Micra 100-Installers Handbook
Micra 100-Installers Handbook
Micra 100-Installers Handbook
Installer’s Handbook
LM 80024 • Issue 3
WWW.UKPANELS.COM
Introduction 3
1. Indicators 4
5. Design Limitations 19
6. Installation 21
7. Interfacing 25
8. Event Log 30
9. Commissioning 32
10. Maintenance 33
11. Troubleshooting 36
Page 2
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
Introduction Stratos-Micra 100® is a highly sophisticated ‘next generation‘ of High Sensitivity
Aspirating Smoke Detection product that has been designed to ensure that installation
and commissioning is as simple as possible, while optimising performance.
Stratos-Micra 100 incorporates a patented ‘artificial intelligence‘ known as ClassiFire®,
which allows the detector to configure itself to optimum sensitivity, alarm thresholds
and minimum nuisance alarms for any environment.
ClassiFire intelligence also monitors the detector chamber and dust separator for
contamination, continually adjusting the appropriate operating parameters to
counteract the negative effects of such contamination.
The Stratos range of detectors is unique in being able to provide a consistent level of
protection in a very wide range of environments by continuously making minor
adjustments to sensitivity.
The Stratos range of detectors has proven its worth many times by detecting ‘difficult-
to-detect‘ slow growth electrical overload incipient fires in ‘difficult‘ environments.
This handbook gives information likely to be needed for most installations, but for more
detailed information on subjects such as Fresh Air Referencing, please refer to the
complete Technical Manual or System Design Guide.
This equipment is Class 111 as defined in EN60950 (i.e., this equipment is designed to
operate from Safety Extra Low Voltages and does not generate any hazardous
voltages).
This symbol appears on the main board of the unit and indicates that the board
contains static sensitive components. Suitable anti-static precautions must be taken
when handling the board.
This label is located on the laser chamber and signifies that the unit is a Class 1 Laser
LASER CLASS 1 product as specified in IEC 60825-1. The unit incorporates a Class 3B embedded laser
PRODUCT which must not be removed from the detector as retinal damage may result if the laser
beam enters the eye.
This symbol indicates the Safety Earth stud (see section 6.2). This is for grounding cable
screens and should not be connected to 0V or signal earth.
AirSense Technology has taken every care to ensure that Stratos-Micra 100 is as simple to
install as possible but in case of difficulty, please contact our Help Line to ensure trouble free
installation and operation.
HELP LINE AirSense Technology takes no responsibility for damage or injury occasioned as a result of
(+44) (0) 1462 440666 failing to install or operate the equipment in accordance with these instructions.
Page 3
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
1. Indicators
1 Fire indicator illuminates when the alarm level has been reached and the
appropriate time delays have expired.
2 Fault. Illuminates when the unit has a fault and a fault signal is being sent
to the fire alarm panel.
3 OK. Illuminates to show normal operation when there are no faults. The OK
lamp will flash during the 15 minute Fastlearn™ period when the detector
is first learning about its environment.
Page 4
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 31
2. Inside the
Detector
Page 5
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
2.2 Detector
terminal block
connections
3 4 5 6
Page 6
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
3 Programming The Stratos-Micra 100 may be programmed from a PC when connected to the detec-
the Detector tor via a standard 9-pin serial lead connected to the serial port of the computer and
the 9 way socket at the base of the detector (see section 7.4, ‘Connecting to a PC’).
In order to do this, it is necessary to install the remote control software onto the com-
puter. A copy of the remote control software is contained on a floppy disk supplied
with each detector. Install the software in accordance with the on-screen instructions.
To open the software, select “Start Ô Programs Ô AirSense Ô Remote 2.0” “Access
the drop-down list to the right hand side of the toolbar. This defaults to “Detector
001”. Scroll down this list to select the detector number corresponding to the con-
nected detector’s address number if the address is other then the factory default set-
ting of 1 (see section 7.1).”
The programmable functions are all accessed though the “Options Ô Detector set-
tings” submenu or by clicking on the detector symbol in the remote software toolbar
as indicated below.
“The software will display a prompt for the detector’s access code (see section 3.31).
The default access code is 0102. When the correct code is entered, the programmable
functions may be accessed and amended as required. “
This window contains all the programmable functions for the Stratos-Micra 100.
To amend one of the programmable functions, go to the relevant tab in the “Function
settings” window, make the change and then click “OK”. This will save the change to
the detector’s internal firmware.
A list and explanation of the various functions is given overleaf, with the functions
grouped by the tab under which they appear.
Page 7
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
3.1 Time and date – Time and Date tab
It is important that the time and date be set up correctly on the controller’s internal cal-
endar/clock because it uses this information to store events in the event log. See sec-
tion 8, “Event log” for more details. Unless specially ordered, units are supplied with
the correct setting for UK time. This is backed up with a rechargeable battery. Later
adjustments to the clock setting should not exceed ± 70 minutes unless a FastLearn is
initiated
3.2 Alarm levels - Alarm levels and delays tab, Level subgroup
The value set in the Fire, Pre-Alarm and Aux functions in the Level subgroup is
the relatively scaled bargraph level at which the appropriate alarm is initiated on the
detector. The Fire 2 level assigns an absolutely scaled alarm level in % obs/m.
The Aux level is set by factory default at level 10 which means that this alarm will occur
after the Fire alarm. The default level settings for Pre-Alarm and Fire 1 are 6 and 8
respectively. The default setting for Fire 2 is 20% obs/m.
3.3 Alarm delays - Alarm levels and delays tab, Delay subgroup
The alarm delay is the number of seconds that an alarm level has to be continuously
sensed before the alarm is initiated. Each alarm level has a programmable delay of
between 0 and 90 seconds. The default delay for each alarm level is 5 seconds.
