Reefer
Reefer
Reefer
Container Refrigeration
T-354
Models
69NT--40--541--306, 314 & 328
TABLE OF CONTENTS
PARAGRAPH NUMBER
Page
Safety--1
1--1
1.1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2
CONFIGURATION IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1.3
OPTION DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1.3.1 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1.3.2 Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1--1
1--1
1--1
1.3.7 USDA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1.3.8 Interrogator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1--1
1.3.10 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1.3.11 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1--1
1.3.13 Autotransformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--1
1--1
1.3.15 Gutters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--2
1.3.16 Handles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--2
1--2
1--2
1--2
1--2
1--2
1--2
1--2
1--2
1--2
1--2
1.3.27 Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--2
1--2
1.3.29 Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--2
1--2
1.3.31 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1--2
1--2
1--2
1--1
T-354
T-354
ii
iii
T-354
Page
4--9
4--9
4--10
4--10
5--1
5.1
5.2
5--1
5--1
5.3
5--2
5.4
5.5
5--2
5--2
5.6
5--2
5.7
5.8
5--3
5--3
5.9
CONTROLLER MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5--3
5--4
5--4
5--4
5--4
6--1
6.1
SECTION LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6--1
6.2
6.3
SERVICE VALVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MANIFOLD GAUGE SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6--1
6--1
6.4
6--3
6.5
6.6
6--3
6--3
6.6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6--3
6.6.2 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6.3 Procedure - Complete System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6--3
6--3
6--4
REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.1 Checking the Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6--4
6--4
6--4
6--4
6--5
6--5
6--6
6--8
6.8.4 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.8.5 Installing the Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6--8
6--9
6--9
6--10
6--10
6--10
6.7
6.9
T-354
iv
T-354
LIST OF ILLUSTRATIONS
FIGURE NUMBER
Page
2--1
Figure 2-2 Evaporator Section -- UPFLOW Units With Center Access Panel . . . . . . . . . . . . . . . . . . . . . . . . . .
2--2
2--3
2--4
2--5
2--6
2--11
2--12
3--1
3--2
3--2
3--3
3--10
3--11
4--1
4--2
4--6
4--6
4--7
4--7
4--8
4--8
6--1
6--1
6--2
6--2
6--4
6--5
6--6
6--6
6--7
6--7
6--7
6--8
6--8
6--8
6--8
6--10
6--12
6--12
6--13
6--13
6--13
T-354
vi
Page
6--14
6--15
6--15
6--17
6--19
6--19
6--22
6--22
6--23
6--23
6--25
6--27
6--28
6--29
Figure 6-36 R-134a Compressor Pressure and Motor Current Curves Versus Ambient Temperature . . . . .
Figure 7-1 LEGEND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-2 SCHEMATIC DIAGRAM -- Units with Single Evaporator Fan Capability & VPS . . . . . . . . . . . . . .
Figure 7-3 UNIT WIRING DIAGRAM -- Units with Single Evaporator Fan Capability & VPS . . . . . . . . . . . . .
Figure 7-5 SCHEMATIC DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-6 UNIT WIRING DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6--33
7--1
7--2
7--3
7--5
7--6
LIST OF TABLES
TABLE NUMBER
Page
Table 2-1 Safety and Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--9
Table 3-1 Keypad Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--2
Table 3-2 DataCORDER Configuration Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--8
Table 3-3 DataCORDER Standard Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--9
Table 3-4 Controller Configuration Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--13
Table 3-5 Controller Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--14
Table 3-6 Controller Alarm Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--18
Table 3-7 Controller Pre-Trip Test Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--22
Table 3-8 DataCORDER Function Code Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--26
Table 3-9 DataCORDER Pre-Trip Result Records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--27
Table 3-10 DataCORDER Alarm Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--28
Table 6-1 Sensor Temperature/Resistance Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--21
Table 6-2 Crack, Chip and Hole Repair Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--27
Table 6-3 Insert Repair Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--27
Table 6-4 Drill Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--27
Table 6-5 Recommended Bolt Torque Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--30
Table 6-6 Wear Limits For Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--30
Table 6-7 Compressor Torque Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--31
Table 6-8 R-134a Temperature - Pressure Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--32
vii
T-354
SAFETY SUMMARY
GENERAL SAFETY NOTICES
The following general safety notices supplement the
specific warnings and cautions appearing elsewhere in
this manual. They are recommended precautions that
must be understood and applied during operation and
maintenance of the equipment covered herein. The
general safety notices are presented in the following
three sections labeled: First Aid, Operating Precautions
and Maintenance Precautions. A listing of the specific
warnings and cautions appearing elsewhere in the
manual follows the general safety notices.
FIRST AID
An injury, no matter how slight, should never go
unattended. Always obtain first aid or medical attention
immediately.
OPERATING PRECAUTIONS
WARNING
WARNING
Do not attempt to remove power plug(s) before turning OFF start-stop switch (ST), unit
circuit breaker(s), and external power
source.
WARNING
Make sure the power plugs are clean and
dry before connecting to any power
receptacle.
WARNING
Make sure that the unit circuit breaker(s)
(CB-1 & CB-2) and the START-STOP switch
(ST) are in the O (OFF) position before
connecting to any electrical power source.
WARNING
Never use air for leak testing. It has been determined that pressurized mixtures of refrigerant and air can undergo combustion
when exposed to an ignition source.
T-354
WARNING
WARNING
Make sure power to the unit is OFF and
power plug disconnected before servicing
capacitor(s).
WARNING
With power OFF discharge the capacitor
before disconnecting the circuit wiring.
WARNING
Make sure power to the unit is OFF and
power plug disconnected before replacing
the compressor.
WARNING
The unit power plug must be disconnected
to remove power from circuit breaker CB1
WARNING
WARNING
WARNING
WARNING
WARNING
Oakite No. 32 is an acid. Be sure that the
acid is slowly added to the water. DO NOT
PUT WATER INTO THE ACID. This will
cause spattering and excessive heat.
CAUTION
Do not remove wire harnesses from controller unless you are grounded to the unit
frame with a static safe wrist strap.
WARNING
CAUTION
Unplug all controller wire harness connectors before performing arc welding on any
part of the container.
WARNING
CAUTION
CAUTION
CAUTION
The unit will remain in the full cooling mode
as long as the emergency bypass switch is
in the BYPASS position and the MODE
SWITCH is in the FULL COOL position. If
the cargo may be damaged by low temperatures, the operator must monitor container
temperature and manually cycle operation
as required to maintain temperature within
required limits.
When Pre-Trip key is pressed, dehumidification and bulb mode will be deactivated.
At the completion of Pre-Trip activity, dehumidification and bulb mode must be
reactivated.
CAUTION
When condenser water flow is below 11 lpm
(3 gpm) or when water-cooler is not in use,
the CFS switch MUST be set to position I
or the unit will not operate properly.
CAUTION
The unit will remain in the DEFROST mode
as long as the emergency defrost switch is
in the DEFROST position. To prevent cargo
damage, the operator must monitor container temperature and manually cycle operation as required to maintain temperature
within required limits.
CAUTION
Pre-trip inspection should not be performed with critical temperature cargoes in
the container.
CAUTION
To prevent trapping liquid refrigerant in the
manifold gauge set, be sure set is brought
to suction pressure before disconnecting.
CAUTION
WARNING
When Pre-Trip key is pressed, dehumidification and bulb mode will be deactivated.
At the completion of Pre-Trip activity, dehumidification and bulb mode must be
reactivated.
CAUTION
CAUTION
CAUTION
CAUTION
When Pre-Trip test Auto 2 runs to completion without being interrupted, the unit will
terminate pre-trip and display Auto 2
end. The unit will suspend operation until
the user depresses the ENTER key!
T-354
CAUTION
CAUTION
Do not remove wire harnesses from controller unless you are grounded to the unit
frame with a static safe wrist strap.
CAUTION
CAUTION
Unplug all controller connectors before
performing arc welding on any part of the
container.
CAUTION
CAUTION
The unit must be OFF whenever a programming card is inserted or removed from the
controller programming port.
CAUTION
Do not allow moisture to enter wire splice
area as this may affect the sensor
resistance.
CAUTION
CAUTION
CAUTION
CAUTION
DO NOT disassemble piston from NEW suction modulating valve powerhead assembly. Doing so may result in damage to
piston.
T-354
Safety--4
SECTION 1
INTRODUCTION
1.1 INTRODUCTION
T-354
1.3.15 Gutters
1--2
SECTION 2
DESCRIPTION
2.1 GENERAL DESCRIPTION
13
1
12
11
10
2
7
6
5
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
T-354
5
4
2
1
16
14
13
12
11
10
9
15
1.
2.
3.
4.
5.
6.
7.
8.
TXV Bulb
(under Insulation)
T-354
2--2
1
5
11
10
12
13
21
22
16
14
17
20
19
1.
2.
3.
4.
5.
6.
7.
8
9.
10.
11.
15
18
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
Autotransformer
Power Cables and Plug
Compressor Sight Glass View Port
Compressor Guard
Return Temperature Sensor
Return Recorder Sensor
Ambient Sensor
Return Air Thermometer Port
Discharge Service Valve
Discharge Temperature Sensor
Discharge Pressure Regulating Valve
2--3
T-354
6
7
5
8
9
15
10
11
12
13
14
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
Sight Glass
Fusible Plug (Rupture Disc -- Alternate)
Condenser Pressure Transducer
Sight Glass/Moisture Indicator
Filter-Drier
Liquid Line Service Valve
Quench Valve
2--4
1
9
11
1.
2.
3.
4.
5.
6.
10
Sight Glass
7. Liquid Line Service Valve
Water-Cooled Condenser
8. Moisture/Liquid Indicator
Rupture Disc
9. Coupling (Water In)
Condenser Pressure Transducer
10. Self Draining Coupling (Water Out)
Quench Valve
11. Water Pressure Switch
Filter-Drier
Figure 2-5 Water-cooled Condenser Section
2--5
T-354
20
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
19
18
17
16
15
14
12
13
Compressor Contactor
Heater Contactor
Display Module
Communications Interface Module
Controller/DataCORDER Module (Controller)
Key Pad
Emergency Defrost Light
Start-Stop Switch
Remote Monitoring Receptacle
Manual Defrost Switch
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
11
2--6
10
T-354
8 7
a. Compressor/Motor
Assembly
Number of Cylinders
Model
CFM
Weight (Dry)
Approved Oil
Oil Charge degrees
Oil Sight Glass
Verify at -18 C
(0F) container box
temperature
Opens
c. Heater Termination Thermostat
Closes
Cutout
d. High Pressure Switch
Cut-In
b. Expansion Valve Superheat
Unit Configuration
e. Refrigerant Charge
Water-Cooled
Condenser
Receiver
6
06DR
41
118 kg (260 lb)
Castrol Icematic
3.6 liters (7.6 U.S. pints)
The oil level range, with the compressor off,
should be between the bottom and one-eighth
level of the sight glass.
4.5 to 6.7C (8 to 12F)
54 (+/-) C = 130 (+/-) F
38 (+/- 4) C = 100 (+/- 7) F
25 (+/- 1.0) kg/cm@ = 350 (+/- 10) psig
18 (+/- 0.7) kg/cm@ = 250 (+/- 10) psig
Charge Requirements -- R-134a
3 row condenser
4.9 kg (10.75 lbs)
j. Unit Weight
k. Water Pressure Switch
Cut-In
Cutout
l. Discharge Pressure
Regulating Valve
Factory Setting
* Rupture Disc, part number 14 -00215 -04 may be installed as an alternate for the receiver mounted fusible plug.
2--7
T-354
c. Condenser Fan
Motor
d. Evaporator Coil
Heaters
e. Evaporator Fan
Motor(s)
f. Fuses
29 amps
62.5 amps
87.5 amps
17.6 amps @ 460 VAC
(with current limiting set at 21 amps)
380 VAC, Single Phase,
460 VAC, Single Phase,
50 Hz
60 hz
1.3 amps
1.6 amps
0.43 hp
0.75 hp
1425 rpm
1725 rpm
360 -- 460 VAC +/- 2.5 hz
400 -- 500 VAC +/- 2.5 hz
Factory lubricated, additional grease not required.
Counter-clockwise when viewed from shaft end.
