Air System Sizing Summary For Main Deck AHU
Air System Sizing Summary For Main Deck AHU
Air System Sizing Summary For Main Deck AHU
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ..................................................... 124.7 kW Load occurs at ................................................. Jun 1400
Sensible coil load .................................................. 39.1 kW OA DB / WB ................................................... 37.6 / 36.8 °C
Coil L/s at Jun 1400 ............................................. 1527 L/s Entering DB / WB ........................................... 30.7 / 30.3 °C
Max block L/s ...................................................... 1527 L/s Leaving DB / WB ............................................. 9.5 / 10.6 °C
Sum of peak zone L/s .......................................... 1527 L/s Coil ADP .................................................................... 7.1 °C
Sensible heat ratio .............................................. 0.313 Bypass Factor ........................................................ 0.100
m²/kW .................................................................... 1.2 Resulting RH .............................................................. 60 %
W/m² .................................................................. 831.6 Design supply temp. ................................................ 12.0 °C
Water flow @ 5.6 °K rise ....................................... N/A Zone T-stat Check ................................................. 3 of 3 OK
Max zone temperature deviation ................................ 0.0 °K
Max coil load ......................................................... 4.8 kW Load occurs at ................................................. Jun 1300
Coil L/s at Jun 1300 ............................................. 1527 L/s W/m² ........................................................................ 32.2
Max coil L/s ......................................................... 1527 L/s Ent. DB / Lvg DB .............................................. 9.4 / 12.0 °C
Water flow @ 11.1 °K drop ................................... N/A
Actual max L/s ..................................................... 1527 L/s Fan motor BHP ........................................................ 0.00 BHP
Standard L/s ........................................................ 1524 L/s Fan motor kW .......................................................... 0.00 kW
Actual max L/(s-m²) ............................................ 10.19 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................. 894 L/s
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.2 20.9 60 1367.2 12191.5 12741.1 0.0 1975.0 0.0
0100 32.8 20.9 60 1367.2 12041.1 12588.4 0.0 2119.7 0.0
0200 32.5 20.9 60 1367.2 11898.3 12443.3 0.0 2257.2 0.0
0300 32.3 20.9 60 1367.2 11766.9 12309.1 0.0 2384.3 0.0
0400 32.1 20.9 60 1367.2 11649.4 12188.6 0.0 2498.4 0.0
0500 32.0 20.9 60 1367.2 11554.4 12089.6 0.0 2592.2 0.0
0600 32.1 20.9 60 1367.2 11493.3 12023.2 0.0 2655.1 0.0
0700 32.5 20.9 60 1367.2 11529.2 12049.3 0.0 2630.4 0.0
0800 33.0 20.9 60 1367.2 11890.1 12384.4 0.0 2313.0 0.0
0900 33.8 20.9 60 1367.2 12359.3 12824.4 0.0 1896.1 0.0
1000 34.8 20.9 60 1367.2 12816.4 13254.6 0.0 1488.5 0.0
1100 35.9 21.0 60 1367.2 13236.5 13651.1 0.0 1112.9 0.0
1200 36.9 21.0 60 1367.2 13675.4 14066.8 0.0 719.1 0.0
1300 37.6 21.0 60 1367.2 14111.3 14480.7 0.0 326.9 0.0
1400 38.1 21.1 60 1367.2 14883.0 15027.0 0.0 0.0 0.0
1500 38.3 21.4 60 1367.2 15633.9 15406.9 0.0 0.0 0.0
