Integra 30s

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64
At a glance
Powered by AI
The document provides an operations and service manual for an Integra 30S truck refrigeration unit, describing its components and functions as well as maintenance procedures.

The document is an operations and service manual for an Integra 30S truck refrigeration unit. It provides descriptions of the unit and its components as well as operating instructions and troubleshooting information.

The refrigeration system has a condensing section including a condenser/subcooler, filter drier, oil separator, hot gas solenoid valve, condenser pressure control valve, compressor, standby motor, receiver, high pressure switch, and condenser pressure control switch. The evaporator section includes a thermostatic expansion valve, compressor pressure regulating valve, defrost termination thermostat, quench valve, evaporator, and low pressure switch.

Truck Refrigeration

EVAPORATOR
TXV BULB
CONDENSER

TXV

RECEIVER

OPERATION & SERVICE


for

INTEGRA 30S
Truck Refrigeration Units
Beginning With S/N PB 225225

62--10848 Rev B

OPERATION AND
SERVICE MANUAL

INTEGRA 30S
TRUCK REFRIGERATION UNIT
BEGINNING WITH S/N PB 225225

TABLE OF CONTENTS
PARAGRAPH NUMBER
Page
GENERAL SAFETY NOTICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1
FIRST AID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1
OPERATING PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1
MAINTENANCE PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1
SPECIFIC WARNING AND CAUTION STATEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-2
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.2 GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.3 CONDENSING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.3.1 Condenser/Subcooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.3.2 Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.3.3 Oil Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
1.3.4 Hot Gas Solenoid Valve (HGS1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
1.3.5 Condenser Pressure Control Valve (HGS2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
1.3.6 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
1.3.7 Standby Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
1.3.8 Receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
1.3.9 High Pressure Switch (HP1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.3.10 Condenser Pressure Control Switch (HP2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.4 EVAPORATOR SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.4.1 Thermostatic Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.4.2 Compressor Pressure Regulating Valve (CPR) (115V Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.4.3 Defrost Termination Thermostat (DTT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.4.4 Quench Valve (BPV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.4.5 Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.4.6 Low Pressure Switch (LP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1.5 SYSTEM OPERATING CONTROLS AND COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8
1.6 UNIT SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9
1.6.1 Compressor Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9
1.6.2 Refrigeration System Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9
1.6.3 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
1.6.4 Torque Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
1.7 SAFETY DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
1.8 REFRIGERANT Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
1.8.1 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
1.8.2 Heat And Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12

62--10848

TABLE OF CONTENTS (Continued)


PARAGRAPH NUMBER

Page

OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1

2.2

2-1

CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-1

2.1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-1

1.8.3 Microprocessor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-1

2.1.2 Cab Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-1

START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2

2.2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2

2.2.2 Connect Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-3

2.2.3 Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-3

2.3

SETPOINT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-3

2.4

MANUAL DEFROST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-3

2.5

DEFROST CYCLE ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-3

2.6

ALARM DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-4

2.6.1 Accessing Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-4

2.6.2 Low Battery Voltage Alarm for Road Only Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-5

2.6.3 Clearing Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-5

2.7

CHECKING THE EEPROM VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-5

2.8

STOPPING THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-5

2.9

MICROPROCESSOR CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-6

2.9.1 ROAD ONLY FUNCTIONAL SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-6

2.9.2 ROAD/STANDBY FUNCTIONAL SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-7

TEMPERATURE CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1

3.1

SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1

3.1.1 Perishable Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1

3.1.2 Frozen Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1

3.2

DEFROST CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-2

3.3

MINIMUM OFF TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-2

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-1

4.1
4.2

MAINTENANCE SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-1

BELT MAINTENANCE AND ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-2

4.2.1 Standby Motor--Compressor V-Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-2

INSTALLING R-134A MANIFOLD GUAGE SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-2

4.3.1 Preparing Manifold Gauge/Hose Set For Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-2

4.3.2 Connecting Manifold Gauge/Hose Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-2

4.3.3 Removing the Manifold Gauge Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-3

REMOVING THE REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-3

4.4.1 Refrigerant Removal From A Non--Working Compressor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-3

4.5

REFRIGERANT LEAK CHECKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-3

4.6

EVACUATION AND DEHYDRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-4

4.6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-4

4.3

4.4

4.6.2 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-4

4.6.3 Procedure For Evacuation And Dehydrating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-4

62--10848

ii

TABLE OF CONTENTS (Continued)


PARAGRAPH NUMBER
Page
SERVICE (Continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
4.7 CHARGING THE REFRIGERATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5
4.7.1 Checking The Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5
4.7.2 Installing A Complete Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5
4.7.3 Adding A Partial Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5
4.8 CHECKING FOR NON--CONDENSABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5
4.9 REPLACING THE COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
4.9.1 Removing Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
4.9.2 Installing Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
4.10 CHECKING AND REPLACING FILTER-DRIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
4.10.1 Checking Filter-Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
4.10.2 Replacing The Filter-Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
4.11 HIGH PRESSURE (HP1) AND CONDENSER PRESSURE (HP2) SWITCHES . . . . . . . . . . . . . . . .
4-6
4.11.1 Removing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
4.11.2 Checking Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
4.12 CHECKING AND REPLACING CONDENSER FAN MOTOR BRUSHES . . . . . . . . . . . . . . . . . . . . .
4-7
4.13 HOT GAS (HGS1) AND CONDENSER PRESSURE CONTROL SOLENOID VALVES . . . . . . . . .
4-7
4.13.1 Replacing Solenoid Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7
4.13.2 Replacing Valve Internal Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7
4.14 ADJUSTING THE COMPRESSOR PRESSURE REGULATING VALVE (CPR) (115V ONLY) . . . .
4-8
4.15 THERMOSTATIC EXPANSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8
4.15.1 Replacing expansion valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8
4.15.2 Measuring Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8
4.16 DIAGNOSTIC TOOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
4.17 MICROPROCESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
4.18 EVAPORATOR COIL CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
4.19 CONDENSER COIL CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
5.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
5.2 REFRIGERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
5.2.1 Unit Will Not Cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
5.2.2 Unit Runs But Has Insufficient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
5.2.3 Unit Operates Long or Continuously in Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
5.2.4 Unit Will Not Heat or Heating Insufficient . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
5.2.5 Defrost Malfunction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
5.2.6 Abnormal Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
5.2.7 Abnormal Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
5.2.8 Cab Command Malfunction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
5.2.9 No Evaporator Air Flow or Restricted Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
5.2.10 Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
5.2.11 Malfunction Hot Gas Solenoid or Condenser Pressure Regulating Valve . . . . . . . . . . . . . . . . . .
5-4
5.2.12 Standby Compressor Malfunction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
SCHEMATIC DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
6.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
iii

62--10848

LIST OF ILLUSTRATIONS
FIGURE NUMBER
Figure 1-1 Integra 30S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-2 Top View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-3 Rear View Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-4 Oil Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-5 Typical Standby Control Box
Figure 1-6 Standby Microprocessor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-7 Road Microprocessor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-8 Cab Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-9 Refrigeration Circuit Cooling Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-10 Refrigeration Circuit Heating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 2-1 Cab Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 2-2 Green Light Status -- Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 2-3 Green Light Status -- Road Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 2-4 Temperature Selection Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-1 Operating Sequence -- Perishable Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-2 Operating Sequence -- Frozen Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-1 Belt Tension Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-2 Layout of V-belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-3 Manifold Gauge Set (R-134a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-4 Vacuum Pump Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-5 Typical Setup For Testing Pressure Switches HP1 And HP2 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-6 Fan Motor Brushes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-7 Hot Gas or Condenser Pressure Control Solenoid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-8 Compressor Pressure Regulating Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-9 Thermostatic Expansion Valve Bulb And Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-10 Cab Command Diagnostic Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-1 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61350 Rev D . . . . . . . . . . . . .
Figure 6-2 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61350 Rev D . . . . . . . . . . . . .
Figure 6-3 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61353 Rev A . . . . . . . . . . . . . .
Figure 6-4 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61354 Rev A . . . . . . . . . . . . . .
Figure 6-5 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61354 Rev A . . . . . . . . . . . . . .
Figure 6-6 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61352 Rev A . . . . . . . . . . . . . .

Page
1-2
1-2
1-3
1-3
1-5
1-6
1-7
1-8
1-13
1-14
2-1
2-2
2-2
2-7
3-1
3-1
4-2
4-2
4-3
4-4
4-7
4-7
4-7
4-8
4-8
4-9
6-2
6-3
6-5
6-6
6-7
6-9

LIST OF TABLES
TABLE NUMBER
Table 1-1
Model Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 1-2
Additional Support Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2-1
Alarms For Road Only Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2-2
Alarms For Standby Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-1
Maintenance Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-2
Service Category Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-3. Belt Tension (See Figure 4-2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-4
R-134a Temperature-Pressure Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 5-1
Alarm Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 5-2
Mechanical Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
62--10848

iv

Page
1-1
1-1
2-4
2-5
4-1
4-1
4-2
4-10
5-1
5-2

SAFETY SUMMARY
SAFETY PRECAUTIONS
Your Carrier Transicold refrigeration unit has been designed with the safety of the operator in mind. During normal
operation, all moving parts are fully enclosed to help prevent injury. During all pre-trip inspections, daily inspections,
and problem troubleshooting, you may be exposed to moving parts. Stay clear of all moving parts when the unit is in
operation and when the ON/OFF switch is in the ON position.
FIRST AID
No injury, no matter how slight, should go unattended. Always obtain first aid or medical attention immediately.
OPERATING PRECAUTIONS
Always wear safety glasses. Wear hearing protection as required.
Keep hands, clothing and tools clear of the evaporator and condenser fans.
No work should be performed on the unit until all circuit breakers are turned off, and battery power supply is
disconnected.
Always work in pairs. Never work on the equipment alone.
In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the unit. This unit is equipped with Auto--Start in both the road and standby modes.
The unit may start at any time. When performing any check of the system make certain all circuit breakers are turned
off, and battery power supply is disconnected.
Be sure power is turned off before working on motors, controllers, solenoid valves and electrical control switches. Tag
circuit breaker and vehicle ignition to prevent accidental energizing of circuit.
Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems with
the system should be diagnosed, and any necessary repairs performed, by qualified service personnel.
When performing any arc welding on the unit or container, disconnect all wire harness connectors from the
microprocessor. Do not remove wire harness from the modules unless you are grounded to the unit frame with a static
safe wrist strap.
In case of electrical fire, open circuit switch and extinguish with CO2 (never use water).
REFRIGERANTS
The refrigerant contained in your unit can cause frostbite, severe burns, or blindness when in direct contact with the
skin or eyes. For this reason, and because of legislation regarding the handling of refrigerants during system service,
we recommend that you contact your nearest Carrier Transicold authorized repair facility whenever your unit requires
refrigeration system service .

Safety--1

62--10848

SPECIFIC WARNING AND CAUTION STATEMENTS


To help identify the label hazards on the unit and explain the level of awareness each one carries, an explanation is
given with the appropriate consequences:
DANGER -- means an immediate hazard which WILL result in severe personal injury or death.
WARNING -- means to warn against hazards or unsafe conditions which COULD result in severe personal injury or
death.
CAUTION -- means to warn against potential hazard or unsafe practice which could result in minor personal injury,
product or property damage.
The statements listed below are applicable to the refrigeration unit and appear elsewhere in this manual. These
recommended precautions must be understood and applied during operation and maintenance of the equipment
covered herein.

WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and operating compressor
unexpectedly as control requirements dictate. Press OFF key on the cab command and disconnect
power plug.

WARNING
Inspect battery cables for signs of wear, abrasion or damage at every Pre--Trip inspection
and replace if necessary. Also check battery cable routing to ensure that clamps are secure
and that cables are not pinched or chafing against any components.

WARNING
Do not attempt to connect or remove power plug before ensuring the unit is OFF (press OFF key on
Cab Command) and external power circuit breaker is open.

WARNING
Beware of V-belt and belt-driven components as the unit may start automatically.

WARNING
Ensure power to the unit is OFF, power plug is disconnected and circuit breaker is open or vehicle
engine is OFF and negative battery cable is connected before replacing compressor.

WARNING
Slowly open the plug on the suction and discharge valves of the new compressor to vent the nitrogen
holding charge.

WARNING
Do not use a nitrogen cylinder without a pressure regulator. (See Figure 4-5) Cylinder pressure is
approximately 2350 psig (160 bars). Do not use oxygen in or near a refrigerant system as an explosion may occur.
62--10848

Safety--2

CAUTION
Under no circumstances should anyone attempt to repair the microprocessor module or Cab Command! Should a problem develop with these components, contact your nearest Carrier Transicold
dealer for replacement.

CAUTION
If starting unit for the first time after installation or starting after adding/removing an optional feature
or if Owners operating parameters have changed, the Configuration will need to be reset.

CAUTION
Compressor failure will occur if inert gas brazing procedures are not used on units with
R134A and POE oil. For more information see Technical Procedure 98-50553-00 -- Inert Gas
Brazing.

CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set be sure set is brought to suction
pressure before disconnecting.

CAUTION
Do not damage or over tighten the enclosing tube assembly. Place all parts in the enclosing tube in
proper sequence in order to avoid premature coil burn-out.

CAUTION
Observe proper polarity when installing battery, negative battery terminal must be grounded.

CAUTION
Under no circumstances should a technician electrically probe the processor at any point, other than
the connector terminals where the harness attaches. Microprocessor components operate at different voltage levels and at extremely low current levels. Improper use of voltmeters, jumper wires, continuity testers, etc. could permanently damage the processor.

CAUTION
Most electronic components are susceptible to damage caused by electrical static discharge (ESD).
In certain cases, the human body can have enough static electricity to cause resultant damage to the
components by touch. This is especially true of the integrated circuits found on the microprocessor.
Use proper board handling techniques. (See Section 4.17).

Safety--3

62--10848

SECTION 1
DESCRIPTION
1.1 INTRODUCTION

1.3 CONDENSING SECTION

WARNING
Beware of unannounced starting of the
unit. The unit may cycle the fans and operating compressor unexpectedly as control requirements dictate. Press OFF key on the
Cab Command and disconnect power plug.
This manual contains Operating Data, Electrical Data
and Service Instructions for the Carrier Transicold
Model 30S truck refrigeration units listed in Table 1-1.
Additional support manuals are listed in Table 1-2.
The model/serial nameplate is located on the cover.

