"Air Control 2": 1. General
"Air Control 2": 1. General
"Air Control 2": 1. General
1. General:
A IR C O N T R O L 2
ENTER
w w w . a lm i g . d e
a) Microprocessor logic (with EEPROM memory for data back-up) for all control, monitoring and
display functions;
b) Keyboard with 5 keys for switching the compressor on and off, and for entering recommended
and limit settings;
c) Customized LCD display for showing the current actual and recommended parameters and the
operating status, plus faults/warnings;
2.2) Keyboard:
5 keys,
Customized finish.
2.3) Display:
LCD with display area approx. 75mm* 50mm:
- 7-segment A => 3-digit, 7-segment display (top left);
- 7-segment B => 3-digit, 7-segment display (top right);
- 7-segment C => 1½--digit, 7-segment display (left center);
- 7-segment D => 5-digit, 7-segment display (down);
- symbols for units: oC, oF, oK, bar, psi and MPa;
- symbols also for: fault, warning, motor, solenoid valve,
heating, fan, remote operation, restart, automatic (mode),
BLCO (base-load-change-over mode);
1 LED (red);
2.10 Wiring:
1 Signal + (A) ) [Frequency Converter: R+]
2 Signal – (B) ) 1st RS485 interface [FU: R-]
3 Earth ) (Frequency converter)
4 NC )
5 Common ) group fault (potential-free)
6 NO )
9 Mains phase )
10 N ) 230V~ mains feed
11 Protective earth )
12 Motor phase )
13 N ) Fan motor selection
14 Protective earth )
15 Valve phase )
16 N ) solenoid valve selection
17 Protective earth )
18 Earth )
19 Signal - (B) ) Option: 2nd RS485 interface
20 Schnittstelle 2
19 RS485
18
38
Optionsmodul DE 6 (Trockner ok)
steckbar 37
36 steckbares
35 DE 5 (Temp.Begrenz.)) I/O
34 Erweiterungs-
33 DE 4 (GLW ok)
modul
32 DE 3 (Fern Last/Leer)
31
30
29 DE 2 (Fern Ein/Aus)
10
12
13
14
15
16
17
21
22
23
24
11
1
2
3
4
5
6
7
8
(Schlau ch 6mm )
Schnittstelle 1
te mp.)
(p oten tia lfrei)
(pot entialfre i)
Ma gnetven til
Drucksensor
L üftermot or
(Freque nz-
um richter)
Anschluß
H eizung
RS 485
PTC
X91
X90
Steckplatz für
optionale Schnittstelle
(R S- 48 5)
X82
Anschluß
Drucksensor
(Schlauch 6x1 mm)
X80
X1 X2 X3 X4 X5 X6 X7 X8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 5 16 1 7 1 8 19 2 0 21 22 23 24
If a key is assigned to multiple use, then the next position is selected each time it is pressed.
<red LED> : flashes for warning/service message, steady light for fault;
I : Switch on compressor;
Press the 0-key in the basic display for more than 3 seconds ...
Using the up-/down-keys, the necessary code (customer-, service-, factory-code) can be input.
By pressing the ENTER-key the actual code will be accepted, pressing the 0-key will abort
the code-input.
First the adequate code has to be input (see: item 3.1 / code input).
Afterwards the corresponding code-level can be selected, using the up-/down-keys.
Only those code-levels are displayed, which can be altered with the actual code.
Pressing the ENTER-key will activate the selected code-level.
Pressing the 0-key results in returning one level ( selection of code-level basic screen ).
All parameters, which can be altered in the basic display by pressing the ENTER-key, can only
be edited when code-level “1” is activated before, apart from that only the display can be
shown.
If the operation mode "AUTOMATIK" is selected, you can see that at the symbol "Automatic"
If the compressor motor is running and the air end temperature is over the limit „Switching On temp.“
then the fan is switched on. If the compressor motor does not run, or the air end temperature is
sinking under the limit „Switching Off temp.“, then the fan is switched off.
After switching on the fan, first the given delay time (0-99s) is running, before the fan power was
controlled for the given limit.
If the fan power is higher than the given „max. fan power”, after procedure of delay time (and is this
limit > 0), or the input is "DE 1 / fan OK" (clamps 27+28) open, then the compressor is switching
off, with fault [7] „hiCur“.
