10-3512-505-LS10-02 LaserSense 100 Installers Handbook
10-3512-505-LS10-02 LaserSense 100 Installers Handbook
10-3512-505-LS10-02 LaserSense 100 Installers Handbook
Certification
Certification body 0832
Manufacturer UTC CCS Manufacturing Polska Sp. Z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland
Authorized EU manufacturing representative:
UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH Weert,
Netherlands
Year of first CE marking 15
Declaration of Performance 360-3512-0199
number
EN 54 EN 54-20: 2006
Product identification See model number on product identification label
Intended use See DoP point 3
Essential characteristics See DoP point 9
Content
Important information 3
EN 54-20 and UL installation 5
Chapter 3 Commissioning 31
Introduction 32
Commissioning checklist 32
Precommissioning preparation 34
Acclimation period 34
Transport time verification 34
ASD System Performance Tests 34
Chapter 4 Troubleshooting 35
Troubleshooting the detector 36
Chapter 5 Maintenance 39
Introduction 40
Scheduled maintenance 40
Maintenance procedures 41
Index 47
Regulatory information
This equipment is Class III as defined in EN 60950 (i.e., this equipment is
designed to operate from Safety Extra Low Voltages and does not generate any
hazardous voltages).
As this equipment is part of a fire detection system, input power should be
supplied from an approved power supply conforming to EN 54-4 or UL/ULC and
FM3230 standards.
In order for the installation to conform to EN 54-20, pipes must conform at least
to EN 61386-1 Class 1131.
This product has been designed to meet the following requirements:
• NFPA 72 National Fire Alarm and Signaling Code
• UL 268 Smoke Detectors for Fire Alarm Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 864 Control Units for Fire Protective Signaling Systems
• CAN/ULC-S524 Installation of Fire Alarm Systems
• ULC S527 Control Units for Fire Alarm Systems
• CAN/ULC-S529 Smoke Detectors for Fire Alarm Systems
System reacceptance test after reprogramming (UL/ULC and FM3230): To
ensure proper system operation, this system must be retested in accordance with
NFPA 72 after any programming change. Reacceptance testing is also required
after any addition or deletion of system components, and after any modification,
repair, or adjustment to system hardware or wiring.
Limitation of liability
To the maximum extent permitted by applicable law, in no event will UTCFS be
liable for any lost profits or business opportunities, loss of use, business
interruption, loss of data, or any other indirect, special, incidental, or
consequential damages under any theory of liability, whether based in contract,
tort, negligence, product liability, or otherwise. Because some jurisdictions do not
allow the exclusion or limitation of liability for consequential or incidental
damages the preceding limitation may not apply to you. In any event the total
liability of UTCFS shall not exceed the purchase price of the product. The
foregoing limitation will apply to the maximum extent permitted by applicable law,
regardless of whether UTCFS has been advised of the possibility of such
damages and regardless of whether any remedy fails of its essential purpose.
Installation in accordance with this manual, applicable codes, and the instructions
of the authority having jurisdiction is mandatory.
Advisory messages
Advisory messages alert you to conditions or practices that can cause unwanted
results. The advisory messages used in this document are shown and described
below.
WARNING: Warning messages advise you of hazards that could result in injury
or loss of life. They tell you which actions to take or to avoid in order to prevent
the injury or loss of life.
Caution: Caution messages advise you of possible equipment damage. They tell
you which actions to take or to avoid in order to prevent the damage.
Note: Note messages advise you of the possible loss of time or effort. They
describe how to avoid the loss. Notes are also used to point out important
information that you should read.
Product Symbols
This symbol appears on the main board of the unit and indicates that the
board contains static sensitive components.
This label is located on the laser chamber at the bottom right of the open
detector and signifies that the unit is a Class 1 Laser product as specified
in IEC 60825-1. The unit incorporates a Class 3B embedded laser which
must not be removed from the detector, as retinal damage may result if
the laser beam enters the eye.
