Manual Stratos Micro 100
Manual Stratos Micro 100
Manual Stratos Micro 100
,QVWDOOHU¶V+DQGERRN
LM 80024 • Issue 12
Introduction 3
1. Indicators 4
5. Design Limitations 20
6. Installation 24
7. Interfacing 28
8. Event Log 33
9. Commissioning 35
10. Maintenance 36
11. Troubleshooting 39
Page 2
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
Introduction Stratos-Micra 100® is a highly sophisticated ‘next generation‘ of High Sensitivity
Aspirating Smoke Detection product that has been designed to ensure that installation
and commissioning is as simple as possible, while optimising performance.
Stratos-Micra 100 incorporates a patented ‘artificial intelligence‘ known as ClassiFire®,
which allows the detector to configure itself to optimum sensitivity, alarm thresholds
and minimum nuisance alarms for any environment.
ClassiFire intelligence also monitors the detector chamber and dust separator
for contamination, continually adjusting the appropriate operating parameters to
counteract the negative effects of such contamination.
0832
The Stratos range of detectors is unique in being able to provide a consistent level
Kidde Products Limited of protection in a very wide range of environments by continuously making minor
Unit 2 Blair Way Dawdon adjustments to sensitivity.
City: Seaham, County Durham
SR7 7PP, UK The Stratos range of detectors has proven its worth many times by detecting ‘difficult-
09 to-detect‘ slow growth electrical overload incipient fires in ‘difficult‘ environments.
0832-CPD-0982 This handbook gives information likely to be needed for most installations, but for
more detailed information on subjects such as Fresh Air Referencing, please refer to the
EN54-20: 2006 complete Technical Manual or System Design Guide.
Aspirating smoke detectors This equipment is Class 111 as defined in EN60950 (i.e., this equipment is designed
for fire detection and fire alarm to
systems for buildings operate from Safety Extra Low Voltages and does not generate any hazardous
Class A, B and C voltages).
This symbol appears on the main board of the unit and indicates that the board
contains static sensitive components. Suitable anti-static precautions must be taken
when handling the board.
This label is located on the laser chamber and signifies that the unit is a Class 1 Laser
LASER CLASS 1 product as specified in IEC 60825-1. The unit incorporates a Class 3B embedded laser
PRODUCT which must not be removed from the detector as retinal damage may result if the laser
beam enters the eye.
This symbol indicates the Safety Earth stud (see section 6.2.1). This is for grounding
cable screens and should not be connected to 0V or signal earth.
Kidde Products Ltd. has taken every care to ensure that Stratos-Micra 100 is as simple to
install as possible but in case of difficulty, please contact our Help Line to ensure trouble
free installation and operation.
HELP LINE Kidde Products Ltd. takes no responsibility for damage or injury occasioned as a result of
(+44) (0) 1844 265004 failing to install or operate the equipment in accordance with these instructions.
Page 3
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
1. Indicators
1 Fire indicator illuminates when the alarm level has been reached and the
appropriate time delays have expired.
2 Fault. Illuminates when the unit has a fault and a fault signal is being sent
to the fire alarm panel.
3 OK. Illuminates to show normal operation when there are no faults. The OK
lamp will flash during the 15 minute Fastlearn™ period when the detector
is first learning about its environment.
Page 4
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
2. Inside the
Detector
Page 5
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
2.2 Detector
terminal block
connections
3 4 5
Page 6
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
3 Programming The Stratos-Micra 100 may be programmed from a PC when connected to the detec-
the Detector tor via a standard 9-pin serial lead connected to the serial port of the computer and
the 9 way socket at the base of the detector (see section 7.4, ‘Connecting to a PC’).
In order to do this, it is necessary to install the remote control software onto the com-
puter. A copy of the remote control software is contained on a disk supplied with each
detector. Install the software in accordance with the on-screen instructions. To open
the software, select “Start ➔ Programs ➔ AirSense ➔ Remote x” (where x is the version
of software installed). Access the drop-down list to the right hand side of the toolbar.
This defaults to “Detector 001”. Scroll down this list to select the detector number
corresponding to the connected detector’s address number if the address is other then
the factory default setting of 1 (see section 7.1).
The programmable functions are all accessed though the “Options ➔ Detector set-
tings” submenu or by clicking on the detector symbol in the remote software toolbar
as indicated below.
The software will display a prompt for the detector’s access code (see section 3.33).
The default access code is 0102. When the correct code is entered, the programmable
functions may be accessed and amended as required.
This window contains all the programmable functions for the Stratos-Micra 100.
To amend one of the programmable functions, go to the relevant tab in the “Function
settings” window, make the change and then click “OK”. This will save the change to
the detector’s internal memory.
A list and explanation of the various functions is given overleaf, with the functions
grouped by the tab under which they appear.
NB ☞ NB: Users should be aware that using settings other than those given in section
5.2 may alter the performance of the detector from that tested for EN54-20 or
UL238.
Page 7
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
3.1 Time and date – Time and Date tab
It is important that the time and date be set up correctly on the controller’s internal
calendar/clock because it uses this information to store events in the event log. See
section 8, “Event log” for more details. Unless specially ordered, units are supplied with
the correct setting for UK time. This is backed up with a rechargeable battery. Later
adjustments to the clock setting should not exceed ± 70 minutes unless a FastLearn is
initiated
3.2 Alarm levels - Alarm levels and delays tab, Level subgroup
The value set in the Fire, Pre-Alarm and Aux functions in the Level subgroup is
the relatively scaled bargraph level at which the appropriate alarm is initiated on the
detector. The Fire 2 level assigns an absolutely scaled alarm level in % obs/m.
