Reefer

Download as pdf or txt
Download as pdf or txt
You are on page 1of 114

r

Container Refrigeration

OPERATION AND SERVICE


for
69NT40--541--306, 314 & 328
Upflow Container Refrigeration Units

T-354

OPERATION AND SERVICE MANUAL


UPFLOW CONTAINER
REFRIGERATION UNITS

Models
69NT--40--541--306, 314 & 328

TABLE OF CONTENTS
PARAGRAPH NUMBER

Page

GENERAL SAFETY NOTICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety--1


FIRST AID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Safety--1

OPERATING PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety--1


MAINTENANCE PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety--1
UNIT LABEL IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety--1
SPECIFIC WARNING AND CAUTION STATEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety--2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.1

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2

CONFIGURATION IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3

OPTION DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.1 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.2 Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.3 Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.5 Temperature Readout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.6 Pressure Readout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.7 USDA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.8 Interrogator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.9 Remote Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.10 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.11 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.12 Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.13 Autotransformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.14 Temperature Recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--1

1.3.15 Gutters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.16 Handles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.17 Thermometer Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.18 Water Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.19 Back Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.20 460 Volt Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.21 230 Volt Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.22 Cable Restraint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.23 Upper Air (Fresh Air Make Up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.24 Lower Air (Fresh Air Make Up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.25 Arctic Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.26 Power Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.27 Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.28 Evaporator Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.29 Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.30 Plate Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.31 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.32 Condenser Grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1.3.33 Emergency Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1--2

1--1

T-354

TABLE OF CONTENTS - Continued


PARAGRAPH NUMBER
Page
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--1
2.1 GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--1
2.1.1 Refrigeration Unit -- Front Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--1
2.1.2 Fresh Air Makeup Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--1
2.1.3 Evaporator Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--2
2.1.4 Compressor Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--3
2.1.5 Air-cooled Condenser Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--4
2.1.6 Water-cooled Condenser Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--5
2.1.7 Control Box Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--6
2.1.8 Communications Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--6
2.2 REFRIGERATION SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--7
2.3 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--8
2.4 SAFETY AND PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--9
2.5 REFRIGERATION CIRCUIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--10
2.6 ARCTIC OPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--12
MICROPROCESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--1
3.1 TEMPERATURE CONTROL MICROPROCESSOR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--1
3.1.1 Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--2
3.1.2 Display Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--2
3.1.3 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--3
3.2 CONTROLLER SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--3
3.2.1 Configuration Software (Configuration Variables) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--3
3.2.2 Operational Software (Function Codes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--3
3.3 MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--4
3.3.1 Temperature Control -- Perishable Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--4
3.3.2 Evaporator Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--4
3.3.3 Defrost Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--4
3.3.4 Failure Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--4
3.3.5 Generator Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--4
3.3.6 Condenser Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--4
3.3.7 Arctic Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--4
3.3.8 Perishable Mode -- Conventional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--5
3.3.9 Perishable Mode -- Economy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--5
3.3.10 Perishable Mode -- Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--5
3.3.11 Perishable, Dehumidification -- Bulb Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--5
3.3.12 Temperature Control -- Frozen Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--6
3.3.13 Frozen Mode -- Conventional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--6
3.3.14 Frozen Mode -- Economy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--6
3.4 CONTROLLER ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--6
3.5 UNIT PRE-TRIP DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--7

