Software v3.x
⑦
FOUNDATION fieldbus) _____________
NOTE: For applications using the Model 7xQ or 7xS steam probes, it
is mandatory to keep the transmitter and probe matched as a
set.
1.2.1 Probe
② Carefully place the probe into the vessel. Align the probe
process connection with the threaded or flanged mounting
on the vessel.
➪
3. Use the Up or Down Arrow ( ) keys to move from one
➪
Down
Up step of the configuration program to the next step.
LvlUnits!
➪
4. Press the Enter Arrow ( ) key. The last
character in the first line of the display xxx
changes to an exclamation point (!).
➪
5. Use the Up or Down Arrow ( ) keys to increase or
➪
decrease the value in the display or to scroll through the
choices.
➪
6. Press the Enter Arrow ( ) key to accept a value and move
to the next step of the configuration program (the default
password is 0).
7. After entering the last value, allow 10 seconds before
removing power from the transmitter.
The following configuration entries are the minimum required for
configuration (the default password is 0 from the LCD/keypad).
PrbModel
① (select)
Select the Probe Model to be used
Model 705: 7xA-x, 7xB-x, 7xD-x, 7xE-x, 7xF-F, 7xF-P,
7xF-4, 7xF-x, 7xJ-x, 7xK-x, 7xP-x, 7xQ-X,
7xR-x, 7xS-x, 7xT-x, 7x1-x, 7x2-x, 7x5-x, 7x7-x
PrbMount
② (select)
4 Select the type of Probe Mounting to vessel (NPT, BSP,
2 Probe Mount In or Cm
or flange).
MeasType
③ (select)
20 mA
Select from Level Only, Level and Volume, Interface Level
9
or Interface Level and Volume.
Lvl Units
(100% Point)
④ xxx
Select the Units of measurement for the level readout (inches,
cm, feet or meters). Not included on Model 705 Fieldbus.
Probe Ln
1 Probe Model 5
⑤ xxx.x
Probe Length
Enter the exact Probe Length as printed on the probe
Dielectric nameplate.
LvlOfst
7
⑥
of Medium
xxx.x
Enter the Level Offset value. Refer to Section 2.6.6 for
4 mA Level
further information. (The unit is shipped from the factory
8
(0%-point) with offset = 0; i.e., all measurements are referenced to
Level Offset 6 the bottom of the probe).
Dielctrc
⑦ (select)
Enter the Dielectric range for the material to be measured.
Set 4mA
NOTE: A small transition zone (0–6")
⑧ xxx.x
may exist at the top and bottom Enter the level value (0%-point) for the 4 mA point.
of the probe. See Specifications,
Set 20mA
Enter the level value (100%-point) for the 20 mA point.
⑨ xxx.x
Section 3.6.
2.1 Unpacking
Model Number
Serial Number
2.4 Mounting
NOTE: For applications using the Model 7xQ or 7xS steam probes, it
is mandatory to keep the transmitter and probe matched as a
set.
①
stillwell diameter for Twin Rod probe is 3".
③ Carefully place the probe into the vessel. Align the gasket
③
④
on flanged installations.
⑤ ④ Align the probe process connection with the threaded or
flanged mounting on the vessel.
⑤ For threaded connections, tighten the hex nut of the probe
Active Inactive
probe rod probe rod
2.4.4.1 Applications
1. Plastic pellets, sugar: Dielectric constant 1.9-2.0
2. Grain, seeds, sand: Dielectric constant 2.0-3.0
3. Salts: Dielectric constant 4.0-7.0
4. Metallic powder, coal dust: Dielectric constant >7
2.4.4.2 Mounting recommendations
1. Use a weight instead of securing the probe to the vessel.
2. Mount probe at least 12 inches from the wall. Ideal
location is 1⁄4 to 1⁄6 the diameter to average the angle
of repose.
3. A metal flange must be used when mounting on plastic
vessels.
2.4.4.3 To install a Model 7x5 bulk solids flexible twin rod
probe:
➀ Make sure the process connection is at least 2" NPT or a
flanged mounting.
➀
nector to get dirty.
➂ Align the universal connection at the base of the transmitter
➄ housing with the top of the probe. Hand-tighten the
➂ connection.
➃ Rotate the transmitter to face the most convenient direction
for wiring, configuration, and viewing.
➄ When the transmitter is facing the desired direction, use a
11⁄2" (38 mm) wrench to tighten the universal connection on
the transmitter to 45 ft-lbs. A torque wrench is highly rec-
ommended. This is a critical connection. DO NOT LEAVE
HAND-TIGHT.
➀
wrench, tighten the universal connection on the transmitter
to 45 ft-lbs. A torque wrench is highly recommended. This is
a critical connection. DO NOT LEAVE HAND-TIGHT.
➂
➁
The keypad has three arrows used to scroll through the dis-
plays and to calibrate the transmitter. The Up and Down
➪
➪
Arrow ( ) keys and the Enter ( ) key.
➪
Function in Function in
Arrows Display Mode Configuration Mode
Up and Down Moves forward and backward Increases or decreases the
in the configuration program value displayed or moves to
➪
➪
NOTE: If the password is not known, the menu item New Password
displays an encrypted value representing the present pass-
word. Call the factory with this encrypted value to determine
the present password.
% Output
xx.x%
Transmitter Display Transmitter displays % Output measurement derived from 20 mA
3
span
Loop
xx.xx mA
Transmitter Display Transmitter displays Loop value (mA)
4
Select the type of probe Select from 7xA-x, 7xB-x, 7xD-x, 7xE-x, 7xF-x, 7xF-E, 7xF-F,
PrbModel 7xF-4, 7xG-x, 7xF-P, 7xG, 7xJ-x, 7xK-x, 7xL, 7xM, 7xN, 7xP-x,
(select)
used
5 7xQ-x, 7xR-x, 7xS-x, 7xT-x, 7x1-x, 7x2-x, 7x5-x, 7x7-x as
(Example: 7xR-x)
shown on the probe nameplate
PrbMount
(select)
Select the type of probe Select from NPT, BSP, or Flange
6
mounting
MeasType
(select)
Select type of measurement Select Lvl Only
7
LvlUnits
(select)
Select level units Select from cm, inches, feet or meters
8
Probe Ln
xxx.x
Enter the exact length of Probe length is printed on the nameplate and order information
9
probe and is the last three digits of the probe model number
Lvl Ofst
xxx.x
Enter the desired reading Level Offset is the distance from the probe tip to the desired 0
10
when probe is dry level point (-90 to 300"). Refer to Section 2.6.6
Dielctrc
Select range bounding the Select from 1.4–1.7; 1.7–3; 3–10; 10–100
11 (select) dielectric constant of the
media
Set 20mA
Enter the PV value for the A small transition zone (0–6") may exist at the top/bottom of
15 xxx.x lu 20 mA point the probe. Top 4" (100 mm) of 7xB Twin Rod Probe is inactive.
