Sigma CP Main Man-1078
Sigma CP Main Man-1078
Sigma CP Main Man-1078
Sigma CP T series
Fire Control Panel
Operation and
Maintenance Manual
MODEL NUMBERS
K11020M2, K11040M2, K11080M2
Man-1078 T11020M2, T11040M2, T11080M2
Issue 10 Sept 2008
Index Page
1. Introduction .........................................................................................................................3
2. Safety and mounting .............................................................................................................3
3. Technical specification...........................................................................................................4
4. Using intrinsically safe barriers...............................................................................................8
5. Control panel fascia...............................................................................................................9
6. Connecting to the circuit board ............................................................................................ 11
7. Software revision number.................................................................................................... 11
8. Detection zone wiring.......................................................................................................... 12
9. Sounder circuit wiring.......................................................................................................... 13
10. Connection to remote control terminals .............................................................................. 13
11. Aux 24V DC supply............................................................................................................ 14
12. Connection to relay contacts .............................................................................................. 14
13. Connection to Repeater panels........................................................................................... 14
14. Connection to Ancillary boards ........................................................................................... 14
15. Connection to 8 way Sounder boards ................................................................................. 15
16. Panel operation................................................................................................................. 16
17. Configuration options ........................................................................................................ 17
18. Watchdog reset switch ...................................................................................................... 19
19. Processor reset switch ....................................................................................................... 20
20. Internal indications – troubleshooting................................................................................. 20
20.1 Mains fail ................................................................................................................................20
20.2 Batt fail...................................................................................................................................20
20.3 CPU fault ................................................................................................................................20
20.4 Aux 24V fault ..........................................................................................................................20
20.5 Batt low ..................................................................................................................................20
20.6 Earth fault...............................................................................................................................20
20.7 Sys fuse fault ..........................................................................................................................20
20.8 S1 fault and S2 fault ................................................................................................................20
20.9 Comms fault............................................................................................................................20
21. Power supply .................................................................................................................... 21
22. Maintenance ..................................................................................................................... 22
22. Zone designation label....................................................................................................... 22
24. Record of Configuration..................................................................................................... 23
Man-1078_Sigma_CP_10
Page 2 of 24
1. Introduction
The SIGMA CP range consists of a series of conventional fire alarm control panels designed in accordance
with European standards EN54-2 and EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating
Equipment.
The range consists of 2, 4 and 8 zone control panels. All control panels are available in two versions:
Sigma K11 range in which detectors and call points are wired on separate circuits to sounders (two sounder
circuits are provided).
Sigma T11 range in which detectors, call points and sounders are wired to the same pair of cables. This is
what is commonly referred to as a two-wire system.
Wiring sounders to the detection circuits eliminates the need to install sounder circuit cables and also offers
the ability to provide zoned or two stage sounder operation.
All control panels have an integral, mains powered battery charger and power supply designed in
accordance with the requirements of EN54-4.
In addition to the requirements of EN54-2 the control panel has the following facilities:
………….Test condition to allow the automatic resetting of zones in alarm for testing purposes. EN54-2
Section 10 option with requirements.
………….Delay of the actioning of fire alarm devices (sounders) so that an alarm may be verified before a
premises is evacuated. EN54-2 Section 7.11 option with requirements.
………….Fire alarm devices to enable an audible warning to be sounded throughout a premises upon the
detection of a fire condition or the operation of a manual call point. EN54-2 Section 7.8 option with
requirements.
In addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and
local fire which operate upon fire condition. These are to be used for local control and signalling.
2. Safety and mounting
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974
to ensure as reasonably as is practical that the article will be safe and without risk to health when properly
used.
An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’
relating to its use made available by the supplier.
This product should be installed, commissioned and maintained by trained service personnel in accordance
with the following:
(i) IEE regulations for electrical equipment in buildings
(ii) Codes of practice
(iii) Statutory requirements
(iv) Any instructions specifically advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are necessary to
ensure that you make any appropriate information about this product available to anyone concerned with its
use.