6
750 watts +5/ -10% each @ 230 VAC
66.8 to 77.2 ohms @ 20C (68F)
Sheath
380 VAC/50 hz
460 VAC/60 hz
1.6
2.1
0.6
0.6
0.58
1.0
0.07
0.12
2850 rpm
3450 rpm
1425 rpm
1750 rpm
T-354
2--8
Setpoint Range
SAFETY DEVICE
DEVICE SETTING
5 amp rating
5 amp rating
N/A
N/A
N/A
Abnormal pressures /
temperatures in the high
refrigerant side
Abnormally high discharge
pressure
99C = (210F)
Opens at 25 kg/cm@
(350 psig)
2--9
T-354
T-354
2--10
EVAPORATOR
THERMOSTATIC
EXPANSION VALVE
(TXV)
TXV BULB
CONDENSER
HEAT EXCHANGER
DISCHARGE PRESSURE
REGULATING VALVE
QUENCH
VALVE BULB
SERVICE VALVE
MODULATING
VALVE
FUSIBLE PLUG
QUENCH VALVE
SIGHT GLASS
FILTER DRIER
Suction
Liquid
Discharge
PRESSURE TRANSDUCER
SIGHT GLASS /
MOISTURE INDICATOR
SERVICE
VALVE
RECEIVER
THERMOSTATIC
EXPANSION VALVE
(TXV)
TXV BULB
CONDENSER
HEAT EXCHANGER
DISCHARGE PRESSURE
REGULATING VALVE
RUPTURE DISC
MODULATING VALVE
SERVICE VALVE
MOISTURE
INDICATOR
QUENCH
VALVE BULB
WATER-COOLED
CONDENSER
SIGHT GLASS
Suction
Liquid
Discharge
SERVICE VALVE
QUENCH VALVE
FILTER DRIER
T-354
T-354
2--12
SECTION 3
MICROPROCESSOR
operating parameters and cargo temperature
parameters for future retrieval. Coverage of the
temperature control software begins with paragraph
3.2. Coverage of the DataCORDER software is
provided in paragraph 3.6.
DISPLAY MODULE
CONTROL MODULE
CONFIGURATION
SOFTWARE
CONFIGURATION
VARIABLE
(CnF##)
OPERATIONAL
SOFTWARE
FUNCTION
CODE (Cd)
ALARMS
(AL<70)
PRE--TRIP
INTERROGATION
CONNECTOR
TO
DISPLAY
DATAREADER
DataCORDER SOFTWARE
CONFIGURATION
SOFTWARE
OPERATIONAL
SOFTWARE
CONFIGURATION
VARIABLE
(dCF## read only)
FUNCTION
CODE (dC)
DATA
STORAGE
MEMORY
ALARMS
(AL>68)
TO
DISPLAY
(Scrollback)
TO
DISPLAY
Computer Device
With DataLine
Software
PCMCIA CARD
T-354
3.1.1 Keypad
The keypad (Figure 3-7) is mounted on the right-hand
side of the control box. The keypad consists of 11 push
button switches that act as the users interface with the
controller. Descriptions of the switch functions are
provided in Table 3-1.
CODE
SELECT
PRE
TRIP
ALARM
LIST
MANUAL
DEFROST/
INTERVAL
KEY
FUNCTION
Alarm List
Manual
Defrost/
Interval
Enter
Arrow Up
ENTER
Displays selected defrost mode. Depressing and holding the Defrost interval key for five seconds will initiate
defrost using the same logic as if the
optional manual defrost switch was
toggled on.
Confirms a selection or saves a
selection to the controller
Change or scroll a selection upward.
Pre-trip advance or test interruption.
_C
_F
BATTERY
POWER
ALT.
MODE
COOL
SETPOINT/Code
Battery
Power
ALT. Mode
NOTE
The controlling probe in the perishable range
will be the SUPPLY air probe and the controlling
probe in the frozen range will be the RETURN
air probe.
Degrees C/
Degrees F
SUPPLY RETURN
AIR TEMPERATURE/Data
3--2
1.
2.
3.
4.
Mounting Screw
Micro-Link 3
Controller
Connectors
Test Points
5.
6.
Fuses
Control Circuit Power Connection
(Location: In back of controller)
7. Software Programming Port
8. Battery Pack
Figure 3-9 Micro-Link 3 Controller
c. Provide ability to read, and if applicable, modify the
configuration software variables, operating software
function codes, and alarm code indications.
3.1.3 Controller
CAUTION
d. Provide a pre-trip step-by-step checkout of refrigeration unit performance, including proper component
operation, electronic and refrigeration control operation, heater operation, probe calibration, pressure
limiting, and current limiting settings.
Do not remove wire harnesses from controller unless you are grounded to the unit
frame with a static safe wrist strap.
CAUTION
Unplug all controller wire harness connectors before performing arc welding on any
part of the container.
NOTE
Do not attempt to service the controller. Breaking the seal will void the warranty.
Software
(Configuration
NOTE
Do not attempt to use an ML2i PC card in an
ML3 equipped unit. The PC cards are physically
different and will result in damage to the
controller.
The Micro-Link 3 controller is a single module
microprocessor as shown in Figure 3-9. It is fitted with
test points, harness connectors and a software card
programming port.
T-354
b. The right window will display the value of this item for
five seconds before returning to the normal display
mode.
c. If a longer time is desired, press the ENTER key to
extend the time to 30 seconds.
3.3 MODES OF OPERATION
The operational software responds to various inputs.
These inputs come from the temperature and pressure
sensors, the temperature set point, the settings of the
the configuration variables, and the function code
assignments. The action taken by the operational
software will change if any one of the inputs changes.
Overall interaction of the inputs is described as a mode
of operation. The modes of operation include perishable
(chill) mode and frozen mode. Descriptions of the
controller interaction and modes of operation are
provided in the following sub paragraphs.
3--4
T-354
NOTE
On start up of the unit, SMV will reset to a known
open position. This is accomplished by assuming the valve was fully open, driving it fully
closed, resetting the percentage open to zero,
then opening to a known 21% staging position.
3--6
3.6 DataCORDER
b. The alarm queue stores up to 16 alarms in the sequence in which they occurred. The user may scroll
through the list by depressing an ARROW key.
3.6.1 Description
The Carrier Transicold DataCORDER software is
integrated into the controller and serves to eliminate the
temperature recorder and paper chart. The
DataCORDER functions may be accessed by keypad
selections and viewed on the display module. The unit is
also fitted with interrogation connections (see
Figure 3-6), which may be used with the Carrier
Transicold Data Reader to download data. A personal
computer with Carrier Transicold Data View software
may also be used to download data and configure
settings. The resulting file uses a proprietary file format
that protects it from potential tampering or altering of
data. Therefore, once downloaded, all dcx files shall be
considered secured. The DataCORDER consists of:
S Configuration Software
S Operational Software
S Data Storage Memory
S Battery Low (Battery Pack)
S Real--Time Clock (with internal battery backup)
S Six thermistor inputs
S Interrogation Connections
S Power Supply (battery pack)
NOTE
AL26 is active when all of the sensors are not responding. Check the connector at the back of the
controller, if it is loose or unplugged, reconnect it.
Then run a pretrip test (P5) to clear AL26.
3.5 UNIT PRE-TRIP DIAGNOSTICS
CAUTION
S
S
S
S
S
S
S
S
S
S
CAUTION
S
S
S
S
When Pre-Trip key is pressed, dehumidification and bulb mode will be deactivated. At
the completion of Pre-Trip activity, dehumidification and bulb mode must be
reactivated.
S
S
S
S
S
S
S
S
S
S
S
Container ID Change
Software Upgrades
Alarm Activity
Battery Low (Battery Pack)
Data Retrieval
Defrost Start and End
Dehumidification Start and End
Power Loss (w/wo battery pack)
Power Up (w/wo battery pack)
Remote Probe Temperatures in the Container
(USDA cold treatment and cargo probe recording)
Return Air Temperature
Set Point Change
Supply Air Temperature
Real Time Clock Battery (Internal Battery)
Replacement
Real--Time Clock Modification
Trip Start
ISO Trip Header (When entered via Interrogation
program)
Economy Mode Start and End
Auto 2 Pre-Trip Start and End
Bulb Mode Start
Bulb Mode changes
Bulb Mode End
USDA Trip Comment
Humidification Start and End
USDA Probe Calibration
T-354
b. Generic Mode
The generic recording mode allows user selection of the
network data points to be recorded. The user may select
up to a total of eight data points for recording. A list of the
data points available for recording follows. Changing the
configuration to generic and selecting which data points
to record may be done using the Carrier Transicold Data
Retrieval Program.
1. Control mode
2. Control temperature
3. Frequency
4. Humidity
5. Phase A current
6. Phase B current
7. Phase C current
8. Main voltage
9. Suction modulation valve percentage
10. Discrete outputs (See Note )
11. Discrete inputs (See Note )
12. Ambient sensor
13. Compressor suction sensor
14. Compressor discharge sensor
15. Return temperature sensor
16. Supply temperature sensor
17 Defrost temperature sensor
18. Discharge pressure transducer
19. Suction pressure transducer
20. Condenser pressure transducer
b. Configuration Software
The configuration software controls the recording and
alarm functions of the DataCORDER. Reprogramming
to the factory-installed configuration is achieved via the
same configuration card as the unit control module
software. Changes to the software may be made made
using the Data View integration device. A listing of the
configuration variables is provided in Table 3-2.
Descriptions of DataCORDER operation for each
variable setting are provided in the following
paragraphs.
3.6.3 Sensor Configuration (dCF02)
Two modes of operation may be configured, the
Standard Mode and the Generic Mode.
a. Standard Mode
In the standard mode, the user may configure the
DataCORDER to record data using one of seven
standard configurations. The seven standard
configuration variables, with their descriptions, are
listed in Table 3-3.
T-354
TITLE
(Future Use)
Sensor Configuration
Logging Interval (Minutes)
Thermistor Format
Thermistor Sampling Type
Controlled Atmosphere/Humidity Sampling Type
Alarm Configuration USDA Sensor 1
Alarm Configuration USDA Sensor 2
Alarm Configuration USDA Sensor 3
Alarm Configuration Cargo Sensor
3--8
DEFAULT
---2
60
Short
A
A
A
A
A
A
OPTION
---2,5,6,9,54,64,94
15,30,60,120
Low, Normal
A,b,C
A,b
Auto, On, Off
Auto, On, Off
Auto, On, Off
Auto, On, Off
Standard
Config.
2 sensors
(dCF02=2)
5 sensors
(dCF02=5)
6 sensors
(dCF02=6)
9 sensors
(dCF02=9)
Description
2 thermistor inputs(supply & return)
2 thermistor inputs(supply & return)
3 USDA thermistor inputs
2 thermistor inputs(supply & return)
3 USDA thermistor inputs
1 humidity input
Not Applicable
3.6.8
DataCORDER Power-Up
3--9
T-354
Serial : 04189552
Format
Resolution
3--10
c DataLine
a. USDA Recording
A special type of recording is used for USDA cold
treatment purposes. Cold treatment recording requires
three remote temperature probes be placed at
prescribed locations in the cargo. Provision is made to
connect these probes to the DataCORDER via
receptacles located at the rear left-hand side of the unit.
Four or five receptacles are provided. The four three-pin
receptacles are for the probes and fifth, five-pin,
receptacle is the rear connection for the the Interrogator.
The probe receptacles are sized to accept plugs with
tricam coupling locking devices. A label on the back
panel of the unit shows which receptacle is used for
each probe.
The standard DataCORDER report displays the supply
and return air temperatures. The cold treatment report
displays USDA #1, #2, #3, and the supply and return air
temperatures. Cold treatment recording is backed up by
a battery so recording can continue if AC power is lost.
b. USDA Message Trip Comment
A special feature is incorporated which allows the user
to enter a USDA (or other) message at the head of a
data report. The maximum message length is 78
characters. Only one message will be recorded per day.