T-354

ii

TABLE OF CONTENTS - Continued


PARAGRAPH NUMBER
Page
3.6 DataCORDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--7
3.6.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--7
3.6.2 DataCORDER Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--8
3.6.3 Sensor Configuration (dCF02) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--8
3.6.4 Logging Interval (dCF03) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--9
3.6.5 Thermistor Format (dCF04) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--9
3.6.6 Sampling Type (dCF05 & dCF06) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--9
3.6.7 Alarm Configuration (dCF07 -- dCF10) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--9
3.6.8 DataCORDER Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--9
3.6.9 Pre-Trip Data Recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--11
3.6.10 DataCORDER Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--11
3.6.11 USDA Cold Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--11
3.6.12 USDA Cold Treatment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--12
3.6.13 DataCORDER Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--12
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--1
4.1 INSPECTION (Before Starting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--1
4.2 CONNECT POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--1
4.2.1 Connection To 380/460 VAC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--1
4.2.2 Connection to190/230 VAC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--1
4.3 ADJUST FRESH AIR MAKEUP VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--2
4.3.1 Upper Fresh Air Makeup Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--2
4.3.2 Fresh Air Position Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--2
4.4 CONNECT WATER-COOLED CONDENSER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--2
4.5 CONNECT REMOTE MONITORING RECEPTACLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.6 STARTING AND STOPPING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.6.1 Starting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.6.2 Stopping the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.7 START-UP INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.7.1 Physical Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.7.2 Check Controller Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.7.3 Start Temperature Recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.7.4 Complete Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.8 PRE-TRIP DIAGNOSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--3
4.9 OBSERVE UNIT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--5
4.9.1 Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--5
4.9.2 Probe Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--5
4.10 SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--7
4.10.1 Sequence of Operation -- Perishable Mode Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--7
4.10.2 Sequence of Operation -- Perishable Mode Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--7
4.10.3 Sequence of Operation -- Frozen Mode Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--8
4.10.4 Sequence of Operation -- Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4--8

iii

T-354

TABLE OF CONTENTS - Continued


PARAGRAPH NUMBER

Page

4.11 EMERGENCY OPERATION (OPTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.11.1 Emergency Bypass Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--9
4--9

4.11.2 Emergency Defrost Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--10

4.12 ARCTIC MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--10
5--1

5.1
5.2

UNIT WILL NOT START OR STARTS THEN STOPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--1
5--1

5.3

UNIT RUNS BUT HAS INSUFFICIENT COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--2

5.4
5.5

UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


UNIT WILL NOT TERMINATE HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--2
5--2

5.6

UNIT WILL NOT DEFROST PROPERLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--2

5.7
5.8

ABNORMAL PRESSURES (COOLING) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


ABNORMAL NOISE OR VIBRATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--3
5--3

5.9

CONTROLLER MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--3

5.10 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


5.11 THERMOSTATIC EXPANSION VALVE MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--4
5--4

5.12 AUTOTRANSFORMER MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--4

5.13 WATER-COOLED CONDENSER OR WATER PRESSURE SWITCH . . . . . . . . . . . . . . . . . . . . . . . .


SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5--4
6--1

6.1

SECTION LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--1

6.2
6.3

SERVICE VALVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MANIFOLD GAUGE SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--1
6--1

6.4

PUMPING THE UNIT DOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--3

6.5
6.6

REFRIGERANT LEAK CHECKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


EVACUATION AND DEHYDRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--3
6--3

6.6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--3

6.6.2 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6.3 Procedure - Complete System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--3
6--3

6.6.4 Procedure - Partial System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--4

REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.1 Checking the Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--4
6--4

6.7.2 Adding Refrigerant to System (Full Charge) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--4

6.7.3 Adding Refrigerant to System (Partial Charge) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


6.8 COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--4
6--5

6.8.1 Removal and Replacement of Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--5

6.8.2 Compressor Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


6.8.3 Compressor Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--6
6--8

6.8.4 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.8.5 Installing the Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--8
6--9

