

120mm 150mm

Frame A Frame B Frame A Frame B

NOTE

 Prevent fiber particles, scraps of paper, shredded wood, sawdust, metal particles, etc. from adhering to the
heat sink.
 Install the AC motor drive in a metal cabinet to prevent the risk of fire accident.

1-10
Chapter 1 Introduction  VFD-EL-W

1.3 Dimensions
Frame A1
VFD002EL21W(-1), VFD004EL21W(-1), VFD004EL43W(-1), VFD007EL21W(-1), VFD007EL43W(-1)

See A

(mounting hole)

Unit: mm [inch]

Frame W W1 H H1 D D1 S1
92.0 82.0 162.0 152 128.7 5.4 5.4
A1
[3.62] [3.23] [6.38] [5.98] [5.07] [0.21] [0.21]

1-11
Chapter 1 Introduction  VFD-EL-W

Frame A2
VFD015EL43W(-1)

See A

(mounting hole)

Unit: mm [inch]
Frame W W1 H H1 H2 D D1 S1
92.0 82.0 180.5 162.0 152 128.7 2.0 5.4
A2
[3.62] [3.23] [7.11] [6.38] [5.98] [5.07] [0.08] [0.21]

1-12
Chapter 1 Introduction  VFD-EL-W

Frame B
VFD015EL21W(-1), VFD022EL21W(-1), VFD022EL43W(-1), VFD040EL43W(-1)

See B

(mounting hole)

(mounting hole)

Unit: mm [inch]

Frame W W1 H H1 D D1 S1 S2
100.0 89.0 174.0 162.9 136.0 4.0 5.9 5.4
B
[3.94] [3.50] [6.86] [6.42] [5.36] [0.16] [0.23] [0.21]

1-13
Chapter 1 Introduction  VFD-EL-W

This page intentionally left blank

1-14
Chapter 2 Installation and Wiring

2.1 Wiring
2.2 External Wiring
2.3 Main Circuit
2.4 Control Terminals
2.5 NPN / PNP Mode

After removing the covers of input/output side terminals and control board terminals, verify the main circuit
terminals and control circuit terminals are clear. Be sure to observe the following precautions when wiring.

 Turn off the AC motor drive power before installing any wiring. A hazardous charge may
still remain in the DC bus capacitors after the power has been turned off. For your safety,
wait until the digital keypad indictor turns off and measure the DC voltage with the
voltmeter. Makes sure the voltage drops to a safe level < 25 VDC before wiring. Performing
DANGER a wiring installation while voltage remains may cause sparks and short circuits.
 Only qualified personnel familiar with AC motor drives are allowed to do the wiring. Make
sure the power is turned off before wiring to prevent electric shock.
 Make sure that power is only applied to the R/L1, S/L2, and T/L3 terminals. Failure to
comply may result in damage to the equipment. The voltage and current should be in the
range on the AC motor drive nameplate.(refer to Section 1-1 Receiving and Inspection for
details)
 The grounding terminals must be well-grounded to prevent electric shock or fire accidents
and to reduce noise interference.
 Make sure that you correctly tighten the main circuit terminal screws to prevent sparks that
can be caused by screws loosened due to vibration.

 When wiring, choose wires that comply with local regulations for your safety.
 Check following items after finishing the wiring:
1. Are all connections correct?
2. Are there any loose wires?
3. Are there any short circuits between the terminals or to ground?

2-1
Chapter 2 Installation and Wiring VFD-EL-W

2.1 Wiring
There are wirings for main circuits and control circuits. You must wire according to the following wiring diagrams.

 230V One-phase
VFD002EL21W(-1), VFD004EL21W(-1), VFD007EL21W(-1), VFD015EL21W(-1), VFD022EL21W(-1)

2-2
Chapter 2 Installation and Wiring VFD-EL-W

 460V Three-phase
VFD004EL43W(-1), VFD007EL43W(-1), VFD015EL43W(-1), VFD022EL43W(-1), VFD040EL43W(-1)

2-3
Chapter 2 Installation and Wiring VFD-EL-W

Wiring for NPN and PNP mode


Internal power supply

External power supply

CAUTION!

1. Separate the main circuit and control circuit wiring to prevent erroneous actions.
2. Use shielded wire for the control wiring and do not expose the peeled-off shield in front of the terminal.
3. Use shielded wire or conduit for the power wiring and ground the two ends of the shielded wire or conduit.
4. Damaged insulation of wiring may cause personal injury or damage to circuits and equipment if it comes in
contact with high voltage.
5. The AC motor drive, motor and wiring may cause interference. To prevent equipment damage, take care of
interference between the surrounding sensors and the equipment.
6. Connect the AC drive output terminals U/T1, V/T2, and W/T3 to the motor terminals U/T1, V/T2, and W/T3,
respectively. To permanently reverse the direction of motor rotation, switch over any of the two motor leads.
7. With long motor cables, high capacitive switching current peaks can cause over-current, high leakage current
or lower current readout accuracy. To prevent this, the motor cable should be less than 20 m for 4.0 kW
models and below. The cable should be less than 50 m for 5.5 kW models and above. For longer motor
cables, use an AC output reactor.
8. The AC motor drives, electric welding machines and the larger horsepower motors should be grounded
separately.
9. Use ground leads that comply with local regulations and keep them as short as possible.
10. The VFD-EL-W series does not have a built-in brake unit,and no support for external brake unit and brake
resistor.
11. When grounding, choose wires that comply with local regulations for your safety.
12. To prevent lightning strike and electric shock, the metal grounding wire of electrical equipment should be
thick and short, and connected to the dedicated grounding terminal of the inverter system.
13. You can install multiple VFD-EL-W units in one location. All the units should be grounded directly to a
common ground terminal, as shown in the figure below. Ensure that there are no ground loops.

2-4
Chapter 2 Installation and Wiring VFD-EL-W

Excellent grounding method:

Acceptable grounding method:

Grounding method not allowed:

Not allowed

2-5
Chapter 2 Installation and Wiring VFD-EL-W

2.2 External Wiring

Items Explanations

Please follow the specific power supply


Power supply
requirements in Appendix A.
There may be an inrush current during power-
Fuse/NFB up. Please check the chart in Appendix B and
select the correct fuse for the rated current. Use
(optional)
of an NFB is optional.
Magnetic Do not use a magnetic contactor as the I/O
contactor switch for the AC motor drive, as it will reduce
(optional) the operating life of the AC drive.
Use to improve the input power factor, reduce
harmonics and provide protection from AC line
disturbances (such as surges, switching spikes,
Input AC Line
short interruptions). Install an AC line reactor
Reactor
when the power supply capacity is 500 kVA or
(optional)
more, or advanced capacity is activated. The
wiring distance should be  10m. Refer to
Appendix B for details.

Use zero phase reactors to reduce radio noise,


Zero-phase especially when audio equipment is installed
Reactor near the inverter. They are effective for noise
(Ferrite Core reduction on both the input and output sides.
Common Attenuation quality is good for a wide range from
Choke) the AM band to 10 MHz. Appendix B lists the
(optional) specifications for zero-phase reactors
(RF220X00A).

EMI filter Use to reduce electromagnetic interference.

Motor surge voltage amplitude depends on


Output AC
motor cable length. For applications with long
Line Reactor
motor cable (>20 m), install a reactor at the
(optional)
inverter output side.

2-6
Chapter 2 Installation and Wiring VFD-EL-W

2.3 Main Circuit


2.3.1 Main Circuit Connection

No Fuse Breaker
(NFB) MC
R Motor
R(L1) U(T1)
S S(L2) IM
V(T2)
T T(L3) 3~
W(T3)
E
E

Terminal Symbol Explanation of Terminal Function


R/L1, S/L2, T/L3 Mains input terminals (one-phase/three-phase)
U/T1, V/T2, W/T3 Motor drive output terminals for connecting three-phase induction motor
Ground connection. Please comply with local regulations.

CAUTION!

Mains power terminals (R/L1, S/L2, T/L3)


 Do NOT connect three-phase motor drives to single-phase AC power. There is no sequential order when
connecting mains power terminals R/L1, S/L2, T/L3. Connect these terminals with a freely usable standard.
 Connect terminals (R/L1, S/L2, and T/L3) with a non-fuse breaker to three-phase AC power for circuit
protection. It is recommended that you add a magnetic contactor (MC) in the power input wiring to cut off
power quickly and reduce malfunction when activating the protection function for the AC motor drives. Both
ends of the MC should have an R-C surge absorber.
 Make sure that you correctly tighten the main circuit terminal screws to prevent sparks caused by loosening
screws due to vibration.
 Use voltage and current levels according to the specifications in Appendix A.
 When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity of 200 mA or
higher, and not less than 0.1 second operation time to avoid nuisance tripping. For specific GFCI of the AC
motor drive, select a current sensor with sensitivity of 30 mA or higher.
 Do NOT run or stop AC motor drives by turning the power ON or OFF. Use the RUN or STOP command
through the control terminals or a keypad. If you still need to run or stop the AC drives by turning the power
ON or OFF, it is recommended to do so no more often than ONCE per hour.

Output terminals for main circuit (U, V, W)


 The default for the operation direction is running forward. The method to control the running direction is to set
by the communication parameters. Refer to the Parameter Group 09 in Chapter 4 for details.
 When it is necessary to install the filter at the output side of terminals U/T1, V/T2, W/T3 on the AC motor
drive, use an inductance filter. Do not use phase-compensation capacitors or L-C (Inductance-Capacitance)
or R-C (Resistance-Capacitance), unless approved by Delta.
 DO NOT connect phase-compensation capacitors or surge absorbers at the output terminals of AC motor
drives.
 Use a well-insulated motor, suitable for inverter operation.

2-7
Chapter 2 Installation and Wiring VFD-EL-W

2.3.2 Main Circuit Terminals


Frame A1 Frame A2 Frame B

Main Circuit Terminals


R/L1, S/L2, T/L3,U/T1, V/T2, W/T3,
Frame Model Maximum Minimum Screw Size
Wire Wire Tightening
Gauge Gauge Torque (±10%)

VFD002EL21W(-1)
2.5 mm2
VFD004EL21W(-1)
[14 AWG]
M4 screw
VFD004EL43W(-1)
A1 4 mm2 15 kgf-cm
4 mm2
VFD007EL21W(-1) [12 AWG] [13 lbf-in]
[12 AWG]
[1.47 N-m]
VFD007EL43W(-1) 2.5 mm2

A2 VFD015EL43W(-1) [14 AWG]

VFD015EL21W(-1) 10 mm2
M4 screw
VFD022EL21W(-1) [8 AWG]
10 mm2 13 kgf-cm
B 2.5 mm2
VFD022EL43W(-1) [8 AWG] [11.4 lbf-in]
[14 AWG]
[1.3 N-m]
VFD040EL43W(-1)

NOTE
 For installation at an ambient temperature of 50°C, select copper wires with temperature resistance of 75°C or
90°C. For installation at an ambient temperature over 50°C, select copper wires with temperature resistance
of 90°C or above.
 For installation of VFD007EL21W(-1) at an ambient temperature of 40°C, select copper wires with temperature
resistance of 75°C or 90°C. For installation at an ambient temperature over 40°C, select copper wires with
temperature resistance of 90°C or above.
 When installing VFDxxxEL21W(-1), select wires with voltage rating of 300VAC or above. When installing
VFDxxxEL43W(-1), select wires with voltage rating of 600VAC or above.

2-8
Chapter 2 Installation and Wiring VFD-EL-W

2.4 Control Terminals

Terminal symbols and functions

Terminal Symbol Terminal Function Defaults (NPN mode) ON: Connect to DCM

ON: Run in MI1 direction


MI1 Run-Stop Command
OFF: Stop acc. to Stop Method

MI2 Multi-function Input 2


Refer to Pr.04.06 to Pr.04.08 for programming the
multi-function inputs.
MI3 Multi-function Input 3
ON: the activation current is 5.5 mA.
OFF: leakage current tolerance is 10 μA.
MI4 Multi-function Input 4

The common terminal is only used for a multi-function


input terminal.
Output voltage: 23–25V, load capacity: 20 mA
+24V terminal is only used for digital control signal
common when in the internal power supply PNP mode.
(Or used for digital control signal common when in the
+24V DC Voltage Source external power supply NPN mode.)
For detailed wiring instructions, refer to NPN and PNP
mode description.
NOTE
Do not use the +24V terminal for other external power
loads to avoid damage to the hardware circuit.

DCM Digital Signal Common (Sink) Common for multi-function input terminals.

SG+ Internally connected to RJ45 terminal PIN5 and PIN4,


Modbus RS-485 providing flexible choice for users (only support one of
SG- them at one time).

RA Multi-function Relay Output (N.O.) a Resistive Load:


5A (N.O.) / 3A (N.C.) 240 VAC
5A (N.O.) / 3A (N.C.) 24 VDC
RB Multi-function Relay Output (N.C.) b Inductive Load:

2-9
Chapter 2 Installation and Wiring VFD-EL-W

Terminal Symbol Terminal Function Defaults (NPN mode) ON: Connect to DCM
1.5A (N.O.) / 0.5A (N.C.) 240 VAC
RC Multi-function Relay Common 1.5A (N.O.) / 0.5A (N.C.) 24 VDC
Refer to Pr.03.00 for programming

+10V Potentiometer Power Supply +10 VDC 3 mA (Variable resistor 3–5 kΩ)

Analog Voltage Input


+10V Impedance: 47 kΩ
AVI circuit
Resolution: 10 bits
Range: 0–10 VDC /4–20 mA =
AVI AVI
0–maximum output frequency (Pr.01.00)
Selection: Pr.02.00, Pr.02.09, Pr.10.00
AC M Setting: Pr.04.14–Pr.04.17
internal circuit

ACM Analog Control Signal (Common) Common for AVI

NOTE Control signal wiring size: 18 AWG (0.75 mm2) with shielded wire.

Analog inputs (AVI, ACM)


 Analog input signals are easily affected by external noise. Use shielded wiring and keep it as short as
possible (<20 m) with proper grounding. If the noise is inductive, connecting the shield to the ACM terminal
can cause improvement.
 If the analog input signals are affected by noise from the AC motor drive, connect a capacitor (0.1  F and
above) and a ferrite core as shown in the following diagrams:

AVI
C
ACM

ferrite core
Wind each wire three times or more around the core

Digital inputs (MI1, MI2, MI3, DCM)


 When using contacts or switches to control the digital inputs, use high-quality components to avoid contact
bounce.

2-10
Chapter 2 Installation and Wiring VFD-EL-W

Specification for the control terminals

o n e -ro w te rmin a l tw o -ro w te rmin a l

One-row terminal torque Two-row terminal (±10%)


Frame Model Wire
(±10%)

VFD002EL21W(-1)

VFD004EL21W(-1)

A1 VFD004EL43W(-1)

VFD007EL21W(-1)
4 kgf-cm 7 kgf-cm
VFD007EL43W(-1) 16~24 AWG
[3.5 lbf-in] [6.2lbf-in]
A2 VFD015EL43W(-1) [1.3~0.2mm2]
[0.4 N-m] [0.7 N-m]
VFD015EL21W(-1)

VFD022EL21W(-1)
B
VFD022EL43W(-1)

VFD040EL43W(-1)

2-11
Chapter 2 Installation and Wiring VFD-EL-W

2.5 NPN / PNP Mode


NPN/PNP Internal power supply External power supply

MI..
MI..
.
.

DC 24V

NPN PNP NPN PNP Max:20mA


Max:20mA
NPN/Sink Switch-
+24V
NPN +24V
DC 24V
DC 24V
DCM
DCM

MI..
MI..
.
.

DC 24V NPN PNP


NPN PNP Max:20mA
Max:20mA
PNP/Source
+24V
Switch-PNP +24V
DC 24V
DCM
DC 24V

DCM

NOTE

1) The total load capacity of +24V-DCM internal 24V power is 60 mA, and only supplies power for the MI
terminal of NPN and PNP mode. If you want to know available load capacity to support other external
accessories, deduct the load consumed by corresponding MI terminals. Each MI terminal consumes 6mA.
2) The power supply of the cooling fan is 24VDC. Internal power is applied from terminal +24V/DCM. Once you
install a cooling fan on VFD007EL21W(-1), do not connect any other external accessory to avoid overload
on terminal +24V which will damage the motor drive.

2-12
Chapter 2 Installation and Wiring VFD-EL-W

This page intentionally left blank.

2-13
Chapter 3 Keypad and Start-up

3.1 Description of the Digital Keypad


3.2 Operation Method
3.3 Trial Run

 Make sure that the wiring is correct. In particular, ensure that the output terminals
U/T1, V/T2, W/T3 are NOT connected to power and that the drive is well grounded.
 Verify that no other equipment is connected to the AC motor drive.
 Do NOT operate the AC motor drive with wet hands.
 Please check if the digital keypad displays F60.0 or F50.0 is ON when power is
applied.

 Stop the motor when a fault occurs during running and refer to Chapter 6 Fault
Code Information and Maintenance for solutions. DO NOT touch output terminals
U, V, W when power is still applied to L1/R, L2/S, L3/T, even when the AC motor
drive is stopped to prevent electric shock.

3-1
Chapter 3 Keypad and Start-up VFD-EL-W

3.1 Description of the Digital Keypad

VFD-EL-W series operates the running and displays the functions by the digital keypad.

There are four LEDs on the keypad

 STOP : Lights when the drive stops.

 RUN : Lights when the motor is running.

 FWD : Lights when the motor is running forward.

 REV : Lights when the motor is running in reverse.

3-2
Chapter 3 Keypad and Start-up VFD-EL-W

Description of the Displayed Functions

Display Function Description

Displays current setting frequency of the AC motor drive.

Displays the actual output frequency to the motor.

Displays the user-defined unit (where U = F x Pr.00.05)

Displays the loading current.

FWD command.

REV command.

The counter value (C).

Displays the selected parameter.

Displays the actual stored value of the selected parameter.

Displays the external fault.

Displays “End” for approximately one second (as shown in the left figure)
if the data has been accepted and automatically stored in the register.

Displays if the setting data is not accepted or data value exceeds the
allowed range.

3-3
Chapter 3 Keypad and Start-up VFD-EL-W

Keypad Operation Process

Setting Mode
S TAR T

MO DE MO DE MO DE MO DE MO DE

GO START

NOTE: In the selection mode, press MO DE to set the parameters.

Setting parameters

or

ENTER ENTER ENTER Success to Input data error


set parameter.

NOTE:In the parameter setting mode, you can press MODE to return the selecting mode.

To shift data

Setting direction (When operation source is digital keypad)

M ODE M ODE M O DE MO DE
or

Reference Table for the Seven-segment LED Display of the Digital Keypad
Digit 0 1 2 3 4 5 6 7 8 9
LED Display

English alphabet A b Cc d E F G Hh Ii Jj
LED
Display

English alphabet K L n Oo P q r S Tt U
LED
Display

English alphabet v Y Z
LED
Display

3-4
Chapter 3 Keypad and Start-up VFD-EL-W

3.2 Operation Method


You can set Pr.02.01 to select the operation method to be through the digital keypad, RS-485
communication or control terminals.

3-5
Chapter 3 Keypad and Start-up VFD-EL-W

Operation Method Frequency Source Operation Command Source

When using communication from the PC, use an IFD6500 / IFD6530 or


Operate through
IFD8500 converter to connect the drive to the PC.
communication
Refer to the communication address 2000H and 2101H setting for details.

Operate through the


digital keypad

Figure 3-1

Set the operation command source


Set the frequency source through the
through the RUN, STOP / RESET
▲▼ keys, as shown in Figure 3-1.
keys, as shown in Figure 3-1.

Operate through
external signals

Figure 3-2

Set MI1-DCM as Run / Stop.


MI3-DCM (Set Pr.04.05=d10) Refer to the parameter descriptions
MI4-DCM (Set Pr.04.06=d11) in Chapter 04 for details of
FWD/REV operations.

3-6
Chapter 3 Keypad and Start-up VFD-EL-W

3.3 Trial Run

The default for the operation source is the digital


keypad. The setting methods are as follows:
 After applying power, verify that the LED display shows F
60.0 Hz.
 Press key to set the frequency to be around 5 Hz.
(Refer to Figure 3-1)
 If you want to change FWD to REV, press MODE to find
the FWD function, then press the UP or DOWN key to
locate the REV function to finish the direction change.
 Check following items: RUN
 Check if the motor rotation direction is correct.
 Check if the motor runs steadily without abnormal
noise and vibration.
 Check if acceleration and deceleration are smooth.

If the results of trial run are normal, increase the operating frequency to continue the trial run. If the
trial run still goes normally, then you can start the formal run.

Motor operating direction


When the AC drive output terminals U/T1, V/T2 and W/T3 are connected to the motor terminals
U/T1, V/T2 and W/T3 respectively, the FWD LED indicator on the digital keypad is ON. This means
the AC motor drive executes running forward, and the motor rotates as the figure below shows. On
the contrary, when the REV LED indicator lights, the AC motor drive executes running in reverse,
and the motor rotates in an opposite direction as the figure below shows. If the AC motor drive
executes running forward but the motor rotates in a reverse direction, exchange any two of the U/T1,
V/T2 and W/T3 motor terminals.

Figure 3-3

3-7
Chapter 3 Keypad and Start-up VFD-EL-W

This page intentionally left blank.

3-8
Chapter 4 Parameters

4.1 Summary of Parameter Settings


4.2 Parameter Settings for Applications
4.3 Description of Parameter Settings

The VFD-EL-W parameters are divided into 11 groups by property for easy setting. In most applications, the
user can finish all parameter settings before start-up without the need for re-adjustment during operation.

The 11 groups are as follows:

Group 0: User Parameters


Group 1: Basic Parameters
Group 2: Operation Method Parameters
Group 3: Output Function Parameters
Group 4: Input Function Parameters
Group 5: Multi-Step Speed Parameters
Group 6: Protection Parameters
Group 7: Motor Parameters
Group 8: Special Parameters
Group 9: Communication Parameters
Group 10: PID Control Parameters

4-1
Chapter 4 ParametersVFD-EL-W

4.1 Summary of Parameter Settings


: You can set this parameter during operation.
Group 0 User Parameters
Parameter Function Setting Default Customer
0: 230V, 0.25HP
2: 230V, 0.5HP
3: 460V, 0.5HP
4: 230V, 1 HP
Identity Code of the AC motor 5: 460V, 1 HP Read
00.00
drive 6: 230V, 2 HP only
7: 460V, 2 HP
8: 230V, 3 HP
9: 460V, 3 HP
11: 460V, 5.5 HP
Rated Current Display of the AC Read
00.01 Read only
motor drive only
0: Parameter can be read/written
1: All parameters are read only
8: Keypad lock

00.02 Parameter Reset 9: All parameters are reset to default 0


(50 Hz, 230V/400V or 220V/380V
depends on Pr.00.12)
10: All parameters are reset to default
(60 Hz, 220V/440V)
0: F (frequency command)
1: H (actual frequency)
00.03 Start-up Display Selection 2: A (output current) 0
3: U (user-defined, see Pr.00.04)
4: FWD/REV command
0: Display the content of user-defined unit
0
(Uxxx)
1: Display the counter value (c)
2: Display the status of multi-function input
terminals (d)
3: Display DC bus voltage (u)
4: Display output voltage (E)

00.04 Content of Multi-function Display 5: Display PID analog feedback signal value
(b) (%)
6: Output power factor angle (n)
7: Display output power (P)
8: Display PID setting and feedback signal
9: Display AVI (I) (V)
10: Display ACI (i) (mA)
11: Display the temperature of IGBT (h) (°C)
00.05 User-Defined Coefficient K 0.1–160.0 1.0

4-2
Chapter 4 ParametersVFD-EL-W

Parameter Function Setting Default Customer


00.06 Software Version Read only #.##
0–9999
00.08 Password Input 0–2: the number of password attempts 0
allowed
0–9999
0: No password protection / password
00.09 Password Set 0
entered correctly (Pr.00.08)
1: Parameter has been set
0: V/F control
00.10 Control Mode 0
1: Vector control
0: 230V/400V
00.12 50 Hz Base Voltage Selection 0
1: 220V/380V
User-defined value (correspond
00.13 0–9999 0
to max. operating frequency)
Decimal place of User-defined
00.14 0–3 0
Value

4-3
Chapter 4 ParametersVFD-EL-W

Group 1 Basic Parameters


Parameter Function Setting Default Customer
01.00 Maximum Output Frequency (Fmax) 50.00–400.0 Hz 60.00
01.01 Motor Rated Frequency (Fbase) 0.10–400.0 Hz 60.00
230V series: 0.1–255.0 V 220.0
01.02 Motor Rated Voltage (Vbase)
460V series: 0.1–510.0 V 440.0
01.03 Mid-Point Frequency (Fmid) 0.10–400.0 Hz 1.50
230V series: 0.1–255.0 V 10.0
01.04 Mid-Point Voltage (Vmid)
460V series: 0.1–510.0 V 20.0
01.05 Minimum Output Frequency (Fmin) 0.10–400.00 Hz 1.50
230V series: 0.1–255.0 V 10.0
01.06 Minimum Output Voltage (Vmin)
460V series: 0.1–510.0 V 20.0
01.07 Output Frequency Upper Limit 0.1–120.0% 110.0
01.08 Output Frequency Lower Limit 0.0–100.0 % 0.0
01.09 Acceleration Time 1 (Taccel 1) 0.1–600.0 / 0.01–600.00 sec. 10.0
01.10 Deceleration Time 1 (Tdecel 1) 0.1–600.0 / 0.01–600.00 sec. 10.0
01.11 Acceleration Time 2 (Taccel 2) 0.1–600.0 / 0.01–600.00 sec. 10.0
01.12 Deceleration Time 2 (Tdecel 2) 0.1–600.0 / 0.01–600.00 sec. 10.0
01.13 Jog Acceleration Time 0.1–600.0 / 0.01–600.00 sec. 1.0
01.14 Jog Deceleration Time 0.1–600.0 / 0.01–600.00 sec. 1.0
01.15 Jog Frequency 0.10–400.0 Hz 6.00
0: Linear Acceleration and linear
deceleration
1: Auto-acceleration and linear
deceleration
2: Linear acceleration and auto-
Auto-Acceleration and
01.16 deceleration 0
Auto-Deceleration
3: Auto-acceleration and auto-
deceleration (Set by load)
4: Auto-acceleration and auto-
deceleration (set by Acceleration
/ Deceleration Time setting)
0.0 (S-curve disabled)
01.17 Acceleration S-Curve
0.1–10.0 / 0.01–10.00
0.0 / 0.00
[S-curve enabled (10.0/10.00 is the
01.18 Deceleration S-Curve
smoothest)]
0: Unit: 0.1 sec.
01.19 Acceleration / Deceleration Time Unit 0
1: Unit: 0.01 sec.
01.20 Simple Positioning Stop Frequency 0 0.00
01.21 Simple Positioning Stop Frequency 1 5.00
01.22 Simple Positioning Stop Frequency 2 0.00–400.0 Hz 10.00
01.23 Simple Positioning Stop Frequency 3 20.00
01.24 Simple Positioning Stop Frequency 4 30.00

4-4
Chapter 4 ParametersVFD-EL-W

Parameter Function Setting Default Customer


01.25 Simple Positioning Stop Frequency 5 40.00
01.26 Simple Positioning Stop Frequency 6 0.00–400.0 Hz 50.00
01.27 Simple Positioning Stop Frequency 7 60.00
01.28 Delay Time of Simple Positioning Stop 0 0.00
01.29 Delay Time of Simple Positioning Stop 1 0.00
01.30 Delay Time of Simple Positioning Stop 2 0.00
01.31 Delay Time of Simple Positioning Stop 3 0.00
0.00–600.00 sec.
01.32 Delay Time of Simple Positioning Stop 4 0.00
01.33 Delay Time of Simple Positioning Stop 5 0.00
01.34 Delay Time of Simple Positioning Stop 6 0.00
01.35 Delay Time of Simple Positioning Stop 7 0.00

4-5
Chapter 4 ParametersVFD-EL-W

Group 2 Operation Method Parameters


Parameter Function Setting Default Customer
0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN.
First Master Frequency 1: 0–10 V from AVI
02.00 0
Command Source 2: 4–20 mA from ACI
3: RS-485 (RJ45) communication
4: Digital keypad potentiometer
0: Digital keypad
1: External terminals. Keypad STOP/RESET
enabled.
2: External terminals. Keypad STOP/RESET
First Operation Command
02.01 disabled. 0
Source
3: RS-485 communication. Keypad
STOP/RESET enabled.
4: RS-485 communication. Keypad
STOP/RESET disabled.
0: STOP: ramp to stop; E.F.: coast to stop
1: STOP: coast to stop; E.F.: coast to stop
02.02 Stop Method 2: STOP: ramp to stop; E.F.: ramp to stop 0
3: STOP: coast to stop; E.F.: ramp to stop
4: Simple Positioning Stop; E.F.:coast to stop
PWM Carrier Frequency
02.03 2–12 kHz 8
Selection
0: Forward/reverse operation enabled
02.04 Motor Direction Control 1: Reverse operation disabled 0
2: Forward operation disabled
0: Start running when power is on.
1: Do not run when power is on
2: When the source of the command changes,
the drive’s operation remains the same.
3: When the source of the command changes,
Power-On Command and Run
the drive’s operation follows the new
02.05 Command Source Modifies 1
command.
the Drive Operating Control
4: The motor drive can start to run at power on
or after reset. When the source of the
command is a two-wire external terminal, the
operating command changes as the external
terminal’s status changes.
0: Decelerate to 0 Hz
1: Coast to stop and display “AErr”
02.06 Loss of ACI Signal (4–20 mA) 2: Continue the operation according to the last 0
frequency command
3: Continue the operation according to the
setting at Pr.02.11.
0: Digital keypad up/down keys mode
1: Based on Accel./ Decel. time
02.07 Up/Down Mode 0
2: Constant speed (according to Pr.02.08)
3: Pulse input unit (according to Pr.02.08)

4-6
Chapter 4 ParametersVFD-EL-W

Parameter Function Setting Default Customer


Accel./ Decel. Rate of Change
02.08 of UP/DOWN Operation with 0.01–10.00 Hz / 2ms 0.01
Constant Speed
0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN.
Second Frequency Command 1: 0–10V from AVI
02.09 0
Source 2: 4–20 mA from ACI
3: RS-485 (RJ45) communication
4: Digital keypad potentiometer
0: First Master Frequency Command Only
Combining the First and 1: First Master Frequency Command+ Second
02.10 Second Master Frequency Master Frequency Command 0
Commands 2: First Master Frequency Command -
Second Master Frequency Command

02.11 Keypad Frequency Command 0.00–400.0 Hz 60.00

Communication Frequency
02.12 0.00–400.0 Hz 60.00
Command
0: Save Keypad & Communication Frequency
Saving Keypad or
02.13 Communication Frequency 1: Save Keypad Frequency Only 0
Command Selection
2: Save Communication Frequency Only
0: Current Frequency Command
Initial Frequency Selection (for
02.14 1: Zero Frequency Command 0
keypad & RS-485)
2: Refer to Pr.02.15 to set up
Initial Frequency Setting (for
02.15 0.00–400.0 Hz 60.00
keypad & RS-485)
Read Only
1: bit0=1: First Master Frequency Source
Display the Master Frequency (Pr.02.00) Read
02.16
Command Source 2: bit1=1: Second Master Frequency Source only
(Pr.02.09)
4: bit2=1: Multi-function input
Read Only
1: bit0=1: Digital Keypad
Display the Operation Read
02.17 2: bit1=1: RS-485 communication
Command Source only
4: bit2=1: External Terminal (MI1)
8: bit3=1: Multi-function input
02.18 User-defined Value 2 Setting 0–Pr.00.13 0
Read
02.19 User-defined Value 2 0–9999
only

4-7
Chapter 4 ParametersVFD-EL-W

Group 3 Output Function Parameters


Parameter Function Setting Default Customer
0: No function
1: Indication during RUN
2: Indication of master frequency reached
3: Zero speed
4: Over-torque detection
5: Base-Block (B.B.) indication
6: Low-voltage indication
7: Operation mode indication
8: Fault indication
9: Desired frequency reached
10: Terminal count value reached
11: Preliminary count value reached
Multi-function Output 12: Over-voltage stall prevention
03.00 Relay (RA1, RB1, 8
RC1) 13: Over-current Stall prevention
14: IGBT overheat warning
(85°C: ON, 80°C: OFF)
15: Over-voltage
16: PID feedback error
17: Forward command
18: Reverse command
19: Zero speed output signal
20: Warning
21: Mechanical brake control (Desired frequency
reached)
22: Drive ready
23: Multi-pump system error display (only master)
24: Preheating function indication
25: Fire mode indication
Desired Frequency
03.02 0.00–400.0 Hz 0.00
Reached
03.05 Terminal Count Value 0–9999 0
Preliminary Count
03.06 0–9999 0
Value
EF Active when 0: Terminal count value reached, no EF display
03.07 Terminal Count Value 0
Reached 1: Terminal count value reached, EF active
0: Fan is always ON
1: One minute after the AC motor drive stops, the fan
is OFF.
2: Fan is ON when the AC motor drive runs, fan is
OFF when the AC motor drive stops.
03.08 Fan Control 0
3: Fan is ON when the preliminary heat sink
temperature is reached.
4: Fan is ON when the AC motor drive runs; fan is
OFF when the AC motor drive stops. And the fan
is in a standby mode at 0 Hz.