DataReader
T-354
T-354
3--12
TITLE
DEFAULT
OPTION
CnF01
Bypass Valve Enable
In
Out
CnF02
Evaporator Fan Speed
dS (Dual)
SS (Single)
CnF03
Control Sensors
FOUr
duAL
CnF04
Dehumidification Mode
On
OFF
CnF05
Reserved for future use
---------n/a
CnF06
Condenser Fan Speed Select
OFF (Single)
On (Variable)
CnF07
Unit Selection, 20FT/ 40FT/45FT
40ft
20ft,45
CnF08
Single Phase/Three Phase Motor
1Ph
3Ph
CnF09
Refrigerant Selection
r134a
r12, r22, bLEnd
CnF10
Two Speed Compressor Logic
Out (Single)
In (Dual)
CnF11
Defrost Off Selection
noOFF
OFF
CnF12
TXV/Solenoid Quench Valve
Out (TXV)
In (Solenoid)
CnF13
Unloader
Out
In
CnF14
Condenser Pressure Control (CPC)
In
Out
CnF15
Discharge Temperature Sensor
Out
In
CnF16
DataCORDER Present
On (Yes)
OFF (No)
CnF17
Discharge Pressure Sensor
Out (No)
In (Yes)
CnF18
Heater
Old (Low Watt)
nEW (High Watt)
CnF19
Controlled Atmosphere
Out (No)
In (Yes)
CnF20
Suction Pressure Sensor
Out (No)
In (Yes)
CnF21
Autotransformer
Out
In
CnF22
Economy Mode Option
OFF
Standard, Full
CnF23
Defrost Interval Timer Save Option
noSAv
SAv
CnF24
Advanced Pre-Trip Enhanced Test Series Option
Auto
Auto2, Auto 3
CnF25
Pre-Trip Test Points/Results Recording Option
rSLtS
dAtA
CnF26
Heat Lockout Change Option
Set to -10C
Set to -5C
CnF27
Suction Temperature Display Option
Out
In
CnF28
Bulb Mode Option
NOr
bULb
CnF29
Arctic Mode
Out
In
CnF30
Compressor Size
41 CFM
37 CFM
CnF31
Probe Check Option
Standard
SPEC
CnF32
Single Evaporator Fan Option
2EF0
1EF0
CnF33
Snap Freeze Option
OFF
SnAP
CnF34
Degree Celsius Lockout Option
bOth
F
CnF35
Humidification Mode
OFF
On
CnF36
SMV Type
1 (standard)
2, 3 (stepper)
CnF37
Electronic Temperature Recorder
rEtUR
SUPPL, bOth
CnF38
Quench Bypass Valve
Out
In
CnF39
Expanded Current Limit Range
Out
In
CnF40
Demand Defrost
Out
In
CnF41
Lower DTT Setting
Out
In
CnF42
Auto Pre-trip Start
Out
In
CnF47
Fresh Air Vent Position Sensor
OFF
UPP, LOW
CnF48
CFS Override
OFF
On
CnF49
Datacorder Configuration Restore
OFF
On
CnF50
Enhanced Bulb Mode Selection
OFF
Bulb, dEHUM
CnF51
Timed Defrost Disable
0
0-out, 1-in
Note: Configuration numbers not listed are not used in this application. These items may appear when loading
configuration software to the controller but changes will not be recognized by the controller programming.
3--13
T-354
TITLE
DESCRIPTION
Displays the SMV percent open. The right display reads 100% when the valve
is fully open and 0% when the valve is fully closed. The valve will usually be at
21% on start up of the unit except in very high ambient temperatures.
Not used
The current sensor measures current on two legs. The third unmeasured leg is
calculated based on a current algorithm. The current measured is used for control and diagnostic purposes.
For control processing, the highest of the Phase A and B current values is
used for current limiting purposes. For diagnostic processing, the current draws
are used to monitor component energization.
Whenever a heater or a motor is turned ON or OFF, the current draw increase/
reduction for that activity is measured. The current draw is then tested to determine if it falls within the expected range of values for the component.
Failure of this test will result in a pre-trip failure or a control alarm indication.
The main supply voltage is displayed.
The value of the main power frequency is displayed in Hertz. The frequency
Cd08 Main Power Frequency displayed will be halved if either fuse F1 or F2 is bad (alarm code AL21).
Cd09 Ambient Temperature
Compressor Suction
Cd10 Temperature
Compressor Discharge
Cd11 Temperature
Compressor discharge temperature sensor reading is displayed.
Compressor Suction
Cd12 Pressure
Compressor
Cd14 Discharge Pressure
Compressor Motor
Cd16 Hour Meter / Switch
On Time
Records total hours of compressor run time. Total hours are recorded in increments of 10 hours (i.e., 3000 hours is displayed as 300).
/ Press Enter to display Start Switch ON time.
Humidity sensor reading is displayed. This code displays the relative humidity,
as a percent value.
This code checks the Controller/DataCORDER battery pack. While the test is
running, btest will flash on the right display, followed by the result. PASS will
be displayed for battery voltages greater than 7.0 volts. FAIL will be displayed
for battery voltages between 4.5 and 7.0 volts, and -- -- -- -- -- will be displayed for battery voltages less than 4.5 volts. After the result is displayed for
four seconds, btest will again be displayed, and the user may continue to
scroll through the various codes.
Cd20 Config/Model #
This code indicates the dash number of the model for which the Controller is
configured (i.e., if the unit is a 69NT40-541-100, the display will show 41100).
This code displays the status of the humidity water pump (-- -- -- -- -- , forward,
reverse or off). If not configured, the mode is permanently deactivated and will
display -- -- -- -- -- .
T-354
3--14
TITLE
Controlled
Cd24 Atmosphere State
Compressor Run
Cd25 Time Remaining
Until Defrost
Defrost Temperature
Cd26 Sensor Reading
DESCRIPTION
Not used in this application
This code displays the time remaining until the unit goes into defrost (in tenths of
an hour). This value is based on the actual accumulated compressor running
time.
Defrost temperature sensor reading is displayed.
Configurable Functions
NOTE
Function codes Cd27 through Cd37 are user-selectable functions. The operator can change the value of
these functions to meet the operational needs of the container.
There are two modes for defrost initiation, either user-selected timed intervals or
automatic control. The user-selected values are (OFF), 3, 6, 9, 12, or 24 hours
while the factory default is 12 hours.
Automatic defrost starts with an initial defrost at three hours and then adjusts the
interval to the next defrost based on the accumulation of ice on the evaporator
coil. Following a start-up or after termination of a defrost, the time will not begin
counting down until the defrost temperature sensor (DTS) reading falls below set
point. If the reading of DTS rises above set point any time during the timer count
down, the interval is reset and the countdown begins over.
Defrost Interval
Cd27 (Hours or Automatic) If DTS fails, alarm code AL60 is activated and control switches over to the the
return temperature sensor. The controller will act in the same manner as with the
DTS except the return temperature sensor reading will be used.
Defrost Interval Timer Value (Configuration variable CnF23):
If the software is configured to SAv (save) for this option, then the value of the
defrost interval timer will be saved at power down and restored at power up. This
option prevents short power interruptions from resetting an almost expired defrost
interval, and possibly delaying a needed defrost cycle.
NOTE
The defrost interval timer counts only during compressor run time.
Temperature Units
Cd28 (Degrees C or
Degrees F)
Failure Action
Cd29 (Mode)
This code determines the temperature units (C or F) which will be used for all
temperature displays. The user selects C or F by selecting function code Cd28
and pushing the ENTER key. The factory default value is Celsius units.
NOTE
This function code will display --- --- --- --- --- if Configuration Variable CnF34 is
set to F.
If all of the control sensors are out of range (alarm code AL26) or there is a probe
circuit calibration failure (alarm code AL27), the unit will enter the shutdown state
defined by this setting. The user selects one of four possible actions as follows:
A -- Full Cooling (stepper motor SMV at maximum allowed opening)
B -- Partial Cooling (stepper motor SMV 11% open)
C -- Evaporator Fan Only
D -- Full System Shutdown -- Factory Default
The in-range tolerance will determine the band of temperatures around the set
point which will be designated as in-range. If the control temperature is in-range,
the in-range light will be illuminated. There are four possible values:
1 = +/- 0.5C (+/-0.9F)
2 = +/- 1.0C (+/-1.8F)
3 = +/- 1.5C (+/-2.7F)
4 = +/- 2.0C (+/-3.6F) -- Factory Default
3--15
T-354
TITLE
Current Limit
Cd32 (Amperes)
Perishable Mode
Dehumidification /
Cd33 Humidification
Control (% RH)
DESCRIPTION
The stagger start offset time is the amount of time that the unit will delay at startup, thus allowing multiple units to stagger their control initiation when all units are
powered up together. The eight possible offset values are:
0 (Factory Default), 3, 6, 9, 12, 15, 18 or 21 seconds
The current limit is the maximum current draw allowed on any phase at any time.
Limiting the units current reduces the load on the main power supply. This is accomplished by reducing the SMV position until current draw is reduced to the set
point. When desirable, the limit can be lowered. Note, however, that capacity is
also reduced. The five values for 460VAC operation are:
15, 17, 19, 21 (Factory Default), 23
Relative humidity set point is available only on units configured for dehumidification. When the mode is activated, the control probe LED flashes on and off every
second to alert the user.
If not configured, the mode is permanently deactivated and -- -- -- -- -- will display. The value can be set to OFF. TEST, or a range of 65 to 95% relative humidity in increments of 1%. [If bulb mode is active (code Cd35) and Lo speed
evaporator motors are selected (code Cd36) then set point ranges from 60 to
95%].
When TEST is selected or test set point is entered, the heat LED should illuminate, indicating that dehumidification mode is activated. After a period of five minutes in the TEST mode has elapsed, the previously selected mode is reinstated.
NOTE
If humidification (CnF35) is enabled, then humidification will be enabled and
dehumidification locked out at set points of 75% and above. At set points below 75%, dehumidification will be enabled and humidification locked out.
Economy Mode
Cd34 (On--Off)
Economy mode is a user selectable mode of operation provided for power saving
purposes.
Bulb mode is a user selectable mode of operation that is an extension of dehumidification control (Cd33). If dehumidification is set to Off, code Cd35 will display Nor and the user will be unable to change it.
After a dehumidification set point has been selected and entered for code Cd33,
the user may then change code Cd35 to bulb. After bulb has been selected and
entered, the user may then utilize function codes Cd36 and Cd37 to make the
desired changes.
Evaporator Speed
Cd36 Select
Defrost Termination
Cd37 Temperature Setting
(Bulb Mode)
T-354
This code is enabled only if in the dehumidification mode (code Cd33) and bulb
mode (Cd35) has been set to bulb. If these conditions are not met, alt will be
displayed (indicating that the evaporator fans will alternate their speed) and the
display cannot be changed.
If a dehumidification set point has been selected along with bulb mode then alt
may be selected for alternating speed, Lo for low speed evaporator fan only, or
Hi for high speed evaporator fan only.
If a setting other than alt has been selected and bulb mode is deactivated in any
manner, then selection reverts back to alt.
This code, as with function code Cd36, is used in conjunction with bulb mode and
dehumidification. If bulb mode is active, this code allows the user to change the
defrost termination thermostat settings. If bulb mode is deactivated, the DTS setting returns to the default.
3--16
TITLE
DESCRIPTION
Supply Recorder
Cd38 Sensor (SRS)
Code Cd38 will display the current secondary supply temperature sensor reading
for units configured for four probes. If the unit is configured with a DataCORDER,
Cd38 will display -- -- -- -- -- . If the DataCORDER suffers a failure, (AL55) Cd38
will display the supply recorder sensor reading.
Return Recorder
Cd39 Sensor (RRS)
Code Cd39 will display the current secondary return temperature sensor reading
for units configured for four probes. If the unit is configured with a DataCORDER,
Cd39 will display -- -- -- -- -- . If the DataCORDER suffers a failure, (AL55) Cd39
will display the return recorder sensor reading.
Container
Cd40 Identification
Number
Cd41
Cd42 Not Applicable
Code Cd43 is a user selectable mode of operation that allows the opening and
closing of a mechanical air vent door via a stepper motor. These selection modes
are as follows:
OFF -- Air makeup vent will remain closed.
User -- Allows for manual selection of the setting.
Delay --The opening of the door is based on selected time, return temperature
and flow rate (percent opened).
Cd43 AutoFresh Mode
gASLM -- The opening is based percent open and CO2 and O2 selectable limits
(LM). This selection is only active if the unit has a CO2 sensor.
TEST / CAL (CO2 sensor option units only) -- The door will fully open and close
to allow the user to inspect its operation. If CAL is selected, the controller will
zero calibrate the CO2 sensor input.
If the unit is not configured with AutoFresh, the CD43 will display --------
Code Cd44 will display CO2 and O2 concentrations and limits. If the unit is not
configured for AutoFresh or a CO2 sensor is not installed, CD44 will display
Cd44 AutoFresh Values
--------
Code Cd45 will display whenever the control detects movement via the sensor
Vent Position Sensor unless alarm 50 is active. The code will display for 30 seconds, then time out and
Cd45 (VPS)
return to the normal display mode. If the Temperature unit is degrees F, the VPS
units will be CFM and in degrees C the VPS units shall be CMH.
Cd46 Not Used
Variable Economy
Cd47 Temperature Setting
Dehumidification/
Cd48 Bulb Mode
Parameter Selection
Days Since Last
Cd49 Successful Pre-trip
3--17
T-354
TITLE
DESCRIPTION
Manual Defrost
AL05 Switch Failure
Keypad or Harness
AL06 Failure
Alarm 07 is triggered if the VPS is reading greater than 0 CMH based on the
Fresh Air Vent Open function code display value and a frozen set point is active.