6.8.6 Compressor Oil Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--9

HIGH PRESSURE SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


6.9.1 Replacing High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--10
6--10

6.9.2 Checking High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--10

6.7

6.9

T-354

iv

TABLE OF CONTENTS - Continued


PARAGRAPH NUMBER
Page
6.10 CONDENSER COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--10
6.11 CONDENSER FAN AND MOTOR ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--10
6.12 WATER-COOLED CONDENSER CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--11
6.13 FILTER-DRIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--12
6.14 THERMOSTATIC EXPANSION VALVE (TXV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--12
6.14.1 Checking Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--13
6.14.2 Expansion Valve Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--13
6.15 EVAPORATOR COIL AND HEATER ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--14
6.15.1 Evaporator Coil Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--14
6.15.2 Evaporator Heater Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--14
6.16 EVAPORATOR FAN AND MOTOR ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--15
6.17 EVAPORATOR FAN MOTOR CAPACITORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--16
6.17.1 When To Check For a Defective Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--16
6.17.2 Removing the Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--16
6.17.3 Checking the Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--16
6.18 EVAPORATOR SECTION CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--16
6.19 SUCTION MODULATION VALVE (SMV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--17
6.19.1 Pre-check Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--17
6.19.2 Checking the Stepper Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--18
6.19.3 Checking the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--18
6.19.4 Emergency Repair Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--18
6.20 DPRV Check Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--19
6.21 AUTOTRANSFORMER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--19
6.22 CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--19
6.22.1 Handling Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--19
6.22.2 Controller Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--20
6.22.3 Controller Programming Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--20
6.22.4 Removing and Installing the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--21
6.22.5 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--21
6.23 TEMPERATURE SENSOR SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--21
6.23.1 Sensor Checkout Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--21
6.23.2 Sensor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--22
6.23.3 Sensor Re-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--23
6.24 VENT POSITION SENSOR (VPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--23
6.25 ELECTRONIC TEMPERATURE RECORDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--24
6.25.1 Replacing the Recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--24
6.25.2 Changing the Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--24
6.25.3 Rezeroing the Recording Thermometer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--24
6.26 MAINTENANCE OF PAINTED SURFACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--26
6.27 COMPOSITE CONTROL BOX REPAIRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--26
6.28 COMMUNICATIONS INTERFACE MODULE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--29
6.29 POWER FACTOR CORRECTOR CAPACITORS (PFC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--29
ELECTRICAL WIRING SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7--1
7.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7--1
v

T-354

LIST OF ILLUSTRATIONS
FIGURE NUMBER

Page

Figure 2-1 Refrigeration Unit -- Front Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2--1

Figure 2-2 Evaporator Section -- UPFLOW Units With Center Access Panel . . . . . . . . . . . . . . . . . . . . . . . . . .

2--2

Figure 2-3 Compressor Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2--3

Figure 2-4 Condenser Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2--4

Figure 2-5 Water-cooled Condenser Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2--5

Figure 2-6 Control Box Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2--6

Figure 2-7 Refrigeration Circuit Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2--11

Figure 2-8 Arctic Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2--12

Figure 3-6 Temperature Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3--1

Figure 3-7 Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3--2

Figure 3-8 Display Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3--2

Figure 3-9 Micro-Link 3 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3--3

Figure 3-10 Standard Configuration Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3--10

Figure 3-11 Data Reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3--11

Figure 4-1 Autotransformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--1

Figure 4-2 Make Up Air Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--2

Figure 4-3 Controller Operation -- Perishable Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--6

Figure 4-4 Controller Operation -- Frozen Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--6

Figure 4-5 Perishable Mode Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--7

Figure 4-6 Perishable Mode Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--7

Figure 4-7 Frozen Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--8

Figure 4-8 Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4--8

Figure 6-1 Service Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--1

Figure 6-2 Manifold Gauge Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--1

Figure 6-3 R-134a Manifold Gauge/Hose Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--2

Figure 6-4 Refrigeration System Service Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--2

Figure 6-5 Compressor Service Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--4

Figure 6-6 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--5

Figure 6-7 Exploded View of Valve Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--6

Figure 6-8 Bottom Plate Removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--6

Figure 6-9 Oil Pump and Bearing Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--7

Figure 6-10 Low Profile Oil Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--7

Figure 6-11 Motor End Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--7

Figure 6-12 Equalizing Tube and Lock Screw Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--8

Figure 6-13 Crankshaft Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--8

Figure 6-14 Suction Valve & Positioning Springs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--8

Figure 6-15 Piston Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--8

Figure 6-16 High Pressure Switch Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--10

Figure 6-17 Water-Cooled Condenser Cleaning -- Forced Circulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--12

Figure 6-18 Water-Cooled Condenser Cleaning -- Gravity Circulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--12

Figure 6-19 Thermostatic Expansion Valve Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--13

Figure 6-20 Thermostatic Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--13

Figure 6-21 Hermetic Thermostatic Expansion Valve Brazing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--13