This symbol indicates the Safety ground studs. These are for grounding
cable screens, etc., and should not be connected to 0V or signal earth.
EN 54 -20 installation
Select Options > Calculate, or click on the calculator icon. The software will
prompt you to choose from Use set hole sizes, Best flow balance, and Max.
permissible transit time. Select the appropriate option and click OK. The results
for each pipe (View > Results) show calculations for each sampling hole on the
pipe with the nearest to the detector at the top of the screen, and the endcap
hole at the bottom.
For EN 54-20 compliance the transport time of the last sampling hole shall be
checked following all installation and proven to be less than or equal to that
determined by PipeCAD.
For the installation to comply with EN 54-20 Classes A, B, and C, each sampling
hole must be no less sensitive than 0.62% obs/m.
The calculation can be further refined by leaving a working detector in the
protected area for at least 24 hours at the intended alarm factor for the
installation (this could be done before or after installation). The detector
sensitivity can be read from the Sensitivity figure on the histogram screen of the
Remote Control software supplied with each detector. Click Options > Calculation
options to open the Hole calculation options dialog box. Enter the sensitivity
value obtained from the practical test, and then click OK. The new calculated
value will use the real sensitivity from the practical test.
The PipeCAD software will determine the classification of any used configuration.
Commissioning and periodic system tests must involve smoke tests to verify that
the system performs as expected and enters Fire 1 alarm within the time
determined by PipeCAD from the farthest hole. The detector sensitivity must also
be inspected to ensure it has not radically fallen from the installed figure. If it has
changed for any reason, the new figure must be re-entered into PipeCAD and the
recalculated hole sensitivities must be confirmed to be within the class limits
shown above. The settings of a compliant system should be recorded, as it is
possible by changing certain programmable functions to make the system
noncompliant. If functions are changed, it is recommended that the system is
retested if continuing compliance is in any doubt.
UL installation
Note: UL certified products may also contain additional approvals, e.g. FM3230.
Please refer to the product labels.
Summary
This chapter provides descriptions of the detector features, specifications, and
controls and indicators.
Content
Introduction 2
Available software for the detector 2
Specifications 2
Indicators 4
Inside the detector 5
Removable terminal block connections 6
Introduction
This detector is a highly sophisticated next generation high sensitivity aspirating
smoke detection product that provides all the benefits of air sampling high
sensitivity smoke detection, including very early warning. Designed for easy
installation and commissioning, the detector incorporates a patented artificial
intelligence known as ClassiFire, which allows the detector to configure itself to
optimum sensitivity, alarm thresholds, and minimum nuisance alarms for various
environments.
The detector operates by drawing air from a protected space via a supervised
piping network in relatively small areas. The sampled air is passed through a
dust separator (filter) to remove dust and dirt before entering the laser detection
chamber. State-of-the-art electronics are used to analyse the sampled air and
generate a signal representing the level of smoke present.
ClassiFire intelligence also monitors the detector chamber and dust separator for
contamination, continually adjusting the appropriate operating parameters to
counteract the negative effects of any contamination. Aspirating smoke detectors
are unique in being able to provide a consistent level of protection in a very wide
range of environments by continuously making minor adjustments to sensitivity.
Specifications
Caution: This equipment is only to be used in accordance with these
specifications. Failure to operate the equipment as specified may cause damage
to the unit, injury, or property damage.
Table 1: Specifications
Specification Value
SELV rating (EN 60950) Class III
Supply Voltage 21.6V to 26.4VDC
PSU Type: conforming to EN 54-4
Electrical safety complies with BS EN 610190-1
Size 300 W x 220 H x 90 D (mm) 11.8 W x 8.6 H x 3.5 D (in.)