If the fan power is lower than the „min.fan power“ for a longer time than the delay time
(and this limit is > 0), then the compressor is switching off with fault [8] „LoCur“.
If remote control has been switched in and the systems is keyed (via the I key), then this is
indicated by the Remote symbol
If the system is switched off using the 0 key, then the Remote symbol in the LCD is
extinguished once more.
This temperature will be used for the switching On / Off, only if „modus = 1“ and
the compressor is in operation (see also 3.5.7).
If the additional heating is deactivated (modus = 0 ), then the 2.KTY-Sensor (heating
temperature / only at “new” AirControl-2 available! ) will not be monitored for wire fault.
In this case the 1. KTY-sensor ( air end temperature) will be used for the control of
rely output for additional heating !
0 = not BLCO mode, e.g. Load/No load via local pressure sensor
1 = BLCO mode, Load/No load via the optional RS485 interface
or input “S2” on FU control
or input “DE 3” on option board
If BLCO mode has been activated and the BLCO-OK signal from the BLCO control unit
(via RS485 or via input S4 on the FU control or input “DE 4” on the option board) is present,
then this is indicated by the BLCO symbol in the LCD
In BLCO mode, the local pressure sensor is used purely for monitoring the safety pressure
(P_ALLOWED).
If the data exchange via the interface is interrupted for more than 20 seconds and signal “BLCO-
OK” from input “S4” on the FU control or from input “DE 4” on the option board, then the
control unit switches back to Local mode.
The BLCO symbol, in this case, is again extinguished in the LCD.
Code-level 30 selected :
If the current position is not reserved, then the following notice is shown:
7‐Segm.A,B => Err ###
‐
7‐Segm.C =>
‐ ‐ ‐ ‐ ‐ ‐
7‐Segm.D =>
The arrow key allows to page
through 20 positionen of fault
logger. Position 1 includes always
the „new“failure ! The individual
positiones of fault logger will be filed
at the EEPROM‐memory and they be
available also after a power failure.
AirControl ALMiG V1.72_gb Page 13 of 33 07/2015
3.2.10) Editing of set point for
maintenance intervals:
a) Air filter:
Select code-level 41 => 7-segment A,B 000 041
7-segment C 1
#####h
7-segment D
b) Oil/oil filter:
Select code-level 42 => 7-segment A,B 000 042
7-segment C 1
#####h
7-segment D
c) Oil separator:
Select code-level 43 => 7-segment A,B 000 043
7-segment C 1
7-segment D #####h
d) Motor lubrication:
Select code-level 44 => 7-segment A,B
000 044
7-segment C 1
7-segment D #####h
e) Compressor:
Select code-level 45 => 7-segment A,B
000 045
7-segment C 1
7-segment CD #####h
You can use the arrow keys in steps of 500 to select the relevant recommended value,
and then accept with the ENTER key (range: 0-20,000 hours).
If you accept a recommended setting with the ENTER key, then the relevant
interval (remaining time) is also started afresh with the recommended setting.
Dependent on the system type selected here, the following parameters: Run- up time, maximum
number of cycles (ABO), No loa d time, speed reduction by (mA), speed reduction (bar),
min. control range (%) and the servicing intervals are preset with the backing table values.
The upper pressure threshold is preset to the value chosen here and the lower pressure threshold
is preset to 2.0 bar.
The pressure range set here is also used as the upper limit when editing the lower and upper
pressure threshold settings (refer to: Item 3.1 / ENTER key).
The maximum quantity delivered for the compressor is specified here (in m³/h !)
The pressure can be regulate, at which the max. set point for the frequency converter is limited.
(Adjustment range : 5.0 to 13.0 bar // Basic setting : 5.0 bar, at „FLEX 15“: 8,0 bar)
The pressure can be regulate, from them the max. set point for the frequency converter is not further
limited (Adjustment range : 5.0 bis 14.0 bar // Basic setting : 13.0 bar )
The current value can be regulate, which about the max. set point should be lowered at most
( Adjustment range: 3 bis 15 mA // Basic setting: 12 mA // 20mA = FU 100% ! )
Here you can regulate the reset time ( I-part of controller, at „0“ => no share I-part ! ) .