T-354

vi

LIST OF ILLUSTRATIONS - Continued


FIGURE NUMBER
Figure 6-22 Hermetic Thermostatic Expansion Valve Bulb Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-23 Evaporator Fan Locating Dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-24 Evaporator Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-25 Suction Modulation Valve (SMV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-26 DPRV Replacement Value Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-27 Controller Section of the Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-28 Sensor Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-29 Sensor and Cable Splice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-30 Return Sensor Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-31 Supply Sensor Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page
6--14
6--15
6--15
6--17
6--19
6--19
6--22
6--22
6--23
6--23

Figure 6-32 Electronic Partlow Temperature Recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Figure 6-33 Door Hinge Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--25
6--27

Figure 6-34 Insert Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Figure 6-35 Communications Interface Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--28
6--29

Figure 6-36 R-134a Compressor Pressure and Motor Current Curves Versus Ambient Temperature . . . . .
Figure 7-1 LEGEND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-2 SCHEMATIC DIAGRAM -- Units with Single Evaporator Fan Capability & VPS . . . . . . . . . . . . . .
Figure 7-3 UNIT WIRING DIAGRAM -- Units with Single Evaporator Fan Capability & VPS . . . . . . . . . . . . .
Figure 7-5 SCHEMATIC DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-6 UNIT WIRING DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6--33
7--1
7--2
7--3
7--5
7--6

LIST OF TABLES
TABLE NUMBER
Page
Table 2-1 Safety and Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2--9
Table 3-1 Keypad Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--2
Table 3-2 DataCORDER Configuration Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--8
Table 3-3 DataCORDER Standard Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3--9
Table 3-4 Controller Configuration Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--13
Table 3-5 Controller Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--14
Table 3-6 Controller Alarm Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--18
Table 3-7 Controller Pre-Trip Test Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--22
Table 3-8 DataCORDER Function Code Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--26
Table 3-9 DataCORDER Pre-Trip Result Records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--27
Table 3-10 DataCORDER Alarm Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--28
Table 6-1 Sensor Temperature/Resistance Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--21
Table 6-2 Crack, Chip and Hole Repair Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--27
Table 6-3 Insert Repair Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--27
Table 6-4 Drill Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--27
Table 6-5 Recommended Bolt Torque Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--30
Table 6-6 Wear Limits For Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--30
Table 6-7 Compressor Torque Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--31
Table 6-8 R-134a Temperature - Pressure Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--32
vii

T-354

SAFETY SUMMARY
GENERAL SAFETY NOTICES
The following general safety notices supplement the
specific warnings and cautions appearing elsewhere in
this manual. They are recommended precautions that
must be understood and applied during operation and
maintenance of the equipment covered herein. The
general safety notices are presented in the following
three sections labeled: First Aid, Operating Precautions
and Maintenance Precautions. A listing of the specific
warnings and cautions appearing elsewhere in the
manual follows the general safety notices.
FIRST AID
An injury, no matter how slight, should never go
unattended. Always obtain first aid or medical attention
immediately.

WARNING -- Warns against hazards or unsafe


conditions which COULD result in severe personal
injury or death.
CAUTION -- Warns against potentially hazardous or
unsafe practices that could result in minor personal
injury, product or property damage.
SPECIFIC WARNING AND CAUTION
STATEMENTS
The statements listed below are applicable to the
refrigeration unit and appear elsewhere in this manual.
These recommended precautions must be understood
and applied during operation and maintenance of the
equipment covered herein.

OPERATING PRECAUTIONS

WARNING

Always wear safety glasses.


Keep hands, clothing and tools clear of the evaporator
and condenser fans.
No work should be performed on the unit until all circuit
breakers, start-stop switches are turned off, and power
supply is disconnected.
Always work in pairs. Never work on the equipment
alone.
In case of severe vibration or unusual noise, stop the
unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator and
condenser fans. Do not open the condenser fan grille or
evaporator access panels before turning power off, and
disconnecting and securing the power plug.
Be sure power is turned off before working on motors,
controllers, solenoid valves, and electrical control
switches. Tag circuit breaker and power supply to
prevent accidental energizing of circuit.
Do not bypass any electrical safety devices, e.g.
bridging an overload, or using any sort of jumper wires.
Problems with the system should be diagnosed and any
necessary repairs performed by qualified service
personnel.
When performing any arc welding on the unit or
container, disconnect all wire harness connectors from
the modules in both control boxes. Do not remove wire
harness from the modules unless you are grounded to
the unit frame with a static safe wrist strap.
In case of electrical fire, open circuit switch and
extinguish with CO2 (never use water).
UNIT LABEL IDENTIFICATION
To help identify the label hazards on the unit and explain
the level of awareness each one carries, an explanation
is given with the appropriate consequences:
DANGER -- Indicates an immediate hazard that WILL
result in severe personal injury or death.
Safety--1

