Limit Value Switch Type TR 210: For 2 Temperature-Sensors or 0/4-20 Ma, 0-10 V, 2 Limits, Analog Output

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Pt 100-temperature relays type TR

Limit Value Switch type TR 210


for 2 temperature-sensors or 0/4-20 mA, 0-10 V, 2 limits, analog output
TR 210 The limit value switch TR 210 Application:
monitors up to 2 measuring inputs The TR 210 is very versatile and can thus be used in
for Pt 100 (RTD), Pt 1000, many applications. Nevertheless multiple preset
thermocouples, or standard- programs allow an easy setting.
signals 0/4-20 mA, 0-10 V. It can be used as a limit switch or as a controller for 2
The signals are monitored for up limits (with day/night shift up to 4 limits).
to 4 limits. The value of one or of As a measuring transducer it can convert signals from
both inputs can be read out at an the temperature-sensors to standard-signals or change
analog output. the scaling of standard-signals. The user can also
select, if minimum or maximum of 2 signals or the
difference of 2 signals is connected to the analog
output.
For more applications see basic programs.

• Measuring and monitoring Switching-Functions:


Function range -270...+1820 °C • 2 relays (co-contacts)
• resolution 0,1 °C (to 999.9 °C) • 2-4 limits
• Analog output (scaleable) for • Warmest/coldest sensor switches relay
1 input, min./max. of 2 inputs • Programmable for every relay:
or difference of 2 sensors - hysteresis (+ or - = MIN- or MAX-function)
(no isolation between inputs -199.9...999.9 s
and output) - autoreset or electronic reclosing lock
• 2 relay outputs - elay-time for switching and switching back
• Shifting of day/night 0...9999 s
(selectable with contact at • - operating- or closed current-mode
terminals Y1/Y2 ) • - cyclic check of function
• Universal power supply AC/ Monitoring of difference in temperature
DC 24-240 V Preset basic programs
• Easy setting with 3 buttons
and preset programs Order-number: T 224071
• Storing of min- and max- Us
values of inputs DC + –
• Code-lock against AC ~ ~
manipulation of settings

1185 1200
A1 A2 12 11 14 22 21 24
• Terminals pluggable ~ Us ~ Dif
+ – K1 K2
AC/DC 24...240 V

2 Measuring-Inputs: °C
Er 1= 0 Ω
• Resistance-sensors Pt 100 Grenzwert- Er 2= ∞
(RTD), Pt 1000, KTY 83/84 in Relais Er 3= >25 mA

2- or 3-wire-connection TR 210
_ t hermocouple
• Thermocouples types B, E, J, Pt 100
Set /
Pt 1000 _ +
K, L, N, R, S or T KTY 83
KTY 84 _
0 /4...2 0 mA 2s Reset
+
• different sensors at both Sensor 1 0...1 0 V Sensor 2
Reset
Out
inputs possible
1T1 1T2 1T3 2T1 2T2 2T3 Y1 Y2 U I
• Standard-signals 0/4-20 mA,
0-10 V (scaleable)
0/4...20 mA
0...10 V

ϑ ϑ Reset
V A
Displays: + KTY - + KTY -
• 4-digit for measuring value
• 2 LEDs for state of relays thermocouple
• 3 LEDs sensor/difference
0/4...20 mA
• 2 LEDs day/night
0...10 V

1.3.5
ZIEHL industrie-elektronik GmbH+Co KG, Daimlerstr. 13, D-74523 Schwäb.Hall, Tel.: +49 791504-0, www.ziehl.com
Pt 100-temperature relays type TR

Basic Programs Program 1: Program 6:


1 Temperature-sensor, 1 Standard-Signal 0/4-20 mA or 0-10 V, 2 Limits
2 Limits Display can be scaled, e.g. measuring input 4-20 mA =
Application: Monitoring of a display 0...1200 l/h.
temperature for 2 limits, e.g. over- Application: Monitoring of signals from a measuring
temperature with warning and transducer for 2 limits, e.g. over- or under- exceeding of
switchjing off or monitoring of a limits with pre-alarm and alarm or monitoring of a
temperature-range (min/max). signal-range (min/max) and/or as measuring-
transducer.
Program 2: In combination with any measuring-transducers, signals
2 Temperature-Sensors, like pressure, volume-flow, pH-value, ... can be
1 Limit for each Sensor monitored.
Application: Monitoring of 2
temperatures for 1 limit each, e.g. Program 7:
over.temperature or as double 2 Standard-Signals 0/4-20 mA or 0-10 V,
electronic controller. 1 Limit each
Display can be scaled, e.g. measuring input 4-20 mA =
Program 3: display 0...1200 l/h.
1 Temperature-Sensor, Application: Monitoring of signals from 2 measuring
2 Limits each day/night transducers, each for 1 limit, e.g. over- or under-
Application: Controlling of a exceeding of a limit as double electronic controller.
temperature with first limit, diffe-
rent for day and night. Program 8:
Monitoring of the same 2 Standard-Signals 0/4-20 mA or 0-10 V for
temperature with second limit, dif- monitoring of differences of signals
ferent for day and night. Application: Regulation or monitoring of the difference
of 2 analog signals for 2 limits, e.g. levels of liquids.
Program 4:
2 Temperature-Sensors, Program 9:
each 1 Limit for day/night 2 Temperature-Sensors, 2 shared Limits
Application: Monitoring or Application: Coldest (MIN) or warmest (MAX) sensor
controlling of 2 temperatures for switches relay. Monitoring of 2 bearings for pre-alarm
2 limits, depending on operation and alarm.
mode, e.g. controlling of 2
circulation pumps (day/night) or Application as Measuring-Transducer:
of processes (active/stand-by). At programs with 1measuring-input the output can be
scaled for this input, e.g. 0...200.0 = 4-20 mA.
Program 5: At programs with 2 measuring-inputs the output can
2 Temperature-Sensores for be scaled for 1 input or min- or max- value of both
monitoring of differences in inputs.
temperature, 2 Limits At programs for measuring of differences output can
Application: Regulation or be scaled for 1 signal or for the difference input 2 minus
monitoring of the difference of 2 input or for min- or max- value of both inputs.
measuring-points for 2 limits, e.g. Thus the TR 210 can be used as limit value switch and/
circulation pumps in solar or measuring-transducer simultaneously. The measured
systems. values ca be forwarded to e.g. a remote display or a
superior control.

Rated supply voltageUs AC/DC 24-240V, <3W, <5VA


Technical Data (AC 20-264 V, DC 20,4-297 V)
2 Measuring inputs Pt 100, Pt 1000 according to EN 60 751
Thermocouples types B, E, J, K, L, N, R, S,
according to EN 60 584, DIN 43 710
0/4-20 mA (22Ω), 0-10 V (13 kΩ)
Measuring-time <2,5 s to 5 s, depending on speed of change of signal
Analog output 0/4-20 mA, max. 500 Ω. 0-10 V, max. 10 mA
(without isolation to inputs)

Relay output type 3, see "general technical informations"


2 x 1 co- (change-over) contact

Test conditions see "general technical informations"


Rated ambient temperature -20…+60°C
renge

Dimensions h x w x d design V4: 90 x 70 x 58 [mm], mounting height 55 mm


Protection housing / terminals IP 30 / IP 20 (terminals pluggable)
Weight app. 200 g
Attachment on 35 mm DIN-rail or with screws M 4
1.3.6
ZIEHL industrie-elektronik GmbH+Co KG, Daimlerstr. 13, D-74523 Schwäb.Hall, Tel.: +49 791504-0, www.ziehl.com