See Functional Specifications Probe, Section 3.6.1
Damping
xx s
Enter time constant of A Damping factor (0–10 seconds) may be added to smooth the
16
desired damping output due to turbulence
Fault
(select)
Select the loop current value Select from 3.6 mA, 22 mA or HOLD
17
in presence of a fault
BlockDis
Enter distance below refer- Allows user to ignore level measurements near the top of the
18 xx.x lu ence point where level is not probe
sensed
Select loop current behavior Safety Zone is a user-defined area just below the Blocking
when level is sensed in safety Distance. Enable Fault if necessary to ensure safe, reliable high-
SZ Fault
(select)
zone level readings in critical applications. Choices are None, 3.6 mA,
19
22 mA, Latch 3.6 or Latch 22. If Latch 3.6 or Latch 22 is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#21)
SZ Height
Enter distance below Enter a distance value that develops a safety zone just below the
20 (xx.x lu) BlockDis where SZ Fault will Blocking Distance. Here the unit will report a Safety Zone Fault
be asserted (#19) if the level rises into this area.
SZ Alarm Reset
Press Enter to clear a Clear a latched Safety Zone alarm
21
latched Safety Zone alarm
Select the type of threshold Unit default CFD. Only select Fixed in application with low
Threshld
(select)
22 dielectric material over higher dielectric material and unit is read-
ing incorrect level. Example: Oil over water. (Adjustment of Trim
Level may be necessary when threshold is changed)
Poll Adr
xx
Enter HART polling address Select a HART poll address (0–63). Enter 0 for a single
23
number (0-63) transmitter installation. Poll address does not affect loop current.
Loop Mode
Enable/Disable Determines whether the loop is fixed at 4.0 mA or controlled by
24
the PV.
Trim Lvl
xx.x lu
Enter value to adjust Level -10.0 inches ≤ Lvl Trim ≤ +10.0 inches
25
reading (Requires superuser password)
Trim 4
xxxx
Fine tune the 4 mA point Adjust setting to output exactly 4.0 mA on current meter
26
Trim 20
xxxx
Fine tune the 20 mA point Adjust setting to output exactly 20.0 mA on current meter
27
Loop Tst
xx.x mA
Enter a mA Output value Set mA output to any given value to perform loop test
28
LvlTicks
Xxxxx
Diagnostic Display Time of flight from fiducial to level signal
29
New Pass
xxx
Enter new password (0-255) Displays encrypted value of present password
30
Language
(select)
Select from English, Spanish, Language choice for LCD display
31
French, German
Mdl705HT
Ver3.0a0
Transmitter display Product identification Firmware version
32
35 Run Time
History Reset
Press Enter and select yes Similar to SZ Alarm Reset
36
to clear history
HF cable
(select)
Superuser Parameter Select from 3-foot or 12-foot remote
37
FidTicks
xxxx
Diagnostic Display Time of flight from start of ramp to fiducial
38
39 FidSprd
Fid Type
(select)
Superuser Parameter Select from positive or negative
40
(Selection only allowed for some probes)
Fid Gain
xxx
Superuser Parameter Amount of gain applied to the fiducial signal
41
Window
xxx
Factory Parameter
42
Conv Fct
xxxx
Factory Parameter Calibration parameter
43
Scl Ofst
xxx
Factory Parameter Calibration parameter
44
Neg Ampl
xxx
Superuser Password Diagnostic parameter
45
Pos Ampl
xxx
Superuser Password Diagnostic parameter
46
Signal
xxx
Diagnostic Display Indication of level signal amplitude
47
Compsate
(select)
Superuser Password Select from None, Manual, Auto
48
DrateFct
xxxx
Diagnostic Display Compsate = Auto. Velocity derating factor for Model 7xS Steam
49
probe
Targ Ampl
xxxx
Diagnostic Display Compsate = Auto. Indication of steam reference target amplitude
50
Targ Tks
xxxx
Diagnostic Display Compsate = Auto. Measured time of flight from fiducial to steam
51
reference target
Targ Cal
xxxx
Diagnostic Display Compsate = Auto. Calibrated time of flight from fiducial to target
52
in room temperature air
OperMode
(select)
Superuser Password Compsate = Auto. Select from Run, Cal, Off
53
7xKCorr
xxx
Superuser Password Distance in mm from fiducial to user reference point
54
(7xK probe characteristic)
ElecTemp
xxx C
Diagnostic Display Present temperature in electronics compartment
55
(degrees Celsius)
Max Temp
xxx C
Superuser Password Maximum electronics temperature recorded
56
Min Temp
xxx C
Superuser Password Minimum electronics temperature recorded
57
SZ Hyst
xx.x lu
Superuser Password
58
Volume
xxx vu
Transmitter Display Transmitter displays Volume in selected units
2
% Output
xx.x%
Transmitter Display Transmitter displays % Output measurement derived from 20 mA
3
span
Loop
xx.xx mA
Transmitter Display Transmitter displays Loop value (mA)
4
Level
xxx.x 1u
Transmitter Display Transmitter displays Level Value in selected units
5
Select the type of probe Select from 7xA-x, 7xB-x, 7xD-x, 7xE-x, 7xF-x, 7xF-E, 7xF-F,
PrbModel
(select)
used 7xF-4, 7xF-P, 7xG-x, 7xJ-x, 7xK-x, 7xL, 7xM, 7xN, 7xP-x, 7xQ-x,
6
7xR-x, 7xS-x, 7xT-x, 7x1-x, 7x2-x, 7x5-x, 7x7-x as shown on the
(Example: 7xR-x)
probe nameplate
PrbMount
(select)
Select the type of probe Select from NPT, BSP, or Flange
7
mounting
MeasType
(select)
Select type of measurement Select from Lvl&Vol
8
LvlUnits
(select)
Select level units Select from cm, inches, feet or meters
9
Probe Ln
xxx.x lu
Enter the exact length of Probe length is printed on the nameplate and order information
10
probe and is the last three digits of the probe model number
Lvl Ofst
xxx.x lu
Enter desired Level reading Level Offset is the distance from the probe tip to the desired 0
11
when probe is dry level point (-90 to 300"). Refer to Section 2.6.6
VolUnits
(select)
Select the volume units Select from liters or gallons