(Range : 0 bis 9999 Sek. // Basic setting : 8 Sek.)
Range: 0 = without
1 = with dryer
If the value “1” (e.g. “with dryer”) is programmed, then a fault message will be triggered if
signal "dryer OK" on input "S3" of the frequency converter control is missing.
If an option board is installed then a fault message will be triggered if the signal “Dryer OK”
(DE 6) is missing.
Select code-level 105 => Here, the displayed value of pressure can be adapt from
-0,5bar to +0,5bar to get the same value at several displays.
Select code-level 9900 => Press the '0'-button is deleting the operating- and load hours
ATTENTION: You have to make sure that all connected compressors have their own address set !
Additionally the considering interface module (RS485) have to be available at the
control !
ATTENTION: Note that you have to set all connected compressor with the same baut rate
(transmission speed) !
--------------------
ENTER => 7-Segm.A,B 009 980
7-Segm.C 8 8 = Output 1
#
7-Segm.D (0= Off-/1=Switch on)
Select code-level 9999 => Confirm with Enter = Installed software version
will be displayed
Confirm again with Enter = Random number will be displayed
(is needed for generating daily code)
3.4.1) Fault: The Tool symbol flashes and the relevant number is shown
flashing in the "7- segment C" field.
7-Segm.C 7-Segm.D
[ 1] [Por ] "Incorrect setting" (Change recommended pressure settings)
[ 2] [EPROm] "EEPROM?" (Change all settings)
[ 3] [Lo AC] "Low voltage" (only if detection is activated/refer to: item 3.6)
[ 4] [No AC] "Power cut" (only if Automatic Restart is not set)
[ 5] [DEFEC] "Incor.compens.setting" (Check for repairs / co mpensation)
[ 6] [mot t] "Motor temperature" (PTC )
[ 7] [hiCur] "Fan current too high" Fan current > max. fan current )_ and delay
[ 8] [LoCur] "Fan current too low" Fan current < min. fan current ) cycled
[ 9] [SE t ] "Temp.sensor def." (monitoring: KTY sensor 1 compressor temp.)
[10] [SE P ] "Press. sensor def." (monitoring: pressure sensor)
[11] [hi t ] "Compr.temp.too high" (Temperature > max. compression temperature)
[12] [hi P ] "Network pres. too high" (Network pressure > Safety pressure)
[13] [FU ] "FU fault" Frequency converter does not respond or registers a fault
[14] [dryEr] “Dryer fault” Signal “dryer OK” missing
[15] [SE t2] “Heating temp.sens.fault” (Monitoring: KTY sensor 2 / heating temperature)
If any of these faults appear, then this leads to the compressor switching off.
The red LED stays on until the fault has been cleared. The fault can only be cleared with the 0 key if
its cause has been rectified in the interim.
3.4.2) Warning/Servicing: The Warning Triangle symbol flashes and the relevant
number is shown flashing in the "7- segment C" field.
7-Segm.C 7-Segm.D
[ 2] [hi t ] "Compr.temperature up" (Temperature > max. compression temp. - 5°C )
[ 3] [hi P ] "Network pressure up" (pressure > [safety pressure - 0.3 bar])
[ 4] [Cold ] "Comp. temp. too low" (temperature < +1°C)
[ 5] [oilHE] "Oillevel/Heating" „Heating activated“, and no signal on „DE 5“
[11] [m Air] "Air filter servicing" (Time to service < 100 hours)
[12] [mOilF] "Oil/oil filter servicing" (Time to service < 100 hours)
[13] [m SEP] "Oil separator servicing" (Time to service < 100 hours)
[14] [m mot] "Lubrication servicing" (Time to service < 100 hours)
[15] [m Com] "Compressor servicing" (Time to service < 100 hours)
3.5.1) Modes:
b) the compressor is switched on, but the current pressure is still higher than the lower
pressure threshold (run-up guard).