1600 38.1 21.5 60 1367.2 16088.1 15654.3 0.0 0.0 0.0
1700 37.7 21.5 60 1367.2 16046.7 15660.7 0.0 0.0 0.0
1800 37.0 21.2 60 1367.2 15042.9 15187.6 0.0 0.0 0.0
1900 36.2 21.0 60 1367.2 13625.3 14170.4 0.0 620.9 0.0
2000 35.3 21.0 60 1367.2 13081.2 13627.5 0.0 1135.3 0.0
2100 34.7 21.0 60 1367.2 12793.5 13343.3 0.0 1404.5 0.0
2200 34.0 20.9 60 1367.2 12561.6 13112.6 0.0 1623.1 0.0
2300 33.5 20.9 60 1367.2 12363.1 12913.8 0.0 1811.4 0.0
ZONE: Zone 2
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.2 20.8 60 134.2 704.6 728.7 0.0 688.0 0.0
0100 32.8 20.8 60 134.2 699.4 723.5 0.0 692.9 0.0
0200 32.5 20.8 60 134.2 694.7 718.8 0.0 697.4 0.0
0300 32.3 20.8 60 134.2 690.3 714.4 0.0 701.5 0.0
0400 32.1 20.8 60 134.2 686.5 710.6 0.0 705.1 0.0
0500 32.0 20.8 60 134.2 683.7 707.7 0.0 707.9 0.0
0600 32.1 20.8 60 134.2 682.2 706.2 0.0 709.3 0.0
0700 32.5 20.8 60 134.2 688.8 712.5 0.0 703.4 0.0
0800 33.0 20.8 60 134.2 725.4 747.9 0.0 669.8 0.0
0900 33.8 20.8 60 134.2 772.6 793.8 0.0 626.3 0.0
1000 34.8 20.8 60 134.2 805.1 825.6 0.0 596.3 0.0
1100 35.9 20.8 60 134.2 827.7 847.8 0.0 575.2 0.0
1200 36.9 20.8 60 134.2 843.3 863.1 0.0 560.7 0.0
1300 37.6 20.8 60 134.2 852.0 871.8 0.0 552.5 0.0
1400 38.1 20.8 60 134.2 859.3 879.1 0.0 545.5 0.0
1500 38.3 20.8 60 134.2 861.2 881.1 0.0 543.7 0.0
1600 38.1 20.8 60 134.2 852.4 872.7 0.0 551.6 0.0
1700 37.7 20.8 60 134.2 832.3 853.3 0.0 569.9 0.0
1800 37.0 20.8 60 134.2 801.8 823.8 0.0 597.9 0.0
1900 36.2 20.8 60 134.2 767.1 790.1 0.0 629.9 0.0
2000 35.3 20.8 60 134.2 742.5 766.1 0.0 652.6 0.0
2100 34.7 20.8 60 134.2 728.2 752.1 0.0 665.8 0.0
2200 34.0 20.8 60 134.2 718.5 742.5 0.0 674.9 0.0
2300 33.5 20.8 60 134.2 710.8 734.9 0.0 682.1 0.0
ZONE: Zone 3
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.2 21.0 60 26.0 227.5 256.5 0.0 23.6 0.0
0100 32.8 21.0 60 26.0 226.3 254.9 0.0 25.1 0.0
0200 32.5 21.0 60 26.0 225.3 253.4 0.0 26.5 0.0
0300 32.3 21.0 60 26.0 224.3 252.1 0.0 27.8 0.0
0400 32.1 20.9 60 26.0 223.4 250.8 0.0 29.1 0.0
0500 32.0 20.9 60 26.0 222.6 249.6 0.0 30.2 0.0
0600 32.1 20.9 60 26.0 222.0 248.5 0.0 31.2 0.0
0700 32.5 20.9 60 26.0 221.7 247.8 0.0 31.9 0.0
0800 33.0 20.9 60 26.0 223.8 248.8 0.0 30.9 0.0
0900 33.8 21.0 60 26.0 231.7 254.4 0.0 25.6 0.0
1000 34.8 21.0 60 26.0 242.6 262.4 0.0 18.0 0.0
1100 35.9 21.0 60 26.0 253.5 270.6 0.0 10.2 0.0
1200 36.9 21.0 60 26.0 277.0 282.8 0.0 0.0 0.0
1300 37.6 21.1 60 26.0 296.7 285.7 0.0 0.0 0.0
1400 38.1 21.2 60 26.0 307.3 287.6 0.0 0.0 0.0
1500 38.3 21.2 60 26.0 308.1 288.1 0.0 0.0 0.0
1600 38.1 21.2 60 26.0 305.2 288.1 0.0 0.0 0.0
1700 37.7 21.2 60 26.0 293.4 286.7 0.0 0.0 0.0
1800 37.0 21.1 60 26.0 272.5 283.8 0.0 0.0 0.0
1900 36.2 21.0 60 26.0 248.1 275.2 0.0 5.9 0.0
2000 35.3 21.0 60 26.0 237.3 265.8 0.0 14.8 0.0
2100 34.7 21.0 60 26.0 233.1 261.8 0.0 18.6 0.0
2200 34.0 21.0 60 26.0 230.7 259.3 0.0 21.0 0.0
2300 33.5 21.0 60 26.0 229.0 257.3 0.0 22.8 0.0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.0 W/(L/s)
Site Altitude = 15.8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.0 W/(L/s)
Site Altitude = 15.8 m
80
70
60
50
40
30
20
10
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: Zone 1
Data for July
14000
12000
10000
W
8000
6000
4000
2000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 2
Data for July
800
700
600
500
W
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 3
Data for July
250
200
W
150
100
50
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0.035
0.025
0.020
0.015
6
3 45 0.010
0.005
0.000
0 5 10 15 20 25 30 35 40
Temperature ( °C )