The Aux level is set by factory default at level 10 which means that this alarm will occur
after the Fire alarm. The default level settings for Pre-Alarm and Fire 1 are 6 and 8
respectively. The default setting for Fire 2 is 20% obs/m.
3.3 Alarm delays - Alarm levels and delays tab, Delay subgroup
The alarm delay is the number of seconds that an alarm level has to be continuously
sensed before the alarm is initiated. Each alarm level has a programmable delay of
between 0 and 90 seconds. The default delay for each alarm level is 5 seconds.
Page 8
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
The following table gives suggested settings of ClassiFire alarm setting for different locations
Alarm Probability of
Sensitivity
Factor Nuisance Alarm
0 Extremely High Once per year Semiconductor manufacturing clean room
Suggested Protected Area
1 Once per 5 years Computer room
2 Once per 10 years Non-smoking office
3 Once per 50 years Clean factory
4 Medium Once per 1000 years Warehouse
5 Medium Once per 5,000 years Warehouse with diesel trucks operating
6 Medium Once per 10,000 years Warehouse with diesel trucks operating
7 Low Once per 20,000 years Warehouse with diesel trucks operating
8 Low Once per 100,000 years Warehouse with diesel trucks operating
Page 9
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
3.9 ClassiFire 3D - Alarm levels and delays tab
If this function is ticked, then the detector will ignore any pre-set time delays in the
event of a rapid increase in smoke density, thereby minimising response time to 'rapid
growth' fires. This function would normally only be used where there were long time
delays programmed on the alarm levels. This function is disabled by default.
Page 10
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
3.14 Remote Reset – Alarm actions tab, Remote input subgroup
This function allows latching alarms or faults (see sections 3.17 and 3.18) to be
remotely reset when the relevant activating terminals are shorted together by volt-free
contacts.
When the function is enabled, entering a value of 01, 02 or 03 to the numeric field to
the left of the tick-box assigns the “I/P 1”, “I/P 2” or “I/P 3” terminals of a connected
relay/input card respectively as the activating terminals.
Remote terminals 4 and 5 are retained for future expansion.
Note: This function is only available via the optional Input/Relay Card. This board
is fitted in the same manner as an APIC card (see section 7.3). Only a single
expansion port is available, so an APIC card cannot be fitted at the same time as
an Input/Relay card.
Page 11
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
3.19 Cascading alarms – Alarm actions tab
Ticking this function box means that only when the detector has gone into Pre-Alarm
does it start counting down the main Fire delay i.e. the time delays on Pre-Alarm and
Fire 1 are cumulative. The Aux alarm is not included in the cumulative delay since it
may be set to a higher level than either the Pre-Alarm or Fire 1 levels. This function is
enabled by default.
Page 12
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
3.28 Reference back-off – Referencing tab
This value is the delay time between a build up of pollution being seen by the reference
(if used) and the pollution being seen by the detector. The default value is 15.
Page 13
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
3.33 Access code – Miscellaneous tab
This is the access code required to amend programmable parameters. The default code
is 0102. Once the appropriate code is entered it may be changed here to any four digit
number to limit unauthorised access.
In the above table the grayed section indicates flow rate recording while the white sec-
tion indicates detector and alarm level recording.
At the slowest recording rate, one month of data can be recorded. The factory default
setting is 8.
Page 14
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
3.35 Separator condition – Miscellaneous tab
The value given at this function is the efficiency rating of the dust separator element in
the detector as a percentage of the efficiency of a clean separator. A new element will
give a reading of 99 in this function. When the efficiency has decreased to 80%, the
Fault indicator LED will illuminate and the event log will show “Separator renew”.
Note - After fitting a new element, it will be necessary to start a FastLearn to reset the
separator condition reading (see section 3.7).
This function defaults to “--“, which means that a separator fault will only appear
when the efficiency decreases to 80% (see 3.35, “Separator condition”). However, a
date may be entered into this function to allow for a scheduled maintenance period.
The detector will then generate a separator fault at the planned time regardless of the
condition of the separator, although degradation of the separator to below 80% effi-
ciency before this date will override this.
See section 10, “Maintenance” for further details.
Enabling this function will reset each programmable function to the default value indi-
cated in the text, where a default setting is specified. It will also put the detector into
FastLearn mode, regardless of whether or not Auto Fastlearn is enabled (see section
3.8). This ensures that the flow setups and alarm thresholds are optimised to the detec-
tor’s working environment after resetting. It should be noted that where a ClassiFire
alarm factor other than the default is required for the protected area, this will need to
be re-entered. Section 3.5 gives details of the ClassiFire alarm factors.
Page 15
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
4.2 Histogram screen
The histogram screen shows various aspects of the detector function. To enter the his-
togram screen, either select the menu options “View ➔ Histogram viewer…” or click
the symbol indicated below.
Smoke density
histogram
Alarm flags
There are two types of smoke density histogram; one shown in blue (the “fast” histo-
gram) which updates every 15 minutes, feeding information to the long-term “slow”
histograms (which appear in yellow). These set the detector sensitivity based on the
ambient smoke conditions and it takes 24 hours for the two slow histograms (the
“day” and the “night” histograms) to complete their learning phase (see section 3.7).