4-8
Chapter 4 ParametersVFD-EL-W

Parameter Function Setting Default Customer


Mechanical Brake
03.11 0.00–20.00 Hz 0.00
Release Frequency
Mechanical Brake
03.12 0.00–20.00 Hz 0.00
Engage Frequency
Display the Status of Read
03.13 the Multi-function Read only
Output Terminals only

4-9
Chapter 4 ParametersVFD-EL-W

Group 4 Input Function Parameters


Parameter Function Setting Default Customer

04.00 Keypad Potentiometer Bias 0.0–100.0% 0.0

0: Positive bias
04.01 Keypad Potentiometer Bias Polarity 0
1: Negative bias

04.02 Keypad Potentiometer Gain 0.1–200.0% 100.0

Keypad Potentiometer Negative 0: No negative bias command


04.03 Bias, Reverse Motion Enable / 0
Disable 1: Negative bias: REV motion enabled
Mode 1 (Pr.04.19=0)
0: MI1 start-up (keypad FWD lights) /
Start-up / Stop Method of MI stop
04.04 Terminals and Multi-function Input Mode 2 (Pr.04-19=1) 0
Selection 0: Two-wire (1) MI1, MI2
1: Two-wire (2) MI1, MI2
2: Three-wire, MI1, MI2, MI3
04.05 Reserved 0: No function -
Start-up / Stop or Multi-function
04.06 1: Multi-step speed command 1 1
Input Terminal (MI2)
Start-up / Stop or Multi-function
04.07 2: Multi-step speed command 2 2
Input Terminal (MI3)
04.08 Multi-function Input Terminal (MI4) 3: Multi-step speed command 3 3
5: External reset
6: Accel. / decel. inhibit
7: The 1st, 2nd acceleration or
deceleration time selection
8: JOG operation control
9: External Base Block (Refer to
Pr.08.06)
10: UP: Increase Master Frequency
11: DOWN: Decrease Master
Frequency
12: Counter trigger
13: Counter reset
14: External fault
15: PID function disabled
16: Output shutoff stop
17: Parameter lock enable
18: Operation command selection
(Pr.02.01 setting / external
terminals)
19: Operation command selection
(Pr.02.01 setting / digital keypad)
20: Operation command selection
(Pr.02.01 setting / communication)
21: Forward / reverse
22: Second frequency command
source
4-10
Chapter 4 ParametersVFD-EL-W

Parameter Function Setting Default Customer


23: Simple positioning stop by forward
limit
24: Simple positioning stop by reverse
limit
25: Multi-pump control by Hand or Auto
mode
26: Auto-trigger preheating function
27: Fire mode enabled (without
Operation Command)
28: Fire mode enabled (with Operation
Command)
Multi-function Input Contact
04.09 0–63 0
Selection
Digital Terminal Input Response
04.10 1–20 (*2ms) 1
Time
04.11 Minimum AVI Voltage 0.0–10.0 V 0.0
Minimum AVI Frequency 0.0–100.0% [100% corresponds to
04.12 0.0
(percentage of Pr.01.00) Fmax (Pr.01.00)]
04.13 Maximum AVI Voltage 0.0–10.0 V 10.0
Maximum AVI Frequency 0.00–100.00% [100% corresponds to
04.14 100.00
(percentage of Pr.01.00) Fmax (Pr.01.00)]
04.15 Minimum ACI Current 0.0–20.0 mA 4.0
Minimum ACI Frequency 0.00–100.00% [100% corresponds to
04.16 0.0
(percentage of Pr.01.00) Fmax (Pr.01.00)]
04.17 Maximum ACI Current 0.0–20.0 mA 20.0
Maximum ACI Frequency 0.00–100.00% [100% corresponds to
04.18 100.0
(percentage of Pr.01.00) Fmax (Pr.01.00)]
0: Mode 1
(MI1: Start-up/Stop terminal; MI2 &
MI3: multi-function input terminals)
04.19 MI Terminal Control Mode Selection 0
1: Mode 2
(MI1/MI2/MI3 support two-wire /
three-wire start-up)
Display the Status of Multi-function Read
04.26 Read only
Input Terminal only
Internal/External Multi-function
04.27 0–4095 0
Input Terminals Selection
04.28 Internal Terminal Status 0–4095 0
Delay Time of Multi-function Input
04.29 0.00–360.00 sec. 0.00
Terminal (MI1) Turn On
Delay Time of Multi-function Input
04.30 0.00–360.00 sec. 0.00
Terminal (MI1) Turn Off
Delay Time of Multi-function Input
04.31 0.00–360.00 sec. 0.00
Terminal(MI2) Turn On
Delay Time of Multi-function Input
04.32 0.00–360.00 sec. 0.00
Terminal (MI2) Turn Off
Delay Time of Multi-function Input
04.33 0.00–360.00 sec. 0.00
Terminal (MI3) Turn On

4-11
Chapter 4 ParametersVFD-EL-W

Parameter Function Setting Default Customer


Delay Time of Multi-function Input
04.34 0.00–360.00 sec. 0.00
Terminal (MI3) Turn Off

4-12
Chapter 4 ParametersVFD-EL-W

Group 5 Multi-Step Speed Parameters


Parameter Function Setting Default Customer
05.00 1st Step Speed Frequency 0.00–400.0 Hz 0.00
05.01 2nd Step Speed Frequency 0.00–400.0 Hz 0.00
05.02 3rd Step Speed Frequency 0.00–400.0 Hz 0.00
05.03 4th Step Speed Frequency 0.00–400.0 Hz 0.00
05.04 5th Step Speed Frequency 0.00–400.0 Hz 0.00
05.05 6th Step Speed Frequency 0.00–400.0 Hz 0.00
05.06 7th Step Speed Frequency 0.00–400.0 Hz 0.00

4-13
Chapter 4 ParametersVFD-EL-W

Group 6 Protection Parameters


Parameter Function Setting Default Customer

Over-Voltage Stall 230V series: 330.0–410.0 V 390.0


06.00
Prevention 460V series: 660.0–820.0 V 780.0
Over-Current Stall 0:Disable
06.01 Prevention during 170
Acceleration 20–250%

Over-Current Stall 0:Disable


06.02 Prevention during 170
Operation 20–250%

0: Over-torque detection disabled


1: Over-torque detection enabled during constant
speed operation. After over-torque is detected,
keep running until oL1 or oL occurs.
2: Over-torque detection enabled during constant
speed operation. After over-torque is detected,
Over-Torque Detection
06.03 stop running. 0
Mode (oL2)
3: Over-torque detection enabled during
acceleration. After over-torque is detected, keep
running until oL1 occurs.
4: Over-torque detection enabled during
acceleration. After over-torque is detected, stop
running.
Over-Torque Detection
06.04 10–200% 150
Level
Over-Torque Detection
06.05 0.1–60.0 sec. 0.1
Time
0: Standard motor (self-cooled by fan)
Electronic Thermal
06.06 Overload Relay Selection 1: Special motor (forced external cooling) 2
(oL1)
2: Disabled
Electronic Thermal
06.07 30–600 sec. 60
Characteristic
06.08 Present Fault Record 0: No fault
Second Most Recent 1: Over current (oc)
06.09
Fault Record 2: Over voltage (ov)
Third Most Recent Fault 3: IGBT Overheat (oH1)
06.10
Record 5: Overload (oL)
Fourth Most Recent Fault 6: Overload1 (oL1)
06.11
Record 7: Motor overload (oL2)
Fifth Most Recent Fault 8: External fault (E.F.)
06.12
Record 9: Current exceeds two times the rated current
during acceleration (ocA)
10: Current exceeds two times the rated current
during deceleration (ocd) 0
11: Current exceeds two times the rated current
during constant speed operation (ocn)
14: Phase-Loss (PHL)
16: Auto-acceleration / auto-deceleration failure
(CFA)
17: Software / Password protection (codE)
18: Power Board CPU WRITE failure (cF1.0)
19: Power Board CPU READ failure (cF2.0)
20: CC, OC Hardware protection failure (HPF1)
21: OV Hardware protection failure (HPF2)
4-14
Chapter 4 ParametersVFD-EL-W

Parameter Function Setting Default Customer


23: OC Hardware protection failure (HPF4)
24: U-phase error (cF3.0)
25: V-phase error (cF3.1)
26: W-phase error (cF3.2)
27: DC bus error (cF3.3)
28: IGBT Overheat error (cF3.4)
34: Motor PTC overheat protection (PtC1)
35: FBE_ERR: PID feedback error (Incorrect
feedback signal)
36: dEv: unusual PID feedback deviation
37: OPHL
Motor Disconnection 0.0–60.0
06.13 0.0
Detection Time 0.0: Disable the OPHL detection function
Motor Disconnection
06.14 10–100 30
Detection Current Level

4-15
Chapter 4 ParametersVFD-EL-W

Group 7 Motor Parameters


Parameter Explanation Settings Default Customer
07.00 Motor Rated Current 23–120% FLA 100
07.01 Motor No-Load Current 0–99% FLA 40
07.02 Torque Compensation 0.0–10.0 0.0
07.03 Slip Compensation Gain 0.00–10.00 0.00
0: Disable
1: Auto-tuning R1 (Motor does not run)
07.04 Motor Parameter Auto-Tuning 0
2: Auto-tuning R1 + No-load current
(with running motor)
Motor Line-to-line Resistance R1
07.05 0–65535 mΩ 0
(Motor 0)
07.06 Motor Rated Slip (Motor 0) 0.00–20.00 Hz 3.00
07.07 Slip Compensation Limit 0–250% 200
Torque Compensation Time
07.08 0.01–10.00 sec. 0.10
Constant
Slip
07.09 0.05–10.00 sec. 0.20
Compensation Time Constant
Accumulated Motor Operation
07.10 0–1439 Min. 0
Time (Minute)
Accumulated Motor Operation
07.11 0–65535 Day 0
Time (Day)
0: Disable
07.12 Motor PTC Overheat Protection 0
1: Enable
Motor PTC Protection Input
07.13 0–9999 (*2 ms) 100
Response Time
Motor PTC Overheat Protection
07.14 0.1–10.0 V 2.4
Level
Motor PTC Overheat Warning
07.15 0.1–10.0 V 1.2
Level
Motor PTC Overheat Reset Delta
07.16 0.1–5.0 V 0.6
Level
0: Warn and ramp to stop
07.17 Motor PTC Overheat Action 1: Warn and coast to stop 0
2: Warn and keep operating

4-16
Chapter 4 ParametersVFD-EL-W

Group 8 Special Parameters


Parameter Explanation Settings Default Customer
08.00 DC Brake Current Level 0–100% 0
DC Brake Time during
08.01 0.0–60.0 sec. 0.0
Start-Up
DC Brake Time during
08.02 0.0–60.0 sec. 0.0
Stopping
08.03 Start-point for DC Brake 0.00–400.0 Hz 0.00
0: Operation stops (coast to stop) after
momentary power loss
1: Operation continues after momentary power
Momentary Power Loss loss, speed search starts with the last
08.04 0
Action frequency
2: Operation continues after momentary power
loss, speed search starts with the minimum
frequency
Maximum Allowable
08.05 0.1–20.0 sec. 2.0
Power Loss Time
0: Disable
1: Speed search starts with the last frequency
Base Block Speed
08.06 command 1
Search
2: Speed search starts with the minimum output
Frequency (Pr.01.05)
Base Block Time for
08.07 0.1–5.0 sec. 0.5
Speed Search (B.B.)
Current Limit for Speed
08.08 30–200% 150
Search
Skip Frequency 1 Upper
08.09 0.00–400.00 Hz 0.00
Limit
Skip Frequency 1 Lower
08.10 0.00–400.00 Hz 0.00
Limit
Skip Frequency 2 Upper
08.11 0.00–400.00 Hz 0.00
Limit
Skip Frequency 2 Lower
08.12 0.00–400.00 Hz 0.00
Limit
Skip Frequency 3 Upper
08.13 0.00–400.00 Hz 0.00
Limit
Skip Frequency 3 Lower
08.14 0.00–400.00 Hz 0.00
Limit
Number of Auto-restarts
08.15 0–10 0
after Fault
Auto-reset Time for
08.16 0.1–6000 sec. 60.0
Restart after Fault
0: Disable Energy-saving operation
08.17 Auto-energy Saving 0
1: Enable Energy-saving operation
0: AVR function enable
Automatic Voltage 1: AVR function disable
08.18 0
Regulation (AVR) 2: AVR function disable for deceleration
3: AVR function disable for stop
Compensation
08.20 Coefficient for Motor 0.0–5.0 0.0
Instability
DC Current Level during
08.21 0–100% 0
Preheating
DC Current Cycle Time
08.22 0–100% 0
during Preheating
0:No function
08.23 Fire mode 1:Forward running 0
2:Reverse in reverse
Operating Frequency
08.24 0.00–400.00 Hz 60.00
during Fire Mode
4-17
Chapter 4 ParametersVFD-EL-W

Parameter Explanation Settings Default Customer


Number of Fire Mode
08.25 Refer to parameter description Read only
Actions

4-18
Chapter 4 ParametersVFD-EL-W

Group 9 Communication Parameters


Parameter Explanation Settings Default Customer
09.00 Communication Address 1–254 1
0: Baud rate 4800 bps (bits / second)
1: Baud rate 9600 bps (bits / second)
09.01 Transmission Speed 1
2: Baud rate 19200 bps (bits / second)
3: Baud rate 38400 bps (bits / second)
0: Warn and keep operating
1: Warn and ramp to stop
09.02 Transmission Fault Action 3
2: Warn and coast to stop
3: No warning and keep operating
0.0–120.0 sec.
09.03 Time-out Detection 0.0
0.0: Disable
0: 7,N,2 (Modbus, ASCII)
1: 7,E,1 (Modbus, ASCII)
2: 7,O,1 (Modbus, ASCII)
3: 8,N,2 (Modbus, RTU)
4: 8,E,1 (Modbus, RTU)
5: 8,O,1 (Modbus, RTU)
09.04 Communication Protocol 0
6: 8,N,1 (Modbus, RTU)
7: 8,E,2 (Modbus, RTU)
8: 8,O,2 (Modbus, RTU)
9: 7,N,1 (Modbus, ASCII)
10: 7,E,2 (Modbus, ASCII)
11: 7,O,2 (Modbus, ASCII)

09.07 Response Delay Time 0–200 (1 unit = 2 ms.) 1

4-19
Chapter 4 ParametersVFD-EL-W

Group 10 PID Control Parameters


Parameter Explanation Settings Default Customer
0: Disable PID operation
1: Digital keypad UP/DOWN keys
10.00 PID Set Point Selection 2: Reserved 0
3: Reserved
4: PID set point (Pr.10.11)
0: Positive PID feedback from external
terminal AVI (0–10 VDC)
1: Negative PID feedback from external
Input Terminal for PID terminal AVI (0–10 VDC)
10.01 0
Feedback 2: Positive PID feedback from external
terminal ACI (4–20 mA)
3: Negative PID feedback from external
terminal ACI (4–20 mA)
10.02 Proportional Gain (P) 0.0–10.0 1.0
10.03 Integral Time (I) 0.00–100.0 sec. (0.00=disable) 1.00
10.04 Differential Time (D) 0.00–1.00 sec. 0.00
Upper Bound for Integral
10.05 0–100% 100
Control
10.06 PID Filter Time 0.0–2.5 sec. 0.0
PID Output Frequency
10.07 0–110% 100
Limit
PID Feedback Signal
10.08 0.0–3600.0 sec. 60.0
Detection Time
0: Warn and ramp to stop
Erroneous PID Feedback
10.09 1: Warn and coast to stop 0
Signal Action
2: Warn and keep operation
Gain Over the PID
10.10 0.0–10.0 1.0
Detection Value
10.11 PID Set Point Value 0.00–400.00 Hz (valid when Pr.10.00=4) 0.00
10.12 PID Deviation Level 0.0–100.0% 10.0
PID Deviation Detection
10.13 0.1–300.0 sec. 5.0
Time
10.14 Sleep Detection Time 0.0–6550 sec. 0.0
10.15 Sleep Frequency 0.00 to Fmax Hz 0.00
10.16 Wake-up Frequency 0.00 to Fmax Hz 0.00
10.17 PID Offset 0.00–60.00 Hz 0.00
Feedback of PID Physical
10.18 1.0–99.9 99.9
Quantity Value
PID Calculation Mode 0: Serial mode
10.19 0
Selection 1: Parallel mode

4-20
Chapter 4 ParametersVFD-EL-W

Parameter Explanation Settings Default Customer


0: Warn and keep operating
1: Warn and coast to stop
2: Warn and ramp to stop
3: Ramp to stop and restart after Pr.10.21
Erroneous PID Feedback delay time (No display of error and
10.20 0
Deviation Level Action warning)
4: Ramp to stop and restart after Pr.10.21
delay time. The number of times of restart
is limited by Pr.10.50 (Number of Times of
Restart after PID Fault).
Restart Delay Time after
10.21 Erroneous PID Deviation 0–9999 sec. 60
Level
10.22 Set Point Deviation Level 0–100% 0
Detection Time of Set
10.23 0–9999 sec. 10
Point Deviation Level
Deviation Level of Liquid
10.24 0–50% 0
Leakage
Liquid Leakage Change
10.25 0–100% (0: disable) 0
Detection
Time Setting for Liquid
10.26 0.1–10.0 sec. (0: disable) 0.5
Leakage Change
0: Disable
Multi-Pump Control 1: Fixed Time Circulation (alternative
10.35 operation) 0
Mode
2: Fixed quantity control (multi-pump
operating at constant pressure)
0: Multi-pump control mode is disabled
10.36 Multi-pump ID 1: Master 0
2–4: Slave
Multi-pump’s Fixed Time
10.37 1–65535 (minute) 60
Circulation Period
Frequency to Start
10.38 0.00 Hz–Fmax 60.00
Switching Pumps
Time Detected When
10.39 Pump Reaches the 0.0–3600.0 sec. 1
Starting Frequency
Frequency to Stop
10.40 0.00 Hz–Fmax 48.00
Switching Pumps
Time Detected When
10.41 Pump Reaches the 0.0–3600.0 (sec.) 1.0
Stopping Frequency
Pump’s Frequency at Time-
10.42 0.00 Hz–Fmax 0.00
out (Disconnection)
bit0: Determines whether the erroneous pump
switches to an alternative pump when an
10.43 Pump’s Error Treatment error occurs in the running pump 1
0: All pumps stop
1: Switch to an alternative pump

4-21
Chapter 4 ParametersVFD-EL-W

Parameter Explanation Settings Default Customer


bit1: Determines the erroneous pump to be in
a standby or stop status after reset
0: Set the erroneous pump to be in a standby
status after reset
1: Set the erroneous pump to be in a stop
status after reset
bit2: Determines whether the master pump
received the RUN command or not when
an error occurs in the running pump
0: When an error occurs in the running pump,
the master pump does not receive the RUN
command
1: When an error occurs in the running pump,
the master pump can choose to run with an
alternative pump, instead of the erroneous
pump
Selection of Pump’s Start- 0: By pump ID #
10.44 1
up Sequence 1: By running time.
Running Time of Multi-
10.45 pump Under Alternative 0.0–360.0 sec. 60.0
Operation
0: Use the existing setting (default), and
check for any error per the feedback
Specify the Setting for deviation
10.49 Pr.10.12 [PID Deviation 0
Level] 1: Set the low water pressure percentage (%),
and check for any error per the physical
quantity feedback.
Number of Times of
10.50 0–1000 times 0
Restart after PID Fault

4-22
Chapter 4 ParametersVFD-EL-W

4.2 Parameter Settings for Applications


Speed Search
Related
Applications Purpose Functions
Parameters
Before the free-running motor stops
Windmills, winding
Restart a free-running completely, the AC motor drive auto-searches
machines, fans and all 08.04–08.08
motor the motor speed and accelerates when its
inertia loads
speed is the same as the motor speed.

DC Brake before Running


Related
Applications Purpose Functions
Parameters
Windmills, fans, pumps
If the running direction of the free-running
and others rotate freely Keep the free-running 08.00,
motor is not steady, execute DC brake before
without power due to motor at standstill 08.01
start-up.
wind or flow

Energy Saving
Related
Applications Purpose Functions
Parameters
Save energy when the AC motor drive runs at
Punching machines,
Save energy and reduce constant speed, yet has full power
fans, pumps and 08.17
vibration acceleration and deceleration. For precision
precision machinery
machinery, it also helps reduce vibration.

Eight-step Speed Operation


Related
Applications Purpose Functions
Parameters
To control eight-step speed (including master
Cyclic operation at multi- 04.06–04.08
Conveying machinery frequency) and duration by simple contact
step speed 05.00–05.06
signals.

Switching Acceleration and Deceleration Time


Related
Applications Purpose Functions
Parameters
Switch acceleration and When an AC motor drive drives two or more
Auto-turntable for 01.09–01.12
deceleration time through motors, it can reach a high-speed but still start
conveying machinery 04.06–04.08
external signal and stop smoothly.

Overheating Warning
Related
Applications Purpose Functions
Parameters
When an AC motor drive overheats, a
03.00,
Air conditioners Safety measure thermal sensor triggers the overheating
04.06–04.08
warning.

Operation Command
Related
Applications Purpose Functions
Parameters
Select the AC motor drive control by
Select the control signal 02.01,
General application external terminals or digital keypad or
source 04.06–04.08
RS-485.

4-23
Chapter 4 ParametersVFD-EL-W

Frequency Hold
Related
Applications Purpose Functions
Parameters
Acceleration / Hold output frequency during acceleration
General application 04.06–04.08
deceleration pause / deceleration

Auto-restart after Fault


Related
Applications Purpose Functions
Parameters
The AC motor drive can automatically
Air conditioners, remote For continuous and
restart / reset up to 10 times after a fault 08.15, 08.16
pumps reliable operation
occurs.

Emergency Stop by DC Brake


Related
Applications Purpose Functions
Parameters
The AC motor drive can use the DC
brake for emergency stop when a quick
Emergency stop without
High-speed rotors stop is needed without a brake resistor. 08.00–08.03
brake resistor
Take motor cooling into consideration
when using DC braking often.

Over-torque Setting
Related
Applications Purpose Functions
Parameters
Set the over-torque detection level.
When OC stall, OV stall or over-torque
To protect machines and
Pumps, fans and occurs, the drive automatically adjusts
for continuous / reliable 06.00–06.05
extruders the output frequency. It is suitable for
operation
machines like fans and pumps that
require continuous operation.

Upper / Lower Limit Frequency


Related
Applications Purpose Functions
Parameters
When you cannot provide the upper /
Control the motor speed lower limit, gain or bias from external 01.07
Pumps and fans
within upper / lower limit signals, you can set the limits in the AC 01.08
motor drive.

Skip Frequency Setting


Related
Applications Purpose Functions
Parameters
The AC motor drive does not run at
To prevent machine constant speed in the skip frequency
Pumps and fans 08.09–08.14
resonance vibration range. You can set up to three skip
frequency ranges.

Carrier Frequency Setting


Related
Applications Purpose Functions
Parameters
Increase the carrier frequency to reduce
General application Reduce noise 02.03
motor noise.

4-24
Chapter 4 ParametersVFD-EL-W

Keep Running when Frequency Command is Lost


Related
Applications Purpose Functions
Parameters
When the frequency command is lost
because of a system malfunction, the AC
Air conditioners For continuous operation 02.06
motor drive still runs. Suitable for
intelligent air conditioners.

Output Signal during Running


Related
Applications Purpose Functions
Parameters
Signal available to stop braking (brake
General application; Provide a signal for release) when the AC motor drive is
03.00
mechanical brake running status running. (This signal disappears when
the AC motor drive is free-running.)

Output Signal in Zero Speed


Related
Applications Purpose Functions
Parameters
When the drive’s output frequency is
General application; Provide a signal for lower than the minimum output
03.00
machine tools running status frequency, gives a signal for an external
system or control wiring.

Output Signal at Set Frequency


Related
Applications Purpose Functions
Parameters
When the drive’s output frequency
reaches the set frequency (from the
General application; Provide a signal for
frequency command), gives a signal for 03.00
machine tools running status
an external system or control wiring
(frequency reached).

Output Signal at Over-torque


Related
Applications Purpose Functions
Parameters
When the motor over-torque is larger
Machine tools, fans, To protect machines and than the drive's setting level, gives a 03.00,
pumps, and extruders for reliable operation signal to prevent the machine from 06.04–06-05
damage due to load.

Output Signal at Low Voltage


Related
Applications Purpose Functions
Parameters
When low voltage is detected after the
Provide a signal for motor detects the P-N voltages, gives a
General application 03.00
running status signal for an external system or control
wiring.

Output Signal at Desired Frequency


Related
Applications Purpose Functions
Parameters
When the drive’s output frequency
Provide a signal for reaches the desired frequency, gives a
General application 03.00–03.02
running status signal for an external system or control
wiring.

4-25
Chapter 4 ParametersVFD-EL-W

Output Signal for Base Block


Related
Applications Purpose Functions
Parameters
When executing a Base Block, gives a
Provide a signal for
General application signal for an external system or control 03.00
running status
wiring.

Overheating Warning for Heat Sink


Related
Applications Purpose Functions
Parameters
When the heat sink overheats, gives a
General application For safety signal for an external system or control 03.00
wiring.

4-26
Chapter 4 ParametersVFD-EL-W

4.3 Description of Parameter Settings


Group 0: User Parameters
 You can set this parameter during operation.
00.00 AC Motor Drive Identity Code
Settings Read Only Default: ##
00.01 AC Motor Drive Rated Current Display
Settings Read Only Default: #.#
 Pr. 00.00 displays the AC motor drive identity code. The identity code includes the capacity, rated current,
rated voltage and the maximum carrier frequency. The following table explains the identity code.
 Pr.00.01 displays the rated current of the AC motor drive. You can use it to check if the AC motor drive is
correct.
230V Series
kW 0.2 0.4 0.75 1.5 2.2
HP 0.25 0.5 1.0 2.0 3.0
Pr.00.00 0 2 4 6 8
Rated Output Current (A) 1.6 2.5 4.2 7.5 11.0
Max. Carrier Frequency 12 kHz

460V Series
kW 0.4 0.75 1.5 2.2 4.0
HP 0.5 1.0 2.0 3.0 5.5
Pr.00.00 3 5 7 9 11
Rated Output Current (A) 1.5 2.5 4.2 5.5 9.0
Max. Carrier Frequency 12 kHz

00.02 Parameter Reset


Default: 0
Settings 0 Parameter can be read/written
1 All parameters are read-only
8 Keypad lock
9 Reset all parameters to defaults (50Hz, 230V/400V or 220V/380V depending on
Pr.00.12)
10 Reset all parameters to defaults (60Hz, 220V/440V)
 9 or 10: Resets all parameters to defaults when the parameter settings are abnormal.
 9: Resets all parameters to defaults for 50 Hz; the base voltage depends on the Pr.00.12 settings.
 1: All parameters are read-only and you cannot change any parameter settings. Err displays when you enter
any input. To write all parameters, set Pr.00.02 = 0.

00.03 Start-up Display Selection


Default: 0
Settings 0 Display the frequency command value (F)
1 Display the actual output frequency (H)
2 Display the output current in Amps supplied to the motor (A)
3 Display the content of the user-defined unit (U)
4 FWD/REV command
 Determines the start-up display page after power is applied to the drive.

4-27
Chapter 4 ParametersVFD-EL-W

00.04 Content of Multi-function Display


Default: 0
Settings 0 Display the content of the user-defined unit (U)
Display the counter value that counts the number of pulses on
1
TRG terminal (c)
2 Display status of multi-function input terminals

3 Display the actual DC bus voltage in VDC for the AC motor drive
Display the output voltage in VAC for terminals U/T1, V/T2, W/T3
4
to the motor. (E)
5 Display the PID analog feedback signal value in % (b)
Display the power factor angle in º for terminals U/T1, V/T2,
6
W/T3 to the motor (n)
Display the output power in kW for terminals U, V and W to the
7
motor. (P)
8 Display the setting values for PID control and feedback signal.

9 Display the signal of the AVI analog input terminal (V).


Display the signal of the ACI analog input terminal that
10
corresponds to 0–100% (mA/V) (i).
11 Display the temperature of the IGBT in °C (h)
 When you set Pr.00.03 to 3, the display is according to Pr.00.04.

00.05 User-defined Coefficient K Unit: 0.1


Settings 0.1–160.0 Default: 1.0
 Determines the multiplying factor (K) for the user-defined unit.
The display value is calculated as follows:
User-defined unit (U) = Output frequency (H) * User-defined Coefficient (K) (Pr.00.05)

00.06 Software Version


Settings Read Only Default: #.##

00.07 Reserved

00.08 Password Input Unit: 1


Settings 0–9999 Default: 0
 Displayed value 0–2 is the number of wrong password attempts.
 Enter the password that is set in Pr.00.09. Enter the correct password here to enable changing parameter
settings. You are limited to a maximum of three attempts. After three consecutive failed attempts, a blinking
“codE” appears. You must restart the AC motor drive before you can try again to enter the correct password.