This function has no current use on the Stratos-Micra 100 but is reserved for future expan-
sion purposes.
The detector sensitivity is set with this entry, which will also affect the probability of nui-
sance alarms. 0 = high sensitivity, higher probability, 8 = low sensitivity, lower proba-
bility. The default alarm factor is 4.
Note: The highest sensitivity setting is suitable for clean, environmentally controlled envi-
ronments, e.g. semiconductor manufacturing clean rooms where airborne pollutants are
kept to an absolute minimum and the least contamination is cause for alarm.
Use of this setting in a busy machine shop would lead to relatively frequent nuisance alarms
due to the normal variation of atmospheric contamination and a lower sensitivity setting is
recommended. It is therefore important that the alarm factor chosen is suitable for the
area to be protected. When the appropriate alarm factor for the protected area has been
set, nuisance alarms will be reduced to an absolute minimum.
Page 8
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
The following table gives suggested settings of ClassiFire alarm setting for different locations
Alarm Probability of
Sensitivity Suggested Protected Area
Factor Nuisance Alarm
0 Extremely High Once per year Semiconductor manufacturing clean room
1 Once per 5 years Computer room
2 Once per 10 years Non-smoking office
3 Once per 50 years Clean factory
4 Medium Once per 1000 years Warehouse
5 Medium Once per 5,000 years Warehouse with diesel trucks operating
6 Medium Once per 10,000 years Warehouse with diesel trucks operating
7 Low Once per 20,000 years Warehouse with diesel trucks operating
8 Low Once per 100,000 years Warehouse with diesel trucks operating
When this function is ticked, Laser Dust Discrimination (LDD™) increases the response
time of the detector slightly, whilst greatly reducing the likelihood of nuisance alarms
due to dust ingress. LDD may be disabled in very clean rooms for a slightly faster
response to smoke by setting this function to unticking the box. This function is
enabled by default. NB: Disabling LDD is not recommended for areas other than man-
ufacturing clean rooms, due to the increased probability of nuisance alarms in most
other operating environments.
If the detector is in FastLearn mode, unticking this box will stop the FastLearn process.
Using the function in this way is neither recommended nor supported by AirSense
Technology Ltd.
Ticking the box will start a FastLearn at any time. The green “OK” LED on the front of
the detector will flash for the fifteen minutes that it takes for the FastLearn process, and
will then change to constant illumination to indicate that the FastLearn is complete.
Note: It will take a further 24 hours after the FastLearn for full sensitivity to be reached,
unless Demonstration Mode has been initiated (See section 3.10, “Demo mode”). It is
essential for proper functioning that the detector not be left in Demonstration mode, and
that it be allowed to complete the 24-hour learning period. To cancel demo mode, tick this
box or power down and restart the detector to initiate FastLearn mode.
When enabled, this function ensures that if the detector is powered off for any reason
(e.g. for maintenance or to be moved to a new area), a FastLearn is commenced auto-
matically on power-up. There may be occasions when it is desirable to power down the
detector for short periods of time, and it is highly likely that ambient contaminant lev-
els will be the same on power-up. Under these circumstances it may not be desirable
that the detector should to go through the whole learning process again. To this end,
this function can be unticked before power-down, whereupon it will return to the orig-
inal settings on power-up. This function is enabled by default.
Page 9
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
3.9 ClassiFire 3D - Alarm levels and delays tab
If this function is ticked, then the detector will ignore any pre-set time delays in the
event of an unacceptably rapid increase in smoke density, thereby minimising response
time to 'rapid growth' fires. This function would normally only be used where there
were long time delays programmed on the alarm levels. This function is disabled by
default.
Demonstration mode is an operating mode whereby the normal 24-hour learning peri-
od is bypassed, so that the detector can reach high sensitivity after only the 15 minute
FastLearn period. This can be used so that initial smoke testing and other commission-
ing can be carried out.
However, it must be understood that, since the alarm levels will be based solely
upon the sparse data gathered during the FastLearn period, there is a risk of nui-
sance alarms due to normal variations in ambient smoke levels. For this reason, the
detector should not be left in Demo mode for normal use when connected to a fire
panel.
These values are the times to the nearest hour at which the day/night switching is
desired to take place on the detector. Entries are made in 24-hour format, e.g. 19 for
7pm. Day and night switching is intended so that the detector may automatically select
a different sensitivity when the protected area is unoccupied and fewer contaminants
are being produced. ClassiFire automatically detects the change in smoke level after the
protected area is left, and if the time at which this happens is within + 70 minutes of
the programmed switchover time it selects the night-time histogram. This means that
changes in time setting, e.g. changing to summer time, may be ignored as the detec-
tor will take this into account. The default times for day and night start are 08:00 and
19:00 respectively
Note that if the environment actually becomes more contaminated during the night period
for any reason then ClassiFire will adapt to that too, reducing the night-time sensitivity.
These functions have no current use on the Stratos-Micra 100 but are reserved for future
expansion purposes.
Page 10
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
3.14 Programmed Isolate – Alarm actions tab
When this function is ticked the controller will not generate alarms and will not indi-
cate a fault condition on any fire panel which is connected, e.g. for use during detec-
tor maintenance. The “Fault” light will be illuminated on the detector front panel. The
isolated condition will be disabled automatically after 7 days if not manually disabled.
This function is disabled by default.
When this function box is ticked it requires a reset from the controlling computer to
clear an alarm condition.
If unticked, the alarm signal is extinguished as soon as the alarm condition ends. This
is the factory default setting.
When this function box is ticked it requires a reset from the controlling computer to
clear a fault condition.
If unticked, the fault signal is extinguished as soon as the fault condition ends. This is
the factory default setting.
