Zone Sizing Summary For 3F-Canteen C1: Air System Information
Zone Sizing Summary For 3F-Canteen C1: Air System Information
Zone Sizing Summary For 3F-Canteen C1: Air System Information
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Canteen C1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 443 - 6 m - -
Wall Transmission 19 m 115 - 19 m 55 -
Roof Transmission 70 m 614 - 70 m 140 -
Window Transmission 6 m 236 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 40 m 988 - 40 m 0 -
Overhead Lighting 840 W 840 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 700 W 700 - 0 0 -
People 20 1348 704 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 528 70 0% 0 0
>> Total Zone Loads - 5811 774 - 309 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Canteen C1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 19 0.300 - 115 - 55
WINDOW 1 6 1.900 0.500 236 443 114
H EXPOSURE
ROOF 70 0.200 - 614 - 140
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Canteen C2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 C / 28.9 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 570 - 6 m - -
Wall Transmission 15 m 81 - 15 m 45 -
Roof Transmission 60 m 509 - 60 m 120 -
Window Transmission 6 m 235 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 40 m 985 - 40 m 0 -
Overhead Lighting 720 W 720 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 20 1348 704 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 505 70 0% 0 0
>> Total Zone Loads - 5552 774 - 279 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Canteen C2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 15 0.300 - 81 - 45
WINDOW 1 6 1.900 0.500 235 570 114
H EXPOSURE
ROOF 60 0.200 - 509 - 120
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Canteen C3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 C / 28.9 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 667 - 6 m - -
Wall Transmission 19 m 103 - 19 m 55 -
Roof Transmission 70 m 594 - 70 m 140 -
Window Transmission 6 m 235 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 40 m 985 - 40 m 0 -
Overhead Lighting 840 W 840 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 700 W 700 - 0 0 -
People 20 1348 704 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 547 70 0% 0 0
>> Total Zone Loads - 6018 774 - 309 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Canteen C3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 19 0.300 - 103 - 55
WINDOW 1 6 1.900 0.500 235 667 114
H EXPOSURE
ROOF 70 0.200 - 594 - 140
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Canteen C4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 367 - 6 m - -
Wall Transmission 15 m 89 - 15 m 45 -
Roof Transmission 60 m 526 - 60 m 120 -
Window Transmission 6 m 236 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 40 m 988 - 40 m 0 -
Overhead Lighting 720 W 720 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 20 1348 704 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 487 70 0% 0 0
>> Total Zone Loads - 5362 774 - 279 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Canteen C4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 15 0.300 - 89 - 45
WINDOW 1 6 1.900 0.500 236 367 114
H EXPOSURE
ROOF 60 0.200 - 526 - 120
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Corridor 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 50 m 438 - 50 m 100 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 15 m 371 - 15 m 0 -
Overhead Lighting 1000 W 1000 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 750 W 750 - 0 0 -
People 15 1231 1187 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 379 119 0% 0 0
>> Total Zone Loads - 4169 1305 - 100 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Corridor 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 50 0.200 - 438 - 100
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Corridor 2+Stair 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 443 - 6 m - -
Wall Transmission 19 m 118 - 19 m 57 -
Roof Transmission 110 m 964 - 110 m 220 -
Window Transmission 6 m 236 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 15 m 371 - 15 m 0 -
Overhead Lighting 2200 W 2200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1650 W 1650 - 0 0 -
People 15 1231 1187 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 721 119 0% 0 0
>> Total Zone Loads - 7934 1305 - 391 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Corridor 2+Stair 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 19 0.300 - 118 - 57
WINDOW 1 6 1.900 0.500 236 443 114
H EXPOSURE
ROOF 110 0.200 - 964 - 220
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Corridor 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 55 m 482 - 55 m 110 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 15 m 371 - 15 m 0 -
Overhead Lighting 1100 W 1100 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 825 W 825 - 0 0 -
People 15 1231 1187 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 401 119 0% 0 0