Weight 3.8 kg (8.4 lbs.) with docking station
Operating temperature range −10 to +60ºC (EN 54-20)
32 to 100°F (0 to 38°C) (UL 268, CAN/ULC-S529, FM3230)
Operating humidity range 0 to 90% noncondensing
BS EN 61010-1 Pollution degree 1
BS EN 61010-1 Installation Cat. II
Sensitivity range
(%obs/ft.) Min. = 7.62%, Max. = 0.00914% FSD
(%obs/m) Min. = 25%, Max. = 0.03% FSD
Maximum sensitivity resolution 0.0015% obs/m (0.00046% obs/ft.)
Detection principle Laser light scattering mass detection
Particle sensitivity range 0.0003 µm to 10 µm
Current consumption 400 mA
Relay contact rating 500 mA at 30 VDC
Maximum sampling pipe length 100 meters (330 feet) total
Sampling pipe inlets 2
Sampling pipe internal 3/4 in. (ID) or 27 mm (OD)
diameter
Alarm levels 4 (Fire (Alarm) 2, Fire (Alarm) 1, Pre-Alarm and Aux)
1 relay as standard, others available
Chamber service intervals Greater than 8 years (depending on environment)
Dust separator (filter) Greater than 5 years (depending on environment)
replacement intervals
Laser lifetime (MTTF) Greater than 50 years
Programming PC via RS-232 or RS-485
Data bus cable RS-485 data cable
Data bus length 1.2 km (3/4 mile)
IP rating IP50
Indicators
Figure 1 below shows the three indicators on the detector.
(1)
(2) Alarm
Fault
(3)
OK
(1) Alarm: Illuminates when the alarm level has been reached and the appropriate time delays
have expired.
(2) Fault: Illuminates when the unit has a fault and a fault signal is being sent to the fire alarm
panel. It also illuminates when the unit is isolated.
(3) OK: Illuminates to show normal operation when there are no faults. The OK lamp will flash
during the 15-minute FastLearn period when the detector is first learning about its
environment.
(1)
Summary
This chapter provides information necessary to install and configure the detector
system.
Content
Introduction 8
Antistatic precautions 8
General installation guidelines 10
Docking station 10
Application 11
System design 12
Below or above the ceiling installations 14
Installation 17
Mechanical installation 17
Removing the front cover 17
Electrical installation 17
Relay connections 20
Interfacing with fire alarm panels 21
Connecting the detector to an APIC 22
Setting the detector address 23
Address table 23
Connecting the detector to a SenseNET/RS-485 detector network 25
Final installation 26
Removing the detector 26
Configuring the detector after installation 27
List of programmable functions 28
Connecting to a PC 29
Event log 30
Introduction
This topic provides information necessary to install the detector system.
Antistatic precautions
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits. This recommendation must be
followed when removing the equipment case, and during installing and servicing.
Docking station
The basic principle behind installation of the detector is that all wiring and
pipework is installed using a docking station. This is a convenient feature which
means that the detector can be dismounted or replaced without disturbing any
wiring or installed pipework.
The docking station inlet (sampling) ports and exhaust port is used to interface
with the pipe network. The inlet ports are used for aspirating the pipework
network. The exhaust port allows the detector exhaust air to be routed back to
the sampling area, when differing atmospheric pressures require this. Refer to
Figure 4 on page 11.
Application
The detector is intended to provide small area incipient fire detection. This means
that it is suitable for the substantial range of applications typified by small
compartmentalised rooms, warehouse racking, or pieces of electronic or
electromechanical equipment where it is desirable to achieve individual incipient
fire reporting. In compartmentalised rooms, each compartment would normally
use an individual aspirating detector.
The detector is not intended to protect large areas, or to sample from areas
where there may be any difference in airflow rates or pressure differentials. If
detection in environments conforming to these descriptions is required, other
type detectors should be used.
System design
Simple designs with short sampling pipes produce the best results. Complex
sampling pipe runs should be avoided with the detector. The use of
T-branch pipes is not recommended. The detector is fitted with two sampling pipe
inlets as standard. It is always preferable to use two shorter pipes as opposed to
one longer pipe. If two sampling pipes are used, care should be taken to keep
the sampling pipe lengths and number of sampling holes on each pipe within
10% of the other. This can be verified using the PipeCAD system design
software. Unused sampling pipe inlets should be fitted with pipe bungs.