This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As
such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a
readily accessible double pole disconnect device meeting the requirements of EN60950/IEC950 which
disconnects live and neutral simultaneously shall be incorporated in the fixed wiring.
Switch disconnect devices such as MK Sentry 63A or similar are suitable for this.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded
to the protective earth will render the equipment unsafe.
This control panel is designed for indoor use only and at temperatures between -50C (+/- 3) and +400C (+/-
2) and with a maximum relative humidity of 95%.
The IP rating for the enclosure is IP30.
Man-1078_Sigma_CP_10
Page 3 of 24
Operation outside of these limits may render the equipment unsafe.
Mounting
The control panel should be mounted on a dry, flat surface, at eye height to the display and in a level
position such that the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all three mounting
positions.
It should be positioned in an accessible position as agreed with the end user.
Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not
liable to move once fixed.
The control panel should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable
entry points are required, all swarf and debris caused by drilling of additional cable entries must be cleared
before power is applied to the panel.
3. Technical specification
Table 1 - Electrical specifications
Mains supply 230V AC +10% - 15% (100 Watts maximum)
Mains supply fuse 1.6Amp (F1.6A L250V) Replace only with similar type
Power supply rating 3 Amps total including battery charge 28V +/ 2V
Maximum ripple current 200 millivolts
Battery type (Yuasa NP) Two 12 Volt sealed lead acid (7Ah maximum) See table 2 for capacities
Battery charge voltage 27.6VDC nominal (temperature compensated) See table 3
Battery charge current 0.7A maximum
Battery lead fuse 20mm, 3.15A glass Replace only with the same type
Maximum current draw from batteries 3 Amps With main power source disconnected
R0V output Fused at with electronic fuse
Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1.6 Amp total load over all circuits
Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1.6 Amp total load over all circuits
Fault relay contact rating 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded
Fire relay contact rating 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded
Local fire relay contact rating 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded
Zone quiescent current 1.6mA maximum See table 4 for detector types
Terminal capacity 0.5mm2 to 2.5mm2 solid or stranded wire
Number of detectors per zone > 20 Dependent on type
Number of sounders per circuit Dependent on type and current consumption See table 6 for sounder types
Detection circuit end of line 6K8 5% ½ Watt resistor Supplied in terminals
Sounder circuit end of line 10K 5% ¼ Watt resistor Supplied in terminals
No. of detection circuits (see table 2 for number of zones for each model) Dependent on model
No. of sounder outputs 2 (plus one per zone on T models)
SIL, AL, FLT, RST inputs Switched -ve, max resistance 100 Ohms
Zone normal threshold 8K ohm TO 1K ohm
Detector alarm threshold 999 ohms to 400 ohms
Call point alarm threshold 399 ohms to 100 ohms
Short circuit threshold 99 ohms to 0 ohms
Head removal condition 15.5 to 17.5 volts Zener clamp detector base to be used
Cabling FP200 or equivalent (maximum capacitance 1uF Metal cable glands must be used
maximum inductance 1 millihenry)
Man-1078_Sigma_CP_10
Page 4 of 24
20 27.36
30 27
40 26.4
Although the current consumption of many detection devices would allow more than 32 to be connected to a
zone, this number should be limited to 32 to ensure that a short or open circuit on the wiring does not
Man-1078_Sigma_CP_10
Page 5 of 24
prevent the indication of a fire alarm from more than 32 fire detectors and/or call points as required by
European standard EN54-2.
No more than 32 detectors and call points should be fitted to any one zone.
Man-1078_Sigma_CP_10
Page 6 of 24
Table 5 - Compatible detector bases and call points
Model Type Manufacturer Comments
YBN-R/4 STANDARD Hochiki
YBO-R/5 STANDARD WITH REMOTE LED Hochiki
YBN-R/4SK DIODE BASE Hochiki Must be used with LCMU
YBO-R/5SK DIODE BASE WITH REMOTE LED Hochiki Must be used with LCMU
YBO-R/5PA SAVWIRE Hochiki Only with T series panels
AUBDR100-470 470R RESISTOR + DIODE Argus Vega Must be used with LCMU
AUBSR100-470 470R RESISTOR Argus Vega
Note: LCMU (Line Continuity Monitoring Device) part number K1406 allows call points mounted
downline of detectors that have been removed from diode bases to continue to operate.