If AL 50 is active, AL 07 will not be generated.
AL07 with Frozen Set
The alarm will go inactive if the VPS reading transitions to 0 CMH, the set point
Point
transitions to the perishable range, or an AL50 is active.
AL10 CO2 Sensor Failure
Alarm 10 is triggered when the CO2 sensor voltage is operating outside of the 0.9
v to 4.7 v range, or if the sensor is out of range. This is a display alarm and has
no associated failure action.
Evaporator Motor 1
AL11 IP Trip
Alarm 11 is applicable to units with Single Evaporator Fan Capability (CnF32 set
to 1EFO) only. The alarm is triggered if the evaporator fan motor #1 internal protector opens. If the alarm is active, probe check is deactivated.
Evaporator Motor 2
AL12 IP Trip
Alarm 12 is applicable to units with Single Evaporator Fan Capability (CnF32 set
to 1EFO) only. The alarm is triggered if the evaporator fan motor #2 internal protector opens. If the alarm is active, probe check is deactivated.
Alarm 20 is triggered by control power fuse (F3A, F3B) opening and will cause
the software shutdown of all control units. This alarm will remain active until the
fuse is replaced.
Evaporator Fan
AL22 Motor Safety
Alarm 22 responds to the evaporator motor internal protectors. On units with Normal Evaporator Fan Operation (CnF32 set to 2EFO) the alarm is triggered by
opening of either internal protector. It will disable all control units until the motor
protector resets. On units with Single Evaporator Fan Capability (CnF32 set to
1EFO), the alarm is triggered by opening of both internal protectors. It will disable
all control units until a motor protector resets.
Compressor Motor
AL24 Safety
Condenser Fan
AL25 Motor Safety
Alarm 26 is triggered if the Controller determines that all of the control sensors
are out-of-range. This can occur for box temperatures outside the range of -50C
to +70C (-58F to +158F). This alarm triggers the failure action code set by
Function Code Cd29.
Probe Circuit
AL27 Calibration Failure
The Controller has a built-in Analog to Digital (A-D) converter, used to convert
analog readings (i.e. temperature sensors, current sensors, etc.) to digital readings. The Controller continuously performs calibration tests on the A-D converter.
If the A-D converter fails to calibrate for 30 consecutive seconds, this alarm is
activated.This alarm will be inactivated as soon as the A-D converter calibrates.
T-354
3--18
TITLE
Primary Supply
AL54 Temperature Sensor
Failure (STS)
DESCRIPTION
Alarm 29 is triggered if CO2 or O2 level is outside of the limit range and the vent
position is at 100% for longer than 90 minutes. Alarm LED will be activated and
user intervention is required. The alarm is triggered off when atmospheric conditions are within limit settings.
Alarm 50 is activated whenever the sensor is outside the valid range. There is a
five minute adjustment period where the user can change the vent position without generating an alarm event. The sensor requires five minutes of no movement
to confirm stability. If the vent position changes at any point beyond the five minute adjustment period, the sensor will generate an alarm event. The alarm is triggered off when the unit power cycles and the sensor is within valid range.
During start-up diagnostics, the EEPROM is examined to determine validity of its
contents. This is done by testing the set point and the alarm list. If the contents
are invalid, Alarm 51 is activated.
During control processing, any operation involving alarm list activity that results in
an error will cause Alarm 51 to be activated. Alarm 51 is a display only alarm
and is not written into the alarm list.
Pressing the ENTER key when CLEAr is displayed will result in an attempt to
clear the alarm list. If that action is successful (all alarms are inactive), Alarm 51
will be reset.
Alarm 52 is activated whenever the alarm list is determined to be full; at start-up
or after recording an alarm in the list. Alarm 52 is displayed, but is not recorded in
the alarm list. This alarm can be reset by clearing the alarm list. This can be done
only if all alarms written in the list are inactive.
Alarm 53 is caused by the battery pack charge being too low to provide sufficient
power for battery-backed recording. Renew replaceable batteries.
If this alarm occurs on start up, allow a unit fitted with rechargeable batteries to
operate for up to 24 hours to charge rechargeable batteries sufficiently to deactivate the alarm
Alarm 54 is activated by an invalid primary supply temperature sensor reading
that is sensed outside the range of -50 to +70C (-58F to +158F) or if the probe
check logic has determined there is a fault with this sensor.
If Alarm 54 is activated and the primary supply is the control sensor, the secondary supply sensor will be used for control if the unit is so equipped. If the unit
does not have a secondary supply temperature sensor, and AL54 is activated,
the primary return sensor reading, minus 2C will be used for control.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm
Primary Return
AL56 Temperature Sensor
Failure (RTS)
Ambient
AL57 Temperature Sensor
Failure
Compressor High
AL58 Pressure Safety
Alarm 58 is triggered when the compressor high discharge pressure safety switch
remains open for at least one minute. This alarm will remain active until the pressure switch resets, at which time the compressor will restart.
Alarm 59 is triggered by the opening of the heat termination thermostat and will
result in the disabling of the heater. This alarm will remain active until the thermostat resets.
Heat Termination
AL59 Thermostat
3--19
T-354
TITLE
DESCRIPTION
T-354
3--20
TITLE
DESCRIPTION
The controller performs self-check routines. If an internal failure occurs, an ERR
alarm will appear on the display. This is an indication the controller needs to be
replaced.
ERROR
DESCRIPTION
Indicates that the controller working memory has
ERR 0 -- RAM failure
failed.
EER 1 -- Program Memory
Indicates a problem with the controller program.
failure
EER 2 -- Watchdog
The controller program has entered a mode whereby
time-out
the controller program has stopped executing.
EER 3 -- N/A
EER 4 -- N/A
N/A
N/A
The Controllers Analog to Digital (A-D) converter
has failed.
Internal program/update failure.
Internal version/firmware incompatible.
Internal
Microprocessor
Failure
Entr
StPt
Enter Setpoint
(Press Arrow &
Enter)
Low Main Voltage
(Function Codes
Cd27-38 disabled
and NO alarm
stored.)
LO
This message will be alternately displayed with the set point whenever the supply
voltage is less than 75% of its proper value.
3--21
T-354
P3
Low Speed
Evaporator Fans
P3-0
Low Speed
Evaporator Fan
Motors On
P3-1
Low Speed
Evaporator Fan
Motors Off
Setup: Condenser fan is turned OFF, a current draw test is done after
10 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
Requirements: The unit must be equipped with a low speed evaporator fan, as
determined by the Evaporator Fan speed select configuration variable.
NOTE
If the unit is configured for single evaporator fan operation, Pre-Trip tests
P3-0, P3-1, P4-0 and P4-1 will fail immediately if Controller alarm codes
AL11 or AL12 are active at the start of testing.
Setup: The high speed evaporator fans will be turned on for 10 seconds, then off
for two seconds, then the low speed evaporator fans are turned on. A current
draw test is done after 60 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range specified. Fails if AL11 or AL12 activates during test.
Setup: The low speed Evaporator Fan is turned off, a current draw test is done
after 10 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range specified. Fails if AL11 or AL12 activates during test.
P4-0
High Speed
Evaporator Fan
Motors On
Setup: The high speed Evaporator Fan is turned on, a current draw test is done
after 60 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range specified. Fails if AL11 or AL12 activates during test.
P4-1
High Speed
Evaporator Fan
Motors Off
Setup: The high speed Evaporator Fan is turned off, a current draw test is done
after 10 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range specified. Fails if AL11 or AL12 activates during test.
P5-0
Supply/Return
Probe Test
P5-1
T-354
Setup: The High Speed Evaporator Fan is turned on and run for eight minutes,
with all other outputs de-energized.
Pass/Fail Criteria: A temperature comparison is made between the return and
supply probes.
NOTE
If this test fails, P5-0 and FAIL will be displayed. If both Probe tests (this test
and the PRIMARY/ SECONDARY) pass, the display will read P5 PASS.
Requirements: For units equipped with secondary supply probe only.
Pass/Fail Criteria: The temperature difference between primary and secondary
probe (supply) is compared.
NOTE
If this test fails, P5-1 and FAIL will be displayed. If both Probe tests (this
and the SUPPLY/ RETURN TEST) pass, because of the multiple tests, the
display will read P 5 PASS.
3--22
TITLE
DESCRIPTION
Requirements: For units equipped with secondary return probe only.
Pass/Fail Criteria: The temperature difference between primary and secondary
probe (return) is compared.
NOTES
P5-2
1. If this test fails, P5-2 and FAIL will be displayed. If both Probe tests
(this test and the SUPPLY/ RETURN) pass, because of the multiple
tests, the display will read P 5, PASS.
2. The results of Pre-Trip tests 5-0, 5-1 and 5-2 will be used to activate or
P6-4
P6-5
Not Applicable
Not Applicable
Setup: The compressor suction temperature is measured with the Quench valve
closed. The Quench valve is energized and the suction temperature drop is
checked.
Pass/Fail Criteria: Passes if suction temperature is within the valid range.
Not Used
Not Used
3--23
T-354
TITLE
DESCRIPTION
NOTE
P7-0 & P8 are included with the Auto2 & Auto 3 only. P9-0 through P10 are included with Auto2 only
Setup: When the unit is running, the condenser fan is de-energized, and a
15 minute timer is started. The right display shows discharge pressure if the unit
is equipped with a discharge pressure transducer (DPT). If no DPT is installed,
the condenser pressure transducer (CPT) reading will be displayed.
Pass/Fail Criteria: The test fails if high pressure switch fails to open in
15 minutes.
Note, this test is skipped if the unit does NOT have:
A compressor discharge sensor (CPDS).
A discharge pressure transducer (DPT).
Condenser pressure transducer (CPT).
In addition, this test is skipped if:
The sensed ambient temperature is less than 7C (45F).
The return air temperature is less than -17.8C (0F).
P7-0
High Pressure
Switch Closed
The water pressure switch (WP) is open, indicating that the unit is operating
with a water-cooled condenser.
Pass/Fail Criteria: Under conditions of the above NOTE; the test immediately
fails if the following inputs are sensed to be invalid:
Compressor discharge sensor (CPDS).
Discharge pressure transducer (DPT).
Condenser pressure transducer (CPT).
OR, if any one of the following inputs are sensed to be invalid:
Return temperature sensor (RTS).
Ambient sensor (AMBS).
In addition, the test will fail if:
The high pressure switch (HPS) fails to open within 15 minutes.
The discharge temperature exceeds 138C (280F).
The discharge temperature is less than or equal to ambient temperature
plus 5C (9F).
P7-1
P8-0
T-354
High Pressure
Switch Open
Perishable Mode
Heat Test
The condenser pressure transducer (CPT) or discharge pressure transducer (DPT) pressure exceeds 27.42kg/cm2 (390psig).
Requirement: Test P7-0 must pass for this test to execute. Setup: The condenser fan is started and a 60 second timer is started.
Pass/Fail Criteria: Passes the test if the high pressure switch (HPS) closes
within the 60--second time limit, otherwise, it fails.
Setup: If the container temperature is below 15.6C (60F), the set point is
changed to 15.6C, and a 60--minute timer is started. The left display will read
P8-0. The control will then heat the container until 15.6C is reached. If the
container temperature is above 15.6C at the start of the test, then the test proceeds immediately to test P8-1 and the left display will change to P8-1.
Pass/Fail Criteria: The test fails if the 180--minute timer expires before the control temperature reaches set point. The display will read P8-0, FAIL.
3--24
P8-1
P8-2
P9-0
P10-0
P10-1
P10-2
TITLE
DESCRIPTION
Perishable Mode
Pull Down Test
Perishable Mode
Maintain
Temperature Test
Defrost Test
Setup: The defrost temperature sensor (DTS) reading will be displayed on the
left display. The right display will show the supply air temperature. The unit will
run FULL COOL for 30 minutes maximum until the DTT is considered closed.
Once the DTT is considered closed, the unit simulates defrost by running the
heaters for up to two hours, or until the DTT is considered open.
Pass/Fail Criteria: The test fails if: the DTT is not considered closed after the
30 minutes of full cooling, HTT opens when DTT is considered closed or if return
air temperature rises above 248C (120F).
Frozen Mode
Setup Test
Setup: After completion of the defrost test, the testing proceeds directly to test
P10-1 if the container temperature is above 7C (45F). If the container temperature is below 7C, a 180--minute timer will be started, the set point will be set to
7C and the control will be placed in normal heat. The left display will read
P10-0 and the unit will continue in operation until the temperature is raised to
set point.