The condensing section (see Figure 1-2) contains the


condenser fan & coil, filter--drier, oil separator, hot gas
solenoid valve, receiver, and a condenser pressure
control valve. On road/standby units the condensing
section also houses the standby compressor, control
box and rectifier and houses the transformer assembly
(see Figure 1-2 and Figure 1-5 ).
1.3.1 Condenser/Subcooler
The condenser is of the tube and fin type and acts as a
heat exchanger in which the compressed refrigerant
gas is condensed into a liquid and lowered in temperature. Air movement over the condenser is provided by a
fan mounted in the condensing section.

1.2 GENERAL DESCRIPTION

A portion of the condenser is occupied by the subcooler.


Refrigerant leaving the receiver is passed through the
The unit (Figure 1-1) is of the split system type with the
subcooler where additional heat is removed. Removal
condenser mounted outside the truck body, evaporator
of this additional heat helps to ensure that only liquid
mounted in the body, and a Cab Command control
refrigerant enters the thermal expansion valve.
center mounted in the drivers compartment. Two types
of compressor drive are available:
1.3.2 Filter Drier
D Road operation: the road compressor is located in
the engine compartment and is driven by the engine
of the vehicle when in operation over--the--road
The drier is a cylindrical shell containing a drying agent
and screen. It is installed in the liquid line and functions
D Road/Standby version: a second compressor is
mounted in the condensing section and is driven by
to keep the system clean and remove moisture from the
an electric motor when in standby mode.
refrigerant.
Table 1-1 Model Chart
R134a
Model No.

Description

8002189

Road Only
Road/Standby
115/1/60Hz
Road/Standby
230/1/60Hz
Road/Standby
230/3/60Hz

8002191
8002193
8002195

LB

Kg

Road
Compressor

Standby
Compressor

Condenser Weight
Road and
Road
Standby

Evap. Wt.

--

1.8

TM 16

TM 16

88 lb
(40 kg)

165 lb (75
kg

66 lb (30
Kg)

Table 1-2. Additional Support Manuals


Manual Number
62--10835
62--10847
62--10849

Equipment Covered
Supra 30S
Supra 30S
Supra 30S

1--1

Type of Manual
Parts List
Easy To Run
Operators Manual

62-10848

CAB COMMAND

Figure 1-1 Integra 30S


2

17

16
15
1.
2.
3.
4.
5.
6.
7.
8.
9.

14

13

11

12

Nameplate
Condenser Coil
Transformer (TR)
Oil Separator
Standby Motor
Standby Compressor (See Table 1-1)
Control Box
Filter Drier
Liquid Line Check Valve

10.
11.
12.
13.
14.
15.
16.
17.

1--2

10

Sight Glass
Receiver
Discharge Manifold
Hot Gas Solenoid Valve (HGS1)
Condenser Pressure Control Switch (HP2)
Frame
High Pressure Switch (HP1)
Condenser Pressure Control Valve (HGS2)

Figure 1-2 Top View

62-10848

8
9

2
3
5
4

1.
2.
3.
4.

Low Pressure Switch (LP)


5. Evaporator coil
Expansion Valve (TXV)
6. Compressor Pressure Regulating Valve
Quench Valve (BPV)
(CPR)115V only
Defrost Termination Thermostat (DTT)
Figure 1-3 Rear View Evaporator
1.3.3 Oil Separator
1.3.5 Condenser Pressure Control Valve (HGS2)
The condenser pressure control valve (or condenser
The oil separator is installed in the discharge line from
closing valve) is a normally open valve that is powered
the road compressor. The hot gas coming from the comwhen the condenser pressure control switch (HP2) is
pressor is forced through a filter which separates the
closed. With the solenoid coil de-energized, the valve is
gas from the oil. The oil collects at the bottom after
in the cool mode and the compressor discharge gas is
passing through a second filter and then returns to the
delivered to the condenser. In the cool mode, heat is
compressor via a capillary tube.
removed from the air inside the truck body and rejected
to the surrounding air. With the solenoid coil energized,
the valve is in the heat mode and the compressor disOIL AND GAS
REFRIGERANT
charge gas is diverted to the evaporator and rejected to
FROM COMP.
the air inside the truck body.
GAS TO
1.3.6 Compressor
COND.
The compressor withdraws refrigerant gas from the
evaporator and delivers it to the condenser at an increased pressure. The pressure is such that refrigerant
heat can be absorbed by the surrounding air at ordinary
temperatures.
1.3.7 Standby Motor
OIL TO
The
standby
motor
operates
on
nominal
COMP.
115v--1ph--60hz
or
208/230v--1ph--60hz
or
SUCTION
230v--3ph--60hz power. An overload and short cycle
LINE
protection is provided along with automatic reset. Units
OIL
are also equipped with a remote mounted power receptacle.
Figure 1-4 Oil Separator
1.3.8 Receiver
1.3.4 Hot Gas Solenoid Valve (HGS1)
HGS1 is normally closed and prevents discharge gas
from entering the evaporator. The valve opens to allow
hot gas refrigerant to be delivered from the compressor
to the evaporator during heat or defrost modes.

1--3

Liquid refrigerant from the condenser is deliver to the


receiver. The receiver serves as a liquid reservoir when
there are surges due to load changes in the system; as a
storage space when pumping down the system and as a
liquid seal against the entrance of refrigerant gas into
the liquid line.

62-10848

1.3.9 High Pressure Switch (HP1)


HP1 is a normally closed switch which monitors the
system for high pressure and shuts down the unit when
pressure rises above predetermined setting. For HP1
settings see Section 1.6.2.
1.3.10 Condenser Pressure Control Switch (HP2)
HP2 is a normally open switch which closes to signal the
microprocessor to activate the condenser fan. HP2 also
cycles the condenser pressure control valve (HGS2)
and the quench valve (BPV) in addition to the condenser
fan in order to maintain head pressure for heating capacity. For HP2 settings see Section 1.6.2.
1.4 EVAPORATOR SECTION
The evaporator assembly consists of an evaporator fan,
evaporator coil, thermostatic expansion valve, defrost
termination thermostat, a compressor pressure
regulating valve (115V only) and a quench valve.
1.4.1 Thermostatic Expansion Valve
The thermostatic expansion valve is an automatic device which controls the flow of liquid to the evaporator
according to changes in superheat to the refrigerant
leaving the evaporator. The thermal expansion valve
maintains a relatively constant degree of superheat in
the gas leaving the evaporator regardless of suction
pressure. Thus, the valve has a dual function; automatic
expansion control and preventing liquid from returning
to the compressor. For TXV superheat settings see
Section 1.6.2. To adjust the TXV, refer to Section 4.15.2.
1.4.2 Compressor Pressure Regulating Valve
(CPR) (115V Only) (See Figure 1-3)
The CPR valve is installed on the suction line of the
standby compressor to regulate the suction pressure
entering the compressor. The CPR valve is set to limit
the maximum suction pressure. For CPR settings refer
to section 1.6.2.
The suction pressure is controlled to avoid overloading
the electric motor during high refrigerated compartment
temperature operation. To adjust the CPR valve, refer to
section 4.17

62-10848

1--4

1.4.3 Defrost Termination Thermostat (DTT)


Normally closed thermal switch on Standby units only.
As evaporator cools to set point, the switch closes and
signals microprocessor that defrost may be initiated.
Switch terminates defrost by opening at predetermined
set point. For DTT settings refer to section 1.6.2.
1.4.4 Quench Valve (BPV)
The quench valve is a normally closed solenoid valve
controlled by the quench thermostat (BPT) mounted on
the road compressor discharge line. The valve allows
metered liquid refrigerant to enter the suction line in the
evaporator in order to provide compressor cooling. For
BPT settings refer to section 1.6.2.
1.4.5 Evaporator
The evaporator is of the tube and fin type. The operation
of the compressor maintains a reduced pressure within
the coil. At this reduced pressure, the liquid refrigerant
evaporates at a temperature sufficiently low enough to
absorb heat from the air. Air movement over the evaporator is provided by an electric fan.
1.4.6 Low Pressure Switch (LP)
The low pressure switch is a normally closed switch
which signals the microprocessor to shut down the unit
when the system is outside the low pressure limit. For
LP settings refer to section 1.6.2.

6 7

5
3

4
10

11
1

14

13
115/1/60

12
115/1/60

1.
2.
3.
4.
5.
6.
7.

12
230/1/60

13
230/1/60

Standby clutch fuse (F2) -- 30 Amp


Standby Fuse (F3) -- 5 Amp
Transformer Fuse (F4) -- 5 Amp
Clutch Time Delay Relay (CT) -- Single Phase
Only
Clutch Relay (CR)
Motor Contactor (MC)
Overload Relay (OL) (230V Only)

8.
9.
10.
11.
12.
13.
14.

Diode
Rectifier Bridge Assembly (BR)
Filter Capacitor (C1)
Start Relay (STBR)
Run Capacitor (CR)
Start Capacitor (CS)
Heat sink (rectifier bridge)

Figure 1-5 Typical Standby Control Box

1--5

62-10848

1
2

9
3

8
4

1.
2.
3.
4.
5.

Connector
6.
C_ or F_ Temperature Selector
Road Relay (RR)
7.
Microprocessor (PC)
12 Volt dc Road Connection
8.
Road Fuse (F1) 30A
12 Volt dc Standby Connection
9.
Overload Relay (OL) 25A (115V Only)
Standby Relay (SR)
Figure 1-6 Standby Microprocessor Module

62-10848

1--6

3
4

1.
2.
3.
4.
5.

C_ or F_ Temperature Selector
Road fuse (25A)
+ Positive Battery Connection
-- Negative Battery Connection
--Microprocessor (PC)
Figure 1-7 Road Microprocessor Module

1--7

62-10848

1.5 SYSTEM OPERATING CONTROLS AND


COMPONENTS

CAUTION

The unit is furnished with a microprocessor control system. Once the set point is entered at the Cab Command,
the unit will operate automatically to maintain the desired temperature within very close limits.

WARNING
Beware of unannounced starting of the,
standby motor, evaporator fan or condenser fan. The unit may cycle the standby motor or fans unexpectedly as control requirements dictate.
The control system consists of the Cab Command located in the drivers section (See Figure 1-8) and the
microprocessor module (See Figure 1-6) located in the
control box.
The Carrier Transicold Control System incorporates the
following features:
a. Control return air temperature to tight limits by providing refrigeration control, heat and defrost to ensure
conditioned air delivery to the load.
b. Permanently displays the return air temperature and
on request the set point temperature.
c. Digital display and selection of data.

62-10848

1--8

Under no circumstances should anyone attempt to repair the microprocessor module


or Cab Command! Should a problem develop with these components, contact your
nearest Carrier Transicold dealer for replacement.

Figure 1-8 Cab Command

1.6 UNIT SPECIFICATIONS


1.6.1 Compressor Data
Model

TM 16
9.9 in3
cm3)

Displacement

(162

No. Cylinders

Weight

15.5 lbs
(7 kg)

Oil Charge

5.07in3 (180 cm3)

Approved Oil

Mobil Arctic EAL68

1.6.2 Refrigeration System Data


a. Defrost Timer
Automatic triggering or at preset intervals :
0 (Disabled), auto, 1h, 2h, 3h, 4h, 5h, 6h
b. Defrost Termination Thermostat (DTT) (Standby
Only)
Opens at:

48_ 5_F (9_ 3_C)

Closes at: 37_ 5_F (3_ 3_C)


c. High Pressure Switch (HP1)
Opens at : 355 psig 10 PSI (24.5 bars)
Closes at : 290 psig 10 PSI (20 bars)
d. Condenser Pressure Control Switch (HP2)
Opens at : 130 psig 10 PSI (9 bars)
Closes at : 175 psig 10 PSI (12 bars)
e. Refrigerant charge
Refer to Table 1-1.
f. Compressor Pressure Regulating Valve (CPR)
115V only
191 psig (1.3 Bar)
g. Thermostatic Expansion Valve (TXV)
Superheat setting = 4_C (7.2_F) at refrigerated
compartment temperature of - 20_C (0_F).
h. Low Pressure switch (LP)
Opens at : --13.23 in HG 6 in HG
(-- 0.45 0.2 bar)
Closes at : +6.5 psig 3 psig
(+0.44 0.2 bar)
i. Quench Thermostat (BPT)
Opens at: 248_F (120_C)
Closes at: 220_F (104_C)

1--9

62-10848

1.6.3 Electrical Data


a. Fan Motors
Evaporator Fan Motor (EFM)
Bearing Lubrication
Factory Lubricated
Horse Power
0.1 kw
Operating Amps
10.8 amps
Speed
2800/3000 rpm

Condenser Fan Motor (CFM)


Bearing Lubrication
Factory Lubricated
Operating Amps
Speed

10 amps
3300 rpm

b. Standby Compressor Speed


1740 rpm -- 60 hz
c. Standby Motor Ratings
Voltage

Type of Connection

Phase

115/1/60

208/1/60

230/1/60

230/3/60

kW

1.5

HP

* MRA = Maximum Rotor Amps


LRA = Locked Rotor Amps
Resistance = 9.2
d. Road Compressor Clutch
Amp Draw = 3.75A
Resistance = 3.2
e. Hot Gas Solenoid Valve (HGS1) Coil
Amp Draw = 1.33 Amp
Resistance = 9.2
f. Condenser Pressure Control Valve (HGS2) Coil
Amp Draw = 1.65 Amp
Resistance = 7.3
g. Quench Valve (BPV) Coil
Amp Draw = 1.16 Amp
Resistance = 10.3
h. Standby Motor Contactor Coil
Amp Draw = 0.19 Amp
Resistance = 60
1.6.4 Torque Values
Assembly
Standby compressor platform
Standby motor platform
Standby motor pulley
Evaporator fan motor
Evaporator fan
Condenser - frame
Mounting Bolts

62-10848

ft-lb
40
40
32
13
7
7
44 to 60

kg-m
5.5
5.5
4.5
1.8
1.0
1.0
6 to 8

1--10

Speed

Contactor Data
MRA*

LRA*

1745 rpm

18.3

132.5

1690 rpm

9.2

70

1715 rpm

8.5

60

1700 rpm

5.9

40

1.7 SAFETY DEVICES


System components are protected from damage caused by unsafe operating conditions by automatically shutting
down the unit when such conditions occur. This is accomplished by the following fuses and safety devices.
Automatic
restart
Safety Device
Device setting
Unsafe Conditions
with fault
cleared
1

Excessive drop in pressure

Automatic reset of low


pressure switch (LP)

Excessive current draw on all mi- Electronic relay


croprocessor outputs (evaporator
and condenser fan)

YES

Excessive current draw control


circuit

Fuse on electronic board

NO

Excessive current draw motor


compressor

230 = Overload relay


115/1/60 = Circuit Breaker

Excessive current draw evaporator and condenser fan motors

Electronic relay

Excessive compressor discharge Automatic reset of High


pressure
pressure switch (HP1)

Excessive current draw standby


clutch

Fuse F3 (a)

Excessive current draw unit in


standby operation

Standby fuse F2 (a)

Excessive current draw unit in


road operation

Fuse F1 (b)

10

Connection error on primary


transformer

Fuse F4 and/or F5 (a)

11

Excessive temperature on stand- Internal Motor Thermostat


by motor bearing
(PT0)

YES

12

Clutch malfunction - road (exces- Electronic relay


sive current draw)

YES

Self-protected opening
Opens 311_ F (155 C)

13

Clutch malfunction - road (insuffi- Electronic relay


cient current draw)

YES

Detection of min. threshold


at 750 mA

14

Double power supply (road +


standby)

Microprocessor
YES

Display on Cab Command


until one of the 2 power supplies have been disconnected.

