AC Voltage Transducer Kusam Meco
AC Voltage Transducer Kusam Meco
AC Voltage Transducer Kusam Meco
STANDARD :
TDV-S INPUT: 0 ~ 150V AC, OUTPUT : 4 ~ 20mA DC, POWER : 110/220V AC
SPECIFICATION
Accuracy : 0.2% RO at 23oC ± 5oC (Self-Power Mode 0.25% RO at 23oC ± 5oC).
Input Range : Normal Voltage 110V Effective 50 ~ 150V.
Input Burden : 0.1VA / 60Hz at 150V AC ; Self-Power Mode 2VA at 150V AC.
Input Over : Normal AC 110V, Voltage Over 500V Continuous.
Self-Power Mode 150V AC Maximum.
Output Load : DC Current Mode: 10V DC Maximum, DC Voltage Mode:10mA DC Maximum.
Output Protection : Without Damage for Output Open or Short Circuit.
Dielectric Strength : 2.6KV AC / 1 Min, between Input / Power / Case.
Impulse : 5KV (1.2X50 mS), ANSI C37.90a / 1983. DIN, IEC 255 - 4, IEC 688-1992
2.5KV - 0.25mS / 1MHz IEC 801-3 (Ring WAVE).
Common Mode Rejection : > 120db, 50 / 60Hz.
Stability : < 0.2% / Year.
Calibration : SPAN and ZERO ± 10%.
Response Time & Ripple(p-p) : £ 400mS. 0 ~ 99%; 0.5% P-P (STD).
Magnetic Effect : DIN - IEE688 £ 0.005% Change 10" Center 100A - Turn.
Temperature Coefficient : £ 100ppm / oC from 0 ~ 60oC; £ 50ppm / 23oC ± 3oC
Operating Condition : -10oC ~ + 65oC, 20 ~ 95% RH Non-Condensed.
Storage Condition : -40oC ~ + 75oC, 20 ~ 95% RH Non-Condensed.
Power Supply : AC or DC ± 20%, 50 / 60Hz 1 f 3VA / AC : 3 f 3VA/AC.
Aux. Power Effect : < 0.01% / V.
Housing Material : ABS Plastic, Self-Extinguishing to UL Subject 94 Class V-O. Case IP 50
Snap Mounting On DIN EN 50022-35 Or Surface Mounting. Compliance With
IEC 529, BS 5490, Din 40054. Protection Touch-Proof Terminals and
Enclosure Meeting Requirements Of VBG 4 & VDE 0106 oart 100(Germany).
Mounting : DIN Rail or Wall Mounting.
Size : 1 f [ 50W X 115H X 73.4L mm ]; 3 f [ 120W X 115H X 73.4L mm ]
*Self-Power Mode : Effective Range 85 ~ 150V, Power Source From V, Voltage.
1
AC Voltage Transducer volt transducer output 4-20mA Kusam Meco voltage transducer Kusum Meco Transducer Kusam-Meco Kusum-Meco Transducer
Outline Dimension : (Unit : mm)
Model : TDV, TDVR
73.4
60
70
115
8.0
40
50
1.6
M5
M4
8.6
2 115 110
120
M5
M4
Terminal Connection :
Model : TDV, TDVR Model : TDV3, TDVR3
I/P A B C
I/P I/P I/P
1 2 3 4 5
1 2 3 4 5 6 7 8 9 10
+ -
Aux Power + - + - + -
Aux Power
+ - + DC - + - + - + - + DC -
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20