Ticking this function box means that only when the detector’s controller has gone into
Pre-Alarm does the controller start counting down the main Fire delay i.e. the time
delays on Pre-Alarm and Fire 1 are cumulative. The Aux alarm is not included in the
cumulative delay since it may be set to a higher level than either the Pre-Alarm or Fire
1 levels. This function is enabled by default.
This function is for display purposes only. It shows any special designation for the unit,
which will normally be Stratos-Micra 100.
This function is for display purposes only. It shows the version number of the fitted
firmware chip.
This function is for display purposes only. It shows the cumulative total number of hours
that the device has run (NB: this is not the time that has elapsed since last power-up, but
the sum total of run time since the detector memory was last reset).
Page 11
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
3.21 Watchdog count – Device information tab
The watchdog is a circuit built into the controller that restarts the controller in the
event of a failure to function properly. This could be as a result of electrical spikes. This
count shows the number of interruptions found. The details of each problem can be
found in the event log. See section 8, “Event log” for further details.
This function has no current use on the Stratos-Micra 100 but is reserved for future expan-
sion purposes.
A Micra detector may use another detector as a fresh air reference. This function is the
address of the detector which will be used as the reference.
To set a detector as a reference detector, enter its address as set by its internal DIP
switch into this function. This function is disabled by default.
Ticking this box enables the reference for the detector, if one has previously been allo-
cated in Reference detector (see section 3.23) This function is disabled by
default.
The value set with this function is the percentage reference signal subtracted from the
detector’s signal, if a reference device has been allocated. The default value is 0.
This value is the delay time between a build up of pollution being seen by the refer-
ence (if used) and the pollution being seen by the detector. The default value is 15.
This function is for display purposes only, and shows a value corresponding to the cur-
rent airflow through the detector.
This value is the level above which airflow needs to increase to trigger a fault indica-
tion (which may indicate a loose or damaged inlet pipe).
Flow low limit and Flow high limit parameters are automatically set up on
initial power-up.
This value is the level below which airflow needs to be reduced to trigger a fault read-
ing (which may indicate a blocked pipe).
Flow low limit and Flow high limit parameters are automatically set up on
initial power-up.
Page 12
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
3.30 Aspirator speed – Flow monitoring tab
This function has no current use on the Stratos-Micra 100 but is reserved for future expan-
sion purposes.
This is the access code required to amend programmable parameters. The default code
is 0102. Once the appropriate code is entered it may be changed here to any four digit
number to limit unauthorised access.
This function controls how frequently the detector and alarm level or flow rates are
stored in the Stratos-Micra 100’s internal chart recorder log. (See section 4.3, ‘Chart
recording’).
In the above table the grayed section indicates flow rate recording while the white sec-
tion indicates detector and alarm level recording.
At the slowest recording rate, one month of data can be recorded. The factory default
setting is 8.
Page 13
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
3.33 Separator condition – Miscellaneous tab
The value given at this function is the efficiency rating of the dust separator element in
the detector as a percentage of the efficiency of a clean separator. A new element will
give a reading of 99 in this function. When the efficiency has decreased to 80%, the
Fault indicator LED will illuminate and the event log will show “Separator renew”.
Note - After fitting a new element, it will be necessary to start a FastLearn to reset the sep-
arator condition reading (see section 3.7).
This function defaults to “--“, which means that a separator fault will only appear
when the efficiency decreases to 80% (see 3.33, “Separator condition”). However, a
date may be entered into this function to allow for a scheduled maintenance period.
The detector will then generate a separator fault at the planned time regardless of the
condition of the separator, although degradation of the separator to below 80% effi-
ciency before this date will override this.
See section 10, “Maintenance” for further details.
Enabling this function will reset each programmable function to the default value indi-
cated in the text, where a default setting is specified. It will also put the detector into
FastLearn mode, regardless of whether or not Auto Fastlearn is enabled (see section
3.8). This ensures that the flow setups and alarm thresholds are optimised to the detec-
tor’s working environment after resetting. It should be noted that where a ClassiFire
alarm factor other than the default is required for the protected area, this will need to
be re-entered. Section 3.5 gives details of the ClassiFire alarm factors.
Page 14
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
4.2 Histogram screen
The histogram screen shows various aspects of the detector function. To enter the his-
togram screen, either select the menu options “View Ô Histogram viewer…” or click
the symbol indicated below.
Smoke density
histogram
Alarm flags
There are two types of smoke density histogram; one shown in blue (the “fast” his-
togram) which updates every 15 minutes, feeding information to the long-term “slow”
histograms (which appear in yellow). These set the detector sensitivity based on the
ambient smoke conditions and it takes 24 hours for the two slow histograms (the “day”
and the “night” histograms) to complete their learning phase (see section 3.7).
Detector sensitivity is based on the fast histogram during FastLearn and is thereafter
based on the currently active slow histogram. However, although the positions of the
alarm flags are based on the slow histogram, sudden changes in smoke density are
Page 15
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
picked up by the fast histogram so that early warning is given.
The chart recording function shows how smoke density in the protected area has var-
ied over time. The chart may be downloaded to disk or printed out from a connected
printer.
To access the chart log, select the menu options “View Ô Chart recording…” or click
the symbol indicated below.
Page 16
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
The following screen appears:
The red trace is the current alarm level and the black trace is the detector output. By
moving the cursor along the chart, the “Chart information” window (shown at the bot-
tom left) updates to show the date and time, detector level and alarm level of the rel-
evant period. The ‘File’ menu option in the chart recording window allows the chart
recording to be saved to disk or printed to a connected printer, and allows a previous-
ly saved chart recording to be loaded. Chart recording files have the extension “.rcw”.