Detector sensitivity is based on the fast histogram during FastLearn and is thereafter
based on the currently active slow histogram. However, although the positions of the
alarm flags are based on the slow histogram, sudden changes in smoke density are
picked up by the fast histogram so that early warning is given.
Page 16
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
Sensitivity: The current absolute sensitivity of the detector in percentage obscura-
tion per metre (% obs/m)
Mean: The current mean value of smoke density, taken from the currently “active”
histogram and given as a percentage of full scale deflection.
Variance: The “spread” of data in the currently “active” histogram and given as a
percentage of full scale deflection.
FastLearn: If the detector is currently in FastLearn mode, this will show the number
of minutes remaining in the FastLearn period. When this period has elapsed it will read
“OFF”.
Alarm factor: This is the ClassiFire alarm factor (see section 3.5, “Alarm factor”)
Day/night: This indicates the currently active slow histogram
Alarm levels: These figures give the position of the various alarm flags in terms of a
percentage of full scale deflection.
Detector output: This shows the real-time variation in background smoke levels in
terms of a percentage of full scale deflection.
The chart recording function shows how smoke density in the protected area has var-
ied over time. The chart may be downloaded to disk or printed out from a connected
printer.
To access the chart log, select the menu options “View ➔ Chart recording…” or click
the symbol indicated below.
Page 17
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
The following screen appears:
The red trace is the current alarm level and the black trace is the detector output. By
moving the cursor along the chart, the “Chart information” window (shown at the
bottom left) updates to show the date and time, detector level and alarm level of the
relevant period. The ‘File’ menu option in the chart recording window allows the chart
recording to be saved to disk or printed to a connected printer, and allows a previously
saved chart recording to be loaded. Chart recording files have the extension “.rcw”.
Where a custom set of programmable function settings is commonly used, these may
conveniently be saved to or loaded from disk. To open a detector function settings
(.dfs) file, select the menu options “File ➔ Open” or click on the symbol indicated
below.
Page 18
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
Click on the “List files of type” drop-down box and select “Detector settings (*.dfs)”
as indicated below.
A list will appear of all detector settings files stored on the current drive. As a special
case, if desiring to recall the factory default settings, there is a file named ‘default.
dfs’ in the ‘remote2k’ directory. Loading this file will reset the detector to the factory
default.
Page 19
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
5. Design Stratos-Micra 100 is intended to provide LOCALISED incipient fire detection only.
Limitations This means that it is suitable for the substantial range of applications typified by;
small non-compartmentalised rooms, warehouse racking, or pieces of electronic or
electromechanical equipment where it is desirable to achieve individual incipient
! fire reporting. In compartmentalised rooms, each compartment would normally use
individual Stratos-Micra 100 or Stratos-Micra 25 detectors.
IMPORTANT
This product employs a very low-power aspirator and the aspirating capability of the
Stratos-Micra 100 detector is limited accordingly. Stratos-Micra 100 is NOT intended
to protect large areas, or to sample from areas where there may be any difference
in airflow rates or pressure differentials. Application of Stratos-Micra 100 in these
circumstances is not recommended. If detection in environments conforming to these
descriptions is required, alternative versions of Stratos products should be used.
Maximum length of sampling pipe used with the Stratos-Micra 100 detector is 100
metres in STILL AIR with 25 sampling holes (or Capillary Remote Sampling Points). This
will provide a transport time from the end of the sampling pipe within 120 seconds. If
the protected area has airflow present, the maximum permitted sampling pipe length
will be reduced. In areas or applications where the airflow rate exceeds 1 metre per
second, maximum sampling pipe length is reduced to 40 metres.
In order for the installation to conform to EN5420, pipes must conform at least to
EN61386-1 Class 1131.
Stratos-Micra 100 is available with an optional ‘Piped Exhaust’ type Docking Station
(see illustration ‘A’ overleaf). This is primarily intended to allow the detector to sample
from areas which may be at different air pressure to the detector location. Typical uses
are for air-duct sampling and allowing the installation of the detector in under-floor or
ceiling voids or when sampling from pieces of computer related equipment.
Page 20
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
(A.) Above ceiling
sampling with exposed Sampling hole
detector
False ceiling
Exhaust pipe
Stratos-Micra 100
Sampling pipe
False ceiling
Stratos-Micra 100
Page 21
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
5.1 System Design Simple designs with short sampling pipes produce the best results. Complex sampling
pipe runs should be avoided with the Stratos-Micra 100 detector. The use of ‘T’
branch-pipes is not recommended. The Stratos-Micra 100 detector is fitted with two
sampling pipe inlets as standard. It is always preferable to use two shorter pipes as
opposed to one longer pipe. If two sampling pipes are used, care should be taken to
keep the sampling pipe lengths and number of sampling holes on each pipe within
10% of the other. This can be verified using the PipeCAD system design software.
Unused sampling pipe inlets should be fitted with pipe bungs.
Always locate the sampling points in positions to which smoke may reasonably
be expected to travel. Do not expect ceiling mounted sampling points to operate
satisfactorily if air flow from air-conditioning systems keeps the cool smoke from an
incipient fire reaching from reaching ceiling level. In this instance it is usually better
to locate the sampling pipe directly in the airflow (for example across the return air
register of an air conditioning unit).
There is no substitute for carrying out smoke tests prior to installation of pipe work to
indicate suitable sampling point location.
