Ahu 6
Ahu 6
Ahu 6
Calculation Months ................................ Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................ Calculated Space CFM Sizing ........... Individual peak space loads
Total coil load ..................................................... 1.2 Tons Load occurs at ................................................. Jul 1600
Total coil load ................................................... 14.1 MBH OA DB / WB .................................................. 99.3 / 68.8 °F
Sensible coil load .............................................. 13.7 MBH Entering DB / WB .......................................... 77.4 / 64.4 °F
Coil CFM at Jul 1600 ......................................... 692 CFM Leaving DB / WB ........................................... 58.9 / 57.6 °F
Max block CFM .................................................. 692 CFM Coil ADP ................................................................. 56.8 °F
Sum of peak zone CFM ..................................... 692 CFM Bypass Factor ...................................................... 0.100
Sensible heat ratio .......................................... 0.973 Resulting RH ............................................................. 52 %
CFM/Ton ........................................................ 588.3 Design supply temp. ............................................... 58.0 °F
ft²/Ton ............................................................. 193.8 Zone T-stat Check ................................................ 1 of 1 OK
BTU/(hr·ft²) ....................................................... 61.9 Max zone temperature deviation ............................... 0.0 °F
Water flow @ 10.0 °F rise .................................. N/A
Max coil load ....................................................... 3.1 MBH Load occurs at .................................................. Des Htg
Coil CFM at Des Htg .......................................... 692 CFM BTU/(hr·ft²) ............................................................. 13.5
Max coil CFM ..................................................... 692 CFM Ent. DB / Lvg DB ........................................... 68.7 / 72.9 °F
Water flow @ 20.0 °F drop ................................. N/A
Actual max CFM ................................................ 692 CFM Fan motor BHP ....................................................... 0.00 BHP
Standard CFM ................................................... 686 CFM Fan motor kW ......................................................... 0.00 kW
Actual max CFM/ft² ........................................... 3.03 CFM/ft² Fan static ................................................................ 0.00 in wg
Calculation Months ................................ Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................ Calculated Space CFM Sizing ........... Individual peak space loads
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 31
110.1 Bio Lab 1 12.6 Aug 1600 692 2.0 227.9 3.03
1. Summary
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................ 39 CFM
TABLE 1.1.A. Component Loads For Space "110.1 Bio Lab" In Zone "Zone 31"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 99.3 °F / 68.8 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 96 ft² 2145 - 96 ft² - -
Wall Transmission 225 ft² 417 - 225 ft² 455 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 96 ft² 591 - 96 ft² 720 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 303 W 869 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1900 W 6021 - 0 0 -
People 5 957 1025 0 0 0
Infiltration - 835 -307 - 859 0
Miscellaneous - 753 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 12587 718 - 2034 0
TABLE 1.1.B. Envelope Loads For Space "110.1 Bio Lab" In Zone "Zone 31"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WSW EXPOSURE
WALL 225 0.081 - 417 - 455
WINDOW 1 96 0.300 0.250 591 2145 720
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.071 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4705.2 BTU/(hr-CFM)
Site Altitude = 242.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.071 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4705.2 BTU/(hr-CFM)
Site Altitude = 242.0 ft