Where a custom set of programmable function settings is commonly used, these may
conveniently be saved to or loaded from disk. To open a detector function settings
(.dfs) file, select the menu options “File Ô Open” or click on the symbol indicated
below.
Page 17
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
Click on the “List files of type” drop-down box and select “Detector settings (*.dfs)” as
indicated below.
A list will appear of all detector settings files stored on the current drive. As a special
case, if desiring to recall the factory default settings, there is a file named ‘default.dfs’
in the ‘remote2k’ directory. Loading this file will reset the detector to the factory
default.
Page 18
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
5. Design Stratos-Micra 100 is intended to provide LOCALISED incipient fire detection only. This
Limitations means that it is suitable for the substantial range of applications typified by; small non-
compartmentalised rooms, warehouse racking, or pieces of electronic or
electromechanical equipment where it is desirable to achieve individual incipient fire
! reporting. In compartmentalised rooms, each compartment would normally use
individual Stratos-Micra 100 detectors.
IMPORTANT
This product employs a very low-power aspirator and the aspirating capability of the
Stratos-Micra 100 detector is limited accordingly. Stratos-Micra 100 is NOT intended
to protect large areas, or to sample from areas where there may be any difference in
airflow rates or pressure differentials. Application of Stratos-Micra 100 in these
circumstances is not recommended. If detection in environments conforming to these
descriptions is required, alternative versions of Stratos products should be used.
Maximum length of sampling pipe used with the Stratos-Micra 100 detector is 100
metres in STILL AIR with 25 sampling holes (or Capillary Remote Sampling Points). This
will provide a transport time from the end of the sampling pipe within 120 seconds. If
the protected area has airflow present, the maximum permitted sampling pipe length
will be reduced. In areas or applications where the airflow rate exceeds 1 metre per
second, maximum sampling pipe length is reduced to 40 metres.
Stratos-Micra 100 is available with an optional ‘Piped Exhaust’ type Docking Station
(see illustration ‘A’ overleaf). This is primarily intended to allow the detector to sample
from areas which may be at different air pressure to the detector location. Typical uses
are for air-duct sampling and allowing the installation of the detector in under-floor or
ceiling voids or when sampling from pieces of computer related equipment.
Page 19
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
(A.) Above ceiling
sampling with exposed
detector Sampling hole
False ceiling
Exhaust pipe
Stratos-Micra 100
Sampling pipe
False ceiling
Stratos-Micra 100
Page 20
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
5.1 System Design Simple designs with short sampling pipes produce the best results. Complex sampling
pipe runs should be avoided with the Stratos-Micra 100 detector. The use of ‘T’
branch-pipes is not recommended. The Stratos-Micra 100 detector is fitted with two
sampling pipe inlets as standard. It is always preferable to use two shorter pipes as
opposed to one longer pipe. If two sampling pipes are used, care should be taken to
keep the sampling pipe lengths and number of sampling holes on each pipe within
10% of the other. This can be verified using the PipeCAD system design software.
Unused sampling pipe inlets should be fitted with pipe bungs.
Always locate the sampling points in positions to which smoke may reasonably be
expected to travel. Do not expect ceiling mounted sampling points to operate
satisfactorily if air flow from air-conditioning systems keeps the cool smoke from an
incipient fire reaching from reaching ceiling level. In this instance it is usually better to
locate the sampling pipe directly in the airflow (for example across the return air
register of an air conditioning unit).
There is no substitute for carrying out smoke tests prior to installation of pipe work to
indicate suitable sampling point location.
No more than TWO Air Handling Units may be protected with one Stratos-Micra 100
detector. In this application, ensure that the sampling pipe is raised clear of high
velocity air in the immediate vincinity of the air intake grille on stand-off posts as shown
below.
Sampling pipe
Incorrect
Standoff posts
Detector
Correct
Direction
of smoke
Detector
AHU
equipment
cabinet
Page 21
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
6. Installation Before installing the detector the local standards for installation of aspirating detection
systems must be consulted as these standards differ throughout the world. Specific
advice for one country may not be applicable to another. The following is a brief set of
guidelines on installing detectors.
n The detector will normally be mounted at a level where there is easy access to the
unit for configuration and programming.
n The exhaust air from the unit must not be impeded in any way. If the unit is
mounted in a different air pressure from where the air is being sampled (for
example an air duct), then a pipe must be taken from the exhaust port back to the
same air pressure zone as the sampling holes.
n All signal cables must be screened and must be of a suitable type. The specific type
of cable will normally depend upon the local fire regulations.
n The unit must not be placed in areas where either the temperature or humidity is
outside the specified operating range.
n The unit should not be placed in close proximity to any equipment expected to
generate high Radio Frequency levels (such as radio alarms) or units generating
high levels of electrical energy (such as large electric motors or generators).
6.1 Docking station The basic principle behind installation of the Micra is that all wiring and pipe-work is
installed using a docking station. This is a convenient feature which means that the
detector can be dismounted or replaced without disturbing any wiring or installed
pipe-work.
There are two types of docking station, one with a single inlet port for aspirating pipe-
work, the other with a second port allowing the detector exhaust air to be taken back
to the area of different atmospheric pressure from which the inlet is sampling (see
section 4, “Sampling Pipe Design”, paragraph 1).
Sampling Sampling
pipe ports Exhaust pipe ports
Cable glands Cable glands port
Mounting Mounting
screw holes screw holes
Page 22
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
6.1.2 Mechanical installation
The docking station is connected to the installed sampling pipe-work and fixed to the
wall or mounting surface using 3 off screws of a type appropriate to the mounting sur-
face. Ensure that the sampling and/or exhaust pipes are securely seated in the pipe
ports before fixing. If using a piped exhaust docking station be sure that the sampling
and exhaust pipes are fitted into the relevant ports as shown in section 6.1.
