TECHNICAL FEATURES
• Electronic controller multifunction, industrial use, for air screw compressor operation.
• Developed in accordance to E.C. standards.
• Grey auto-extinguishing box in ABS with protection IP64 for the frontal panel and IP30 for
all the others parts.
• Inputs and outputs via terminal-blocks board to wires.
• Power supply: 12V a.c. ± 10%, 50 ÷ 60 Hz..
• Maximum current with power supply 12V = 250m.A..
• Operating temperature: 0 ÷ 55 °C with 90% RH (not condensing).
• Storage temperature: -20 ÷ +70 °C.
• Visualization through no. 4 numeric green digits displays and no. 8 led (no.1 green and no.7 red).
• no.4 function keys: ON/OFF (Stand by) – working hours visualization – test/reset.
• no.1 emergency stop button.
• no.1 KTY temperature probe to check screw temperature, working range –10 ÷ +130 °C, resolution
1 °C, precision ± 1 °C.
• Check minimum and maximum power supply.
• no.4 digital inputs for connection with lacking phases and reverse survey control.
• no.5 digital inputs from 12V a.c. to detect:
IN 1 motor overload, IN 2 fan overload, IN 3 remote start/stop, IN 4 air filter clogging pressure
switch, IN 5 working pressure switch.
• no.5 outputs via relay - SPST 8 (2) A. 250V a.c., 100.000 cycles electrical life:
RL1 line contactor, RL2 delta contactor, RL3 star contactor, RL4 loading solenoid valve, RL5 fan
contactor.
• no.1 no-volatile memory to store setting data, working hours and alarms holding.
• The electronic controller switches OFF due to micro interruptions of the power supply higher than
350 m.s..
• no.1 temperature probe to check the screw temperature with KTY10.5 sensor, cable in silicon
rubber length 2,5 m, working range –10 ÷ +130 °C, resolution 1 °C, precision ± 1 °C.
• no.1 control phases l unit for power supply at 230V 3phases, 380 ÷ 400 3phases, 440 ÷ 460
3phases.
Rel.5 – 04-11-2004 2
Logika Control s.r.l.
DL1 DL6
DL2 DL7
DL3 DL8
DL9
P3 P1
DL10
EMERG.
R/T 0
P4 P2
Led:
Rel.5 – 04-11-2004 3
Logika Control s.r.l.
x 3 sec.
OFF 0 A-L
PIn
R
Assistance 1 Assistance 2 Factory
= 22 = 444 = 6666
H1 I SET I
H2
P-H I H3
P-H
R P-t H4
P-F H5
R
C-C H6
A-L
P--C
rE-t
Rel.5 – 04-11-2004 4
Logika Control s.r.l.
VISUALIZATION DESCRIPTION
User level
With compressor in OFF pushing the key 0 for 3 seconds the controller visualizes the parameter family
A-L concerning the alarm codes.
Rel.5 – 04-11-2004 5
Logika Control s.r.l.
PARAMETERS SETTING
With compressor in OFF, pushing the key 0 and subsequently the key (both pushed)
the controller enters in parameters setting with the visualization on the display of the message “Pin1”:
with the buttons and/or R/T set on the last figure the pin number (1÷3) and confirm by the button
I.
The display visualizes:
-with selection pin no.1, the last figure blinks and the next one to the last figure is fixed.
-with selection pin no.2, the last figure blinks and the following 2 figures are fixed.
-with selection pin no.3, the last figure blinks and the following 3 figures are fixed.
With the buttons and/or R/T set the first figure and confirm it by the button I,
the second figure starts to blink; set the following figures on the same way.
With the set of the last figure of the pin number set, pushing the button I the display
shows the first family of the parameters, “P-P”, concerning the pressure parameters.
If the pin number set is wrong the message visualized is “Pin”, blinking for 2 seconds and then the
compressor turns in OFF.
Assistance no.1 (pin level 1) = set 0 ÷ 99, default 22
Assistance no.2 (pin level 2) = set 0 ÷ 999, default 444
Factory (pin level 3) = set 0 ÷ 9999, default 6666
Attention:
in case of lost of the pin number, power on the compressor pushing the button for 5 seconds and
than all the led blink for 3 seconds advising that the default pin values of the
3 levels have been loaded.
Rel.5 – 04-11-2004 6
Logika Control s.r.l.
After the last parameter the controller turns back to the visualization of the message “P-H”.
After the last parameter the controller returns to the visualization of the message “P-t”.