12
StrapTbl
nn pnts
Enter to access strapping 20-point strapping table enables conversion from level to volume
13
table (Refer to Section 2.6.7 for more information)
Dielctrc
Select range bounding the Select from 1.4–1.7; 1.7–3; 3–10; 10–100
14 (select) dielectric constant of the
media
Senstvty
Enter value upward or Allows fine gain adjustment for single rod probes (this parameter
15 xxx downward to sense liquid is password protected for coaxial and twin rod probes)
surface
LoopCtrl
(select)
Select variable to control Select from Level or Volume
16
loop current
Set 4mA
xxxx vu
Enter the PV value for the A small transition zone (0–6") may exist at the top/bottom of
17
4 mA point the probe. See Functional Specifications Probe, Section 3.6.1
Set 20mA
xxxx vu
Enter the PV value for the A small transition zone (0–6") may exist at the top/bottom of
18
20 mA point the probe
Damping
xx s
Enter time constant of A Damping factor (0–10 seconds) may be added to smooth the
19
desired damping output due to turbulence
Fault
(select)
Select the loop current value Select from 3.6 mA, 22 mA or HOLD
20
in presence of a fault
BlockDis
Enter distance below refer- Allows user to ignore level measurements near the top of the
21 xx.x lu ence point where level is not probe
sensed
SZHeight
Enter distance below Enter a distance value that develops a safety zone just below the
23 xx.x lu BlockDis where SZ Fault will Blocking Distance. Here the unit will report a Safety Zone Fault
be asserted (#21) if the level rises into this area.
SZ Alarm Reset
Press Enter to clear a Clear a latched Safety Zone alarm
24
latched Safety Zone alarm
Select the type of threshold Unit default CFD. Only select Fixed in application with low
Threshld
(select)
dielectric material over higher dielectric material and unit is read-
25
ing incorrect level. Example: Oil over water. (Adjustment of Trim
Level may be necessary when threshold is changed)
Poll Adr
xx
Enter HART polling address Select a HART poll address (0–63). Enter 0 for a single
26
number (0-63) transmitter installation. Poll address does not affect loop current.
Loop Mode
Enable/Disable Determines whether the loop is fixed at 4.0 mA or controlled by
27
the PV.
Trim Lvl
xx.x lu
Enter value to adjust Level -10.0 inches <= Lvl Trim <= +10.0 inches
28
reading (Requires superuser password)
Trim 4
xxxx
Fine tune the 4 mA point Adjust setting to output exactly 4.0 mA on current meter
29
Trim 20
xxxx
Fine tune the 20 mA point Adjust setting to output exactly 20.0 mA on current meter
30
Loop Tst
xx.x mA
Enter a mA Output value Set mA output to any given value to perform loop test
31
LvlTicks
xxxx
Diagnostic Display Time of flight from fiducial to level signal
32
New Pass
xxx
Enter new password (0-255) Displays encrypted value of present password
33
Language
(select)
Select from English, Spanish, Language choice for LCD display
34
French, German
Mdl705HT
Ver3.0a0
Transmitter display Product identification Firmware version
35
DispFact
(select)
Select Yes to display factory Allows for viewing the factory parameters
36
parameter menus
History
(current status)
Press Enter to view history Diagnostic Display
37
of recent exceptions
HF cable
(select)
Superuser Parameter Select from 3-foot or 12-foot remote
38
39 Run Time
History Reset
Press Enter and select yes Similar to SZ Alarm Reset
40
to clear history
FidTicks
xxxx
Diagnostic Display Time of flight from start of ramp to fiducial
41
Fid Type
(select)
Superuser Password Select from positive or negative
42
(Selection only allowed for some probes)
43 Fid Spread
Window
xxx
Factory Parameter
45
Conv Fct
xxxx
Factory Parameter Calibration parameter
46
Scl Ofst
xxx
Factory Parameter Calibration parameter
47
Neg Ampl
xxx
Superuser Password Diagnostic factory setting
48
Pos Ampl
xxx
Superuser Password Diagnostic factory setting
49
Signal
xxx
Diagnostic Display Indication of level signal amplitude
50
Compsate
(select)
Superuser Parameter Select from None, Manual, Auto
51
7xKCorr
xxx
Superuser Parameter Distance in mm from fiducial to user reference point
52
(7xK probe characteristic)
ElecTemp
xxx C
Diagnostic Display Present temperature in electronics compartment
53
(degrees Celsius)
Max Temp
xxx C
Diagnostic Display Maximum electronics temperature recorded
54
Min Temp
xxx C
Diagnostic Display Minimum electronics temperature recorded
55
SZ Hyst
xx.x lu
Diagnostic Display Diagnostic factory setting
56
IfcLvl
xxxx vu
Transmitter Display Transmitter displays interface level in selected units
2
% Output
xx.x%
Transmitter Display Transmitter displays % Output measurement derived from
3
20 mA span
Loop
xx.xx mA
Transmitter Display Transmitter displays Loop value (mA)
4
5 Level
Select the type of probe Select from 7xB-x, 7xD-x, 7xF-x, 7xG, 7xL, 7xM, 7xN, 7xT-x,
PrbModel 7x7-x as shown on the probe nameplate
(select)
used
6
(Example: 7xT-x)
PrbMount
(select)
Select the type of probe Select from NPT, BSP, or Flange
7
mounting
MeasType
(select)
Select type of measurement Select from Intrface
8
LvlUnits
(select)
Select level units Select from cm, inches, feet or meters
9
Probe Ln
xxx.x
Enter the exact length of Probe length is printed on the nameplate and order information
10
probe and is the last three digits of the probe model number
Lvl Ofst
x.xx
Enter the desired reading Level Offset is the distance from the probe tip to the desired 0%
11
when probe is dry level point (-90 to 300"). Refer to Section 2.6.6
Upr Diel
Enter the dielectric constant Interface mode or Manual compensation mode
(select)
12 of the upper liquid
Dielctrc
Select range bounding the Select 10–100