00.09 Set Password Unit: 1


Settings 0–9999 Default: 0
 Sets a password to protect your parameter settings.
If the display shows 0, no password is set or the password is correctly set in Pr.00.08. You can then change all
parameters, including Pr.00.09.
The first time you can set a password directly. After successfully setting the password, the display shows 1.
Be sure to record the password for later use.
To cancel the parameter lock, set Pr.00.09 to 0 after entering the correct password in Pr.00.08.
The password consists of between 1–4 digits.
 You can re-enable the password after decoding with Pr.00.08:
Method 1: Enter the original password in Pr.00.09 again (or you can enter a new password; be sure to record it).
Method 2: Restart the drive to re-enable the password function.
4-28
Chapter 4 ParametersVFD-EL-W

Method 3: Enter any value that is not the password in Pr.00.08. (Pr.00.08 displays End regardless of whether the
password is entered correctly.)

Password Decode Flow Chart

00.10 Control Mode


Default: 0
Display 0 V/F Control
1 Vector Control
 Determines the control method for the AC motor drive.
 V/F Control: (Voltage/Frequency Control)
The V/F control is a constant value control mode. In this control mode, frequency decreasing and magnetic
field increasing are under control. But as the frequency decreases, a problem rises: the insufficiency of motor’s
torque in a weaken low frequency magnetic field. To solve this problem, set Pr.07.02 Torque Compensation to
compensate torque then to have the best operating performance. Common applications are water pumps,
conveyors, compressors and treadmills.
 Vector Control:
The vector control mode can eliminate the relationship between the field current vector and the armature flux,
and auto-tune the torque compensation and slip compensation to increase the dynamic response of the motor
drive. Common applications are textile equipment, printing equipment, crane equipment and drilling machinery.
 Related parameter: Pr.07.02 Torque Compensation.

00.11 Reserved

00.12 50 Hz Base Voltage Selection


Default: 0
Settings 0 230V/400V
1 220V/380V
 Determines the base voltage for 50 Hz.

4-29
Chapter 4 ParametersVFD-EL-W

00.13 User-defined Value (corresponds to maximum operating frequency Pr.01.00)


Settings 0–9999 Default: 0
 When Pr.00.13 is not set to 0, “F” automatically disappears in frequency mode and the rightmost digit blinks.
The ranges for many functions display according to Pr.00.13, including the UP/DOWN key on keypad
potentiometer, multi-step speed function, and JOG function.
 When Pr.00.13 is not set to 0, and the frequency source is from communications, use Pr.02.18 to change the
frequency command instead of using communication address 2001H.

00.14 Decimal Place of User-defined Value


Settings 0–3 Default: 0
 Sets the place of decimal point for Pr.00.13.
 Example: If you want to set the user-defined value to 10.0, set Pr.00.13 to 100 and Pr.00.14 to 1.

4-30
Chapter 4 ParametersVFD-EL-W

Group 1: Basic Parameters


 You can set this parameter during operation.
01.00 Maximum Output Frequency (Fmax) Unit: 0.01
Settings 50.00–400.0 Hz Default: 60.00
 Determines the AC motor drive’s Maximum Output Frequency. All the AC motor drive frequency command
sources (analog inputs 0–10 V and 4–20 mA) are scaled to correspond to the output frequency range.

01.01 Motor Rated Frequency (Fbase) Unit: 0.01


Settings 0.10–400.0 Hz Default: 60.00
 Set this value according to the rated motor frequency as indicated on the motor nameplate. The Maximum
Voltage Frequency determines the V/F curve ratio. For example, if the drive is rated for 460 VAC output and
you set the maximum voltage frequency to 60 Hz, the drive maintains a constant ratio of 7.66 V/Hz (460 V / 60
Hz = 7.66 V/Hz). This parameter value must be equal to or greater than the Mid-Point Frequency (Pr.01.03).

01.02 Motor Rated Voltage (Vbase) Unit: 0.1


Settings 230V series 0.1–255.0 V Default: 220.0
460V series 0.1–510.0 V Default: 440.0
 For 230V series, the default is 220.0 V; for 460V series, the default is 440.0 V.
 Sets the maximum output voltage. The setting must be smaller than or equal to the rated motor voltage as
indicated on the motor nameplate.

01.03 Mid-Point Frequency (Fmid) Unit: 0.01


Settings 0.10–400.0Hz Default: 1.50
 Sets the Mid-Point Frequency of any V/F curve. This setting determines the V/F ratio between the Minimum
Frequency and the Mid-Point frequency.

01.04 Mid-Point Voltage (Vmid) Unit: 0.1


Settings 230V series 0.1–255.0 V Default: 10.0
460V series 0.1–510.0 V Default: 20.0
 For 230V series, the default is 10.0 V; for 460V series, the default is 20.0 V.
 Sets the Mid-Point Voltage of any V/F curve. This setting determines the V/F ratio between the Minimum
Frequency and the Mid-Point Frequency.

01.05 Minimum Output Frequency (Fmin) Unit: 0.01


Settings 0.10–400.00 Hz Default: 1.50
 Sets the Minimum Output Frequency of the AC motor drive. This parameter must be equal to or less than the
Mid-Point Frequency (Pr.01.03).

01.06 Minimum Output Voltage (Vmin) Unit: 0.1


Settings 230V series 0.1–255.0 V Default: 10.0
460V series 0.1–510.0 V Default: 20.0
 For 230V series, the default is 10.0 V; for 460V series, the default is 20.0 V.
 Sets the Minimum Output Voltage of the AC motor drive. This parameter must be equal to or less than the Mid-
Point Voltage (Pr.01.04).
 The settings for Pr.01.01–Pr.01.06 must meet the condition of Pr.01.02  Pr.01.04  Pr.01.06 and Pr.01.01 
Pr.01.03  Pr.01.05.

01.07 Output Frequency Upper Limit Unit: 0.1


Settings 0.1–120.0% Default: 110.0
 This parameter must be equal to or greater than the Output Frequency Lower Limit (Pr.01.08). The Maximum
Output Frequency (Pr.01.00) is equal to 100%.
 The Output Frequency Upper Limit value = (Pr.01.00 * Pr.01.07) /100.
4-31
Chapter 4 ParametersVFD-EL-W

01.08 01.07
Output Frequency Output Frequency
Voltage Lower Limit Upper Limit

01.02
Maximum
Output
Voltage

01.04
Mid-point
Voltage
The limit of
Output
Frequency
01.06 Frequency
Minimum
Output
01.05 01.03 01.01 01.00
Mid-point Maximum Voltage Maximum
Voltage Minimum Frequency Output
Output Freq.
Freq. (Base Frequency) Frequency

V/f Curve

01.08 Output Frequency Lower Limit Unit: 0.1


Settings 0.0–100.0% Default: 0.0
 The Output Frequency Lower Limit value = (Pr.01.00 * Pr.01.08) / 100.
 The Upper / Lower Limits are to prevent operation faults and machine damage.
 If the Output Frequency Upper Limit is 50 Hz and the Maximum Output Frequency (Pr.01.00) is 60 Hz, the
Output Frequency will be limited to 50 Hz.
 If the Output Frequency Lower Limit is 10 Hz, and the Minimum Output Frequency (Pr.01.05) is 1.0 Hz, then
any command frequency between 1.0–10 Hz generates a 10 Hz output from the drive. If the command
frequency is less than 1.0 Hz, the drive is in ready status without output.
 If the Output Frequency Upper Limit is 60 Hz and the Maximum Output Frequency (Pr.01.00) is 60 Hz, the
maximum output frequency will not be larger than 60 Hz even executing slip compensation. If the output
frequency must be larger than 60 Hz, adjust the output frequency upper limit or increase the maximum
operation frequency.

01.09 Acceleration Time 1 (Taccel 1) Unit: 0.1/0.01


01.10 Deceleration Time 1 (Tdecel 1) Unit: 0.1/0.01
01.11 Acceleration Time 2 (Taccel 2) Unit: 0.1/0.01
01.12 Deceleration Time 2 (Tdecel 2) Unit: 0.1/0.01
Settings 0.1–600.0 sec. / 0.01–600.00 sec. Default: 10.0
 You can switch the acceleration/deceleration time 1 or 2 by setting the external terminals MI2–MI4 to 7.

01.19 Acceleration / Deceleration Time Unit


Default: 0
Settings 0 Unit: 0.1 sec.
1 Unit: 0.01 sec.
 Use the Acceleration Time to determine the time required for the AC motor drive to ramp from 0.0 Hz to
Maximum Output Frequency (Pr.01.00). Use the Deceleration Time to determine the time required for the AC
motor drive to decelerate from the Maximum Output Frequency (Pr.01.00) down to 0 Hz.
 You select the Acceleration/Deceleration Time 1, 2 with the Multi-function Input Terminals Settings. The
defaults are Acceleration Time 1 / Deceleration Time 1.
 The setting for Pr.01.19 changes the time unit of Pr.01.09–Pr.01.12, Pr.01.13, and Pr.01.14, further changing
the setting range of the acceleration / deceleration time.

4-32
Chapter 4 ParametersVFD-EL-W

Frequency
01.00
Max. output
Frequency

setting
operation
frequency

01.05
Min. output
frequency

0 Hz
Accel. Time Decel. Time Time
01.09 01.11 01.10 01.12
The definition of
Accel./Decel. Time
Resulting Resulting
Accel. Time Decel. Time
Resulting Accel./Decel. Time

01.13 Jog Acceleration Time Unit: 0.1/0.01


Settings 0.1–600.0/0.01–600.0 sec. Default: 1.0
01.14 Jog Deceleration Time Unit: 0.1/0.01
Settings 0.1 to 600.0/0.01 to 600.0 sec. Default: 1.0
01.15 Jog Frequency Unit: 0.01
Settings 0.10 to 400.0 Hz Default: 6.00
 Use only external terminal JOG (setting MI2, MI3 or MI4 to 8). When the Jog command is ON, the AC motor
drive accelerates from the Minimum Output Frequency (Pr.01.05) to the Jog Frequency (Pr.01.15). When the
Jog command is OFF, the AC motor drive decelerates from the Jog Frequency to zero. The
acceleration/deceleration time is set by the Jog Acceleration/Deceleration time (Pr.01.13, Pr.01.14).
 The drive must be stopped before using the JOG command. During Jog operation, other operation commands
are not accepted, except FORWARD/REVERSE commands.
Frequency
01.15
JOG
Frequency

01.05
Min. output
frequency

0 Hz
JOG Accel. Time JOG Decel. Time
Time
01.13 01.14 01.12
The definition of JOG Accel./Decel. Time01.21

01.16 Auto-Acceleration and Auto-Deceleration


Default: 0
Settings 0 Linear acceleration and linear deceleration
1 Auto-acceleration and linear deceleration.
4-33
Chapter 4 ParametersVFD-EL-W

2 Linear acceleration and auto-deceleration.


3 Auto-acceleration and auto-deceleration (set by load)
4 Auto-acceleration and auto-deceleration (set by Acceleration/Deceleration Time
setting)
 With auto-acceleration and auto-deceleration it is possible to reduce vibration and shocks during starting and
stopping the load.
During auto-acceleration, the torque is automatically measured and the drive accelerates to the set frequency
with the shortest acceleration time and the smoothest starting current.
During auto-deceleration, the drive measures the regenerative energy and the motor is stopped smoothly with
the shortest deceleration time.
When this parameter is set to 4, the actual acceleration/deceleration time are equal to or greater than
Pr.01.09–Pr.01.12.
 Auto-acceleration and auto-deceleration makes the complicated processes of tuning unnecessary. It makes
operation efficient and saves energy by acceleration without stalling and deceleration without using the brake
resistor.
 In applications with the brake resistor or brake unit, it is not recommended to use auto-deceleration.

01.17 Acceleration S-Curve Unit: 0.1 / 0.01


01.18 Deceleration S-Curve Unit: 0.1 / 0.01
Default: 0.0 / 0.00
Settings 0.0 S-curve disabled
0.1–10.0/0.01–10.00 S-curve enabled (10.0/10.00 is the smoothest)
 Ensure smooth acceleration and deceleration using an S-curve.
0: Disables the S-curve function.
0.1–10.0/0.01–10.00: Enables the S-curve function.
Setting the parameter to 0.1/0.01 gives the shortest S-curve and setting the parameter to 10.0/10.00 gives the
longest and smoothest S-curve.
 The following diagram shows that the original setting of the Acceleration and Deceleration Time is only for
reference when you enable the S-curve. The actual acceleration and deceleration time depends on the
selected S-curve (0.1 to 10.0). Pr.01.17 must be smaller than Pr.01.09 or Pr.01.11; Pr.01.18 must be smaller
than Pr.01.10 or Pr.01.12. Otherwise, the S-curve is invalid.
The total acceleration time = Pr.01.09 + Pr.01.17 or Pr.01.11 + Pr.01.17
The total deceleration time = Pr.01.10 + Pr.01.18 or Pr.01.12 + Pr.01.18

1 2

3
4

1 2
3
4
1 2
3 4
Disable S curve
Enable S curve
Acceleration/deceleration Characteristics

01.20 Simple Positioning Stop Frequency 0 Unit: 0.01


Settings 0.00–400.00Hz Default: 0.00
01.21 Simple Positioning Stop Frequency 1 Unit: 0.01
Settings 0.00–400.00Hz Default: 5.00
01.22 Simple Positioning Stop Frequency 2 Unit: 0.01
Settings 0.00–400.00Hz Default: 10.00

4-34
Chapter 4 ParametersVFD-EL-W

01.23 Simple Positioning Stop Frequency 3 Unit: 0.01


Settings 0.00–400.00Hz Default: 20.00
01.24 Simple Positioning Stop Frequency 4 Unit: 0.01
Settings 0.00–400.00Hz Default: 30.00
01.25 Simple Positioning Stop Frequency 5 Unit: 0.01
Settings 0.00–400.00Hz Default: 40.00
01.26 Simple Positioning Stop Frequency 6 Unit: 0.01
Settings 0.00–400.00 Hz Default: 50.00
01.27 Simple Positioning Stop Frequency 7 Unit: 0.01
Settings 0.00–400.00 Hz Default: 60.00
 The setting for Pr.01.20–Pr.01.27 must follow the condition below:
 Pr.01.20 ≤ Pr.01.21 ≤ Pr.01.22 ≤ Pr.01.23 ≤ Pr.01.24 ≤ Pr.01.25 ≤ Pr.01.26 ≤ Pr.01.27
 If any two of the parameters (between Pr.01.20–Pr.01.27) have the same stop frequency, set their Delay Time
of Simple Positioning Stop to the same values.

01.28 Delay Time of Simple Positioning Stop 0 Unit: 0.01


Settings 0.00–600.00 sec. Default: 0.00
01.29 Delay Time of Simple Positioning Stop 1 Unit: 0.01
Settings 0.00–600.00 sec. Default: 0.00
01.30 Delay Time of Simple Positioning Stop 2 Unit: 0.01
Settings 0.00–600.00 sec. Default: 0.00
01.31 Delay Time of Simple Positioning Stop 3 Unit: 0.01
Settings 0.00–600.00 sec. Default: 0.00
01.32 Delay Time of Simple Positioning Stop 4 Unit: 0.01
Settings 0.00–600.00 sec. Default: 0.00
01.33 Delay Time of Simple Positioning Stop 5 Unit: 0.01
Settings 0.00–600.00 sec. Default: 0.00
01.34 Delay Time of Simple Positioning Stop 6 Unit: 0.01
Settings 0.00–600.00 sec. Default: 0.00
01.35 Delay Time of Simple Positioning Stop 7 Unit: 0.01
Settings 0.00–600.00 sec. Default: 0.00
 This is valid only when Pr.02.02 motor stop method is set to 4: simple positioning stop.
 The settings 0–7 for Pr.01.20–Pr.01.27 must work with the settings 0–7 for Pr.01.28–Pr.01.35 and correspond
to each other. Below is their corresponding.
(Pr.01.20, Pr.01.28)
(Pr.01.21, Pr.01.29)
(Pr.01.22, Pr.01.30)
(Pr.01.23, Pr.01.31)
(Pr.01.24, Pr.01.32)
(Pr.01.25, Pr.01.33)
(Pr.01.26, Pr.01.34)
(Pr.01.27, Pr.01.35)

 The function of Pr.01.28–Pr.01.35 is simple positioning. Speed starts to decelerate after the time set at
Pr.01.28–Pr.01.35 elapses. The accuracy of positioning is self-assessed by user.

4-35
Chapter 4 ParametersVFD-EL-W

 t  t x  t2   nf
120
S  n x 
 2  p

s: operation distance (revolution) n: rotation speed (revolution/ minute)


n: rotation speed (revolution/second) p: number of poles in the motor
t x : delay time (second) f: operation frequency (Hz)

t 2 : deceleration time (second)

The value of t x in the equation above describes as below.

When the slope is negative (t1 > t2) When the slope is positive (t1 < t2)

As shown in the figure below, assume that the radius of the four-pole motor is r and rotation speed is n (RPM).
n

Example 1
When the motor swivel table rotates at 50 Hz, and Pr.02.02 = 4 [Simple Positioning Stop; E.F.: coast to stop], and
Pr.01.26 = 50 Hz [Simple Positioning Stop Frequency 6], and its corresponding Pr.01.34 = 2 sec. [Delay Time of
Simple Positioning Stop 6], then the deceleration time from 50 Hz to 0 Hz is 10 seconds.
After executing the stop command, Simple Positioning Stop activates, its rotation speed is
n = 120 x 50 / 4 (revolution / minute) = 25 (revolution / second)
The number of revolution of the swivel table = (25 x (2 + 12)) / 2 = 175 (revolutions)

4-36
Chapter 4 ParametersVFD-EL-W

Therefore, the motor’s operation distance after executing the stop command = number of revolutions x
circumference = 175 x 2 πr. It also menas that the swivel table goes back to the top after 175 revolutions.

Example 2
Assume that the motor swivel table rotates at 1.5 Hz, and Pr.01.22 = 10 Hz [Simple Positioning Stop Frequency 2],
and Pr.01.30 = 10 sec. [Delay Time of Simple Positioning Stop 2], then the deceleration time from 60 Hz to 0 Hz is
40 seconds.

The delay time at stop for 1.5 Hz is 1.5 second; the deceleration time from 1.5 Hz to 0 Hz is 1 second.

After executing the stop command, Simple Positioning Stop activates, its rotation speed is
n = 120 x 1.5 / 4 (revolution / minute) = 1.5 / 2 (revolution / second)
The number of revolution of the swivel table = (1.5 / 2 x (1.5 + 2.5)) / 2 = 1.5 (revolutions)

Therefore, the motor’s operation distance after executing the stop command = number of revolutions x
circumference = 1.5 x 2 πr. It also means the swivel table stops after running 1.5 revolutions.

4-37
Chapter 4 ParametersVFD-EL-W

Group 2: Operation Method Parameters


 You can set this parameter during operation.
02.00 First Master Frequency Command Source
Default: 0
02.09 Second Master Frequency Command Source
Default: 0
Settings 0: Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN.
1: 0–10 V from AVI
2: 4–20 mA from ACI
3: RS-485 (RJ45) communication
4: Digital keypad potentiometer
 Sets the Master Frequency Command Source for the AC motor drive.
 Pr.02.09 is only valid when you set one of Pr.04.06, Pr.04.07, or Pr.04.08 = 22. When setting 22 is activated,
the frequency command source is the setting for Pr.02.09. You can only enable only one of the first master
frequency command and second master frequency command sources at one time.
 When using the AVI terminal, pay attention to the ACI / AVI dip switch location on the AC motor drive. If you
select ACI, the drive receives 4–20 mA analog current signal; if you select AVI, the drive receives 0–10 VDC
analog voltage signal.

02.01 First Operation Command Source


Default: 0
Settings 0: Digital keypad
1: External terminals. Keypad STOP/RESET enabled.
2: External terminals. Keypad STOP/RESET disabled.
3: RS-485 communication. Keypad STOP/RESET enabled.
4: RS-485 communication. Keypad STOP/RESET disabled.
 Sets the operation command source of the drive.

02.10 Combining the First and Second Master Frequency Commands


Default: 0
Settings 0: First Master Frequency Command Only
1: First Master Frequency + Second Master Frequency
2: First Master Frequency - Second Master Frequency
02.02 Stop Method
Default: 0
Settings 0: STOP: ramp to stop E.F.: coast to stop
1: STOP: coast to stop E.F.: coast to stop
2: STOP: ramp to stop E.F.: ramp to stop
3: STOP: coast to stop E.F.: ramp to stop
4: Simple positioning stop E.F.: coast to stop
 This parameter determines how the motor is stopped when the AC motor drive receives a valid stop command
or detects an external fault.
Ramp to stop: The AC motor drive decelerates to the Minimum Output Frequency (Pr.01.05) according to the
deceleration time and then stops.
Coast to stop: The AC motor drive stops the output instantly and the motor coasts until it comes to a standstill.
 The motor stop method is usually determined by the characteristics of the motor load and how frequently it is
stopped.
(1) It is recommended that you use “ramp to stop” for the safety of personnel or to prevent material from
being wasted in applications where the motor has to stop after the drive is stopped. Set the deceleration
time accordingly.
(2) If motor coasting is allowed or the load inertia is large, it is recommended that you use “coast to stop”.

4-38
Chapter 4 ParametersVFD-EL-W

Example uses are blowers, punching machines, centrifuges and pumps.


Frequency Frequency
output
output
frequency
frequency
motor
motor
speed
speed

Time Time
stops according to free run to stop
operation decel eration time operation
command RUN STOP command RUN STOP

ramp to stop and free run to stop

Frequency Frequency

frequency output
motor
speed

frequency
motor output
speed

stops according to
operation decel eration time free run to stop
operation
command command

EF EF
When Pr.02.02 is set to 2 or 3 When Pr.02.02 is set to 0 or 1

02.03 PWM Carrier Frequency Selection Unit: 1


Default: 8
Settings 2–12 kHz
 Determines the PWM carrier frequency of the AC motor drive.
Carrier Electromagnetic Heat Current
Acoustic
Frequency Noise or leakage Dissipation Wave
Noise
current
Significant Minimal Minimal Minimal
2kHz

8kHz

12kHz Minimal Significant Significant Significant


 From the table, you can see that the PWM carrier frequency has a significant influence on the electromagnetic
noise, AC motor drive heat dissipation, and motor acoustic noise. The PWM carrier frequency is decreased
automatically according to the ambient temperature and output current of the AC motor drives. It is used to
prevent the AC motor drive from overheating and thus extend the IGBT’s life. Increasing the PWM carrier
frequency may reduce the noise of motor operation, but interference measures have to be taken for the
consideration of overall wiring.

4-39
Chapter 4 ParametersVFD-EL-W

 Take VFD007EL21W(-1) as an example, assume that the ambient temperature is 40°C, the drive output
current must be controlled within 100% of the rated current. If the ambient temperature is 50°C, the drive
output current should not exceed 80% of the rated current. For other models in an ambient temperature of
50°C, the drive output current must be controlled within 100% of the rated current; for other models in an
ambient temperature of 60°C, the drive output current must be controlled within 80% of the rated current.
Rated current (%)

Ambient temperature (°C)


Other models

 Take VFD007EL21W(-1) as an example, assume that the ambient temperature is 40°C, and default carrier
frequency is 8 kHz, then the drive output current reaches 100% of the rated current; if the carrier frequency is
12 kHz, the drive output current must be controlled within 80% of the rated current. If the ambient temperature
is 25°C, the installation method is single drive installation, and the carrier frequency is 12 kHz, then the drive
reaches 100% of the rated current.
Rated current (%)

Carrier Frequency (kHz)


Other models 40°C All models 25°C

NOTE
Other models: VFD002EL21W(-1), VFD004EL21W(-1), VFD015EL21W(-1), VFD022EL21W(-1),
VFD004EL43W(-1), VFD007EL43W(-1), VFD015EL43W(-1), VFD022EL43W(-1), VFD040EL43W(-1)

02.04 Motor Direction Control


Default: 0
Settings 0: Forward / Reverse operation enabled
1: Reverse operation disabled
2: Forward operation disabled
 Disables one direction of rotation for the AC motor drive.

02.05 Power-On Command and Run Command Source Modifies the Drive Operating Control
Default: 1
Settings 0: Start running when power is on.
1: Do not run when power is on.
2: When the source of the command changes, the drive’s operation remains the
same.
3: When the source of the command changes, the drive’s operation follows the new
command.
4: The motor drive can start to run at power on or after reset.
When the source of the command is a two-wire external terminal, the operating

4-40
Chapter 4 ParametersVFD-EL-W

command changes as the external terminal’s status changes.


 Determines the response of the drive at power-on and when the operation command source is changed.
Start lockout Operation status when operation command source is
Pr.02.05
(Run when power is ON) changed
0 AC motor drive runs Keeps previous status
1 AC motor drive does not run Keeps previous status
Changes according to the new operation command
2 AC motor drive runs
source
Changes according to the new operation command
3 AC motor drive does not run
source
4 AC motor drive runs Changes as the external terminal’s status changes
 Use this parameter to determine whether the AC motor drive receives the operation command or not when the
operation command source is the external terminal, the operation command remains, and the AC motor drive
power is ON.
1. 0: The drive receives the operation command and runs immediately.
2. 1: The drive does not receive the operation command. To make the motor run, cancel the operation
command, and then input again.
3. 4: It is an external terminal control setting when the motor drive restarts after an instantaneous power
failure. When the motor drive has an instantaneous power failure, the DC bus decreases to Lv. If you send
a command from the host computer while the DC bus is at Lv, and the operating command is still on
conductive trigger, the motor drive can be restarted.
 Power-on:
When the operation command source is the external terminal and the operation command is ON (MI1-
DCM=closed), the AC motor drive operates according to Pr.02.05 after power is applied.
(1) When you set Pr.02.05 to 0 or 2 or 4, the AC motor drive runs immediately.
(2) When you set Pr.02.05 to 1 or 3, the AC motor drive remains stopped until the operation command is
received after the previous operation command is cancelled.

 When the operation command source is not the external terminals, regardless of whether the AC motor drive
runs or stops, the AC motor drive operates according to Pr.02.05 if the two conditions below are both met.
1. The operation command source is changed to external terminal (Pr.02.01 = 1 or 2)
2. The status of the terminal and the AC motor drive are different.
And the operation of the AC motor drive will be:
1. When you set Pr.02.05 to 0 or 1, the status of the AC motor drive is not changed by the terminal status.
2. When you set Pr.02.05 to 2 or 3 or 4, the status of the AC motor drive is changed by the terminal status.

4-41
Chapter 4 ParametersVFD-EL-W

 When you set Pr.02.05 to 1 or 3, it does not guarantee that the motor will never run under this condition. It is
possible the motor may be set in motion by a malfunctioning switch.

02.06 Loss of ACI Signal (4–20 mA)


Default: 0
Settings 0: Decelerate to 0 Hz
1: Coast to stop and display “AErr”
2: Continue the operation according to the last frequency command
3: Continue the operation according to the setting at Pr.02.11.
 Determines the action when ACI signal is lost.
 1: Display the warning message “AErr” on the keypad when the ACI signal is lost and execute the Pr.02.06
setting. When the ACI signal is recovered, the warning message atomically stops blinking. You can also press
“STOP/RESET” to clear the warning message.

02.07 Up/Down Mode


Default: 0
Settings 0: Digital keypad up/down keys mode
1: Based on Accel./ Decel. Time
2: Constant speed (according to Pr.02.08)
3: Pulse input unit (according to Pr.02.08)
Accel. / Decel. Rate of Change of UP / DOWN Operation with Constant Unit: 0.01
02.08
Speed
Settings 0.01–10.00 Hz/2ms Default: 0.01
 Determine the increase / decrease of the master frequency when operated through the multi-function inputs
and you set Pr.04.06–Pr.04.08 10 (Up command) or 11 (Down command).
 Pr.02.07=0: Use the external terminal’s UP/DOWN keys to increase or decrease the frequency. This is valid
only when the AC motor drive is running.
 Pr.02.07=1: Increase and decrease the frequency by the acceleration and deceleration settings. This is valid
only when the AC motor drive is running.
 Pr.02.07=2: Increase and decrease the frequency by Pr.02.08 settings.
 Pr.02.07=3: Increase and decrease the frequency according to Pr.02.08 (unit: pulse input). Every ON after
OFF is regarded as an input pulse.

02.11 Keypad Frequency Command Unit: 0.01


Settings 0.00–400.00 Hz Default: 60.00
 Sets the frequency command or reads the keypad frequency command.

4-42
Chapter 4 ParametersVFD-EL-W

02.12 Communication Frequency Command Unit: 0.01


Settings 0.00–400.00 Hz Default: 60.00
 Sets the frequency command or reads the communication frequency command.

02.13 Saving Keypad or Communication Frequency Command Selection


Default: 0
Settings 0: Save Keypad & Communication Frequency
1: Save Keypad Frequency Only
2: Save Communication Frequency Only
 Saves the keypad or RS-485 frequency command.

02.14 Initial Frequency Selection (for Keypad & RS-485)


Default: 0
Settings 0 Current Frequency Command
1 Zero Frequency Command
2 Refer to Pr.02.15 to set up
02.15 Initial Frequency Setting (for Keypad & RS-485) Unit: 0.01
Settings 0.00–400.00 Hz Default: 60.00
 Determinates the frequency at stop.
Pr.02.14=0: The initial frequency is the current frequency.
Pr.02.14=1: The initial frequency is 0.
Pr.02.14=2: The initial frequency is the Pr.02.15 setting.

02.16 Display the Master Frequency Command Source


Settings Read Only Default: Read Only

 You can read the master frequency command source from this parameter.
Display Value Bit Function
The Master Frequency Command Source is the First Master Frequency
1 bit0=1
Source (Pr.02.00).
The Master Frequency Command Source is the Second Master Frequency
2 bit1=1
Source (Pr.02.09).
4 bit2=1 The Master Frequency Command Source is the Multi-function input.

02.17 Display the Operation Command Source


Settings Read Only Default: Read Only

 You can read the operation command source from this parameter.
Display Value Bit Function
1 bit0=1 Operation Command Source is the Digital Keypad
2 bit1=1 Operation Command Source is the RS-485 communication
4 bit2=1 Operation Command Source is the External Terminal (MI1)
8 bit3=1 Operation Command Source is the Multi-function Input

02.18 User-defined Value 2 Setting


Settings 0–Pr.00.13 Default: 0
 Reads and writes the user-defined value settings. Changes the operation frequency when Pr.00.13 is not set
to 0 and frequency source is from communication.
4-43
Chapter 4 ParametersVFD-EL-W

02.19 User-defined Value 2


Settings Read only Default: 0
 For example, assume that the frequency source is the first frequency + the second frequency command (the
first frequency source is the digital keypad and the second frequency source is AVI), the user-defined value 1
is set to 180.0 (Pr.00.13 is set to 1800; Pr.00.14 is set to 1).
When AVI=2V, the user-defined value is 36.0 [180.0/(2V/10V)], and the frequency is 12.0 Hz
[36.0/(180.0/60.0)].
When Pr.02.18=30.0, the frequency is 10.0 Hz [30.0/(60.0/180.0)].
At this time, the keypad displays 66.0 (36.0+30.0), and the output frequency is 22.0 Hz (12.0+10.0). If you read
the values by using the communication address, the values display as follows: 2102H and 2103H are 22.0 Hz;
0212H (Pr.02.18) is 30.0 Hz; 0213H (Pr.02.19) is 66.0.