The Stratos-Micra 100 detector is supplied with removable terminal blocks (See illus-
trations in Section 2.2). These are simply removed from their sockets by lifting them
up at right angles to the circuit board. Take note of the orientation of each terminal
block and its function before removing it. It may also be beneficial to mark the con-
nection wires with suitable identification labels or coloured rings to aid in the connec-
tion process. NB: All connections should be made with the power turned off.
The power supply cable should be of screened type and should be led through the
metal cable gland provided, leaving about 35mm of the cable extending from the bot-
tom of the cable gland. Depending on the type of cable used, it may be necessary to
increase the diameter of the cable with sleeving or insulating tape to ensure that the
cable is firmly held when the cable gland is fully tightened.
Page 23
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
6.2.2 Signal connections
To connect the signal wire, lead a suitable wire type (RS485 cable 9841, 120 ohm
screened twisted pair or equivalent) through the second cable gland and tighten it into
position with about 35mm of cable from the bottom of the cable gland.
Remove either the three-way terminal block next to the power supply socket if con-
necting the detector to a SenseNET system, or the four-way “Bus” terminal block if
connecting the detector to an alarm panel in conjunction with the APIC addressable
bus card (see section 7.3). For example, in a SenseNET system using screened cable,
connect the screen wire(s) to the “SCN” terminal, Bus A wire(s) to the “A” terminal
and Bus B wire(s) to the “B” terminal.
If the detector is in the middle of a SenseNET chain, with input and output connec-
tions, it may be more convenient to link the common Bus A, Bus B and screen wires
to single A, B and screen wires for linking to the terminal block.
The following illustration shows the power and signal connections to the docking sta-
tion for connection to a single SenseNET cable.
SenseNET/RS485
bus A wire
SenseNET/RS485
bus B wire
Power supply
0V wire
Page 24
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
6.3 Final installation
Once the power and signal connections are made, slide the detector body up into the
docking station and fasten it into position using the M4 pan head screws provided. Slot
the power and signal terminal blocks into the relevant sockets on the detector PCB
(they will only click fully home in the correct orientation) and replace the detector
cover using the four M3 pan head screws provided.
NB: The detector is designed solely for operation with the front cover securely fit-
ted using all four fixing screws.
Removing the detector is simply the reverse of this process, leaving the pipe-work and
wiring connections installed in the docking station.
Dock fixing
screws
Page 25
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
7. Interfacing Because of the flexible nature of the Stratos-Micra 100® detector and the many possible
configurations, there are many options for interfacing the detectors to the Fire Panel.
These include many third party interfaces available from various manufacturers.
Because of this, it is not possible to give a complete list of all interfacing methods but
the following pages will give details of the most common methods that are likely to be
used.
In order to identify itself to the PC Command Module or fire panel, each detector needs
to have a unique address ranging from 1 to 127. The detector address is simply set on
the DIP switch SW1 at the bottom left of the opened detector on the main circuit
board. The switch settings are on for 1 and off for 0, and the detector address is set as
a 7-bit binary code (switch 8 equates to a value of 128 and so is outside the usable
address range). An example is shown below.
DIL ON
1 2 3 4 5 6 7 8
Page 26
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
7.1.2 Address table
ADDRESS 1 2 3 4 5 6 7 8 65 1 0 0 0 0 0 1 0
1 1 0 0 0 0 0 0 0 66 0 1 0 0 0 0 1 0
2 0 1 0 0 0 0 0 0 67 1 1 0 0 0 0 1 0
3 1 1 0 0 0 0 0 0 68 0 0 1 0 0 0 1 0
4 0 0 1 0 0 0 0 0 69 1 0 1 0 0 0 1 0
5 1 0 1 0 0 0 0 0 70 0 1 1 0 0 0 1 0
6 0 1 1 0 0 0 0 0 71 1 1 1 0 0 0 1 0
7 1 1 1 0 0 0 0 0 72 0 0 0 1 0 0 1 0
8 0 0 0 1 0 0 0 0 73 1 0 0 1 0 0 1 0
9 1 0 0 1 0 0 0 0 74 0 1 0 1 0 0 1 0
10 0 1 0 1 0 0 0 0 75 1 1 0 1 0 0 1 0
11 1 1 0 1 0 0 0 0 76 0 0 1 1 0 0 1 0
12 0 0 1 1 0 0 0 0 77 1 0 1 1 0 0 1 0
13 1 0 1 1 0 0 0 0 78 0 1 1 1 0 0 1 0
14 0 1 1 1 0 0 0 0 79 1 1 1 1 0 0 1 0
15 1 1 1 1 0 0 0 0 80 0 0 0 0 1 0 1 0