LCMU units are not compatible with 2 wire “T” series Sigma CP Panels.
Man-1078_Sigma_CP_10
Page 7 of 24
4. Using intrinsically safe barriers
SIGMA CP control panels support the use of I.S. barriers for connecting to equipment in hazardous areas.
Only certified detectors, call points and sounders may be used in hazardous areas and these
must be connected to the control panel via a compatible I.S. barrier as listed in table 7.
Connection of the I.S. barrier changes the characteristics of the detection circuit so zones that have I.S.
barriers connected must be adjusted to work with them.
Programmable options C61 to C68 allow each zone to operate with I.S. barriers.
The amount of detectors and call points that can be connected to a zone is limited by the I.S. approval
system diagram which should be supplied by the detector manufacturer. The power rating of the end of line
resistor will be dependent upon the Zone classification rating (Gas class) this will be specified on the system
diagram.
I.S. DETECTOR
6K8 END OF
LINE RESISTOR
-
IN
-
OUT
POWER RATING WILL
DEPEND UPON I.S. ZONE
CLASSIFICATION
Man-1078_Sigma_CP_10
Page 8 of 24
5. Control panel fascia
In addition to the mandatory controls and indications required by the EN54-2 standard, two, seven segment,
LED displays and MODE, SELECT and ENTER buttons are provided to allow easy entry and storage of codes
to configure the control panel to suit the requirements of the installation.
Man-1078_Sigma_CP_10
Page 9 of 24
It is most important that the polarity of the red and black wires is observed as wrong
connection of these will damage the control panel.
Man-1078_Sigma_CP_10
Page 10 of 24
6. Connecting to the circuit board
All connections for field wiring are to a single row of terminals along the top of the circuit board.
The connections for the power cables are to a pluggable terminal block which may be pulled off of the board
to remove the plate/PCB assembly. Remove this pluggable terminal only with mains power off.
Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the
panel.
The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be bonded
securely to the enclosure via a metal gland.
Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily
to the appropriate terminals leaving only enough wire to ensure that there is no strain on the PCB.
Terminals are capable of accepting wires of up to 2.5mm2.
Wiring must not go across the front of the circuit board plate or between the plate and the circuit board.
If cable entries need to be in positions other than at the knockouts provided, wiring must be fed behind and
well away from the surface of the circuit board.
The space at the bottom of the enclosure is largely occupied by the standby batteries so this must be borne
in mind when considering cable entries.
CORRECT
INCORRECT INCORRECT
X1 X2
C7 C6 C5 C4 C3 C2 C1 C23 C22 C21 C20 C127 C128 C35 C36 C33 C34 C60 C61 C106 C107
FB21 FB20
FB7
VDR2
FB10
FB8
FB1
VDR4
FB6
FB5
FB4
FB2
VDR3 VDR1
FB3
FB9
C102
C100
C108
C109
C101
C99
C98
F9
R99
C51 TR19
R51
R14 R18
TR23
R12
F4
F3
R60
F12
LED16
R117
R168
C94
R98
R6
F11
+
updated. The software revision can be located
D4
C76
R19
R166 R167
TR1
TR3
TR2
LED34
C75
LED12
D3 D2 D1 TR9 D11
R13 R7 R1
TR26
C105
R158
R53 R69
C30
R10D R11
R16C R17
R16B R15
R57
R4D R3
R10C R9
R4E R5
LED9
LED11 LED15
C104
R157
R80 R156
R81 C103
C31 R155
R10E
R10B
R10A
R16D
R10F
R22A
R16A
R4C
R4B
R4A
R56
R52
R55
R4F
C24
D30
D20
LED13
+
a number such as “Sig24.hex” and it is this
R116 C39 C38 C37 C40 C96
R89
J1 R129 TR24
D9 IC4
C45 C44
D10
LED14
R112 R67 R61
R113 R62 R64
R63
R104
R118
D15
TR28 R126
R128
R102
R137
C55
C83 C81
D41
REG3
IC6
R110
Jason C25
D23 VR1
C27 L1
R133 D22 C82 IC5
C42 R90
R78
R74
R73
R71
R72
C41 R135
R134
C56
T3 SW2 SW1
SW4
SERIAL NUMBER TH1
+ R75
D1008 ISSUE 06
R76
LED17 LED35 LED5 LED4 LED3 LED6 LED7
R70
Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the
monitoring circuit to work correctly.
