BFT Libra C Ma
BFT Libra C Ma
BFT Libra C Ma
05 02-07-07
I QUADRO COMANDO
GB CONTROL PANEL
F CENTRALE DE COMMANDE
8 027908 288554
D SELBSTÜBERWACHENDE STEUERUNG
E CUADRO DE MANDOS
P QUADRO DE COMANDO
LIBRA-C-MA
12 - LIBRA-C-MA - Ver. 05
D811494_05
LIBRA-C-MA - Ver. 05 - 13
D811494_05
ENGLISH INSTALLATION MANUAL
If this setting is not activated (OFF), it inhibits the photocell checking - Read (read)
function, allowing connection of devices not provided with additional Checks one key of a receiver; if stored it displays a message showing
checking contact. the receiver number in the memory location (from 01 to 64), and the key
- Gate-open or 2nd radio channel warning light (SCA 2ch) [ OFF ] number (T1, T2, T3 or T4).
ON: The output between terminals 21 and 22 is configured as Gate-open - Eliminate list (erease 64)
warning light, in this case the 2nd radio channel controls pedestrian WARNING! Completely removes all memorised radio control devices
opening. from the receiver memory.
OFF:The output between terminals 21 and 22 is configured as 2nd radio - Receiver code reading (RX code)
channel. This displays the code entered in the receiver (par. 11).
- Motors in operation (1 mot ON) [ OFF ] Consult paragraphs 8, 9, 10 and 11 for further information concerning
ON: Only motor 2 is in operation (terminals 3, 4 and 5). the advanced functions of the Clonix incorporated receiver.
With this configuration, the pedestrian input is disabled.
OFF:Both motors are in operation. 6.4) LANGUAGE MENU (language)
- Lock hold (block persist) [ OFF ] (Fig. 5) Allows you to set the language on the display programmer.
ON: To be used when the mechanical closing backstop is fitted. - ITALIAN (ITA)
This function activates leaf pressure on the mechanical backstop, without - FRENCH (FRA)
this being considered as an obstacle by the Ampere-stop sensor. - GERMAN (DEU)
Therefore the rod continues its travel for another 0.5 sec. after detecting - ENGLISH (ENG)
the closing limit switch or upon reaching the mechanical backstop. So - SPANISH (ESP)
by activating the closing limit switches slightly earlier, the leaves will
come to a perfect halt against the backstop. (Fig. 5a) 6.5) DEFAULT MENU (default)
OFF:To be used when no mechanical closing backstop is fitted. Restores the preset default values on the control unit. After restoring, a new
Movement is exclusively halted by activation of the closing limit switches; autoset operation must be carried out.
in this case proceed to carrying out precise setting of the closing limit-
switch activation. (Fig. 5b) 6.6) DIAGNOSTICS AND MONITORING
- Hold-to-run control (hold-to-run) [ OFF ] The display on the LIBRA-C-MA panel shows some useful information, both
ON: Hold-to-run operation: the manoeuvre continues as long as the control during normal operation and in the case of malfunctions.
key is kept pressed. Diagnostics:
WARNING!: Enabling the Hold-to-run logic entails a different use of the In the case of malfunctions, the display shows a message indicating which
START and PEDESTRIAN buttons: device needs to be checked:
START takes on the hold-to-run OPEN function STRT = START input activation
PEDESTRIAN takes on the hold-to-run CLOSE function STOP = STOP input activation
OFF:Impulse operation, according to the 3 or 4 step logic. PHOT = PHOT input activation
- Fixed code (fixed code) [ OFF ] FLT = FAULT input activation for checked photocells
(Advanced logics ⇒ address 13) TH = Activation of software thermal protection
ON: The receiver is configured for operation in fixed-code mode, see para- ER 1 = Board error during safety device check
graph on “Radio Transmitter Cloning”. ER 2 = Board error during safety device check
OFF:The receiver is configured for operation in rolling-code mode, see When using traditional limit switches connected to terminals 24-25-26-27:
paragraph on “Radio Transmitter Cloning”. SWO1 = activation of Motor 1 opening limit switch input
- Radio transmitter programming (radio prog) [ ON ] SWC1 = activation of Motor 1 closing limit switch input
(Advanced logics ⇒ address 15) SWO2 = activation of Motor 2 opening limit switch input
ON: This enables transmitter storage via radio: SWC2 = activation of Motor 2 closing limit switch input
1 – First press the hidden key (P1) and then the normal key (T1, T2, T3 In the case where an obstacle is found, the LIBRA-C-MA panel stops the
or T4) of a transmitter already memorised in standard mode by means door and activates a reverse manoeuvre; at the same time the display shows
of the radio menu. the “AMP” message.