No more than TWO Air Handling Units may be protected with one Stratos-Micra
100 detector. In this application, ensure that the sampling pipe is raised clear of high
velocity air in the immediate vincinity of the air intake grille on stand-off posts as shown
below.
Sampling pipe
Incorrect
Standoff posts
Detector
Correct
Direction
of smoke
Detector
AHU
equipment
cabinet
Page 22
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
5.2 The installation must be designed using PipeCAD software, which is provided free
EN54-20 and on the CD shipped with each detector. After designing the installation including
UL compliance pipes, endcaps and sampling holes, enter the detector type. To select the detector
type, select Options, select Calculation options, and then select the detector from
the Type drop-down list.
5.2.1 EN54-20 Select “Options” “Calculate” or click on the calculator icon. The software will prompt
you to choose from “Use set hole sizes” “Best flow balance” and “Max. permissible
transit time”. Select the appropriate option and click “OK”. The results for each pipe
(“View” “Results”) show calculations for each sampling hole on the pipe with the
nearest to the detector at the top of the screen, and the endcap hole at the bottom.
For EN54-20 compliance the transport time of the last sampling hole shall be
checked following all installation and proven to be less than or equal to that
determined by PipeCAD.
These settings gave satisfactory responses to the test fires in 120 seconds or
better. For the purposes of UL268 compliance, these should be regarded as worst
case values. Layouts should be planned in PipeCAD and the indicated worst-case
hole sensitivity should be better than 1.28% obs/ft*. Commissioning smoke tests
should be performed to ensure that the farthest sampling hole from the detector is
capable of generating a fire alarm within 120s of receiving smoke.
*The results should be verified at installation by entering the installed detector's Fire 1
sensitivity (as indicated in the remote software histogram screen) into the PipeCAD
“Options/Calculation options/Detector sensitivity” field and recalculating the layout results.
Page 23
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
ULC-S529-02 fire tests were passed with an installation as follows:
These settings gave satisfactory responses to the test fires in 120 seconds or better.
For the purposes of ULC529-2 compliance, these should be regarded as worst case
values. Layouts should be planned in PipeCAD and the indicated worst-case hole is
more sensitive than 0.51% obs/ft*. Commissioning smoke tests should be performed
to ensure that the farthest sampling hole from the detector is capable of generating a
fire alarm within 120s of receiving smoke.
*The results should be verified at installation by entering the installed detector's Fire
1 sensitivity (as indicated in the remote software histogram screen) into the PipeCAD
“Options/Calculation options/Detector sensitivity” field and recalculating the layout results.
6. Installation Before installing the detector, the local standards for installation of aspirating detection
systems must be consulted as these standards differ throughout the world. Specific
advice for one country may not be applicable to another. The following is a brief set of
guidelines on installing detectors.
■ The detector will normally be mounted at a level where there is easy access to the
unit for configuration and programming.
■ The exhaust air from the unit must not be impeded in any way. If the unit is
mounted in a different air pressure from where the air is being sampled (for example
an air duct), then a pipe must be taken from the exhaust port back to the same air
pressure zone as the sampling holes.
■ All signal cables must be screened and must be of a suitable type. The specific type
of cable will normally depend upon the local fire regulations.
■ The unit must not be placed in areas where either the temperature or humidity is
outside the specified operating range.
■ The unit should not be placed in close proximity to any equipment expected to
generate high Radio Frequency levels (such as radio alarms) or units generating high
levels of electrical energy (such as large electric motors or generators).
6.1 Docking station The basic principle behind installation of the Micra is that all wiring and pipe-work is
installed using a docking station. This is a convenient feature which means that the
detector can be dismounted or replaced without disturbing any wiring or installed
pipe-work.
There are two types of docking station, one with a single inlet port for aspirating
pipe-work, the other with a second port allowing the detector exhaust air to be taken
back to the area of different atmospheric pressure from which the inlet is sampling (see
section 4, “Sampling Pipe Design”, paragraph 1).
Page 24
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
6.1.2 Mechanical installation
The docking station is connected to the installed sampling pipe-work and fixed to the
wall or mounting surface using 3 off screws of a type appropriate to the mounting
surface. Ensure that the sampling and/or exhaust pipes are securely seated in the pipe
ports before fixing. If using a piped exhaust docking station be sure that the sampling
and exhaust pipes are fitted into the relevant ports as shown in section 6.1.
The Stratos-Micra 100 detector is supplied with removable terminal blocks (See illus-
trations in Section 2.2). These are simply removed from their sockets by lifting them
up at right angles to the circuit board. Take note of the orientation of each terminal
block and its function before removing it. It may also be beneficial to mark the connec-
tion wires with suitable identification labels or coloured rings to aid in the connection
process. NB: All connections should be made with the power turned off.
Each detector is supplied with a pair of RF suppression
ferrite rings. To ensure compliance with all relevant EMC
requirements, the conductors of each cable should be
wound once around a ferrite as shown here before enter-
ing the relevant connector. Power conductors should be on
a separate ferrite, but different forms of signal conductor
(e.g. RS485 and relays) can share the same ferrite.
The power supply cable should be of screened type and should be led through the
metal cable gland provided, leaving about 35mm of the cable extending from the bot-
tom of the cable gland. Depending on the type of cable used, it may be necessary to
increase the diameter of the cable with sleeving or insulating tape to ensure that the
cable is firmly held when the cable gland is fully tightened.
