II.1 Set-1 Differential Protection For 380KV Dhahiyah Line-1 RED670
II.1 Set-1 Differential Protection For 380KV Dhahiyah Line-1 RED670
II.1 Set-1 Differential Protection For 380KV Dhahiyah Line-1 RED670
CT Ratio: 3000-2500-2000-1500-1250-1000-
750/1A
Adopted Tap: 2000 A
CT sec.: 1A
Rct: 3.10 ohms
Class: TPS
Ual: 3700 V
Ial: 75 mA @ Ual
Kssc: 31.500 (63000/2000)
K: 12.6 (Ual/(Kssc*Isec*(RCT+Rb))
Diff/Dist. relay (RED670): 0.25 VA RED670 Burden: (VA / I2) = (0.25 /1^2)
(87L) 0.2500 Ohms
Rb = 0.2600 Ohms
Relay (RED670) constants
a: 2.00
Time constant: (45.09 ms)
k: 6.00 (for phase faults)
k: 4.00 (for Earth faults)
Time constant: (49.34 ms)
Distance (2 way): 340.00 mtr Sec. Cable resistance : =Distance x 1.2 x res./mtr
(CT to set1 panel) (Annexure F) = (340 x0.0035x1.2)
1.428 ohms
Cable resistance(ohms/mtr):
SQmm 6 sq mm 0.00350
The CT Accuracy Limiting Voltage (Ual) shall meet the following requirements.
I x a x Rct Rl Rr Rb -2
B) Ual2 k max
I k max1 x I
C) Ual3 sn
x Rct Rl Rb SR/Ir^2 -3
I
pn
I
t max x I
x 2 x Rct Rl SR/Ir^2
sn
D) Ual4 Rb
I -4
pn
Itfdb x I sn /Ipn x Rct Rl SR/Ir^2 Rb -5
E) Ual5
Document Title: CT/PT sizing Calculation DOC No: EE-150546
Ual1 = Accuracy Limit Voltage for end of zone1 Line fault (Dist. Protection)
Ual2 = Accuracy Limit Voltage for close-in Line fault (Dist. Protection)
Ual4, Ual5 = Accuracy Limit Voltage for through fault (Diff. Protection)
Itfdb = Maximum primary fundamental frequency through fault current that passes two main CT's (one
and a half breaker) without passing the protected line
Rr = Relay resistance
k = Factor for the relay which depends on system primary Time constant for zone-1 fault
a = This factor is a function of the primary time constant for the dc component in the fault current.
CT Ual value is decided on the highest value obtained for the formulae 1 to 5 mentioned above.
CT Ual Calculation
Sys. Time const. for end of zone1 3ph.fault = (X/R ratio)/(2*PI*F) =(18.6) / (2 x 3.14 x 60)
= 49.34 ms
Sys. Time const. for end of zone1 1ph.fault = (X/R ratio)/(2*PI*F) =(9.11) / (2 x 3.14 x 60)
= 24.17 ms
System time constant for close-up fault = (X/R ratio)/(2*PI*60) = (17) / (2 x PI x 60)
= 45.09 ms
= 219.75 V - Result 1A
= 116.33 V - Result 1B
Document Title: CT/PT sizing Calculation DOC No: EE-150546
Result 2B is higher than other Results and CT sizing is calculated based on result 2B.