Pass/Fail Criteria: If the temperature does not reach set point (less -0.3C or
6.7F) before the timer times out display will read P100, FAIL. The test will
not auto-repeat.
Frozen Mode
(Pull Down) Test
Setup: When the container temperature is greater than or equal to the 7.2C
(45F) set point which was set in the Frozen Mode Setup Test, the left display
will read P10-1 and the right display will show the return air temperature. The
set point will then be changed to -17.7C (0F). The unit will then have a maximum of three hours to pull the container temperature down to the -17.7C set
point.
Pass/Fail Criteria: If this occurs within the three hour time limit, the test passes.
If pulldown is not completed within the three hour time, the test fails.
Frozen Mode
Maintain
Temperature Test
Setup: After the unit has successfully completed frozen pulldown test, the left
display will read P10-2 and the right display will show return air temperature.
The unit will then be required to maintain -17.7C (0F) temperature within
+/-0.5C (0.9F) of set point until a DataCORDER recording is executed.
The recorder return probe temperature running total (and its associated counter)
will be zeroed for the remainder of the recording period at the start of this test, so
that the actual recorded value will be an average of only this tests results.
Once the recording interval is complete, the average return temperature will be
recorded in the DataCORDER, and stored in memory for use in applying the test
pass/fail criteria.
Pass/Fail Criteria: If the recorded temperature is within +/-0.5C of set point
from test start to DataCORDER recording, the test passes. If temperature is outside of the tolerance range at the DataCORDER recording, the test fails.
3--25
T-354
TITLE
DESCRIPTION
dC1
Recorder Supply
Temperature
dC2
Recorder Return
Temperature
dC3-5
USDA 1,2,3
Temperatures
dC6-13
Network Data
Points 1-8
Current values of the network data points (as configured). Data point 1 (Code
6) is generally the humidity sensor and its value is obtained from the Controller once every minute.
dC14
Cargo Probe 4
Temperature
dC28
dC29
Days Stored
dC30
dC31
dC32
dC33
dC34
dC35
T-354
These codes are for future expansion, and are not in use at this time.
Current calibration offset values for each of the five probes: supply, return,
USDA #1, #2, and #3. These values are entered via the interrogation program.
This code is for future expansion, and is not in use at this time.
The DataCORDER serial number consists of eight characters. Function code
dC26 contains the first four characters. Function code dC27 contains the last
four characters. (This serial number is the same as the Controller serial
number)
An approximation of the number of logging days remaining until the DataCORDER starts to overwrite the existing data.
3--26
Heater On
Heater Off
2-0
Condenser Fan On
2-1
6-4
6-5
7-0
7-1
8-0
8-1
Perishable Heat
Perishable Pull Down
8-2
Perishable Maintain
9-0
Defrost Test
10-0
10-1
10-2
3-0
3-1
4-0
4-1
5-0
5-1
5-2
6-0
6-1
6-2
TITLE
DATA
Pass/Fail/Skip Result, Change in current for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Water pressure switch (WPS) -- Open/Closed,
Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, STS, RTS, SRS and RRS
Pass/Fail/Skip Result
Pass/Fail/Skip Result
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Not Used
Pass/Fail/Skip Result, Is current or pressure limit in effect (Y,N)
Not Used
Not Used
Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens
Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes
Pass/Fail/Skip Result, STS, time it takes to heat to 16C (60F)
Pass/Fail/Skip Result, STS, time it takes to pull down to 0C (32F)
Pass/Fail/Skip Result, Averaged DataCORDER supply temperature
(SRS) over last recording interval.
Pass/Fail/Skip Result, DTS reading at end of test, line voltage, line
frequency, time in defrost.
Pass/Fail/Skip Result, STS, time unit is in heat.
Pass/Fail/Skip Result, STS, time to pull down unit to -17.8C (0F).
Pass/Fail/Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.
3--27
T-354
TITLE
dAL70
Recorder Supply
Temperature Out of
Range
dAL71
Recorder Return
Temperature Out of
Range
The return recorder sensor reading is outside of the range of -50 to 70C
(-58F to +158F) or, the probe check logic has determined there is a fault
with this sensor.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm.
dAL72-74
USDA Temperatures
1, 2, 3 Out of Range
dAL75
dAL76, 77
Future Expansion
dAL78-85
dAL86
These alarms are for future expansion, and are not in use at this time.
The network data point is outside of its specified range. The DataCORDER is configured by default to record the supply and return recorder sensors.
The DataCORDER may be configured to record up to 8 additional network
data points. An alarm number (AL78 to AL85) is assigned to each configured point.
When an alarm occurs, the DataCORDER must be interrogated to identify
the data point assigned.
When a humidity sensor is installed, it is usually assigned to AL78.
The Real Time Clock (RTC) backup battery is too low to adequately
maintain the RTC reading.
dAL87
RTC Failure
An invalid date or time has been detected. This situation may be corrected
by changing the Real Time Clock (RTC) to a valid value using DataLINE.
dAL88
DataCORDER
EEPROM Failure
dAL89
An error has been detected in the process of writing daily data to the nonvolatile FLASH memory.
dAL90
dAL91
Future Expansion
Alarm List Full
This alarm is for future expansion, and is not in use at this time.
The DataCORDER alarm queue is determined to be full (eight alarms).
T-354
3--28
SECTION 4
OPERATION
4.1 INSPECTION (Before Starting)
WARNING
Beware of unannounced starting of the
evaporator and condenser fans. The unit
may cycle the fans and compressor unexpectedly as control requirements dictate.
WARNING
Do not attempt to remove power plug(s) before turning OFF start-stop switch (ST), unit
circuit breaker(s) and external power
source.
WARNING
4--1
T-354
NOTE
The user has four minutes to make necessary
adjustments to the vent setting. This time
begins on the initial movement of the sensor.
The vent can be moved to any position within
the four minutes.
On completion of the first four minutes, the vent
is required to remain stable for the next four
minutes. If vent position changes are detected
during the four minutes stability period, an
alarm will be generated. This provides the user
with the ability to change the vent setting
without generating multiple events in the
DataCorder.
To clear the gap between the slots, loosen the wing nut
until the disc clears the stop. Figure 4-2 gives air
exchange values for an empty container. Higher values
can be expected for a fully loaded container.
69NT40 FRESH AIR MAKEUP
AIR
FLOW
(CMH)
240
T-BAR
T-BAR
1-!/2
210
2-%/8
180
T-BAR
150
a. Connect the water supply line to the inlet side of condenser and the discharge line to the outlet side of the
condenser (see Figure 2-5).
120
90
60
30
0
NOTE
If controller configuration variable CNF48 is activated the condenser fan motor will activate if
the HPS opens twice in less than seven minutes. Power cycling the unit resets the counter.
0 10 20 30 40 50 60 70 80 90 100
PERCENT OPEN
For 60Hz operation multiply curves by 1.2
T--354
c. To shift to air-cooled condenser operation, disconnect the water supply and the discharge line to the
water-cooled condenser.
The refrigeration unit will shift to air-cooled condenser
operation when the water pressure switch closes or if
the controller configuration variable CNF48 is activated, the condenser fan motor will activate if the
HPS opens twice in less than seven minutes. Power
cycling the unit resets the count.
4--2
DataCORDER
a. Check, and if required, set the DataCORDER Configuration in accordance with desired recording parameter (refer to paragraph 3.6.3).
b. Enter a Trip Start. To enter a Trip Start, do the
following:
FUNCTION
Energizes remote cool light
Energizes remote defrost light
Energizes remote in-range light
WARNING
CAUTION
Pre-trip inspection should not be performed with critical temperature cargoes in
the container.
CAUTION
When Pre-Trip key is pressed, dehumidification and bulb mode will be deactivated.
At the completion of Pre-Trip activity, dehumidification and bulb mode must be
reactivated.
Pre-Trip diagnosis provides automatic testing of the unit
components using internal measurements and
comparison logic. The program will provide a PASS or
FAIL display to indicate test results.
4--3
T-354
Auto 3
CAUTION
CAUTION
When Pre-Trip test Auto 2 runs to
completion without being interrupted,
the unit will terminate pre-trip and
display Auto 2 end. The unit will
suspend operation until the user
depresses the ENTER key!
T--354
4--4
4--5
T-354
FALLING
TEMPERATURE
+2.5C (4.5F)
RISING
TEMPERATURE
+1.5C (2.7F)
MODULATING
COOLING
+1C (1.8F)
MODULATING
COOLING
+0.5C (0.9F)
+0.20C
AIR CIRCULATION
SET POINT
-0.20C
-0.5C (0.9F)
AIR CIRCULATION
-1C (1.8F)
HEATING
-1.5C (2.7F)
HEATING
FALLING
TEMPERATURE
RISING
TEMPERATURE
+1.5C (2.7F)
COOLING
+1C (1.8F)
COOLING
+0.5C (0.9F)
+0.20C
SET POINT
-0.20C
-0.5C (0.9F)
AIR
CIRCULATION
ONLY
-1C (1.8F)
AIR
CIRCULATION
ONLY
-1.5C (2.7F)
T--354
4--6
NOTE
In low temperature ambients, the condenser
fan will be cycled by the controller to maintain
proper condensing pressure.
NOTE
The unit will heat only when in the Perishable
Mode, relay TH is electronically locked out
when in the Frozen Mode.
a. With supply air temperature above set point and decreasing, the unit will be cooling with the condenser
fan motor (CF), compressor motor (CH), evaporator
fan motors (EF) energized, and the COOL light illuminated (see Figure 4-5).
ENERGIZED
DE--ENERGIZED
FOR FULL DIAGRAM AND
LEGEND, SEE SECTION 7
CONTROL TRANSFORMER
POWER TO
CONTROLLER
SIGNAL TO
CONTROLLER
ENERGIZED
DE-ENERGIZED
FOR FULL DIAGRAM AND
LEGEND, SEE SECTION 7
CONTROL TRANSFORMER
POWER TO
CONTROLLER
SIGNAL TO
CONTROLLER
SIGNAL TO
CONTROLLER
SIGNAL TO
CONTROLLER
d. The controller monitors the supply air. Once the supply air falls below set point and 0% SMV position is
reached, the controller periodically records the supply air temperature, set point, and time. A calculation
is then performed by subtracting the set point reading
T-354
NOTES
1.. In the Frozen Mode of operation the
evaporator motors run in low speed.
2.. In low temperature ambients, the
condenser fan will be cycled by the
controller to maintain proper condensing
pressure.
NOTE
The Manual Defrost / Interval key can be used
to initiate a manual defrost. Minimum Software
release version #5126 is required in order to
use this function.
a. With supply air temperature above set point and decreasing, the unit will be cooling with the condenser
fan motor (CF), compressor motor (CH), evaporator
fan motors (ES) energized and the COOL light illuminated (see Figure 4-7).
b.When the air temperature decreases to a predetermined tolerance above set point, the in-range light is
illuminated.
ENERGIZED
DE-ENERGIZED
FOR FULL DIAGRAM AND
LEGEND, SEE SECTION 7
CONTROL TRANSFORMER
POWER TO
CONTROLLER
SIGNAL TO
CONTROLLER
ENERGIZED
DE-ENERGIZED
FOR FULL DIAGRAM AND
LEGEND, SEE SECTION 7
SIGNAL TO
CONTROLLER
POWER TO
CONTROLLER
SIGNAL TO
CONTROLLER
T--354
CONTROL TRANSFORMER
SIGNAL TO
CONTROLLER
SIGNAL TO
CONTROLLER
4--8
CAUTION
The unit will remain in the full cooling mode
as long as the emergency bypass switch is
in the BYPASS position and the MODE
SWITCH is in the FULL COOL position.
If the cargo may be damaged by low temperatures, the operator must monitor container
temperature and manually cycle operation
as required to maintain temperature within
required limits.
In the ON position the EBS will be enabled. With the
MODE SWITCH in the FULL COOL MODE. The
following will occur simultaneously:
1. The EBS switch will enable EBS input.
2. The phase detection circuit will detect the phase
rotation and close to provide power to the compressor contactor.
3. The condenser fan contact will close to energize the
condenser contactor and provide power to the condenser fan motor.
4. The evaporator fan contact will close to energize the
high speed evaporator contactor and provide power
to the evaporator fan motor.
4--9
T-354
CAUTION
NOTE
1. If the unit is in the emergency bypass
cooling mode, the emergency defrost
switch will override this mode and place the
unit in defrost.
