1-2 Major Component Specifications (B) Outdoor Unit

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1.

Specifications

1-2 Major Component Specifications


(B) Outdoor Unit

Model No. SPW-C253G5 SPW-C303G5 SPW-C363G5


SPW-C253G5/M SPW-C303G5/M SPW-C363G5/M
Source 220 - 230 - 240 V / 1 phase / 50 Hz
Compressor Rotary (Hermetic)
Model ... Code No. C - R221H5V C - R240H5W
Nominal output W 2,200 2,400
Compressor oil cc 1,350
Coil resistance (at 25°C) C - R : 0.76, C - S : 2.76 C - R : 0.69, R - S : 3.34, S - C : 2.66
Refrigerant amount at shipment kg R22 - 2.4 R22 - 2.6 R22 - 4.2
Safety device Internal / OL - D24 Internal type
1 Operating temperature Open °C 160 ± 5 / 150 ± 10 175 ± 5
Close °C 87 ± 9 / 63 ± 10 105 ± 9
Run capacitor V, µF 400V, 40
High pressure switch ACB - 1TB07
2 + 2.0
Set pressure OFF kg/cm 30 + 0.5
ON kg/cm2 24 ± 2.0
Fan (Number…diameter (mm)) Propeller (1…ø 460) Propeller (2…ø 460)
Fan motor
Model…Nominal output W KFC6S - 91C5P…100 W KFC6S - 91C5PX2
100WX2
No. of pole ... rpm (230V, High) rpm 6...868 6…871
Coil resistance BRW – WHT : 61.0
(Ambient temperature 20°C) YEL – PNK : 17.7
WHT – YEL : 64.3
Safety device Internal type Internal type
Operating temperature Open °C 130 ± 8 130 ± 8
Close °C 79 ± 15 79 ± 15
Run capacitor VAC, µF 440 V, 5 µF 440 V, 5 µF / 5 µF
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows ... fin pitch mm 2...2.0 2...2.0
Face area m2 0.616 1.08

SM830042
– 18 –