4-44
Chapter 4 ParametersVFD-EL-W

Group 3: Output Function Parameters


 You can set this parameter during operation.
03.00 Multi-function Output Relay (RA1, RB1, RC1)
Default: 8
Settings 0–25

Settings Function Description


0 No Function There is no function for the output terminals.
1 Indication During Run Active when the drive is ready or RUN command is ON.
Indication of Master
2 Active when the AC motor drive reaches the output frequency setting.
Frequency Reached

3 Zero Speed Active when Frequency command is lower than the Minimum Output
Frequency.
Active when the drive detects over-torque. Pr.06.04 sets the over-
4 Over-Torque Detection torque detection level, and Pr.06.05 sets the over-torque detection
time.
Base Block (B.B.) Active when the output of the AC motor drive is shut off during Base
5 Block. You can force Base Block with the multi-function input (setting
Indication
09).
6 Low-Voltage Indication Active when low voltage (Lv) is detected.

7 Operation Mode Indication Active when the operation command is controlled by the external
terminal.
Active when the drive detects abnormal conditions; the contact will be
8 Fault Indication closed (example: oc, ov, oH1, oL, oL1, EF, cF3.0–5, HPF1, 2, 4, ocA,
ocd, ocn).
Desired Frequency
9 Active when the desired frequency (Pr.03.02) is reached.
Reached
Terminal Count Value
10 Active when the counter reaches the Terminal Count Value.
Reached
Preliminary Count Value Active when the drive executes the external counter if the count value
11
Reached is equal to the setting value for Pr.03.06.

12 Over-voltage Stall
Active when the Over-voltage Stall Prevention function is operating.
Prevention
13 Over-current Stall
Active when the Over-current Stall Prevention function is operating.
Prevention
When the IGBT overheats, it signals to prevent OH from turning off the
14 IGBT Overheat Warning drive. When the temperature is higher than 85oC (185oF), it is ON.
When it is lower than 80oC (180oF), it is OFF.
15 Over-voltage Active when the DC bus voltage exceeds the setting level.

16 PID Feedback Error Active when the PID feedback signal is abnormal (refer to Pr.10.08 and
Pr.10.12).
17 Forward Command Active when the direction command is FWD.
18 Reverse Command Active when the direction command is REV.
19 Zero Speed Output Signal Active when the drive is in standby or stop.

20 Warning Active when there is a communication warning (CExx, AoL2, AUE,


FbE, SAvE).
Mechanical Brake Control
21 (Desired Frequency Active when the output frequency  Pr.03.11. Deactivated when the
Reached) output frequency  Pr.03.12 after STOP command.

22 Drive Ready Active when the drive is on and no abnormality is detected.


Multi-pump System Error If any error occurred on the drive for the multi-pump system, the RLY
23
Display (Only Master) outputs.

4-45
Chapter 4 ParametersVFD-EL-W

Settings Function Description


Preheating Function
24 Active when the preheating function is enabled.
Indication
25 Fire Mode Indication Active when MI is set to 27 or 28 (fire mode).

※ “Active” means ON or low voltage.

03.01 Reserved

03.02 Desired Frequency Reached Unit: 0.01


Settings 0.00–400.0 Hz Default: 0.00
 If you set a multi-function output terminal to function as Desired Frequency Reached (Pr.03.00–Pr.03.01 = 09),
then the output is activated when the output frequency reaches the Pr.03.02 setting.
Frequency
detection
master 2Hz 4Hz range
frequency
detection range detection
desired -2Hz range
frequency waiting time
03.02 for DC braking time
frequency during stop

Time
run/stop ON OFF

master freq. attained OFF ON OFF


(output signal)
desired freq. attained OFF ON OFF

setting 03 zero speed indication ON OFF ON

setting 19 zero speed indication ON OFF ON

output timing chart of multiple function terminals


when setting to frequency attained or zero speed indication

03.03 Reserved

03.04 Reserved

03.05 Terminal Count Value Unit: 1


Settings 0–9999 Default: 0
 Sets the count value of the internal counter.
You can use the external multi-function input terminals on the control terminals to trigger the counter. When
the count reaches the setting value, the specified output terminal activates by setting one of the multi-function
input terminals (the count value resets after reaching the setting for Pr.03.05).
NOTE
When the display shows c555, the drive has counted 555 times. If the display shows c555, it means that the
actual counter value is between 5,550 and 5,559.

03.06 Preliminary Count Value Unit: 1


Settings 0–9999 Default: 0
 When the counter value counts from c1 to this setting value, the corresponding multi-function output terminal
activates. You can use it as an indication for the AC motor drive running at low speed to stop when the
counting is going to reach the setting value before stop.
 The timing diagram shows as follows:

4-46
Chapter 4 ParametersVFD-EL-W

2msec
Display
(Pr.00.04=1)
TRG
Counter Trigger
2msec
The width of trigger signal
Preliminary Count Value should not be less than
(Pr. 03.00=11) Ex:03.05=5,03.06=3 2ms(<250 Hz)

Terminal Count Value


(Pr. 03.00=10)

03.07 EF Active when Terminal Count Value Reached


Default: 0
Settings 0: Terminal count value reached, no EF display.
1: Terminal count value reached, EF active.
 If you set this parameter to 1 and the desired counter setting value is reached, the AC motor drive treats it as a
fault. The drive stops and shows the “EF” message on the display. The AC motor drive continues to run until
you press RESET.

03.08 Fan Control


Default: 0
Settings 0: Fan is always ON.
1: One minute after the AC motor drive stops, the fan is OFF.
2: Fan is ON when the AC motor drive runs, fan is OFF when the AC motor drive
stops.
3: Fan is ON when the preliminary heat sink temperature is reached.
4: Fan is ON when the AC motor drive runs; fan is OFF when the AC motor drive
stops. And the fan is in a standby mode at 0 Hz.
 Determines the operation mode of the cooling fan.
 This parameter is only valid for fan cooling models. The 1 HP models have no fans (convective cooling) so this
parameter cannot be used for 1 HP models.

03.09 Reserved

03.10 Reserved

03.11 Mechanical Brake Release Frequency Unit: 0.01


Settings 0.00–20.00 Hz Default: 0.00
03.12 Mechanical Brake Engage Frequency Unit: 0.01
Settings 0.00–20.00 Hz Default: 0.00
 These two parameters set control of the mechanical brake through the output terminals (Relay) by setting
Pr.03.00 to 21. Refer to the following example for details.
Example:
1. Case 1: Pr.03.12  Pr.03.11
2. Case 2: Pr.03.12  Pr.03.11

4-47
Chapter 4 ParametersVFD-EL-W

Frequency
Output

Case 1: Pr.03.12

Pr. 03.11

Case 2: Pr.03.12

Time

Run/Stop

Case 1: Pr.03.00=21

Case 2: Pr.03.00=21

 Pr.03.00 multi-function output terminal 21 (Mechanical Brake Control): When the output frequency reaches
Pr.03.11 (Mechanical Brake Release Frequency), the multi-function output terminal is closed. When the output
frequency reaches Pr.03.12 (Mechanical Brake Engage Frequency), the multi-function output terminal is open.

03.13 Display the Status of the Multi-function Output Terminals


Settings Read Only Default: Read Only

 For the standard AC motor drive, the multi-function output terminals are falling-edge triggered.
 0: Relay is ON; 1: Relay is OFF.

4-48
Chapter 4 ParametersVFD-EL-W

Group 4: Input Function Parameters


 You can set this parameter during operation.
04.00 Keypad Potentiometer Bias Unit: 0. 1
Settings 0.0–100.0% Default: 0.0
04.01 Keypad Potentiometer Bias Polarity
Default: 0
Settings 0: Positive Bias
1: Negative Bias
04.02 Keypad Potentiometer Gain Unit: 0.1
Settings 0.1–200.0% Default: 100.0
Keypad Potentiometer Negative Bias, Reverse Motion
04.03
Enable/Disable
Default: 0
Settings 0: No Negative Bias Command
1: Negative Bias: REV Motion Enabled
 Use Pr.04.00–04.03 for applications that use the potentiometer signal on the digital keypad to adjust the
setting frequency. The potentiometer is not an external device, but you need to use it when setting
parameters. Refer to the following examples to know how to use it.
 As shown in the left figure below, operating the potentiometer on the digital keypad to the leftmost means the
minimum value that the lowest voltage 0 VDC corresponds to. As shown in the right figure below, operating the
potentiometer on the digital keypad to the rightmost means the maximum value that the highest voltage 5 VDC
corresponds to.

The minimum The maximum

Example 1:
You set Pr.02.00 to 4 (the master frequency command comes from keypad potentiometer), set Pr.04.00~04.03
to defaults, and then you can set the main frequency command through the keypad potentiometer.
Frequency/Hz
Pr.01.00 60Hz
Max. Default:
operation Pr.01.00=60 Hz Max. operation frequency
frequency Pr.04.00=0 % Bias adjustment
Pr.04.01=0 Bias direction adjustment
Pr.04.02=100 % Gain of frequency adjustment
Pr.04.03=0 No negative bias command
0Hz
Min.(0V) Max.(5V) Potentiometer
(voltage/V)

4-49
Chapter 4 ParametersVFD-EL-W

Example 2:
If you want the corresponded minimum value to be 12 Hz (the master frequency setting) when operating the
keypad potentiometer to the leftmost, and you set other frequency settings, refer to the diagram below. The
correspondence between the keypad potentiometer (voltage) and setting frequency has been changed from
0–5 V (min.–max.) / 0–60 Hz to 0–4 V / 0–60 Hz. Therefore, the 4 V and above from the keypad potentiometer
all correspond to 60 Hz. To use the full potentiometer range, refer to Example 3.

Example 3:
As shown in this example, the keypad potentiometer can be used for all ranges of 0–5 V / 0–60 Hz settings.
This increases flexibility.

Example 4:
This example shows how to use the first half range 0–2.5 V (min.–1/2 * max.) from the keypad potentiometer
to set 0–60 Hz frequency settings. You can achieve the same results by either adjusting Pr.04.02 gain or
setting Pr.01.00 to 120 Hz.

4-50
Chapter 4 ParametersVFD-EL-W

Example 5:
This example uses a 1 V negative bias. In noisy environments, negative bias can be useful to provide a noise
margin (1 V in this example).

Example 6:
This example uses a negative bias to provide a noise margin. In additional, it uses a potentiometer frequency
gain to reach the Maximum Output Frequency.

Example 7:
In this example, you perform the input to run the motor in both the forward and reverse directions. The motor is
idle when the potentiometer position is at its mid-point. Using the settings in this example disables the external
FWD and REV controls.

4-51
Chapter 4 ParametersVFD-EL-W

Example 8:
This example uses negative slope. With these settings, the AC motor drive always runs in only one direction
(reverse).

04.11 Minimum AVI Voltage


Unit: 0.1
Default: 0.0
Settings 0.0–10.0 V
04.12 Minimum AVI Frequency (percentage of Pr.01.00)
Unit: 0.1
Default: 0.0
Settings 0.0–100.0 % [100% corresponds to Fmax (Pr.01.00)]
04.13 Maximum AVI Voltage
Unit: 0.1
Default: 10.0
Settings 0.0–10.0 V
04.14 Maximum AVI Frequency (percentage of Pr.01.00)
Unit: 0.1
Default: 100.00
Settings 0.00–100.00% [100% corresponds to Fmax (Pr.01.00)]
04.15 Minimum ACI Current
Unit: 0.1
Default: 4.0
Settings 0.0–20.0 mA
04.16 Minimum ACI Frequency (percentage of Pr.01.00)
Unit: 0.1
Default: 0.0
Settings 0.00–100.00% [100% corresponds to Fmax (Pr.01.00)]
04.17 Maximum ACI Current
Unit: 0.1
Default: 20.0
Settings 0.0–20.0 mA
04.18 Maximum ACI Frequency (percentage of Pr.01.00)
Unit: 0.1
Default: 100.0
Settings 0.00–100.00% [100% corresponds to Fmax (Pr.01.00)]
 These parameters set the analog input reference values. The minimum and maximum frequencies are set
based on Pr.01.00 (during open-loop control) as shown in the following diagrams.

4-52
Chapter 4 ParametersVFD-EL-W

04.19 MI Terminal Control Mode Selection


Default: 0
0: Mode 1
Settings (MI1: Start-up/Stop terminal; MI2 & MI3: multi-
function input terminals)
1: Mode 2
(MI1/MI2/MI3 support two-wire/three-wire start-up)
 Determines the MI terminal control modes.
 Mode 1: MI1 is the start-up/stop terminal; MI2 and MI3 are the multi-function input terminals.
 Mode 2: MI1, MI2 and MI3 support the two-wire / three-wire start-up.

04.20 Reserved
04.21 Reserved
04.22 Reserved
04.23 Reserved
04.24 Reserved
04.25 Reserved

04.04 Start-up / Stop Method of MI Terminals and Multi-function Input Selection


Default: 0
Settings

4-53
Chapter 4 ParametersVFD-EL-W

Mode 1 0: MI1 Start-up (keypad FWD lights) / Stop


(Pr.04.19=0)
Mode 2 0: Two-wire (1) MI1, MI2
(Pr.04.19=1)
1: Two-wire (2) MI1, MI2
2: Three-wire, MI1, MI2, MI3
 Pr.04.19 determines the setting range and function for Pr.04.04.
 Mode 1 (Pr.04.19=0): MI1 controls the start-up / stop, and MI2 / MI3 / MI4 are set as multi-function terminals.
 Mode 2 (Pr.04.19=1): two-wire (1)/two-wire (2) MI1 and MI2 are used for start-up/stop and forward/reverse
control; MI3 and MI4 are set as multi-function terminals; three-wire (MI1, MI2 and MI3) are used for start-
up/stop and forward/reverse control; MI4 is set as the multi-fucntion terminal.
 There are four different control modes:
Setting for Pr.04.19 Setting for Pr.04.04 External terminal control circuit

Pr.04.04=0
Mode 1
Single-wire
Pr.04.19=0
FWD/STOP

Pr.04.04=0
Two-wire (1)
FWD/STOP,
REV/STOP

Pr.04.04=1
Mode 2 Two-wire (2)
Pr.04.19=1 RUN/STOP,
REV/FWD

Pr.04.04=2
Three-wire
Operation Control

04.05 Reserved
04.06 Start-up/Stop or Multi-function Input Terminal (MI2)
Default: 1
04.07 Start-up/Stop or Multi-function Input Terminal (MI3)
Default: 2
04.08 Multi-function Input Terminal (MI4)
Default: 3
Settings 0–28

Settings Function Description


Program any unused terminals to 0 to ensure they have no effect
0 No Function
on operations.
1 Multi-Step Speed Command 1
Use these three terminals to set the seven-step speed operation.
2 Multi-Step Speed Command 2 There are nine steep speed frequencies (including Master
Frequency and Jog Frequency) available.
3 Multi-Step Speed Command 3
4 Reserved

4-54
Chapter 4 ParametersVFD-EL-W

Settings Function Description


5 External Reset Use this terminal to reset the drive after drive faults are cleared.
When you enable this function, the drive stops acceleration and
deceleration immediately. The AC motor drive resumes from the
inhibit point once this function is disabled.

6 Accel./ Decel. Inhibit

Selects the acceleration and deceleration time of the drive with this
terminal; there are two acceleration and deceleration selections.

The 1st, 2nd acceleration or


7
deceleration time selection

Executes the JOG operation only when the drive stops completely.
While running, you can still change the operation direction, and the
8 JOG Operation Control STOP key on the keypad is valid. Once the external terminal
receives the OFF command, the motor stops in the JOG
deceleration time. Refer to Pr.01.13–Pr.01.15 for details.
When the AC motor drive receives a Base Block signal, it blocks all
output and the motor coasts. When Base Block control is
deactivated, the AC drive starts its speed search function and
synchronizes with the motor speed. It then accelerates to the
Master Frequency. Refer to Pr.08.06–Pr.08.07 for details.

External Base Block


9
(Refer to Pr.08.06)

ON: the frequency of the drive increases or decreases by one unit.


UP: Increase Master
10 If this function remains ON continuously, the frequency increases or
Frequency
decreases according to Pr.02.07 / Pr.02.08 settings.

4-55
Chapter 4 ParametersVFD-EL-W

Settings Function Description


These two functions are the same as the up / down key on the
DOWN: Decrease Master digital keypad, but are only valid when the frequency command
11 source is set as digital keypad (Pr.02.00 / 02.09=0). You cannot use
Frequency
these two functions to change the parameter setting.
Uses external signals such as connecting ON/OFF switch,
lightening senor, etc., to trigger the counter. You can also use
signals of the multi-function output terminal (counter reached,
12 Counter Trigger
desired counter reached) to control the applications that based on
the counter. For example: winding machine, packing machine.
(Refer to Pr.03.05 and Pr.03.06 for details.)
ON: the current counter value is cleared and displays “c 0”. The
13 Counter Reset
drive starts to count up only when this function is disabled.
When the drive receives status change from the EF terminal, the
output of the drive stops immediately, and displays EF on the
14 External Fault
keypad. The motor coasts. The drive keeps running until the fault is
cleared after you press RESET on the keypad (EF: External Fault).
15 PID function disabled ON: the PID function is disabled.
AC motor drive stops output and the motor coasts if one of these
16 Output Shutoff Stop settings is enabled. If the status of terminal is changed, AC motor
drive restarts from 0 Hz.
17 Parameter lock enable Locks all parameters and disables writing parameters.
ON: Operation command through External Terminals
Operation Command Selection
OFF: Operation command through Pr.02.01 setting
18 (Pr.02.01 setting/external
terminals) When 18, 19, and 20 are ON at the same time, the priority is
settings 18 > setting 19 > setting 20.
ON: Operation command through Digital Keypad
Operation Command Selection
OFF: Operation command through Pr.02.01 setting
19 (Pr.02.01 setting/Digital
Keypad) When 18, 19 and 20 are ON at the same time, the priority is setting
18 > setting 19 > setting 20.
ON: Operation command through the Communication
Operation Command Selection
OFF: Operation command through Pr.02.01 setting
20 (Pr.02.01 setting/
Communication) When 18, 19 and 20 are ON at the same time, the priority is setting
18 > setting 19 > setting 20.
This function has top priority to set the running direction (If
21 Forward/Reverse
“Pr.02.04=0”).
Select the first or second Frequency command source. Refer to
Second frequency command Pr.02.09.
22
source enabled ON: Second Frequency command source
OFF: First Frequency command source
Simple positioning stop by If a motor receives such signal while running forward, it stops running
23
forward limit forward.
Simple positioning stop by If a motor receives such signal while running in reverse, it stops
24
reverse limit running in reverse.
Multi-pump control by Hand or When this function is enabled, switch to hand or auto mode from this
25
Auto mode terminal.
Auto-trigger preheating When this function is enabled, control the motor preheating function
26
function from this terminal.

Fire mode enabled When this function is enabled, the fire mode is activated. The drive
27 displays fire message but does not run automatically. You must give
(without Operation Command) the operation command to make the drive run.

Fire mode enabled When this function is enabled, the fire mode is activated. The drive
28 displays fire message, runs and automatically accelerates to Pr.08.24
(with Operation Command) setting values.

4-56
Chapter 4 ParametersVFD-EL-W

04.09 Multi-function Input Contact Selection Unit: 1


Settings 0–63 Default: 0
 Sets the contact status of external multi-function input terminals MI2–MI4 to be normally open (N.O.) or
normally closed (N.C.) according to the start-up / stop mode (Pr.04.19 and Pr.04.04).
 When the start-up/stop mode is single-wired, MI1 setting is invalid; when the start-up/stop mode is two-wired,
MI2 setting is invalid; when the start-up/stop mode is three-wired, MI2 and MI3 settings are invalid. See the
table below for details.

Start-up / Stop Mode MI4 MI3 MI2 MI1 The Setting of the MI Terminals
The Terminals
Bit Bit Bit Bit Multi-function Input Occupied by the
Mode Pr.04.19 Pr.04.04
3 2 1 0 Terminals Start-up / Stop
Function
MI4, MI3, MI2 can be MI1 is only controlled
Single-wire 0 0 0/1 0/1 0/1 -
set as N.O. or N.C. by external terminals
MI1, MI2 are only
MI4, MI3 can be set
Two-wire 1 0 or 1 0/1 0/1 - - controlled by
as N.O. or N.C.
external terminals
MI1, MI2, MI3 are
MI4 can be set as
Three-wire 1 2 0/1 - - - only controlled by
N.O. or N.C.
external terminals

 Setting method: When setting this parameter, covert Bit3–Bit0 that represent the status of MI4–MI1 from
binary to decimal.
For example: setting MI3 and MI4 to be 1 = N.C.; seting MI1 and MI2 to be 0 = N.O.
The setting value for Pr.04.09 should be 12.

04.10 Digital Terminal Input Response Time Unit: 1 msec


Settings 1–20 (*2ms) Default: 1
 This parameter delays the signals on digital input terminals. A value of 1=2 ms, 2=4 ms, and so on. The delay
time helps with noisy signals that could cause the digital terminals to malfunction. This parameter could
effectively improve the interference, but the response time will be delayed.

04.26 Display the Status of Multi-function Input Terminal


Settings Read Only Default: Read Only
 Displays 63 in Pr.04.26 when all the MI terminals are not active.
1. When MI1 (corresponds to bit0) is triggered, and the weight is 1, Pr.04-26=62 (63-1).
2. When MI2 (corresponds to bit1) is triggered, and the weight is 2, Pr.04-26=61 (63-2).
4-57
Chapter 4 ParametersVFD-EL-W

3. When MI3 (corresponds to bit2) is triggered, and the weight is 4, Pr.04-26=59 (63-4).
4. When MI4 (corresponds to bit3) is triggered, and the weight is 8, Pr.04-26=55 (63-8).
5. If more than one MI terminals are triggered, use 63 minus the weight that corresponds to the MI terminal.

For example, if you set MI2 and MI3 to ON, Pr.04.26 displays 57 (63-2-4=57, decimal)

04.27 Internal/External Multi-function Input Terminals Selection Unit: 1


Settings 0–4095 Default: 0
 Selects the terminals MI1–MI4 to be either internal terminal or external terminal. You can activate internal
terminals with Pr.04.28. A terminal cannot be both an internal terminal and an external terminal at the same
time.

 When setting this parameter, convert Bit3–Bit0 that represent the status of MI4–MI1 from binary to decimal.
Set MI3 and MI4 as internal terminals; set MI1 and MI2 as external terminals. Pr.04-27 should be set to 12.

04.28 Internal Terminal Status Unit: 1


Settings 0–4095 Default: 0
 Sets the internal terminal action (ON/OFF) through the keypad or communication. And use this parameter
with Pr.04.27.

4-58
Chapter 4 ParametersVFD-EL-W

For example, to activate MI3 and MI4, set Pr.04.28 to 12.

04.29 Delay Time of Multi-function Input Terminal (MI1) Turn On


Settings 0.00–360.00 sec. Default: 0.00

04.30 Delay Time of Multi-function Input Terminal (MI1) Turn Off


Settings 0.00–360.00 sec. Default: 0.00

04.31 Delay Time of Multi-function Input Terminal (MI2) Turn On


Settings 0.00–360.00 sec. Default: 0.00

04.32 Delay Time of Multi-function Input Terminal (MI2) Turn Off


Settings 0.00–360.00 sec. Default: 0.00

04.33 Delay Time of Multi-function Input Terminal (MI3) Turn On


Settings 0.00–360.00 sec. Default: 0.00

04.34 Delay Time of Multi-function Input Terminal (MI3) Turn Off


Settings 0.00–360.00 sec. Default: 0.00
 The delay function of multi-function input terminals ON/OFF: In the testing process of automatic production
line, the conveyor uses photoelectric switch as a triggered switch for the position reached, which means the
conveyor stops once the product arrives the specified position. However, there may be a difference between
the installation position of the photoelectric switch and the specified position the product arrives. Therefore,
this delay time function is added for the convenience of tuning.

4-59
Chapter 4 ParametersVFD-EL-W

Group 5: Multi-Step Speed Parameters


 You can set this parameter during operation.
05.00 1st Step Speed Frequency Unit: 0.01
05.01 2nd Step Speed Frequency Unit: 0.01
05.02 3rd Step Speed Frequency Unit: 0.01
05.03 4th Step Speed Frequency Unit: 0.01
05.04 5th Step Speed Frequency Unit: 0.01
05.05 6th Step Speed Frequency Unit: 0.01
05.06 7th Step Speed Frequency Unit: 0.01
Settings 0.00–400.00Hz Default: 0.00
 The multi-function input terminals (refer to Pr.04.06–Pr.04.08) select one of the AC motor drive multi-step
speeds (maximum of seven speeds). The speeds (frequencies) are determined by Pr.05.00–Pr.05.06 as
shown in the following table.
Multi-step speed Multi-step speed Multi-step speed
Parameter
command 1 command 2 command 3
Master Master speed
OFF OFF OFF
frequency
1st speed 05.00 ON OFF OFF
2nd speed 05.01 OFF ON OFF
3rd speed 05.02 ON ON OFF
4th speed 05.03 OFF OFF ON
5th speed 05.04 ON OFF ON
6th speed 05.05 OFF ON ON
7th speed 05.06 ON ON ON

4-60
Chapter 4 ParametersVFD-EL-W

Group 6: Protection Parameters


 You can set this parameter during operation.
06.00 Over-Voltage Stall Prevention Unit: 0.1
Settings 230V series 330.0–410.0V Default: 390.0
460V series 660.0–820.0V Default: 780.0
 The default for 230V series is 390.0; the default for 460V series is 780.0.
 0.0: Disables the Over-voltage Stall Prevention (with brake unit or brake resistor)
 During deceleration, the DC bus voltage may exceed its Maximum Allowable Value due to motor regeneration.
When this function is enabled, the AC motor drive does not decelerate further and keep the output frequency
constant until the voltage drops below the preset value again.
 This parameter is suitable for uncertain load inertia. In normal inertia load condition, over-voltage stall
prevention does not occur and the actual deceleration time is the deceleration time setting. However, when the
load inertia is large, the AC motor drive automatically increases the deceleration time until it stops. You can
also install a brake resistor to absorb the excessive regenerative voltage. If the deceleration time affects your
application, it is not recommended to use this function.
high voltage at DC side

over-voltage
detection level

time
output
frequency

Frequency Held

Deceleration characteristic
when Over-Voltage Stall
Prevention enabled

time

previous deceleration time

actual time to decelerate to stop when over-voltage


stall prevention is enabled

06.01 Over-Current Stall Prevention during Acceleration Unit: 1


Settings 20–250% Default: 170
0: Disable
 A setting of 100% is equal to the AC motor drive’s Rated Output Current.
 During acceleration, the AC motor drive output current may increase abruptly and exceed the value specified
in Pr.06.01 due to rapid acceleration or excessive load on the motor. When this function is enabled, the AC
motor drive stops accelerating and keeps the output frequency constant until the current drops below this
setting.

4-61
Chapter 4 ParametersVFD-EL-W

06.01
Over-Current output current
Detection
Level setting
frequency

Over-Current Stall
prevention during
Acceleration, Output
frequency held Frequency

time

previous acceleration time


actual acceleration time when over-current stall
prevention is enabled

06.02 Over-current Stall Prevention during Operation Unit: 1


Settings 20–250% Default: 170
0: Disable
 If the output current exceeds the setting for Pr.06.02 when the drive is operating, the drive decreases its output
frequency to prevent motor stall. If the output current is lower than the setting for Pr.06.02, the drive
accelerates again to catch up with the set frequency command value.
Over-Current Stall
Prevention during
Over-Current Operation, output
Detection frequency decrease
Level
06.02 Output Current

Output
Frequency

over-current stall prevention during operation

06.03 Over-torque Detection Mode (OL2)


Default: 0
Settings 0
Over-torque detection disabled.
1
Over-torque detection enabled during constant speed operation. After over-
torque is detected, keep running until OL1 or OL occurs.
2 Over-torque detection enabled during constant speed operation. After over-
torque is detected, stop running.
3 Over-torque detection enabled during acceleration. After over-torque is
detected, keep running until OL1 occurs.
4 Over-torque detection enabled during acceleration. After over-torque is
detected, stop running.
 Determines the operation mode of the drive after detecting over-torque (OL2). It uses the following methods:
1. If the output current exceeds the Over-torque Detection Level (Pr.06.04) and the detection time is
longer than the setting for Pr.06.05 (Over-torque Detection Time), the warning message “OL2”
displays.
2. If a multi-functional output terminal is set to over-torque detection (Pr.03.00=4), the output is ON. Refer
to Pr.03.00 for details.

06.04 Over-torque Detection Level Unit: 1


Settings 10–200% Default: 150

4-62
Chapter 4 ParametersVFD-EL-W

 This setting is proportional to the Rated Output Current of the drive.


06.05 Over-torque Detection Time Unit: 0.1
Settings 0.1–60.0 sec. Default: 0.1
 Sets the length of time that over-torque must be detected before “OL2” displays.
 Over-torque is detected when the following occurs:
1. The output current exceeds the Over-torque Detection Level (Pr.06.04).
2. The over-toque time exceeds the Over-torque Detection Time (Pr.06.05).
If a multi-function output terminal is set to over-torque detection (Pr.03.00=4) , the contact is “closed”.
Refer to Pr.03.00 for details.

06.06 Electronic Thermal Overload Relay Selection (OL1)


Default: 2
Settings 0 Standard Motor (self-cooled by fan)
1 Special Motor (forced external cooling)
2 Disable
 Sets the operation of the electronic thermal overload relay that protects the motor from overloading or
overheating. When the motor (self-cooled by fan) operates in low frequency, overloads rarely happen. Refer to
the following figures.
rated current of the m otor%

rated current of the motor%


100 100
80 80
60 60
40 40
20 20

25 50 100 150 25 50 100 150


rated frequency of the motor % rated frequency of the motor %
Standard motor Special Motor
(self-cooled by fan) (forced external cooling)

06.07 Electronic Thermal Characteristic Unit: 1


Settings 30–600 sec Default: 60
 Determines the time required to activate the I2t electronic thermal protection function. The figure below shows
I2t curves for 150% output power for one minute.
Operation
time (seconds)
350

300
50Hz or more
250 10Hz
5Hz
200

150

100

50
Load
0 50 100 150 200 250 factor (%)

06.08 Present Fault Record


06.09 Second Most Recent Fault Record
06.10 Third Most Recent Fault Record
06.11 Fourth Most Recent Fault Record
06.12 Fifth Most Recent Fault Record
Display 0–40 Default: 0
Readings 0 No fault
1 Over-current (oc)
2 Over-voltage (ov)
4-63
Chapter 4 ParametersVFD-EL-W

3 IGBT overheat (oH1)


4 Reserved
5 Overload (oL)
6 Overload (oL1)
7 Motor overload (oL2)
8 External Fault (E.F.)
9 Current exceeds two times the rated current during acceleration (ocA)
10 Current exceeds two times the rated current during deceleration (ocd)
11 Current exceeds two times the rated current during constant speed operation
(ocn)
12 Reserved
13 Reserved
14 Phase-loss (PHL)
15 Reserved
16 Auto-acceleration / auto-deceleration failure (CFA)
17 Software/password protection (codE)
18 Power Board CPU WRITE failure (cF1.0)
19 Power Board CPU READ failure (cF2.0)
20 CC, OC Hardware protection failure (HPF1)
21 OV Hardware protection failure (HPF2)
22 Reserved
23 OC Hardware protection failure (HPF4)
24 U-phase error (cF3.0)
25 V-phase error (cF3.1)
26 W-phase error (cF3.2)
27 DC bus error (cF3.3)
28 IGBT Overheat error (cF3.4)
29–31 Reserved
32 Reserved
33 Reserved
34 Motor PTC overheat protection (PtC1)
35 FBE_ERR: PID feedback error (Incorrect feedback signal)
36 dEv: unusual PID feedback deviation
37 OPHL
38–40 Reserved
 Pr.06.08 to Pr.06.12 store the five most recent faults that occurred. After clearing the cause of the faults, use
the RESET command to reset the drive.