>> Total Zone Loads - 4410 1305 - 110 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Corridor 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 55 0.200 - 482 - 110
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Gym '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 C / 28.9 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 72 m 6097 - 72 m - -
Wall Transmission 191 m 886 - 191 m 573 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 72 m 2267 - 72 m 1368 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 965 m 15262 - 965 m 0 -
Overhead Lighting 19300 W 19298 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 19300 W 19299 - 0 0 -
People 290 60303 92559 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 12341 9256 0% 0 0
>> Total Zone Loads - 135754 101815 - 1941 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Gym '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 97 0.300 - 426 - 291
WINDOW 1 36 1.900 0.500 1134 4003 684
NE EXPOSURE
WALL 94 0.300 - 460 - 282
WINDOW 1 36 1.900 0.500 1134 2093 684
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Library '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.9 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 18 m 1718 - 18 m - -
Wall Transmission 55 m 313 - 55 m 165 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 18 m 577 - 18 m 342 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 53 m 1160 - 53 m 0 -
Overhead Lighting 4560 W 4560 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3420 W 3420 - 0 0 -
People 60 4308 3606 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1606 361 0% 0 0
>> Total Zone Loads - 17661 3967 - 507 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Library '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 55 0.300 - 313 - 165
WINDOW 1 18 1.900 0.500 577 1718 342
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Staff Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 C / 28.9 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 667 - 6 m - -
Wall Transmission 19 m 103 - 19 m 55 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 6 m 235 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 10 m 246 - 10 m 0 -
Overhead Lighting 700 W 700 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 350 W 350 - 0 0 -
People 6 431 360 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 273 36 0% 0 0
>> Total Zone Loads - 3005 397 - 169 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Staff Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 19 0.300 - 103 - 55
WINDOW 1 6 1.900 0.500 235 667 114
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Store '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 443 - 6 m - -
Wall Transmission 19 m 92 - 19 m 55 -
Roof Transmission 48 m 382 - 48 m 96 -
Window Transmission 6 m 190 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 25 m 398 - 25 m 0 -
Overhead Lighting 576 W 576 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 480 W 480 - 0 0 -
People 10 865 1333 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 343 133 0% 0 0
>> Total Zone Loads - 3769 1466 - 265 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Store '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 19 0.300 - 92 - 55
WINDOW 1 6 1.900 0.500 190 443 114
H EXPOSURE
ROOF 48 0.200 - 382 - 96
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Store 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m 1071 - 12 m - -
Wall Transmission 48 m 221 - 48 m 144 -
Roof Transmission 68 m 542 - 68 m 136 -
Window Transmission 12 m 381 - 12 m 228 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 25 m 398 - 25 m 0 -
Overhead Lighting 816 W 816 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 680 W 680 - 0 0 -
People 10 865 1333 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 497 133 0% 0 0
>> Total Zone Loads - 5470 1466 - 508 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Store 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 19 0.300 - 95 - 57
WINDOW 1 6 1.900 0.500 190 443 114
SW EXPOSURE
WALL 29 0.300 - 126 - 87
WINDOW 1 6 1.900 0.500 190 628 114
H EXPOSURE
ROOF 68 0.200 - 542 - 136
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-Supervisor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 C / 28.9 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m 307 - 4 m - -
Wall Transmission 11 m 66 - 11 m 33 -
Roof Transmission 29 m 251 - 29 m 58 -
Window Transmission 4 m 154 - 4 m 76 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 10 m 244 - 10 m 0 -
Overhead Lighting 580 W 580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 290 W 290 - 0 0 -
People 6 431 360 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 232 36 0% 0 0
>> Total Zone Loads - 2555 397 - 167 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-Supervisor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 11 0.300 - 66 - 33
WINDOW 1 4 1.900 0.500 154 307 76
H EXPOSURE
ROOF 29 0.200 - 251 - 58