Micromho Distance Relay For Tanta 220 Kvnewfinal

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 15

distance relay micromho setting cal.

Tanta ----- ELAATAF circuit 1

C.T.R 1200 In 1
P.T.R 2200 Un 100
ZONES SEC. PRIM. ko 0.7
Z1 11.78182 21.6 ǿ 82.447
Z2 16.06364 29.45 L KM 90
Z3 36.98182 67.8 UZ 0.545455
Z3R 2.945455 5.4
Z5 36.98182 67.8
Z5R 2.945455 5.4
Z6 47.50909 87.1
Z6R 9.136364 16.75
ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 11.78182

K14 1

k11+k12+13 2.455

k11 2 k12 0.4 k13 0.055

check z1 11.784

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 16.06364

K24 1

k21+k22 3.346591

k21 3 k22 0.35


checkz2 16.08

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 36.98182

k33 1

k31+k32 7.704545
k31 7 k32 0.7
z3 check 36.96
ZONE 3 R MULTIPLECATION FACTORS

Z3R= K33*K34*ZPH 2.945455


K34 0.613636 K34 0.6

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2

POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.07377 k54 0.1

k50 = (k51+k52)*k53*zph K50 = 19.96364 K53 1

Z5 = 2*(1-K54)K50 K53(K51+K52)= 4.159091


K51 4 K52 0.16

check z5 36.98182

Z5R =2*K54*K50 2.945455

Z6= K50.(0.3+2(1-K54)) 42.97091 Z6+Z6R=1.3(Z5+Z5R)

Z6R =K50(0.3+2K54) 8.934545 CHECK 1.3


TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.36 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06
MUTUAL IMPEDANCE
K6 0 K7 0 K8 0

NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 2 8 on on on on on off
K12 0.4 4 on on on on off off
K13 0.055 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 3
k22 0.35
k24 1

option select
K31 7 xy number 0 3
K32 0.7 scheme type POR 3PH TRIP
K33 1 a/b 1
K34 0.6 zph 0
zn 3.36
k21 3 zm 0
k22 0.35 pph theta 4.8
k24 1 gr theta 82.447
mut theta 82.447
distance relay micromho setting cal.
Tanta ----- ETYA circuit 2

C.T.R 800 In 1
P.T.R 1200 Un 110

ZONES SEC. PRIM. ko 0.75


Z1 7.866667 11.8 ǿ 82.447
Z2 11.33333 17 L KM 34.95
Z3 33.33333 50 uz 0.666667
Z3R 2.446667 3.67
Z5 33.33333 50
Z5R 2.446667 3.67

ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k2/ In 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 7.866667

K14 1

k11+k12+13 1.639

k11 1 k12 0.6 k13 0.036

check z1 7.8528

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 11.33333

K24 1

k21+k22 2.361111

k21 2 k22 0.73


checkz2 13.104

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 33.33333

k33 1

k31+k32 6.944444
k31 6 k32 0.628
z3 check 31.8144

ZONE 3 R MULTIPLECATION FACTORS


Z3R= K33*K34*ZPH 2.446667
K34 0.509722 K34 0.5

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2

POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.068381 k54 0.1

k50 = (k51+k52)*k53*zph K50 = 17.89 K53 1

Z5 = 2*(1-K54)K50 K53(K51+K52)= 3.727083


K51 3 K52 0.52

check z5 33.33333

Z5R =2*K54*K50 2.446667

Z6= K50.(0.3+2(1-K54)) 38.70033 Z6+Z6R=1.3(Z5+Z5R)

Z6R =K50(0.3+2K54) 7.813667 CHECK 1.3


TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.6 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06
MUTUAL IMPEDANCE
K6 0 K7 0 K8 0

NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 1 8 on on on on on off
K12 0.6 4 on on on on off off
K13 0.036 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 2
k22 0.73
k24 1

option select
K31 6 xy number 0 3
K32 0.628 scheme type POR 3PH TRIP
K33 1 a/b 1
K34 0.5 zph 0
zn 3.6
k21 2 zm 0
k22 0.73 pph theta 4.8
k24 1 gr theta 82.447
mut theta 82.447
distance relay micromho setting cal.
tanta ----- nubaria circuit

c.t.r 1200 In 5
p.t.r 2200 Un 100
zones ko 0.7
Z1 14.16 ǿ 82
Z2 22.5 L KM 59
Z3 40 uz 0.545455
Z3R 2.5
Z5 40
Z5R 2.5

ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 7.723636
K14 1
k11+k12+13 1.609

k11 1 k12 0.6 k13 0.009

check z1 7.7232

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 12.27273
K24 1
k21+k22 2.556818
k21 2 k22 0.56
checkz2 12.288