Beware of unannounced starting of the


evaporator and condenser fans. The unit
may cycle the fans and compressor unexpectedly as control requirements dictate.

WARNING
Do not attempt to remove power plug(s) before turning OFF start-stop switch (ST), unit
circuit breaker(s), and external power
source.

WARNING
Make sure the power plugs are clean and
dry before connecting to any power
receptacle.

WARNING
Make sure that the unit circuit breaker(s)
(CB-1 & CB-2) and the START-STOP switch
(ST) are in the O (OFF) position before
connecting to any electrical power source.

WARNING
Never use air for leak testing. It has been determined that pressurized mixtures of refrigerant and air can undergo combustion
when exposed to an ignition source.
T-354

WARNING

WARNING
Make sure power to the unit is OFF and
power plug disconnected before servicing
capacitor(s).

Never use air for leak testing. It has been


determined that pressurized, air-rich mixtures of refrigerants and air can undergo
combustion when exposed to an ignition
source.

WARNING
With power OFF discharge the capacitor
before disconnecting the circuit wiring.

WARNING
Make sure power to the unit is OFF and
power plug disconnected before replacing
the compressor.

WARNING
The unit power plug must be disconnected
to remove power from circuit breaker CB1

WARNING

WARNING

Do not use a nitrogen cylinder without a


pressure regulator. Do not use oxygen in or
near a refrigeration system as an explosion
may occur.

Make sure power to the unit is OFF and


power plug disconnected before removing
capacitor(s).

WARNING
WARNING

Before removing the capacitors, the


terminals must be checked for voltage with
a multimeter. The discharge resistors
installed on the unit (capacitors) should
bring the voltage to a safe level in a minute.
However, there may be a broken resistor
that retains voltage for a longer period.
Therefore, it is highly recommended to wait
15 minutes and to check for voltage.

Do not open the condenser fan grille before


turning power OFF and disconnecting
power plug.

WARNING
Oakite No. 32 is an acid. Be sure that the
acid is slowly added to the water. DO NOT
PUT WATER INTO THE ACID. This will
cause spattering and excessive heat.

CAUTION
Do not remove wire harnesses from controller unless you are grounded to the unit
frame with a static safe wrist strap.

WARNING

CAUTION

Wear rubber gloves and wash the solution


from the skin immediately if accidental contact occurs. Do not allow the solution to
splash onto concrete.

Unplug all controller wire harness connectors before performing arc welding on any
part of the container.

WARNING

CAUTION

Always turn OFF the unit circuit breakers


(CB-1 & CB-2) and disconnect main power
supply before working on moving parts.
T-354

Pre-trip inspection should not be performed with critical temperature cargoes in


the container.
Safety--2

CAUTION

CAUTION
The unit will remain in the full cooling mode
as long as the emergency bypass switch is
in the BYPASS position and the MODE
SWITCH is in the FULL COOL position. If
the cargo may be damaged by low temperatures, the operator must monitor container
temperature and manually cycle operation
as required to maintain temperature within
required limits.

When Pre-Trip key is pressed, dehumidification and bulb mode will be deactivated.
At the completion of Pre-Trip activity, dehumidification and bulb mode must be
reactivated.

CAUTION
When condenser water flow is below 11 lpm
(3 gpm) or when water-cooler is not in use,
the CFS switch MUST be set to position I
or the unit will not operate properly.

CAUTION
The unit will remain in the DEFROST mode
as long as the emergency defrost switch is
in the DEFROST position. To prevent cargo
damage, the operator must monitor container temperature and manually cycle operation as required to maintain temperature
within required limits.