On T series panels, polarised sounders must also be wired across the detection zone but in reverse polarity
to that shown by the zone terminals (see figure 5 below). At least one sounder should be fitted to each
detection zone. Each zone can be configured individually as a 2-wire type zone or a non 2-wire type zone
using configuration options C1 to C8.
For non 2-wire systems that are required to comply with BS5839 Part 1: 2002 detector removal
requirements, detector bases fitted with a Schottky diode should be used and the end of line resistor
replaced with an LCMU active end of line monitoring device.
DETECTOR
CALL POINT
+IN +
OUT
6K8 END OF
LINE RESISTOR
-
IN
-
OUT
DETECTOR POLARISED
SOUNDER
6K8 END OF
+ + LINE RESISTOR
-
IN
-
OUT
IN OUT
Man-1078_Sigma_CP_10
Page 12 of 24
9. Sounder circuit wiring
Whether using standard or T series control panels, all sounders must be of the polarised type. If non-
polarised sounders are used the control panel will permanently show a fault condition. See table 6 on page 7
for a list of compatible sounder types.
Sounder circuits are monitored for open and short circuit faults by placing a 10K end of line monitoring
resistor across the last device on the circuit.
Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the
monitoring circuit to work correctly.
A maximum of 1.6 Amps is available for powering sounders with a maximum load of 0.5 Amps on any one
circuit.
To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open
switch or contact and via a resistance of no greater than 100 ohms.
All of the remote control inputs are non-latching.
Man-1078_Sigma_CP_10
Page 13 of 24
11. Aux 24V DC supply
An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door
release controllers.
The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative
terminal and is the same terminal that should be used to switch the remote control terminals.
It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote, volt
free contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another
system for example to give an alert. See programming code 24 on page 17.
The supply is fitted with an electronic self resetting fuse to protect the control panel’s 24V supply in the
event of a wiring fault.
Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times
as standby time will be significantly affected by even modest standing loads. It is recommended that the
Aux24V output is not used to power standing loads and not used to supply loads of greater than 500
milliamps
Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is
imperative that a suppression diode is fitted across the coil of the electromechanical device to prevent the
generation of high voltage transients back to the control panels power supply.
The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards, a separate power supply
should be used for these.
Fault relay
The fault relay is normally energised and will de-energise upon any fault condition including total loss of power.
Fire relay
The fire relay will energise upon activation of a fire condition on any of the zones. The relay will remain
activated until the control panel is reset. This relay will NOT operate upon activation of the remote AL input.
Individual zones can be configured not to operate the Fire relay by setting configuration options E1 to E8.
Set the ancillary board address using the DIP switch (SW7); ensure no two ancillary boards share the same
address.
Apply power to main panel and all ancillary boards then briefly press the PROCESSOR RESET button on the
main panel, wait for a few seconds and the main panel will show the addresses of the ancillary boards that
were found on the display for instance o1 indicates that an ancillary board at address 1 has been found.
Press the ENTER button to accept each ancillary board that has been found.
The control panel will report a fault if any ancillary boards that have been accepted
become faulty or go off line.
For full details of commissioning procedures for ancillary boards see the Sigma CP Ancillary board Operation
and maintenance manual.
Please note that Ancillary boards can only be fitted to panels containing boards labelled S4XXA
or S4XXB. They will not work with panels containing boards without the A or B suffix.