T--354
4--10
SECTION 5
TROUBLESHOOTING
CONDITION
POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
No power to unit
Compressor hums,
but does not start
Turn on
Check
Check
4.2.2
Check
Replace
Check
Check
6.16
6.11
6.8
5.7
Replace
Check
Check
6.8
6.8
Refrigeration System
5--1
Normal
Repair
6.7.1
5.6
6.15
6.15/6.16
6.17
Check
Reset
Open valves
completely
6.10
6.8
3.3.5
6.19
T-354
CONDITION
POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
Refrigeration System
6.8
5.7
5.9
6.16
6.19
Check
6.7.1
No control power
Check
Check
Turn ON
Replace
Replace
6.16
Check
6.15
6.15
Replace
6.15/6.16
Replace
5.9
Replace
Tighten
2.3
Reset
5.9
6.15
Table 3-5
Tighten/
Replace
Replace
Replace
4.10.4
2.3
Replace
6.15
T-354
5--2
Replace
CONDITION
POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
Wet load
Normal
6.10
6.11
6.11
6.7.1
6.20
Open
6.19
Open
6.13
6.7.1
6.14
6.15
5.6
6.16
6.20
6.19
Replace
6.8
Check
Compressor
Tighten
6.8
6.8
6.14
6.8.6
Check
6.11/6.16
6.11/6.16
Defective Sensor
Defective wiring
Fuse (F1, F2) blown
Stepper motor suction modulation valve circuit malfunction
5--3
6.23
Check
Replace
6.19
T-354
CONDITION
POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
Frost on coil
Dirty coil
Evaporator fan motor internal protector open
Evaporator fan motor(s) defective
Evaporator fan(s) loose or defective
Evaporator fan contactor defective
5.6
6.15
6.16
6.16
6.16
Replace
6.7.1
Open
6.14
6.7.1
6.14
6.14
Open
6.14
6.14
Check
6.21
Check
4.2.2
T-354
Dirty coil
Noncondensibles
Water pressure switch malfunction
Water supply interruption
5--4
6.12
Check
Check
SECTION 6
SERVICE
NOTE
To avoid damage to the earths ozone layer, use a refrigerant recovery system whenever removing refrigerant. When working with refrigerants, you must comply with all local government environmental laws. In the
U.S., refer to EPA section 608.
WARNING
Never use air for leak testing. It has been determined that pressurized mixtures of refrigerant and air can undergo combustion
when exposed to an ignition source.
OPENED (Backseated )
HAND VALVE
C
CLOSED (Frontseated)
HAND VALVE
VALVE
FRONTSEATED
(Clockwise)
DISCHARGE
PRESSURE
GAUGE
SUCTION
PRESSURE
GAUGE
5
4
VALVE
BACKSEATED
(Counterclockwise)
T--354
4. Front seat both manifold gauge set valves and disconnect from cylinder. The gauge set is now ready
for use.
To Low Side
Service Port
To High Side
Service Port
2
3
Blue
4
6
Blue Knob
13
3 - Red
11
3 - Yellow 4
12
10
5
Red Knob
1. Discharge Service
7.
8.
Valve
9.
2. Compressor
3. Suction Service Valve 10.
4. Receiver or Water
11.
Cooled Condenser
5. Liquid Service Valve 12.
13.
6. Vacuum Pump
T--354
5
7-BLUE
8-YELLOW
9-RED
S D
CAUTION
To prevent trapping liquid refrigerant in the
manifold gauge set, be sure set is brought
to suction pressure before disconnecting.
c. Removing the Manifold Gauge Set
1. While the compressor is still ON, backseat the high
side service valve.
2. Midseat both hand valves on the manifold gauge set
and allow the pressure in the manifold gauge set to
be drawn down to suction pressure. This returns any
liquid that may be in the high side hose to the system.
3. Backseat the suction service valve. Backseat both
field service couplings and frontseat both manifold
set valves. Remove the couplings from the service
ports.
4. Install both service valve stem caps and service port
caps (finger-tight only).
6--2
6.6.1 General
Moisture is the deadly enemy of refrigeration systems.
The presence of moisture in a refrigeration system can
have many undesirable effects. The most common are
copper plating, acid sludge formation, freezing-up of
metering devices by free water, and formation of acids,
resulting in metal corrosion.
6.6.2 Preparation
a. Evacuate and dehydrate only after pressure leak test
(refer to paragraph 6.5).
d. Additional time may be saved during a complete system pump down by replacing the filter-drier with a
section of copper tubing and the appropriate fittings.
Installation of a new drier may be performed during
the charging procedure.
WARNING
b. The recommended method to evacuate and dehydrate the system is to connect three evacuation
hoses (see Figure 6-5) to the vacuum pump and
refrigeration unit. Be sure the service hoses are
suited for evacuation purposes.
NOTE
Only refrigerant 134a should be used to pressurize the system. Any other gas or vapor will
contaminate the system, which will require
additional purging and evacuation of the
system.
T--354
1
S D
a. Connect the gauge manifold to the compressor discharge and suction service valves. For units operating on a water cooled condenser, change over to aircooled operation.
b. Bring the container temperature to approximately
1.7 C (35_F) or -17.8_C (0_F). Set the controller set
point to -25_C (-13_F) to ensure that the suction modulation valve is at maximum allowed open position.
c. Partially block the condenser coil inlet air. Increase
the area blocked until the compressor discharge
pressure is raised to approximately 12kg/cm@
(175psig).
d. On units equipped with a receiver, the level should be
between the glasses. On units equipped with a watercooled condenser, the level should be at the center of
the glass. If the refrigerant level is not correct, continue with the following paragraphs to add or remove refrigerant as required.
6.7.2 Adding Refrigerant to System (Full Charge)
a. Evacuate unit and leave in deep vacuum (refer to
paragraph 6.6).
b. Place cylinder of R-134a on scale and connect charging line from cylinder to liquid line valve. Purge charging line at liquid line valve and then note weight of cylinder and refrigerant.
c. Open liquid valve on cylinder. Open liquid line valve
half-way and allow the liquid refrigerant to flow into
the unit until the correct weight of refrigerant (refer to
paragraph 2.2) has been added as indicated by
scales.
9
7
10
1. Reclaimer
6.
2. Discharge Service
7.
Valve
8.
3. Compressor
4. Suction Service Valve 9.
5. Receiver or Water
10.
Cooled Condenser
NOTE
It may be necessary to finish charging unit
through suction service valve in gas form, due
to pressure rise in high side of the system (refer
to section paragraph 6.7.3).
6--4
16
6.8 COMPRESSOR
15
WARNING
14
13
12
NOTES
11
10
6
9
1. Discharge Valve
Flange
2. High Side Pressure
Connection
3. Low Side Pressure
Connection
4. Suction Valve Flange
5. Motor End Cover
6. Serial/Model No. Plate
7. Crankcase Heater
8.
9.
10.
11.
12.
13.
14.
15.
16.
Bottom Plate
Sight Glass
Oil Drain Plug
Oil Charging Valve
Bearing Head
Oil Pump
Oil Fill Plug
Cylinder Head
Valve Plate
b. Pump down low side (refer to paragraph 6.4) or frontseat compressor service valves and remove refrigerant from compressor using a refrigerant recovery
system.
c. Locate the compressor junction box. Tag and disconnect wiring from compressor terminals and remove
compressor junction box.
g. Remove high pressure switch (HPS) from compressor and check operation of switch (refer to paragraph
6.9.2).
T--354
WARNING
5
4
CAUTION
Removing the compressor motor press-fit
stator in the field is not recommended. The
rotor and stator are a matched pair and
should not be separated.
d. Turn the compressor on its side and remove the bottom plate oil suction screen and screen hold down
plate. Inspect the screen for holes or an accumulation
of dirt. The screen can be cleaned with a suitable solvent.
e. Match mark each connecting rod cap (see Figure 6-8)
and connecting rod for correct reassembly. Remove
the bolts and connecting rod caps. Push the piston
rods up as far as they will go without having the piston
rings extend above the cylinders.
CAUTION
The copper tube, which connects to the oil
suction strainer extends out the bottom
with the bottom plate removed. Take precautions to avoid bending or breaking it
while changing crankcase positions.
JACK HERE
6
4.
5.
6.
7.
Discharge Valve
Valve Plate
Valve Plate Assembly
Valve Plate Gasket
6--6
6
5
2
3
2
1
7
11
1.
2.
3.
4.
5.
6.
Cap screws
Cover
Reversing Assembly
Pinion
Gear
Drive
12
4.
5.
6.
7.
10
9
7. O-Ring
8. Oil Pump & Bearing
9. Set Screw
10. Relief Valve
11. Pin
12. Gasket
6--7
T--354
1. Suction Valve
2. Suction Valve
Positioning Spring
8
4
3
2
10
1
1.
2.
3.
4.
5.
Cap screw
Cap
Crankshaft
Thrust Washer
Rotor Drive Key
6.
7.
8.
9.
10.
Connecting Rod
Compression Ring
Piston
Pin
Retainer
T--354
6--8
CAUTION
Ensure that thrust washer does not fall off
dowel pins while installing oil pump.
CAUTION
The set screw on the crankshaft must be
removed for this type of oil pump (see
Figure 6-9).
c. Install the bearing head assembly with a new gasket
on the compressor crankshaft. Carefully push oil
pump on by hand, ensuring that the thrust washer remains on the dowel pins. The tang on the end of the
drive engages the slot in the crankshaft, and the oil
inlet port on the pump is aligned with the oil pickup
tube in the crankcase. The pump should mounted
flush with the crankcase, and should be oriented with
the oil pick up tube and oil inlet port aligned as shown
in Figure 6-9.
d. Align the gasket and install the eight cap screws in the
mounting flange. Refer to Table 6-7 for applicable
torque values.
e. Install matching connecting rod caps Be sure rod is
not bound and crankshaft will turn correctly as each
set of rod bolts is torqued.
f. Be sure key fits properly when installng rotor on shaft.
Screw on equalizer tube and lock screw assembly
with lock washer and bend over tabs of lock washer.
Assemble suction strainer to motor and cover, and
bolt cover to crankcase. Assemble valve plates and
gaskets. Assemble cylinder heads and gaskets. Turn
the shaft by hand to see that it moves freely.
g. Install the oil suction screen, the oil suction screen
hold down plate, and the bottom plate.
6.8.6 Compressor Oil Level
CAUTION
Use only Carrier Transicold approved
Polyol Ester Oil (POE) -- Castrol-Icematic
SW20 compressor oil with R-134a. Buy in
quantities of one quart or smaller. When
using this hygroscopic oil, immediately
reseal. Do not leave container of oil open or
contamination will occur.
6--9
T--354
a. Turn unit start-stop switch OFF. Frontseat both suction and discharge service valves to isolate compressor. Remove the refrigerant from the compressor.
b. Disconnect wiring from defective switch. The high
pressure switch is located on the center head and is
removed by turning counterclockwise
(see Figure 2-3).
WARNING
Do not open the condenser fan grille before
turning power OFF and disconnecting
power plug.
WARNING
Do not use a nitrogen cylinder without a
pressure regulator. Do not use oxygen in or
near a refrigeration system as an explosion
may occur.
f. Leak-check the coil connections per paragraph paragraph 6.5. Evacuate the unit per paragraph 6.6 then
charge the unit with refrigerant per paragraph 6.7.
6.11 CONDENSER FAN AND MOTOR ASSEMBLY
NOTE
The high pressure switch is non-adjustable.
WARNING
CAUTION
Take necessary steps (place plywood over
coil or use sling on motor) to prevent motor
from falling into condenser coil.
g. Slowly open bleed-off valve to decrease the pressure. The switch should close at 18kg/cm@
(250psig).
1
4
5
1. Cylinder Valve
and Gauge
2. Pressure Regulator
3. Nitrogen Cylinder
4. Pressure Gauge
(0 to 36 kg/cm@ =
0 to 400 psig)
5. Bleed-Off Valve
6. 1/4 inch Connection
6--10
WARNING
Oakite No. 32 is an acid. Be sure that the
acid is slowly added to the water. DO NOT
PUT WATER INTO THE ACID -- This will
cause spattering and excessive heat.
WARNING
Wear rubber gloves and wash the solution
from the skin immediately if accidental contact occurs. Do not allow the solution to
splash onto concrete. PUT WATER INTO
THE ACID -- this will cause spattering and
excessive heat.
5. Fill the tubes with this solution by filling from the bottom. See Figure 6-17.
NOTE
It is important to provide a vent at the top for
escaping gas.
6. Allow the Oakite No. 32 solution to soak in the tube
coils for several hours, periodically pump-circulating
it with an acid-proof pump.