13 (select) dielectric constant of the
lower liquid
Senstvty
Enter value upward or Allows fine gain adjustment for single rod probes (this parameter
14 xxx downward to sense liquid is password protected for coaxial and twin rod probes)
surface
LoopCtrl
(select)
Select variable to control Select from Level or IfcLvl
15
loop current
Set 4mA
xxx.x 1u
Enter the PV value for the A small transition zone (0–6") may exist at the top/bottom of
16
4 mA point the probe. See Functional Specifications Probe, Section 3.6.1
Set 20mA
xxx.x lu
Enter the PV value for the A small transition zone (0–6") may exist at the top/bottom of
17
20 mA point the probe
Damping
xx s
Enter time constant of A Damping factor (0–10 seconds) may be added to smooth the
18
desired damping output due to turbulence
Fault
(select)
Select the loop current value Select from 3.6 mA, 22 mA or HOLD
19
in presence of a fault
BlockDis
Enter distance below Allows user to ignore level measurements near the top of probe
20 xx.x lu reference point where
level is not sensed
SZ Fault
zone level readings in critical applications. Choices are None, 3.6 mA,
21 (select) 22 mA, Latch 3.6 or Latch 22. If Latch 3.6 or Latch 22 is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#23)
SZ Height
Enter distance below Enter a distance value that develops a safety zone just below the
22 xx.x lu BlockDis where SZ Fault will Blocking Distance. Here the unit will report a Safety Zone Fault
be asserted (#21) if the level rises into this area.
SZ Alarm Reset
Press Enter to clear a Clear a latched Safety Zone alarm
23
latched Safety Zone alarm
Threshld
(select)
Select from CFD, Fixed For interface, refers to threshold for upper level pulse. (Set to
24
Fixed for most common applications.)
IfcThrsh
(select)
Select from CFD, Fixed Interface mode only. Threshold for interface level pulse. (Set to
25
CFD for most common applications.)
Poll Adr
xx
Enter HART polling address Select a HART poll address (0–63). Enter 0 for a single
26
number (0-63) transmitter installation. Poll address does not affect loop current.
Loop Mode
Enable/Disable Determines whether the loop is fixed at 4.0 mA or controlled by
27
the PV.
Trim Lvl
xx.x lu
Enter value to adjust Level -10.0 inches <= Lvl Trim <= +10.0 inches
28
reading (Requires superuser password)
Trim 4
xxxx
Fine tune the 4 mA point Adjust setting to output exactly 4.0 mA on current meter
29
Trim 20
xxxx
Fine tune the 20 mA point Adjust setting to output exactly 20.0 mA on current meter
30
Loop Tst
xx.x mA
Enter a mA Output value Set mA output to any given value to perform loop test
31
LvlTicks
xxxx
Diagnostic Display Time of flight from fiducial to interface signal
32
IfcTicks
xxxx
Diagnostic Display Interface mode only. Time of flight through upper liquid
33
Medium
Diagnostic Display Interface mode only. Displayed messages are: Unknown,
34
Oil Only, Thin Oil, Thick Oil, Dry Probe
New Pass
xxx
Enter new password (0-255) Displays encrypted value of present password
35
Language
(select)
Select from English, Spanish, Language choice for LCD display. (no HART counterpart)
36
French, German
Mdl705HT
Ver3.0a0
Transmitter display Product identification. Firmware version
37
DispFact
(select)
Select Yes to display factory Access for viewing the factory parameter
38
parameter menus
History
(current status)
Press Enter to view history Diagnostic Display
39
of recent exceptions
40 Run Time
History Reset
Press Enter and select yes Similar to SZ Alarm Reset
41
to clear history
HF cable
(select)
Superuser Parameter Select from 3-foot or 12-foot remote
42
Fid Sprd
xxx
Diagnostic Display Spread in fiducial ticks readings
44
Fid Type
(select)
Superuser Parameter Select from positive or negative
45
(Selection only allowed for some probes)
Fid Gain
xxx
Superuser Parameter Amount of gain applied to fiducial signal
46
Window
xxx
Factory Parameter
47
Conv Fct
xxxx
Factory Parameter Calibration parameter
48
Scl Ofst
xxx
Factory Parameter Calibration parameter
49
Neg Ampl
xxx
Superuser Password
50
Ifc Ampl
Superuser Password
51
Pos Ampl
xxx
Superuser Password
52
Signal
xxx
Diagnostic Display Indication of level signal amplitude
53
Compsate
Superuser Parameter Select from None, Manual, Auto
54
7xKCorr
xxx
Superuser Parameter Distance in mm from fiducial to user reference point
55
(7xK probe characteristic)
ElecTemp
xxx C
Diagnostic Display Present temperature in electronics compartment
56
(degrees Celsius)
Max Temp
xxx C
Superuser Password Maximum electronics temperature recorded
57
Min Temp
xxx C
Superuser Password Minimum electronics temperature recorded
58
SZ Hyst
xx.x lu
Superuser Parameter Safety Zone hysteresis height
59
IfcLevel
xxx.x lu
Transmitter Display LoopCtrl = IfcLevel
2
Ifc Vol
xxxx vu
Transmitter Display LoopCtrl = Ifc Vol
3
% Output
xx.x%
Transmitter Display Transmitter displays % Output measurement derived from
4
20 mA span
Loop
xx.xx mA
Transmitter Display Transmitter displays Loop value (mA)
5
6 Level
7 Volume
Select the type of probe Select from 7xB-x, 7xD-x, 7xF-x, 7xG, 7xL, 7xM, 7xN, 7xT-x,
PrbModel 7x7-x as shown on the probe nameplate
(select)
used
8
(Example: 7xT-x)
PrbMount
(select)
Select the type of probe Select from NPT, BSP, or Flange
9
mounting
MeasType
(select)
Select type of measurement Select from Ifc&Vol
10
LvlUnits
(select)
Select level units Select from cm, inches, feet or meters
11
Probe Ln
xxx.x lu
Enter the exact length of Probe length is printed on the nameplate and order information
12
probe and is the last three digits of the probe model number
Lvl Ofst
xxx.x lu
Enter the desired reading Offset is the distance from the probe tip to the desired 0 level