06.13 Motor Disconnection Detection Time Unit: 1


Settings 0.1–60.0 sec. Default: 0.0
0.0: Disable
06.14 Motor Disconnection Detection Current Level
Settings 10–100% Default: 30
 Use Pr.06.13 with Pr.06.14. When three-phase imbalance occurs among three-phase motors and the
imbalance reaches Pr.06.14 setting percentage (the percentage is 100% equal to the AC motor drive's rated
current settings in Pr.00.01), and lasts the time set in Pr.06.13, OPHL warning displays and the drive stops to
prevent the motor from damage due to the three-phase unbalanced operation.

4-64
Chapter 4 ParametersVFD-EL-W

Group 7: Motor Parameters


 You can set this parameter during operation.
07.00 Motor Rated Current Unit: 0.1
Settings 23% FLA–120% FLA Default: 100
 Use the following formula to calculate the percentage value entered in this parameter:
FLA = (Motor Current / AC Motor Drive Current) x 100%
Motor Current = Motor rated current in A on the motor nameplate
AC Motor Drive Current = Rated current of AC motor drive in A (see Pr.00.01)

07.01 Motor No-load Current Unit: 0.1


Settings 0% FLA–99% FLA Default: 40
 The rated current of the AC motor drive is equal to 100%. The setting for the motor no-load current affects the
slip compensation.
 The setting value must be smaller than Pr.07.00 (Motor Rated Current).

07.02 Torque Compensation Unit: 0.1


Settings 0.0–10.0 Default: 0.0
 Sets the AC motor drive to automatically increase voltages to get a higher torque when the AC motor drive is
running.
 Note that too high a torque compensation can overheat the motor.

07.03 Slip Compensation Gain Unit: 0.01


Settings 0.00–10.00 Default: 0.00
 For an asynchronous motor, increasing the load on the AC motor drive causes slip to increase and results in
decreased speed. Use this parameter to compensate for slip by increasing the output frequency. When the
output current of the AC motor drive is larger than the motor no-load current value (Pr.07.01), the AC motor
drive adjusts the output frequency according to this parameter.

07.04 Motor Parameter Auto-Tuning


Settings 0: Disable Default: 0
1: Auto-tuning R1 (Motor does not run)
2: Auto-tuning R1 + No-load current (with
running motor)
 Start auto-tuning by pressing the RUN key after you set this parameter to 1 or 2.
1: Auto-detect only the R1 value, and manually enter Pr.07.01.
2: Unload the AC motor drive and automatically set the values for Pr.07.01 and Pr.07.05.
The steps for auto-tuning are:
1. Ensure that all the parameters are set to defaults and the motor wiring is correctly.
2. Ensure that the motor is not loaded before executing auto-tuning and that the shaft is not connected to
any belt or reducer.
3. Enter the correct settings for Pr.01.01 Motor Rated Frequency (Fbase), Pr.01.02 Motor Rated Voltage
(Vbase), Pr.07.00 Motor Rated Current, and Pr.07.06 Motor Rated Slip (Motor 0).
4. After you set Pr.07.04 to 2, the AC motor drive executes auto-tuning immediately after receiving a RUN
command (CAUTION: the motor will run!). The total auto-tuning time is 15 seconds = Pr.01.09 + Pr.01.10.
Higher-power drives need longer acceleration and deceleration time (the default is recommended). After
executing auto-tuning, it sets Pr.07.04 to 0.
5. After executing auto-tuning, check to ensure there are values filled in for Pr.07.01 and Pr.07.05. If not,
press the RUN key after setting Pr.07.04 again to repeat auto-tuning.
6. Finally, set Pr.00.10 to 1 and set other parameters according to your application requirements.
 Related parameters: Pr.01.01 Motor Rated Frequency (Fbase); Pr.01.02 Motor Rated Voltage
(Vbase); Pr.07.00 Motor Rated Current; Pr.07.01 Motor No-Load Current; Pr.07.05 Motor Line-to Line
Resistance R1 (Motor 0); Pr.07.06 Motor Rated Slip (Motor 0).
. NOTE
1. In vector control mode, it is not recommended to have motors run in parallel.
4-65
Chapter 4 ParametersVFD-EL-W

2. Vector control mode is not recommended if the motor rated power exceeds the rated power of the AC
motor drive.

07.05 Motor Line-to-line Resistance R1 (Motor 0)


Settings 0–65535 mΩ Default: 0
 The motor auto-tuning procedure sets this parameter. You can also set this parameter without using Pr.07.04
(Motor Parameter Auto-Tuning). This resistance value is the R value between phase and phase of the motor.
Regardless of the motor wiring method, this resistance value is the measured value of any two motor leads.

07.06 Motor Rated Slip (Motor 0)


Settings 0.00–20.00 Hz Default: 3.00
 Sets the motor rated slip. Enter the actual rated RPM from the motor nameplate.
 Refer to the rated RPM and the number of poles from the motor nameplate and use the following equation to
calculate the rated slip:
Rated Slip = F – N  P / 120
F: Rated frequency (Hz)
N: Rated speed (RPM)
P: Number of poles (Pole)
Assume that the rated frequency of the motor is 60 Hz with 4 poles, and the rated RPM is 1650. The rated
slip calculated by the formula is 60 Hz – (1650 rpm  4 / 120) = 5 Hz.
 This parameter is related to Pr.07.03 Slip Compensation Gain. To get the best slip compensation effect, you
must enter the correct settings. The incorrect setting may cause invalid slip compensation and even damage
the motor and the AC motor drive.
 Related parameter: Pr.07.03 Slip Compensation Gain

07.07 Slip Compensation Limit


Settings 0–250% Default: 200
 This parameter sets the upper limit of the compensation frequency (the percentage of Pr.07.06). If the motor
speed is lower than the target speed and the speed does not change after adjusting the Pr.07.03 setting, the
AC motor drive may reach the upper limit of the compensation frequency and you may need to increase the
Pr.07.07 setting.
 Related parameters: Pr.07.03 Slip Compensation Gain, Pr.07.06 Motor Rated Slip (Motor 0).

07.08 Torque Compensation Time Constant


Settings 0.01–10.00 sec. Default: 0.10
 This function is usually applied in applications with heavy load where the motor current changes frequently for
the current compensation to increase the output torque. The frequent current change can cause machine
vibration. Increase the Pr.07.08 setting to solve this problem.

07.09 Slip compensation Time Constant


Settings 0.05–10.00 sec. Default: 0.20
 This function is usually applied in applications with heavy load where the motor speed changes frequently for
the speed compensation to reach the synchronous speed. The frequent speed change can cause machine
vibration. Increase the Pr.07.09 setting to solve this problem.
 Setting the time constants too high (set Pr.07.08 and Pr.07.09 to 10) results in slow response; setting them too
low results in unstable operation.

07.10 Accumulated Motor Operation Time (Minute) Unit: 1


Settings 0–1439 Default: 0
07.11 Accumulated Motor Operation Time (Day) Unit: 1
Settings 0–65535 Default: 0
 Pr.07.10 and Pr.07.11 record the motor operation time. Clear the values by setting them to 0. Any time that is
less than one minute is not recorded.

4-66
Chapter 4 ParametersVFD-EL-W

07.12 Motor PTC Overheat Protection Unit: 1


Default: 0
Settings 0 Disable
1 Enable
07.14 Motor PTC Overheat Protection Level Unit: 0.1
Settings 0.1–10.0 V Default: 2.4
 Running the motor at low frequency for a long time reduces the cooling function of the motor fan. To prevent
overheating, use a Positive Temperature Coefficient thermistor on the motor, and connect the thermistor
output signal to the drive’s corresponding control terminals.
 When you set the source of the first and second frequency command to AVI (Pr.02.00=1 / Pr.02.09=1), you
disable the motor PTC overheat protection (that is, Pr.07.12 cannot be set to 1).
 If the temperature exceeds the setting level, the motor coasts to stop and PtC1 ( ) displays. When the
temperature decreases below the level of (Pr.07.15 minus Pr.07.16) and stops blinking, you can press
the RESET key to clear the fault.
 Pr.07.14 (overheat protection level) must be greater than Pr.07.15 (overheat warning level).
 The PTC function uses the AVI-input and is connected with a resistor-divider as shown in the diagram below.
1. The voltage between +10 V to ACM: between 10.4–11.2 V.
2. The impedance for AVI is around 47 kΩ.
3. The recommended value for the resistor-divider R1 is 1–10 kΩ.
4. Please contact your motor dealer for the temperature curve and resistance value for the PTC function.

 Refer to the following calculation for the protection and warning levels.
1. Protection level
Pr.07.14 = V+10 * (RPTC1//47k) / [R1+( RPTC1//47k)]
2. Warning level
Pr.07.15 = V+10 * (RPTC2//47k) / [R1+( RPTC2//47k)]
3. Definition:
V+10: voltage between +10 V to ACM, Range 10.4–11.2 V
RPTC1: motor PTC overheat protection level; set the corresponding voltage level in Pr.07.14
RPTC2: motor PTC overheat warning level; set the corresponding voltage level in Pr.07.15
47 kΩ: the AVI input impedance
R1: resistor-divider (recommended value: 1–10 kΩ)
 Example: using a standard PTC thermistor, if the protection level is 1330 Ω, the voltage between +10 V to
ACM is 10.5 V and resistor-divider R1 is 4.4 kΩ. Refer to the following calculation for the Pr.07.14 setting.
1330//47000 = (1330*47000) / (1330+47000) = 1293.4
10.5*1293.4 / (4400+1293.4) = 2.38(V) ≒ 2.4(V)
Therefore, set Pr.07.14 to 2.4.

4-67
Chapter 4 ParametersVFD-EL-W

resistor value ( Ω)

1330

550

Tr temperature (℃)
Tr-5℃ Tr+5℃

07.15 Motor PTC Overheat Warning Level Unit: 0.1


Settings 0.1–10.0 V Default: 1.2
07.16 Motor PTC Overheat Reset Delta Level Unit: 0.1
Settings 0.1–5.0 V Default: 0.6
07.17 Motor PTC Overheat Action
Default: 0
Settings 0 Warn and ramp to stop
1 Warn and coast to stop
2 Warn and keep operating
 If the temperature exceeds the motor PTC Overheat Warning Level (Pr.07.15), the drive acts according to
Pr.07.17 and displays PtC2 ( ) on the digital keypad. If the temperature decreases below the result of
(Pr.07.15 minus Pr.07.16), the warning message disappears.

07.13 Motor PTC Protection Input Response Time Unit: 1


Settings 0–9999 (*2 ms) Default: 100

4-68
Chapter 4 ParametersVFD-EL-W

Group 8: Special Parameters


 You can set this parameter during operation.
08.00 DC Brake Current Level Unit: 1
Settings 0–100% Default: 0
 Sets the level of the DC Brake Current output to the motor during start-up and stopping. When setting the DC
Brake Current, the AC Motor Drive Rated Current (Pr.00.01) is equal to 100%. It is recommended to start with
a low DC Brake Current Level and then increase it until you reach the proper holding torque.

08.01 DC Brake Time during Start-up Unit: 0.1


Settings 0.0–60.0 sec. Default: 0.0
 Determines the duration of the DC Brake current after a RUN command. When the time has elapsed, the AC
motor drive starts accelerating from the Minimum Output Frequency (Pr.01.05).

08.02 DC Brake Time during Stopping Unit: 0.1


Settings 0.0–60.0 sec. Default: 0.0
 Determines the duration of the DC Brake current during stopping. If you want to stop the motor with the DC
Brake, set Pr.02.02 (Stop Method) to 0 or 2 for Ramp to Stop.

08.03 Start-point for DC Brake Unit: 0.01


Settings 0.00–400.00 Hz Default: 0.00
 Determines the frequency at which the DC Brake is applied during deceleration.

 Use the DC Brake during Start-up for loads that may move before the AC drive starts, such as fans and
pumps. The DC Brake can hold the load in position before starting the motor.
 Use the DC Brake during stopping to shorten the stopping time, and to hold a stopped load in position, such
as cranes and cutting machines.

08.04 Momentary Power Loss Action


Default: 0
Settings 0 Operation stops (coast to stop) after momentary power loss.
1 Operation continues after momentary power loss, speed search starts with the
last frequency.
2 Operation continues after momentary power loss, speed search starts with the
minimum frequency.
 Determines the operation mode when the AC motor drive restarts from a momentary power loss.

08.05 Maximum Allowable Power Loss Time Unit: 0.1


Settings 0.1–20.0 sec. Default: 2.0
 Sets the maximum allowable power loss time. If the time exceeds the Maximum Allowable Power Loss Time,
the AC motor drive output turns off (coast to stop).

4-69
Chapter 4 ParametersVFD-EL-W

 The selected operation after power loss in Pr.08.04 is only executed when the maximum allowable power loss
time is  5 seconds and the AC motor drive keypad displays “Lu”.
If the AC motor drive is powered off due to overload, even if the maximum allowable power loss time is  5
seconds, the drive does not execute the operation mode you set for Pr.08.04. In that case it starts up
normally.

08.06 Base Block Speed Search


Default: 1
Settings 0 Disable
1 Speed search starts with the last frequency command
2 Speed search starts with the minimum output frequency (Pr.01.05)
 Determines the AC motor drive restart method after an External Base Block is enabled.

Output frequency Input B.B. signal


(H)
Stop output voltage

Output voltage(V) Disable B.B. signal


Waiting time 08.07
08.08 Current Limit A Speed Search
for Speed SearchSpeed
Synchronization speed detection

Time
FWD Run

B.B.
Fig 1:B.B. Speed Search with Last Output Frequency Downward Timing Chart
(Speed Search Current Attains Speed Search Level)

Output frequency
(H) Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
08.08 Current Limit A Speed Search
for Speed SearchSpeed
Synchronization speed detection

Time

FWD Run

B.B.
Fig 2: B.B. Speed Search with Last Output Frequency Downward Timing Chart
(Speed Search Current doesn't Attain Speed Search Level)

Output frequency Input B.B. signal


(H) Stop output voltage
Disable B.B. signal
06.01 Waiting time 08.07
Over current
stall prevention A Restart
A
during acceleration Synchronization speed detection
Keep accelerating
Time

FWD Run

B.B.
Fig3: B.B. Speed Search with Minimum Output Frequency Upward Timing Chart

08.07 Base Block Time for Speed Search (B.B.) Unit: 0.1

4-70
Chapter 4 ParametersVFD-EL-W

Settings 0.1–5.0 sec. Default: 0.5


 When the AC motor drive detects a momentary power loss, it blocks its output and then waits for a period of
time specified by this parameter before resuming operation. Set this parameter at a value that ensures that
any residual regeneration voltage from the motor on the output has disappeared before the drive is activated
again.
 This parameter also determines the waiting time before resuming operation after an External Base Block and
Number of Auto-restarts after Fault (Pr.08.15).

08.08 Current Limit for Speed Search Unit: 1


Settings 30–200% Default: 150
 Limits the drive output current during a speed search.
 When executing a speed search, the V/F curve is defined by the settings in Parameter Group 01.

08.09 Skip Frequency 1 Upper Limit Unit: 0.01


08.10 Skip Frequency 1 Lower Limit Unit: 0.01
08.11 Skip Frequency 2 Upper Limit Unit: 0.01
08.12 Skip Frequency 2 Lower Limit Unit: 0.01
08.13 Skip Frequency 3 Upper Limit Unit: 0.01
08.14 Skip Frequency 3 Lower Limit Unit: 0.01
Settings 0.00–400.00 Hz Default: 0.00
 These parameters cause the AC motor drive not to remain in these frequency ranges with continuous
frequency output. Set these six parameters as follows Pr.08.09  Pr.08.10  Pr.08.11  Pr.08.12  Pr.08.13 
Pr.08.14.
internal frequency command

08.09
08.10
08.11
08.12
08.13
08.14

0
setting frequency

08.15 Number of Auto-restarts After Fault Unit: 1


Settings 0–10 Default: 0
08.16 Auto-reset Time for Restart after Fault Unit: 0.1
Settings 0.1–6000 sec. Default: 60.0
 After an over-current OC or over-voltage OV fault occurs, the AC motor drive can automatically reset/restart
up to ten times.
 Setting this parameter to 0 disables automatic reset/restart operation after any fault.
When enabled, the AC motor drive restarts with speed search, which starts at the last frequency before the
fault.
4-71
Chapter 4 ParametersVFD-EL-W

 Use this parameter in conjunction with Pr.08.15.


For example: If you set Pr.08.15 to 10 and Pr.08.16 to 600 seconds (10 minutes), and if there is no fault for
over 600 seconds from the restart for the previous fault, then the number of auto-restarts after a fault is reset
to 10.

08.17 Auto-energy Saving


Default: 0
Settings 0 Disable Energy-saving operation
1 Enable Energy-saving operation
 When you set Pr.08.17 to 1, acceleration and deceleration operate at full voltage. During constant speed
operation, the AC motor drive automatically calculates the best voltage value for the power for the current
load. This function is not suitable for constantly changing loads or near-full loads during operation.

08.18 Automatic Voltage Regulation (AVR)


Default: 0
Settings 0 AVR function enabled
1 AVR function disabled
2 AVR function disabled for deceleration
3 AVR function disabled for stop
 The motor rated voltage is usually 230/200 VAC 50/60 Hz and the AC motor drive input voltage may vary
between 180–264 VAC 50/60 Hz. Therefore, when you use the AC motor drive without the AVR function, the
output voltage is the same as the input voltage. When the motor runs at voltages exceeding the rated voltage
by 12–20%, the motor’s lifetime is shortened and the motor can be damaged due to higher temperature,
failing insulation and unstable torque output.
 The AVR function automatically regulates the AC motor drive output voltage to the Maximum Output Voltage
(Pr.01.02). For instance, if you set Pr.01.02 to 200 VAC and the input voltage is at 200–264 VAC, then the
Maximum Output Voltage is automatically reduced to a maximum of 200 VAC.
 When the motor ramps to stop, the deceleration time is longer. When setting this parameter to 2 with auto-
acceleration / auto-deceleration, the deceleration is quicker.

08.19 Reserved

08.20 Compensation Coefficient for Motor Instability Unit: 0.1


Settings 0.0–5.0 Default: 0.0
 The drift current occurs in a specific zone of the motor and it causes serious motor vibration. It is
recommended to use this parameter (the recommended value is 2.0) to greatly improve this situation. (The
drift current zone for high-power motors is usually in the low frequency area.)

08.21 DC Current Level during Preheating


Settings 0–100% Default: 0

4-72
Chapter 4 ParametersVFD-EL-W

 Sets the DC current level input to the motor during preheating. The DC current during preheating is 100%
equal to the Motor Rated Current (Pr.07.00). When setting this parameter, increase the current level slowly
until you reach the desired preheating temperature.
 Related parameters: Pr.08.22 (DC Current Cycle Time during Preheating), Pr.03.00 (Multi-function Output
Relay #24: Preheating function indication), Pr.04.06–Pr.04.08 (Multi-function Input Terminal #26: Auto-trigger
preheating function).

08.22 DC Current Cycle Time during Preheating


Settings 0–100% Default: 0
 Sets the cycle time that the DC current input to the motor during preheating. 0–100% corresponds to 0–10
seconds. When you set the cycle time to 0%, it means that there is no current output; 100% means
continuous current output. For example, if you set the cycle time to 50%, the time that the current input to the
motor for one cycle is five seconds; the stopping time is five seconds. When the AC motor drive stops
running, continuous DC current automatically and cyclically input to the motor. When you use this parameter
with MI=26 (Auto-trigger preheating function), this parameter works with the MI signal continuously and
cyclically until the AC motor drive starts the motor operation or MI=26 is disabled.
 The preheating function works when Pr.08.21 and Pr.08.22 are not set to 0.
 When MI=26 (Auto-trigger preheating function) is enabled, MI terminal determines the preheating function.
 When MI=26 is disabled, the preheating function is enabled after the AC motor drive stops its first operation or
when the AC motor drive starts after re-applying power.
 The diagram below shows the 50% setting for the cycle time that the DC current input to the motor during
preheating when MI=26 (Auto-trigger preheating function) is enabled.

 The diagram below shows the 50% setting for the cycle time that the DC current input to the motor during
preheating when MI=26 (Auto-trigger preheating function) is disabled. The preheating function automatically
enables continuous current input after the drive stops running.

4-73
Chapter 4 ParametersVFD-EL-W

 The diagram below shows the sequential relationship between the preheating function and enabled DC brake.

08.23 Fire Mode


Settings 0: No function Default: 0
1: Forward running
2: Running in reverse
 Use this parameter with Pr.04.06–Pr.04.08 multi-function input terminals #27 or #28 (Fire mode enabled
with/without operation command) and Pr.03.00 multi-function output terminal #25 (Fire Mode Indication).
0: The fire mode is invalid.
1: The motor runs in a clockwise direction (U, V, W) during fire accident.
2: The motor runs in a counterclockwise direction (U, V, W) during fire accident.

08.24 Operating Frequency during Fire Mode


Settings 0.00–400.00 Hz Default: 60.00
 Sets the AC motor drive’s operating frequency when the fire mode is enabled.

08.25 Number of Fire Mode Actions


Settings Read only Default: Read only
 As long as the fire mode is enabled for more than four minutes, regardless of whether the AC motor drive
runs or not, the fire mode action and its number of occurrences are recorded. Note that this parameter is
read-only. Any parameter value that is not zero voids the warranty.

※ Fire mode end process flow:


 If you set the Pr.04.06–Pr.04.08 multi-function input terminal=27/28 to ON or the communication address to
2002H with bit5=1 (fire mode enabled), and the fire mode is enabled for more than four minutes, and then you
set the Pr.04.06–Pr.04.08 multi-function input terminal=27/28 to OFF or the communication address to 2002H
with bit5=0 (no function), the counter starts to count from four minutes after the fire mode is enabled. After the
fire mode is enabled for 2.5 hours, the AC motor drive resumes normal operation, and stops or operates to
normal operating frequency according to the original input status.
 If you set the Pr.04.06–Pr.04.08 multi-function input terminal=27/28 to ON or the communication address to
2002H with bit5=1 (fire mode enabled), and the fire mode is enabled for less than four minutes, the AC motor
drive resumes normal operation once the fire mode is disabled, and stops or operates to normal operating
frequency according to the original input status.

4-74
Chapter 4 ParametersVFD-EL-W

※ Fault code list of normal mode and fire mode:


No. Fault Name Normal Mode Fire Mode
1 Over current (oc) V V
2 Over voltage (ov) V V
3 Over heat 1 (oH1) V No detection
4 Over heat 2 (oH2) V No detection
5 Over Load (oL) (150% 1 Min., Drive) V No detection
6 Internal electronic overload trip (oL1) V No detection
7 Motor over load (oL2) V No detection
8 External fault (EF) V V
9 Over current during Acceleration (ocA) V V
10 Over current during Deceleration (ocD) V V
11 Over current during normal speed (ocN) V V
12 Reserved
13 Low voltage (LV) V V
14 Input phase loss (PHL) V V
15 base block (bb) V V
16 Auto acceleration/deceleration failure (cFA) V V
17 Software parameter protection failure (code) V V
18 Internal EE parameter OM cannot write (cF10) V V
19 Internal EE parameter OM cannot read (cF20) V V
20 Hardware NMI (HPF1) V V
21 Hardware OV (HPF2) V V
22 Reserved
23 Hardware OC (HPF4) V V
24 Hardware IU (CF3.0) V V
25 Hardware IV (CF3.1) V V
26 Hardware IW (CF3.2) V V
27 Hardware DC bus (CF3.3) V V
28 Hardware Temperature (CF3.4) V No detection
32 Analog signal Error (AErr) V V
34 Motor overheat parameter protect (PTC) V V
35 Analog feedback error (FBE) V V
36 Deviation error (DEV) V V

4-75
Chapter 4 ParametersVFD-EL-W

Group 9: Communication Parameters


 You can set this parameter during operation.
The AC motor drive includes a built-in RS-485 serial interface, marked RJ45 near the control terminals. The RS-
485 pins are defined below.
RS-485
8 1 Serial interface
1: Reserved 2: EV 3: GND
4: SG- 5: SG+ 6: Reserved
7: Reserved 8: Reserved

09.00 Communication Address


Settings 1–254 Default: 1
 You must set the communication address this drive if the AC motor drive is controlled by RS-485 serial
communication. The communication address for each AC motor drive must be unique.

09.01 Transmission Speed


Default: 1
Settings 0: Baud rate 4800 bps (bits / second)
1: Baud rate 9600 bps (bits / second)
2: Baud rate 19200 bps (bits / second)
3: Baud rate 38400 bps (bits / second)
 Sets the transmission speed between the RS-485 master (such as PC) and the AC motor drive.

09.02 Transmission Fault Action


Default: 3
Settings 0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and keep operating
 Determines how the AC motor drive reacts if a transmission fault occurs.

09.03 Time-out Detection Unit: 0.1


Settings 0.0–120.0 sec. Default: 0.0
0.0 Disable
 If Pr.09.03 is not equal to 0.0, and Pr.09.02=0–2, and there is no communication on the bus during the time-
out detection period (set by Pr.09.03), the digital keypad displays “cE10”.

09.04 Communication Protocol


Default: 0
Settings 0: Modbus ASCII mode, protocol <7, N, 2>
1: Modbus ASCII mode, protocol <7, E, 1>
2: Modbus ASCII mode, protocol <7, O, 1>
3: Modbus RTU mode, protocol <8, N, 2>
4: Modbus RTU mode, protocol <8, E, 1>
5: Modbus RTU mode, protocol <8, O, 1>
6: Modbus RTU mode, protocol <8, N, 1>
7: Modbus RTU mode, protocol <8, E, 2>
8: Modbus RTU mode, protocol <8, O, 2>
9: Modbus ASCII mode, protocol <7, N, 1>
10: Modbus ASCII mode, protocol <7, E, 2>
4-76
Chapter 4 ParametersVFD-EL-W

11: Modbus ASCII mode, protocol <7, O, 2>


 Control by PC
1. When using RS-485 to connect with the communication port, you must set the communication address
for each VFD-EL-W drive in Pr.09.00 first so that the PC controls according to each address.
2. You can set a VFD-EL-W drive to communicate over Modbus networks using one of the following
modes: ASCII (American Standard Code for Information Interchange) or RTU (Remote Terminal Unit).
Select the desired mode along with the serial port communication protocol in this parameter.
3. Code Description:
The CPU delays about 1 second when using the communication reset; therefore, there is at least 1
second delay time in the master station.
ASCII mode:
Each 8-bit data is the combination of two ASCII characters. For example, a 1-byte data: 64 Hex, shown as
‘64’ in ASCII, consists of ‘6’ (36Hex) and ‘4’ (34Hex).
Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’
ASCII code 30H 31H 32H 33H 34H 35H 36H 37H

Character ‘8’ ‘9’ ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’


ASCII code 38H 39H 41H 42H 43H 44H 45H 46H
RTU mode:
Each 8-bit data is the combination of two 4-bit hexadecimal characters. For example, 64 Hex.

 Data Format
Character Frame for ASCII:

(7 , N , 2)

Start Stop Stop


bit 0 1 2 3 4 5 6
bit bit

7-data bits
10-bits character frame

(7 , E , 1)

Start Even Stop


bit 0 1 2 3 4 5 6 parity bit
7-data bits
10-bits character frame

(7 , O , 1)

Start Odd Stop


bit 0 1 2 3 4 5 6 parity bit
7-data bits
10-bits character frame

(7 , N , 1)

Start Stop
bit 0 1 2 3 4 5 6
bit
7-data bits
9-bits character frame

4-77
Chapter 4 ParametersVFD-EL-W

(7 , E , 2)

Start Even Stop Stop


bit 0 1 2 3 4 5 6 parity bit bit
7-data bits
11-bits character frame

(7 , O , 2)

Start Odd Stop Stop


bit 0 1 2 3 4 5 6 parity bit bit
7-data bits
11-bits character frame

Character Frame for RTU:

( 8 , N , 2)

Start Stop Stop


bit 0 1 2 3 4 5 6 7
bit bit
8-data bits
11-bits character frame

(8 , E , 1)

Start Even Stop


bit 0 1 2 3 4 5 6 7
parity bit
8-data bits
11-bits character frame

(8 , O , 1)

Start Odd Stop


bit 0 1 2 3 4 5 6 7
parity bit
8-data bits
11-bits character frame

(8 , N , 1)

Start Stop
bit 0 1 2 3 4 5 6 7
bit
8-data bits
10-bits character frame

(8 , E , 2)

Start Even Stop Stop


bit 0 1 2 3 4 5 6 7
parity bit bit
8-data bits
12-bits character frame

4-78
Chapter 4 ParametersVFD-EL-W

(8 , O , 2)

Start Odd Stop Stop


bit 0 1 2 3 4 5 6 7
parity bit bit
8-data bits
12-bits character frame

 Communication Protocol
1. Communication Data Frame
ASCII mode:
STX Start character ‘:’ (3AH)
Address Hi Communication address:
Address Lo 8-bit address consists of two ASCII codes.

Function Hi Command code:


Function Lo 8-bit command consists of two ASCII codes.

Contents of data:
DATA (n-1) to DATA 0 Nx8-bit data consists of 2n ASCII codes.
n ≤ 20, maximum of 40 ASCII codes.
LRC CHK Hi LRC checksum:
LRC CHK Lo 8-bit checksum consists of two ASCII codes.

