Proposal Setting Gi Tanjung Bunga
Proposal Setting Gi Tanjung Bunga
Proposal Setting Gi Tanjung Bunga
No Description Page
II Lampiran
II.1 Diagram Proteksi PUNAGAYA 1 ….............................................................. 19
II.2 Diagram Proteksi PUNAGAYA 2 ….............................................................. 20
PT PLN (PERSERO)
PENYALURAN DAN PUSAT PENGATUR BEBAN
Designation : -F210
Relay Type : Siemens 7SA52
Rated Current : In = 5A
Rated Voltage : Vn = 110 V
1 System Data
Line Length Ln = 59.000 km
Tegangan Nominal Vn = 150 kV
CT Ratio Ct = 2000 / 5A CT = 400
PT Ratio PT = 150000 / 110 V PT = 1364
Freqwency f = 50 Hz
Line angle
Calculate the setting value for the parameter Line angle from the line constants for
the line to be protected as follows:
where:
RL R L Resistance of the line to be protected
XL X L Reactance of the line to be protected
Kr = 3.52
Kx = 1.20
. .
= ∗( . ± .
-1)
= 0.5951
ϑK0 = 2.62
Perhitungan Relay 21
Doc. No (4) QTEP0102-TBG33-S001 Bay OHL PUNAGAYA 1 DAN 2 3 of 18
DISTANCE PROTECTION RELAY
Minimum fault Current
Minumum fault current Ifmin on protected transmission line is the current of the phase to earth of nearest remote
terminal
Ifmin = I0 = I1 = I2 = Vs
(3 x Zs + Zo + Z1x2)
Ifmin = 2.3125 kA
The spread angle of the load trapezoid characteristic ϕloadmust be greater (approx. 5°) than the maximum arising
load angle (corresponding to the minimum power factor cosϕ).
Assume minimum power factor
cosϕmin = 0.8
ϕph-E = = 36.87 degree
ϕph-ph = ϕph-E+5 = 41.87 degree
Assume:
Average tower base resistance 15 15 Ω
Grounding conductor 60 60 mm 2 steel
Distance: Phase-to-tower/phase-to-ground (mid-span) 3 m
Distance: phase-to-phase 5 m
Maximum fault resistance 250 Ω
Perhitungan Relay 21
Doc. No (4) QTEP0102-TBG33-S001 Bay OHL PUNAGAYA 1 DAN 2 4 of 18
DISTANCE PROTECTION RELAY
2 Perhitungan Setting Distance
S1 Line Impedance
S2 Arc impedance + opposite line Impedance
Assume arc impedance is 1.8750 ohm
Opposite Impedance 2 time line impedance
Perhitungan Relay 21
Doc. No (4) QTEP0102-TBG33-S001 Bay OHL PUNAGAYA 1 DAN 2 5 of 18
DISTANCE PROTECTION RELAY
Automatic Reclosing Function
For the cyclic automatic reclosing function, there are 4 operating modes, from which one can be selected for
the parameterization (parameter (_:6601:101) 79 operating mode).
The selection of the operating mode is dependent on the tripping behavior of the protection functions and the
circuit breaker.
The operating mode with op., with act. time allows different automatic reclosing cycles depending
on the tripping type and operate time of the protection function(s). With this operating mode, the automatic
reclosing must be started with the operate indications. Additionally, the general pickup must also be consid-
ered. With raising general pickup, the action times of the configured automatic reclosing cycles start. The general
pickup is in this connection the group indication of all internal protection functions configured for starting the
automatic reclosing and the external binary input for general pickup >Gen. pickup for start .
Through the time between the raising general pickup and clearing operate indication, the automatic reclosing
cycle to be started will be determined. Here for multiple automatic reclosing cycles, the sequence of the
expiring automatic reclosing cycles is not fixed, like the operating modes without action time.
parameter (_:6601:101) 79 operating mode With Op, with Action Time
Synchronization Function
The Synchronization function (ANSI 25) checks whether the activation is permissible without a risk to the
stability of the system when interconnecting 2 parts of an electrical power system. Typical applications are the
synchronization of a line and a busbar or the synchronization of 2 busbars via a cross-coupling. A power
transformer between the 2 measuring points can also be taken into consideration.
The following operating modes are covered:
• Synchrocheck • Switching asynchronous power systems
• Switching synchronous power systems • Switching to dead line line/busbar
In This setting, device only use for Synchrochek Function
The definition of the variables is important for understanding the following implementation. The reference side
1 indicates the function with 1. This yields the reference values voltage V1, frequency f1, and phase angle α1.
The side to be synchronized indicates the function with 2. The electrical variables of side 2 are then the
voltage V2, frequency f2, and phase angle α2.
When forming the differential variables, the function is oriented to the definition of the absolute measuring
error (Δ x = measured value – real value). The reference value and hence the real value is side 1. This results
in the following calculation specifications:
Differential voltage dV = V2 – V1
A positive sign means that the voltage V2 is greater than the voltage V1. In other cases, the sign is negative.
