System Report - HAP (Factory Building)
System Report - HAP (Factory Building)
System Report - HAP (Factory Building)
Calculation Months ................................ Jan to Dec Zone L/s Sizing ................. Sum of space airflow rates
Sizing Data ............................................ Calculated Space L/s Sizing ............. Individual peak space loads
Total coil load ................................................... 62.8 kW Load occurs at ................................................. Jul 1500
Sensible coil load .............................................. 33.9 kW OA DB / WB .................................................. 34.2 / 28.8 °C
Coil L/s at Jul 1500 .......................................... 3281 L/s Entering DB / WB .......................................... 34.2 / 28.8 °C
Max coil L/s ..................................................... 3281 L/s Leaving DB / WB ........................................... 25.6 / 25.1 °C
Sensible heat ratio .......................................... 0.540 Bypass Factor ....................................................... 0.100
Water flow @ 5.6 K rise ..................................... N/A
Actual max L/s ................................................. 3281 L/s Fan motor BHP ....................................................... 1.91 BHP
Standard L/s .................................................... 3273 L/s Fan motor kW ......................................................... 1.52 kW
Actual max L/(s·m²) .......................................... 1.25 L/(s·m²) Fan static ................................................................. 250 Pa
Calculation Months ................................ Jan to Dec Zone L/s Sizing ................. Sum of space airflow rates
Sizing Data ............................................ Calculated Space L/s Sizing ............. Individual peak space loads
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
Factory Area- DOAS 1 0.0 Jan 0000 3281 0.0 2625.0 1.25
1. Summary
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Design Ventilation Airflow Rate ............................................................ 3281 L/s