Air System Sizing Summary For FCU-01
Air System Sizing Summary For FCU-01
Air System Sizing Summary For FCU-01
Zone L/s ......................... Sum of space airflow rates Calculation Months ....................................... Jan to Dec
Space L/s ..................... Individual peak space loads Sizing Data ................................................... Calculated
Total coil load ....................................................... 20.1 kW Load occurs at .................................................. Jul 1400
Sensible coil load .................................................. 15.4 kW OA DB / WB ................................................... 41.4 / 23.8 °C
Coil L/s at Jul 1400 .............................................. 1226 L/s Entering DB / WB ........................................... 23.9 / 17.9 °C
Max block L/s ...................................................... 1226 L/s Leaving DB / WB ............................................ 13.5 / 12.9 °C
Sum of peak zone L/s .......................................... 1226 L/s Coil ADP .................................................................. 12.3 °C
Sensible heat ratio .............................................. 0.766 Bypass Factor ........................................................ 0.100
m²/kW .................................................................... 2.7 Resulting RH ............................................................... 57 %
W/m² .................................................................. 374.3 Design supply temp. ................................................. 13.0 °C
Water flow @ 6.0 °K rise ....................................... 0.80 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0.0 °K
Actual max L/s ..................................................... 1226 L/s Fan motor BHP ........................................................ 0.21 BHP
Standard L/s ........................................................ 1225 L/s Fan motor kW .......................................................... 0.17 kW
Actual max L/(s-m²) ............................................ 22.83 L/(s-m²) Fan static .................................................................... 75 Pa