Maximum length of sampling pipe used with the detector is 100 m in still air with
20 sampling holes (or Capillary Remote Sampling Points). This will provide a
transport time from the end of the sampling pipe within 120 seconds. If the
protected area has airflow present, the maximum permitted sampling pipe length
will be reduced. In order for the installation to conform to EN 54-20, pipes must
conform at least to EN61386-1 Class 1131.
Note: PipeCAD pipe modeling software must be used when designing a pipe
network and verifying its performance. Refer to the PipeCAD System Design and
Installation User Manual or complete instructions on how to design and install an
air sampling pipe network.
Always locate the sampling points in positions to which smoke may reasonably
be expected to travel. For example, do not expect ceiling mounted sampling
points to operate satisfactorily if air flow from air-conditioning systems keeps the
cool smoke from an incipient fire from reaching ceiling level. In this instance, it is
usually better to locate the sampling pipe directly in the airflow (for example,
across the return air register of an air conditioning unit).
Note: There is no substitute for carrying out smoke tests prior to installation of
pipework to indicate suitable sampling point location.
No more than two air handling units may be protected with one detector. In this
application, ensure that the sampling pipe is raised clear of high velocity air in the
immediate vicinity of the air intake grill on standoff posts as shown in Figure 5. 95H
Figure 6: Installation of pipework above ceiling with exposed detector (piped exhaust)
(1) (2)
(5)
(4)
(3)
Figure 7: Installation of pipework above ceiling with detector mounted in ceiling void (no
exhaust piping)
Installation
Mechanical installation
The docking station is connected to the installed sampling pipework and fixed to
the mounting surface using three screws of a type appropriate to the mounting
surface. Ensure that the sampling and exhaust pipes are securely seated in the
pipe ports before securing. If using a piped exhaust docking station, be sure that
the sampling and exhaust pipes are fitted into the relevant ports as shown in
Figure 4 on page 11.
104H 105H
Electrical installation
The detector is supplied with removable terminal blocks (Refer to Figure 3 on 106H 107H
page 6). These may be removed from their sockets by lifting them up at right
angles to the circuit board.
Take note of the orientation of each terminal block and its function before
removing it. It may also be beneficial to mark the connection wires with suitable
identification labels or colored rings to aid in the connection process.
Each detector is supplied with three RF suppression ferrite rings. To ensure
compliance with all relevant EMC requirements, the conductors of each cable
should be wound once around a ferrite as shown here before entering the
relevant connector.
Note: Both power conductors and relay conductors should be on a separate
ferrite, but different forms of signal conductor (e.g. RS-485) can share the same
ferrite.
There should be about 30 mm (1-1/4 in.) of wire between the end of the ferrite
and the terminal block to give adequate stress relief. To achieve this, it is
necessary to strip back the cable screen approximately 130 mm (5 in.). The
screen should be terminated under the cable gland cap as shown in Figure 8. 71H
Signal connections
(1) (2)
For example, in a networked system using screened cable, connect the screen
wires to the SCN terminal, Bus A wires to the A terminal and Bus B wires to the B
terminal.
If the detector is in the middle of a networked chain (with input and output
connections) it may be more convenient to link the common Bus A, Bus B, and
screen wires to single A, B and screen wires for linking to the terminal block.
Figure 11 below shows the power and signal connections to the docking station
for connection to a single network cable.
(1) Power supply shielded wire to ground stud (5) RS-485/SenseNET Bus shielded wire
(2) Power supply 0V wire (6) RS-485/SenseNET Bus A wire
(3) Power supply +24V wire (7) RS-485/SenseNET Bus B wire
(4) Wire from earth terminal to ground stud
Relay connections
The detector includes an Fire (Alarm) relay (corresponding to the Fire 1 alarm
level), which closes on alarm, and a general Fault relay, which opens on any fault
condition or on power-down (see Figure 12 on page 21). The relays are of the
volt-free type, with a maximum current capacity of 500 mA at 30 VDC. Connect
the screen of the relay cables to the ground stud of the detector.