15

Low battery voltage

Microprocessor

YES

Cutout/cut-in at 10 V

16

Excessive current draw on ignition circuit (Neiman)

Fuse FI

YES

YES/NO
NO
YES

Cutout : --13.23 in HG
(-- 0.45 bar)
Timer 5 min
Self-protected opening
Self-protected opening
Depending on Selection
See electrical wiring diagram
Self-protected opening

YES

Cutout : 355 psig (24.5 bar )

NO

Opens at 5 A (12 V)

NO
NO
NO

NO

Opens at 30 A (12 V)
Opens at 30 A (12 V)
Opens at 4 A
Self-protected opening

Opens at 1 A

(a) On road/standby unit only (b) This fuse is located close to the vehicle battery (12 v).

1--11

62-10848

1.8 REFRIGERANT Circuit


1.8.1 Cooling (See Figure 1-9)
When cooling, the unit operates as a vapor compression
refrigeration system. The main components of the
system are the reciprocating compressor, air-cooled
condenser, thermostatic expansion valve and the direct
expansion evaporator.
The compressor raises the pressure and temperature of
the refrigerant and forces it through the discharge check
valve and condenser pressure control valve into the
condenser tubes. The discharge check valves prevent
reverse flow through the non operating compressor.
When operating on the road compressor, the flow also
passes through the oil separator where oil is removed
and returned to the road compressor.
The condenser fan circulates surrounding air over the
outside of the condenser tubes. Heat transfer is thus
established from the refrigerant gas (inside the tubes) to
the condenser air (flowing over the tubes). The
condenser tubes have fins designed to improve the
transfer of heat. This removal of heat causes the
refrigerant to liquefy. Liquid refrigerant flows from the
condenser to the receiver.
The receiver stores the additional charge necessary for
low ambient operation and for heating and defrost
modes.
The refrigerant leaves the receiver and flows through a
manual receiver shut-off valve (king valve).
The refrigerant then flows through a check valve. The
check valve serves to prevent reverse flow of refrigerant
during the heating/defrost cycle.
The refrigerant then flows through the filter-drier, where
an absorbent keeps it dry and clean. The refrigerant
then flows though a sight glass. The sight glass is fitted
with an indicator that changes color to indicate moisture
content of the refrigerant. The refrigerant then flows
through the subcooler which removes additional heat
from the liquid to improve system efficiency.
The liquid than enters the thermostatic expansion valve
(with external pressure equalizer) which regulates the
flow rate of refrigerant towards the evaporator in order to
obtain maximum use of the evaporator heat transfer
surface.

62-10848

1--12

The evaporator tubes have aluminium fins to increase


heat transfer; therefore heat is removed from the air
circulated through the evaporator. This cold air is
circulated throughout the truck to maintain the cargo at
the desired temperature.
The transfer of heat from the air to the low temperature
liquid refrigerant causes the liquid to vaporize. The
vapor at low temperature and is then drawn out by the
compressor. From this point, the cycle starts over.
On 115v units the refrigerant then enters the
compressor regulating valve (CPR) which regulates
refrigerant pressure entering the compressor. The cycle
then starts over.
The quench valve opens as required to maintain a
maximum discharge temperature. (Refer to section
1.6.2 for settings.)
1.8.2 Heat And Defrost (See Figure 1-10)
When refrigerant vapor is compressed to a high
pressure and temperature in a compressor, the
mechanical energy necessary to operate the
compressor is transferred to the gas as it is being
compressed. This energy is referred to as the heat of
compression and is used as the source of heat during
the heating or defrost cycle.
When the microprocessor activates heating or defrost,
the hot gas solenoid valve energizes and the condenser
pressure control valve energizes, closing the port to the
condenser and opening a port which allows heated
refrigerant vapor to flow directly to the evaporator coil .
The main difference between heating and defrosting is
that when in heating mode the evaporator fans continue
to run thus circulating the air throughout the truck to heat
the product. When in defrost, the evaporator fans stop,
thus allowing the heated vapor to defrost any ice
build-up on the coil.
When the pressure is above the setting of the
condenser pressure control switch, the condenser
pressure control valve (HGS2) is closed to prevent
additional pressure rise in the system. When pressure is
below the setting of the condenser pressure control
switch, the valve is opened to pressurize the receiver
and force additional refrigerant into the system and
increase heating capacity.

QUENCH VALVE (BPV)

TXV EQUALIZER LINE

SUBCOOLER

TXV
FILTER DRIER/SIGHTGLASS

EVAP.

LP

CHECK
VALVE
DEFROST
ELEMENT

CONDENSER

KING VALVE

RECEIVER

HOT GAS SOLENOID


VALVE (HGS1)

SUCTION
CHARGING
PORT
OIL SEPARATOR

CPR
115V
ONLY

DISCHARGE
CHECK VALVE
MANIFOLD
ASSEMBLY

HP1

COND.
PRESS.
CONTROL
VALVE
(HGS2)

HP2

DISCHARGE
CHARGING
PORT
QUENCH
THERMOSTAT
(BPT)

STAND BY
COMPRESSOR
ROAD
COMPRESSOR

DISCHARGE
LIQUID
LIQUID INJECTION LINE
HOT GAS LINE
SUCTION LINE

Figure 1-9 Refrigeration Circuit Cooling Cycle


1--13

62-10848

QUENCH VALVE
(BPV)

TXV EQUALIZER LINE

SUBCOOLER

TXV
FILTER DRIER/SIGHTGLASS

EVAP.
CHECK
VALVE

LP
DEFROST
ELEMENT

CONDENSER

KING VALVE

RECEIVER

HOT GAS SOLENOID


VALVE (HGS1)

SUCTION
CHARGING
PORT
OIL SEPARATOR

CPR
115V
ONLY

DISCHARGE
CHECK VALVE
MANIFOLD
ASSEMBLY

HP1

COND.
PRESS.
CONTROL
VALVE
(HGS2)

HP2

DISCHARGE
CHARGING
PORT
QUENCH
THERMOSTAT
(BPT)

STAND BY
COMPRESSOR
ROAD
COMPRESSOR

DISCHARGE
LIQUID
LIQUID INJECTION LINE
HOT GAS LINE
SUCTION LINE

Figure 1-10 Refrigeration Circuit Heating Cycle

62-10848

1--14

SECTION 2
OPERATION
viewed on the display.

2.1 CONTROL SYSTEM


2.1.1 Introduction

CAUTION
Under no circumstances should anyone attempt to service the microprocessor module and Cab Command. Should a problem
develop with the control system, contact
your nearest Carrier Transicold dealer for
replacement components.
The Control System consists of the microprocessor
module (Figure 1-6), Cab Command (Figure 2-1) and
interconnecting wiring.
a. The Microprocessor Module includes the temperature control software and necessary input/output circuitry to interface with the unit controls.
b. The Cab Command is remotely mounted in the truck.
The Cab Command includes the LCD display and
keypad. The keypad and display serve to provide
user access and readouts of microprocessor information. The information is accessed by keypad
selections and viewed on the display.
1.8.3 Microprocessor Module
The microprocessor controls the following functions:
a. Maintains the refrigerated compartment temperature at set point by regulating the cooling, heat, off
mode and automatic defrost cycles.
b. Permanently displays the return air temperature and
on request the set point temperature.
c. Digital display and selection of data.
For further details on digital message display, see
section 2.6.
2.1.2 Cab Command
The Cab Command is mounted in the cab and allows the
driver to carry out the control operations:

Figure 2-1 Cab Command


a. Display
The digital display consists of 3 alphanumeric
characters. The default value displayed is the
refrigerated compartment temperature.
The
microprocessor enables selection of the display in
degrees Celsius or Fahrenheit. The display also
includes settings for defrost operation (dF). The display
also includes three LEDs:
Digital Display
Standby operation LED
Road operation LED
Unit operating LED
D Green : cycling (left-hand side)
D Red : malfunction (right-hand side)

start up and shut-down the unit


automatic start-up in road or standby mode
adjust the set point
defrost
The driver can display the refrigerated compartment
temperature, and see whether the set point is being
maintained by checking the green indicator. The
indicator lights up red in the event of a malfunction.
When the battery voltage is too low, a fail-safe system
shuts down the unit. Unit restart is automatic and
time-delayed if the voltage rises to the normal level.
The command consists of the display and the keypad.
The keypad and display serve to provide user access
and readouts of microprocessor information. The
information is accessed by keypad selections and

2--1

62-10848

b. Red Light Status


After an alarm has been present for 15 minutes, the red
unit indicating light flashes at 3 Hz. The light will
continue to flash at 0.5 Hz until the temperature returns
to set point differential. At that point the steady green
indicator light will light and the alarm become inactive.

Unit operating LEDs


a. Green Light Status for Standby Units
Under normal operation, the green LED will indicate the
temperature control status as follows:
Setpoint + 9F Green LED
flashing 3 Hz
(5_C)
Green LED
flashing 0.5 Hz

NULL
BAND

Steady
green LED
Steady
green LED
Green LED
flashing 0.5 Hz

Setpoint -- 9F
(5_C)

Green LED
flashing 3 Hz

c. Keypad
The keypad consists of six keys that enable the operator
to activate various functions, display operating data and
modify operating parameters.

Setpoint +
differential of
1.8F (1C),
3.6F (2C) or
5.4F (3_C)

Manual defrost control key


Unit start-up key

SETPOINT

Unit shut-down key in standby or road


mode
On road operation, the unit can also be
shut down with the ignition key.

Setpoint -differential of
1.8F (1C),
3.6F (2C) or
5.4F (3_C)

Unit data and function modification keys


The SET key, together with the + and -keys, enables display and modification
of unit operating data.
The display scrolls through parameters
each time the SET key is pressed.

Figure 2-2 Green Light Status -- Standby


a. Green Light Status for Road Only Units
Under normal operation, the green LED will indicate the
temperature control status as follows:

Steady green
LED

NULL
BAND

Green LED is
OFF

Green LED
flashing 1 Hz

Decrease key for selected data


Increase key for selected data

COOLING

SETPOINT

HEATING

Figure 2-3 Green Light Status -- Road Only

62-10848

2--2

2.2 START--UP

CAUTION

2.2.1 Inspection
Before starting the truck engine or connecting standby
power check the following

If starting unit for the first time after installation the compressor pressure regulating
valve will need to be reset (refer to paragraph 4.14)

a. Check condenser coil for cleanliness


b. Check condition of refrigerant hoses
c. Check condition and tension of compressor belt(s)

CAUTION

d. Check condition of condenser fan blade, motor and


brushes

If starting unit for the first time after installation or starting after adding/removing an
optional feature or if Owners operating parameters have changed the Configuration
will need to be reset (refer to paragraph 2.9)

e. Check truck battery fluid level


f. Check truck battery and terminal connections -- clean
and tighten as necessary

WARNING

Depending on desired mode of operation, either start


the vehicle engine or close the power source circuit
breaker.

Inspect battery cables for signs of wear,


abrasion or damage at every Pre--Trip
inspection and replace if necessary.
Also check battery cable routing to ensure that clamps are secure and that
cables are not pinched or chafing
against any components.

Press the ON key to start the unit


(For Standby units, start up is
time delayed for 10 seconds.
For Road units, start up is time
delayed for 40 seconds.)
The digital display of the Cab
Command displays the refrigerated compartment temperature.

g. Check defrost water drains from evaporator

Check that temperature set point


is correct by pressing the SET
key. The set point temperature is
highlighted on the digital display.

h. Check evaporator coil for cleanliness


i. Check condition of evaporator fan blades, motor and
brushes
j. Check oil level in standby compressor sight glass

2.3 SET POINT ADJUSTMENT

2.2.2 Connect Power

It is possible to increase or decrease the set point by


whole numbers until the required set point is displayed.
If display stays highlighted, the set point displayed has
not been validated.
The new setting for the set point is validated by pressing
the SET key.

If the unit is to be operated in the standby mode, connect


power as follows:

WARNING
Do not attempt to connect or remove power
plug before ensuring the unit is OFF (press
OFF key on Cab Command) and external
power circuit breaker is open.

Displays the set point temperature


Decrease the set point

WARNING

Increase the set point

Make sure the power plug is clean and dry


before connecting to any power source

Validate set point temperature


Return to display of refrigerated
compartment temperature.

a. Check that the external power source corresponds to


the characteristics of the unit (see paragraph 1.6.3
step c.). Make sure external power source circuit
breaker is open.

2.4 MANUAL DEFROST


Check that refrigerated compartment temperature is
40F (4.4C) or lower.

b. Make sure unit is OFF by pressing the OFF button on


the Cab Command.

Press manual defrost key to


initiate manual defrost.

c. Plug the power cord into unit receptacle.


