B1115 - Rec Office With ERU
B1115 - Rec Office With ERU
B1115 - Rec Office With ERU
Office
Project Name: Bahrain Marina_Z06_Fresh Air 09/05/2016
Prepared by: Mott MacDonald 02:49PM
Calculation Months ...................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads
Total coil load ............................................................ 0.7 kW Load occurs at ................................................... Jun 1600
Sensible coil load ..................................................... 0.3 kW OA DB / WB ...................................................... 33.3 / 31.0 C
Coil L/s at Jun 1600 .................................................. 25 L/s Entering DB / WB ............................................. 26.8 / 23.1 C
Max coil L/s ............................................................... 25 L/s Leaving DB / WB .............................................. 16.0 / 15.6 C
Sensible heat ratio ............................................... 0.447 Bypass Factor .......................................................... 0.200
Water flow @ 5.6 K rise ......................................... N/A
Actual max L/s ........................................................... 25 L/s Fan motor BHP ........................................................... 0.00 BHP
Standard L/s .............................................................. 25 L/s Fan motor kW .............................................................. 0.00 kW
Actual max L/(s-m) ................................................ 1.53 L/(s-m) Fan static ......................................................................... 0 Pa
Calculation Months ...................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2946.9 W/(L/s)
Site Altitude = 1.8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2946.9 W/(L/s)
Site Altitude = 1.8 m