Differential frequency df = f2 – f1
Perhitungan Relay 21
Doc. No (4) QTEP0102-TBG33-S001 Bay OHL PUNAGAYA 1 DAN 2 6 of 18
DISTANCE PROTECTION RELAY
Connection Definition
A positive result means that according to the example from above Figure the busbar frequency is greater than
the line frequency.
Phase-angle difference dα = α2 – α1
Perhitungan Relay 21
Doc. No (4) QTEP0102-TBG33-S001 Bay OHL PUNAGAYA 1 DAN 2 7 of 18
PARAMETER SETTING RELAY PROTEKSI GI 150kV TANJUNG BUNGA ARAH PUNAGAYA 1 DAN 2
DISTANCE PROTECTION RELAY -F210 (7SA52)
132 Teleprot. E/F Dir.Comp.Pickup Dir.Comp.Pickup Teleprotection for Earth fault over-
SIGNALv.ProtInt curr.
UNBLOCKING
BLOCKING
Disabled
133 Auto Reclose 1 AR-cycle Disabled Auto-Reclose Function
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
134 AR control mode Pickup w/ Tact Trip w/ Tact Auto-Reclose control mode
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
135 Synchro-Check Disabled Disabled Synchronism and Voltage Check
Enabled
136 FREQUENCY Prot. Disabled Disabled Over / Underfrequency Protection
Enabled
Quadrateral
1301 Op. mode Z1 Forward Forward Operating mode Z1
Reverse
Non-Directional
Inactive
1302 R(Z1) Ø-Ø 1A 0.050 .. 600.000 Ω R(Z1), Resistance for ph-
ph-faults
5A 0.010 .. 120.000 Ω 0.569 Ω
1303 X(Z1) 1A 0.050 .. 600.000 Ω X(Z1), Reactance
5A 0.010 .. 120.000 Ω 4.222 Ω
1304 RE(Z1) Ø-E 1A 0.050 .. 600.000 Ω RE(Z1), Resistance for ph-
e faults
5A 0.010 .. 120.000 Ω 6.589 Ω
1305 T1-1phase 0.00 .. 30.00 sec; ∞ 0.00 sec T1-1phase, delay for
single phase faults
1306 T1-multi-phase 0.00 .. 30.00 sec; ∞ 0.00 sec T1multi-ph, delay for multi
phase faults
1307 Zone Reduction 0 .. 45 ° 0° Zone Reduction Angle
(load compensation)
1308 Iph>(Z1) 1A 0.05 .. 20.00 A Minimum current for Z1
5A 0.25 .. 100.00 A 1.00 A only Iph>(Z1)
3456 Dead time after 1pole trip 0.01 .. 1800.00sec; ∞ ∞ Dead time after 1pole trip
3457 Dead time after 3pole trip 0.01 .. 1800.00sec; ∞ 0.50 sec Dead time after 3pole trip
3458 Dead time after evolving 0.01 .. 1800.00sec; ∞ 5.00 sec Dead time after evolving
fault fault
3459 CB ready interrogation • YES YES CB ready interrogation
before re-closing • NO before re-closing
3460 Request for synchro-check • YES YES Request for synchro-check
after 3pole AR • NO after 3pole AR
Synchrocheck
3501 Synchronism and Voltage • ON ON Synchronism and Voltage
Check function • OFF Check function
• ON w/o Close Cmd
3502 Voltage threshold dead line 1 .. 100 V 5V Voltage threshold dead line/bus
/bus
3503 Voltage threshold live line 20 .. 125 V 80 V Voltage threshold live line/bus
/bus
3504 Maximum permissible 20 .. 140 V 110 V Maximum permissible
voltage voltage
Designation : -F511
Relay Type : Siemens 7SJ62
Rated Current : In = 5A
Rated Voltage : Vn = 110 V
1 System Data
Line Length Ln = 59.000 km
Tegangan Nominal Vn = 150 kV
CT Ratio Ct = 2000 / 5A CT = 400
PT Ratio PT = 150000 / 110 V PT = 1364
Freqwency f = 50 Hz
Jenis Penghantar : SUTT 2 x ACSR 450 Sqmm
CCC : 1620 A 4.1 sekunder
MVA Base =1.732 * In * Vn = 519.6 MVA
2 Setelan OCR
Isbs = 1.2x CCC Isbs = 1944
3 Setelan GFR
Isbs = 0.3x CCC Isbs = 486
Panel
Device Circuit Breaker 86/1 86/2 79-AR 86B 94
Supply (Central Unit Process)
-Q0 Start
150kV, 10KA