An alternate method may be used whereby a pail
(see Figure 6-18) filled with the solution and attached to the coils by a hose can serve the same purpose by filling and draining. The solution must contact the scale at every point for thorough de-scaling.
Air pockets in the solution should be avoided by regularly opening the vent to release gas. Keep flames
away from the vent gases.
7. The time required for de-scaling will vary, depending
upon the extent of the deposits. One way to determine when de-scaling has been completed is to
titrate the solution periodically, using titrating equipment provided free by the Oakite Technical Service
representative. As scale is being dissolved, titrate
readings will indicate that the Oakite No. 32 solution
is losing strength. When the reading remains
constant for a reasonable time, this is an indication
that scale has been dissolved.
Summary of Procedure:
1 Drain water from condenser tubing circuit.
2. Clean water tubes with Aluminum Cleaner 164 to
remove mud and slime. Clean water tubes with
Oakite No. 22 to remove mud and slime.
3 Flush.
4 De-scale water tubes with Oakite No. 32 to remove
scale.
5 Flush.
6 Neutralize.
7 Flush.
6--11
T--354
7
6
4
3
9
11. Put the unit back in service and operate under normal load. Check the head pressure. If normal, a thorough de-scaling has been achieved.
10
1
11
12
1. Pump support
2. Tank
3. Suction
4. Pump
5. Priming Connection
(Centrifugal pump
50 gpm at 35 head)
6. Globe valves
7. Vent
8. Close vent pipe valve
when pump is running
9. Condenser
10. Remove water
regulating valve
11. Return
12. Fine mesh screen
b. To Replace Filter-Drier:
3 to 4
2.
3.
4.
5.
Approximately 5
Condenser
Vent pipe
1 pipe
6.13 FILTER-DRIER
a. To Check Filter-Drier:
NOTE
TXV Bulb Clamp is soldered to the suction line.
6--12
Suction Line
Thumbscrew
TXV Bulb Clamp
TXV Bulb
Foam Insulation
6
1
2
5
3
4
1.
2.
3.
4.
5.
6.
6--13
T--354
g. Unsolder the two coil connections, one at the distributor and the other at the coil header.
3
2
5
T--354
6--14
5
1
WARNING
Always turn OFF the unit circuit breakers
(CB-1 & CB-2) and disconnect main power
supply before working on moving parts.
8
a. Remove upper access panel (See Figure 2-1) by removing mounting bolts and T.I.R. locking device.
Reach inside of unit and remove Ty-Rap securing
wire harness loop.
4
(STS / SRS)
1--- probe; 3--- wire
6--15
T--354
WARNING
Make sure power to the unit is OFF and
power plug disconnected before servicing
capacitor(s).
WARNING
With power OFF discharge the capacitor
before disconnecting the circuit wiring.
Capacitors must be discharged properly before testing.
To discharge the capacitor, first turn the unit power OFF
and disconnect the unit power plug. Then place a
20,000 ohm, 2 watt resistor across the terminals of the
capacitor for approximately 30 seconds.
The capacitors are located on the motor and may be
removed by two methods:
1. If container is empty, open upper rear panel of the
unit.
2. If container is full, turn the unit power OFF and disconnect power plug. Remove the evaporator fan
motor access panel (see Figure 2-1). For removal of
the evaporator fan assembly, refer to section 6.16.
6.17.3 Checking the Capacitor
If the capacitor is suspected of malfunction, you may
choose to simply replace it. Direct replacement requires
a capacitor of the same value. Two methods for
checking capacitor function are:
1. Volt-ohmmeter set on RX 10,000 ohms.
Connect ohmmeter leads across the capacitor
terminals and observe the meter needle. If the capacitor
T--354
www.nucalgon.com/products/coil_cleaners_tripower.htm
6--16
Prior to Cleaning:
-- Always wear goggles, gloves and work boots.
-- Avoid contact with skin and clothing, and avoid
breathing mists.
NOTE
Carefully listen to the valve. During reset, the
valve will make a ratcheting noise that may be
heard or felt as it is attempting to close. If this
can be heard or felt, it indicates that the controller and drive module are attempting to close the
valve, and may serve as a quick indication that
the drive module is in working order.
e. During the first few minutes of unit operation, compressor reliability enhancement logic (CREL) may be
in effect. This places the valve at a 21% staging position and is sufficient to drive the temperature of the
supply probe down several degrees during this interval.
Cleaning Procedure:
a. Remove the upper evaporator access panel inside of
the unit.
b. Spray the surface with water before applying the
cleaning solution. This helps the cleaner work better.
f. After the CREL time-out has been met, the valve will
start responding to the control logic and open or close
relative to the demand. Scrutinize the unit operation
for a few minutes. While in pulldown, the unit will open
the SMV to a maximum discharge pressure of 325
psig in high ambient conditions, or as much as the
current setting and control logic will allow. The current
level should be high. A lower discharge pressure will
be seen in lower ambient temperatures. Once the unit
has reached set point, the SMV will go into control
mode. Both the discharge/suction pressures, and
current draw will go significantly lower. Once below
set point, the suction pressure should go into a vacuum within several minutes. Should the operation differ as mentioned, the SMV, controller, or wiring, may
be faulty.
NOTE
The unit may shut off for a short time. Wait until
the unit self starts and sufficient time has
elapsed to cause the valve to fully modulate.
T--354
5. If the valve is determined to be faulty after completing the above steps, perform a low side pump down.
Remove valve powerhead assembly, and replace
with a NEW valve powerhead assembly, torque nut
to 35 ft-lb, evacuate low side, and open all service
valves.
k. If the unit still does not operate properly, stop unit and
proceed to the following step to check out the SMV
system.
DO NOT disassemble piston from NEW suction modulating valve powerhead assembly. Doing so may result in damage to piston.
CAUTION
To check operation:
T--354
6--18
6.21 AUTOTRANSFORMER
If the unit does not start, check the following:
a. Make sure the 460VAC (yellow) power cable is
plugged into the receptacle (item 3, Figure 4-1) and
locked in place.
b. Make sure that circuit breakers CB-1 and CB-2 are in
the ON position. If the circuit breakers do not hold in,
check voltage supply.
c. There is no internal protector for this transformer design; therefore, no checking of the internal protector is
required.
d. Using a voltmeter and with the primary supply circuit
ON, check the primary (input) voltage (460VAC).
Next, check the secondary (output) voltage
(230VAC). The transformer is defective if output voltage is not available.
6.22 CONTROLLER
6.22.1 Handling Controller
Replacement Differential
Pressure (psi)
CAUTION
Do not remove wire harnesses from controller unless you are grounded to the unit
frame with a static safe wrist strap.
70
60
CAUTION
REPLACE DPRV
50
40
30
20
10
0
30
40
50
60
70
80
90
100
110
120
6--19
T--354
TP 8
This test point is not applicable to the units covered
herein.
TP 9
This test point is the chassis (unit frame) ground
connection.
TP 10
This test point enables the user to check if the heat
termination thermostat (HTT) contact is open or closed.
6.22.3 Controller Programming Procedure
To load new software into the module, the programming
card (PCMIA) is inserted into the programming/
software port.
CAUTION
The unit must be OFF whenever a programming card is inserted or removed from the
controller programming port.
1.
Controller Software
Programming Port
Mounting Screw
2.
3.
Controller
4.
Test Points
NOTE
Use a digital voltmeter to measure AC voltage
between TPs and ground (TP9), except for
TP8.
TP2
This test point enables the user to check if the internal
protector for the compressor motor (IP-CP) or high
pressure switch is open.
TP3
This test point enables the user to check if the water
pressure switch (WP) contact is open or closed.
TP 4
This test point enables the user to check if the internal
protector for the condenser fan motor (IP-CM) is open or
closed.
TP 5
This test point enables the user to check if the internal
protectors for the evaporator fan motors (IP-EM1 or
IP-EM2) are open or closed.
TP 6
This test point enables the user to check if the controller
water tank heater relay (TQ) is open or closed.
TP 7
This test point is not used in this application.
T--354
6--20
14 Wait for default display -- setpoint on the left and control temperature on the right.
15.Confirm software is correct using keypad code select 18 to view Cd18 XXXX.
b.Installation:
9. When the software loading has successfully completed, the display will show the message EEPrM
donE. (If a problem occurs while loading the software, the display will blink the message Pro FAIL or
bad 12V. Turn start-stop switch OFF and remove
the card.)
e. Using the plug connector marked EC, that is connected to the back of the controller, locate the sensor
wires (RRS, RTS, SRS, STS, AMBS, DTS, CPDS
OR CPSS as required). Follow those wires to the connector and using the pins of the plug, measure the
resistance. Values are provided in Table 6-1.
12.Confirm correct model configuration using the keypad to choose code select 20 (CD20). The model
displayed should match the unit serial number plate.
0
25
Temperature
Fahrenheit
Resistance
(Ohms)
32
32,650 + 1720
- 1620
25
77
10,000 + 450
- 430
T--354
c. If required, prepare the replacement sensor by cutting sensor wire(s) back 40mm (1-1/2 inch). For
3-wire sensors, the black wire should be cut at the
middle length and the red/white wire cut to the shorter
length (See Figure 6-28).
When replacing two single sensors with a combination (3-wire) sensor, the black wires of the cables
should be cut to the same length and the red wire of
one cable cut to the shorter length.
CAUTION
6.3mm (1/4--inch)
40 mm (1-1/2 inches)
6.3--mm (1/4--inch)
NOTE
The P5 Pre-Trip test must be run to inactivate
probe alarms (refer to paragraph 4.8).
Bulb Type
Figure 6-28 Sensor Types
Cable
Sensor
REPLACEMENT FOR DUAL, SINGLE SENSOR CONFIGURATION
Sensor
6--22
Cables
RED
BLACK
RED/WHITE
a. Sensors RTS/RRS
Probe
Holder
Return
Air
Stream
Return Sensor
6mm
(1/4--inch)
Seal
Mounting
Clamp
T--354
NOTE
CAUTION
Do not allow the recorder stylus to snap
back down. The stylus arm base is spring
loaded, and damage may occur to the chart,
or the stylus force may be altered.
DO NOT move the stylus arm up and down
on the chart face. This will result in damage
to the stylus motor gear.
T--354
c.
6--24
3
2
4
5
10
9
8
7
6
1.
2.
3.
4.
5.
Recorder Door
Change Chart Button
Recorder Box
Pen Tip
Stylus Arm
6. Connector
7. Calibration Button (Located underneath)
8. Mounting Screws, #10-24 x 7/16 inches long
9. Hold Down Tab
10. Chart Retaining Nut
Figure 6-32 Electronic Partlow Temperature Recorder
6--25
T--354
NOTE
An epoxy application gun is also needed,
Carrier Transicold part number 07-00391-00.
a. The surface must be clean and dry. Roughen the surface with sandpaper to ensure a good bond.
b. Cut the fiberglass cloth to allow a 25mm (1 inch) overlap around the area to be repaired.
c. Stretch and position the cloth over the area to be repaired and secure it with masking tape.
d. Make up sufficient epoxy glue to cover the cloth by
mixing equal parts of resin and hardener. Saturate the
cloth with the epoxy glue, spreading evenly.
e. Remove the tape and overlap the edge of the cloth
approximately 6 to 12mm (1/4 to 1/2) with glue.
f. Epoxy will dry in 45-60 minutes. When completely
cured (12 hours), use sandpaper to smooth edges of
the patch.
T--354
6--26
1
2
3
4
DESCRIPTION
PART NUMBER
76-00724-00SV
76-00724-00Z
02-00067-02Z
98-02339-00
Qty
1
10
10
10
1
2
3
4
5
6
7
8
9
10
DESCRIPTION
PART NUMBER
76-50084-00
34-06231-01
34-06231-03
34-06231-04
34-06231-05
34-06231-06
34-06231-07
02-00082-00
07-00390-00
98-02338-00
Qty
1
10
10
10
10
10
10
1
1
1
Note: Insert repair procedures require use of an Application Gun, Carrier part number 07-00391-00 (Loctite 983435).
Table 6-4 Drill Information
ITEM
1
2
3
4
5
6
34- 06231- 01
34- 06231- 03
34- 06231- 04
34- 06231- 05
34- 06231- 06
34- 06231- 07
6--27
T--354
T--354
6--28
07
03
03
04
05
06
05
07
01
03
03
03
04
03
CB1
WARNING
Communications
interface Module
WARNING
Before removing the capacitors the
terminals must be checked for voltage with
a multimeter. The discharge resistors
installed on the unit (capacitors) should
bring the voltage to a safe level in a minute.