13
when probe is dry point (-90 to 300"). Refer to Section 2.6.6
VolUnits
(select)
Select the volume units Select from liters or gallons
14
Measure type = Lvl&Vol or Ifc&Vol
StrapTbl
nn pnts
Enter to access strapping Measure type = Lvl&Vol or Ifc&Vol
15
table
Upr Diel
Enter the dielectric constant Interface mode
16 (select) of the upper liquid
Dielctrc
Select range bounding the Select 10–100
17 (select) dielectric constant of the
lower liquid
Senstvty
Enter value upward or Allows fine gain adjustment for single rod probes (this parameter
18 xxx downward to sense liquid is password protected for coaxial and twin rod probes)
surface
LoopCtrl
(select)
Select variable to control Select from Level, Volume, IfcLvl or IfcVol
19
loop current
Set 4mA
xxx.x 1u
Enter the PV value for the A small transition zone (0–6") may exist at the top/bottom of
20
4 mA point the probe. See Functional Specifications Probe, Section 3.6.1
Set 20mA
xxx.x lu
Enter the PV value for the A small transition zone (0–6") may exist at the top/bottom of
21
20 mA point the probe
Damping
xx s
Enter time constant of A Damping factor (0–10 seconds) may be added to smooth the
22
desired damping output due to turbulence
Fault
(select)
Select the loop current value Select from 3.6 mA, 22 mA or HOLD
23
in presence of a fault
BlockDis
Enter distance below Allows user to ignore level measurements near the top of the
24 xx.x lu reference point where level is probe
not sensed
Select lop current behavior Safety Zone is a user-defined area just below the Blocking
when level is sensed in safety Distance. Enable Fault if necessary to ensure safe, reliable high-
SZ Fault
(select)
zone level readings in critical applications. Choices are None, 3.6 mA,
25
22 mA, Latch 3.6 or Latch 22. If Latch 3.6 or Latch 22 is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#27)
SZ Height
Enter distance below Enter a distance value that develops a safety zone just below the
26 xx.x lu BlockDis where SZ Fault will Blocking Distance. Here the unit will report a Safety Zone Fault
be asserted (#25) if the level rises into this area.
SZ Alarm Reset
Press Enter to clear a Clear a latched Safety Zone alarm
27
latched Safety Zone alarm
Threshld
(select)
Select from CFD, Fixed For interface, refers to threshold for upper level pulse. (Set to
28
Fixed for most common applications.)
IfcThrsh
(select)
Select from CFD, Fixed Interface mode only. Threshold for interface level pulse. (Set to
29
CFD for most common applications.)
Poll Adr
xx
Enter HART polling address Select a HART poll address (0–63). Enter 0 for a single
30
number (0-63) transmitter installation. Poll address does not affect loop current.
Loop Mode
Enable/Disable Determines whether the loop is fixed at 4.0 mA or controlled by
31
the PV.
Trim Lvl
xx.x lu
Enter value to adjust Level -10.0 inches <= Lvl Trim <= +10.0 inches
32
reading (Requires superuser password)
Trim 4
xxxx
Fine tune the 4 mA point Adjust setting to output exactly 4.0 mA on current meter
33
Trim 20
xxxx
Fine tune the 20 mA point Adjust setting to output exactly 20.0 mA on current meter
34
Loop Tst
xx.x mA
Enter a mA Output value Set mA output to any given value to perform loop test
35
LvlTicks
Xxxxx
Diagnostic Display Time of flight from fiducial to interface signal
36
IfcTicks
Xxxxx
Diagnostic Display Interface mode only
37
Time of flight through upper liquid
Medium
Diagnostic Display Interface mode only
38
Displayed messages are: Unknown, Oil Only, Thin Oil, Thick Oil
New Pass
Xxx
Enter new password (0-255) Displays encrypted value of present password
39
Language
(select)
Select from English, Spanish, Language choice for LCD display. (no HART counterpart)
40
French, German
Mdl705HT
Ver3.0a0
Transmitter display Product identification. Firmware version
41
DispFact
(select)
Select Yes to display factory Allows for viewing the factory parameters
42
parameter menus
History
(current status)
Press Enter to view history Diagnostic Display
43
of recent exceptions
HF cable
(select)
Superuser Parameter Select from 3-foot or 12-foot remote
44
45 Run Time
Hist Rst
Press Enter and select yes Similar to SZ Alarm Reset
46
to clear history
FidTicks
xxxx
Diagnostic Display Time of flight from start of ramp to fiducial
47
48 Fid Sprd
Fid Type
(select)
Superuser Parameter Select from positive or negative
49
(Selection only allowed for some probes, fixed for others)
Fid Gain
xxx
Superuser Parameter
50
Window
xxx
Factory Parameter
51
Conv Fct
xxxx
Factory Parameter Calibration parameter
52
Scl Ofst
xxx
Factory Parameter Calibration parameter
53
Neg Ampl
xxx
Superuser Parameter
54
Ifc Ampl
Superuser Parameter
55
Pos Ampl
xxx
Superuser Parameter
56
Signal
xxx
Diagnostic Display Indication of level signal amplitude
57
Compsate
(select0
Superuser Parameter Select from None, Manual, Auto
58
7xKCorr
xxx
Superuser Parameter Distance in mm from fiducial to user reference point
59
(7xK probe characteristic)
ElecTemp
xxx C
Diagnostic Display Present temperature in electronics compartment
60
(degrees Celsius)
Max Temp
xxx C
Superuser Password Maximum electronics temperature recorded
61
Min Temp
xxx C
Superuser Password Minimum electronics temperature recorded
62
SZ Hyst
xx.x lu
Superuser Password Diagnostic factory setting
63
Lvl Ofst
Example 1 (Lvl Ofst = 0 as shipped from factory):
0.0 in
Application calls for a 72-inch NPT Coaxial probe in
60"
Dielctrc water with the bottom of the probe 10 inches above the
10-100
4 mA Set 4mA
bottom of the tank. The user wants the 4 mA point at
24" 24.0 in 24 inches and the 20 mA point at 60 inches as referenced
Set 20mA from the bottom of the probe.