2.2.3 Starting
2--3

62-10848

2.5 DEFROST CYCLE ADJUSTMENT


Defrost parameters may be set to eliminate defrost,
decrease the time between defrosts, allow full
automatic defrost, increase the time between defrosts
or set a forced interval between defrosts. To adjust the
defrost cycle, do the following:

2.6 ALARM DISPLAY


In the event of a malfunction the unit will shut down and
the Cab Command will display an error message or
alarm message. The message will remain displayed
until the malfunction is corrected. If standby power is
connected and the malfunction is such that standby
operation can be allowed, the unit will start in the
standby mode. A listing of the error messages and
alarm codes is provided in Table 2-1.
2.6.1 Accessing Alarm Messages
To access the alarm messages:

Shut-down unit.
+
OR

Display parameters.

Press SET for 5 seconds : enables access to alarm messages.

Modify parameters.
Validate modified settings
Return to display of refrigerated
compartment temperature.

OR

In the event of more than one alarm,


press the + or -- keys to list them.

NOTE
If no key is pressed within 5 seconds of
adjusting settings the system reverts to displaying the refrigerated compartment temperature. Only validated changes are recorded.
Table 2-1 Alarms For Road Only Units
Malfunction
ALARM
Description
Codes
ONLY
Red LED flashes
No malfunction.
A00
Unit in operation.

A01
A02
A04
A06
A07
A09
A10
A11

High or Low pressure switch

High or Low pressure switch

Road clutch malfunction

Condenser fan motor fault

Evaporator fan motor fault

Hot gas solenoid valve malfunction (HGS1)

Quench valve malfunction (BPV)

Condenser pressure control valve (HGS2)

A15

Setpoint adjusted out of the range --20.2 to


86F (-- 29C/+ 30C) or below the
programmed low threshold

BAT

Low battery voltage

EE

Probe malfunction or evaporator temperature


out of limits [-- 49 to 174F (-- 45 to 79C)]

Err

Programming error on part of operator

62-10848

ALARM AND UNIT SHUT


DOWN

2--4

Table 2-2 Alarms For Standby Units


Malfunction
Codes

ALARM
ONLY

Description

A00

Red LED flashes


No malfunction.
Unit in operation.

A01

Low pressure switch

A02

High pressure switch

A03

Electric motor overload


protection on start-up

A04
A05
A06
A07
A08
A09
A10
A11
A12
A13
A14

Road clutch malfunction

Standby clutch and contactor

Condenser fan motor fault

Evaporator fan motor fault

Heating option command

Hot gas valve malfunction (HGS1)

Quench valve malfunction (BPV)

Condenser pressure control valve (HGS2)

High temperature alarm

Low temperature alarm

Defrost alarm > 45 minutes

A15

Setpoint adjusted out of the range -- 20.2 to


86F (-- 29C/+ 30C) or below the
programmed minimum set point

BAT

Low battery voltage

EE

Probe malfunction or evaporator temperature


out of limits [-- 49 to 174F (-- 45 to 79C)]

Err

Programming error on part of operator

ALARM AND UNIT SHUT


DOWN

X -- AFTER 3 SUCCESSIVE
FAULTS
X -- AFTER 5 SUCCESSIVE
FAULTS
X -- AFTER 3 SUCCESSIVE
FAULTS

SEE SECTION 2.6.2

X
has been noted and service is complete, the alarm list
may be cleared. To clear the alarm messages:

2.6.2 Low Battery Voltage Alarm for Road Only


Units
There is a 40 second time delay during start--up. After
this delay if the battery voltage drops below 10V 0.2V
for Standby units or 10.5V 0.5V for Road only units, the
microprocessor will react 20 seconds later and the unit
will go out of temperature control mode. The
microprocessor will check the voltage after another 20
seconds. If battery voltage still has not risen, the unit will
remain out of temperature control mode for another 10
minutes, and the battery alarm will be activated and the
Cab Command will display the message bAt. Unit will
return to temperature control mode if battery voltage
has risen after 10 minutes. If the battery voltage has not
risen after this 10 minute period the unit will remain out
of temperature control mode another 2 minutes and the
microprocessor will check the battery voltage every 2
minutes. Unit will return to temperature control mode in
its current configuration when battery voltage rises to
10V 0.2V for Standby units or 10.5V 0.5V for Road
only units.

Press the ON, the + and


the -- keys at the same
time.

2.7 CHECKING THE EEPROM VERSION


Start up unit
Press the SET key to display eeprom
version number.
Press SET key to return to refrigerated
compartment temperature.
2.8 STOPPING THE UNIT

2.6.3 Clearing Alarm Messages


The alarm list provides information on current alarms
and past alarms which may be helpful in trouble
shooting unit problems. Once all the alarm information

Press the OFF key or turn the ignition


key to off position.

2--5

62-10848

6 hours) using the (+) or (--) keys. Selection MUST be


validated by pressing the SET key.
3. The next steps must be performed with the unit ON:

2.9 MICROPROCESSOR CONFIGURATION

CAUTION
If starting unit for the first time after installation or starting after adding/removing an
optional feature or if Owners operating parameters have changed, the Configuration
will need to be reset.

Unit start-up

THEN

2.9.1 ROAD ONLY FUNCTIONAL SETTINGS


The procedure for adjusting the functional parameters is
as follows:
1. The temperature display is selectable between Fahrenheit and Celsius. Units are configured for Celsius
from the factory. To set the display to Fahrenheit, the
selection jumper must be removed and discarded.
See Figure 1-6.
NOTE
The board contains another set of pins similar to
the Degrees C/Degrees F selection jumper,
marked as J1. This jumper is not used for unit
operation, but it is used during the microprocessor controller manufacturing process. DO NOT
CONNECT THE J1 PINS TOGETHER.
2. The following steps must be performed with the unit
OFF:

OR

NOTE
If no buttons are depressed within 5 seconds of
pressing the ON key or modifying parameters,
the Cab Command reverts to refrigerated compartment temperature display and the configuration procedure is aborted.
a. The minimum set point parameter is displayed. The
minimum set point can be selected by scrolling
through available options [-- 20F (-- 28.9C), -- 4F
(-- 20C), 32F (0C)] using the (+) or (--) keys. Factory setting is -- 20F. Selection MUST be validated by
pressing the SET key.
b. The null mode differential temperature is displayed
next. This setting determines the temperature difference between refrigerated compartment temperature and set point that controls compressor cycling.
The differential can be selected by scrolling through
available options [1.8F (1C), 3.6F (2C), or 5.4F
(3C)] using the (+) or (--) keys. Factory setting is
3.6F (2C). Selection MUST be validated by pressing the SET key.
c. The ON/OFF (Continuous airflow) parameter for the
evaporator fan is displayed next. This feature determines whether the evaporator fan is on or off when
the unit cycles off upon reaching set point. The factory
setting is OFF. Change setting by using the (+) or (--)
keys. Selection MUST be validated by pressing the
SET key.
d. The return air temperature will be displayed after the
above sequence.

Shut-down unit.
THEN
OR

Hold both keys


momentarily in order to
display parameters.
Modify parameters. (See a.
and b. below)
Validate modified settings.

NOTE
If no buttons are depressed within 5 seconds of
pressing the Defrost and On Keys (Step 2 of the
above procedure) or modifying parameters, the
Cab Command reverts to refrigerated compartment temperature display and the configuration
procedure is aborted.
a. The defrost duration parameter is displayed. This setting determines the length of time in minutes the unit
will remain in defrost once defrost is initiated. The defrost duration can be selected by scrolling through
available options (10, 20, 25, 30 or 45 minutes) using
the (+) or (--) keys. Selection MUST be validated by
pressing the SET key.
b. The defrost interval parameter is displayed next. This
setting determines the time between defrosts in
hours. The defrost interval can be selected by scrolling through available options (0, 1, 1.5, 2, 2.5, 3, 4, 5,

62-10848

THEN

Press the +, then -- then


DEFROST keys. All
keys should be held
momentarily after
pressing in the correct
sequence.
Modify parameters.
(See a., b. and c.
below)

2--6

2.9.2 ROAD/STANDBY FUNCTIONAL SETTINGS

Unit start-up

The procedure for adjusting the functional parameters is


as follows:
1. The temperature display is selectable between Fahrenheit and Celsius. Units are configured for Celsius
from the factory. To set the display to Fahrenheit,
move the Celsius end of the jumper to the Fahrenheit
pin as shown in Figure 2-4.

THEN

OR
C

THEN

Press the +, then -- then


DEFROST keys. All
keys should be held
momentarily after
pressing in the correct
sequence.
Modify parameters.
(See a., b., c. and d.
below)

NOTE
Keys must be pressed before the unit starts.
NOTE
If no buttons are depressed within 5 seconds of
pressing the ON key or modifying parameters,
the Cab Command reverts to refrigerated compartment temperature display and the configuration procedure is aborted.

Figure 2-4 Temperature Selection Jumper


NOTE
The board contains another set of pins similar to
the Degrees C/Degrees F selection jumper,
marked as J1. This jumper is not used for unit
operation, but it is used during the microprocessor controller manufacturing process. DO NOT
CONNECT THE J1 PINS TOGETHER.

a. The minimum set point parameter is displayed. The


minimum set point can be selected by scrolling
through available options [-- 20F (-- 28.9C), -- 4F
(-- 20C), 32F (0C)] using the (+) or (--) keys. Factory setting is -- 20F. Selection MUST be validated by
pressing the SET key.
b. The null mode differential temperature is displayed
next. This setting determines the temperature difference between refrigerated compartment temperature and set point that controls compressor cycling.
The differential can be selected by scrolling through
available options [1.8F (1C), 3.6F (2C), or 5.4F
(3C)] using the (+) or (--) keys. Factory setting is
3.6F (2C). Selection MUST be validated by pressing the SET key.
c. The ON/OFF (Continuous airflow) parameter for the
evaporator fan is displayed next. This feature determines whether the evaporator fan is on or off when
the unit cycles off upon reaching set point. The factory
setting is OFF. Change setting by using the (+) or (--)
keys. Selection MUST be validated by pressing the
SET key.
d. The 2ET or 3ET parameter is now displayed. This
feature determines heating mode operation based on
the presence of a condenser pressure control valve.
Since all 30S units covered by this manual have a
condenser pressure control valve installed, 3ET must
be selected. This enables cooling, null, and heating
modes of operation. Selection MUST be validated by
pressing the SET key. Change setting by using the (+)
or (--) keys. Selection MUST be validated by pressing
the SET key.

2. The following steps must be performed with the unit


OFF:
Shut-down unit.
THEN
OR

Hold both keys


momentarily in order to
display parameters.
Modify parameters. (See a.
and b. below)
Validate modified settings.

NOTE
If no buttons are depressed within 5 seconds of
pressing the Defrost and On Keys (Step 2 of the
above procedure) or modifying parameters, the
Cab Command reverts to refrigerated compartment temperature display and the configuration
procedure is aborted.
a. The defrost interval parameter is displayed. This setting determines the time between defrosts in hours.
The defrost interval can be selected by scrolling
through available options. Settings are for either automatic defrost (AUT) or fixed time intervals between
1 to 6 hours. The setting can be selected by pressing
the (+) or (--) keys. Selection MUST be validated by
pressing the SET key.

WARNING
Beware of unannounced starting of the
unit. The unit may cycle the fans and operating compressor unexpectedly as control requirements dictate. Press OFF key on the
Cab Command and disconnect power plug.

The next steps must be performed with the unit ON:


2--7

62-10848

SECTION 3
TEMPERATURE CONTROL
3.1 SEQUENCE OF OPERATION
General operation sequences for cooling, null, and
heating are provided in the following paragraphs. The
microprocessor automatically selects the mode
necessary to maintain refrigerated compartment
temperature at set point.

COOL
+ 1.8_F (+ 1_C)
or + 3.6_F (+ 2_C )

3.1.1 Perishable Mode

or + 5.4_F (+ 3_C )

The unit operates in the perishable mode with set points


above 10F (--12C)

UNIT STOPPED

a. With return air temperature above set point and decreasing, the unit will be cooling with the compressor
and evaporator fans operating. (See Section 1.8.1 for
a description of the refrigeration circuit during cooling) The condenser fan will operate for the first three
minutes after start up then operate under the control
of the condenser pressure control switch (HP2). The
green unit operating LED will operate in accordance
with Figure 2-2 or Figure 2-3.

SETPOINT

-- 1.8_F (-- 1_C)


HEAT

or -- 3.6_F (-- 2_C)


or -- 5.4_F (-- 3_C)
(setting)

Figure 3-1 Operating Sequence -- Perishable


Mode
3.1.2 Frozen Mode
The unit operates in the frozen mode with set points at or
below 10F (--12C). Operation in the frozen mode is the
same as in the perishable mode except no heating takes
place.

b. If discharge temperature increases to the set point of


the quench thermostat (BPT), the thermostat will
close, energizing the quench valve (BPV). This will allow liquid into the suction line in order to cool compressor. Once the discharge temperature decreases
to the certainty of the PPT, the thermostat will open,
DE--energizing the PP.
c. Once temperature decreases to the certainty, the unit
will enter the null mode. If the continuous air flow parameter is set to ON, the evaporator fans will continue
to operate with all other components OFF. If the continuous air flow parameter is OFF, the evaporator
fans and all other components will be OFF. A 5 minute delay is required before restart is allowed.

COOL

+ 1.8_F (+ 1_C )
or + 3.6_F (+ 2_C )
or + 5.4_F (+ 3_C )

d. If temperature increases during the null mode, the


unit will restart in cooling.

SETPOINT

e. If temperature continues to decrease the unit will enter the heating mode with the compressor and evaporator fans operating and the hot gas solenoid valve
(HGS1) energized (open). The condenser fan and
condenser pressure control valve (HGS2) will operate under the control of the condenser pressure
switch (HP2). If the engine coolant or electric heat option is installed, the optional heaters will also be energized. (See Section 1.8.2 for a description of the refrigeration circuit during heat and defrost.)

