Tranducer

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

DC ISOLATING TRANSDUCER

Applied Standards & Rules


Measuring and conversion IEC 688 / 1992 - 04
Dielectrical strength IEC 688 2KVac / 1 min.
Surge and Impulse test ANSI C37.90 / 1989
IEC 255-3 (1989) 4KV 1.2 x 50 us

Order form
FPD-1 -□-□-□ Single output DC isolation transducer
FPD-2 -□-□-□ Dual output DC isolation transducer
FPDH-1 -□-□-□ Single output DC high voltage isolation transducer
FPDH-2 -□-□-□ Dual output DC high voltage isolation transducer

Pn On Bn Example : FPD-1-A -P -O3

In p u t & O u tp u t p a ram e te rs
An:电流输入范围 Vn:电压输入范围 Pn:电源 rating
Input Ranges Current Input Ranges Voltage Aux. Power Standard range
A1 A2 V1 V2 V3 P1 PD1
0-1m A 0-2m A 0-50m V 0-100m V 0-200m V AC110 V DC110V
120 V ± 15% 120 V ± 15%
A3 A4 V4 V5 V6 P2 PD2
0-5m A 0-10m A 0-500m V 0-1V 0-2V AC220 V D C 2 20V
240 V ± 15% 240V ± 15%
A5 A6 V7 V8 V9 Ps PD3
0-20m A 4-20m A 0-5V 1-5V 0-10V Internal Power DC24 V
24 V ± 20%
A7 A8 V 10 V 11 V 12 Py PDy
0-50m A 10-50m A 2-10V 0-120V 0-200V Specified S p ecified
A9 V 13 V 14
0-75m V 0-350V 0-600V

O n :输出 O1 O2 O3 O4 O5
Output Range 0-1m A 0-20m A 4-20m A 0-5m A 0-10m A

O7 O8 O9 O 10 O 11 O 13
0-1V 0-5V 0-10V 2-10V 1-5V 用户指定

https://www.jihancn.com/ WHATSAPP:+86 13511286898 +86 13511286898 3 -1


DC ISOLATING TRANSDUCER
Specification
A c c u ra c y ( 2 3±3 °C ) 0.2% of effecive range
L in e arty & re p e a tab ility 0.05% typical
D ie le ctric s tre n g th 2 0 0 0Vac ... power / input & output terminals...... FPD
2000Vac ... input / output / case............................FPD
4000Vac ... power / input & output terminals...... FPDH
4000Vac ... input / output / case............................FPDH
O u tp u t d rive c a p ab ility ≤10mA for voltage mode, ≤10V for current mode
M a xim u m in p u t o ve r ≤300Vrms continuous.....> 2V ranges
≤150Vrms continuous....≤2V ranges
≤150mA continuous for current input
In p u t re s is ta n c e -o h m ≤100M ... ≤2V ranges,≤500K...>2V ranges
≤20..... for all current input range
P o w er e ffe c t < 0.003% for per volt chang
R e s p o n se tim e & rip p le 250 ms typically, ripple < 0.1% rms ro
C o m m o n m o d e re je c tio n 120dB, DC to 60Hz
T e m p era tu re d s ta b ility ≤0.007% ro per degree C
S to ra g e c o n d itio n Temperature range -10 to 70°C, RH 20 to 95% non condensed
O p e ra tin g c o n d itio n Temperature range -5 to 55°C, RH 20 to 95% non condensed
P o w er s u p p ly ±10% of rated, less 3.5 VA for AC input
±10% of rated, less 3.5 Watt for DC input
C o n s tru c tio n Socket plug-in type with barrier terminals