16 0 0 0 0 1 0 0 0 81 1 0 0 0 1 0 1 0
17 1 0 0 0 1 0 0 0 82 0 1 0 0 1 0 1 0
18 0 1 0 0 1 0 0 0 83 1 1 0 0 1 0 1 0
19 1 1 0 0 1 0 0 0 84 0 0 1 0 1 0 1 0
20 0 0 1 0 1 0 0 0 85 1 0 1 0 1 0 1 0
21 1 0 1 0 1 0 0 0 86 0 1 1 0 1 0 1 0
22 0 1 1 0 1 0 0 0 87 1 1 1 0 1 0 1 0
23 1 1 1 0 1 0 0 0 88 0 0 0 1 1 0 1 0
24 0 0 0 1 1 0 0 0 89 1 0 0 1 1 0 1 0
25 1 0 0 1 1 0 0 0 90 0 1 0 1 1 0 1 0
26 0 1 0 1 1 0 0 0 91 1 1 0 1 1 0 1 0
27 1 1 0 1 1 0 0 0 92 0 0 1 1 1 0 1 0
28 0 0 1 1 1 0 0 0 93 1 0 1 1 1 0 1 0
29 1 0 1 1 1 0 0 0 94 0 1 1 1 1 0 1 0
30 0 1 1 1 1 0 0 0 95 1 1 1 1 1 0 1 0
31 1 1 1 1 1 0 0 0 96 0 0 0 0 0 1 1 0
32 0 0 0 0 0 1 0 0 97 1 0 0 0 0 1 1 0
33 1 0 0 0 0 1 0 0 98 0 1 0 0 0 1 1 0
34 0 1 0 0 0 1 0 0 99 1 1 0 0 0 1 1 0
35 1 1 0 0 0 1 0 0 100 0 0 1 0 0 1 1 0
36 0 0 1 0 0 1 0 0 101 1 0 1 0 0 1 1 0
37 1 0 1 0 0 1 0 0 102 0 1 1 0 0 1 1 0
38 0 1 1 0 0 1 0 0 103 1 1 1 0 0 1 1 0
39 1 1 1 0 0 1 0 0 104 0 0 0 1 0 1 1 0
40 0 0 0 1 0 1 0 0 105 1 0 0 1 0 1 1 0
41 1 0 0 1 0 1 0 0 106 0 1 0 1 0 1 1 0
42 0 1 0 1 0 1 0 0 107 1 1 0 1 0 1 1 0
43 1 1 0 1 0 1 0 0 108 0 0 1 1 0 1 1 0
44 0 0 1 1 0 1 0 0 109 1 0 1 1 0 1 1 0
45 1 0 1 1 0 1 0 0 110 0 1 1 1 0 1 1 0
46 0 1 1 1 0 1 0 0 111 1 1 1 1 0 1 1 0
47 1 1 1 1 0 1 0 0 112 0 0 0 0 1 1 1 0
48 0 0 0 0 1 1 0 0 113 1 0 0 0 1 1 1 0
49 1 0 0 0 1 1 0 0 114 0 1 0 0 1 1 1 0
50 0 1 0 0 1 1 0 0 115 1 1 0 0 1 1 1 0
51 1 1 0 0 1 1 0 0 116 0 0 1 0 1 1 1 0
52 0 0 1 0 1 1 0 0 117 1 0 1 0 1 1 1 0
53 1 0 1 0 1 1 0 0 118 0 1 1 0 1 1 1 0
54 0 1 1 0 1 1 0 0 119 1 1 1 0 1 1 1 0
55 1 1 1 0 1 1 0 0 120 0 0 0 1 1 1 1 0
56 0 0 0 1 1 1 0 0 121 1 0 0 1 1 1 1 0
57 1 0 0 1 1 1 0 0 122 0 1 0 1 1 1 1 0
58 0 1 0 1 1 1 0 0 123 1 1 0 1 1 1 1 0
59 1 1 0 1 1 1 0 0 124 0 0 1 1 1 1 1 0
60 0 0 1 1 1 1 0 0 125 1 0 1 1 1 1 1 0
61 1 0 1 1 1 1 0 0 126 0 1 1 1 1 1 1 0
62 0 1 1 1 1 1 0 0 127 1 1 1 1 1 1 1 0
63 1 1 1 1 1 1 0 0
64 0 0 0 0 0 0 1 0
Page 27
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
7.2 Connecting a Stratos-Micra 100 to a SenseNET/RS485 detector
network
Up to 127 detectors may be linked in a single SenseNET bus, supporting a total length
of wire between adjacent detectors of up to 1.2km.
In the above example, two Stratos-Micra 100 detectors are linked into a 127-detector
bus with a Command Module and a number of Stratos-HSSD 2 detectors. It will be
noted that whereas the Stratos-HSSD 2 units have two input / output buses (1A / 1B
and 2A / 2B), the Stratos-Micra 100 has only a single such bus (A / B) and therefore
each bus terminal has an input and an output wire, compared with a single wire in each
terminal in the Stratos-HSSD 2.
For this reason, it may be easier to join the input and output wires for each bus and
screen connections together and to solder or crimp a single wire or connecting ferrule
to each wire pair so that they are easier to fit into the screw terminals. If this is done it
is recommended that bare wire joints be insulated to prevent possible shorting of the
data bus, which will cause a drop-out of data on the SenseNET bus.
In the above example, there could be a total length of RS485 cable of up to 1.2km
between the Command Module and Detector 3, since these are all on a single bus.
However, Detector 3 is a Stratos-HSSD 2 which has a second communications bus
(RS485 bus 2) and an RS485 repeater. This allows a further total of 1.2km of cable until
the next Stratos-HSSD 2 in the RS485 loop.
In the above example, if detectors 4-126 (not shown) were all of the Stratos-Micra 100
type then the total length of wiring between detectors 3 and 127 would be limited to
1.2km. However, each additional Stratos-HSSD 2 detector wired up using both RS485
buses would allow an additional 1.2km of cabling to be added to the RS485 loop.
Page 28
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
7.3 Connecting a Stratos-Micra 100 to an addressable Fire Panel
An Addressable Protocol Interface Card (APIC) may be used to decode detector infor-
mation and to relay this to a Fire Panel.
The APIC is fitted to the four mounting studs on the Stratos-Micra 100 PCB using the
supplied screws as shown below:
Mounting
studs x 4
APIC
Address
switch x 2
APIC
Interface
connection
The connections to the Fire Panel are made using the BUS L1 and H1 (bus 1 input and
output) and the BUS L2 and H2 (bus 1 input and output) terminal connectors shown
in Section 6.2.2.
The only settings that need to be made are on the APIC address DIP switches. The start
loop address Is entered on SW1 and the end loop address on SW2. In the case of a sin-
gle Stratos-Micra 100 the start and end addresses will be the same.