UNIT STOPPED

-- 1.8_F (-- 1_C)


or -- 3.6_F (-- 2_C)
or -- 5.4_F (-- 3_C)
(setting)

Figure 3-2 Operating Sequence -- Frozen Mode

3--1

62-10848

During defrost, the evaporator fans shut down and


operation of the condenser fan is controlled by the
microprocessor. The end of the cycle is controlled by the
opening of the defrost termination thermostat. (See
Section 1.8.2 for a description of the refrigeration circuit
during heat and defrost.)
3.3 MINIMUM OFF TIME
Once the unit has cycled off, it will remain off for the
minimum off time of 5 minutes. This prevents the unit
from rapid cycling due to changes in air temperature. Air
temperature in the refrigerated compartment changes
rapidly but it takes time for the product temperature to
change.

3.2 DEFROST CYCLE


Defrost is an independent cycle overriding cooling and
heating functions in order to melt frost and ice from the
evaporator when necessary. Defrost may be initiated by
the microprocessor or manually by the operator once
the defrost termination thermostat has closed. (See
Section 1.6.2 for settings). In defrost mode, the
microprocessor displays dF on the cab command and
set point is no longer displayed.

62-10848

3--2

SECTION 4
SERVICE

WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and operating compressor
unexpectedly as control requirements dictate. Press OFF key on the cab command and disconnect
power plug.

CAUTION
Compressor failure will occur if inert gas brazing procedures are not used on units with
R134A and POE oil. For more information see Technical Procedure 98-50553-00 -- Inert Gas
Brazing.
NOTE
To avoid damage to the earths ozone layer, use a refrigerant recovery system whenever removing
refrigerant. When working with refrigerants you must comply with all local government environmental
laws, U.S.A. EPA section 608.
Table 4-2 Service Category Descriptions
4.1 MAINTENANCE SCHEDULE
Service A 1. Check the tension of the compressor
Regular servicing is required in order to optimize the life
belt(s).
and reliability of your unit. The recommended scheduled
2 .Check that the vehicle engine idles
maintenance intervals and categories are provided in
correctly with unit operating. Check
Table 4-1 while descriptions of the service procedures
compressor mounting hardware and
to be carried out under each category are provided in
belt tension. (Paragraph 4.2)
Table 4-2
3 .Check the tightness of bolts and
Table 4-1 Maintenance Schedules
screws and that the unit is correctly
fastened onto the box.
5
30
60
90 120 150 180 210
Kilometers
000 000 000 000 000 000 000 000
Service B 1 . Clean evaporator & condenser.
(Paragraphs 4.18 & 4.19)
3
18
36
54
72
90 108 126
Miles
2. Replace the road and standby com000 000 000 000 000 000 000 000
pressor belt(s).
J
J
J
J
J
J
J
J
Service A
3. Check and if required replace the
filter-drier. (Paragraph 4.10)
J
J
J
J
J
J
J
Service B
4. Check the operation of cab comJ
J
J
Service C
mand.
J
Service D
5. Check the defrost
DCut-in
Refrigerant : Type R134a.
DFan shut-down
DCut-out
Road compressor oil type: The road compressors are
DDefrost water drain
supplied with CARRIER POLYESTER (POE) oil. Oils of
Service C 1. Check the operation of the evaporaPAG type are strictly incompatible with the operation
tor and condenser fans. Change the
of this unit, never use an oil other than that approved
condenser/evaporator motor brushes.
by CARRIER.
2. Change the compressor oil. Use
polyester oil (POE) approved by CARRIER. Refer to paragraph 1.6.1.
Service D 1. Change the removable relays, fuses
and capacitor (if any) in the control
box.

4--1

62-10848

Table 4-3. Belt Tension (See Figure 4-2)

4.2 BELT MAINTENANCE AND ADJUSTMENT

BELTS

WARNING

Standby Motor
to Compressor

Beware of V-belt and belt-driven components as the unit may start automatically.
A belt tension gauge provides an accurate and easy
method of adjusting belts to their proper tension.
Properly adjusted belts give long lasting and efficient
service. Too much tension shortens belt and bearing life,
and too little tension causes slippage and excessive belt
wear. It is also important to keep belts and sheaves free
of any foreign material which may cause the belts to slip.
The Belt Tension gauge can be used to adjust all belts.
The readings which we specify for Carrier Transicold
units are applicable only for our belts and application, as
the tension is dependent on the size of the belt and
distance between sheaves. When using this gauge, it
should be placed as close as possible to the midpoint
between two sheaves.

New Install
Tension
90 ft./lbs
(122 Nm)

Running
Tension
80 to 90 ft./lbs
(108 to 122
Nm)

4.2.1 Standby Motor--Compressor V-Belt


a. Loosen the retaining bolts of the standby motor support plate.
b. Replace the V-belt. Position the motor to correct belt
tension. Tighten the motor retaining bolts.
4.3 INSTALLING R-134A MANIFOLD GUAGE SET
A R-134a manifold gauge/hose set with self-sealing
hoses is required for service of models covered within
this manual. The manifold gauge/hose set is available
from Carrier Transicold. (Carrier Transicold P/N
07-00294-00, which includes items 1 through 6,
Figure 4-3). To perform service using the manifold
gauge/hose set, do the following:
4.3.1 Preparing Manifold Gauge/Hose Set For Use
a. If the manifold gauge/hose set is new or was
exposed to the atmosphere it will need to be evacuated to remove contaminants and air as follows:
b. Back seat (turn counterclockwise ) both field service
couplers (see Figure 4-3) and midseat both hand
valves.
c. Connect the yellow hose to a vacuum pump and an
R-134a cylinder.

Figure 4-1 Belt Tension Gauge


(Carrier Part Number 07--00203--00)
Belt tension depends on each kit. Refer to Installation
Instructions provided with the kit for belt tension
requirements. In each kit installation instruction, we
indicate the belt tension (given with belt tension gauge
P/N 07-00203-00.
When installing a new V-belt the tension should be
somewhat higher than specified and readjusted after
allowing the unit to run for some time.
Standby
motor

d. Evacuate to 10 inHg (254mmHg) and then charge


with R-134a to a slightly positive pressure of 1.0 psig
(0.07 Bar).
e. Front seat both manifold gauge set hand valves and
disconnect from cylinder. The gauge set is now
ready for use.
4.3.2 Connecting Manifold Gauge/Hose Set
To connect the manifold gauge/hose set for reading
pressures, do the following:

Compressor

a. Remove access valve cap.


b. Connect the field service coupler (see Figure 4-3) to
the access valve.
c. Turn the field service coupling knob clockwise, which
will open the system to the gauge set.
1. Standby Motor-Compressor V-belt

d. Read system pressures.


e. Repeat the procedure to connect the other side of
the gauge set.

Figure 4-2 Layout of V-belt

62-10848

4--2

4.3.3 Removing the Manifold Gauge Set


1. While the compressor is still ON, backseat the high
side service valve.
2. Midseat both hand valves on the manifold gauge set
and allow the pressure in the manifold gauge set to
be drawn down to low side pressure. This returns
any liquid that may be in the high side hose to the
system.

4.4 REMOVING THE REFRIGERANT CHARGE


NOTE
To avoid damage to the earths ozone layer, use
a refrigerant recovery system whenever removing refrigerant.
Connect a refrigerant recovery system (Carrier P/N
MVS--115--F--L--CT (115V) or MVS--240--F--L--CT
(240V) ) to the unit to remove refrigerant charge. Refer
to instructions provided by the manufacturer of the refrigerant recovery system.

CAUTION
To prevent trapping liquid refrigerant in the
manifold gauge set be sure set is brought to
suction pressure before disconnecting.

4.4.1 Refrigerant Removal From A Non--Working


Compressor.

3. Backseat the low side service valve. Backseat both


field service couplers and frontseat both manifold set
hand valves. Remove the couplers from the access
valves.
4. Install both service valve stem caps and access
valve caps (finger-tight only).
Low Pressure
Gauge

To remove the refrigerant from a compressor that is not


operational, do the following:
a. Attach a manifold gauge set as shown in Figure 4-3
b. Recover refrigerant with a refrigerant recovery system.

High Pressure
Gauge

c. Service or replace components as required and leak


check the entire system. (See Section 4.5).
4.5 REFRIGERANT LEAK CHECKING

Closed
(Frontseated)
Hand Valve

Opened
(Backseated )
Hand Valve
2

To Low Side
Access Valve
3
BLUE

4
6
(Blue Knob)
1.
2.
3.
.
4.
5.
6.

A refrigerant leak check should always be performed


after the system has been opened to replace or repair a
component. To check for leaks in the refrigeration
system, perform the following procedure:
NOTE
Use only R134a to pressurize the system. Any
other gas or vapor will contaminate the system
which will require additional purging and evacuation of the high side (discharge) of the system.

To High Side
Access Valve

3
RED

a. If system is without refrigerant, charge system with


refrigerant to build up pressure between 30 to 50 psig
(2 to 3.4 Bars). Remove refrigerant cylinder and leak
check all connections.

3
YELLOW 4

b. Add sufficient nitrogen to raise system pressure to


150 to 200 psig (10.21 to 13.61 bar).

5
(Red Knob)

c. Check for leaks. The recommended procedure for


finding leaks in a system is with an electronic leak detector. (Carrier P/N 07--00295--00). Testing joints
with soap suds is satisfactory for locating large leaks
but be necessary when an electronic leak detector will
not function correctly.

Manifold Gauge Set


Hose Fitting (0.5-16 Acme)
Refrigeration and/or Evacuation Hose
(SAE J2196/R-134a)
Hose Fitting w/O-ring (M14 x 1.5)
High Side Field Service Coupler
Low Side Field Service Coupler

d. Remove refrigerant using a refrigerant recovery system and repair any leaks. Evacuate and dehydrate
the unit. (Refer to section 4.6) Charge unit with refrigerant. (Refer to section 4.7)

Figure 4-3 Manifold Gauge Set (R-134a)

4--3

62-10848

um gauge (vacuum
0700414--00).

4.6 EVACUATION AND DEHYDRATION


4.6.1 General

a. Evacuate and dehydrate only after pressure leak test.


(Refer to section 4.5)

d. Additional time may be saved during a complete system pump down by replacing the filter--drier with a
section of copper tubing and the appropriate fittings.
Installation of a new filter--drier may be performed
during the charging procedure.

b. Essential tools to properly evacuate and dehydrate


any system include a good vacuum pump (5 cfm =
8m#H volume displacement, P/N 07-00176-01) and a
good vacuum indicator such as a thermocouple vacu-

3
4

1
2
3

P/N

c. Keep the ambient temperature above 60_F (15.6_C)


to speed evaporation of moisture. If ambient temperature is lower than 60_F (15.6_C), ice might form before moisture removal is complete. Heat lamps or alternate sources of heat may be used to raise system
temperature.

4.6.2 Preparation

(Carrier

NOTE
Use of a compound gauge is not recommended
because of its inherent inaccuracy.

Moisture can seriously damage refrigerant systems.


The presence of moisture in a refrigeration system can
have many undesirable effects. The most common are
copper plating, acid sludge formation, freezing-up of
metering devices by free water, and formation of acids,
resulting in metal corrosion.

indicator).

Refrigerant Recovery Unit


Refrigerant Cylinder
Evacuation Manifold

4 Valve
5 Vacuum Pump
6 Electronic Vacuum Gauge
Figure 4-4 Vacuum Pump Connection

4.6.3 Procedure For Evacuation And Dehydrating System


Also, as shown, connect a evacuation manifold, with
evacuation hoses only, to the vacuum pump, electronic vacuum gauge, and refrigerant recovery system.

a. Remove refrigerant using a refrigerant recovery system.


b. The recommended method to evacuate and dehydrate the system is to connect three evacuation
hoses (Do not use standard service hoses, as they
are not suited for evacuation purposes.) as shown in
Figure 4-4 to the vacuum pump and refrigeration unit.
62-10848

c.Connect lines to unit and manifold and make sure vacuum gauge valve is closed and vacuum pump valve is
open.
4--4

g. Start unit and check for non--condensables.

d. Start vacuum pump. Slowly open valves halfway and


then open vacuum gauge valve.
e. Evacuate unit until the electronic vacuum gauge indicates 2000 microns. Close the electronic vacuum
gauge and vacuum pump valves. Shut off the vacuum
pump. Wait a few minutes to be sure the vacuum
holds.
f. Break the vacuum with clean dry nitrogen. Raise system pressure to approximately 2 psig (0.14 Bar).
g. Purge nitrogen from system.
h. Repeat steps e through g one time.
i. Evacuate unit to 500 microns. Close off vacuum
pump valve and stop pump. Wait five minutes to see if
vacuum holds. This checks for residual moisture and/
or leaks.
j. With a vacuum still in the unit, the refrigerant charge
may be drawn into the system from a refrigerant container on a scale. The correct amount of refrigerant
may be added by observing the scale. (Refer to section 4.7)

4.7.3 Adding A Partial Charge

NOTE
When partially charging the refrigeration system with R134a, install a vapor charge.

a. Place refrigerant cylinder on scale and connect


charging line between suction port and refrigerant
cylinder.
b. Note weight of refrigerant cylinder.
c. Run unit on high speed cool and open cylinder vapor
valve.

4.7 CHARGING THE REFRIGERATION SYSTEM


4.7.1 Checking The Refrigerant Charge
a. Start unit in cooling mode and run approximately ten
minutes.
b. Partially block off air flow to condenser coil so discharge pressure rises to 174 psig (12 Bars).
c. The unit is correctly charged when there are no
bubbles in the sight glass.
4.7.2 Installing A Complete Charge

d. If necessary, partially block off air flow to condenser


coil so discharge pressure rises to 174 psig (12 Bars).
e. The unit is correctly charged when there are no
bubbles in the sight glass.
f. Start unit and check for non--condensables.

NOTE
It may be necessary to finish charging the unit
using the partial charge method, due to pressure rise in the high side of the system. (Refer to
paragraph 4.7.3)

4.8 CHECKING FOR NON--CONDENSABLES


To check for non--condensables, proceed as follows:

a. Dehydrate unit and leave in deep vacuum. (Refer to


section 4.6)
b. Place refrigerant cylinder on scale and connect
charging line from cylinder to receiver outlet (king)
valve. Purge charging line at outlet valve.
c. Note weight of refrigerant cylinder.
d. Open liquid valve on refrigerant cylinder. Open king
valve half way and allow the liquid refrigerant to flow
into the unit until the correct weight of refrigerant has
been added as indicated by scale. Correct charge will
be found in Table 1-1.

a. Stabilize system to equalize pressure between the


suction and discharge side of the system.