60.0 in
10"
Dielctrc
30"
10-100
Set 4mA
4 mA
0 in
6"
Set 20mA
30.0 in
Example 3
Procedure 2:
The ECLIPSE Model 705 transmitter also allows the level
points to be entered automatically.
As above, a twenty-point table is available. However, with
this procedure, the user can allow the Model 705 to use the
present level as the strapping table entry.
1. Scroll down to the Strapping Table parameter and press
enter, Pt01Lvl is displayed.
2. Press and hold the ENTER button, then press the UP
arrow at the same time. (The present level reading is now
captured and entered into the strapping table.) Press enter
and the display shows Pt01Vol.
3. Enter the corresponding volume and press enter.
4. Add a known liquid volume to the vessel.
5. For the remaining points, add a known liquid volume to
vessel and repeat steps 2 to 3.
2.7.1 Connections
A HART communicator can be operated from a remote
location by connecting it to a remote junction or by con-
necting it directly to the terminal block in the electronics
housing of the ECLIPSE transmitter.
HART uses the Bell 202 frequency shift keying technique
Junction
of high-frequency digital signals. It operates on the 4–20
mA loop and requires 250 Ω load resistance. A typical
connection between a communicator and the ECLIPSE
transmitter is shown at left.
R L > 250 Ω
- +
2.7.2 Display Menu
A typical communicator display is an 8-line by 21-character
Control LCD. When connected, the top line of each menu displays
Room
Display
the model (Model 705 3.x) and its tag number or address.
Power Usually the bottom line of each menu is reserved for software-
Supply
defined function keys (F1–F4). For detailed operating infor-
mation, refer to the instruction manual provided with the
Current HART communicator.
Meter
1 Level
2 Volume
3 IfcLvl
4 IfcVol
2.8.1 Description
FOUNDATION fieldbus is a digital communications system
that serially interconnects devices in the field. A Fieldbus
system is similar to a Distributed Control System (DCS)
with two exceptions:
• Although a Fieldbus system can use the same physical
wiring as an existing 4–20 mA device, Fieldbus devices are
not connected point-to-point, but rather are multidropped
on a single pair of wires (referred to as a segment).
• Fieldbus is a system that allows the user to distribute
control across a network. Fieldbus devices are smart and
actually maintain control over the system.
Unlike 4–20 mA analog installations in which the two
wires carry a single variable (the varying 4–20 mA current),
a digital communications scheme such as Fieldbus considers
the two wires as a network. The network can carry many
process variables as well as other information. The ECLIPSE
Model 705FF transmitter is a FOUNDATION fieldbus regis-
tered device that communicates with the H1 Foundation
Fieldbus protocol operating at 31.25 kbits/sec. The H1
physical layer is an approved IEC 61158 standard. The
figure on page 38 shows a typical Fieldbus installation.
An IEC61158 shielded twisted pair wire segment can be as
long as 6234 feet (1900 meters) without a repeater. Up to
4 repeaters per segment can be used to extend the distance.
The maximum number of devices allowed on a Fieldbus
segment is 32 although this depends on the current draw
of the devices on any given segment.
57-600 Eclipse® Guided Wave Radar Transmitter 37
Details regarding cable specifications, grounding, termination,
and other network information can be found in IEC 61158
or at www.fieldbus.org.
PC
Power
Conditioner
Terminator Terminator
Power Supply
Control Room
2.8.2 Benefits
The benefits of Fieldbus can be found throughout all phases
of an installation:
1. Design/Installation: Connecting multiple devices to a single
pair of wires means less wire and fewer I/O equipment.
Initial Engineering costs are also reduced because the
Fieldbus Foundation™ requires interoperability, defined as
“the ability to operate multiple devices in the same system,
regardless of manufacturer, without a loss of functionality.”
All FOUNDATION fieldbus devices must be tested for
interoperability by the Fieldbus Foundation. MAGNETROL
Model 705FF device registration information can be found
at www.fieldbus.org.
2. Operation: With control now taking place within the
devices in the field, better loop performance and control are
the result. A Fieldbus system allows for multiple variables to
be brought back from each device to the control room for
additional trending and reporting.
3. Maintenance: The self-diagnostics residing in the smart
field devices minimizes the need to send maintenance
personnel to the field.
3.1 Description
ECLIPSE is a loop-powered two-wire, 24 VDC, level transmitter
based on the concept of Guided Wave Radar. Guided Wave
Radar, or Micropower Impulse Radar (MIR), is a revolutionary,
new level measurement technology.
The ECLIPSE electronics are housed in an ergonomic hous-
ing comprised of two tandem compartments angled at a
45-degree angle for ease of wiring and calibration. These
two compartments connect via an explosion proof and
watertight feed-through.
PACTware™ PC Program
The ECLIPSE Model 705 offers the ability to do Trending and Echo Curve analysis using a PACTware DTM.
This is a powerful troubleshooting tool that can aid in the resolution of some of the Error Messages shown above.
Refer to Bulletins 59-101 and 59-601 for more information.
Emulsion Layer
High Dielectric
Medium
(e.g., water)
➀ Factory Sealed: This product has been approved by Factory Mutual Research (FM), and Canadian Standards Association (CSA), as
a Factory Sealed device.
➁ IMPORTANT: Measured media inside vessel must be non-flammable only. If media inside vessel is flammable, then the
explosion proof version (which contains an internal barrier making the probe Intrinsically Safe) is required.
➂ Special conditions for safe use
Because the enclosure of the Guided Wave Radar Level Transmitter ECLIPSE Model 705-5 _ _ _ - _1 _ and/or Probe ECLIPSE Model
7_ _ -_ _ _ _ - _ _ _ is made of aluminum, if it is mounted in an area where the use of category 1 G (Zone 0) apparatus is required, it
must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
For applications in explosive atmospheres caused by gases, vapors or mists and where category 1G (Zone 0) apparatus is required,
electrostatic charges on the non-metallic parts of the Probe ECLIPSE Model 7x5- _ _ _ _ - _ _ _ , Model 7x7- _ _ _ _ - _ _ _ and
Model 7_ F- _ _ _ _ - _ _ _ shall be avoided.