Page 25
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
6.2.2 Signal connections
To connect the signal wire, lead a suitable wire type (RS485 cable 9841, 120 ohm
screened twisted pair or equivalent) through the second cable gland and tighten it into
position with about 35mm of cable from the bottom of the cable gland.
Remove either the three-way terminal block next to the power supply socket if con-
necting the detector to a SenseNET system, or the four-way “Bus” terminal block if
connecting the detector to an alarm panel in conjunction with the APIC addressable
bus card (see section 7.3). For example, in a SenseNET system using screened cable,
connect the screen wire(s) to the “SCN” terminal, Bus A wire(s) to the “A” terminal
and Bus B wire(s) to the “B” terminal.
If the detector is in the middle of a SenseNET chain, with input and output connec-
tions, it may be more convenient to link the common Bus A, Bus B and screen wires
to single A, B and screen wires for linking to the terminal block.
Page 26
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
6.3 Final installation
Once the power and signal connections are made, slide the detector body up into the
docking station and fasten it into position using the M4 pan head screws provided.
Slot the power and signal terminal blocks into the relevant sockets on the detector
PCB (they will only click fully home in the correct orientation) and replace the detector
cover using the four M3 pan head screws provided.
NB: The detector is designed solely for operation with the front cover securely
fitted using all four fixing screws.
Removing the detector is simply the reverse of this process, leaving the pipe-work and
wiring connections installed in the docking station.
Dock fixing
screws
Page 27
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
7. Interfacing Because of the flexible nature of the Stratos-Micra 100® detector and the many possible
configurations, there are many options for interfacing the detectors to the Fire Panel.
These include many third party interfaces available from various manufacturers.
Because of this, it is not possible to give a complete list of all interfacing methods but
the following pages will give details of the most common methods that are likely to
be used.
In order to identify itself to the PC Command Module or fire panel, each detector needs
to have a unique address ranging from 1 to 127. The detector address is simply set
on the DIP switch SW1 at the bottom left of the opened detector on the main circuit
board. The switch settings are on for 1 and off for 0, and the detector address is set
as a 7-bit binary code (switch 8 equates to a value of 128 and so is outside the usable
address range). An example is shown below.
DIL ON
1 2 3 4 5 6 7 8
Page 28
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
7.1.2 Address table
ADDRESS 1 2 3 4 5 6 7 8 65 1 0 0 0 0 0 1 0
1 1 0 0 0 0 0 0 0 66 0 1 0 0 0 0 1 0
2 0 1 0 0 0 0 0 0 67 1 1 0 0 0 0 1 0
3 1 1 0 0 0 0 0 0 68 0 0 1 0 0 0 1 0
4 0 0 1 0 0 0 0 0 69 1 0 1 0 0 0 1 0
5 1 0 1 0 0 0 0 0 70 0 1 1 0 0 0 1 0
6 0 1 1 0 0 0 0 0 71 1 1 1 0 0 0 1 0
7 1 1 1 0 0 0 0 0 72 0 0 0 1 0 0 1 0
8 0 0 0 1 0 0 0 0 73 1 0 0 1 0 0 1 0
9 1 0 0 1 0 0 0 0 74 0 1 0 1 0 0 1 0
10 0 1 0 1 0 0 0 0 75 1 1 0 1 0 0 1 0
11 1 1 0 1 0 0 0 0 76 0 0 1 1 0 0 1 0
12 0 0 1 1 0 0 0 0 77 1 0 1 1 0 0 1 0
13 1 0 1 1 0 0 0 0 78 0 1 1 1 0 0 1 0
14 0 1 1 1 0 0 0 0 79 1 1 1 1 0 0 1 0
15 1 1 1 1 0 0 0 0 80 0 0 0 0 1 0 1 0
16 0 0 0 0 1 0 0 0 81 1 0 0 0 1 0 1 0
17 1 0 0 0 1 0 0 0 82 0 1 0 0 1 0 1 0
18 0 1 0 0 1 0 0 0 83 1 1 0 0 1 0 1 0
19 1 1 0 0 1 0 0 0 84 0 0 1 0 1 0 1 0
20 0 0 1 0 1 0 0 0 85 1 0 1 0 1 0 1 0
21 1 0 1 0 1 0 0 0 86 0 1 1 0 1 0 1 0
22 0 1 1 0 1 0 0 0 87 1 1 1 0 1 0 1 0
23 1 1 1 0 1 0 0 0 88 0 0 0 1 1 0 1 0
24 0 0 0 1 1 0 0 0 89 1 0 0 1 1 0 1 0
25 1 0 0 1 1 0 0 0 90 0 1 0 1 1 0 1 0
26 0 1 0 1 1 0 0 0 91 1 1 0 1 1 0 1 0
27 1 1 0 1 1 0 0 0 92 0 0 1 1 1 0 1 0
28 0 0 1 1 1 0 0 0 93 1 0 1 1 1 0 1 0
29 1 0 1 1 1 0 0 0 94 0 1 1 1 1 0 1 0
30 0 1 1 1 1 0 0 0 95 1 1 1 1 1 0 1 0
31 1 1 1 1 1 0 0 0 96 0 0 0 0 0 1 1 0
32 0 0 0 0 0 1 0 0 97 1 0 0 0 0 1 1 0
33 1 0 0 0 0 1 0 0 98 0 1 0 0 0 1 1 0
34 0 1 0 0 0 1 0 0 99 1 1 0 0 0 1 1 0