NOTE
It is possible that all liquid may not be pulled into
the receiver, as outlined in step d. above. In this
case, vapor charge remaining refrigerant
through the suction service port (See Section
4.7.3).

e. If gauge reading is 3 psig (0.2 Bar) or more than the


calculated P/T pressure in step d., non--condensables are present.

b. Check temperature at the condenser and receiver.


c. Check pressure at the receiver outlet (King) valve.
d. Check saturation pressure as it corresponds to the
condenser/receiver temperature using the Temperature-Pressure Chart, Table 4-4.

f. Remove refrigerant using a refrigerant recovery system. (Refer to section 4.4)


g. Evacuate and dehydrate the system. (Refer to section 4.6.)

e. When refrigerant cylinder scale indicates that the correct charge has been added, close liquid line valve on
cylinder and backseat the king valve.
f. Replace all valve caps.

h. Charge the unit. (Refer to section 4.7.)

4--5

62-10848

4.9 REPLACING THE COMPRESSOR

4.10 CHECKING AND REPLACING FILTER-DRIER

4.9.1 Removing Compressor

4.10.1 Checking Filter-Drier


Check for any obstruction of the filter-drier by feeling the
inlet and outlet connections of the liquid line on the filter
cartridge. If the temperature of the outlet connection
seems lower than the temperature of the inlet
connection, replace the filter-drier.

WARNING
Ensure power to the unit is OFF, power plug
is disconnected and circuit breaker is open
or vehicle engine is OFF and negative battery cable is connected before replacing
compressor.

4.10.2 Replacing The Filter-Drier


Remove refrigerant charge (See section 4.4). Remove
the drier mounting clip, then replace the filter-drier.
Following drier replacement, evacuate and recharge
unit (refer to sections 4.6 & 4.7).

a.Remove the refrigerant. (See Section 4.4.1).

4.11 HIGH PRESSURE (HP1) AND CONDENSER


PRESSURE (HP2) SWITCHES
4.11.1 Removing Switch

WARNING

a. A SCHRAEDER valve is located under each switch to


allow removal and installation without removing the
refrigerant charge.

Slowly open the plug on the suction and


discharge valves of the new compressor to
vent the nitrogen holding charge.

b. Remove switch and test in accordance with paragraph 4.11.2.


c. Replace or reinstall switch.

b. Remove bolts from flanges.

4.11.2 Checking Pressure Switch

c. Release and remove belt.


d. Remove the bolts mounting the compressor. Remove the compressor from chassis.

WARNING

e. Remove the pulley from the compressor.

Do not use a nitrogen cylinder without a


pressure regulator. (See Figure 4-5) Cylinder pressure is approximately 2350 psig
(160 bars). Do not use oxygen in or near a
refrigerant system as an explosion may occur.

4.9.2 Installing Compressor


a.. To install the compressor, reverse the procedure outlined when removing the compressor. Refer to section 1.6.4 for torque values.
NOTE
The service replacement compressor is sold
without flanges.

a. Remove switch as outlined in paragraph 4.11.1.


b. Connect ohmmeter across switch terminals. Ohmmeter will indicate resistance if switch is closed (HP1)
or open (HP2) after relieving pressure.

b. Pump down the compressor. (See Section 4.4)

b. Connect switch to a cylinder of dry nitrogen (see


Figure 4-5).

c. Charge compressor. (See Section 4.7.2)

c. Set nitrogen pressure regulator higher than cut-out


point on switch being tested. Pressure switch settings
points are provided in paragraph 1.6.2.

NOTE
It is important to check the compressor oil level
of the new compressor and fill if necessary. (Refer to section 1.6.1)

d. Close valve on cylinder and open bleed-off valve.


e. Open cylinder valve. While observing meter, slowly
close bleed-off valve and increase pressure until the
switch opens (HP1) or closes (HP2). Slowly open
bleed-off valve (to decrease pressure) until switch reverts to normal position.

d. Check refrigerant cycles.


Compressor oil type: The road compressors are
supplied with CARRIER POLYESTER (POE) oil.
Ensure compressor is marked with a factory sticker
indicating the correct oil has been installed. Oils of PAG
type are strictly incompatible with the operation of this
unit, never use an oil other than that approved by
CARRIER.
62-10848

f. The meter will indicate open. Open pressure on


gauge. Slowly open bleed-off valve (to decrease
pressure) until switch closes (ohmmeter will move).
g. If switch does not activate within tolerances provided,
replace switch. Test new switch before installation.
4--6

paper. Wipe out any accumulation of greasy material


using a clean rag dampened with solvent. Reassemble the motor. Install new brushes and replace cap.

1
4

4.13 HOT GAS (HGS1) AND CONDENSER


PRESSURE CONTROL SOLENOID VALVES

4.13.1 Replacing Solenoid Coil


It is not necessary to remove the refrigerant charge to
replace the coil (see Figure 4-7).
a. Remove coil snap cap, voltage plate and coil assembly. Disconnect leads and remove coil junction box if
necessary.
b. Verify coil type, voltage and frequency. This information appears on the coil voltage plate and the coil
housing.
c. Place new coil over enclosing tube and then install
voltage plate and snap cap.

6
3

1.
2.
3.
4.
5.
6.

Cylinder valve and gauge


Pressure regulator
Nitrogen cylinder
Pressure gauge (0 to 400 psig = 0 to 28 bars)
Bleed-off valve
1/4 inch connection

2
3

Figure 4-5 Typical Setup For Testing Pressure


Switches HP1 And HP2
4.12 CHECKING AND REPLACING CONDENSER
FAN MOTOR BRUSHES

To maintain proper operation of the fan motors, the fan


motor commutator and brushes should be checked
periodically for cleanliness and wear .
1.
2.
3.
4.

4.13.2 Replacing Valve Internal Parts


a. Remove the refrigerant charge. (See Section 4.4).
b. Remove coil snap cap, voltage cover and coil assembly. Remove the enclosing tube.
c. Check for foreign material in valve body.
d. Check for damaged plunger and o-ring. If o-ring is to
be replaced, always put refrigerant oil on o-rings before installing.

1
Brush Cap

7
5. Plunger assembly
6. Valve body assembly
7. Direction of flow

Figure 4-7 Hot Gas or Condenser Pressure


Control Solenoid

1.

6
Snap cap
Voltage plate
Coil assembly
Enclosing tube

2. Brush

Figure 4-6 Fan Motor Brushes


To check brushes proceed as follows :
a. With unit off and battery disconnected, remove brush
cap (Item 1 ; 2 per motor). See Figure 4-6
b. Remove brushes (Item 2; 2 per motor) and check the
length of the brush. If the length is less than 1/4 inch (6
mm) the brushes should be replaced.

CAUTION
Do not damage or over tighten the enclosing tube assembly. Place all parts in the enclosing tube in proper sequence in order to
avoid premature coil burn-out.

c. Blow out the brush holder with low pressure air to remove any carbon dust in the holder. This dust could
prevent a good contact between the brushes and
commutator.
d. Remove the back cover of the motor and inspect the
commutator. If the commutator is heavily grooved,
polish it using fine sandpaper. Do not use abrasive

e. Tighten enclosing tube.


f. Install coil assembly, voltage cover and snap cap.
4--7

62-10848

g. Evacuate, dehydrate and recharge unit. See Sections 4.6 and 4.7.
h. Start unit and check operation.
1

e. Braze the equalizer tubes to expansion valve.


f. Evacuate, dehydrate and recharge unit. (See Sections 4.6 and 4.7).

g. Check superheat (See Section 1.6.2.g.).


4.15.2 Measuring Superheat
a. Remove insulation from expansion valve bulb and
suction line. See Figure 4-9
b. Loosen one TXV bulb clamp and make sure area under clamp (above TXV bulb) is clean.

1. Cap
2. Jam Nut
3. Set Screw

c. Place thermocouple above (parallel to) the TXV bulb


and then secure loosened clamp making sure both
bulbs are firmly secured to suction line as shown in
Figure 4-9

Figure 4-8 Compressor Pressure Regulating Valve


4.14 ADJUSTING THE COMPRESSOR PRESSURE
REGULATING VALVE (CPR) (115V ONLY)

d. Connect an accurate gauge to the port on the suction service valve.

When adjusting the compressor pressure regulating


valve (CPR) (see Figure 4-8), the unit must be running
in heating or defrost mode. This will ensure a suction
pressure above the proper CPR setting. To adjust the
CPR valve, proceed as follows :
a. Install a gauge on the suction line .
b. Remove cap from CPR valve.
c. With an 8 mm Allen wrench, loosen the jam nut.
d. Using the 8 mm Allen wrench, adjust the set screw. To
raise the suction pressure turn the set screw clockwise; to lower the suction pressure, turn counterclockwise. Refer to paragraph 1.6.2 for CPR valve
setting.
e. When the setting has been adjusted, tighten the jam
nut securely against the set screw. This will prevent
any movement of the set screw due to vibrations in
the unit. Replace the cap.

e. Run unit until stabilized at -- 4_F (-- 20_C) refrigerated


compartmenttemperature.
f. From the temperature/pressure chart (Table 4-4), determine the saturation temperature corresponding to
the evaporator outlet pressure.
g. Note the temperature of the suction gas at the expansion valve bulb.
h. Subtract the saturation temperature determined in
Step f. from the average temperature measured in
Step g.. The difference is the superheat of the suction
gas. Refer to paragraph 1.6.2 for superheat setting.
i. If required, adjust superheat by turning the adjusting
screw located under the cap on the side of the valve.

4.15 THERMOSTATIC EXPANSION VALVE


The thermal expansion valve is an automatic device
which maintains constant superheat of the refrigerant
gas leaving the evaporator regardless of suction
pressure. The valve functions are:
(a) automatic
response of refrigerant flow to match the evaporator
load and (b) prevention of liquid refrigerant entering the
compressor. Unless the valve is defective, it seldom
requires any maintenance.

5
4

NOTE
Due to the time involved in adjusting the superheat, replace the valve rather than adjusting it.
4.15.1 Replacing expansion valve
a. Remove refrigerant charge (See section 4.4).
b. Remove insulation from expansion valve bulb and
then remove bulb from suction line.
c. Loosen flare nut and disconnect equalizer line from
expansion valve.
d. The txv bulb is located below the center of the suction
line. This area must be clean to ensure positive bulb
contact. Strap bulb to suction line and insulate both.
62-10848

1. Suction Line
(end view)
2. TXV Bulb Clamp

3. TXV Bulb
4. Thermocouple
5. Nut and Bolt (Clamp)

Figure 4-9 Thermostatic Expansion Valve Bulb


And Thermocouple
4--8

When welding is required on the unit frame, or on the


front area of the truck, ALL wiring to the microprocessor
MUST be disconnected. When welding is performed on
other areas of the truck and van, the welder ground
connection MUST be in close proximity to the area being
welded. It is also a good practice to remove both battery
cables before welding on either the unit frame or the
truck to prevent possible damage to other components
such as the alternator and voltage regulator.

4.16 DIAGNOSTIC TOOL


NOTE
The Cab Command diagnostic tool comes with
two jumpers. These are not applicable to the
30S system and should not be used in this application.

4.18 EVAPORATOR COIL CLEANING


The use of recycled cardboard cartons is increasing.
The recycled cardboard cartons create much more fiber
dust during transport than new cartons. The fiber dust
and particles are drawn into the evaporator where they
lodge between the evaporator fins. If the coil is not
cleaned on a regular basis, sometimes as often as after
each trip, the accumulation can be great enough to
restrict air flow, cause coil icing, repetitive defrosts and
loss of unit capacity. Due to the washing action of
normal defrost the fiber dust and particles may not be
visible on the face of the coil but may accumulate deep
within.

REMOTE
TOOL

PRIMARY
TOOL

Figure 4-10 Cab Command Diagnostic Tool


(CTD P/N 07--00440--00)
a. Testing a cab command cable that is already
installed on the unit and routed into the truck cab requires the use of both pieces of the diagnostic tool.
b. Unplug the cab command cable from the microprocessor and also from the back of the cab command
module.
c. Plug one end of the cable into the primary tool and
the other end into the remote tool.
d. Begin the test by turning on the power switch and observing the sequence of green lights. As each circuit
is tested, the corresponding light is illuminated. If a
fault is found in the cable, the light that corresponds
to that particular circuit is not illuminated.
e. To test a cable that is not installed on a unit, simply
plug each end of the cable into the primary tool and
perform the test as above.
4.17 MICROPROCESSOR

It is recommended to clean an the evaporator coil on a


regular basis, not only to remove cardboard dust, but to
remove any grease oil film which sometimes coats the
fins and prevents water from draining into the drain pan.
Cardboard fiber particles after being wetted and dried
several times can be very hard to remove. Therefore,
several washings may be necessary.
a. Spray coil with a mild detergent solution such as any
good commercial-grade automatic dish washer detergent and let the solution stand for a few minutes.
Reverse flush (opposite normal air flow) with clean
water at mild pressure. A garden hose with spray
nozzle is usually sufficient. Make sure drain lines are
clean.
b. Run unit until defrost mode be initiated to check for
proper draining from drain pan.

WARNING

4.19 CONDENSER COIL CLEANING


Remove all foreign material from the condenser coil by
reversing the normal air flow. (Air is pulled in through the
front.) Compressed air or water may be used as a
cleaning agent. It may be necessary to use warm water
mixed with any good commercial dishwasher detergent.
Rinse coil with fresh water if a detergent is used.

Under no circumstances should anyone attempt to repair the microprocessor module


or Cab Command! Should a problem develop with these components, contact your
nearest Carrier Transicold dealer for replacement.
Although there is less danger of electrical static
discharge (ESD) damage in the outdoor environment,
where the processor is likely to be handled, proper
board handling techniques should be stressed. Boards
should always be handled by their edges, in much the
same way one would handle a photograph. This not only
precludes the possibility of ESD damage, but also
lowers the possibility of physical damage to the
electronic components. Although the microprocessor
boards are fairly rugged when assembled, they are
more fragile when separated and should always be
handled carefully.