(1) (2)
The interface is set to a single address mode, the card appears as a single
address on the SLC, and the detector status is read from that address.
(1)
(3)
(2)
Address table
Addresses chosen for detectors do not have to be consecutive or in a given order
so long as they are all different. Table 3 on page 24 provides the address table
12H 12H
for detectors.
53 1 0 1 0 1 1 0 0 118 0 1 1 0 1 1 1 0
54 0 1 1 0 1 1 0 0 119 1 1 1 0 1 1 1 0
55 1 1 1 0 1 1 0 0 120 0 0 0 1 1 1 1 0
56 0 0 0 1 1 1 0 0 121 1 0 0 1 1 1 1 0
57 1 0 0 1 1 1 0 0 122 0 1 0 1 1 1 1 0
58 0 1 0 1 1 1 0 0 123 1 1 0 1 1 1 1 0
59 1 1 0 1 1 1 0 0 124 0 0 1 1 1 1 1 0
60 0 0 1 1 1 1 0 0 125 1 0 1 1 1 1 1 0
61 1 0 1 1 1 1 0 0 126 0 1 1 1 1 1 1 0
62 0 1 1 1 1 1 0 0 127 1 1 1 1 1 1 1 0
63 1 1 1 1 1 1 0 0
64 0 0 0 0 0 0 1 0
It is easy to join the input and output wires for each bus and screen connection
together and to solder or crimp a single wire or connecting ferrule to each wire
pair so that they are easier to fit into the screw terminals. If this is performed, it is
recommended that bare wire joints be insulated to prevent possible shorting of
the data bus, which will cause a drop-out of data on the SenseNET bus.
In the example shown in Figure 15 on page 25, there could be a total length of
124H 125H
RS-485 cable of up to 1.2 km (3/4 mile) between the command module and
detector 3, since these are all on a single bus. However, detector 3 is a HSSD-2
which has a second communications bus (RS-485 bus 2) and an RS-485
repeater. This allows a further total of 1.2 km (3/4 mile) of cable until the next
HSSD-2 in the RS-485 loop.
In the example shown in Figure 15, if detectors 4-126 (not shown) are all this
126H
type of detector, then the total length of wiring between Detectors 3 and 127
would be limited to 1.2 km (3/4 mile). However, each additional HSSD-2 detector
wired up using both RS-485 buses would allow an additional1.2 km (3/4 mile) of
cabling to be added to the RS-485 loop.
Final installation
Once the power and signal connections are made, slide the detector body up into
the docking station and fasten it into position using the M4 pan head screws
provided. Slot the power and signal terminal blocks into the relevant sockets on
the detector PCB (which will only click fully home in the correct orientation).
Lastly, replace the detector cover using the six pan head screws provided. Refer
to Figure 16.
130H
Note: The detector is designed solely for operation with the front cover securely
fitted using all six fixing screws.
SenseNET
The SenseNET software is available for purchase. SenseNET software can
configure and manage a large network of detectors with a simple,
streamlined graphical user interface from a computer connected to a detector
or command module via an RS-232 serial cable or RS-485 converter interface.
Complete instructions on how to install, launch and use the SenseNET software
are provided in the SenseNET Software User Manual under separate cover.
Note: Since the detector does not include a front panel display or keypad,
programmable functions cannot be accessed via the unit itself.
Connecting to a PC
To connect a single stand-alone detector to a PC, connect the PC’s serial port
directly to the detector’s 9-way RS-232 port. Connections for this cable are
shown in Figure 17 below.
Figure 18 shows the RS-232 cable connection from the detector to a PC.
