Trafo Differential & Line Differential-2

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

TRANSFORMER DIFFERENTIAL & LINE DIFFERENTIAL CALCULATION

FOR SLOPE 1
ID MIM = Y1 0.2 ID2 0.26
ID MAX = Y3 10
END SECTION-1= X1 1.25 FOR SLOPE 2
END SECTION-2= X2 3 ID2 0.932
SLOPE -1 0.4
SLOPE-2 0.8
Y2 0.9 FOR SLOPE 1
X3-X2 11.375 I1 1.66
X3 14.375 I2 1.4
FOR SLOPE 2
FOR SLOPE 1 I1 3.506
IB2 1.4 I2 2.574

FOR SLOPE 2
IB2 3.04

ALL THE SETTING VALUES IN PER UNIT


NE DIFFERENTIAL CALCULATION

TRAFO RATED POWER IN MVA 800000 VA


TRAFO RATED HV VOLTAGE 66000 V
TRAFO RATED LV VOLTAGE 6600 V
TRAFO RATED HV FL CURRENT 6.9981850712637 A
TRAFO RATED LV FL CURRENT 69.981850712637 A
HV SIDE CT PRIMARY CURRENT 100 A
HV SIDE CT SECONDARY CURRENT 1A
LV SIDE CT PRIMARY CURRENT 1000 A
LV SIDE CT SECONDARY CURRENT 1A
HV SIDE FL SEC CURRENT 0.0699818507126 A
LV SIDE FL SEC CURRENT 0.0699818507126 A
HV SIDE MF 14.2894191825
LV SIDE MF 14.2894191825
INJECTED CURRENT HV SIDE I1 0.116169872183 SLOPE 1
INJECTED CURRENT LV SIDE I2 0.0979745909977 SLOPE 1
INJECTED CURRENT HV SIDE I1 0.2453563685985 SLOPE 2
INJECTED CURRENT LV SIDE I2 0.1801332837343 SLOPE 2