- the Motor and Solenoid valve symbols are off
- the text “run” =is flashing in the lower 7-segment indicator
c) The compressor is switched on, but the compressor temperature (or heating temperature if
operated “with heating”) is still less than +1°C
- the Motor and Solenoid valve symbols are off
- the temperature unit symbol is flashing (LCD: °C/°F/K)
- the text “cold” =is flashing in the lower 7-segment indicator
d) The compressor is in operation, but the load valve is switched off, e.g. the compressor is not
compressing. (run -up phase or no load)
- the Motor symbol is on
- the Load Valve symbol is off
If the compressor is in the "Automatic" operating mode, or "Automatic Opt." and the idling
time is active, this is shown in the lower 7-segment display.*
a) AUTOMATIC mode:
After reaching the upper pressure threshold, the system moves to NO LOAD for the duration of
the tracking time (see: 3.2.6).
After the no load time has elapsed, the motor switches off.
After switching off, the text run flashes => ready for a new start-up.
As soon as the pressure is again less than the lower pressure threshold, the system restarts.
The compressor alternates between Load and No Load modes, for example it tracks with no
time restriction.
If the current network pressure is above the set pressure threshold when the compressor is
switched on, then the text run flashes. Only when the network pressure falls below the threshold
does the compressor start.
If the compressor temperature (or heating temperature if operated “with heating”) when
switching on is below +1°C, then the temperature unit (°C/°F/°K) flashes, as does the text
“Cold”.
If the temperature then rises to at least +1°C, then the compressor starts up. (refer to item 3.5.7)
If you switch the compressor of using the 0 key (or the optional RS485 interface, then it switches
first into No Load mode. The remaining No Load cycle time is shown in the lower 7-segment
indicator.
The shutdown time is used as the time here (see item 3.2.6).
Only after this time has elapsed does the system switch off completely.
If the pressure exceeds the "P_allowed – 0.3 bar", then a warning is registered.
If the pressure exceeds the "P_allowed" threshold, then the compressor is switched off and a fault
message is displayed.
a) "no heating"
If the heating temperature falls below the threshold [min. compressor temperature], the
Supplementary Heating output is switched on.
As soon as the heating temperature rises above the threshold [minimum compression
temperature + 2°C], the output is switched off once more.
If the heating temperature falls below the threshold [minimum compression temperature],
then the Supplementary Heating output is switched on.
As soon as the heating temperature rises above the threshold [minimum compression
temperature + 2°C], the output is switched off again.
c) "heating"/compressor is ON
If the function “heating” is activated, and the signal “temp. restriction” (“DE 5”) is missing,
then warning [5] (“oil level / heating”) will be displayed.
In general, the compressor can only be started when the compressor temperature (or heating
temperature if operated “with heating”) has reached at least the threshold of +1°C.
If the supplementary heating output is switched on, then this is shown in the LCD using the
corresponding symbol.
0011 => Release: Release editing of recommended/limit settings which are called up via the
INFO key
0018 => Selection: BLCO mode (0/1) [1 => System is BLCO slave]
0041 => Call up: Editing the Air Filter servicing interval
0042 => Call up: Editing the Oil/Oil Filter servicing interval
0043 => Call up: Editing the Oil separator servicing interval
0044 => Call up: Editing the Motor Lubrication servicing interval
0045 => Call up: Editing the Compressor servicing interval
0060 => Call up: Select system, pressure range and quantity delivered (refer to: Item 3.2.16).
0062 => Call up: Only select the pressure range (e.g. following a software update)
0069 => Call up: Only enter quantity delivered (e.g. following a software update)
0075 => Call up: Set the parameters for selecting the frequency converter;
(see: Item 3.2.15)
0080 => Call up: Program option “with dryer” (see section 3.2.17)
0111 => Call-up: Start of “initial operation” for the compressor motor
( New in Version 1.30 / see: item 3.5 1 )
9950 => Call-up Set system address, interface mode, and baud speed [PC link]
9970 => Call-up Set the behavior when power is restored after a "Low Voltage" warning
--- ---
“random number” for generating
##### the “factory code” (new in V 1.30)
After switching the mains on, if an error in the programming memory (Flash EPROM) has been
detected, the following message then appears in the lower 7-segment indicator:
"FLASH" => In this case, the program must be reloaded into the control unit.
- Press the ▲ and 0 keys simultaneously and switch on the power supply again at the same
time
=> The relevant program (hexadecimal file) can now be transferred to the control unit.
* Slave address: 1
* Baud speed: 9600
* Parity: even
* Pause when sending: 10 ms
* RTS control: active