Documentation Room
Documentation Room
Documentation Room
Calculation Months .................................. Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data .............................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load ........................................................ 2.0 Tons Load occurs at ................................................... Jul 1500
Total coil load ...................................................... 24.5 MBH OA DB / WB .................................................... 87.0 / 71.0 °F
Sensible coil load ................................................ 24.1 MBH Entering DB / WB ............................................ 67.7 / 56.5 °F
Coil CFM at Jul 1500 ......................................... 1294 CFM Leaving DB / WB ............................................. 50.1 / 49.0 °F
Max block CFM .................................................. 1294 CFM Coil ADP .................................................................... 48.1 °F
Sum of peak zone CFM ..................................... 1294 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio ............................................ 0.983 Resulting RH ................................................................ 50 %
CFM/Ton ........................................................... 632.8 Design supply temp. .................................................. 62.6 °F
ft²/Ton .................................................................. 27.4 Zone T-stat Check .................................................. 1 of 1 OK
BTU/(hr·ft²) ........................................................ 438.1 Max zone temperature deviation ................................. 0.0 °F
Water flow @ 10.1 °F rise ................................... 4.87 gpm
Max coil load ....................................................... 22.1 MBH Load occurs at .................................................. Jan 0800
Coil CFM at Jan 0800 ........................................ 1294 CFM BTU/(hr·ft²) .............................................................. 394.8
Max coil CFM ..................................................... 1294 CFM Ent. DB / Lvg DB ............................................. 48.9 / 65.0 °F
Water flow @ 20.0 °F drop .................................. 2.21 gpm
Actual max CFM ................................................ 1294 CFM Fan motor BHP ......................................................... 0.00 BHP
Standard CFM ................................................... 1267 CFM Fan motor kW ........................................................... 0.00 kW
Actual max CFM/ft² ........................................... 23.10 CFM/ft² Fan static .................................................................. 0.00 in wg
Calculation Months .................................. Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data .............................................. Calculated Space CFM Sizing ............ Individual peak space loads
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
DOCUMENTATION ROOM
DOCUMENTATION ROOM 1 4.9 Jul 1500 1294 2.6 56.0 23.10
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 1 CFM
TABLE 1.1.A. Component Loads For Space "DOCUMENTATION ROOM" In Zone "DOCUMENTATION ROOM"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.0 °F / 71.0 °F HEATING OA DB / WB -4.0 °F / -5.3 °F
OCCUPIED T-STAT 66.2 °F OCCUPIED T-STAT 60.8 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 141 ft² 1100 - 141 ft² 2060 -
Roof Transmission 65 ft² 560 - 65 ft² 508 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 56 ft² 0 - 56 ft² 0 -
Partitions 141 ft² 620 - 141 ft² 0 -
Ceiling 56 ft² 246 - 56 ft² 0 -
Overhead Lighting 560 W 1911 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4928 410 - 2567 0
TABLE 1.1.B. Envelope Loads For Space "DOCUMENTATION ROOM" In Zone "DOCUMENTATION ROOM"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 64 0.225 - 439 - 935
E EXPOSURE
WALL 77 0.225 - 661 - 1125
H EXPOSURE
ROOF 65 0.121 - 560 - 508
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.058 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4650.0 BTU/(hr-CFM)
Site Altitude = 568.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.058 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4650.0 BTU/(hr-CFM)
Site Altitude = 568.0 ft
20
Load ( MBH )
15
10
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
4500
4000
3500
3000
BTU/hr
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0.012
0.010
3 45 26 0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( °F )
0.016
0.012
0.010
0.008
2 5 34 0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( °F )