35 1 1 0 0 0 1 0 0 100 0 0 1 0 0 1 1 0
36 0 0 1 0 0 1 0 0 101 1 0 1 0 0 1 1 0
37 1 0 1 0 0 1 0 0 102 0 1 1 0 0 1 1 0
38 0 1 1 0 0 1 0 0 103 1 1 1 0 0 1 1 0
39 1 1 1 0 0 1 0 0 104 0 0 0 1 0 1 1 0
40 0 0 0 1 0 1 0 0 105 1 0 0 1 0 1 1 0
41 1 0 0 1 0 1 0 0 106 0 1 0 1 0 1 1 0
42 0 1 0 1 0 1 0 0 107 1 1 0 1 0 1 1 0
43 1 1 0 1 0 1 0 0 108 0 0 1 1 0 1 1 0
44 0 0 1 1 0 1 0 0 109 1 0 1 1 0 1 1 0
45 1 0 1 1 0 1 0 0 110 0 1 1 1 0 1 1 0
46 0 1 1 1 0 1 0 0 111 1 1 1 1 0 1 1 0
47 1 1 1 1 0 1 0 0 112 0 0 0 0 1 1 1 0
48 0 0 0 0 1 1 0 0 113 1 0 0 0 1 1 1 0
49 1 0 0 0 1 1 0 0 114 0 1 0 0 1 1 1 0
50 0 1 0 0 1 1 0 0 115 1 1 0 0 1 1 1 0
51 1 1 0 0 1 1 0 0 116 0 0 1 0 1 1 1 0
52 0 0 1 0 1 1 0 0 117 1 0 1 0 1 1 1 0
53 1 0 1 0 1 1 0 0 118 0 1 1 0 1 1 1 0
54 0 1 1 0 1 1 0 0 119 1 1 1 0 1 1 1 0
55 1 1 1 0 1 1 0 0 120 0 0 0 1 1 1 1 0
56 0 0 0 1 1 1 0 0 121 1 0 0 1 1 1 1 0
57 1 0 0 1 1 1 0 0 122 0 1 0 1 1 1 1 0
58 0 1 0 1 1 1 0 0 123 1 1 0 1 1 1 1 0
59 1 1 0 1 1 1 0 0 124 0 0 1 1 1 1 1 0
60 0 0 1 1 1 1 0 0 125 1 0 1 1 1 1 1 0
61 1 0 1 1 1 1 0 0 126 0 1 1 1 1 1 1 0
62 0 1 1 1 1 1 0 0 127 1 1 1 1 1 1 1 0
63 1 1 1 1 1 1 0 0
64 0 0 0 0 0 0 1 0
Page 29
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
7.2 Connecting a Stratos-Micra 100 to a SenseNET/RS485 detector
network
Up to 127 detectors may be linked in a single SenseNET bus, supporting a total length
of wire between adjacent detectors of up to 1.2km.
In the above example, two Stratos-Micra 100 detectors are linked into a 127-detector
bus with a Command Module and a number of Stratos-HSSD 2 detectors. It will be
noted that whereas the Stratos-HSSD 2 units have two input / output buses (1A / 1B
and 2A / 2B), the Stratos-Micra 100 has only a single such bus (A / B) and therefore
each bus terminal has an input and an output wire, compared with a single wire in
each terminal in the Stratos-HSSD 2.
For this reason, it may be easier to join the input and output wires for each bus and
screen connections together and to solder or crimp a single wire or connecting ferrule
to each wire pair so that they are easier to fit into the screw terminals. If this is done it
is recommended that bare wire joints be insulated to prevent possible shorting of the
data bus, which will cause a drop-out of data on the SenseNET bus.
In the above example, there could be a total length of RS485 cable of up to 1.2km
between the Command Module and Detector 3, since these are all on a single bus.
However, Detector 3 is a Stratos-HSSD 2 which has a second communications bus
(RS485 bus 2) and an RS485 repeater. This allows a further total of 1.2km of cable until
the next Stratos-HSSD 2 in the RS485 loop.
In the above example, if detectors 4-126 (not shown) were all of the Stratos-Micra 100
type then the total length of wiring between detectors 3 and 127 would be limited to
1.2km. However, each additional Stratos-HSSD 2 detector wired up using both RS485
buses would allow an additional 1.2km of cabling to be added to the RS485 loop.
Page 30
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
7.3 Connecting a Stratos-Micra 100 to an addressable Fire Panel
An Addressable Protocol Interface Card (APIC) may be used to decode detector infor-
mation and to relay this to a Fire Panel.
The APIC is fitted to the four mounting studs on the Stratos-Micra 100 PCB using the
supplied screws as shown below:
Mounting
studs x 4
APIC Address
switch x 2
APIC
Interface
connection
The connections to the Fire Panel are made using the BUS L1 and H1 (bus 1 input and
output) and the BUS L2 and H2 (bus 1 input and output) terminal connectors shown
in Section 6.2.2.
The only settings that need to be made are on the APIC address DIP switches. The start
loop address Is entered on SW1 and the end loop address on SW2. In the case of a
single Stratos-Micra 100 the start and end addresses will be the same.
NB: The detector address on the SenseNET loop and the Fire Panel addressable protocol
address are the same, i.e. no address translation is performed. Some protocols may not
support all the available alarm levels and fault reporting is usually a general fault with no
detailed fault information. Please consult the specific APIC protocol documentation for more
information.