2 – Within 10s press the hidden key (P1) and the normal key (T1, T2,
T3 or T4) of a transmitter to be memorised. Monitoring:
The receiver exits the programming mode after 10s, other new transmit- During the opening and closing phases, the display shows four digits sepa-
ters can be entered before the end of this time. rated by a dot, for example 35.40. The digits are constantly updated during
This mode does not require access to the control panel. the manoeuvre, and represent the maximum torque reached by motor 1
OFF:This disables transmitter storage via radio. (35) and motor 2 (40).
The transmitters can only be memorised using the appropriate Radio These values allow the torque setting to be corrected.
menu. If the maximum torque value reached during the manoeuvre gets sensibly
- Master/Slave (Master) [ OFF ] close to the value set in the parameter menu, malfunctions may occur in the
ON: The control panel is set as Master in a centralised connection (see future following wear or slight door deformation.
Paragraph 7). It is therefore advisable to check the maximum torque reached during some
OFF:The control panel is set as Slave in a centralised connection (see of the manoeuvres carried out in the course of installation, and if necessary
Paragraph 7). set a value about 15-20 percent points higher in the parameter menu.
- Start-Open selection (start - open) [ OFF ]
ON: The input between the two terminals 15-16 acts as open. For closing, 6.7) ADJUSTING PROCEDURE
wait until the TCA, which has to be previously enabled, has elapsed. - Before switching on, check electrical connections.
OFF:The input between the two terminals 15-16 acts as start. - Set the following parameters: Automatic Closing Time, Opening and closing
- Prealarm (pre-alarm) [ OFF ] delay times, Slow-down speed and Zone number.
ON: The blinker comes on 3 sec. before the motors start. - Set all the logics.
OFF:The blinker comes on at the same time as the motors start. - Carry out the autoset procedure.
- Automatic fast time (auto fast time) [ ON ] After completing the autoset procedure, the Motor fast time and the Torque
ON: The control unit automatically calculates slow-down time and offsets fast can be manually adjusted.
time to keep slow-down time constant. With this function active, the fast WARNING! Any incorrect setting can cause injuries to persons and
time value is continually updated (it is therefore possible to find a setting animals or damage to things.
other than the one actually carried out). WARNING: Check that the impact force value measured at
OFF:The control unit does not offset fast time, but applies the preset «fast time» the points established by the EN 12445 standard is lower than that
parameter, independently of any environmental changes. specified in the EN 12453 standard.
To obtain a better result, it is advisable to carry out the autoset procedure
6.3) RADIO MENU (RADIO) and the fast time setting with the motors at rest (i.e. not overheated by a
- Add considerable number of consecutive manoeuvres).
Allows you to add one key of a radio control device to the receiver memory;
after storage it displays a message showing the receiver number in the 6.8) AUTOSET MENU (autoset)
memory location (from 01 to 64). Allows you to automatically set the Motor torque.
Add Start button (add start) WARNING! The autosetting operation is carried out from closing end-of-
associates the required key to Start command stroke devices. If Autoset is commanded in a different position an error
Add 2ch button (add 2ch) message indicating “nsvc” will be displayed and the required manoeuvre
associates the required key to 2nd radio channel will not take place.