However, there may be a broken resistor
that retains voltage for a longer period, it is
highly recommended to wait 15 minutes
and to check for voltage.
WARNING
The unit power plug must be disconnected
to remove power from circuit breaker CB1
a. CB1 is connected to the power system, see wiring
schematic. Ensure that the unit power is off AND that
the unit power plug is disconnected.
b. Open control box, see Figure 6-35 and remove low
voltage shield. Open high voltage shield.
c. Remove the circuit breaker panel, with circuit breaker, from the control box.
d. Locate wires CB21 / CIA3, CB22 / CIA5 and CB23 /
CIA7 that have been tied back in the wire harness.
Remove the protective heat shrink from the ends of
the wires.
e. Attach the three wires as addressed to the LOAD side
of the circuit breaker.
f. Refit the circuit breaker panel.
g. Fit the new RMU into the unit.
h. Remove plugs CIA, CIB and CID from the wiring harness and attach to the module.
i. Replace the low voltage shield.
6--29
T--354
TORQUE
BOLT DIA. THREADS
FREE SPINNING
#4
40
5.2in-lbs
#6
32
9.6in-lbs
#8
32
20in-lbs
#10
24
23in-lbs
1/4
20
75in-lbs
5/16
18
11ft-lbs
3/8
16
20ft-lbs
7/16
14
31ft-lbs
1/2
13
43ft-lbs
9/16
12
57ft-lbs
5/8
11
92ft-lbs
3/4
10
124ft-lbs
2. Capacitor analyzer:
The function of the analyzer is to read the microfarad
value of a capacitor and to detect insulation breakdown
under load conditions. The important advantages of an
analyzer are its ability to locate capacitors that have
failed to hold their microfarad ratings, or those that are
breaking down internally during operation. It is also
useful in identifying capacitors when their microfarad
rating marks have become unreadable.
N.m
.6
1.0
2.25
2.6
8.4
1.52
2.76
4.28
5.94
7.88
12.72
17.14
PART NAME
MAIN BEARING
Main Bearing Diameter
Main Bearing Journal Diameter
PUMP END
Main Bearing Diameter
Main Bearing Journal Diameter
CONNECTING ROD
Piston Pin Bearing
CRANKPIN DIAMETER
Throw
THRUST WASHER (Thickness)
CYLINDERS
Bore
Piston (Diameter)
Piston Pin (Diameter)
Piston Ring Gap
Piston Ring Side Clearance
T--354
FACTORY MAXIMUM
inches
mm
1.6268
41.3207
FACTORY MINIMUM
inches
1.6233
1.3760
1.3768
41.2318
34.9504
1.3735
34.8869
0.6878
1.3735
1.070
0.1520
17.4701
34.8869
27.1780
03.8608
34.9707
1.072
0.154
27.2288
3.9116
2.0010
50.8254
0.013
0.002
mm
00.3302
00.0508
6--30
1.9860
0.6873
0.0050
0.0010
50.4444
17.4574
00.1270
00.0254
MAXIMUM WEAR
BEFORE REPAIR
inches
mm
.0020
.0020
0.0508
0.0508
.0020
.0020
.0020
.0010
.0025
0.0508
0.0508
0.0508
0.0254
0.0635
.0250
0.6350
.0020
.0020
.0010
.0250
.0020
0.0508
0.0508
0.0254
0.6350
0.0508
SIZE
DIAMETER
(inches)
1/16
1/8
1/4
1/4
THREADS
PER INCH
27 (pipe)
20 (pipe)
20 (pipe)
20
1/4
28
5/16
18
3/8
16
7/16
5/8
5/8
#10
1-1/2
14
11
18
32
18 NEF
USAGE
ft-lb
N.m
8 - 12
6 -- 10
20 -- 25
10 -- 12
12 -- 15
12 -- 16
6 -- 10
12 -- 16
11 -- 16
8 -- 13
27 -- 34
13 -- 16
16 -- 20
16 -- 22
8 -- 13
16 -- 22
16 -- 20
2 -- 27
20 -- 30
27 -- 41
40 -- 50
55 -- 70
55
25
60
4
35
76 -- 83
34 -- 41
83 -- 103
5 -- 8
48 -- 62
------
60
30
75
6
45
6--31
T--354
Vacuum
/hg
-40
-40
14.6
49.4
-35
-37
12.3
-30
-34
-25
Pressure
bar
psig
kPa
kg/cm@
bar
37.08
0.49
28
-2
24.5
168.9
1.72
1.69
41.6
31.25
0.42
30
-1
26.1
180.0
1.84
1.80
9.7
32.8
24.64
0.33
32
27.8
191.7
1.95
1.92
-32
6.7
22.7
17.00
0.23
34
29.6
204.1
2.08
2.04
-20
-29
3.5
11.9
8.89
0.12
36
31.3
215.8
2.20
2.16
-18
-28
2.1
7.1
5.33
0.07
38
33.2
228.9
2.33
2.29
-16
-27
0.6
2.0
1.52
0.02
40
35.1
242.0
2.47
2.42
45
40.1
276.5
2.82
2.76
50
10
45.5
313.7
3.20
3.14
55
13
51.2
353.0
3.60
3.53
60
16
57.4
395.8
4.04
3.96
65
18
64.1
441.0
4.51
4.42
70
21
71.1
490.2
5.00
4.90
75
24
78.7
542.6
5.53
5.43
80
27
86.7
597.8
6.10
5.98
85
29
95.3
657.1
6.70
6.57
90
32
104.3
719.1
7.33
7.19
95
35
114.0
786.0
8.01
7.86
100
38
124.2
856.4
8.73
8.56
105
41
135.0
930.8
9.49
9.31
110
43
146.4
1009
10.29
10.09
115
46
158.4
1092
11.14
10.92
120
49
171.2
1180
12.04
11.80
125
52
184.6
1273
12.98
12.73
130
54
198.7
1370
13.97
13.70
135
57
213.6
1473
15.02
14.73
140
60
229.2
1580
16.11
15.80
145
63
245.6
1693
17.27
16.93
150
66
262.9
1813
18.48
18.13
155
68
281.1
1938
19.76
19.37
Temperature
cm/hg kg/cm@
Temperature
Pressure
psig
kPa
kg/cm@
bar
-14
-26
0.4
1.1
0.03
0.03
-12
-24
1.2
8.3
0.08
0.08
-10
-23
2.0
13.8
0.14
0.14
-8
-22
2.9
20.0
0.20
0.20
-6
-21
3.7
25.5
0.26
0.26
-4
-20
4.6
31.7
0.32
0.32
-2
-19
5.6
36.6
0.39
0.39
-18
6.5
44.8
0.46
0.45
-17
7.6
52.4
0.53
0.52
-16
8.6
59.3
0.60
0.59
-14
9.7
66.9
0.68
0.67
-13
10.8
74.5
0.76
0.74
10
-12
12.0
82.7
0.84
0.83
12
-11
13.2
91.0
0.93
0.91
14
-10
14.5
100.0
1.02
1.00
16
-9
15.8
108.9
1.11
1.09
18
-8
17.1
117.9
1.20
1.18
20
-7
18.5
127.6
1.30
1.28
22
-6
19.9
137.2
1.40
1.37
24
-4
21.4
147.6
1.50
1.48
26
-3
22.9
157.9
1.61
1.58
T--354
6--32
Note: Curves to be used as troubleshooting guide only for model series 69NT40 with
fresh air makeup vent closed, unit powered on 460VAC/60Hz and SMV 100% open.
(Bar) psig
(22.0) 320
(20.7) 300
(19.3) 280
(17.9) 260
35_F (1.7_C)
Box
(16.6) 240
(15.2) 220
(13.8) 200
(12.4) 180
(11.0) 160
(9.7) 140
(8.3) 120
(6.9) 100
(5.5)
80
60
(15.6)
70
(21.1)
80
(26.7)
90
(32.2)
100
(37.8)
110
(43.3)
120 (_F)
(48.9) (_C)
(Bar) psig
(22.0) 320
(20.7) 300
(19.3) 280
(17.9) 260
(16.6) 240
(15.2) 220
(13.8) 200
(12.4) 180
(11.0) 160
(9.7) 140
0_F (-17.8_C)
Box
(8.3) 120
(6.9) 100
(5.5)
80
60
(15.6)
70
(21.1)
80
(26.7)
90
(32.2)
100
(37.8)
110
(43.3)
120
(48.9)
(_F)
(_C)
Compressor Discharge Pressure Versus Ambient Air Temperature at Stable Box Temperature
Figure 6-36 R-134a Compressor Pressure and Motor Current Curves Versus Ambient Temperature
(Sheet 1 of 2)
6--33
T--354
(Bar)
(.97)
psig
14
(.83)
12
(.69)
10
(.55)
(.41)
(.28)
(.14)
(0)
(-.14)
--2
(-.28)
--4
(-.41)
--6
60
(15.6)
70
(21.1)
80
(26.7)
90
(32.2)
100
(37.8)
110
(43.3)
120 (_F)
(48.9) (_C)
17
16
15
14
13
12
11
10
9
8
60
(15.6)
70
80
90
100
(21.1)
(26.7)
(32.2)
(37.8)
110
(43.3)
120
(48.9)
(_F)
(_C)
Figure 6-36 R-134a Compressor Pressure and Motor Current Curves Versus Ambient Temperature
(Sheet 2 of 2)
T--354
6--34
SECTION 7
ELECTRICAL WIRING SCHEMATICS
7.1 INTRODUCTION
This section contains Electrical Schematic and Wiring Diagrams, the diagrams are presented as follows:
Figure 7-1 provides the legend for use with all figures.
Figure 7-2 provides the basic schematic diagram for units with single evaporator fan capability and VPS.
Figure 7-3 & Figure 7-4 provide wiring diagrams for units with single evaporator fan capability and VPS.
Figure 7-5 provides the basic schematic diagram for units with normal evaporator fan capability, TransFresh and
Crankcase Heater.
Figure 7-6 & Figure 7-7 provide wiring diagrams for units with normal evaporator fan capability, TransFresh and
Crankcase Heater.
LEGEND
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
AMBS
C
CB1
CB2
CCH
CF
CI
F
HPS
HR
HS
HTT
IC
IP
CH
IRL
PR
C -- L
CM
CP
CPDS
CPSS
CPT
CR
CS
DHBL
DHBR
DHML
DHMR
DHTL
DHTR
DL
DPT
DTS
DVM
DVR
E
TH
TI
TL
TN
TP
EM
S
TR
TRANS
TRC
TV
EF
EM
ES
RM
RRS
RTS
SMV
SPT
SRS
ST
STS
TC
TCC
TE
TF
TFC
VPS
WCR
WP
T-354
BASED ON 62--66686--00
Figure 7-2 SCHEMATIC DIAGRAM -- Units with Single Evaporator Fan Capability & VPS
T--354
7--2
BASED ON 62--66686--00
Figure 7-3 UNIT WIRING DIAGRAM -- Units with Single Evaporator Fan Capability & VPS
(Sheet 1 of 2)
7--3
T-354
BASED ON 62--66686--00
Figure 7-4 UNIT WIRING DIAGRAM -- Units with Single Evaporator Fan Capability & VPS.
(Sheet 2 of 2)
T--354
7--4
BASED ON 62--66680--00
Figure 7-5 SCHEMATIC DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater
7--5
T-354
BASED ON 62--66680--00
Figure 7-6 UNIT WIRING DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater (Sheet 1 of 2)
T--354
7--6
BASED ON 62--66680--00
Figure 7-7 UNIT WIRING DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater (Sheet 2 of 2)
7--7
T-354
INDEX
A
Air Cooled Condenser Section, 2--4
Alarm, 3--6, 3--9, 3--12, 3--18, 3--19, 3--20, 3--21,
3--28
B
Battery Replacement, 6--21
Bulb Mode, 3--5
C
Capacitors, 6--16
Checking Superheat, 6--13
Checking the Capacitor, 6--16
Checking the Controller, 6--18
Compressor, 6--5
Compressor Crankcase Heater, 2--12
Compressor discharge sensor (CPDS), 3--24
Evaporator, 6--14
Index--1
T-354
INDEX -- Continued
Filter--Drier, 6--12
Fumigation, 6--16
Heater, 6--14
Heating Mode, 4--7
Introduction, 1--1
Index--2
T-354
INDEX -- Continued
S
Safety and Protective Devices, 2--9
USDA, 3--11
USDA Cold Treatment Procedure, 3--12
Starting, 4--3
Stopping, 4--3
Suction Modulating Valve, 6--17
Suction Modulation Valve, 3--14
Supply Recorder Sensor (SRS), 3--17
Index--3
T-354