Event log
The Event Log is a record of detector events such as faults, alarms and function
changes. It is stored inside an operating detector and is updated whenever an
event occurs. The event log is nonvolatile, which means that it is retained when
the detector is turned off. The last 200 detector events may be stored.
An event is defined as:
• A change to any programmed function
• A signal received from an external controller such as the remote software,
APIC, or SenseNET
• A detector output level meeting or exceeding the Pre-Alarm, Aux, Fire 1, or
Fire 2 alarm thresholds
• A start of day or night operation
• Demonstration Mode start
• FastLearn start or stop
• Power on or off
Events can either be viewed on a PC screen or downloaded to disk by running
the Remote Control program.
When the detector event log is full (200 events have been logged) and a new
event occurs, the oldest event in the log is deleted (first-in, first-out).
To download the event log, connect a PC to the detector serial port and run the
Remote Control software or SenseNET programs. For details, see the Remote
Control Software User Manual or the SenseNET Software User Manual.
Summary
This chapter provides information to commission the detection system.
Content
Introduction 32
Commissioning checklist 32
Precommissioning preparation 34
Acclimation period 34
Transport time verification 34
ASD System Performance Tests 34
Introduction
This chapter covers the commissioning procedures for the detector.
Commissioning strategy initially depends upon the environment in which the
detector is installed. For instance, the test for a computer room (in a relatively
clean environment) would be very different from, say, a flour mill, with a high
level of airborne particulate content.
A widely accepted standard for computer rooms or EDP areas is British Standard
BS6266, equipment overheating at a stage well before combustion. To perform
the test electrically overload a 1‑metre length of PVC insulated wire of 10/0.1mm
gauge for one minute using an appropriate power supply. The detector has two
minutes from the end of the wire burn to give an alarm indication.
For areas with higher levels of background particulate matter testing
methodology would be similar to that of standard point detectors.
Commissioning should only be done by factory-trained technicians in accordance
with applicable standards.
Commissioning checklist
The following brief checklist allows quick setup of the detector. This procedure
will be adequate for most standard installations.
7. Set an appropriate alarm factor, as shown in Table 4 below, for the protected
15H 152H
environment on the Alarm levels and delays tab. The detector will
automatically perform FastLearn for the new alarm factor (takes
approximately 15 minutes). The OK indicator on the front panel will begin to
flash. If using Day/Night switching, check that the Day Start and Night Start
times reflect site operations.
8. While the detector is still in FastLearn mode, place a checkmark next to the
Demo mode command at the bottom of the Alarm levels and delays screen.
The detector will enter demo mode (where it estimates its final sensitivity)
immediately after the FastLearn cycle has finished.
Note: Checking the Demo mode box only puts the detector into demo mode
while the detector is performing a FastLearn. It has no effect at any other
time.
9. Verify that the FastLearn has concluded (the OK indicator has stopped
flashing). With the detector in demo mode, perform any necessary smoke
tests, ensuring that the detector reacts appropriately, and let the smoke fully
dissipate.
10. Perform another FastLearn, this time NOT putting the detector into demo
mode. Do this by placing a checkmark next to the FastLearn Enable
command in the Alarm levels and delays screen. The OK indicator on the
front panel will begin to flash.
11. The detector will generate no alarms during the 15 minute FastLearn period
and, after this, the detector will operate at a reduced sensitivity for 24 hours
while ClassiFire acclimates to the protected environment and sets up
appropriate day and night sensitivity settings.
12. If desired, exit the Remote Control software or SenseNET software, power
down the PC and remove it from the detector serial port.
Precommissioning preparation
Commissioning should be performed after all construction has been completed
and cleaned of any lingering post-construction dirt. If ambient monitoring
conditions are recorded before the installation is cleaned up, they may not
accurately reflect actual normal operating conditions that need to be used as
reference data for follow-up maintenance procedures and tests.