CAUTION
Pre-trip inspection should not be performed with critical temperature cargoes in
the container.

CAUTION
To prevent trapping liquid refrigerant in the
manifold gauge set, be sure set is brought
to suction pressure before disconnecting.

CAUTION

WARNING

When Pre-Trip key is pressed, dehumidification and bulb mode will be deactivated.
At the completion of Pre-Trip activity, dehumidification and bulb mode must be
reactivated.

Before disassembly of any external compressor component, make sure to relieve


possible internal pressure by loosening the
bolts and tapping the component with a
soft hammer to break the seal.

CAUTION

CAUTION

When a failure occurs during automatic


testing, the unit will suspend operation
awaiting operator intervention.

Removing the compressor motor press-fit


stator in the field is not recommended. The
rotor and stator are a matched pair and
should not be separated.

CAUTION

CAUTION

When Pre-Trip test Auto 2 runs to completion without being interrupted, the unit will
terminate pre-trip and display Auto 2
end. The unit will suspend operation until
the user depresses the ENTER key!

The copper tube that connects to the oil


suction strainer extends out the bottom
with the bottom plate removed. Take precautions to avoid bending or breaking it
while changing crankcase positions.
Safety--3

T-354

CAUTION

CAUTION
Do not remove wire harnesses from controller unless you are grounded to the unit
frame with a static safe wrist strap.

Ensure that the thrust washer does not fall


off dowel pins while installing oil pump.

CAUTION

CAUTION
Unplug all controller connectors before
performing arc welding on any part of the
container.

The set screw on the crankshaft must be


removed for this type of oil pump. (See
Figure 6-9.)

CAUTION

CAUTION

The unit must be OFF whenever a programming card is inserted or removed from the
controller programming port.

Use only Carrier Transicold approved


Polyol Ester Oil (POE) -- Castrol-Icematic
SW20 compressor oil with R-134a. Buy in
quantities of one quart or smaller. When
using this hygroscopic oil, immediately
reseal. Do not leave container of oil open or
contamination will occur.

CAUTION
Do not allow moisture to enter wire splice
area as this may affect the sensor
resistance.

CAUTION

CAUTION

Take necessary steps (place plywood over


coil or use sling on motor) to prevent motor
from falling into condenser coil.

Do not allow the recorder stylus to snap


back down. The stylus arm base is
spring-loaded, and damage may occur to
the chart or the stylus force may be altered.

CAUTION

CAUTION

DO NOT disassemble piston from NEW suction modulating valve powerhead assembly. Doing so may result in damage to
piston.

T-354

DO NOT move the stylus arm up and down


on the chart face. This will result in damage
to the stylus motor gear.

Safety--4

SECTION 1
INTRODUCTION
1.1 INTRODUCTION

1.3.4 Display Module


The unit may be fitted with a backlit Liquid Crystal
Display (LCD) or a Light Emitting Diode (LED) Display.
1.3.5 Temperature Readout
The unit may be fitted with suction and discharge
temperature sensors. The sensor readings may be
viewed on the controller display.
1.3.6 Pressure Readout
The unit may be fitted with suction and discharge
pressure gauges, or suction and discharge transducers
or no pressure readout. The transducer readings may
be viewed on the controller display.
1.3.7 USDA
The unit may be supplied with fittings for additional
temperature probes, which allow recording of USDA
Cold Treatment data by the integral DataCORDER
function of the Micro-Link refrigeration controller.
1.3.8 Interrogator
Units that use the DataCORDER function are fitted with
interrogator receptacles for connection of equipment to
download the recorded data. Two receptacles may be
fitted; one accessible from the front of the container and
the other mounted inside the container (with the USDA
receptacles).
1.3.9 Remote Monitoring
The unit may be fitted with a remote monitoring
receptacle. This item allows connection of remote
indicators for COOL, DEFROST and IN RANGE.
Unless otherwise indicated, the receptacle is mounted
at the control box location
1.3.10 Communications
The unit may be fitted with a communications interface
module. The communications interface module is a
slave module, which allows communication with a
master central monitoring station. The module will
respond to communication and return information over
the main power line. Refer to the ship master system
technical manual for further information.
1.3.11 Compressor
The unit is fitted with a single speed reciprocating
compressor.
1.3.12 Condenser Coil
The unit is fitted with a 3--row coil using 7mm tubing.
1.3.13 Autotransformer
An autotransformer may be provided to allow operation
on 190/230, 3--phase, 50/60 hertz power. The
autotransformer raises the supply voltage to the
nominal 380/460 volt power required by the base unit.
The autotransformer may also be fitted with an
individual circuit breaker for the 230 volt power.
If the unit is equipped with an autotransformer and the
Low Data Rate Communications Interface Module, the
autotransformer will be fitted with a transformer bridge
unit (TBU) to assist in communications.
1.3.14 Temperature Recorder
The unit may be fitted with an electronic temperature
recording device.