15. Connection to 8 way Sounder boards
Sounder boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main
control panel PCB. Up to 7 Sounder boards may be connected and each board has terminals for the
incoming cables and outgoing cables. All except the last Ancillary board, Sounder board or Repeater
connected to the cable must have the jumper links J2 removed. Sounder boards must be powered from a
separate power supply which is suitably rated to supply the full sounder load that is connected. This can be
up to 4 Amps if all circuits are fully loaded.
Set the Sounder board address using the DIP switch (SW7); ensure no two Sounder boards share the same
address.
Apply power to main panel and all Sounder boards then briefly press the PROCESSOR RESET button on the
main panel, wait for a few seconds and the main panel will show the addresses of the sounder boards that
were found on the display for instance b1 indicates that a sounder board at address 1 has been found.
Press the ENTER button to accept each Sounder board that has been found.
The control panel will report a sounder fault if any Sounder boards that have been
accepted become faulty, have cable faults on their outputs or go off line.
For sounder boards to work option 25 must be set. This is set by default in the factory
on ‘T’ type panels only, this setting should be checked if sounder boards are not working.
For full details of commissioning procedures for Sounder boards see the Sigma CP Sounder board Operation
and maintenance manual.
Please note that Sounder boards can only be fitted to panels containing software
SIGMA242.HEX or later.
Man-1078_Sigma_CP_10
Page 15 of 24
16. Panel operation
16.4 Reset
To reset the panel, insert the Enable key then press the Reset button.
16.10 Disablements
It is possible to disable parts of the system. This may be required if there are works going on in a building
which may cause the fire alarm system to operate in error.
Man-1078_Sigma_CP_10
Page 16 of 24
16.10.3 Activate delays
To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears
on the seven segment LED display. When the enter button is pressed any zones that are set as delayed will
have their alarm outputs delayed by the time set in configuration options 00 to 09.
Man-1078_Sigma_CP_10
Page 17 of 24
Figure 9 – Example display showing option set and not set.
Table 8 – Configuration codes
CODE FUNCTION COMMENTS
00 SOUNDER DELAY TIME = 30 SECONDS Sets the time delay before sounders operate in combination with
01 SOUNDER DELAY TIME = 1 MINUTE configuration codes 31 to 48 and access level 2 function AD.
02 SOUNDER DELAY TIME = 2 MINUTES
03 SOUNDER DELAY TIME = 3 MINUTES
04 SOUNDER DELAY TIME = 4 MINUTES
05 SOUNDER DELAY TIME = 5 MINUTES
06 SOUNDER DELAY TIME = 6 MINUTES
07 SOUNDER DELAY TIME = 7 MINUTES
08 SOUNDER DELAY TIME = 8 MINUTES
09 SOUNDER DELAY TIME = 9 MINUTES
10 COMMON ALARM MODE (default) All sounders operate upon any fire condition
11 TWO-STAGE ALARM MODE Continuous sounders in activated zone, pulsing elsewhere
12 ZONED ALARM MODE Only sounders connected to zone in alarm operate
21* DISABLE FIRE BUZZER Buzzer will not operate on fire condition
22* DISABLE FAULT OUTPUT Fault relay will not operate except upon total power failure
23 DISABLE EARTH FAULT MONITORING Connection of fire alarm wiring will not announce a fault
24 PULSED REMOTE CONTROL OUTPUT Aux 24V supply pulses 1 sec on/1 sec off
25 ENABLE SOUNDERS ON DETECTION CIRCUITS Set as default if panel is two wire “T” series (detectors and call
points on same cables)
