Learning Area: Presented By: Deep Dutta

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 14

LEARNING AREA

ON
BOP-MECHANICAL MAINTENANCE

Presented by: Deep Dutta


System
Overview
Description

Learning Index

Maintenance
Documentation
Activity
Coagulant
CT Service Potable
Aid
Makeup Water Water
pump pump pump
Coagulant
Clarified Water
Water Properties ≤ 10 NTU
Reservoir

MHRSCC
Chlorine

Diaphragm
Sludge Balanced
STATIC MIXTURE

pump Mud Valve


Sludge Pond

AGITATOR

Middle Pond Reflux pump

Thickener

Sludge
Diaphragm
Balanced Sludge
Mud Valve Screw Raw Water
Balance pump Pump House
Pond Centrifuge
SM
Screw Conveyor

Coagulant
Aid

Water Pre-Treatment Plant


Water Post-Treatment Plant

C.T. BLOW
DOWN Water
C.T. BLOW ETP CALRIFIRE properties :-
DOWN TANK
PUMP CLARIFIED WATER
TANK Turbidity ≤ 10
NTU

NaClO
Sludge To
Sludge Pond
FILTER WATER
TANK

FILTERED
WATER
ULTRA PUMP BACKWASH
Water
FILTARATION PUMP
property:
WATER TANK Turbidity≤0.1 MULTI
NTU GRADE
pH- 6.5 to 7.5 FILTER
U.F. U.F.
WATER BACKWASH
PUMP WATER PUMP
ULTRA-FILTRATION
SYSTEM

Water
TO DRAIN properties :-
Turbidity ≤ 2
NTU
pH- 6.5 to 7.5

TO RO SYSTEM
ACID
ALKALI Auto Flushing COUGULANT
NaClO Unit
ALAKLI
SCALE INHIBITOR
Na BISULPHATE
FROM UF
R.O. EQUIPMENT Water properties :-
TANK
pH= 6 ~ 6.5 , Silica =50
ppm
CARTRIDGE
FILTER

REVESE
RO HIGH
PRESURE OSMOSIS
PUMP WATER TANK
RO FLUSHING
PUMP
TO DRAIN
FOR RO FLUSHING
pH-6.8 to 7.2 pH-6.5 to 8.0
Silica < 20 ppb Silica<0.6 ppm CW BACK WATER
pH-3.5 to PUMP
Conductivity<0. Conductivity<1 4.0
2 0 Na- <2 FOR C.W.
D. M. WATER MIXED ANION ppm. CATION SYSTEM.
TANK BED EXCHANGER EXCHANGER

R.O WATER
D.M. WATER PUMP
PUMP
HYDRO
CHLOCRIC
REGENRATION ACID
PUMP SODIUM
HYDRAOXIDE
HYDRO CHLOCRIC
ACID
+
SODIUM
HYDRAOXIDE

TO
CONDENSATE
STORAGE
TANK
Water Post-Treatment Plant
Cooling Tower Water Inlet Temp. 41.8oC

Water Outlet Temp. 33oC


Hot Air / Steam
(To Atmosphere)
Cooling Range 8.8oC

Drift Loss 41 M3/h


Flume
Evaporation Loss 1032 M3/h
Fan
Blade-8 nos. M M
Dia. – 10 Mtr
Rpm - 114 Hot Water
Distribution
Drift Eliminator

Fill Pack

Cold
Water
To C.W.
Pump
House Cold Water Basin

Hot Water Hot Water


From From
Condenser Condenser
Make Up Water from
Circulating Water Circuit CT Make Up Pump
@ 1271 M³/hr
+
33.0oC Cooling
Boiler Blow Down IDCT
@105 M³/hr Tower
Fore
Bay 41.8oC
Area
Unit Load > 300 MW 2nd
C.W. Pump will start

CW PUMPS
Condenser
3A SPARE
3B
Aux.

Booster Pump For


Coolers
Coolers
To Aux.

Motor Cooling
From

COC < 4, H H
Blow Down CW
@ 303 M³/hr

M After 15° valve


open,
Start CW Pump
M M M M

P=0.2 Mpa
Instrument air Compressor
Air In
Solenoid valve Loading/Unloading
Valve
Air filter Silencer Pressure
exceed
11.5kg/sqm
Compresso
r Stage1 Automatic Blow
Down Valve

Pressure

Manifol
2.0kg/sqm Inter
Oil Compressor

Oil
cooler

d
Sump Stage2

Moisture
Separator
Oil
pump
Compressed
Air Out
Oil After To Dryer
Cooler cooler

Moisture
Pressure
Separator
8.0kg/sqm.
OCCW Temp-46 °C
In & Out
WATER
OIL
AIR
Service air Compressor

After
Coole
Moisture r
Compressed Separator
Air
Discharge

Return
Intake Air Oil Filter
Filter

Compress
or

Separator
Tank
Air
Oil/Air/water
Oil
Return oil
Driers
Air Out

Regulator
Heate
Heater
r

Adsorption Tower
Adsorption Tower Adsorption Tower
Regeneration Tower

Activated
Alumina Compressed Air In
Pressure
8.0kg/sq,m
Temp-46 °C

Muffler

Diffuser

Muffler
QBD burst at
79°C
Fire Fighting System
D
ΔP=1 Kg/cm²,To Start Compressor Fire Fighting Network V
01 Fire Fighting
Pressure HeldNetwork
at

DP
ΔP=2 Kg/cm²,To Start Compressor 02

S
Pressure Transformer
10Kg/cm² at
Held
10Kg/cm²
HVW Spray
PLC 1/3Air+2/3Water
To Stop
Low Water HL Start
Spray close
Level LL
VL HRSCC Priming valve
Tank-19.5
Very Low Water L Hydro (2250 M³/Hr.)

Level pneumatic To
To Hydrant
Hydrant Network
Network
tank(22.5m3)

J J D D DS
HP HP SP
P P HP HP P

Air comp.01& 02
Jockey pump Motor Hydrant pump Diesel Hydrant pump Motor Spray pump Diesel Spray
FAP at 01 & 02 Auto 01 & 02 Auto Start & Auto Start & Manual Auto start & pump Auto Start &
Start & Stop by Manual Stop at Stop 01 & 02 at Manual Stop at Manual Stop at
ccrat
RAP 7 & 6Kg/cm² 5 & 6Kg/cm² 7Kg/cm² 6Kg/cm²
Level Change in
Fire HP-Tank
FIRE WATER RESERVOIR (3500 M³)
Station
Thank you !!