END Hi End characters:


END Lo END1 = CR (0DH), END0 = LF (0AH)

RTU mode:
START A silent interval of more than 10 ms
Address Communication address: 8-bit address
Function Command code: 8-bit command
DATA (n-1) Contents of data:
to
DATA 0 n×8-bit data, n ≤ 40 (20 x 16-bit data).
CRC CHK Low CRC checksum:
CRC CHK High 16-bit checksum consists of two 8-bit characters.
END A silent interval of more than 10 ms

2. Address (Communication Address)


Valid communication addresses are between 0–254. A communication address of 0 means broadcast to all
AC motor drives (AMD). In this case, the AMD broadcast does not reply with any message to the master
device.
00H: broadcast to all AC motor drives
01H: AC motor drive with address 01
0FH: AC motor drive with address 15
10H: AC motor drive with address 16
:
FEH: AC motor drive with address 254
For example, send communication to AMD with address 16 decimal (10H):
ASCII mode: Address = ’1’,’0’ => ‘1’ = 31H, ‘0’ = 30H
RTU mode: Address = 10H

4-79
Chapter 4 ParametersVFD-EL-W

3. Function (Function code) and DATA (data characters)


The format of the data characters depends on the function code.
03H: Read data from register
06H: Write single register
08H: Loop detection

The available function codes and examples for the VFD-EL-W drive are described in the following tables.
(1) 03H: multi-read, read data from registers.
Example: reading two continuous data from register address 2102H; AMD address is 01H.
ASCII mode:

Command message: Response message:


STX ‘:’ STX ‘:’
‘0’ ‘0’
Address Address
‘1’ ‘1’
‘0’ ‘0’
Function Function
‘3’ ‘3’
‘2’ Number of data ‘0’
‘1’ (Count by byte) ‘4’
Starting data address
‘0’ ‘1’
‘2’ Content of starting address ‘7’
‘0’ 2102H ‘7’
Number of data ‘0’ ‘0’
(count by word) ‘0’ ‘0’
‘2’ ‘0’
Content of address 2103H
‘D’ ‘0’
LRC Check
‘7’ ‘0’
CR ‘7’
END LRC Check
LF ‘1’
CR
END
LF

RTU mode:
Command message: Response message:
Address 01H Address 01H
Function 03H Function 03H
21H Number of data
Starting data address 04H
02H (count by byte)
Number of data 00H 17H
Content of address 2102H
(count by word) 02H 70H
CRC CHK Low 6FH 00H
Content of address 2103H
CRC CHK High F7H 00H
CRC CHK Low FEH
CRC CHK High 5CH

(2) 06H: single write, write single data to register.


Example: writing data 6000 (1770H) to register 0100H; AMD address is 01H.
ASCII mode:
Command message: Response message:
STX ‘:’ STX ‘:’
‘0’ ‘0’
Address Address
‘1’ ‘1’
‘0’ ‘0’
Function Function
‘6’ ‘6’
‘0’ ‘0’
‘1’ ‘1’
Data address Data address
‘0’ ‘0’
‘0’ ‘0’
‘1’ ‘1’
Data content Data content
‘7’ ‘7’
4-80
Chapter 4 ParametersVFD-EL-W

Command message: Response message:


‘7’ ‘7’
‘0’ ‘0’
‘7’ ‘7’
LRC Check LRC Check
‘1’ ‘1’
CR CR
END END
LF LF

RTU mode:
Command message: Response message:
ADR 01H ADR 01H
CMD 08H CMD 08H
00H 00H
Data Data
00H 00H
17H 17H
Data Data
70H 70H
CRC CHK Low 8EH CRC CHK Low 8EH
CRC CHK High 0EH CRC CHK High 0EH

4. CRC (Cyclical Redundancy Check) is calculated by the following steps:


Step 1: Load a 16-bit register (called CRC register) with FFFFH.
Step 2: Exclusive OR the first 8-bit byte of the command message with the low order byte of the 16-bit
CRC register, storing the result in the CRC register.
Step 3: Examine the LSB of CRC register.
Step 4: If the LSB of CRC register is 0, shift the CRC register one bit to the right with MSB zero filling, then
repeat step 3. If the LSB of CRC register is 1, shift the CRC register one bit to the right with MSB zero
filling, Exclusive OR the CRC register with the polynomial value A001H, then repeat step 3.
Step 5: Repeat step 3 and 4 until eight shifts have been performed. When this is done, a complete 8-bit
byte will have been processed.
Step 6: Repeat step 2 to 5 for the next 8-bit byte of the command message. Continue doing this until all
bytes have been processed. The final content of the CRC register is the CRC value. When transmitting the
CRC value in the message, the upper and lower bytes of the CRC value must be swapped, that is the
lower order byte will be transmitted first.

The following is an example of CRC generation using C language. The function takes two arguments:
Unsigned char* data  a pointer to the message buffer
Unsigned char length  the quantity of bytes in the message buffer
The function returns the CRC value as a type of unsigned integer.
Unsigned int crc_chk(unsigned char* data, unsigned char length){
int j;
unsigned int reg_crc=0xFFFF;
while(length--){
reg_crc ^= *data++;
for(j=0;j<8;j++){
if(reg_crc & 0x01){ /* LSB(b0)=1 */
reg_crc=(reg_crc>>1) ^ 0xA001;
}else{
reg_crc=reg_crc >>1;
}
}
}
return reg_crc;
}

4-81
Chapter 4 ParametersVFD-EL-W

5. Address list
The contents of the available addresses are shown in the following table.
Content Address Function
GG means parameter group, nn means parameter number. For
example, the address of Pr.04.01 is 0401H. Refer to Chapter 4
AC motor drive
GGnnH Parameters for the function of each parameter. When reading
Parameters
parameters by command code 03H, only one parameter can be read
at a time.
00B: No function
01B: Stop
bit 0–1
10B: Run
11B: Jog + Run
bit 2–3 Reserved

00B: No function
2000H
01B: FWD
bit 4–5
10B: REV
Command 11B: Change direction
Write only
00B: Comm. forced first acceleration/deceleration
bit 6–7
01B: Comm. forced second acceleration/deceleration
bit 8–15 Reserved
2001H Frequency command
bit 0 1: E.F. (external fault) ON
bit 1 1: Reset
2002H bit 2 1: B.B. ON
bit 3–4
Reserved
bit 6–15
00B: No function
Fire mode
2002H Bit 5 01B: Fire mode enabled (Does not include the running
enabled
commands)
Status Error code:
monitor 2100H 0: No error occurred
Read only
1: Over-current (oc)
2: Over-voltage (ov)
3: IGBT Overheat (oH1)
4: Reserved
5: Drive overload (oL)
6: Motor overload1 (oL1)
7: Over-torque (oL2)
8: External fault (EF)
9: Over-current during acceleration (ocA)
10: Over-current during deceleration (ocd)
11: Over-current during constant speed (ocn)
12: Reserved
13: Reserved
14: PHL (Phase-Loss)
15: Reserved
4-82
Chapter 4 ParametersVFD-EL-W

Content Address Function


16: Auto-acceleration/deceleration failure (cFA)
17: Software and parameter password protection enabled (codE)
18: Power Board CPU WRITE failure (cF1.0)
19: Power Board CPU READ failure (cF2.0)
20: CC, OC Hardware protection failure (HPF1)
21: OV Hardware protection failure (HPF2)
22: Reserved
23: OC Hardware protection failure (HPF4)
24: U-phase error (cF3.0)
25: V-phase error (cF3.1)
26: W-phase error (cF3.2)
27: DC bus error (cF3.3)
28: IGBT Overheat error (cF3.4)
29: Reserved
30: Reserved
31: Reserved
32: Reserved
33: Reserved
34: Reserved
35: Reserved
36: Reserved
37: OPHL
Status of the AC motor drive
00B: RUN LED is off, STOP LED is on (the AC motor
drive stops).
01B: RUN LED blinks, STOP LED is on (when the AC
motor drive decelerates to stop).
bit 0–1
10B: RUN LED is on, STOP LED blinks (when the AC
motor drive is in standby).
11B: RUN LED is on, STOP LED is off (when the AC
motor drive runs).
bit 2 1: JOG command
bit 3–4 00B: FWD LED is on, REV LED is off (when the AC
2101H motor drive runs forward).
01B: FWD LED is on, REV LED blinks (when the AC
motor drive runs from reverse to forward).
10B: FWD LED blinks, REV LED is on (when the AC
motor drive runs from forward to reverse).
11B: FWD LED is off, REV LED is on (when the AC
motor drive runs in reverse).
bit 5–7 Reserved

1: Master frequency is controlled by the communication


bit 8
interface.
bit 9 1: Master frequency is controlled by the analog signal.
4-83
Chapter 4 ParametersVFD-EL-W

Content Address Function


1: Operation command is controlled by the
bit 10
communication interface.
bit 11–15 Reserved

2102H Frequency command (F)


2103H Output frequency (H)
2104H Output current (AXX.X)
2105H Reserved
2106H Reserved
2107H Reserved
2108H DC bus Voltage (UXXX.X)
2109H Output voltage (EXXX.X)
210AH Displays temperature of IGBT (°C)
2116H User-defined (Low word)
2117H User-defined (High word)
Note: 2116H is the number display for Pr.00.04. The high byte of 2117H is the number of decimal places
for 2116H. The low byte of 2117H is the ASCII code of the alphabetic display for Pr.00.04.

6. Exception response:
The AC motor drive is expected to return a normal response after receiving command messages from the
master device. The following describes the conditions when no normal response is returned to the master
device.
The AC motor drive does not receive the messages due to a communication error, and the AC motor drive
has no response. The master device eventually processes a time-out condition.
The AC motor drive receives the messages without a communication error, but cannot handle them. An
exception response is returned to the master device and a fault message “CExx” displays on the AC motor
drive keypad. The xx of “CExx” is a decimal code equal to the exception code (described below).
In the exception response, the most significant bit of the original command code is set to 1, and an
exception code that explains the condition that caused the exception is returned.

The following is an example of an exception response of command code 06H and exception code 02H.

ASCII mode: RTU mode:


STX ‘:’ Address 01H
Address Low ‘0’ Function 86H
Address High ‘1’ Exception code 02H
Function Low ‘8’ CRC CHK Low C3H
Function High ‘6’ CRC CHK High A1H
‘0’
Exception code
‘2’
LRC CHK Low ‘7’
LRC CHK High ‘7’
END 1 CR
END 0 LF

4-84
Chapter 4 ParametersVFD-EL-W

Explanation of exception codes:


Exception code Explanation
Illegal function code:
01 The function code received in the command message is not available for the AC
motor drive.
Illegal data address:
02 The data address received in the command message is not available for the AC
motor drive.
Illegal data value:
03 The data value received in the command message is not available for the AC
motor drive.
Slave device failure:
04
The AC motor drive is unable to perform the requested action.
Communication time-out:
10 If Pr.09.03 is not equal to 0.0, and Pr.09.02 = 0–2, and there is no communication
on the bus during the time-out detection period (Pr.09.03), the keypad displays
“cE10”.

7. Communication program for a PC:


The following is a simple example of how to write a communication program for Modbus ASCII mode on a
PC in the C language.
#include<stdio.h>
#include<dos.h>
#include<conio.h>
#include<process.h>
#define PORT 0x03F8 /* the address of COM1 */
/* the address offset value relative to COM1 */
#define THR 0x0000
#define RDR 0x0000
#define BRDL 0x0000
#define IER 0x0001
#define BRDH 0x0001
#define LCR 0x0003
#define MCR 0x0004
#define LSR 0x0005
#define MSR 0x0006
unsigned char rdat[60];
/* read 2 data from address 2102H of AC drive with address 1 */
unsigned char tdat[60]={':','0','1','0','3','2','1','0',’2', '0','0','0','2','D','7','\r','\n'};
void main(){
int i;
outportb(PORT+MCR,0x08); /* interrupt enable */
outportb(PORT+IER,0x01); /* interrupt as data in */
outportb(PORT+LCR,(inportb(PORT+LCR) | 0x80));
/* the BRDL/BRDH can be access as LCR.b7==1 */
outportb(PORT+BRDL,12); /* set baudrate=9600, 12=115200/9600*/
outportb(PORT+BRDH,0x00);
outportb(PORT+LCR,0x06); /* set protocol, <7,N,2>=06H, <7,E,1>=1AH, <7,O,1>=0AH,
<8,N,2>=07H, <8,E,1>=1BH, <8,O,1>=0BH */
for(i=0;i<=16;i++){
while(!(inportb(PORT+LSR) & 0x20)); /* wait until THR empty */
outportb(PORT+THR,tdat[i]); /* send data to THR */ }
i=0;
while(!kbhit()){
if(inportb(PORT+LSR) & 0x01){ /* b0==1, read data ready */
rdat[i++]=inportb(PORT+RDR); /* read data form RDR */
} } }

09.05 Reserved

4-85
Chapter 4 ParametersVFD-EL-W

09.06 Reserved

09.07 Response Delay Time Unit: 1


Settings 0–200 (1 unit = 2 ms.) Default: 1
 Sets the response delay time after the AC motor drive receives a communication command as shown in the
following diagram.

4-86
Chapter 4 ParametersVFD-EL-W

Group 10: PID Control Parameters


 You can set this parameter during operation.
10.00 PID Set Point Selection
Default: 0
Settings 0 Disable
1 Digital keypad UP/DOWN keys
2 Reserved
3 Reserved
4 PID set point (Pr.10.11)
10.01 Input Terminal for PID Feedback
Default: 0
Settings 0 Positive PID feedback from external terminal AVI (0–10 VDC)
1 Negative PID feedback from external terminal AVI (0–10 VDC)
2 Positive PID feedback from external terminal ACI (4–20 mA)
3 Negative PID feedback from external terminal ACI (4–20 mA)
 Note that the measured variable (feedback) controls the output frequency (Hz). Select the input terminal
accordingly. Ensure that this parameter setting does not conflict with the setting for Pr.10.00 (Master
Frequency).
 Negative feedback: error = set point (SP) – feedback (FB)
Positive feedback: error = feedback (FB) – set point (SP)

10.11 PID Set Point Value Unit: 0.1


Settings 0.00–400.00 Hz Default: 0.00
 Sets the set point in Hz in conjunction with Pr.10.00 setting to 4.

10.02 Proportional Gain (P) Unit: 0.1


Settings 0.0–10.0 Default: 1.0
 Determines the deviation response of Proportional gain (P). Eliminates the system error; usually used to
decrease the error and get faster response speed. It also reduces the steady-state error. But if you set the
value too high, it may cause system oscillation and instability.
 If you set the other two gains (I and D) to zero, proportional control is the only effective parameter.

10.03 Integral Time (I) Unit: 0.01


Settings 0.00–100.00 sec. Default: 1.00
0.00 Disable
 Use the integral controller to eliminate the error during stable system operation. The integral control does
not stop working until the error is zero. The integral is affected by the integral time.
 The smaller the integral time, the stronger the integral action. It is helpful to reduce overshoot and
oscillation for a stable system. Accordingly, the speed to lower the steady-state error decreases. The
integral control is often used with the other two controls for the PI controller or PID controller.
 Sets the integral time of the I controller. When the integral time is long, there is a small I controller gain,
with slower response and slow external control. When the integral time is short, there is a large I controller
gain, with faster response and rapid external control.
 If the integral time is too short, it may cause overshoot and system oscillation.
 Set Integral Time to 0.00 to disable Pr.10.03.

10.04 Differential Time (D) Unit: 0.01


Settings 0.00–1.00 sec. Default: 0.00
 Use the differential controller to show the system error change and to preview the change in the error. You
can use the differential controller to eliminate the error in order to improve the system state. Using a
suitable differential time can reduce overshoot and shorten adjustment time; however, the differential

4-87
Chapter 4 ParametersVFD-EL-W

operation increases noise interference. Note that a too large differential causes more noise interference. In
addition, the differential shows the change and the output is 0 when there is no change. Note that you
cannot use the differential control independently. You must use it with the other two controllers for the PD
controller or PID controller.
 Sets the D controller gain to determine the error change response. Using a suitable differential time
reduces the P and I controllers overshoot to decrease the oscillation for a stable system. A differential time
that is too long may cause system oscillation.
 The differential controller acts on the change in the error and cannot reduce the interference. Do not use
this function when there is significant interference.

10.05 Upper Bound for Integral Control Unit: 1


Settings 0–100% Default: 100
 Defines an upper bound for the integral gain (I) and therefore limits the Master Frequency. The formula is
Integral upper bound = Maximum Output Frequency (Pr.01.00) x (Pr.10.05).
 An excessive integral value causes a slow response due to sudden load changes and may cause motor
stall or machine damage.

10.06 PID Filter Time Unit: 0.1


Settings 0.0–2.5 sec. Default: 0.0
 The output for PID filter time helps reduce the system oscillation.
 Refer to the following closed-loop control diagram:

P I
Integral + Output Digital
+ gain + Freq. filter Freq.
Setpoint limit Limit Command
- 10.02 10.03 10.05 + 10.07 10.06

D
10.04
Input Freq. PID
Gain feedback
10.10 10.01

10.07 PID Output Frequency Limit Unit: 1


Settings 0–110 % Default: 100
 Defines the percentage of the output frequency as the limit for PID control. The formula is Output
Frequency Limit = Maximum Output Frequency (Pr.01.00) X Pr.10.07%. This parameter limits the
Maximum Output Frequency. You can set an overall limit for the output frequency in Pr.01.07.

10.08 PID Feedback Signal Detection Time Unit: 0.1


Settings 0.0–3600.0 sec. Default: 60.0
 This function in only for ACI signal.
 Defines the time during which the PID feedback is abnormal before a warning (see Pr.10.09) is given. It
can also be modified according to the system feedback signal time.
 If you set it to 0.0, the system does not detect any abnormality signal.

10.09 Erroneous PID Feedback Signal Action


Default: 0
Settings 0 Warn and ramp to stop
1 Warn and coast to stop
2 Warn and keep operating
 This function in only for ACI signal.
 Determines the AC motor drive action when the feedback signals (analog PID feedback) are abnormal
according to Pr.10.16.

4-88
Chapter 4 ParametersVFD-EL-W

10.10 Gain Over the PID Detection Value Unit: 0.1


Settings 0.0–10.0 Default: 1.0
 Sets the gain adjustment over the feedback detection value. Refer to the PID closed-loop control diagram
in Pr.10.06 for details.

10.12 PID Deviation Level Unit: 0.1


Settings 0.0–100.0% Default: 10.0
10.13 PID Deviation Detection Time Unit: 0.1
Settings 0.1–300.0 sec. Default: 5.0
 Sets the detection of the deviation between the set point and the feedback signal value.
 The base for Pr.10.12 is Pr.01.00. When the PID feedback control is enabled, and (PID set point source –
feedback) is larger than Pr.10.12, and the time exceeds the Pr.10.13 setting, then the multi-function output
terminal #16 (PID Feedback Error) displays as a warning and acts according to Pr.10.20 settings.
 When you set Pr.10.12 to 0, PID feedback error detection is disabled.

10.14 Sleep Detection Time Unit: 0.1


Settings 0.0–6550 sec. Default: 0.0
10.15 Sleep Frequency Unit: 0.01
Settings 0.00–400.00 Hz Default: 0.00
10.16 Wake-up Frequency Unit: 0.01
Settings 0.00–400.00 Hz Default: 0.00
 Sleep mode setting requirements:
 PID function must be enabled.
 The wake-up frequency Pr.10.16 setting must be higher than the sleep frequency Pr.10.15, and ensure
that there must be an appropriate difference between them (5 Hz or above) to prevent frequent switching
between the two frequency status.
 The sleep frequency Pr.10.15 setting must be higher than the Pr.01.08 output frequency lower limit to
prevent being in sleep mode.
 The sleep frequency Pr.10.15 setting must be higher than the Pr.01.05 minimum output frequency.
 Sleep/wake-up mode status description for the AC motor drive:
 When the actual output frequency H < Pr.10.15 and the time exceeds the Pr.10.14 setting, the AC motor
drive no longer outputs and is in sleep mode after the AC motor drive decelerates to Pr.01.05 minimum
output frequency following the deceleration time limit.
 When the AC motor drive is in sleep mode, the frequency command F is still calculated by PID. The
state of the wake-up shows as the following diagram.
 Before the frequency command F calculated by the PID reaches the wake-up frequency Pr.10.16, the
AC motor drive is in sleep mode, and the output frequency H is 0 Hz. The duration of this period of
time is affected by the PID parameters (Pr.10.02, Pr.10.03, and Pr.10.04).
 When the frequency command F calculated by the PID reaches the wake-up frequency Pr.10.16, the
AC motor drive output frequency H accelerates from Pr.01.05 minimum output frequency to Pr.10.16
wake-up frequency following the V/F curve.
 When the actual output frequency H of the AC motor drive accelerates to Pr.10.16 wake-up
frequency, control the AC motor drive output frequency H by PID.

4-89
Chapter 4 ParametersVFD-EL-W

 When the PID function is enabled and the sleep mode is disabled:
 If Pr.01.08 > Pr.01.05, the lower limit of the AC motor drive output frequency H is limited by Pr.01.08.
 If Pr.01.08 ≤ Pr.01.05, the lower limit of the AC motor drive output frequency H is limited by Pr.01.05.
When it reaches Pr.01.05, the AC motor drive stops output and is in ready status.

10.17 PID Offset


Default: 0.00
Settings: 0.00–60.00 Hz
 Selects the minimum output frequency in the PID control mode according to your applications.

10.18 Feedback of PID Physical Quantity Value Unit: 0.1


Settings 1.0–99.9 Default: 99.9
 When you set Pr.00.04 to 8, 00:00 displays (see the figure below).
 Use this parameter only for display. This parameter does not relate to Pr.00.13, Pr.00.14, Pr.02.18 and
Pr.02.19.

S etp oi nt Fe ed ba ck val ue
( the max. va lu e yo u wo ul d
l ike to co nve rt)

10.19 PID Calculation Mode Selection


Default: 0
Settings 0 Serial mode
1 Parallel mode
 Serial mode

4-90
Chapter 4 ParametersVFD-EL-W

P I
Integral + Output Digital
+ gain + Freq. filter Freq.
Setpoint limit Limit Command
- 10.02 10.03 10.05 + 10.07 10.06

D
10.04
Input Freq. PID
Gain feedback
10.10 10.01

 Parallel mode
P
10.02

+
I
In teg ra l Outp ut Di gi tal
+ g ai n + Freq . fi lte r Fr eq .
Set point l imi t L imi t Co mman d
- 10.03 10.05 + 10.07 10.06

D
10.04
In pu t Fre q. P ID
Gai n fe ed ba ck
10.10 10.01

10.20 Erroneous PID Feedback Deviation Level Action


Default: 0
Settings 0 Warn and keep operating
1 Warn and coast to stop
2 Warn and ramp to stop
3 Ramp to stop and restart after Pr.10.21 delay time (No warning displays)
Ramp to stop, and restart after Pr.10.21 delay time. The number of times of
4 restart is limited by Pr.10.50 (Number of Times of Restart after PID Fault)
 In PID control mode, the AC motor drive acts according to this parameter when erroneous PID feedback
deviation level occurs (Pr.10.12 and Pr.10.13).

10.21 Restart Delay Time after Erroneous PID Deviation Level Unit: 1
Settings 0–9999 sec. Default: 60

10.22 Set Point Deviation Level Unit: 1


Settings 0–100% Default: 0

10.23 Detection Time of Set Point Deviation Level Unit: 1


Settings 1–9999 sec. Default: 10
 Pr.10.22 is based on the set point set by the PID control. When the deviation is less than Pr.10.22 and the
time exceeds Pr.10.23 setting, the AC motor drive decelerates to stop to be in a standby status with
constant pressure (this deceleration time is according to the Deceleration Time 2 in Pr.01.12). If the
deviation is still in the range of the error set during deceleration to stop, the system is in standby status.
 Example: Assume that the set point of a constant pressure control for a pump is 4 kg, Pr.10.22 is set to
5%, and Pr.10.23 is set to 15 seconds, then the deviation is 0.2 kg (4 kg X 5% = 0.2 kg). When the
feedback value is higher than 3.8 kg and the time exceeds 15 seconds, the AC motor drive decelerates to
stop (this deceleration time is according to the Deceleration Time 2 in Pr.01.12). When the feedback value
is less than 3.8 kg, the AC motor drive starts to run.

10.24  Deviation Level of Liquid Leakage Unit: 1


Settings 0–50% Default: 0

4-91
Chapter 4 ParametersVFD-EL-W

 Pr.10.24 is based on the set point set by the PID control. When the drive does not run and is in a constant
pressure status, and if the error is higher than Pr.10.24 due to liquid leakage (minor pressure loss), the AC
motor drive starts to run.
 Use this parameter to avoid the drive’s frequent start-up and stop due to liquid leakage (minor pressure
loss).
 Liquid Leakage Deviation Level Detection

10.25 Liquid Leakage Change Detection Unit: 1


Settings 0–100% Default: 0
(0: Disable)
10.26 Time Setting for Liquid Leakage Change Unit: 0.1
Settings 0.1–10.0 sec. Default: 0.5
(0: Disable)
 Pr.10.25 and Pr.10.26 define the variation of the feedback value within a time unit in the case of liquid
leakage (minor pressure loss).
 Pr.10.25 sets the variation of the feedback value based on the set point set by the PID control; Pr.10.26 is
the setting value within a time unit. If the variation of the feedback value is less than the settings for
Pr.10.25 and Pr.10.26, the liquid leakage occurs. When the drive does not run and is in a constant
pressure status, and if the variation of the feedback value is higher than the settings for Pr.10.25 and
Pr.10.26, the AC motor drive starts to run in order to keep the system stable.
 Liquid Leakage / Usage Deviation Level Detection
set point

10.25
feedbac k v al ue

10.26
 Example:
Assume that the set point of a constant pressure control for a pump is 4 kg, Pr.10.22=5%, Pr.10.23 =15
seconds, Pr.10.24=25%, Pr.10.25=3% and Pr.10.26=0.5 second, then the deviation is 0.2 kg (4 kg X 5% =
0.2 kg). That is, when the feedback value is higher than 3.8 kg and the time exceeds 15 seconds, the AC
motor drive decelerates to stop (this deceleration time is according to the Deceleration Time 2 in Pr.01.12).
When the feedback value is less than 3.8 kg, the AC motor drive starts to run.
 Case 1: Assume that when the AC motor drive does not run and is in a constant pressure status, the
variation of the feedback value is less than 0.12 kg (4 kg X 3% = 0.12 kg) within 0.5 second. When the
feedback value continues to decrease to make the deviation of the set point be less than 1 kg (4 kg X 25%
= 1 kg), that is, when the feedback value is less than 3 kg, the AC motor drive starts to run.
 Case 2: Assume that when the AC motor drive does not run and is in a constant pressure status, the
variation of the feedback value is higher than 0.12 kg (4 kg X 3% = 0.12 kg) within 0.5 second; that is,
when the feedback value is less than 3.88 kg [4-(4 kg X 3%) = 3.88 kg] within 0.5 second, the AC motor
drive starts to run.

10.27
| Reserved
10.33

10.35 Multi-pump Control Mode


Settings 0–2 Default: 0
0: Disable
4-92
Chapter 4 ParametersVFD-EL-W

1: Fixed time circulation (alternative operation)


2: Fixed quantity control (multi-pump operating at constant pressure)
 When using the multi-pump control mode, you must set Pr.10.35 for each pump to the same value.

10.36 Multi-pump ID
Settings 0–4 Default: 0
0: Multi-pump control mode is disabled
1: Master
2–4: Slave
 When using the multi-pump control mode, the settings of each pump for Pr.10.36 cannot be the same.

10.37 Multi-pump’s Fixed Time Circulation Period


Settings 1–65535 minutes Default: 60
 This parameter is only valid for master pump settings.
 Fixed time circulation mode (alternative operation): Assume that when pump #1’s operating time is longer
than the setting for Pr.10.37, pump #1 stops, and then pump #2 activates, and so on.
 Fixed quantity control (multi-pump operating at constant pressure): Assume that when the master pump’s
operating time is longer than the setting for Pr.10.37, the master pump and the slave pump switch
alternatively.

10.38 Frequency to Start Switching Pumps


Settings 0.00 Hz–FMAX Default: 60.00

10.39 Time Detected When Pump Reaches the Starting Frequency


Settings 0.0–3600.0 sec. Default: 1.0

10.40 Frequency to Stop Switching Pumps


Settings 0.00 Hz–FMAX Default: 48.00

10.41 Time Detected When Pump Reaches the Stopping Frequency


Settings 0.0–3600.0 sec. Default: 1.0
 This parameter is only valid for master pump settings.
 This parameter is only valid for fixed quantity control (multi-pump operating at constant pressure) mode.
 When the master pump’s operating frequency ≥ Pr.10.38, and the time exceeds Pr.10.39, slave pump #1
activates. If the quantity of water is still insufficient, slave pump #2 and #3 activates under the same
conditions.
 If the master pump’s operating frequency ≤ Pr.10.40, and the time exceeds Pr.01.41, slave pump #1 stops.
If the master pump can fulfill the conditions, slave pump #2 and #3 stop in sequence, and leave the master
pump in operation only.
 Whether the master pump stops depends on the stopping detection function.

10.42 Pump’s Frequency at Time-out (Disconnection)


Settings 0.00 Hz–FMAX Default: 0.00
 This parameter is only valid for slave pump settings.
 For details on the conditions of communication disconnection and treatment, refer to Pr.09.02
Transmission Fault Action and Pr.09.03 Time-out Detection.
 If disconnection (time-out) occurs in the fixed quantity control (multi-pump operating at constant pressure)
mode, the frequency for the slave pump is Pr.10.42. When you press the STOP key, the disconnected
slave pump is in single-pump mode. (The RUN command and operating frequency is set by the parameter
settings for the slave pump.)
 The master pump can re-detect the disconnection of the salve pump.

4-93
Chapter 4 ParametersVFD-EL-W

10.43 Pump’s Error Treatment


Settings Bit0–Bit2 Default: 1
 This parameter is only valid for master pump settings.
 Bit0: Determines whether the erroneous pump switches to an alternative pump when an error occurs in the
running pump.
0: All pumps stop.
1: Switch to an alternative pump
Example:
When Bit0=0, and if an error occurs in the running pump, all pumps stop.
When Bit0=1, and if an error occurs in the running pump, switch the erroneous pump to an alternative pump.
 Bit1: Determines the erroneous pump to be in a standby or stop status after reset.
0: Set the erroneous pump to be in a standby status after reset (the pump receives the RUN command).
1: Set the erroneous pump to be in a stop status after reset (the pump does not receive the RUN command).
Example:
When Bit1=0, and after resetting the erroneous pump, you can control its running through the controller.
When Bit1=1, and after resetting the erroneous pump, you cannot control its running through the controller
until the master pump gives the STOP command.
 Bit2: Determines whether the master pump receives the RUN command or not when an error occurs in the
running pump.
0: When an error occurs in the running pump, the master pump does not receive the RUN command.
1: When an error occurs in the running pump, the master pump can choose to run with an alternative pump,
instead of the erroneous pump.
Example:
When Bit2=0, the master pump does not receive the RUN command when an error occurs in drive #2.
When Bit2=1, the master pump receives the RUN command and choose to run with an alternative pump
when an error occurs in drive #2.
This parameter setting is only valid for AUTO mode.

10.44 Selection of Pump’s Start-up Sequence


Settings 0–1 Default: 0
0: By pump ID#
1: By running time
 0: By pump ID#, (12341)
 1: By the shortest running time

10.45 Running Time of Multi-pump Under Alternative Operation


Settings 0.0–360.0 sec. Default: 60.0
 This parameter is only valid for master pump settings.
 Sets the time for switching the master pump and the slave pump.

10.46 Reserved
10.47 Reserved
10. 48 Reserved

10.49 Specify the Setting for Pr.10.12 [PID Deviation Level]


Settings 0–1 Default: 0
0: Use the existing setting (default), and check for any error per the
feedback deviation.
1: Set the low water pressure percentage (%), and check for any error
per the physical quantity feedback.
 When the pressure sensor is set to 10 kg, Pr.10.49=0 and Pr.10.12=10.0% (that is, deviation=1 kg), and if
the set point=3 kg and feedback < 2 kg, then the AC motor drive follows the setting for Pr.10.20.