Page 31
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
7.4. Connecting To connect a single stand-alone detector to a PC, connect the PC‘s serial port directly
to a PC to the detector‘s 9-way RS232 port. Connections for this cable are shown below.
2 3
3 2
5 5
7 8
8 7
Serial port
connection
to PC serial port
Page 32
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
8. Event Log An event is defined as
The detector stores an internal log of the last 200 events, and this can either be viewed
on a PC screen or downloaded to disk by use of the remote control software.
When the event log is full (200 events are stored) and a new event occurs, the oldest
event in the log is deleted (First-In, First-Out).
To download the event log, connect a PC to the detector serial port and run the
remote software. Either select the menu options “View ➔ Event log” or click on the
event log symbol as indicated below.
Page 33
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
This shows the time and date of each event stored in the log along with its general
description. The buttons at the bottom of the screen allow control over the input and
output of the log.
Open: opens a previously saved event log. Event logs have the file extension
“.evl”.
Save As: saves the current event log as a .evl file with a user defined name.
Print: prints the event log to a connected printer.
Filter: clicking on this option brings up the following screen:
This allows the user to limit the information printed or viewed on the PC screen.
For example the user might wish to concentrate on alarm events only. To do this,
click on “None”, which unticks all boxes, and then on “Alarms”. To tick all the boxes,
tick “All”.
Any or all of the event categories may be selected or deselected as desired.
Page 34
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
9. Commissioning Before commissioning the detector the local standards of aspirating detection systems
must be consulted. These standards differ widely throughout the world and specific
advice for the market in one country may not be applicable to another.
Commissioning strategy will initially depend upon the environment in which the
detector is installed. For instance, the test for a computer room (which should be a
relatively clean environment) would be very different from, say, a flour mill, which
would probably have a high level of airborne particulate content.
A widely accepted standard for computer rooms/EDP areas is British Standard BS6266,
equipment overheating at a stage well before combustion. To perform the test
electrically overload a 1‑metre length of PVC insulated wire of 10/0.1mm gauge for
one minute using an appropriate power supply. The detector has two minutes from the
end of the wire burn to give an alarm indication.
For areas with higher levels of background particulate matter testing methodology
would be similar to that of standard point detectors.
9.1 Commissioning The following brief checklist allows quick setup of the detector. This procedure will be
checklist adequate for most standard installations.
1. Before powering up the detector, visually check all cabling to ensure correct
connection. If wire identification is not immediately clear (e.g. by use of different
coloured wires or wire identification sleeves) an electrical check should be
3. Verify that the time and date are correct (see section 3.1)
4. Set an appropriate alarm factor for the protected environment. The detector will
perform a FastLearn for the new alarm factor. (see section 3.7)
5. Whilst the detector is still in FastLearn mode set the detector into demonstration
mode (see section 3.10). NB: Aerosol-type synthetic smoke sources should not
be used to test the response of the detector as these may leave acidic residues
which could cause damage to the unit.
6. Wait for the FastLearn to finish and the flashing OK LED indicator will finish and
perform any necessary smoke tests, ensuring that the detector reacts appropriately,
and let the smoke fully dissipate.
7. Perform another FastLearn, this time not putting the detector into demonstration
mode. The detector will generate no alarms during the 15 minute FastLearn
period, and after this the detector will operate at a reduced sensitivity for 24 hours
whilst ClassiFire acclimatises to the protected environment and sets up appropriate
day and night sensitivity settings.
Page 35
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
10. Maintenance Stratos-Micra is a very low maintenance detection system. If required, external cleaning
of the unit should be performed using a damp (not wet) cloth. Do not use solvents as
these may mar the front panel label. The only part that may require field replacement
during servicing is the dust separator assembly*. The dust separator condition can be
checked using the Dust Separator test in the Miscellaneous tab of the remote
software ‘Detector settings’ screen (see section 3.33) which gives a percentage
reading of dust separator efficiency. When this level drops to 80% the detector will
signal a fault and the dust separator will need replacing. To replace the filter, simply
remove the front cover and pull the filter out from the main unit. Slide the replacement
filter in so that the ‘Direction of flow’ arrow printed on the carton duplicates that on
the ‘Direction of flow’ label beside the filter slot.
*It is recommended that dust separators be changed at an interval of not more than
! 3 years. After replacing the filter, the detector must be put into FastLearn mode (see
section 3.7) to reset the filter condition reading.
IMPORTANT NOTE
Page 36
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
10.1 Diagnostics
The remote control software includes a diagnostic function which carries out a number
of checks to verify the correct functioning of the detector. A good time to run these
tests is as a part of planned maintenance. To call up diagnostic mode, select the menu
options “View ➔ Diagnostics” or click on the symbol indicated below.
The software will then scan the loop for up to 127 detectors. For a single detector, wait
until the first detector has been identified and the window indicates that it is scanning
for Detector 2, then press the Cancel button.
Click on the list entry to highlight it and click on the “Diagnostics…” button. The
software will then commence the system tests. During the “Aspirator and flow” test,
the detector fan will suddenly slow down, but this is a normal part of the test and no
cause for alarm.
Page 37
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
When the test has finished and no problems have been found, the following screen
appears:
If any problems were found during the diagnostic tests, the nature of the fault will be
indicated in the “Status” column.
Read Button: This brings up a display of the detector output and flow rate which
updates in real time.