NB: The detector address on the SenseNET loop and the Fire Panel addressable protocol
address are the same, i.e. no address translation is performed. Some protocols may not sup-
port all the available alarm levels and fault reporting is usually a general fault with no
detailed fault information. Please consult the specific APIC protocol documentation for more
information.
Page 29
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
7.4. Connecting To connect a single stand-alone detector to a PC, connect the PC‘s serial port directly
to a PC to the detector‘s 9-way RS232 port. Connections for this cable are shown below.
2 3
3 2
5 5
7 8
8 7
Serial port
connection
to PC serial port
Page 30
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
8. Event Log An event is defined as
The detector stores an internal log of the last 200 events, and this can either be viewed
on a PC screen or downloaded to disk by use of the remote control software.
When the event log is full (200 events are stored) and a new event occurs, the oldest
event in the log is deleted (First-In, First-Out).
To download the event log, connect a PC to the detector serial port and run the
remote software. Either select the menu options “View Ô Event log” or click on the
event log symbol as indicated below.
Page 31
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
This shows the time and date of each event stored in the log along with its general
description. The buttons at the bottom of the screen allow control over the input and
output of the log.
Open: opens a previously saved event log. Event logs have the file extension “.evl”.
Save As: saves the current event log as a .evl file with a user defined name.
Print: prints the event log to a connected printer.
Filter: clicking on this option brings up the following screen:
This allows the user to limit the information printed or viewed on the PC screen.
For example the user might wish to concentrate on alarm events only. To do this,
click on “None”, which unticks all boxes, and then on “Alarms”. To tick all the boxes,
tick “All”.
Any or all of the event categories may be selected or deselected as desired.
Page 32
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
9. Commissioning Before commissioning the detector the local standards of aspirating detection systems
must be consulted. These standards differ widely throughout the world and specific
advice for the market in one country may not be applicable to another.
Commissioning strategy will initially depend upon the environment in which the
detector is installed. For instance, the test for a computer room (which should be a
relatively clean environment) would be very different from, say, a flour mill, which
would probably have a high level of airborne particulate content.
A widely accepted standard for computer rooms/EDP areas is British Standard BS6266,
equipment overheating at a stage well before combustion. To perform the test
electrically overload a 1 metre length of PVC insulated wire of 10/0.1mm gauge for one
minute using an appropriate power supply. The detector has two minutes from the end
of the wire burn to give an alarm indication.
For areas with higher levels of background particulate matter testing methodology
would be similar to that of standard point detectors.
9.1 Commissioning The following brief checklist allows quick setup of the detector. This procedure will be
checklist adequate for most standard installations.
1. Before powering up the detector, visually check all cabling to ensure correct
connection. If wire identification is not immediately clear (e.g. by use of different
coloured wires or wire identification sleeves) an electrical check should be made.
! Any damage caused by mis-connection of the detector is not covered by
warranty.
IMPORTANT NOTE
2. Power up the unit and connect to a PC and set the address switches on the
detector board (see section 7.1) and APIC board if applicable (see section 7.3).
3. Verify that the time and date are correct (see section 3.1)
4. Set an appropriate alarm factor for the protected environment. The detector will
perform a FastLearn for the new alarm factor. (see section 3.7)
5. Whilst the detector is still in FastLearn mode set the detector into demonstration
mode (see section 3.10). NB: Aerosol-type synthetic smoke sources should not
be used to test the response of the detector as these may leave acidic residues
which could cause damage to the unit.
6. Wait for the FastLearn to finish and the flashing OK LED indicator will finish and
perform any necessary smoke tests, ensuring that the detector reacts
appropriately, and let the smoke fully dissipate.
7. Perform another FastLearn, this time not putting the detector into demonstration
mode. The detector will generate no alarms during the 15 minute FastLearn
period, and after this the detector will operate at a reduced sensitivity for 24 hours
whilst ClassiFire acclimatises to the protected environment and sets up appropriate
day and night sensitivity settings.
Page 33
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
10. Maintenance Stratos-Micra is a very low maintenance detection system. If required, external cleaning
of the unit should be performed using a damp (not wet) cloth. Do not use solvents as
these may mar the front panel label. The only part that may require field replacement
during servicing is the dust separator assembly*. The dust separator condition can be
checked using the Dust Separator test in the Miscellaneous tab of the remote
software ‘Detector settings’ screen (see section 3.33) which gives a percentage
reading of dust separator efficiency. When this level drops to 80% the detector will
signal a fault and the dust separator will need replacing. To replace the filter, simply
remove the front cover and pull the filter out from the main unit. Slide the replacement
filter in so that the ‘Direction of flow’ arrow printed on the carton duplicates that on
the ‘Direction of flow’ label beside the filter slot.
*It is recommended that dust separators be changed at an interval of not more than 3
! years. After replacing the filter, the detector must be put into FastLearn mode (see
section 3.7) to reset the filter condition reading.
IMPORTANT NOTE
Page 34
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
10.1 Diagnostics
The remote control software includes a diagnostic function which carries out a number
of checks to verify the correct functioning of the detector. A good time to run these
tests is as a part of planned maintenance. To call up diagnostic mode, select the menu
options “View Ô Diagnostics” or click on the symbol indicated below.
The software will then scan the loop for up to 127 detectors. For a single detector, wait
until the first detector has been identified and the window indicates that it is scanning
for Detector 2, then press the Cancel button.
Click on the list entry to highlight it and click on the “Diagnostics…” button. The soft-
ware will then commence the system tests. During the “Aspirator and flow” test, the
detector fan will suddenly slow down, but this is a normal part of the test and no cause
for alarm.