14 - LIBRA-C-MA - Ver. 05
D811494_05
LIBRA-C-MA - Ver. 05 - 15
D811494_05
16 - LIBRA-C-MA - Ver. 05
D811494_05
LIBRA-C-MA - Ver. 05 - 17
D811494_05
Fig. 1 Fig. 2
10 F1A25T
194 0
29 30
236
SD 1 2 3 4 5 6 7 8 9 10 1112131415 1617181920 21 22 23 24 25 26 27 28
F 1AT (230V)
F 2AT (110V)
OK
Fig. 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
FC M2*
FC M1*
COM
START
PED
STOP
PHOT
FAULT
COM FC
FCA M2
FCC M2
FCA M1
FCC M1
ANT
SHIELD
25W max.
+
L N M2 M1
NO
NO
NO
NC
NC
230V ~
ANT.
24V ~ 24V ~
* Controllo finecorsa negli attuatori con VSafe
gestione finecorsa con 1 solo filo
(PHOBOS BT, IGEA BT).
24V ~
COM
PHOT
FAULT
24V ~
COM
PHOT
FAULT
24V ~VSafe
24V ~VSafe
IGEA BT).
1 2 1 2 1 2
*C o n t r o l o d o f i m - d e - c u r s o n o s Tx 1 Tx 1 Tx 2
42 - LIBRA-C-MA - Ver. 05
D811494_05
Fig. 3a
COM
24V ~
24V ~VSafe
24V ~
FAULT
FAULT
PHOT
PHOT
24V ~VSafe
COM
24V ~VSafe
24V ~
24V ~VSafe
24V ~
18 5 18 5 4-SCS1-MA 5
15 4 2 14 15 4 2 14 5-SCS1-MA 4 2 14
3 1 13 3 1 13 3-SCS1-MA 3 1 13
12 2 12 2 12 2
15 5
11 1 11 1 11 1
Rx 1 Tx 1 19 4 2 14 Rx 1 Tx 1 Rx 3 Tx 3
3-SCS1-MA 3 1 13
12 2
1-SCS1-MA 5 11 1 1-SCS1-MA 5 15 5
2-SCS1-MA 4 Rx 3 Tx 3 2-SCS1-MA 4 19 4 2 14
3 2 14 3 2 14 6-SCS1-MA 3 1 13
12 2 1 13 12 2 1 13 12 2
11 1 11 1 11 1
Rx 2 Tx 2 Rx 2 Tx 2 Rx 4 Tx 4
Fig. 4
UNIPOWER
Contatti
Contacts
UNIFLAT Contacts
Kontakte
Contactos
Contatos
UNIFLAT
Contatti
Contacts
Contacts UNITRC UNIFLAT
Kontakte
Contactos
Contatos
UNIMITTO UNITRC P1
Contatti
Contacts T1 P1
T1 2
Contacts T2 T 3
Kontakte Led T 4
T
Contactos
Contatos
P1 P1
P1
UNIMITTO UNITRC
2 2
1
1
Contatti
Contacts
Contacts
Kontakte
P1 Contactos
Contatos
3 4 3 4
LIBRA-C-MA - Ver. 05 - 43
Fig. 5
0,5s
A
B
Fig. 6
LIBRA-C-MA
SCS1
SBS
230V
(*)
33
33
44 25V
55 33 (*) 110V
LIBRA-C-MA
o
11 12 13 14 15 16 17 18 19 20
elh m
12V, 1.2 AH
Ver
COM
START
PED
STOP
PHOT
FAULT
e-Rot-Rojo
--
Roug
++
ed-
+ - + -
o-R
NO
NO
NO
NC
NC
6 12V, 1.2 AH
SBS 55
ss
5 Ro
4 44
JP1 3 33
--
24V= 24V= 2
1 ++
VSafe
MASTER
SCS1 SCS1 SCS1
RX1
RX2
RX1
RX2
RX1
RX2
TX1
TX2
TX1
TX2
TX1
TX2
Max. 250m