26 DISABLE FIRE OUTPUT Fire relay will not operate upon any alarm
27 REMOVE AUX 24 UPON PANEL RESET 24V supply switches off for about 5 seconds when panel is reset
31 ZONE 1 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options
32 ZONE 2 ALARM FROM DETECTOR DELAYED 0-9 when selected zone(s) triggered by detector only.
33 ZONE 3 ALARM FROM DETECTOR DELAYED Note access level 2 function Ad must be set for this to take
34 ZONE 4 ALARM FROM DETECTOR DELAYED effect.
35 ZONE 5 ALARM FROM DETECTOR DELAYED
36 ZONE 6 ALARM FROM DETECTOR DELAYED
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED
41 ZONE 1 ALARM FROM CALL POINT DELAYED Sounder outputs will be delayed by time set at options
42 ZONE 2 ALARM FROM CALL POINT DELAYED 0-9 when selected zone(s) triggered by call point only.
43 ZONE 3 ALARM FROM CALL POINT DELAYED Note access level 2 function Ad must be set for this to take
44 ZONE 4 ALARM FROM CALL POINT DELAYED effect.
45 ZONE 5 ALARM FROM CALL POINT DELAYED
46 ZONE 6 ALARM FROM CALL POINT DELAYED
47 ZONE 7 ALARM FROM CALL POINT DELAYED
48 ZONE 8 ALARM FROM CALL POINT DELAYED
61 CONFIGURE Z1 FOR I.S BARRIER Detection threshold changed for use with IS barrier
62 CONFIGURE Z2 FOR I.S BARRIER
63 CONFIGURE Z3 FOR I.S BARRIER
64 CONFIGURE Z4 FOR I.S BARRIER
65 CONFIGURE Z5 FOR I.S BARRIER
66 CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68 CONFIGURE Z8 FOR I.S BARRIER
71* ZONE 1 SHORT CIRCUIT INDICATES ALARM Changes the trigger threshold of the
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM zone so that the control panel can be
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM used on older systems that had no short
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM circuit monitoring.
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM
77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
Man-1078_Sigma_CP_10
Page 18 of 24
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM
CODE FUNCTION COMMENTS
81* ZONE 1 NON-LATCHING Renders the zone self-resetting so that
82* ZONE 2 NON-LATCHING it can be used to receive signals from
83* ZONE 3 NON-LATCHING other systems and will reset when the
84* ZONE 4 NON-LATCHING input is removed.
85* ZONE 5 NON-LATCHING Note: It can take up to 20 seconds for zone to reset itself when
86* ZONE 6 NON-LATCHING sounders are operating
87* ZONE 7 NON-LATCHING
88* ZONE 8 NON-LATCHING
91 ZONE 1 DOES NOT SOUND ALARMS Prevents the zone from operating the two common sounder
92 ZONE 2 DOES NOT SOUND ALARMS outputs.
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS
95 ZONE 5 DOES NOT SOUND ALARMS
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT SOUND ALARMS
99
A1* ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously
A2* ZONE 2 ANY ALARM DELAYED before an alarm is generated.
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED
A5* ZONE 5 ANY ALARM DELAYED
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED
C1 ZONE 1 SOUNDERS INHIBITED Enables individual zones to be configured not to operate zonal
C2 ZONE 2 SOUNDERS INHIBITED sounders.
C3 ZONE 3 SOUNDERS INHIBITED On 2 wire “T” series panels this enables individual zones to be
C4 ZONE 4 SOUNDERS INHIBITED configured for use with conventional (non 2-wire) detector
C5 ZONE 5 SOUNDERS INHIBITED bases.
C6 ZONE 6 SOUNDERS INHIBITED
C7 ZONE 7 SOUNDERS INHIBITED
C8 ZONE 8 SOUNDERS INHIBITED SOFTWARE VERSIONS SIGMA242.HEX and above only
E1* ZONE 1 WILL NOT OPERTATE FIRE RELAY Enables individual zones to be selected to not operate the fire
E2* ZONE 2 WILL NOT OPERTATE FIRE RELAY relay. This is sometimes combined with the non-latching
E3* ZONE 3 WILL NOT OPERTATE FIRE RELAY function to prevent ring around on interconnected panels.
E4* ZONE 4 WILL NOT OPERTATE FIRE RELAY
E5* ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6* ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7* ZONE 7 WILL NOT OPERTATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERTATE FIRE RELAY SOFTWARE VERSIONS SIGMA242.HEX and above only
NOTE: Setting the options marked with asterisks does not comply with EN54-2
Once the required configuration options have been set, the Write enable switch must be returned to its
normal position to the right. The General fault indicator will remain lit if the Write enable switch is not turned
off.
18. Watchdog reset switch
If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will
attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate
these events.