➂
➄
➁
3.6.1 Functional
System Design
Measurement Principle Guided time-of-flight via time domain reflectometry
Input
Measured Variable Level, determined by the time-of-flight of a guided radar pulse from
transmitter to product surface and back
Zero and Span 6 inches to 75 feet (15 to 2286 cm)
Output
Type Analog 4 to 20 mA with HART digital signal (HART 6)
Range Analog 3.8 to 20.5 mA useable
Digital 0 to 999" (0 to 999 cm)
Resolution Analog 0.01 mA 1200
7xA: 7xQ:
+300 °F @ 400 psig +650 °F @ 2400 psig
Maximum (+150 °C @ 27 bar) +400 °F @ 275 psig +800 °F @ 1500 psig +400 °F @ 5500 psig (+340 °C @ 165 bar)
Process Temperature 7xG, 7xT & 7xR: (+200 °C @ 19 bar) (+427 °C @ 103 bar) (+200 °C @ 380 bar) 7xS:
+400 °F @ 270 psig +575 °F @ 1275 psig
(+200 °C @ 18 bar) (+300 °C @ 88 bar)
Maximum 1000 psig @ +70 °F 1000 psig @ +70 °F 6250 psig @ +70 °F 6250 psig @ +70 °F 3000 psig @ +100 °F
Process Pressure (70 bar @ +20 °C) (70 bar @ +20 °C) (430 bar @ +20 °C) (430 bar @ +20 °C) (207 bar @ +38 °C)
500 cp (Standard)
500 cp (Standard) 500 cp (Standard)
Maximum Viscosity 1500 cp (Enlarged) 1500 cp
1500 cp (Enlarged) 1500 cp (Enlarged)
500 cp
10,000 Caged Coaxial
Maximum +300 °F @ 400 psig +605 °F @ 1600 psig +300 °F @ 400 psig +150 °F @ 50 psig +300 °F @ 75 psig 160 °F
Process Temperature (+150 °C @ 27 bar) (+320 °C @ 110 bar) (+150 °C @ 27 bar) (+66 °C @ 3.4 bar) (+150 °C @ 27 bar) (71 °C)
10,000
Maximum Viscosity (consult factory if severe agitation/turbulence)
2000
Hermeticity N/A
7xA:
1" (25mm)@ εr= 1.4 1" (25 mm) 1" (25 mm)@ εr = 2.0 8" (200 mm) @
Transition Zone
6"(150mm)@ εr= 80.0 +4" inactive 1" (25 mm) 6"(150 mm) @
(Top) εr>20 εr = 80
7xR: εr = 80.0
None
Transition Zone 6" (150 mm) @ εr = 1.4 6" (150 mm) @ εr = 1.4
12" (305 mm) 1" (25 mm)@ εr = 80
(Bottom) 1" (25 mm) @ εr = 80.0 1" (25 mm) @ εr = 80.0
Pull N/A
7x5: 3000 lbs.
N/A
Force/Tension 7x7: 100 lbs.
NOTE: Transition Zone is dielectric dependent; εr = dielectric permittivity. The transmitter still operates but
level reading may become nonlinear in Transition Zone.
1000
5500
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
-320 -200 -100 0 100 200 300 400 500 600 700 800
Process Temperature (°F)
3.6.6 Physical
3.28 4.12
inches (mm) (83) (105)
45 View 4.00
(102)
Elect.
8.43 Conn.
(214) Qty. 2
2.75
4.94 (70) 45 33.00 or 144
(126) (838 or 3650)
3.00 3.75
2.00 (76) (95)
(51)
3.50 2 Holes
4.38 4.00
(89) .38 (10) Dia.
(111) (102)
Eclipse® Housing
(45° View)
10.08 10.08
(256) (256)
H H
45° 45°
2 cable 2 cable
entries entries
Process Process
H Conn. Conn.
H Probe Probe
Insertion Insertion
Mounting Length Length
Probe Insertion Flange
Probe Insertion Length
Length 1" BSP (G1)
3/4" NPT Process Conn. Probe D D
Process Conn. Insertion
Length Eclipse with 7xD Probe
®
Eclipse with 7xD Probe
®
10.08
10.08 (256)
(256)
45
Elect.
45 Conn.
Elect. Qty. 2
Conn.
Qty. 2
7.37
(187)
6.57
5.89 (167)
(150)
Ø 71 (2.80)
Process Process
2" cage: Ø 0.50 (13) rod Conn. Conn.
3" cage: Ø 19 (0.75) rod Probe
4" cage: Ø 25 (1) rod Insertion Probe Probe
Length Insertion Insertion
Length Length
HT PEEK spacer
D D
Eclipse® with 7xG Probe Eclipse® with 7xR or 7xT Probe Eclipse® with 7xR or 7xT Probe
max 240" (6.1 m) Threaded Connection Flanged Connection
0.88 (22)
Ø .50 (13)
Rods
0.38 (10)
Mounting
Flange
Process 5.08
Twin Rod Probe Conn.
