INSTALLATION AND MAINTENANCE INSTRUCTIONS Web: www.mircom.com
MIX-4010 PHOTO ELECTRIC SMOKE DETECTOR
MIX-4010-ISO PHOTO ELECTRIC SMOKE DETECTOR
ABOUT THIS MANUAL INSTALLATION
This manual is included as a quick reference for installation. For fur- This detector must be installed on a ceiling or wall using a compatible
ther information on the use of this device with a FACP, please refer to base. SLC line and remote output connections for the most common
the panel’s manual. For more information regarding maintenance, base MIX-4001 are show in figure 2. A twisted pair cable should be
testing, spacing, and locating detectors, please refer to the LT-9420
used for the SLC line. If a shielded cabled is used, connect the
MIX-4000 series detector technical bulletin.
shields to the proper terminal on the base. Do not connect shields to
Note: This manual should be left with the owner/operator of this
equipment. earth ground. If a ground continuity wire is required by the local
DETECTOR DESCRIPTION code, it should be a separate conductor. Please note that shielded
The MIX-4010 smoke detector continuously checks air obscuration cables may reduce the SLC loop length that can be achieved due to
and reports it to the Fire-Alarm panel using a fully digital their high capacitance.
communication protocol. The MIX-4010 must be used with a Mircom The detector address should be programmed using the MIX-4090
series 4000 compatible control panel. Obscuration level is selected hand-held device before inserting the detector on the base.
at the Fire alarm panel through the Mircom configuration tool. It also Addresses 1 to 240 can be used for any device on a SLC loop. Each
has a remote output that can be controlled by the panel. Please see device on a loop must have a unique address.
specifications for compatible devices that can use the remote output A breakaway tab inside the base can be inserted in the outer rim of
feature. the base to visibly identify each detector with their address. See
figures 2 and 4. The detector can then be placed on the base using
Note: MIX-4010-ISO is equipped with a bi-directional short-circuit the following steps:
isolator to help protect against wiring faults that may otherwise result
in a loop failure." 1. Position the detector centrally on its adapter base ensuring it is
level.
Before installing this device please thoroughly read this manual and
refer to the applicable codes for guidance on location, spacing and 2. Rotate clockwise applying gentle pressure. The detector will drop
acceptable use. Also seek guidance from the compatible control into its keyed location.
panel instructions for the device operation modes and the 3. Continue to rotate clockwise a few degrees until the detector has
configuration requirements. fully engaged in the adaptor base.
Note: If the detector is used with the remote indicator, then the
voltage value of the detector must be at least 18V as the indicators 4. When the detector is firmly engaged, check the alignment of the
do not operate below 18V raised reference marks on the detector and on the base (figure 4).
FIGURE 1 DETECTOR FRONT:
IMPORTANT NOTES ON DETECTOR INSTALLATION
Disconnect loop power before installing the detector.
This detector comes with a dust cover to protect the device during
shipping and when first installed. It is not intended to provide com-
plete protection against contamination, therefore, detectors should
be removed from their base before construction, major re-decoration
or other dust producing work is started. Dust covers must be
removed before the system becomes operational.

Smoke detectors are not to be used with detector guards unless the
SPECIFICATIONS combination has been evaluated and found suitable for that purpose.
Normal Operating Voltage: 15 to 30VDC
Maximum Alarm Current (LED on): 3.2mA (LED on) When duplicate terminals are not provided to facilitate monitoring of
Standby Current: 160uA (LED flashing) the installation wiring connections, and there is no provision to pre-
Maximum Input Wiring Resistance: 40 Ohms vent looping an unbroken wire around or under a terminal, the word
Temperature Range: 32F to 100F (0C to 37.8C) "CAUTION" and the following or equivalent text in letters not less
Humidity: 10% to 93% Non-condensing than 2.38 mm (3/32 inch) high shall be included on the installation
Dimensions: 4 1/4” Diameter, 1 3/4” Height drawing: "FOR SYSTEM MONITORING - FOR TERMINALS "Loop
Mounting: 4” square by 2 1/8” deep box out (+)" AND "Remote Device (+)", DO NOT USE LOOPED WIRE
Accessories: MIX-4090 Programmer UNDER TERMINALS. BREAK WIRE RUN TO PROVIDE MONITOR-
MIX-4001/MIX-4002 Detector Base ING OF CONNECTIONS.
RA100Z Remote LED
Wiring range on all terminals: 22 to 12 AWG

LT‐6136 rev 1.1 7/16/19


FIGURE 2 DETECTOR WIRING:

FIGURE 3 LOOP WIRING:

FIGURE 4 ALIGNMENT MARKS:

Sensitivity Level Typical Note


Detector LED Colors
Level 1 2.0 %/feet Most sensitive level
Alarm Red (Steady on)
Level 2 2.5 %/feet
Air Sampling Green (Flash)
Level 3 3.0 %/feet
Fault Yellow (Steady on)
Level 4 3.5 %/feet Least sensitive level

LT‐6136 rev 1.1 7/16/19