4-94
Chapter 4 ParametersVFD-EL-W

 When the pressure sensor is set to 10 kg, Pr.10.49=1 and Pr.10.12=10.0% (that is, the physical quantity=1
kg), and if the set point=3 kg and feedback < 1 kg, then the AC motor drive follows the setting for Pr.10.20.

10.50 Number of Times of Restart after PID Fault


Settings 0–1000 times Default: 0
 When you set Pr.10.20 =4, this parameter sets the number of times to restart when PID error occurs.

4-95
Chapter 4 ParametersVFD-EL-W

VFD-EL-W Multi-pump SOP


STEP
The pressure feedback signal only connects to the Master, so set the PID for
the master pump only.
1 PID settings Pr.10.00 (PID Set Point Selection)
Pr.10.01 (Input Terminal for PID Feedback)
Each AC motor drive has a PID controller, so set the following parameters for
all AC motor drives.
2 P, I, D Gain / Time Pr.10.02 Proportional Gain (P)
Pr.10.03 Integral Time (I)
Pr.10.04 Differential Time (D)
Acceleration/ Set the acceleration and deceleration time for each AC motor drive.
3 Deceleration Pr.01.09 (Acceleration Time 1)
Settings Pr.01.10 (Deceleration Time 1)
The keypad of VFD-EL-W displays the PID settings and feedback values.
Set the following parameters for each AC motor drive.
Pr.00.04 (Content of Multi-function Display)
Keypad Setting : 5 (Display the PID analog feedback signal value in % (b) or
4 Multi-function 8 (Display the setting values for PID control and feedback
Display signal.)
Pr.00.13 (User-defined Value)
Pr.00.14 (Decimal Place of User-defined Value)
Pr.10.18 (Feedback of PID Physical Quantity Value)
All drives must have the stopping detection function. Set the related
Stopping parameters for each AC motor drive.
5 Detection Pr.10.22 (Set Point Deviation Level)
Function Pr.10.23 (Detection Time of Set Point Deviation Level)
Pr.01.12 (Deceleration Time 2)
All drives must have the restart function after liquid leakage. Set the related
Liquid parameters for each AC motor drive.
6 Pr.10.24 (Deviation Level of Liquid Leakage)
Leakage Pr.10.25 (Liquid Leakage Change Detection)
Pr.10.26 (Time Setting for Liquid Leakage Change)
Multi-functional Set the Master and Slave pumps and their parameter settings according to
7
Pumps your applications.

4-96
Chapter 4 ParametersVFD-EL-W

Optional Accessories for Multi-pumps under Alternative Operation


When you use the multi-pump operation, pay attention to the following wirings.

1. Use a RJ45 cable (8 pin, Internet cable) without an adapter. Simply connect the master/slave communication
port. If there are more than two pumps, use RMKE-HUB01 to connect RJ45.

RJ45 Female Connector

RMKE-HUB01
RS-485 One-wire to Two-wire

2. Use a RJ11 (6 pin) cable with an adapter to connect the master/slave communication port.

VFD-CMD04
RS-485 RJ11
Four-port communication breakout box

Case:
For alternative operation of multi-pump (Pr.10.35=1 Fixed Time Circulation)
 Enables four pumps to operate alternatively by time to extend their life span.
 Keeps the water pressure at 3 kg in a water system with constant pressure.
Refer to the diagram below:

4-97
Chapter 4 ParametersVFD-EL-W

Related parameters when setting Pr.10.35=1


End End
Parameter Function Settings Default user’s user’s Note
master slave
0: Display the frequency command
value (F)
1: Display the actual output frequency
(H)
Start-up
00.03 Display 2: Display the output current in Amps 0 3 3
Selection supplied to the motor (A)
3: Display the content of the user-
defined unit (U)
4: FWD/REV command
0: Display the content of the user-
defined unit (U)
1: Display the counter value (c)
2: Display the status of multi-function
input terminals (d)
3: Display the DC bus voltage (u)
4: Display the output voltage (E)
5: Display the PID analog feedback
Content of signal value in % (b)
00.04 Multi-function 0 8 8
Display 6: Display the output power factor
angle (n)
7: Display the output power (P)
8: Display the setting values for PID
control and feedback signal
9: Display the AVI (I) (V)
10: Display the ACI (mA/V) (i)
11: Display the temperature of the
IGBT in °C (h)
User-defined
Value Sets the constant
(corresponds pressure control
00.13 to max. 0–9999 0 100 100 to correspond to
operating the largest
frequency physical quantity
Pr.01.00) and the decimal
place. The
Decimal Place number displayed
00.14 of User- 0–3 0 1 1 is 10.0 currently.
defined Value

End End
Parameter Function Settings Default user’s user’s Note
master slave
Maximum Output
01.00 50.00–400.0 Hz 60.00 60.00 60.00
Frequency (Fmax)
Motor Rated Follows the
01.01 0.10–400.0 Hz 60.00 60.00 60.00 specifications of
Frequency (Fbase)
pumps
Motor Rated Voltage 230V series: 0.1–255.0 V 220.0 220.0 220.0
01.02
(Vbase) 460V series: 0.1–510.0 V 440.0

4-98
Chapter 4 ParametersVFD-EL-W

01.09 Accel. Time 1 0.1–600.0 / 0.01–600.00 sec. 10.0 0.5 0.5 Adjusts according
to customer’s
01.10 Decel. Time 1 0.1–600.0 / 0.01–600.00 sec. 10.0 5.0 5.0 applications
The time the AC
motor drive
decelerates to
01.12 Decel. Time 2 0.1–600.0 / 0.01–600.00 sec. 10.0 3.0 3.0
stop when the
pressure reaches
the setting value.

End End
Parameter Function Settings Default user’s user’s Note
master slave
0: Digital keypad UP/DOWN
keys or Multi-function Inputs
UP/DOWN.
First Master 1: 0–10 V from AVI Adjusts according
02.00 Frequency 0 2 2 to customer’s
2: 4–20 mA from ACI
Command Source applications
3: RS-485 (RJ45)
communication
4: Digital keypad potentiometer
0: Digital keypad
1: External terminals. Keypad
STOP/RESET enabled.
2: External terminals. Keypad
STOP/RESET disabled. Adjusts according
First Operation
02.01 0 0 0 to customer’s
Command Source 3: RS-485 communication. applications
Keypad STOP/RESET
enabled.
4: RS-485 communication.
Keypad STOP/RESET
disabled.

4-99
Chapter 4 ParametersVFD-EL-W

End End
Parameter Function Settings Default user’s user’s Note
master slave
0: Disable
1: Digital keypad UP/DOWN
keys Adjusts according
PID Set Point
10.00 0 1 1 to customer’s
Selection 2: Reserved
applications
3: Reserved
4: PID set point (Pr.10.11)
0: Positive PID feedback from
external terminal AVI
(0–10 VDC)
1: Negative PID feedback from
external terminal AVI
Input Terminal for (0–10 VDC)
10.01 0 3 3
PID Feedback 2: Positive PID feedback from
external terminal ACI
(4–20 mA)
3: Negative PID feedback from
external terminal ACI
(4–20 mA)
Proportional Gain
10.02 0.0–10.0 1.0 1.2 1.2 Adjusts according
(P)
to customer’s
0.00–100.00 sec. applications
10.03 Integral Time (I) 1.00 0.7 0.7
(0.00=Disable)
10.04 Differential Time (D) 0.00–1.00 sec. 0.00 - -
When the
10.12 PID Deviation Level 0.0–100.0% 10.0 5 5 pressure feedback
is < 0.5 kg and
PID Deviation time > 15 sec.,
10.13 0.1–300.0 sec. 5.0 15 15 follow the settings
Detection Time
for Pr.10.20.
Sets the maximum
Feedback of PID
feedback of PID
10.18 Physical Quantity 1.0–99.9 99.9 10 10
physical quantity
Value
value to be 10 kg.
The parallel PID
calculation mode
PID Calculation 0: Serial mode applies for the
10.19 0 1 1
Mode Selection 1: Parallel mode constant pressure
water supply
control.
0: Wan and keep operating
Erroneous PID 1: Warn and coast to stop When there is
10.20 Feedback Deviation 2: Warn and ramp to stop 0 3 3 water shortage or
Level Action unusual pressure
3: Ramp to stop and restart feedback, the
after Pr.10.21 delay time pump stops
running for 1800
sec. (30 minutes)
Restart Delay Time until the pressure
10.21 after Erroneous PID 0–9999 sec. 60 1800 1800 feedback is back
Deviation Level to normal.

4-100
Chapter 4 ParametersVFD-EL-W

When the
feedback value
and the set point
deviation are both
0.15 kg (3 kg X
Set Point Deviation 5%=0.15 kg), that
10.22 0–100% 0 5 5
Level is, when feedback
value is ≥ 2.85 kg
and time > 10
seconds, the AC
motor drive starts
to decelerate to
stop. This
deceleration time
is according to the
Detection Time of Deceleration Time
10.23 Set Point Deviation 1–9999 sec. 10 10 10 2 in Pr.01.12.
Level When the
feedback value is
< 2.85 kg, the AC
motor drive starts
to run.
Liquid Leakage:
Assume that when
the AC motor drive
does not run and
is in a constant
Deviation Level of
10.24 0–50% 0 33 33 pressure status,
Liquid Leakage
the variation of the
feedback value is
less than 0.12 kg
(3 kg X 4% = 0.12
kg) within 2
seconds. When
the feedback
value continues to
decrease to make
0–100% the deviation of
Liquid Leakage
10.25 0 4 4 the set point be
Change Detection (0: Disable) less than 0.99 kg
(3 kg X 33% =
0.99 kg), that is,
when the
feedback value is
less than 2.01 kg,
the AC motor drive
starts to run.
Liquid Usage after
Liquid Leakage:
Assume that when
the AC motor drive
does not run and
Time Setting for 0.1–10.0 sec. is in a constant
10.26 Liquid Leakage 0.5 2 2
(0: Disable) pressure status,
Change
the variation of the
feedback value is
higher than 0.12
kg (3 kg X 4% =
0.12 kg) within 2
seconds, the AC
motor drive starts
to run.

4-101
Chapter 4 ParametersVFD-EL-W

0: Disable
1: Fixed time circulation
Multi-pump Control (alternative operation)
10.35 0 1 1
Mode 2: Fixed quantity control
(multi-pump operating at
constant pressure)
0: Multi-pump control mode is
disabled
10.36 Multi-pump ID 0 1 2
1: Master
2–4: Slave
Multi-pump’s Fixed
10.37 Time Circulation 1–65535 minutes 60 1 1
Period
10.42 Pump’s Frequency at
Time-out 0.00 Hz–FMAX 0.00 60 60
(Disconnection)
Bit0: Determines whether the
erroneous pump switches to an
alternative pump when an error
occurs in the running pump.
0: All pumps stop.
1: Switch to an alternative pump
000=0
Bit1: Determines the erroneous 001=1
pump to be in a standby or stop 010=2
status after reset.
Pump’s Error 0: Standby after reset. 011=3
10.43 1 1 1
Treatment 1: Stop after reset. 100=4
101=5
Bit2: Determines whether the 110=6
master pump receives the RUN
command or not when an error 111=7
occurs in the running pump.
0: Does not receives the RUN
command.
1: Choose to run with an
alternative pump.
Adjusts according
Selection of Pump’s 0: By pump ID#
10.44 0 1 1 to customer’s
Start-up Sequence 1: By running time
applications
Running Time of Adjusts according
10.45 Multi-pump Under 0.0–360.0 sec. 60.0 60.0 60.0 to customer’s
Alternative Operation applications

4-102
Chapter 4 ParametersVFD-EL-W

For multi-pump operating at constant pressure (Pr.10.35=2 Fixed Quantity Control)


Related parameters when setting Pr.10.35=2
End End
Parameter Function Settings Default user’s user’s Note
master slave
0: Display the frequency
command value (F)
1: Display the actual output
frequency (H)
Start-up Display 2: Display the output current
00.03 0 3 3
Selection in Amps supplied to the
motor (A)
3: Display the content of
user-defined unit (U)
4: FWD/REV command
0: Display the content of the
user-defined unit (U)
1: Display the counter value
(c)
2: Display the status of
multi-function input
terminals (d)
3: Display the DC bus
voltage (u)
4: Display the output voltage
(E)
5: Display the PID analog
Content of feedback signal value in
00.04 Multi-function % (b) 0 8 8
Display
6: Display the output power
factor angle (n)
7: Display the output power
(P)
8: Display the setting values
for PID control and
feedback signal
9: Display the AVI (I) (V)
10: Display the ACI (mA/V)
(i)
11: Display the temperature
of the IGBT in °C (h)
User-defined
Value
(corresponds to Sets the constant pressure
00.13 0–9999 0 100 100 control to correspond to the
max. operating
frequency largest physical quantity and
Pr.01.00) the decimal place. The
number displayed is 10.0
Decimal Place currently.
00.14 of User-defined 0–3 0 1 1
Value

4-103
Chapter 4 ParametersVFD-EL-W

End End
Parameter Function Settings Default user’s user’s Note
master slave
Maximum
Output
01.00 50.00–400.0 Hz 60.00 60.00 60.00
Frequency
(Fmax)
Motor Rated Follows the specifications of
01.01 Frequency 0.10–400.0 Hz 60.00 60.00 60.00 pumps
(Fbase)
Motor Rated 230V series: 0.1–255.0 V 220.0 220.0 220.0
01.02 Voltage
(Vbase) 460V series: 0.1–510.0 V 440.0

01.09 Accel. Time 1 0.1–600.0 / 0.01–600.00 sec. 10.0 0.5 0.5 Adjusts according to
01.10 Decel. Time 1 0.1–600.0 / 0.01–600.00 sec. 10.0 5.0 5.0 customer’s applications

The time the AC motor drive


decelerates to stop when the
01.12 Decel. Time 2 0.1–600.0 / 0.01–600.00 sec. 10.0 3.0 3.0
pressure reaches the setting
value.

End End
Parameter Function Settings Default user’s user’s Note
master slave
0: Digital keypad UP/DOWN
keys or Multi-function
Inputs UP/DOWN.
First Master 1: 0–10 V from AVI
Frequency Adjusts according to
02.00 2: 4–20 mA from ACI 0 2 2
Command customer’s applications
Source 3: RS-485 (RJ45)
communication
4: Digital keypad
potentiometer
0: Digital keypad
1: External terminals.
Keypad STOP/RESET
enabled.
2: External terminals.
First Operation Keypad STOP/RESET
Adjusts according to
02.01 Command disabled. 0 0 0
customer’s applications
Source
3: RS-485 communication.
Keypad STOP/RESET
enabled.
4: RS-485 communication.
Keypad STOP/RESET
disabled.

End End
Parameter Function Settings Default user’s user’s Note
master slave
0: Disable
1: Digital keypad UP/DOWN
PID Set Point keys Adjusts according to
10.00 0 1 1
Selection customer’s applications
2: Reserved
3: Reserved

4-104
Chapter 4 ParametersVFD-EL-W

End End
Parameter Function Settings Default user’s user’s Note
master slave
4: PID set point (Pr.10.11)
0: Positive PID feedback from
external terminal AVI (0–
10 VDC)
1: Negative PID feedback
from external terminal AVI
Input Terminal (0–10 VDC)
10.01 for PID 0 3 3
Feedback 2: Positive PID feedback from
external terminal ACI (4–
20 mA)
3: Negative PID feedback
from external terminal ACI
(4–20 mA)
Proportional
10.02 0.0–10.0 1.0 1.2 1.2
Gain (P) Adjusts according to
Integral Time 0.00–100.00 sec. customer’s applications
10.03 1.00 0.7 0.7
(I) (0.00=Disable)
Differential
10.04 0.00–1.00 sec. 0.00 - -
Time (D)
PID Deviation
10.12 0.0–100.0% 10.0 5 5 When the pressure feedback
Level
is < 0.5 kg and time > 15
PID Deviation sec., follow the settings for
10.13 Detection 0.1–300.0 sec. 5.0 15 15 Pr.10.20.
Time
Feedback of Sets the maximum feedback
10.18 PID Physical 1.0–99.9 99.9 10 10 of PID physical quantity
Quantity Value value to be 10 kg.
PID The parallel PID calculation
Calculation 0: Serial mode mode applies for the
10.19 0 1 1
Mode 1: Parallel mode constant pressure water
Selection supply control.
0: Wan and keep operating
Erroneous PID 1: Warn and coast to stop
Feedback When there is water
10.20 2: Wand and ramp to stop 0 3 3
Deviation shortage or unusual
Level Action 3: Ramp to stop and restart pressure feedback, the pump
after Pr.10.21 delay time stops running for 1800 sec.
Restart Delay (30 minutes) until the
Time after pressure feedback is back to
10.21 Erroneous PID 0–9999 sec. 60 1800 1800 normal.
Deviation
Level
When the feedback value
and the set point deviation
Set Point are both 0.15 kg (3 kg X
10.22 Deviation 0–100% 0 5 5 5%=0.15 kg), that is, when
Level feedback value is ≥ 2.85 kg
and time > 10 seconds, the
AC motor drive starts to

4-105
Chapter 4 ParametersVFD-EL-W

End End
Parameter Function Settings Default user’s user’s Note
master slave
decelerate to stop. This
Detection deceleration time is
Time of Set according to the
10.23 Point 1–9999 sec. 10 10 10 Deceleration Time 2 in
Deviation Pr.01.12. When the feedback
Level value is < 2.85 kg, the AC
motor drive starts to run.
Liquid Leakage:
Assume that when the AC
motor drive does not run and
Deviation is in a constant pressure
10.24 Level of Liquid 0–50% 0 33 33 status, the variation of the
Leakage feedback value is less than
0.12 kg (3 kg X 4% = 0.12
kg) within 2 seconds. When
the feedback value continues
to decrease to make the
deviation of the set point be
less than 0.99 kg (3 kg X
Liquid
0–100% 33% = 0.99 kg), that is, when
Leakage
10.25 0 4 4 the feedback value is less
Change (0: Disable) than 2.01 kg, the AC motor
Detection
drive starts to run.
Liquid Usage after Liquid
Leakage:
Assume that when the AC
motor drive does not run and
is in a constant pressure
Time Setting
0.1–10.0 sec. status, the variation of the
for Liquid
10.26 0.5 2 2 feedback value is higher
Leakage (0: Disable) than 0.12 kg (3 kg X 4% =
Change
0.12 kg) within 2 seconds,
the AC motor drive starts to
run.
0: Disable
1: Fixed time circulation
Multi-pump (alternativeoperation)
10.35 0 2 2
Control Mode 2: Fixed quantity control (multi-
pump operating at constant
pressure)
0: Multi-pump control mode is
disabled
10.36 Multi-pump ID 0 1 2
1: Master
2–4: Slave
Multi-pump’s
Fixed Time
10.37 1–65535 minutes 60 1 1
Circulation
Period
Pump’s
Frequency at
10.42 0.00 Hz–FMAX 0.00 60 60
Time-out
(Disconnection)

4-106
Chapter 4 ParametersVFD-EL-W

End End
Parameter Function Settings Default user’s user’s Note
master slave
Bit0: Determines whether the
erroneous pump switches to
an alternative pump when an
error occurs in the running
pump.
0: All pumps stop
1: Switch to an alternative
pump
000=0
Bit1: Determines the 001=1
erroneous pump to be in a 010=2
standby or stop status after
Pump’s Error reset. 011=3
10.43 1 1 1
Treatment 0: Standby after reset. 100=4
1: Stop after reset. 101=5
110=6
Bit2: Determines whether the
master pump receives the 111=7
RUN command or not when
an error occurs in the running
pump.
0: Does not receives the RUN
command.
1: Choose to run with an
alternative pump.
Selection of
0: By pump ID# Adjusts according to
10.44 Pump’s Start- 0 1 1
1: By running time customer’s applications
up Sequence
Running Time
of Multi-pump
Adjusts according to
10.45 Under 0.0–360.0 sec. 60.0 60.0 60.0
customer’s applications
Alternative
Operation

4-107
Chapter 4 ParametersVFD-EL-W

This page intentionally left blank.

4-108
Chapter 5 Troubleshooting

5-1 Over-Current (oc)

5-2 Over-Voltage (ov)

5-3 Low Voltage (Lv)

5-4 Overheat (oH1)

5-5 Overload (oL)

5-6 Keypad Display is Abnormal

5-7 Phase Loss (PHL)

5-8 Motor Does Not Run

5-9 Motor Speed Cannot be Changed

5-10 Motor Stalls During Acceleration

5-11 The Motor Does Not Run as Expected

5-12 Electromagnetic / Induction Noise

5-13 Operating Environment Condition

5-14 Affecting Other Machines

5-1
Chapter 5 Troubleshooting VFD-EL-W

5.1 Over-Current (oc)

5-2
Chapter 5 Troubleshooting VFD-EL-W

5.2 Over-Voltage (ov)

5-3
Chapter 5 Troubleshooting VFD-EL-W

5.3 Low Voltage (Lv)

5-4
Chapter 5 Troubleshooting VFD-EL-W

5.4 Overheat (oH1)

5-5
Chapter 5 Troubleshooting VFD-EL-W

5.5 Overload (oL)

5-6
Chapter 5 Troubleshooting VFD-EL-W

5.6 Keypad Display is Abnormal

5.7 Phase Loss (PHL)

5-7
Chapter 5 Troubleshooting VFD-EL-W

5.8 Motor Does Not Run

5-8
Chapter 5 Troubleshooting VFD-EL-W

5.9 Motor Speed Cannot be Changed

5-9
Chapter 5 Troubleshooting VFD-EL-W

5.10 Motor Stalls During Acceleration

5.11 The Motor Does Not Run as Expected

5-10
Chapter 5 Troubleshooting VFD-EL-W

5.12 Electromagnetic/Induction Noise


Many sources of noise surround AC motor drives and affect them by radiation or conduction. This may cause
the control circuits to malfunction and even damage the AC motor drive. Of course, there are solutions to
increase the noise tolerance of an AC motor drive, but this has its limits. Solving the problem from the outside
as follows is the best.

1. Add a surge suppressor on the relays and contacts to suppress switching surges.
2. Shorten the length of the wiring for the control circuit or serial communication and keep them separated
from the power circuit wiring.
3. Comply with the wiring regulations by using shielded wires and isolation amplifiers for long wire length.
4. The grounding terminal must comply with the local regulations and be grounded independently; that is,
do not use a common ground with electric welding machines and other power equipment.
5. Connect a noise filter at the mains input terminal of the AC motor drive to filter noise from the power
circuit.

In short, solutions for electromagnetic noise exist of “no product” (disconnect disturbing equipment), “no
spread” (limit emission from disturbing equipment) and “no receive” (enhance immunity).

5.13 Operating Environment Condition


Since the AC motor drive is an electronic device, you must deal with the operating environment conditions.
Here are some remedial measures to use if necessary.

1. To prevent vibration, anti-vibration dampers are the last choice. Vibration must be within the
specification. Vibration causes mechanical stress and it should not occur frequently, continuously or
repeatedly to prevent damage to the AC motor drive.

2. Store the AC motor drive in a clean and dry location, free from corrosive fumes/dust to prevent corrosion
and poor contacts. Poor insulation in a humid location can cause short circuits. If necessary, install the
AC motor drive in a dust-proof and painted enclosure. If necessary in particular situations, use a
completely sealed enclosure.

3. The ambient temperature should be within the specification. Too high or too low temperature affects the
lifetime and reliability of the AC motor drive. For semiconductor components, damage occurs once any
specification is out of range. It is necessary to periodically check air quality and the cooling fan and
provide extra cooling if required. In addition, the microcomputer may not work in extremely low
temperatures, making cabinet heating necessary.

4. Store the AC motor drive in a relative humidity range of 0% to 90% (non-condensing). Use an air
conditioner and/or desiccator if necessary.

5-11
Chapter 5 Troubleshooting VFD-EL-W

5.14 Affecting Other Machines


An AC motor drive may affect the operation of other machines due to many reasons. Some solutions are listed
below:
 High Harmonics at Power Side

You can reduce high harmonics at the power side during running.

1. Separate the power system: use a transformer for the AC motor drive.
2. Use a reactor at the power input terminal of the AC motor drive.
3. If using phase lead capacitors (never on the AC motor drive output!), use serial reactors to prevent
damage to the capacitors from high harmonics.

serial reactor

phase lead capacitor

 Motor Temperature Rises

When the motor is a standard induction motor with a fan, the cooling will be insufficient at low speed,
causing the motor to overheat. In addition, high harmonics at the output increases copper and core
losses. Use the following measures depending on load and operation range.

1. Use a motor with independent ventilation (forced external cooling) or increase the motor rated power.
2. Use a special inverter-duty motor.
3. Do NOT run at low speed for long periods of time.

5-12
Chapter 5 Troubleshooting VFD-EL-W

This page intentionally left blank.

5-13
Chapter 6 Fault Code Information and Maintenance

6.1 Fault Code Information


6.2 Maintenance and Inspections

The AC motor drive has various warnings and protections against errors such as over-voltage, low
voltage, or over-current. Once an error occurs, the protections activate, the AC motor drive stops output,
activates the error contacts, and the motor coasts to stop. Please refer to the error display from the AC
motor drive and look up the corresponding causes and solutions. The fault record is stored in the AC
motor drive internal memory and can store the five most recent error messages. You can read it from the
digital keypad or through the communications by accessing the parameters.
The AC motor drive includes a large number of electronic components, including ICs, resistors,
capacitors, transistors, and cooling fans. These components do not last forever. Even under normal
circumstances, they will eventually become error-prone if used past their lifespans. Therefore, you must
perform periodic preventive maintenance to identify defective and worn out parts, and eliminate the
causes of malfunctions in the AC motor drive at an early stage. At the same time, parts that have
exceeded their product life should be replaced whenever possible to ensure safe operation.
Visual checks should be done regularly to monitor the AC motor drive's operation, and to make sure
nothing unusual happens. Check the situations listed in the following table.

 Wait five seconds after a fault has been cleared before pressing RESET with the
input terminal keypad.
 The drive must first be switched off for at least five minutes for ≤ 22 kW models
until the charging indicator turns off before it is safe to open the cover to begin
maintenance operations.
 Only qualified personnel can work on maintenance or replace parts. (Remove
metal items such as watch, rings, and other metal items before operation, and use
only insulated tools.)
 Never modify internal components or wiring.
 The performance and the surrounding environment should meet the standard
specifications. There should be no abnormal noise, vibration, or odor.
 Verify if the keypad displays normally. Check if there is any abnormality such as
overheating or color change. Prevent the drive from electronic shock and equipment
accident.

6-1
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

6.1 Fault Code Information


The following messages display when the operation command source is set as digital keypad.
Fault Name Fault Descriptions Corrective Actions

1. Check if the motor power corresponds with the AC


motor drive output power.
2. Check the wiring connections to U/T1, V/T2, and
W/T3 for possible short circuits.
3. Check the wiring connections between the AC motor
Over-current
drive and motor for possible short circuits, and for
Abnormal increase in current.
short to ground.
4. Check for loose contacts between the AC motor drive
and the motor.
5. Increase the Acceleration Time.
6. Check for possible excessive loading on the motor.

1. Check if the input voltage is in the rated AC motor


drive input voltage range.
Over-voltage
2. Check for possible voltage transients.
The DC bus voltage exceeds its
3. DC bus over-voltage may also be caused by motor
maximum allowable value.
regeneration. Either increase the Deceleration Time
or add an optional brake resistor (and brake unit).
1. Ensure that the ambient temperature is in the
specified temperature range.
Overheating 2. Make sure that the ventilation holes are not
Heat sink temperature is too high. obstructed.
3. Provide enough spacing for adequate ventilation. (see
Chapter 1)
1. Check whether the input voltage is in the AC motor
Low voltage
drive rated input voltage range.
The AC motor drive detects that
2. Check for abnormal load on the motor.
the DC bus voltage has fallen
3. Check for correct input power wiring to R-S-T (for
below its minimum value.
three-phase models) without phase loss.
Overload
The AC motor drive detects
excessive drive output current. 1. Check whether the motor is overloaded.
NOTE: The AC motor drive can 2. Reduce the torque compensation setting (Pr.07.02).
withstand up to 150% of the rated 3. Use the next higher power AC motor drive model.
current for a maximum of 60
seconds.
1. Check for possible motor overload.
2. Check the electronic thermal overload setting.
Overload 1 3. Replace the drive with a larger capacity model.
Internal electronic overload trip 4. Reduce the current level so that the drive output
current does not exceed the value in the Motor Rated
Current (Pr.07.00).
1. Reduce the motor load.
Overload 2
2. Adjust the over-torque detection settings to
Motor overload.
appropriate values (Pr.06.03–Pr.06.05).

CC (current clamp) Return the unit to the factory.

OV hardware fault
Return the unit to the factory.
OC hardware fault

6-2
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

Fault Name Fault Descriptions Corrective Actions


External Base Block
1. When the external input
terminals (B.B) (MI1–MI4) are
active, the AC motor drive stops
The “bb” disappears once the signal source is cleared.
output.
2. When changing the
communication address 2002H
bit2 = 1, the drive stops output.
1. Check if the screws between the drive and motor are
loosen.
2. Check for possible poor insulation between the U-V-W
Over-current during
terminals to the motor.
acceleration
3. Increase the Acceleration Time.
4. Decrease the torque compensation setting (Pr.07.02).
5. Replace the drive with a larger capacity model.
1. Check for possible poor insulation between the U-V-W
Over-current during terminals to the motor.
deceleration 2. Increase the Deceleration Time.
3. Replace the drive with a larger capacity model.
1. Check for possible poor insulation between the U-V-W
Over-current during constant terminals to the motor.
speed operation 2. Check for possible motor stall.
3. Replace the drive with a larger capacity model.

External Fault
1. When multi-function input
terminals (MI1–MI4) are set to
external fault, the AC motor The “EF” disappears once the signal source is cleared
drive stops output. and reset.
2. When changing the
communication address 2002H
bit0 = 1, the drive stops output.
Internal EEPROM cannot be
Return the unit to the factory.
programmed.
Internal EEPROM cannot be
Return the unit to the factory.
programmed.
Internal EEPROM cannot be 1. Press RESET key to reset all parameters to defaults.
read. 2. If the fault still exists, return the unit to the factory.
Internal EEPROM cannot be 1. Press RESET key to reset all parameters to defaults.
read. 2. If the fault still exists, return the unit to the factory.

Wiring detection fault U-phase error, return the unit to the factory.

Wiring detection fault V-phase error, return the unit to the factory.

Wiring detection fault W-phase error, return the unit to the factory.

DC bus wiring detection error, return the unit to the


Wiring detection fault
factory.

Wiring detection fault Temperature sensor error, return the unit to the factory.

1. Check if the motor is suitable for operation by the AC


Auto-acceleration/deceleration motor drive.
failure 2. Check if the regenerative energy is too high.
3. Check for sudden load changes.

6-3
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

Fault Name Fault Descriptions Corrective Actions


1. Check the RJ45 connection between the AC motor
drive for loose wires and wiring to the correct pins.
Communication Fault 2. Check if the communication protocol is properly set.
3. Refer to Parameter Group 09 Communication
Parameters in Chapter 4 for detailed information.
1. Check the parameter settings (Pr.10.01) and AVI/ACI
wiring.
PID feedback signal fault 2. Check for possible fault between the system response
time and the PID feedback signal detection time
(Pr.10.08)

Software protection failure Password locked.