Acclimation period
The detector will operate at a reduced sensitivity for 24 hours. ClassiFire will set
up the appropriate day and night sensitivity settings. All air handling units,
thermostats and other systems that can have an effect on the operating
environment should be turned on to simulate normal operating conditions as
closely as possible. After approximately one week of monitoring time (depending
on chart log recording rate), download the detector event log to a PC from the
RS232 port using a serial cable.
Caution: Oil-based canisters that are used to test point detectors are not suitable
for testing aspirating systems, as the particulate is heavy and tends to drop out in
the pipe, never actually reaching the detector. Also, the oily residue that is left
behind may affect the functionality of the detector.
Chapter 4
Troubleshooting
Summary
This chapter provides information to troubleshoot the detection system.
Content
Troubleshooting the detector 36
Summary
This chapter provides scheduled and unscheduled maintenance procedures.
Content
Introduction 40
Scheduled maintenance 40
Maintenance procedures 41
Visual check 41
ASD System Performance Tests 41
Transport time verification test 41
Detector sensitivity test 41
Cleaning the detector 42
Replacing the dust separator cartridge 42
Introduction
This chapter contains maintenance instructions for the detection system. These
procedures should be performed on a scheduled basis. In the event that system
problems are found during routine maintenance, refer to Chapter 4 170H
“Troubleshooting” on page 35. Failure to properly maintain the system may affect
17H 172H
Scheduled maintenance
The scheduled maintenance of the system should be performed at an
established interval. The interval between performance of maintenance
procedures should not exceed any imposed regulations. (See NFPA-72 or other
local requirements.)
Local standards and specification requirements must be adhered to. A typical
maintenance plan is listed in Table 6 below.
Notes
It is prudent to disconnect or isolate the detector from the fire panel during
maintenance to prevent unintentional alarm activations.
The detector should be powered down during internal cleaning (use an air duster
can or dry air gun).
Table 6: Maintenance plan
Step Procedure
1 Check detector, wiring and pipework for damage
2 Check original design is still valid, e.g. changes due to building upgrades
Maintenance procedures
The following paragraphs outline general scheduled maintenance procedures to
be performed on an “as necessary” basis.
Caution: Risk of equipment damage. Always turn the power off before servicing
the detector.
Visual check
The visual check must be performed every six months. This check is to ensure
pipe network integrity.
To perform the visual check, observe the entire piping network and check for
abnormalities in the pipes, including any breaks, blockages, crimps, etc.
Caution: Do not use solvents to clean the detector. Use of solvents may cause
damage to the detector.
°C Degrees centigrade
°F Degrees Fahrenheit
A Ampere
AC Alternating current
ADA Americans with Disabilities Act
AH Ampere hour
AHJ Authority having jurisdiction
ARC Automatic release circuit
AWG American wire gauge
APIC Addressable protocol interface card
CSFM California State Fire Marshal
DACT Digital alarm comm. transmitter
DC Direct current
DET Detector
EOLD End of line device
EOLR End of line resistor
FM Factory Mutual
FSD Full scale deflection
ft. Feet
HSSD High sensitivity smoke detector
Hz Hertz (frequency)
in. Inches
LCD Liquid crystal display
LED Light emitting diode
MEA Materials and Equipment Acceptance
Division of the City of New York
NAC Notification appliance circuit
N.C. Normally closed
NEC National Electrical Code
NFPA National Fire Protection Association
N.O. Normally open
signal connections, 19
A Software
available software, 2
Acclimation period, 34 Specifications, 2
Addressing System design, 12
Address table, 23
Setting the detector address, 23
T
Advisory messages, 4
Application, 11 Terminal blocks, 6
ASD System Performance Tests, 34 Transport time verification, 34
C
Commissioning, 32
D
Detector components, 5
Docking station, 10
E
Event log, 30
I
Installation, 10
Electrical, 17
Mechanical, 17
Interfacing with fire alarm panels, 21
M
Maintenance, 41
Cleaning the detector, 42
Replacing the dust separator (filter), 42
P
Power supply connections, 18
Programmable functions, 28
R
Relays, 20
S
SenseNET
Connecting, 25