If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT LEDs on the front
panel, the CPU fault LED inside the panel.
This fault can only be cleared by pressing the WATCHDOG RESET button on the PCB inside the control
panel. The control panel buzzer can not be silenced and will continue to sound until the watchdog activation
is reset.
Man-1078_Sigma_CP_10
Page 19 of 24
19. Processor reset switch
Once started, the microprocessor controlling the panel should continue to run continuously without
interruption. If the microprocessor fails to run correctly it can be reset by pressing the PROCESSOR RESET
button on the PCB inside the control panel.
This should not normally be necessary but should be done as a matter of course if the system is behaving
abnormally. The system should resume normal operation within a couple of seconds of pressing the
processor reset button.
20. Internal indications – troubleshooting
To assist in identifying fault conditions which are not detailed on the front of the control panel, a number of
internal indicators are visible with the front cover removed as follows:
Man-1078_Sigma_CP_10
Page 20 of 24
21. Power supply
The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply which connects to the
fused terminal block labelled “230V”.
The fused terminal block contains a 20mm, F1.6A L250V fuse which should only be replaced with a similar
type.
The output voltage of the power supply is 28V DC +/- 2V and the total current rating including a maximum
0.7A for battery charging is 3 Amps. Fuse F12 mounted on the circuit board is a self-resetting electronic fuse
rated at 4 Amps.
The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at
least 50mm.
Mains wiring should include an earth conductor which is securely bonded to the building earth and should
enter the enclosure as close as possible to the mains terminal block. Mains wires should be kept very short
inside the enclosure and secured together close to the mains terminal block with a cable tie.
The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity (see
table 2 for battery size required for each model).
The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps.
Battery leads are supplied wired to the PCB along with a link to connect the two batteries in series. The PCB
is fitted with a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit which must only be replaced
with one of the same type.
It is most important that the polarity of the batteries is carefully observed when connecting.
Man-1078_Sigma_CP_10
Page 21 of 24
Figure 9 – Mains and battery connections
22. Maintenance
Sigma CP control panels do not require any specific maintenance but should the control panel become dirty
it can be wiped over with a damp cloth and should then be dried with a dry, lint free cloth. Detergents or
solvents should not be used to clean the panel and care must be taken that water does not enter the
enclosure.
The control panel contains sealed lead acid batteries to provide standby power in the event of a mains
failure.
These batteries have a life expectancy of around 4 years. It is recommended that these batteries be tested
in accordance with the battery manufacturer’s recommendations annually to determine their suitability for
continued standby applications.
Routine testing of the fire alarm system in accordance with BS5839: Part 1: 2002 will identify any
malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance
company immediately.
Should the control panel become faulty the complete electronic assembly can be replaced.
To do this, any configured options should be noted then both mains and battery power should be removed
before the work is started.
The field wiring should be carefully labelled and removed from the terminals.
The PCB can now be taken out of the panel by removing the 2 holding the plate in position.
Fitting the new PCB is the reverse of the procedure for removing the board.
Man-1078_Sigma_CP_10
Page 22 of 24
24. Record of Configuration
Use the table below to record the configuration codes that have been set on the control panel for future
reference. Place a tick in the grey band for any configuration options that are set.
It is recommended that a copy of this table is left with the control panel under the supervision of the person
responsible for the fire detection system.