Page 35
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
When the test has finished and no problems have been found, the following screen
appears:
If any problems were found during the diagnostic tests, the nature of the fault will be
indicated in the “Status” column.
Read Button: This brings up a display of the detector output and flow rate which
updates in real time.
Relays: Brings up a screen allowing the function of the volt-free ‘Fire’ and
Fault LEDs to be tested with the aid of a continuity meter or other
tester. The Fire relay contacts are open in normal operation and will
close on test. The Fault relay contacts operate on a ‘Fail-safe’ basis
and are held closed in normal operation. They will therefore open on
test.
Save As: Saves the summary list of scanned detectors and their status as a text
(.txt) file.
Page 36
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
11. Troubleshooting 11.1 Nuisance alarms occur too often
• Check that the ClassiFire alarm factor setting is appropriate for the normal work-
ing environment of the protected area. See section 3.5
• Check that the detector is not in Demonstration mode. This can be ascertained by
viewing the event log (see section 3) and checking that the entry
Demo mode has a higher log entry number than the most recent
FastLearn start and FastLearn end entries. Remember that the log
entries are in reverse order, with the most recent entries appearing first.
If the log shows that Demonstration mode was invoked during the last FastLearn
period, start a new FastLearn and allow it to complete its 24-hour cycle. (See
section 3.7)
• From the event log (see sections 8), check that 24 hours have elapsed since the
last FastLearn end entry.
• Check that day-night switchover times are appropriately set to reflect active and
non-active periods (see section 3.11).
Page 37
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
11.6 Flow fault errors
• These occur when the airflow rate into the detector is outside the pre-
programmed limits. As the detector ‘learns‘ the flow setup from the initial
installation, this usually means that there has been some change in conditions. A
Flow high fault may indicate that a sampling pipe is damaged, and a Flow low
fault may indicate that the pipe has been blocked, e.g. by nearby building
operations.
• If the detector input is sampled from one area and the exhaust is in another area
with different pressure (e.g. the detector is in a roof space and sampling from an
enclosed room), this may lead to flow faults. In this case it would be necessary to
lead a pipe from the exhaust to the protected area to ensure normal flow. This will
require the detector to be installed using the piped exhaust docking station (see
section 6.1).
• Check that the low flow fault threshold is not set too high (see section 3.29)
• Check that the pipe is pushed home into the inlet and is not broken or cracked
• Check that installed pipe-work is fitted with an end-cap. AirSense Technology Ltd
PipeCAD® pipe modeling software prompts the use of appropriate end-caps.
Open bore pipes are not recommended.
• Check that the high flow fault threshold is not set too low (see section 3.28)
Page 38
© AirSense Technology Ltd. 2005 Stratos-Micra 100 •WWW.UKPANELS.COM
INSTALLER’S HANDBOOK • Iss. 3
12. Do’s and Don’ts DO
4 Ensure that cables are correctly connected before powering up by use of cable
identifiers or electrical continuity checks. Incorrect connection could damage the
detector.
4 Place sampling points so that the detector will be able to detect smoke at the
earliest opportunity.
4 Ensure that the detector exhaust is in an area with the same atmospheric pressure
as the sampling pipes, either by placing the detector physically in the protected
area or by leading a pipe from the detector exhaust to the protected area.
4 Ensure that the environment of the protected area is within the environmental
operating parameters of the detector (temperature -10 to +60°C, (humidity 0-
90%, non-condensing).
DON’T
8 Forget to set the appropriate ClassiFire alarm factor for the area to be detected.
8 Forget to set the Detector Address Switches correctly when used in a network.
8 Attempt to adjust or alter detector settings other than via the user-programmable
functions. In particular, the setting up of the laser is a precision task, and once set
up the potentiometers should be left alone. If it is suspected that the laser
alignment has shifted (e.g. after dropping the detector), it should be returned to
AirSense for recalibration.
8 Operate the detector with the front cover removed, or with one or more of the
cover fixing screws loose or missing.
Page 39
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
13. Stratos-Micra 100 SELV rating (EN 60950) Class III
specification Supply Voltage 21.6V - 26.4V DC
PSU Type: conforming to EN 54-4
Electrical safety complies with BS EN
610190-1
Size (mm) 300W x 220H x 90D
Weight 3.8kg with docking station
Operating temperature range 0 to +38°C (UL268)
–10 to +60°C (CEA4022)
Operating humidity range 0 - 90% Non Condensing
BS EN 61010-1 Pollution degree 1
BS EN 61010-1 Installation Cat. II
Sensitivity range (%Obs/m) Min = 25% Max = 0.03% FSD
Maximum sensitivity resolution 0.0015 % obs/m
Detection principle Laser light scattering mass detection
Particle sensitivity range 0.0003µm to 10µm
Current consumption 400mA
Relay contact rating 500mA @ 30V
Maximum sampling pipe length 100 metres total (see design limitations
on section 5)
Sampling pipe inlets 2
Sampling pipe internal diameter 15-25mm
Alarm levels 4 (Fire 2, Fire 1, Pre-Alarm and Aux)
1 relay as standard, others available
Chamber service intervals Greater than 8 years (depending on
environment)
Dust separator replacement intervals Greater than 5 years (depending on
environment)
Laser lifetime (MTTF) Greater than 1000 years
Programming PC via RS232/RS485
Data bus cable RS485 data cable
Data bus length 1.2 km
IP rating IP50
Page 40
WWW.UKPANELS.COM
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 3 © AirSense Technology Ltd. 2005
AirSense Technology Limited
71 Knowl Piece • Wilbury Way
Hitchin • Hertfordshire • SG4 0TY
Tel: +44 (0)1462 440666 • Fax: +44 (0)1462 440888
e-mail: [email protected] • www.airsensetechnology.com
WWW.UKPANELS.COM