Changing the set value, the new value is stored at the end of the counter in progress.
After the last parameter the controller returns to the visualization of the message “P-F”.
Attention:
1) The counter value is automatically reset by changing the set value.
2) The new value is stored at the end of the counter in progress or after the counter reset.
3) If the parameter C—h is set to 9.999 hrs. the controller doesn’t show the relevant alarm.
4) The calculation concerning the ON time of the line contactor (RL1) is effected backwards:
when the calculation reaches 0 it produces the relevant alarm and it goes on as negative
counting.
Rel.5 – 04-11-2004 7
Logika Control s.r.l.
After the last parameter the controller turns back to the visualization of the message “C-C”.
Attention: the modification of parameter R-- (man/aut) is stored in alarms and it is possible to reset by
general reset only.
Confirming by the button I, the message xAL.yy is visualized: x is the number of times
the same alarm code has been detected in sequence and yy is the alarm code number.
In case the value of x is more than 9 times, the message is visualized.
By the buttons and/or R/T the display flows the whole alarm buffer, after the last alarm the
controller returns to the visualization of the message “A-L”.
If there is not any alarm in memory, the display visualizes “----“.
On the display the message “Pin 1” is visualized (pushing the button 0 the controller turns back to the
message “P—C”); by the buttons and/or R/T set the pin number (1÷3) and confirm it by the
button I, the display will show:
-with selection pin no.1, the last figure blinks and next one to the last figure is fixed.
-with selection pin no.2, the last figure blinks and the following 2 figures are fixed.
-with selection pin no.3, the last figure blinks and the following 3 figures are fixed.
By the buttons and/or R/T set the first figure and confirm it by the button I, the second figure starts
to blink; set the following figures on the same way.
With the set of the last figure of the pin number set, pushing the button I the new pin number of the
level selected is stored and the controller returns to the visualization of the message “P—C”.
Rel.5 – 04-11-2004 8
Logika Control s.r.l.
rE-t = Reset
After selected the parameter, pushing the button R/T, the parameter blinks to point out the operation
reset; with this operation the value memory is reset and the default parameters is stored.
After the last parameter the controller turns back to the visualization of the message “RE-t”.
Rel.5 – 04-11-2004 9
Logika Control s.r.l.
ALARMS
Alarms with prompt stop of the compressor and visualization on the display of the message “AL”
+ relevant led or alarm message
Alarms with stop of the compressor after an idle running time of 30 sec. and visualization of
message “AL” + relevant led on the display
Attention: The alarm “low power supply” (code 21) is not detected if it’s not activated on
menu C-C (compressor configuration).
Rel.5 – 04-11-2004 10
Logika Control s.r.l.
Alarms without stop of the compressor and visualization of alarm code + relvante led alternate
with the main visualisation
When the compressor stops all the relays are switched off.
To reset the stop alarms, push the button R/T with the compressor in OFF status.
To reset the visual alarms only, push the button R/T even if the compressor is working.
Rel.5 – 04-11-2004 11
Logika Control s.r.l.
In every step of the reading hours visualization or reading messages, pushing the button R/T the
controller returns to the main visualization.
With hours visualization higher than 9.999, the last digit of the display visualizes two horizontal
segments to point out that the multiplicative factor is x 100.
If the hourmeter is negative on the first digit has the sign “–“ and the top range is max. 999 hrs.
Automatic restart: in case of lacking power supply, the compressor restarts automatically with a delay
time equal t5; during this time the message “OFF” blinks.
Manual restart: in case of lacking power supply, the compressor doesn' t restart automatically and the
display visualizes the message “P-OF”; after the alarm reset by pushing the button I the compressor
goes in RUN status.
Rel.5 – 04-11-2004 12
Logika Control s.r.l.
NOTES ON OPERATION
Security time t5
By pushing the stop button 0, the compressor stops according the following procedures:
a) If the compressor is on Load phase, it changes into Idle phase for the time set on t5. During this time
the compressor restarts by the start button; when the timer t5 is over the compressor turns off with the
message “OFF”.
b) If the compressor is on Idle phase and the value of t4 is higher than t5, when t4 is over the
compressor turns off with the message “OFF”; if t4 is lower than t5, the timer t5 goes on and when it
is over the compressor turns off with the message “OFF”.
c) If the compressor is in “Set” status, it turns off with the message “OFF”.
d) When the compressor stops and the message “OFF” appears on the display, the timer t5 starts;
during this time if the start button is pushed, the message “OFF” starts blinking and the compressor
doesn’t start; it starts only when the timer t5 is over.