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 21.81818


k33 1
k31+k32 4.545455
k31 4 k32 0.55
z3 check 21.84

ZONE 3 reverse MULTIPLECATION FACTORS

Z3R= K33*K34*ZPH 1.363636


K34 0.284091 K34 0.5 check 1.363636

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2


POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.058824 k54 0.1


k50 = (k51+k52)*k53*zph K50 = 11.59091 K53 1
Z5 = 2*(1-K54)K50 K53(K51+K52)= 2.414773
K51 2 K52 0.42
check z5 21.81818
Z5R =2*K54*K50 1.363636
Z6= K50.(0.3+2(1-K54)) 25.29545 Z6+Z6R=1.3(Z5+Z5R)
Z6R =K50(0.3+2K54) 4.840909 CHECK 1.3
TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.36 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06

MUTUAL IMPEDANCE
K6 0 K7 0 K8 0
NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 1 8 on on on on on off
K12 0.6 4 on on on on off off
K13 0.009 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 2
k22 0.56
k24 1
option select
K31 4 xy number 0 3
K32 0.55 scheme type POR 3PH TRIP
K33 1
K34 0.5
a/b 1
zph 4.8
zn 3.36
zm 0
pph theta 82
gr theta 82
mut theta 82
distance relay micromho setting cal.
tanta ----- quasna circuit

c.t.r 1200 In 5 uz 0.545455


p.t.r 2200 Un 100
zones ko 0.7
Z1 4.843636 ǿ 82
Z2 8.476364 L KM 37
Z3 21.81818
Z3R 1.210909
Z5 21.81818
Z5R 1.210909

ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 4.843636
K14 1
k11+k12+13 1.009

k11 1 k12 0 k13 0.01

check z1 4.848

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 8.476364
K24 1
k21+k22 1.765909
k21 1 k22 0.77
checkz2 8.496

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 21.81818


k33 1
k31+k32 4.545455
k31 4 k32 0.55
z3 check 21.84

ZONE 3 reverse MULTIPLECATION FACTORS

Z3R= K33*K34*ZPH 1.210909


K34 0.252273 K34 0.25

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2


POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.052582 k54 0.1


k50 = (k51+k52)*k53*zph K50 = 11.51455 K53 1
Z5 = 2*(1-K54)K50 K53(K51+K52)= 2.398864
K51 2 K52 0.4
check z5 21.81818
Z5R =2*K54*K50 1.210909
Z6= K50.(0.3+2(1-K54)) 25.27255 Z6+Z6R=1.3(Z5+Z5R)
Z6R =K50(0.3+2K54) 4.665273 CHECK 1.3
TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.36 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06

MUTUAL IMPEDANCE
K6 0 K7 0 K8 0
NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 1 8 on on on on on off
K12 0 4 on on on on off off
K13 0.01 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 1
k22 0.77
k24 1

option select
K31 4 xy number 0 3
K32 0.55 scheme type POR 3PH TRIP
K33 1
K34 0.25
a/b 1
zph 4.8
zn 3.36
zm 0
pph theta 82
gr theta 82
mut theta 82
distance relay micromho setting cal.
tanta ----- el mehalla circuit

c.t.r 1200 In 5
p.t.r 2200 Un 100
zones ko 0.7
Z1 4.450909 ǿ 82
Z2 7.134545 Lkm 34
Z3 21.81818 uz 0.545455
Z3R 1.363636
Z5 21.81818
Z5R 1.363636

ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 4.450909
K14 1
k11+k12+13 0.927

k11 0.9 k12 0.03 k13 0

check z1 4.464

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 7.134545
K24 1
k21+k22 1.486364
k21 1 k22 0.49
checkz2 7.152

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 21.81818


k33 1
k31+k32 4.545455
k31 4 k32 0.55
z3 check 21.84

ZONE 3 reverse MULTIPLECATION FACTORS

Z3R= K33*K34*ZPH 1.363636


K34 0.284091 K34 0.28

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2


POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.058824 k54 0.1


k50 = (k51+k52)*k53*zph K50 = 11.59091 K53 1
Z5 = 2*(1-K54)K50 K53(K51+K52)= 2.414773
K51 4 K52 0.43
check z5 21.81818
Z5R =2*K54*K50 1.363636
Z6= K50.(0.3+2(1-K54)) 25.29545 Z6+Z6R=1.3(Z5+Z5R)
Z6R =K50(0.3+2K54) 4.840909 CHECK 1.3
TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.36 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06

MUTUAL IMPEDANCE
K6 0 K7 0 K8 0
NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 0.9 8 on on on on on off
K12 0.03 4 on on on on off off
K13 0 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 1
k22 0.49
k24 1

option select
K31 4 xy number 0 3
K32 0.55 scheme type POR 3PH TRIP
K33 1
K34 0.28
a/b 1
zph 4.8
zn 3.36
zm 0
pph theta 82
gr theta 82
mut theta 82