31 ZONE 1 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options
32 ZONE 2 ALARM FROM DETECTOR DELAYED 0-9 when selected zone(s) triggered by detector only.
33 ZONE 3 ALARM FROM DETECTOR DELAYED Note access level 2 function Ad must be set for this to take
34 ZONE 4 ALARM FROM DETECTOR DELAYED effect.
35 ZONE 5 ALARM FROM DETECTOR DELAYED
36 ZONE 6 ALARM FROM DETECTOR DELAYED
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED
41 ZONE 1 ALARM FROM CALL POINT DELAYED Sounder outputs will be delayed by time set at options
42 ZONE 2 ALARM FROM CALL POINT DELAYED 0-9 when selected zone(s) triggered by call point only.
43 ZONE 3 ALARM FROM CALL POINT DELAYED Note access level 2 function Ad must be set for this to take
44 ZONE 4 ALARM FROM CALL POINT DELAYED effect.
45 ZONE 5 ALARM FROM CALL POINT DELAYED
46 ZONE 6 ALARM FROM CALL POINT DELAYED
47 ZONE 7 ALARM FROM CALL POINT DELAYED
48 ZONE 8 ALARM FROM CALL POINT DELAYED
51 COINCIDENCE ZONE 1 Zone contributes to ancillary board coincidence O/P. Any number
52 COINCIDENCE ZONE 2 of zones can be selected to contribute.
53 COINCIDENCE ZONE 3
54 COINCIDENCE ZONE 4
55 COINCIDENCE ZONE 5
56 COINCIDENCE ZONE 6
57 COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8
61 CONFIGURE Z1 FOR I.S BARRIER Detection threshold changed for use with IS barrier
62 CONFIGURE Z2 FOR I.S BARRIER
63 CONFIGURE Z3 FOR I.S BARRIER
64 CONFIGURE Z4 FOR I.S BARRIER
65 CONFIGURE Z5 FOR I.S BARRIER
66 CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68 CONFIGURE Z8 FOR I.S BARRIER
71* ZONE 1 SHORT CIRCUIT INDICATES ALARM Changes the trigger threshold of the
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM zone so that the control panel can be
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM used on older systems that had no short
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM circuit monitoring.
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM
77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
Man-1078_Sigma_CP_10
Page 23 of 24
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM
CODE FUNCTION COMMENTS SET
81* ZONE 1 NON-LATCHING Renders the zone self-resetting so that
82* ZONE 2 NON-LATCHING it can be used to receive signals from
83* ZONE 3 NON-LATCHING other systems and will reset when the
84* ZONE 4 NON-LATCHING input is removed.
85* ZONE 5 NON-LATCHING Note: It can take up to 20 seconds for zone to reset itself when
86* ZONE 6 NON-LATCHING sounders are operating
87* ZONE 7 NON-LATCHING
88* ZONE 8 NON-LATCHING
91 ZONE 1 DOES NOT SOUND ALARMS Prevents the zone from operating the two common sounder
92 ZONE 2 DOES NOT SOUND ALARMS outputs
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS
95 ZONE 5 DOES NOT SOUND ALARMS
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT SOUND ALARMS
99
A1* ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously
A2* ZONE 2 ANY ALARM DELAYED before an alarm is generated.
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED
A5* ZONE 5 ANY ALARM DELAYED
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED
C1 ZONE 1 SOUNDERS INHIBITED Enables individual zones to be configured not to operate zonal
C2 ZONE 2 SOUNDERS INHIBITED sounders.
C3 ZONE 3 SOUNDERS INHIBITED On 2 wire “T” series panels this enables individual zones to be
C4 ZONE 4 SOUNDERS INHIBITED configured for use with conventional (non-savwire) detector
C5 ZONE 5 SOUNDERS INHIBITED bases.
C6 ZONE 6 SOUNDERS INHIBITED
C7 ZONE 7 SOUNDERS INHIBITED
C8 ZONE 8 SOUNDERS INHIBITED SOFTWARE VERSIONS SIGMA242.HEX hex and above only
E1* ZONE 1 WILL NOT OPERTATE FIRE RELAY Enables individual zones to be selected to not operate the fire
E2* ZONE 2 WILL NOT OPERTATE FIRE RELAY relay. This is sometimes combined with the non-latching function
E3* ZONE 3 WILL NOT OPERTATE FIRE RELAY to prevent ring around on interconnected panels.
E4* ZONE 4 WILL NOT OPERTATE FIRE RELAY
E5* ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6* ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7* ZONE 7 WILL NOT OPERTATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERTATE FIRE RELAY SOFTWARE VERSIONS SIGMA242.HEX hex and above only
NOTE: Setting the options marked with asterisks does not comply with EN54-2
Man-1078_Sigma_CP_10
Page 24 of 24