4.96 (129)
End View (126)
Probe
Probe Insertion
Insertion Length
Length
Eclipse® with 7xB Twin Rod Eclipse® with 7xB Twin Rod
Probe – NPT Connection Probe – Flanged Connection
Mounting Mounting
NPT Process Flange NPT Process Flange
Connection Connection
2.80 3.13
1.75 (80) 3.25
(71)
(44) (83)
Eclipse® with 7x7 Twin Rod Flexible Probe Eclipse® with 7x5 Twin Rod Bulk Solids Flexible Probe
Flanged or NPT Connection Flanged or NPT Connection
Sanitary
Process Conn. 2.36
7xF: 2.36 (60)
Conn. 7xJ: 4.96 (126) 2.36 (60)
7xF: 2.24 (57)
7xJ: 4.84 (123) (60)
Ø 0.50" (12) Rod Ø 0.50" (12) Rod Ø 0.50" (12) Rod Ø 0.50" (12) Rod
Probe
Insertion 0.625" (16) O.D. PFA Probe
Probe Probe Insertion
Insertion Length Insertion Length
Length Length
Eclipse® with 7xF Probe Eclipse® with 7xF Probe Eclipse® with 7xF-E Probe Eclipse® with 7xF-F Probe
NPT Threaded Connection Flanged Connection Hygienic Connection Faced-Flange Connection
3.00 3.00
(76) (76)
7X1 7X2
12.00 3.00
(305) (76)
Probe Probe
Insertion Ø 0.1875" (5) Cable Insertion
Length Length
2.25" 6.00
3.88 Ø 2.0" (50) Ø 2.0" (50)
(57) (152)
(99)
1"
(25) Ø 0.50" (12) Hole 0.75" (19)
TFE Weight
1 lb. (454 grams)
316SS Weight
5 lb. (2268 grams)
Eclipse® with 7x1 Flexible Probe Eclipse® with 7x2 Bulk Solids Flexible Probe
Flanged or NPT Connection Flanged or NPT Connection
3.7.1 Transmitter
POWER
5 24 VDC, Two-wire
ACCESSORIES
0 No digital display and keypad
A Digital display and keypad
MOUNTING/CLASSIFICATION
Integral, General Purpose & Intrinsically Safe
1
(FM & CSA), Non-incendive (Class I, Div. 2)
Remote, General Purpose & Intrinsically Safe
2
(FM & CSA), Non-incendive (Class I, Div. 2)
3 Integral, Explosion Proof (FM & CSA) & Non-incendive
4 Remote, Explosion Proof (FM & CSA) & Non-incendive
Integral, General Purpose & Intrinsically Safe
A
(ATEX & JIS EEx ia IIC T4)
Remote, General Purpose & Intrinsically Safe
B
(ATEX & JIS EEx ia IIC T4)
Integral, Explosion Proof (ATEX EEx d [ia] IIC T6)
C
(must be ordered with Conduit Connection Codes 0 and 1)
Remote, Explosion Proof (ATEX EEx d [ia] IIC T6)
D
(must be ordered with Conduit Connection Codes 0 and 1)
E Integral, Non-incendive (ATEX EEx n II T4..6)
F Remote, Non-incendive (ATEX EEx n II T4..6)
HOUSING
1 Cast aluminum, dual compartment, 45° angle
2 316 stainless steel, dual compartment, 45° angle ➁
7 Cast aluminum, dual compartment, 45° angle, 12-ft remote
8 316 SS, dual compartment, 45° angle, 12-ft remote ➁
CONDUIT CONNECTION
0 ⁄4" NPT
3
1 M20
➀ Not available with Model 7xQ steam probe.
CONFIGURATION/STYLE
D Coaxial High Temp./High Pressure
R Coaxial Overfill Probe 3
⁄4" process connection
L Coaxial High Temp./High Pressure w/Flushing Conn. Dielectric range ≥1.4
or larger
M Coaxial Overfill Probe w/Flushing Conn.
N Coaxial Interface Probe w/Flushing Conn.
Q Coaxial Hot Water/Steam 2" process connection or larger
Dielectric range ≥10
S Coaxial Hot Water/Steam 3
⁄4" process connection
T Coaxial Interface or larger Dielectric range ≥1.4
B Twin Rod Standard
7 Twin Rod Flexible
5 Twin Rod Flexible Bulk Solid
2" process connection
F Single Rod Standard Dielectric range ≥1.9
or larger
G Caged Overfill 2", 3" or 4"
(hygienic 3⁄4" or larger)
J Single Rod High Temp./High Pressure Flexible Bulk Solid
1 Single Rod Flexible
2 Single Rod Flexible Bulk Solid Dielectric range ≥4.0
MATERIAL OF CONSTRUCTION
A 316/316L stainless steel
B Hastelloy C, Configuration/Style codes A, B, D, F, G, J, P, R and T only
C Monel, Configuration/Style codes A, B, D, F, G, J, P, R and T only
Hygienic, 316/316L stainless steel (20 Ra finish), Configuration/Style code F only,
E
Process connections codes 2P, 3P, 4P, 5P, 6P, and 9P only
PFA faced flange, 2" to 4", 150# to 300#, Configuration/Style code F only,
F
Process connection codes 43, 44, 53, 54, 63, 64, DA, DB, EA, EB, FA, and FB only
Hygienic, AL6XN stainless steel (20 Ra finish), Configuration/Style code F only,
G
Process connections codes 2P, 3P, 4P, 5P, 6P, and 9P only
Hygienic, Hastelloy C22, Configuration/Style code F only,
H
Process connections codes 2P, 3P, 4P, 5P, 6P, and 9P only
J 316/316L SST NACE Construction
K 316/316L stainless steel probe and process connection, ASME B31.1 specifications (model 7xS only)
N Enlarged coaxial probe, 316/316L stainless steel probe, 2" minimum process connection
P Enlarged coaxial probe, Hastelloy C, 2" minimum process connection
R Enlarged coaxial probe, Monel probe, 2" minimum process connection
V Optional PEEK™ spacers (for Model 7xD probe only)
W Optional Teflon® spacers (for Model 7xD probe only)
4 PFA insulated rod, 2" NPT process connection or larger, Configuration/Style code F only
LENGTH
Refer to page 63 for selections
22 1" BSP Thread ➀ 3P 1" or 11⁄2" Triclover® type, 16 AMP Hygienic Flange
41 2" NPT Thread ➂ 4P 2" Triclover® type, 16 AMP Hygienic Flange
42 2" BSP Thread ➂ 5P 3" Triclover® type, 16 AMP Hygienic Flange
6P 4" Triclover® type, 16 AMP Hygienic Flange
9P 21⁄2" Triclover® type, 16 AMP Hygienic Flange
Prb Mount Probe Mount The type of process mounting (NPT, Units The engineering units used to measure level in the system.
BSP or Flange) utilized in the installation. This aids in establishing The choices are in (inches) and cm (centimeters).
exact zero point for Guided Wave Radar Waveguide See Probe.
propagation and measurement.
<Window> A time slice variable that enhances system resolution.
QuickStart The essential information needed for the ECLIPSE (Factory setting).
transmitter and probe to be installed, wired, and calibrated.
ECLIPSE Guided Wave Radar transmitters may be protected by one or more of the following U.S.
Patent Nos. US 6,626,038; US 6,640,629; US 6,642,807. May depend on model.