4--9

62-10848

Table 4-4. R-134a Temperature-Pressure Chart

TEMPERATURE
_F
_C
-- 40
-- 40
-- 35
-- 37
-- 30
-- 34
-- 25
-- 32
-- 20
-- 29
-- 18
-- 28
-- 16
-- 27
-- 14
-- 26
-- 12
-- 24
-- 10
-- 23
-- 8
-- 22
-- 6
-- 21
-- 4
-- 20
-- 2
-- 19
-- 0
-- 18
2
-- 17
4
-- 16
6
-- 14
8
-- 13
10
-- 12
12
-- 11
14
-- 10
16
-- 9
18
-- 8
20
-- 7
22
-- 6
24
-- 4
26
-- 3
28
-- 2

62-10848

BOLD FIGURES = Inches Mercury Vacuum (cm Hg VAC)


LIGHT FIGURES = psig (kg/cm2 and Bar)
PRESSURE
TEMPERATURE
2
Psig
Kg/cm
Bar
_F
_C
Psig
14.6
37.08
-- .49
30
-- 1
26.1
12.3
31.25
-- .42
32
0
27.8
9.7
24.64
-- .33
34
1
29.6
6.7
17.00
-- .23
36
2
31.3
3.5
8.89
-- .12
38
3
33.2
2.1
5.33
-- .07
40
4
35.1
0.6
1.52
-- .02
45
7
40.1
0.4
.03
.03
50
10
45.5
1.2
.08
.08
55
13
51.2
2.0
.14
.14
60
16
57.4
2.9
.20
.20
65
18
64.1
3.7
.26
.26
70
21
71.1
4.6
.32
.32
75
24
78.7
5.6
.39
.39
80
27
86.7
6.5
.46
.45
85
29
95.3
7.6
.53
.52
90
32
104.3
8.6
.60
.59
95
35
114.0
9.7
.68
.67
100
38
124.2
10.8
.76
.74
105
41
135.0
12.0
.84
.83
110
43
146.4
13.2
.93
.91
115
46
158.4
14.5
1.02
1.00
120
49
171.2
15.8
1.11
1.09
125
52
184.6
17.1
1.20
1.18
130
54
198.7
18.5
1.30
1.28
135
57
213.6
19.9
1.40
1.37
140
60
229.2
21.4
1.50
1.48
145
63
245.6
22.9
1.61
1.58
150
66
262.9
24.5
1.72
1.69
155
68
281.1

4--10

PRESSURE
Kg/cm2
1.84
1.95
2.08
2.20
2.33
2.47
2.82
3.30
3.60
4.04
4.51
5.00
5.53
6.10
6.70
7.33
8.01
8.73
9.49
10.29
11.14
12.04
12.98
13.97
15.02
16.11
17.27
18.48
19.76

Bar
1.80
1.92
2.04
2.16
2.29
2.42
2.76
3.14
3.53
3.96
4.42
4.90
5.43
5.98
6.57
7.19
7.86
8.56
9.31
10.09
10.92
11.80
12.73
13.70
14.73
15.80
16.93
18.13
19.37

SECTION 5
TROUBLESHOOTING

WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and operating compressor
unexpectedly as control requirements dictate. Press OFF key on the cab command, turn vehicle engine off or disconnect power plug and open circuit breaker.

CAUTION
Under no circumstances should anyone attempt to service the microprocessor module and cab command. Should a problem develop with the control system, contact your nearest Carrier Transicold
dealer for replacement components.
5.1 INTRODUCTION
Under normal circumstances, unit problems will be indicated by an active alarm in the alarm list. Suggested
troubleshooting actions for each alarm indication are provided in Table 5-1. Suggested corrective actions for
mechanical type problems are listed under subject headings in Table 5-2.
Table 5-1 Alarm Indications
ALARM

Description

A00

No Malfunction

A01

Low Pressure Switch (LP) or


High Pressure Switch (HP1)
Open (Road)

CORRECTIVE ACTION
All components functioning normally
Unit undercharged

Liquid line filter--drier restricted


TXV strainer plugged with foreign material/ice.
TXV malfunction
Verify operation of evaporator fans.
Failed switch
Unit overcharged

A02

Low Pressure Switch (LP) or


High Pressure Switch (HP1)
Open

Verify operation of condenser fan


Noncondensibles in system
Discharge check valve failed closed (standby only
Failed switch

A03
Standby
Electric motor overload
Units
Only
Road Compressor Clutch
A04
(CLHR) Malfunction

Thermal overload open in motor windings.

A05
Standby Standby Contactor (MC) high
amp draw
Units
Only

Contactor coil either high or low (0.2A for 3 phase;


0.5A for 1 phase)
Verify plunger moves freely
Replace contactor
Verify motor rotates freely

A06

Condenser Fan Motor (CFM)


high amp draw

A07

Evaporator Fan Motor (EFM)


high amp draw

Reference
Paragraph
---4.7.1
4.10.1
4.15
4.15
---4.11.2
4.7.1
---4.8
Replace
4.11.2

Current overload tripped.


Verify line voltage
Current draw of road clutch coil either high or low

Verify condition of brushes


Replace motor
Verify motor rotates freely

Replace motor
5--1

Replace

------4.12
---------62-10848

Table 5-1 Alarm Indications -- Continued


ALARM
A08
Standby
Units
Only

Description

CORRECTIVE ACTION

Reference
Paragraph

Heating option control -- Either Verify coil resistance

the hot water control relay or the


electric heat contactor coil amp
draw is high
Check wiring to controls
Current draw of coil high or low (approx 1.6 amp)
Hot Gas Solenoid Valve
(HGS1)
A09
high amp draw
Replace coil
Current draw of coil high or low (approx 1.2 amp)
Quench
Valve
(BPV)
A10
high amp draw
Replace coil
Current draw of coil high or low (approx 1.6 amp)
Condenser Pressure Control
A11
Valve (HGS2) high amp draw Replace coil
Unit out of range for 15 minutes
A12
Standby Out of Range -- High Tempera- Verify cooling operation of unit
ture
Units
Hot gas solenoid open
Only
Unit out of range for more than 15 minutes
A13
Standby Out of Range -- Low Tempera- Verify heating operation of unit
ture
Units
Heating option not active (Set configuration)
Only
Unit terminated defrost after 45 minutes
A14
Standby
Defrost Cycle > 45 minutes
Units
Verify HGS1/HGS2 valve operation
Only
Set point adjusted out of the
range --20.2 to 86F
A15
Check set point
(--29C/+30C) or below the
programmed low threshold
EE
Return Air Sensor
Return air sensor defective
Vehicle battery voltage low
bAt
Low Battery Voltage
Check alternator system
If operating on road, disconnect standby power supUsing Road & Standby opera- ply
-----tion at the same time.
If operating on standby, shut down vehicle engine.
Err
Set point error.
Programming error. Reset.

------4.13.1
---4.13.1
---4.13.1
Verify Setting
---4.13.1
Verify Setting
---2.9
---4.13
2.3
Replace
Correct
------2.3

Table 5-2 Mechanical Indications


INDICATION/TROUBLE

POSSIBLE CAUSES

REFERENCE
SECTION

5.2 REFRIGERATION
5.2.1 Unit Will Not Cool
Compressor drive (clutch) defective
Compressor defective
Defrost cycle has not terminated
Abnormal pressure
Refrigeration system
Hot gas solenoid malfunction (HGS1)
5.2.2 Unit Runs But Has Insufficient Cooling
Compressor
Compressor defective
Abnormal pressure
Expansion valve malfunction
Refrigeration system
Non--existent or restricted evaporator airflow
Compressor malfunction

62-10848

5--2

Replace
4.9
5.2.5
5.2.6
4.13
4.9
5.2.6
5.2.10
5.2.9

Table 5-2 Mechanical Indications -- Continued


INDICATION/TROUBLE

POSSIBLE CAUSES

5.2.3 Unit Operates Long or Continuously in Cooling


Hot Load
Refrigerated compartment
Defective refrigerated compartment insulation or air leak
Refrigeration system
Abnormal pressure
Temperature microprocessor malfunction
Compressor
Defective
5.2.4 Unit Will Not Heat or Heating Insufficient
Abnormal pressure
Temperature microprocessor malfunction
Refrigeration
Hot gas solenoid malfunction (HGS1)
Compressor
Compressor drive (clutch) defective
Compressor defective
5.2.5 Defrost Malfunction
Defrost thermostat (DTT) open or defective
Hot gas solenoid valve malfunction
Automatic defrost will not initiate
Defrost disabled through cab command
Microprocessor defective
Manual defrost will not initiate
Defrost thermostat (DTT) open or defective
Defrost cycle initiates but does
Hot gas solenoid malfunction (HGS1)
not defrost
Condenser Pressure Control valve malfunction (HGS2)
Wet load
Frequent defrost
Defrost settings set to low.
Does not terminate or cycles on
Defrost thermostats (DTT) shorted closed
defrost
5.2.6 Abnormal Pressure
5.2.6.1 Cooling
Condenser coil dirty
Noncondensibles in system
High discharge pressure
Refrigerant overcharge
Condenser fan/motor defective
Low discharge pressure
High suction pressure

Low suction pressure


Suction and discharge pressures
tend to equalize when unit is
operating
5.2.6.2 Heating
High discharge pressure
Low discharge pressure
Low suction pressure

Compressor defective
Hot gas solenoid malfunction
Low refrigerant charge
Compressor defective
Hot gas solenoid malfunction
Compressor pressure regulator misadjusted (CPR)
Filterdrier partially plugged
Low refrigerant charge
Expansion valve malfunction
No evaporator air flow or restricted air flow
Excessive frost on coil
Compressor defective
Hot gas solenoid malfunction

REFERENCE
SECTION
Insufficient pull
down time
Correct
5.2.6
5.2.8
4.9
5.2.6
5.2.8
4.13
Check
4.9
Replace
4.13
2.5
Replace
Replace
4.13
4.13
---2.5
Replace

4.19
4.8
4.7.1
4.12
4.9
4.13
4.7.1
4.9
4.13
4.14
4.10
4.7.1
5.2.10
5.2.9
Check
4.9
4.13

Overcharged system
Condenser fan or HP2 pressure switch defective
Noncondensibles in system
Condenser motor/fan defective

4.7.1
4.11
4.8
4.12

Compressor defective
Hot gas solenoid valve malfunction
Low refrigerant charge
Compressor pressure regulating valve misadjusted (CPR)
Condenser Pressure Regulating valve fault (HGS2)

4.9
4.13
4.7.1
4.14
4.13

5--3

62-10848

Table 5-2 Mechanical Indications -- Continued


INDICATION/TROUBLE

POSSIBLE CAUSES

REFERENCE
SECTION

5.2.7 Abnormal Noise


Compressor

Condenser or evaporator fan

Loose mounting bolts


Worn bearings
Worn or broken valves
Liquid slugging
Insufficient oil
Loose shroud
Bearings defective
Fan loose on shaft
Bent shaft

Tighten
4.9
4.9
5.2.10
Check
Check
Check
Check

5.2.8 Cab Command Malfunction


Fuse open
Microprocessor malfunction
Cab Command nonoperational
Microprocessor/Cab command cable

Replace
Replace
Check

5.2.9 No Evaporator Air Flow or Restricted Air Flow


Heavy frost on coil
Evaporator coil blocked
Coil dirty
Evaporator fan loose or defective
Evaporator fan rotating backwards
No or partial evaporator air flow
Evaporator air flow blocked in refrigerated compartment
Fan motor(s) malfunction

Check
4.18
Check
Check
Check
Replace

5.2.10 Expansion Valve


Low suction pressure with high
superheat

Low refrigerant charge


External equalizer line plugged
Broken capillary
Superheat setting too high

4.7.1
Repair
Repair
4.15.2

Low superheat and liquids lugging in compressor

Superheat setting too low


External equalizer line plugged
Pin and seat of expansion valve eroded or held open by
foreign material

4.15.2
Repair
4.15

Improper bulb location or installation


Insulation missing from sensing bulb
Low superheat setting
High superheat
Expansion valve setting
5.2.11 Malfunction Hot Gas Solenoid or Condenser Pressure Regulating Valve
No power to valve
Improper wiring or loose connections
Valve improperly assembled
Coil or coil sleeve improperly assembled
Valve does not function properly
Movement of plunger restricted due to:
a. Corroded or worn parts
b. Foreign material lodged in valve
c. Bent or dented enclosing tube
Valve shifts but refrigerant
Foreign material lodged under seat
continues to flow
Defective seat
5.2.12 Standby Compressor Malfunction
Motor contactor defective
Motor Overload open
Standby compressor fails to start Improper power supply
5minute timer active
Fluctuating suction pressure

Standby motor starts, then stops

62-10848

Motor Overload open

5--4

4.15
Replace
4.15.2
4.15.2
Check
Check
4.13

4.13

Replace
Check
Correct
Check
Check

SECTION 6
ELECTRICAL SCHEMATIC WIRING DIAGRAM
6.1 INTRODUCTION
This section contains Electrical Schematic Wiring Diagram covering the Models listed in Table 1-1. The following
general safety notices supplement the specific warnings and cautions appearing elsewhere in this manual. They are
recommended precautions that must be understood and applied during operation and maintenance of the equipment
covered herein.

WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and operating compressor
unexpectedly as control requirements dictate. Press OFF key on the cab command and disconnect
power plug.

WARNING
Under no circumstances should ether or any other starting aids be used to start engine.

WARNING
Under no circumstances should anyone attempt to repair the microprocessor module or Cab
Command! Should a problem develop with these components, contact your nearest Carrier
Transicold dealer for replacement.

CAUTION
Observe proper polarity when installing battery, negative battery terminal must be grounded.

CAUTION
Under no circumstances should a technician electrically probe the processor at any point, other than
the connector terminals where the harness attaches. Microprocessor components operate at
different voltage levels and at extremely low current levels. Improper use of voltmeters, jumper
wires, continuity testers, etc. could permanently damage the processor.

CAUTION
Most electronic components are susceptible to damage caused by electrical static discharge (ESD).
In certain cases, the human body can have enough static electricity to cause resultant damage to the
components by touch. This is especially true of the integrated circuits found on the microprocessor.
Use proper board handling techniques. (See Section 4.17).