In case of compressor stops because of an alarm, the timer t5 starts; during this time if the alarm is reset
and the start button is pushed, the message “OFF” blinks and the compressor doesn’t start. When the
timer is over, the compressor will start.
a) t4 = 0 - fixed time
When the pressure reaches the stop set, RL4 turns off with the message “Set” on the display and the
timer t4 starts; when t4 is over, if the pressure is higher than the start set the compressor turns off;
during the timer counting if the pressure decreases under the start set, the load solenoid valve (RL4)
goes ON with visualization of the temperature on the display and the timer t4 is erased.
b) t4 = 1 - variable time
On the first start the compressor operates the cycle as to point a). On the next cycle the controller
counts how long the pressure takes from the stop set to the start set; if this time -tx- is higher than the
timer t4, on the following cycle the timer t4 will decrease of 1 minute and so on up to a minimum time
of 2 minutes.
When -tx- comes to be lower than t4 changed, the set value of t4 is loaded again.
Rel.5 – 04-11-2004 13
Logika Control s.r.l.
When the Start/Stop input (IN3) is open the compressor stops according the following procedures:
a) If the pressure is between Start and Stop set, with the load solenoid valve (RL4) in ON and DL1
fixed (Load Running), the load solenoid valve (RL4) goes OFF for the timer t4 with the blinking
message “Stop”. When the timer is over, if the Start/Stop input (IN3) is still open the compressor turns
OFF with the message “Stop” fixed; during the timer t4 if the Start/Stop input (IN3) is closed, the
compressor turns back under the pressure switch control.
b) If the pressure is between Start and Stop set, with the load solenoid valve (RL4) in OFF and DL1
blinking (Idle Running), when the timer t4 is elapsed, the compressor stops with the message “StOP”
fixed.
c) If the compressor is in “SEt” status, the display visualizes the message “StOP” fixed.
With the delta contactor activated (RL2) the fan contactor is operated (RL5) with the following
procedures:
Rel.5 – 04-11-2004 14
Logika Control s.r.l.
Rel.5 – 04-11-2004 15
Logika Control s.r.l.
LEGEND
Terminal Board M1
Pole no.1-2 = power supply 12V a.c.
Terminal Board M2
Pole no.1 = from T control phases
Pole no.2 = from S phases control
Pole no.3 = from R control phases
Pole no.4 = from GND control phases
Terminal Board M3
Pole no.1-2 = screw temperature probe
Terminal Board M5
Pole no.1 = IN 1 = motor overload
Pole no.2 = IN 2 = fan motor overload
Pole no.3 = IN 3 = remote Start/Stop
Pole no.4 = IN 4 = air filter pressure switch
Pole no.5 = IN 5 = working pressure switch
Pole no.6 = Common = 0V a.c.
Thermal Board M6
Pole no.1 = Fan motor output = K4 = RL5
Pole no.2 = Delta contactor output = K2 = RL2
Pole no.3 = Star contactor output = K3 = RL3
Pole no.4 = Load solenoid valve output = EV1 = RL4
Pole no.5 = Line contactor output = K1 = RL1
Pole no.6 = Common = 230 ÷ 24V a.c.
Rel.5 – 04-11-2004 16
Logika Control s.r.l.
All manufactured products have 2 (two) years warranty starting from the date of production, which is
printed on the serial number label with identification of:
Example 2004 05 00215
the first 4 characters the year, the seconds 2 the week and the last 5 the progressive number of the
device.
The warranty is invalidated whenever the causes of the malfunction are clearly imputable to
negligence, mishandling or improper use of the instrument by the customer.
In order to return damages devices, the customer must require to Logika Control an authorization
number to write on the return documents.
The customer is expected to enclosed a report with the goods returned specifying the code, serial
number and description of the fault found.
Forwarding expenses are always charged to the customer, otherwise return expenses shall also be
charged to the customer.
Repairs shall be carried out within 30 days from the date of the receipt of the damaged devices.
With respect to all returned devices checked, Logika Control undertakes to specify the faults found, the
repairs carried out and the reason of any failure.
Repairs over the warranty period shall be charged to the customer and include the cost of labour plus
component replacement.
Revisions index:
software release no. 1.2 = handbook rev. 3.
software release no. 1.3 = handbook rev. 4.. Add AL13 alarm, new numeration of alarm, add the t5 timer for Emergency
stop button.
software release no. 1.4 = handbook rev. 5: updating timer t5 operation.