Relays: Brings up a screen allowing the function of the volt-free ‘Fire’ and
Fault LEDs to be tested with the aid of a continuity meter or other
tester. The Fire relay contacts are open in normal operation and will
close on test. The Fault relay contacts operate on a ‘Fail-safe’ basis
and are held closed in normal operation. They will therefore open on
test.
Save As: Saves the summary list of scanned detectors and their status as a text
(.txt) file.
Page 38
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
11. Troubleshooting 11.1 Nuisance alarms occur too often
• Check that the ClassiFire alarm factor setting is appropriate for the normal working
environment of the protected area. See section 3.5
• Check that the detector is not in Demonstration mode. This can be ascer-
tained by viewing the event log (see section 3) and checking that the entry
Demo mode has a higher log entry number than the most recent
FastLearn start and FastLearn end entries. Remember that the log
entries are in reverse order, with the most recent entries appearing first.
If the log shows that Demonstration mode was invoked during the last FastLearn
period, start a new FastLearn and allow it to complete its 24-hour cycle. (See
section 3.7)
• From the event log (see sections 8), check that 24 hours have elapsed since the
last FastLearn end entry.
• Check that day-night switchover times are appropriately set to reflect active and
non-active periods (see section 3.11).
Page 39
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
11.6 Flow fault errors
• These occur when the airflow rate into the detector is outside the pre-programmed
limits. As the detector ‘learns‘ the flow setup from the initial installation, this
usually means that there has been some change in conditions. A Flow high fault
may indicate that a sampling pipe is damaged, and a Flow low fault may indicate
that the pipe has been blocked, e.g. by nearby building operations.
• If the detector input is sampled from one area and the exhaust is in another area
with different pressure (e.g. the detector is in a roof space and sampling from an
enclosed room), this may lead to flow faults. In this case it would be necessary to
lead a pipe from the exhaust to the protected area to ensure normal flow. This will
require the detector to be installed using the piped exhaust docking station (see
section 6.1).
• Intermittent flow faults may indicate local short-term fluctuations in air pressure.
To overcome this problem, the flow fault delay is programmable from 30 to 240
seconds.
• Check that the low flow fault threshold is not set too high (see section 3.29)
• In the case of intermittent fault indications, try increasing the flow fault delay time
(see section 3.32).
• Check that the pipe is pushed home into the inlet and is not broken or cracked
• Check that the high flow fault threshold is not set too low (see section 3.30)
• In the case of intermittent fault indications, try increasing the flow fault delay time
(see section 3.32).
Page 40
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
12. Do’s and Don’ts DO
✔ Ensure that cables are correctly connected before powering up by use of cable
identifiers or electrical continuity checks. Incorrect connection could damage the
detector.
✔ Place sampling points so that the detector will be able to detect smoke at the
earliest opportunity.
✔ Ensure that the detector exhaust is in an area with the same atmospheric pressure
as the sampling pipes, either by placing the detector physically in the protected
area or by leading a pipe from the detector exhaust to the protected area.
✔ Ensure that the environment of the protected area is within the environmental
operating parameters of the detector (temperature -10 to +60°C, (humidity 0-
90%, non-condensing).
DON’T
✘ Forget to set the appropriate ClassiFire alarm factor for the area to be detected.
✘ Forget to set the Detector Address Switches correctly when used in a network.
✘ Attempt to adjust or alter detector settings other than via the user-programmable
functions. In particular, the setting up of the laser is a precision task, and once
set up the potentiometers should be left alone. If it is suspected that the laser
alignment has shifted (e.g. after dropping the detector), it should be returned to
the manufacturer for recalibration.
✘ Operate the detector with the front cover removed, or with one or more of the
cover fixing screws loose or missing.
Page 41
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
13. Stratos-Micra 100 SELV rating (EN 60950) Class III
specification Supply Voltage 21.6V - 26.4V DC
PSU Type: conforming to EN 54-4
Electrical safety complies with BS EN
610190-1
Size (mm) 300W x 220H x 90D
Weight 3.8kg with docking station
Operating temperature range 0 to +38°C (UL268)
–10 to +60°C (EN 54-20)
Operating humidity range 0 - 90% Non Condensing
BS EN 61010-1 Pollution degree 1
BS EN 61010-1 Installation Cat. II
Sensitivity range (%Obs/m) Min = 25% Max = 0.03% FSD
Maximum sensitivity resolution 0.0015 % obs/m
Detection principle Laser light scattering mass detection
Particle sensitivity range 0.0003µm to 10µm
Current consumption 400mA
Relay contact rating 500mA @ 30V
Maximum sampling pipe length 100 metres total (see design limitations
on section 5)
Sampling pipe inlets 2
Sampling pipe internal diameter 15-25mm
Alarm levels 4 (Fire 2, Fire 1, Pre-Alarm and Aux)
1 relay as standard, others available
Chamber service intervals Greater than 8 years (depending on
environment)
Dust separator replacement intervals Greater than 5 years (depending on
environment)
Laser lifetime (MTTF) Greater than 1000 years
Programming PC via RS232/RS485
Data bus cable RS485 data cable
Data bus length 1.2 km
IP rating IP50
Page 42
Stratos-Micra 100 • INSTALLER’S HANDBOOK • Iss. 12
Kidde Products Limited • Unit 2 Blair Way Dawdon • City: Seaham,
County Durham, SR7 7PP United Kingdom
Tel: +44(0)191-513 6100 Fax: +44(0)191-513 6102