6--1

62--10848

62--10848

6--2

LP

BPT

BPV

CC

CFM

CLHR

EFM

FI

FUSE

HP1

HP2

HGS1

HGS2

RAS

B--9

B--8

P--9

A--5

P--7

P--4

P--6

B--10

D--3

B--9

B--7

P--8

P--9

B--7

RETURN AIR SENSOR

CONDENSER PRESSURE CONTROL VALVE

HOT GAS SOLENOID VALVE

CONDENSER PRESSURE SWITCH

HIGH PRESSURE SWITCH

25A FUSE

IGNITION FUSE

EVAPORATOR FAN MOTOR

ROAD CLUTCH

CONDENSER FAN MOTOR

CAB COMMAND

QUENCH VALVE

QUENCH THERMOSTAT

LOW PRESSURE SWITCH

DESCRIPTION

EVAPORATOR

CONDENSER

CONDENSER

CONDENSER

CONDENSER

LOGIC BOARD

ENGINE COMPARTMENT

EVAPORATOR

ENGINE COMPARTMENT

CONDENSER

CAB

EVAPORATOR

ROAD COMPRESSOR

EVAPORATOR

LOCATION IN UNIT

Figure 6-1 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61350 Rev D

SYMBOL

LOCATION

ROAD ONLY

6--3

62--10848

Figure 6-2 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61350 Rev E

ROAD ONLY

6--4

62--10848

CS

CT

CFM

HGS2

CLHR

CLHS

C1

L--9/M--11

N--8

J--9

I--2

I--5

I--7

J--12

N--12

FI

CR

N--8

I--8

CP

A--8

EFM

CC

O--12

I--3

BR

D--12

DTT

BTY

I--5

B--2

BPT

BPV

B--3

IGNITION FUSE

EVAPORATOR FAN MOTOR

DEFROST TERMINATION THERMOSTAT

FILTER CAPACITOR

STANDBY CLUTCH

ROAD CLUTCH

CONDENSER PRESSURE CONTROL VALVE

CONDENSER FAN MOTOR

CLUTCH TIME DELAY RELAY

START CAPACITOR

CLUTCH RELAY

PERMANENT CAPACITOR

CAB COMMAND

BRIDGE

BATTERY

QUENCH VALVE

QUENCH THERMOSTAT

LOW PRESSURE SWITCH

LP

B--5

DESCRIPTION
ALARM (I MAX: 0.1A)

SYMBOL

I--9

LOCATION

115V/1/60Hz

ENGINE COMP.

EVAPORATOR

EVAPORATOR

STANDBY PANEL

CONDENSER

ENGINE COMP.

CONDENSER

CONDENSER

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

CAB

STANDBY PANEL

ENGINE COMP.

EVAPORATOR

ROAD COMPR.

CONDENSER

EXTERNAL

LOCATION IN UNIT

PTO

N--7

Q11

P--9

F--10

N--7

D--10

B--5

M--12

TR

STBR

SR

DMB

RR

RAS

PSR

PMC

D--13

N--2

PC

OL

MC

HGS1

HP2

HP1

F4

F3

F2

F1

SYMBOL

D--2

O--5

N--4

I--5

B--4

B--4

S--10

K--11

M--10

D--11

LOCATION

TRANSFORMER

START RELAY

STANDBY RELAY

STANDBY MOTOR

ROAD RELAY

RETURN AIR SENSOR

DISCHARGE RESISTOR

POWER SUPPLY RECEPTACLE

MOTOR INTERNAL THERMOSTAT

GROUND PANEL

MICROPROCESSOR

OVERLOAD RELAY

MOTOR CONTACTOR

HOT GAS SOLENOID VALVE

CONDENSER PRESSURE CONTROL


SWITCH

HIGH PRESSURE SWITCH

TRANSFORMER FUSE

5A FUSE

30A FUSE

IA FUSE

DESCRIPTION

CONDENSER

STANDBY PANEL

MICROPROCESSOR

CONDENSER

MICROPROCESSOR

EVAPORATOR

STANDBY PANEL

EXTERNAL

STANDBY MOTOR

CONTROL BOX

CONTROL BOX

CONTROL BOX

STANDBY PANEL

CONDENSER

CONDENSER

CONDENSER

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

LOCATION IN UNIT

6--5

62--10848

Figure 6-3 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61353 Rev C

115V/1/60Hz

6--6

62--10848

QUENCH VALVE
BATTERY

CAB COMMAND

PERMANENT CAPACITOR

BPT

BPV

BTY

BR

CC

B--3

I--5

D--12

O--12

A--8

C1

FI

CLHS

J--12

N--12

I--8

CLHR

I--7

DTT

HGS2

I--5

EFM

CFM

I--2

I--3

STANDBY CLUTCH

CT

K--9

B--2

ROAD CLUTCH

CS

N--8

ENGINE COMP.

EVAPORATOR

EVAPORATOR

STANDBY PANEL

CONDENSER

ENGINE COMP.

CONDENSER

CONDENSER

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

CAB

STANDBY PANEL

ENGINE COMP.

EVAPORATOR

ROAD COMPR.

CONDENSER

EXTERNAL

LOCATION IN UNIT

PTO

N--7

Q11

P--9

F--10

N--7

D--10

B--5

TR

STBR

SR

DMB

RR

RAS

PSR
M--12

PMC
N--2

PC

OL

MC

HGS1

HP2

HP1

F4

F3

F2

F1

SYMBOL

D--13

D--2

O--5

N--4

I--5

B--4

B--4

S--10

K--11

M--10

D--11

LOCATION

TRANSFORMER

START RELAY

STANDBY RELAY

STANDBY MOTOR

ROAD RELAY

RETURN AIR SENSOR

DISCHARGE RESISTOR

MOTOR INTERNAL THERMOSTAT

POWER SUPPLY RECEPTACLE

GROUND PANEL

MICROPROCESSOR

OVERLOAD RELAY

MOTOR CONTACTOR

HOT GAS SOLENOID VALVE

CONDENSER PRESSURE CONTROL


SWITCH

HIGH PRESSURE SWITCH

TRANSFORMER FUSE

5A FUSE

30A FUSE

IA FUSE

DESCRIPTION

Figure 6-4 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61354 Rev A

IGNITION FUSE

EVAPORATOR FAN MOTOR

DEFROST TERMINATION THERMOSTAT

FILTER CAPACITOR

CONDENSER PRESSURE CONTROL VALVE

CONDENSER FAN MOTOR

CLUTCH TIME DELAY RELAY

START CAPACITOR

CLUTCH RELAY

CP

CR

N--8

L--9/M11

BRIDGE

QUENCH THERMOSTAT

LOW PRESSURE SWITCH

LP

B--5

DESCRIPTION
ALARM (I MAX: 0.1A)

SYMBOL

I--9

LOCATION

230/1/60Hz

CONDENSER

STANDBY PANEL

MICROPROCESSOR

CONDENSER

MICROPROCESSOR

EVAPORATOR

STANDBY PANEL

STANDBY MOTOR

EXTERNAL

CONTROL BOX

CONTROL BOX

CONTROL BOX

STANDBY PANEL

CONDENSER

CONDENSER

CONDENSER

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

LOCATION IN UNIT

6--7

62--10848

Figure 6-5 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61354 Rev C

230/1/60Hz

6--8

62--10848

CLHS

C1

DTT

EFM

FI

J--12

N--12

B--2

I--3

I--8

F1

CLHR

I--7

D--11

HGS2

I--5

A--8

CR

CC

O--12

CFM

BR

D--12

I--2

BTY

I--5

L--9/M--11

BPT

BPV

B--3

IA FUSE

IGNITION FUSE

EVAPORATOR FAN MOTOR

DEFROST TERMINATION THERMOSTAT

FILTER CAPACITOR

STANDBY CLUTCH

ROAD CLUTCH

CONDENSER PRESSURE CONTROL VALVE

CONDENSER FAN MOTOR

CLUTCH RELAY

CAB COMMAND

BRIDGE

BATTERY

QUENCH VALVE

QUENCH THERMOSTAT

LOW PRESSURE SWITCH

LP

B--5

DESCRIPTION
ALARM (I MAX: 0.1A)

SYMBOL

I--9

LOCATION

STANDBY PANEL

STANDBY PANEL

EVAPORATOR

EVAPORATOR

STANDBY PANEL

CONDENSER

ENGINE COMP.

CONDENSER

CONDENSER

STANDBY PANEL

CAB

STANDBY PANEL

ENGINE COMP.

EVAPORATOR

ROAD COMPR.

CONDENSER

EXTERNAL

LOCATION IN UNIT

PTO

N--7

SR
TR

Q11

SMB

RR

RAS

F--10

N--7

D--10

B--5

PSR

N--2

M--12

OMC

PC

OL

MC

HGS1

HP2

HP1

F5

F4

F3

F2

SYMBOL

D--13

D--2

N--5/K--5

M--9

I--5

B--4

B--4

N--10

O--10

K--11

M--10

LOCATION

TRANSFORMER

STANDBY RELAY

STANDBY MOTOR

RUN RELAY

RETURN AIR SENSOR

DISCHARGE RESISTOR

MOTOR INTERNAL THERMOSTAT

POWER SUPPLY RECEPTACLE

GROUND PANEL

MICROPROCESSOR

OVERLOAD RELAY

MOTOR CONTACTOR

HOT GAS VALVE

CONDESNER PRESSURE SWITCH

HIGH PRESSURE SWITCH

400V TRANSFORMER FUSE

230V TRANSFORMER FUSE

5A FUSE

30A FUSE

DESCRIPTION

230/3/60Hz

CONDENSER

MICROPROCESSOR

CONDENSER

MICROPROCESSOR

EVAPORATOR

STANDBY PANEL

STANDBY MOTOR

EXTERNAL

CONTROL BOX

CONTROL BOX

CONTROL BOX

STANDBY PANEL

CONDENSER

CONDENSER

CONDENSER

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

STANDBY PANEL

LOCATION IN UNIT

6--9

62--10848

LP

Figure 6-6 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61352 Rev B

230/3/60Hz

INDEX

A
Abnormal Noise, 5-4

Description, 1-1
Diagnostic Tool, 4-9

Abnormal Pressure, 5-3

Accessing Alarm Messages, 2-4


Alarm Display, 2-4

Electrical Data, 1-10

Alarm Indications, 5-1

Evacuation and Dehydrating System, 4-4


Evacuation And Dehydration, 4-4

Evaporator, 1-4
Evaporator Coil Cleaning, 4-9

Belt Adjustment, 4-2

Evaporator Fan Motor, 1-10

Belt Tension, 4-2

Expansion Valve, 5-4

C
Cab Command, 2-1

Filter Drier, 1-1

Cab Command Malfunction, 5-4

FILTER--DRIER, 4-6

Checking The Eeprom Version, 2-5

Frozen Mode, 3-1

Checking the Refrigerant Charge, 4-5

Clearing Alarm Messages, 2-5


Compressor, 1-3
Compressor Pressure Regulating Valve, 4-8
Compressor Pressure Regulating Valve, 1-4
Condenser Coil Cleaning, 4-9
Condenser Fan Motor, 1-10
Condenser Fan Motor Brushes, 4-7

Heat And Defrost, 1-12


High Pressure Safety Switch, 1-4
High Pressure Switch , 4-6
Hot Gas Solenoid, 4-7
Hot Gas Valve, 1-10
Hot Gas Valve 1, 1-3

Condenser Pressure Control Solenoid , 4-7


Condenser Pressure Control Valve, 1-10

Condenser Pressure Control Valve , 1-3


Condenser Pressure Switch, 4-6

Inspection, 2-2

Condenser Pressure Switch, 1-4

Installing a Complete Charge, 4-5

Condenser Pressure Switch (HP2), 1-9

Insufficient Cooling, 5-2

Condenser/Subcooler, 1-1

Connect Power, 2-3


Control System, 2-1

Low Battery Alarm, 2-5

Cooling, 1-12

Low Pressure Switch, 1-4

Defrost Cycle, 2-3, 3-2

Maintenance Schedule, 4-1

Defrost Malfunction, 5-3

Manual Defrost, 2-3

Defrost Termination Thermostat, 1-9

Microprocessor, 4-9

Defrost Timer, 1-9

Minimum Off Time, 3-2


Index--1

62--10848

INDEX

N
No Evaporator Air Flow or Restricted Air Flow, 5-4

Service, 4-1
Set--point, 2-3
Standby Compressor Malfunction, 5-4
Standby Compressor Speed, 1-10
Standby Motor , 1-3

Oil Separator, 1-3

Standby Motor Contactor, 1-10

OPERATION, 2-1

Standby Motor Ratings, 1-10


Standby Motor--Compressor V--Belt, 4-2

P
Partial Charge, 4-5
Perishable Mode, 3-1

Q
Quench Valve, 1-4, 1-10
Quench Valve (BPV), 1-9

R
Receiver, 1-3

Start--up, 2-2
Starting, 2-3
Stopping, 2-5

T
Temperature Control, 3-1
Thermal Expansion Valve, 1-4
Thermostatic Expansion Valve, 4-8
Thermostatic Expansion Valve, 1-9
Torque Values, 1-10
Troubleshooting, 5-1

Refrigerant Leak Checking, 4-3

Refrigerant Removal From Compressor, 4-3


Refrigeration System, 1-9
Replacing The Compressor, 4-6

Unit Operates Long or Continuously in Cooling, 5-3

Road Compressor Clutch, 1-10

Unit Will Not Cool, 5-2


Unit Will Not Heat or Heating Insufficient, 5-3

Safety Devices, 1-11


Sequence Of Operation, 3-1

62--10848

Wiring Diagram, 6-2, 6-3, 6-5, 6-6, 6-7, 6-9

Index--2

North America
Carrier Transicold
700 Olympic Drive
Athens, GA 30601 USA
Tel: 1--706--357--7223
Fax: 1--706--355--5435

Central America
and Mexico
Ejercito Nacional No. 418
Piso 9, Torre Yumal
Col. Chapultepec Morales
11570 Mexico, D.F.
Tel: (5255) 9126.0300
Fax: (5255) 9126.0373

Carrier Transicold Division,


Carrier Corporation
Truck/Trailer Products Group
P.O. Box 4805
Syracuse, N.Y. 13221 U.S A
www.carrier.transicold.com

A member of the United Technologies Corporation family. Stock symbol UTX


2009 Carrier Corporation D Printed in U. S. A. 0909

You might also like