-T5 Main 1 Main 2 Ident. Type Function TC-1 TC-2 Block -K861 -K862 -F210 -K86B -K941 BB1 BB2 Other End Trip
150 0.11 0.11 X -F210 7SA52
21(Z1/Z1B) X X X
kV 21 (Z2/Z3), 67N, SOTF X X
3 3 3
X 50/51 X X
-F511 7SJ8
E 50N/51N X X E
Cl.0.2 X321
=E09+WR1
X X -K941 Tripping Relay 94 X X X
Cl.3P X322 X -K861 Lock Out Relay 1 86/1 X X X
X -K862 Lock Out Relay 2 86/2 X X X
X X -K86B Lock Out Relay Buspro 86B X X X
(BUS PRO Panel) -F87B Bus Bar Protection 87BB X*
Others Trip from other end X
=E09 X* = TRIP WITH DS SELECTED BUS
OHL PUNAGAYA 1
SIMETRIK INTEGRASI@COPY RIGHT 2018
F
CA5 CA7
DATE 28.11.18 PT. PLN (PERSERO) 150kV OHL PUNAGAYA 1 GARDU INDUK 150KV TANJUNG BUNGA (EXT)
= E00.A
UIP SULAWESI BAGIAN SELATAN PT. TEPPO ELECTRIC
DRAFT AP SLD AND TRIPPING MATRIX +
PEKERJAAN PEMBANGUNAN
A For Approval 28.11.18 AP CHECK AL
GARDU INDUK 150KV PUNAGAYA (EXT) PERSADA (3) QTEP0102-TBG01-S001
SH. / CA6
REV DESCRIPTION DATE NAME APPR DAN GARDU INDUK 150KV TANJUNG BUNGA (EXT) BASIC DESIGN SHS
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
(=E10+S1) (=E10+WR1) 1P Voltage Bus A (Protection)
BUS A MARSHALLING KIOSK 150kV Control & Protection Panel 1P Voltage Bus B (Protection)
NEXT
PANEL
-Q1
BUS B 3P Voltage Bus A (Protection)
NEXT
A -SF210 1 phase 3P Voltage Bus B (Protection) PANEL
A
2RMLG02
-Q1 -Q2 -Q2
-Q1
2000A, 40kA 2000A, 40kA
-F210
-SF210
-Q2
M M
21 25 67N 79 68 85 to Tele Prot Panel
2RMLG
(Telecomunication Panel)
-SF210
-Q0
7SA52
2RMLG
-Q9
B B
-Q0 -F511
2000A, 40kA -SF511
46 FR
2RMLG 1P Voltage Bus A (Measurement) NEXT
1P Voltage Bus B (Measurement) PANEL
7SJ86
M
-Q1
3P Voltage Bus A (Measurement)
NEXT
3P Voltage Bus B (Measurement) PANEL
-Q2
P1 -Q1
Core 1
2000-4000/5A CL.PX X311 -A301
2000-4000/5A CL.5P20 -SA301
-Q2
X312
C Core 2 C
2000-4000/5A CL.PX X313 I/O V A 25 Varh W Var Wh FR
-T1 Core 3 2RMLG
2000-4000/5A CL.PX X314 -Q0
Core 4 6MD8
Core 5
2000-4000/5A CL.0.2s X315 -SA301 3 phase
-SA301 1 phase
-Q9
P2 2RMLG 2RMLG02
-Q9
2000A, 40kA
-F741R -F741S -F741T -K861
M
(=ES0+WS1) 74 74 74 86
-SP403 -P403
2RMLG
-F742R -F742S -F742T -K862 -K86B -K941
D -Q8 2RMLG
74 74 74 86 86 94 D
Energy Meter Panel
Tripping Diagram =E10
F10 Power To Other Feeder
Panel
Device Circuit Breaker 86/1 86/2 79-AR 86B 94
Supply (Central Unit Process)
-Q0 Start
150kV, 10KA
-T5 Main 1 Main 2 Ident. Type Function TC-1 TC-2 Block -K861 -K862 -F210 -K86B -K941 BB1 BB2 Other End Trip
150 0.11 0.11 X -F210 7SA52
21(Z1/Z1B) X X X
kV 21 (Z2/Z3), 67N, SOTF X X
3 3 3
X 50/51 X X
-F511 7SJ8
E 50N/51N X X E
Cl.0.2 X321
=E10+WR1
X X -K941 Tripping Relay 94 X X X
Cl.3P X322 X -K861 Lock Out Relay 1 86/1 X X X
X -K862 Lock Out Relay 2 86/2 X X X
X X -K86B Lock Out Relay Buspro 86B X X X
(BUS PRO Panel) -F87B Bus Bar Protection 87BB X*
Others Trip from other end X
=E10 X* = TRIP WITH DS SELECTED BUS
OHL PUNAGAYA 2
SIMETRIK INTEGRASI@COPY RIGHT 2018
F
CA6 CB1
DATE 28.11.18 PT. PLN (PERSERO) 150kV OHL PUNAGAYA 2 GARDU INDUK 150KV TANJUNG BUNGA (EXT)
= E00.A
UIP SULAWESI BAGIAN SELATAN PT. TEPPO ELECTRIC
DRAFT AP SLD AND TRIPPING MATRIX +
PEKERJAAN PEMBANGUNAN
A For Approval 28.11.18 AP CHECK AL
GARDU INDUK 150KV PUNAGAYA (EXT) PERSADA (3) QTEP0102-TBG01-S001
SH. / CA7
REV DESCRIPTION DATE NAME APPR DAN GARDU INDUK 150KV TANJUNG BUNGA (EXT) BASIC DESIGN SHS
1 2 3 4 5 6 7 8