Analog signal error Check if the wiring for ACI is broken.

Check if wiring for PID feedback is correct and the


Unusual PID feedback
parameter of PID feedback is properly set.

Phase Loss Check if the input power is three-phase.

Multi-motor fault protection Check if the motor wiring is normal.

6-4
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

Reset
Press the “RESET” key (as shown in the figure below) to reset the external terminal after the
fault is cleared, and set this terminal to be ON or send the Reset command through
communication, then the trip is cleared. Make sure the RUN command or signal is OFF before
executing RESET to prevent damage to the drive or personal injury due to immediate
operation after reset.

Digital Keypad for EL-W

6-5
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

6.2 Maintenance and Inspections


Before the check-up, always turn off the AC input power for at least five minutes and remove the
cover. Even if the power has been turned off, a charge may still remain in the filter capacitors with
hazardous voltages before the power is OFF. Make sure the voltage is lower than 25 VDC before
you perform any inspections.

Ambient environment
Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check the ambient
Visual inspection and
temperature, humidity,
measurement with equipment 
vibration and for any dust, gas,
with standard specifications
oil or water drops.
Check for any dangerous
Visual inspection 
objects in the environment.

Voltage
Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year

Check if the voltages of


Measure with multi-meter with
the main circuit and 
standard specifications.
control circuit are correct.

Digital keypad display


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year

Check that the display is


Visual inspection 
clear for reading.
Check for any missing
Visual inspection 
characters in the display.

Mechanical parts
Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year

Check for any abnormal


Visual and auditory inspection 
sounds or vibrations.
Check for any loose
Tighten the screws 
screws.
Check for deformed or
Visual inspection 
damaged parts.
Check for any color
change due to Visual inspection 
overheating.
Check for any dust or dirt. Visual inspection 

6-6
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

Main circuit
Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year

Check for any loose or missing


Tighten or replace the screws. 
screws.
Check for any deformed, cracked, or
damaged machinery or insulation
Visual inspection 
and for any color change due to
overheating or ageing.
Check for any dust or dirt. Visual inspection 

Main circuit terminals and wiring


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year

Check for wiring color change or


Visual inspection 
deformation due to overheating.
Check for wiring insulation damage
Visual inspection 
or color change.

Main circuit terminal block


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year

Check for any damage. Visual inspection 

Main circuit filter capacity


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year

Check for any leakage of liquid,


color change, cracking or Visual inspection 
deformation.
Check if the safety valve is not
removed or if the valve is obviously Visual inspection 
expanded.
Measure static capacity when Static capacity  initial value X

required 0.85

6-7
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

Main circuit resistor


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check for any peculiar odors or
insulation cracking due to Visual inspection, smell. 
overheating.

Check for any disconnections. Visual inspection 

Measure the resistor value with a


Check for damaged connections 
multi-meter

Main circuit transformer and reactor


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check for any abnormal vibrations Visual, auditory inspection and

or peculiar odors. smell.

Main circuit electromagnetic contactor and relay


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check for any vibration sounds. Auditory inspection. 
Check that the contact works
Visual inspection 
correctly.

Main circuit printed circuit board and connector


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check for any loose screws
Tighten the screws. 
and connectors.
Check for any peculiar odors or
Visual inspection and smell 
color changes.
Check for any cracking,
damage, deformation or Visual inspection 
corrosion.
Check for any leakage of liquid
or deformation in the Visual inspection 
capacitors.

Cooling system cooling fan


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Visual, auditory inspection and turn
Check for any abnormal
the fan by hand (turn off the power 
sounds or vibrations.
first) to check for smooth rotation.
Check for any loose screws. Tighten the screws. 
Check for any color change
Change fan. 
due to overheating.

6-8
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

Cooling system ventilation channel


Maintenance Period
Items to Check Methods and Criterion
Daily Half Year One Year
Check for any obstruction
around the heat sink, air intake Visual inspection 
or air outlet.

NOTE
Use chemically neutral cloth to clean and use a dust cleaner to remove dust when necessary.

6-9
Chapter 6 Fault Code Information and Maintenance  VFD-EL-W

This page intentionally left blank.

6-10
Appendix A Specifications

A-1. 230V 1φ Series

A-2. 460V 3φ Series

A-3. General Specifications

A-4. Environment for Operation, Storage and


Transportation

A-5. Operation Temperature and Derating Curve of


Ambient Temperature

NOTE

1. VFD-EL-W has two types of packaging: Individual Package [suffixed with (-1) at the end of the model
name] and 12 pcs/carton.
2. The electrical specifications are the same for either packaging.
3. The VFD-EL-W Series include the 230V and 460V models. The 230V model is one-phase; the 460V
model is three-phase. Refer to following specifications for details.

A-1
Appendix A SpecificationsVFD-EL-W

A1. 230V 1φ Series


Model Number
VFD□□□EL21W (-1) 002 004 007 015 022
Max. Applicable Motor
Output (kW) 0.2 0.4 0.75 1.5 2.2
Max. Applicable Motor
Output (HP) 0.25 0.5 1.0 2.0 3.0
Rated Output
Capacity (kVA) 0.6 1.0 1.6 2.9 4.2
Rated Output
Output Rating

Current (A) 1.6 2.5 4.2 7.5 11.0


Maximum Output
Three-phase Proportional to Input Voltage
Voltage (V)
Output Frequency
0.1–400
(Hz)
Carrier Frequency
2–12 (default: 8)
(kHz)
Rated Input Current
4.9 6.5 9.3 15.7 24.0
(A)
Input Rating

Rated
One-phase, 200–240 V, 50 / 60 Hz
Voltage/Frequency
Voltage Tolerance  10% (180–264 V)
Frequency
Tolerance  5% (47–63 Hz)
Cooling Method Convective Cooling Fan Cooling
Weight (kg) 1.0 1.0 1.0 1.4 1.4

A2. 460V 3φ Series


Model Number
VFD□□□EL43W (-1) 004 007 015 022 040
Max. Applicable Motor Output
(kW) 0.4 0.75 1.5 2.2 4.0
Max. Applicable Motor Output
(HP) 0.5 1.0 2.0 3.0 5.5
Rated Output Capacity
(kVA) 1.2 2.0 3.3 4.4 7.4
Output Rating

Rated Output Current (A) 1.5 2.5 4.2 5.5 9.0


Maximum Output Voltage
Three-phase Proportional to Input Voltage
(V)
Output Frequency (Hz) 0.1–400
Carrier Frequency (kHz) 2–12 (default: 8)
Rated Input Current (A) 1.8 3.2 4.3 7.1 10.0
Rating

Rated Voltage/Frequency Three-phase, 380–480V, 50 / 60Hz


Input

Voltage Tolerance  10% (342–528 V)


Frequency Tolerance  5% (47–63 Hz)
Cooling Method Convective Cooling Fan Cooling
Weight (kg) 1.0 1.0 1.0 1.4 1.4

A-2
Appendix A SpecificationsVFD-EL-W

A3. General Specifications


Characteristics Descriptions
SPWM (Sinusoidal Pulse Width Modulation) control (V/F control, Vector
Control System
Control)
Frequency Setting Resolution 0.01 Hz
Control Characteristics

Output Frequency Resolution 0.01 Hz


Includes the auto-torque/auto-slip compensation; starting torque can be
Torque Characteristics
150% at 5.0 Hz
Overload Tolerance 150% of rated current for one minute
Skip Frequency Three zones, setting range 0.1–400 Hz
Accel/Decel Time 0.1–600 seconds (2 Independent settings for Accel./ Decel. time)
Stall Prevention Level Setting 20–250% of rated current
Operation frequency 0.1–400.0 Hz, output 0–100% rated current
DC Brake
Start time 0–60 seconds, stop time 0–60 seconds
V/F Pattern Adjustable V/F pattern
Keypad Setting by
Frequency
Setting Potentiometer-5 k / 0.5 W, 0–10 VDC, 4–20 mA, RS-485 interface; Multi-
External Signal
function inputs 2 to 4 (7 steps, Jog, up/down)
Operating Characteristics

Operation Keypad Set by RUN and STOP


Setting Single-wire (default setting MI1) or Two-wire/Three-wire (MI1, MI2, MI3) by
Signal External Signal
setting parameters, JOG operation, RS-485 serial interface (Modbus).
Multi-step selection 0–7, Jog, accel./decel. inhibit, two accel./decel.
Multi-function Input Signal switches, counter, external Base Block, ACI/AVI selections, drive reset,
UP/DOWN key settings, NPN/PNP input selection
AC drive operating, frequency reached, zero speed, Base Block, fault
Multi-function Output
indication, overheat alarm, emergency stop and status selections for input
Indication
terminals.
Analog Output Signal Output frequency/current
AVR, accel./decel. S-Curve, over-voltage/over-current stall prevention, five
fault records, reverse inhibition, momentary power loss restart, DC brake,
auto-torque/slip compensation, auto-tuning, adjustable carrier frequency,
Operation Functions output frequency limits, parameter lock/reset, PID control, external counter,
Modbus communication, abnormality reset, abnormality restart, power-
saving, fan control, sleep/wake frequency, first/second frequency source
selections, first/second frequency source combination, NPN/PNP selection.
Over-voltage, over-current, under-voltage, external fault, overload, ground
Protection Functions
fault, overheating, electronic thermal, IGBT short circuit, PTC
Six-key, seven-segment LED with four-digits, four status LEDs, master
Display Keypad frequency, output frequency, output current, custom units, parameter
values for setup and lock, faults, RUN, STOP, RESET, FWD/REV.

A-3
Appendix A SpecificationsVFD-EL-W

A4. Environment for Operation, Storage and Transportation


Built-in EMI Filter N/A
Enclosure Rating IP20
Pollution Degree 2
Installation Location Altitude 1,000 m or lower, keep from corrosive gasses, liquid and dust.
Enviromental Conditions

Non-condensing, non-freezing
-10–50°C (40°C for side-by-side mounting, except VFD007EL21W(-1) which
Ambient Temperature
requires the installation of a cooling fan. Running at full load may reduce
the lifespan of the drive)
Storage/ Transportation
-20–60°C
Temperature
Ambient Humidity Below 90% RH (non-condensing)
1.0 mm, peak to peak 2–13.2 Hz; 0.7–1.0 G, 13.2–55 Hz;
Vibration
1.0 G, 55–512 Hz; compliance with IEC 60068-2-6
Certifications , RoHS, GB 12668.3

A-4
Appendix A SpecificationsVFD-EL-W

A5. Derating Curve for Ambient Temperature and Carrier Frequency


Ambient Temperature Derating Curve

Rated current (%)

Ambient temperature (°C)


Other models

Model Ambient Temperature Limitation


If the AC motor drive operates at the rated current, the ambient temperature needs
to be between -10–40°C. If the temperature is above 40°C, decrease 2% of the
VFD007EL21W(-1)
rated current for every 1°C increase in temperature. The maximum allowable
temperature is 50°C.

If the AC motor drive operates at the rated current, the ambient temperature needs
to be between -10–50°C. If the temperature is above 50°C, decrease 2% of the
Other models
rated current for every 1°C increase in temperature. The maximum allowable
temperature is 60°C.

Other models: VFD002EL21W(-1), VFD004EL21W(-1), VFD015EL21W(-1), VFD022EL21W(-1),


VFD004EL43W(-1), VFD007EL43W(-1), VFD015EL43W(-1), VFD022EL43W(-1), VFD040EL43W(-1)

Carrier Frequency Derating Curve


Rated current (%)

Carrier frequency (kHz)


Other models 50°C All models 25°C

Model Carrier Frequency Limitation

If the AC motor drive is installed at an ambient temperature of 40°C, and operates


at the rated current, the carrier frequency needs to be within 8 kHz. If the carrier
VFD007EL21W(-1) frequency is higher than 8 kHz, decrease 5% of the rated current for every 1 kHz
increase in the carrier frequency. The maximum allowable carrier frequency is 12
kHz.

If the AC motor drive is installed at an ambient temperature of 50°C, and operates


at the rated current, the carrier frequency needs to be within 8 kHz. If the carrier
Other models frequency is higher than 8 kHz, decrease 5% of the rated current for every 1 kHz
increase in the carrier frequency. The maximum allowable carrier frequency is 12
kHz.

A-5
Appendix A SpecificationsVFD-EL-W

This page intentionally left blank.

A-6
Appendix B Accessories

B.1 Non-fuse Circuit Breaker Chart


B.2 Reactor
B.2.1 AC Reactor
B.2.2 Zero Phase Reactor
B.3 Digital Keypad
B.3.1 PU06
B.3.2 PU08 and PU08V
B.4 Optional Cooling Fan

B.1 Non-fuse Circuit Breaker Chart


For one-phase/three-phase drives, the current rating of the breaker must be between 2–4 times the rated input
current.

One-phase Three-phase
Recommended Recommended
Model Model
non-fuse breaker (A) non-fuse breaker (A)
VFD002EL21W 10 VFD004EL43W 5
VFD004EL21W 15 VFD007EL43W 5
VFD007EL21W 20 VFD015EL43W 10
VFD015EL21W 30 VFD022EL43W 15
VFD022EL21W 50 VFD040EL43W 20

Fuse Specification Chart


Fuse specifications lower than the table below are allowed.
I (A) I (A) Line Fuse
Model
Input Output I (A) Bussmann P/N
VFD002EL21W 4.9 1.6 10 JJN-10
VFD004EL21W 6.5 2.5 15 JJN-15
VFD004EL43W 1,8 1,.5 5 JJS-6
VFD007EL21W 9.3 4.2 20 JJN-20
VFD007EL43W 3.2 2.5 5 JJS-6
VFD015EL21W 15.7 7.5 30 JJN-30
VFD015EL43W 4.3 4.2 10 JJS-10
VFD022EL21W 24.0 11.0 50 JJN-50
VFD022EL43W 7.1 5.5 15 JJS-15
VFD040EL43W 10.0 9.0 20 JJS-20

B-1
Appendix B Accessories VFD-EL-W

B.2 Reactor
B.2.1 AC Reactor
AC Input Reactor Recommended Value
230V, 50/60Hz, One-Phase
Fundamental Max. continuous Inductance (mH)
kW HP
Amps Amps 3–5% Impedance
0.2 0.25 4 6 6.5
0.4 0.5 5 7.5 3
0.75 1 8 12 1.5
1.5 2 12 18 1.25
2.2 3 18 27 0.8

460V, 50/60Hz, Three-Phase


Fundamental Max. continuous Inductance (mH)
kW HP
Amps Amps 3% Impedance 5% Impedance
0.4 0.5 2 3 20 32
0.75 1 4 6 9 12
1.5 2 4 6 6.5 9
2.2 3 8 12 5 7.5
4.0 5.5 8 12 3 5

AC Output Reactor Recommended Value


230V, 50/60Hz, Three-Phase
Fundamental Max. continuous Inductance (mH)
kW HP
Amps Amps 3% Impedance 5% Impedance
0.2 0.25 4 6 9 12
0.4 0.5 4 6 6.5 9
0.75 1 8 12 3 5
1.5 2 8 12 1.5 3
2.2 3 12 18 1.25 2.5

460V, 50/60Hz, Three-Phase


Fundamental Max. continuous Inductance (mH)
kW HP
Amps Amps 3% Impedance 5% Impedance
0.4 0.5 2 3 20 32
0.75 1 4 6 9 12
1.5 2 4 6 6.5 9
2.2 3 8 12 5 7.5
4.0 5.5 12 18 3 5

B-2
Appendix B Accessories VFD-EL-W

Applications

Connected in input circuit


Application 1
When more than one AC motor drives are connected to the same mains power and are running, and one of
them is ON during operation.

Issues: When applying power to one of the AC motor drives, the charge current of the capacitors may
cause voltage dip. The AC motor drive may be damaged when over-current occurs during operation.

Correct wiring:
M1 reactor
AC motor drive motor

M2
AC motor drive motor

Mn
AC motor drive motor

Application 2
A silicon rectifier and AC motor drive are connected to the same power.

Issues: Switching spikes are generated when the silicon rectifier switches ON/OFF. These spikes may
damage the mains circuit.

Correct wiring:
Silicon Controlled Rectifier

power reactor
DC

AC motor drive

reactor
motor

Application 3
The power supply capacity is 10 or above times the AC motor drive capacity.

Issues: When the mains power capacity is too large, line impedance is small and the charge current is too
high. This may damage the AC motor drive due to the higher rectifier temperature.

Correct wiring:
large-capacity small-capacity
power reactor AC motor drive

motor

B-3
Appendix B Accessories VFD-EL-W

B.2.2 Zero Phase Reactor


RF220X00A
UNIT: mm [inch]

Cable Recommended Wire Size Diagram A


Wiring
type Nominal Qty. Please wind each wire four times around the core. The
Method
(Note) AWG mm
2
(mm2) reactor must be put as close to the inverter output as
possible.
≤ 10 ≤ 5.3 ≤ 5.5 1 Diagram A
Single-
Zero Phase Reactor
core
≤2 ≤ 33.6 ≤ 38 4 Diagram B
R/L1 U/T1
Power
≤ 12 ≤ 3.3 ≤ 3.5 1 Diagram A Supply
S/L2 V/T2 MOTOR
Three- T/L3 W/T3

core
≤1 ≤ 42.4 ≤ 50 4 Diagram B

NOTE Diagram B
600V Insulated Unshielded Cable Please put all wires through four cores in series without
winding.
1. The table above gives approximate wire size for
zero phase reactors, but the selection is ultimately
governed by the type and diameter of the cable; Zero Phase Reactor
that is, the cable must fit through the center hole of
zero phase reactors. Power R/L1 U/T1

Supply
S/L2 V/T2 MOTOR
T/L3 W/T3
2. When wiring, do not pass the grounding cable
through the zero phase reactor; only pass the
motor wire or power cable through the zero phase
reactor.
3. With longer motor cables the zero-phase reactor
can effectively reduce interference at the motor
output.

B-4
Appendix B Accessories VFD-EL-W

B.3 Digital Keypad


B.3.1 VFD-PU06
B.3.1.1 Digital Keypad VFD-PU06 Description

B.3.1.2 Display Message Explanation


Display Message Descriptions

The current frequency of the drive.

The actual operation frequency that the drive outputs to the motor.

The user-defined unit (u)

The loading current of the drive.

Read parameters. Press PROG/DATA for 2–3 sec. until it is flashing. Then,
you can read four parameters from the AC motor drive to the digital keypad
PU06 (read D0–read D3). Press UP or DOWN key to change to SAVE
function.
Write parameters. Press PROG/DATA for 2–3 sec. until it is flashing. Then,
you can write the parameters from the digital keypad PU06 to the AC motor
drive. Press UP or DOWN key to change to READ function.

The specified parameter setting.

The actual value stored in the specified parameter.

External Fault

B-5
Appendix B Accessories VFD-EL-W

Display Message Descriptions


“End” displays for approximately one second if the entered input data has been
accepted. After a parameter value has been set, the new value is automatically
stored in memory.

“Err” displays if the input is invalid or the input exceeds the setting range.

Communication Error. Refer to Parameter Group 09 in Chapter 04 for details.

B-6
Appendix B Accessories VFD-EL-W

B.3.1.3 Operation Flow Chart

Write Write
parameters parameters
failure success

B-7
Appendix B Accessories VFD-EL-W

B.3.2 VFD-PU08 and VFD-PU08V

VFD-
Item Specification
PU08
Compatible Drive VFD-EL-W, ME300

Communication
RS485
Protocol

PU08: W: 68.0, D: 35.6, H: 46.8.


Size (mm) PU08V: W: 36.5, D: 31.0, H:
70.0.

PU08: By snap-fit or by fastening


Installation method screws.
PU08V: By fastening screws.

Front panel: IP20;


Protection Marking
Rear Panel: IP00

RJ45
Network Interface
(RJ: Registered Jack)

Maximum cable
5 meters
VFD- length

PU08V -RS-485 communication


-Read/Write parameters,
Main Function -Display status,
-Send commands.
-Display startup meu

NOTE
The VFD-PU08 and VFD-PU08V don’t not include the extension cord. Please choose the suitable
extension cords as needed. (Refer to the table below)

B-8
Appendix B Accessories VFD-EL-W

Communication cable

L
No. Model Name
mm inch
1 UC-CMC003-01A 300 11.8
2 UC-CMC005-01A 500 19.6
3 UC-CMC010-01A 1000 39.0
4 UC-CMC015-01A 1500 59.0
5 UC-CMC020-01A 2000 78.7
6 UC-CMC030-01A 3000 118.1
7 UC-CMC050-01A 5000 196.8

B-9
Appendix B Accessories VFD-EL-W

B.4 Optional Fan Kit


After you install the cooling fan to the VFD007EL21W(-1), you can increase the ambient
temperature of the operating environment up to 50°C without derating. If you choose not to install
the cooling fan, the ambient temperature of the operating environment is only up to 40°C without
derating. The power supply of the cooling fan is 24VDC. Internal power is applied from terminal +24V/
DCM. Once you install this cooling fan on the motor drive, do not connect any other external
accessory to avoid overload on terminal +24V which will damage the motor drive. Use only
terminals MI after your install the cooling fan.

Applicable Motor
Cooling Fan Model Product Appearance
Drive

MKEL-AFKM1 VFD007EL21W(-1)

Note: the power cable of the cooling fan is about 150mm.

Cooling Fan Installation

1.
Follow the direction of the arrow to remove
the top cover.

2.
As shown in the image on the right, the
direction pointed by the arrow on top of the
cooling fan should face the heat sink.

Fix the cooling fan and its grill by fastening


screws on the heat sink.
Positive pole of the cooling fan: Connect the
red cable to terminal +24V.

Negative pole of the cooling fan: Connect the


black cable to terminal DCM.

B-10
Appendix B Accessories VFD-EL-W

3.
Replace the top cover to complete the
cooling fan installation

B-11
Appendix C How to Select the Right AC Motor Drive

C.1 Capacity Formulas


C.2 General Precautions
C.3 How to Choose a Suitable Motor
The choice of the right AC motor drive for the application is very important and has a big influence on the drive’s
lifetime. If the capacity of the AC motor drive is too large, it cannot provide complete protection to the motor and
motor might be damaged. If the capacity of the AC motor drive is too small, it cannot provide the required
performance and the AC motor drive might be damaged due to overloading.

Simply selecting the AC motor drive with the same capacity as the motor cannot completely meet the application
requirements. Therefore, a designer should consider all the conditions, including load types, load speeds, load
characteristics, operation methods, rated output, rated speed, power and the change in load capacity. The
following table lists the factors you need to consider, depending on your requirements.

Related Specification
Item Speed and
Time Overload Starting
torque
ratings capacity torque
characteristics
Friction load and weight load
Liquid (viscous) load
Load type ● ●
Inertia load
Load with power transmission
Constant torque
Load speed and
Constant output
torque ● ●
Decreasing torque
characteristics
Decreasing output
Constant load
Shock load
Load
Repetitive load ● ● ● ●
characteristics
High starting torque
Low starting torque
Continuous operation
Short-time operation
Operation mode ● ●
Long-time operation at medium/low
speeds
Maximum output current
Rated output (instantaneous) ● ●
Constant output current (continuous)
Maximum frequency
Rated speed ●
Base frequency
Power supply transformer capacity
or percentage impedance
Voltage fluctuations and unbalance
Power supply ● ●
Number of phases, single phase
protection
Frequency
Load capacity Mechanical friction, losses in wiring ● ●
change Duty cycle modification ●

C-1
Appendix C How to Select the Right AC Motor Drive VFD-EL-W

C.1 Capacity Formulas


1. One AC motor drive operates one motor
The starting capacity should be less than 1.5x the rated capacity of the AC motor drive.
The starting capacity equals:

k×N  GD 2 N 
 TL + ×  ≤ 1.5 × the _ capacity _ of _ AC _ motor _ drive(kVA)
973 × η × cos ϕ  375 t A 

2. One AC motor drive operates more than one motor


2.1 The starting capacity should be less than the rated capacity of the AC motor drive.
 Acceleration time ≤ 60 seconds
The starting capacity equals:
k×N  
[nT + ns(ks − 1)] = PC11 + ns (ks − 1) ≤ 1.5 × the _ capacity _ of _ AC _ motor _ drive(kVA)
η × cos ϕ  nT 

 Acceleration time ≥ 60 seconds

The starting capacity equals:

k×N  
[nT + ns(ks − 1)] = PC11 + ns (ks − 1) ≤ the _ capacity _ of _ AC _ motor _ drive(kVA)
η × cos ϕ  nT 

2.2 The current should be less than the rated current of the AC motor drive (A).
 Acceleration time ≤ 60 seconds

nT + IM 1+ nnTS  kS −1  ≤ 1.5 × the _ rated _ current _ of _ AC _ motor _ drive( A)

 Acceleration time ≥ 60 seconds

nT + IM 1+ nnTS  kS −1  ≤ the _ rated _ current _ of _ AC _ motor _ drive( A)

2.3 When running continuously


 The load capacity requirement should be less than the capacity of the AC motor drive (kVA).
The load capacity requirement equals:

k × PM
≤ the _ capacity _ of _ AC _ motor _ drive(kVA)
η × cos ϕ
 The motor capacity should be less than the capacity of the AC motor drive.

k × 3 × VM × IM × 10−3 ≤ the _ capacity _ of _ AC _ motor _ drive(kVA)


 The current should be less than the rated current of the AC motor drive (A).
k × IM ≤ the _ rated _ current _ of _ AC _ motor _ drive( A)

C-2
Appendix C How to Select the Right AC Motor Drive VFD-EL-W

Symbol explanation
PM Motor shaft output for load (kW)
η Motor efficiency (normally approx. 0.85)
cos ϕ Motor power factor (normally approx. 0.75)
VM Motor rated voltage (V)
IM Motor rated current (A), for commercial power
k Correction factor calculated from the current distortion factor
(1.05–1.1, depending on PWM method)
PC1 Continuous motor capacity (kVA)
kS Starting current/rated current of the motor
nT Number of motors in parallel
nS Number of simultaneously started motors
GD 2 Total inertia (GD2) calculated back to motor shaft (kg m2)
TL Load torque
tA Motor acceleration time
N Motor speed

C-3
Appendix C How to Select the Right AC Motor Drive VFD-EL-W

C.2 General Precautions


Selecting an AC Motor Drive
 When connecting the AC motor drive directly to a large-capacity power transformer (600 kVA or higher), or
when switching a phase lead capacitor, excess peak currents may occur in the power input circuit and may
damage the converter section. To avoid this, use an AC input reactor (optional) before the AC motor drive
mains input to reduce the current and improve the input power efficiency.
 When using a special motor or when driving more than one motor in parallel with a single AC motor drive,
select the AC motor drive current to be ≥ 1.25x (sum of the motor rated currents).
 The starting acceleration and deceleration characteristics of a motor are limited by the AC motor drive
rated current and the overload protection. Compared to running the motor D.O.L. (Direct On-Line), you can
expect a lower starting torque output with the AC motor drive. If a higher starting torque is required (such
as for elevators, mixers, tooling machines, etc.), use a higher capacity AC motor drive or increase the
capacities of both the motor and the AC motor drive.
 When a fault occurs on the drive, a protective circuit is activated and the AC motor drive output is turned off.
The motor coasts to stop. For an emergency stop, use an external mechanical brake to quickly stop the
motor.

Setting Parameters
 You can set the AC motor drive to an output frequency up to 400 Hz (less for some models) with the digital
keypad. Setting errors may create a dangerous situation. For safety, setting an upper limit frequency
function is strongly recommended.
 High DC brake operating voltages and long operation time (at low frequencies) may cause overheating of
the motor. In that case, forced external motor cooling is recommended.
 Motor acceleration and deceleration time is determined by motor rated torque, load torque, and load inertia.
 If you activate the stall prevention function, the acceleration and deceleration time is automatically
extended to a length that the AC motor drive can handle. If the motor must decelerate within a certain time
with a higher load inertia than the AC motor drive can handle in the required time, either use an external
brake resistor and/or a brake unit (depending on the model) to shorten deceleration time only, or increase
the capacity of both the motor and the AC motor drive.

C-4
Appendix C How to Select the Right AC Motor Drive VFD-EL-W

C.3 How to Choose a Suitable Motor


Standard Motors
When using the AC motor drive to operate a standard three-phase induction motor, follow these
precautions.
 The energy loss is greater than that for an inverter-duty motor.
 Avoid running the motor at low speed for a long time. Under this condition, the motor temperature may rise
above the motor rating due to limited airflow produced by the motor’s fan. Consider adding external forced
motor cooling.
 When the standard motor operates at low speed for a long time, the output load must be decreased.
 The load tolerance of a standard motor is according to the following diagram.
Load duty-cycle
25%
40% 60%
100
82
torque(%)

70
60
50 continuous

0
3 6 20 60
Frequency (Hz)
 If 100% of continuous torque is required at low speed, it may be necessary to use a special inverter-duty
motor.
 Motor dynamic balance and rotor endurance should be considered once the operating speed exceeds the
rated speed (60Hz) for a standard motor.
 Motor torque characteristics vary when driving the motor with an AC motor drive instead of a commercial
power supply. Check the load torque characteristics of the machine connected to the motor.
 Because of the high carrier frequency PWM control of the VFD series, pay attention to the following motor
vibration problems:
 Resonant mechanical vibration: use anti-vibration dampers to mount equipment that runs at varying speed.
 Motor imbalance: special care is required for operation at 60 Hz and higher frequencies.

 The motor fan is very noisy when the motor speed exceeds 60 Hz or above.

Special Motors
 Pole-changing (Dahlander) motor:
The rated current differs from that of a standard motor. Check before operation and carefully choose the
capacity of the AC motor drive. When changing the number of poles, stop the motor first. If over-current
occurs during operation or the regenerative voltage is too high, let the motor free run to stop (coast).
 Submersible motor:
The rated current is higher than that of a standard motor. Check before operation and carefully choose the
capacity of the AC motor drive. A long motor cable between the AC motor drive and the motor reduces the
available motor torque.
 Explosion-proof (Ex) motor:
Must be installed in a safe place and the wiring should comply with the (Ex) requirements. Delta AC Motor
Drives are not suitable for (Ex) areas that require special precautions.
 Gear reduction motor:
The lubricating method of the reduction gearbox and the speed range for continuous operation are different
and depend on the motor brand. Carefully consider the lubricating method when operating for a long time
at low speed and for high-speed operation.
 Synchronous motor:
The rated current and the starting current are higher than those of standard motors. Check before

C-5
Appendix C How to Select the Right AC Motor Drive VFD-EL-W

operation and carefully choose the capacity of the AC motor drive. When one AC motor drive operates
more than one motors, pay attention to starting and changing the motor.

Power Transmission Mechanism


Pay attention to reduced lubrication when operating equipment such as gear reduction motors, gearboxes,
belts and chains over long periods at low speeds. At high speeds (60 Hz and above), noises and
vibrations that reduce the lifetime of the equipment may occur.

Motor Torque
The motor torque characteristics operated by an AC motor drive depend on the motor model selection and
AC motor drive parameter settings.

C-6
Appendix C How to Select the Right AC Motor Drive VFD-EL-W

This page intentionally left blank.

C-7

You might also like