Air System Sizing Summary for FCU-01

Project Name: SUBX @Dubai Airport 07/15/2017


Prepared by: JS 06:15PM

Air System Information


Air System Name ............................................ FCU-01 Number of zones ........................................................... 1
Equipment Class .......................................... CW AHU Floor Area ................................................................ 53.7 m²
Air System Type ............................................. SZCAV Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s ......................... Sum of space airflow rates Calculation Months ....................................... Jan to Dec
Space L/s ..................... Individual peak space loads Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ....................................................... 20.1 kW Load occurs at .................................................. Jul 1400
Sensible coil load .................................................. 15.4 kW OA DB / WB ................................................... 41.4 / 23.8 °C
Coil L/s at Jul 1400 .............................................. 1226 L/s Entering DB / WB ........................................... 23.9 / 17.9 °C
Max block L/s ...................................................... 1226 L/s Leaving DB / WB ............................................ 13.5 / 12.9 °C
Sum of peak zone L/s .......................................... 1226 L/s Coil ADP .................................................................. 12.3 °C
Sensible heat ratio .............................................. 0.766 Bypass Factor ........................................................ 0.100
m²/kW .................................................................... 2.7 Resulting RH ............................................................... 57 %
W/m² .................................................................. 374.3 Design supply temp. ................................................. 13.0 °C
Water flow @ 6.0 °K rise ....................................... 0.80 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0.0 °K

Supply Fan Sizing Data

Actual max L/s ..................................................... 1226 L/s Fan motor BHP ........................................................ 0.21 BHP
Standard L/s ........................................................ 1225 L/s Fan motor kW .......................................................... 0.17 kW
Actual max L/(s-m²) ............................................ 22.83 L/(s-m²) Fan static .................................................................... 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0.00 L/s/person
L/(s-m²) ................................................................. 0.00 L/(s-m²)

Hourly Analysis Program v4.61 Page 1 of 4


Zone Sizing Summary for FCU-01
Project Name: SUBX @Dubai Airport 07/15/2017
Prepared by: JS 06:15PM

Air System Information


Air System Name ............................................ FCU-01 Number of zones ........................................................... 1
Equipment Class .......................................... CW AHU Floor Area ................................................................ 53.7 m²
Air System Type ............................................. SZCAV Location .......................... Dubai, United Arab Emirates
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates Calculation Months ....................................... Jan to Dec
Space L/s ..................... Individual peak space loads Sizing Data ................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 14.8 1226 1226 Jul 1500 0.0 53.7 22.83

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
BACK BAR 1 10.4 Jul 1500 861 0.0 10.4 82.79
BOH 1 2.3 Jul 1500 191 0.0 7.4 25.88
SEATING AREA 1 2.1 Jul 1500 174 0.0 35.9 4.84

Hourly Analysis Program v4.61 Page 2 of 4


Air System Design Load Summary for FCU-01
Project Name: SUBX @Dubai Airport 07/15/2017
Prepared by: JS 06:15PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.4 °C / 23.8 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 82 m² 473 - 82 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1385 W 970 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 480 W 480 - 0 0 -
People 13 950 677 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 10570 3600 - 0 0
Safety Factor 10% / 10% 1344 428 0% 0 0
>> Total Zone Loads - 14787 4705 - 0 0
Zone Conditioning - 14807 4705 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 70% 0 - 0 0 -
Plenum Lighting Load 30% 416 - 0 0 -
Return Fan Load 1226 L/s 0 - 1226 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1226 L/s 170 - 1226 L/s -170 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 15393 4705 - -170 0
Central Cooling Coil - 15393 4708 - -170 0
>> Total Conditioning - 15393 4708 - -170 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.61 Page 3 of 4


Zone Design Load Summary for FCU-01
Project Name: SUBX @Dubai Airport 07/15/2017
Prepared by: JS 06:15PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.7 °C / 23.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 82 m² 478 - 82 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1385 W 970 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 480 W 480 - 0 0 -
People 13 950 677 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 10570 3600 - 0 0
Safety Factor 10% / 10% 1345 428 0% 0 0
>> Total Zone Loads - 14793 4705 - 0 0