The Carrier Transicold Upflow container models


69NT40-541-314 series units are made of lightweight
aluminum frame construction. They are designed to fit in
the front of a container and serve as the containers front
wall.
They are one piece, self-contained, all-electric units,
which includes cooling and heating systems to provide
precise temperature control.
The units are suppled with a complete charge of
refrigerant R-134a and compressor lubricating oil, and
are ready for operation upon installation. Forklift
pockets are provided for unit installation and removal.
The base unit operates on nominal 380/460 volt,
3--phase,
50/60 hertz power.
An optional
autotransformer may be fitted to allow operation on
nominal 190/230 , 3--phase, 50/60 hertz power. Power
for the control system is provided by a transformer,
which steps the supply power down to 18 and 24 volts,
single phase.
The controller is a Carrier Transicold Micro-Link 3
microprocessor.
The
controller
will
operate
automatically to select cooling, holding or heating as
required to maintain the desired set point temperature
within very close limits. The unit may also be equipped
with a mechanical or electronic temperature recorder.
The controller has a keypad and display for viewing or
changing operating parameters. The display is also
equipped with lights to indicate various modes of
operation.
1.2 CONFIGURATION IDENTIFICATION
Unit identification information is provided on a plate
located near the compressor. The plate provides the
unit model number, the unit serial number and the unit
parts identification number (PID). The model number
identifies the overall unit configuration while the PID
provides information on specific optional equipment,
factory provision to allow for field installation of optional
equipment and differences in detailed parts.
1.3 OPTION DESCRIPTION
Various options may be factory or field equipped to the
base unit. These options are listed in the tables and
described in the following subparagraphs.
1.3.1 Battery
The refrigeration controller may be fitted with standard
replaceable batteries or a rechargeable battery pack.
1.3.2 Dehumidification
The unit may be fitted with a humidity sensor. This
sensor allows setting of a humidity set point in the
controller. In the dehumidification mode the controller
will operate to reduce internal container moisture level.
1.3.3 Control Box
Units are equipped with either an aluminum or
composite material box, and may be fitted with a
lockable door.
1--1

T-354

1.3.15 Gutters

1.3.25 Arctic Mode


To improve operation in cold ambients, the unit may be
fitted with a crankcase heater. The crankcase heater is
operated any time the unit is under power and the
compressor is not running. The purpose of the heater is
to warm the compressor oil and boil off any liquid
refrigerant that may be present in the crankcase.
1.3.26 Power Correction
The unit may be fitted with a set of power factor
correction capacitors to assist in correction of
imbalance in current draw by the compressor.
1.3.27 Evaporator
The evaporator section is equipped with a hermetic
thermal expansion valve and a heat exchanger. The unit
may have six heaters.
1.3.28 Evaporator Fan Operation
Two evaporator fan motor operation systems are
available. On units with Normal Evaporator Fan
Operation, opening of an evaporator fan internal
protector will shut down the unit. On units equipped with
single evaporator fan capability, additional relays are
installed to allow the unit to continue to operate on a
single fan.
1.3.29 Labels
Operating instruction and function code listing labels will
differ depending on the options installed. For example,
additional operating instructions are required to
describe start-up of a unit equipped with an
autotransformer. Where the labels are available with
additional languages, they are listed in the parts list.
1.3.30 Plate Set
Each unit is equipped with a tethered set of wiring
schematic and wiring diagram plates. The plate sets are
ordered using a seven-digit base part number and a
two-digit dash number.
1.3.31 Controller
Two different controllers are available:

Rain gutters may be fitted over the control box and


recorder section to divert rain away form the controls.
The different gutters include standard length bolted
gutters, extended length gutters, and riveted gutters.
1.3.16 Handles
The unit may be equipped with handles to facilitate
access to stacked containers. These handles may
include fixed handles (located at the sides of the unit)
and/or a hinged handle at the center (attached to the
condenser coil cover).
1.3.17 Thermometer Port
The unit may be fitted with ports in the front of the frame
for insertion of a thermometer to measure supply and/or
return air temperature. If fitted, the port(s) will require a
cap and chain.
1.3.18 Water Cooling
The refrigeration system may be fitted with a
water-cooled condenser. The condenser is constructed
using copper-nickel tube for seawater applications. The
water-cooled condenser is in series with the air-cooled
condenser and replaces the standard unit receiver.
When operating on the water-cooled condenser, the
condenser fan can be deactivated by either a water
pressure switch or condenser fan switch. Depending on
the units configuration and the compressor discharge
temperature, the condenser fan may also be activated
during water-cooled condenser operation.
1.3.19 Back Panels
Back panel designs that may be fitted include panels of
aluminum and stainless steel. Panels may have access
doors and/or hinge mounting.
1.3.20 460 Volt Cable
Various power cable and plug designs are available for
the main 460 volt supply. The plug options tailor the
cables to each customers requirements.

1. Remanufactured -- Controller is the equivalent of a


new OEM controller and is supplied with a 12 month
warranty.

1.3.21 230 Volt Cable


Units equipped with an autotransformer require an
additional power cable for connection to the 230 volt
source. Various power cable and plug designs are
available. The plug options tailor the cables to each
customers requirements.

2. Repaired -- Controller has had previous faults


repaired and upgraded with the latest software.
Note: Repaired controllers are NOT to be used for
warranty repairs. Only full OEM remanufactured
controllers are to be used.

1.3.22 Cable Restraint

Controllers will be factory equipped with the latest


version of operational software, but will NOT be
configured for a specific model number and will need
to be configured at the time of installation or sale.
1.3.32 Condenser Grille
Two styles of condenser grilles are available -- direct
bolted grilles and hinged grilles.
1.3.33 Emergency Bypass

Various designs are available for storage of the power


cables. These options are variations of the compressor
section front cover.
1.3.23 Upper Air (Fresh Air Make Up)
The unit may be fitted with an upper fresh air makeup
assembly. The fresh air makeup assembly is available
with a vent positioning sensor (VPS) and may also be
fitted with screens.

The unit may be equipped with switches to allow


emergency bypass of the controller. The EMERGENCY
BYPASS switch functions to bypass the controller in the
event of controller failure. The EMERGENCY
DEFROST switch functions to bypass all controls and
place the unit in the defrost mode.

1.3.24 Lower Air (Fresh Air Make Up)


The unit may be fitted with a lower fresh air makeup
assembly. The fresh air makeup assembly is available
with a vent positioning sensor (VPS) and may also be
fitted with screens.
T-354

1--2

SECTION 2
DESCRIPTION
2.1 GENERAL DESCRIPTION

parts identification number can be found on the serial


plate to the left of the compressor.

2.1.1 Refrigeration Unit -- Front Section

2.1.2 Fresh Air Makeup Vent

The unit is designed so that the majority of the


components are accessible from the front (see
Figure 2-1). The unit model number, serial number, and

The function of the upper or lower makeup air vent is to


provide ventilation for commodities that require fresh air
circulation.

13
1
12

11

10
2

7
6
5

1.
2.
3.
4.
5.
6.
7.

8.
9.
10.

Access Panel (Evaporator Fan #1)/Thermostatic


Expansion Valve / HTT
Fork Lift Pockets
Control Box
Compressor, Reciprocating
Unit Serial Number, Model Number, and
Parts Identification Number (PID) Plate
Condenser Fan
TransFRESH Communications Connector

11.
12.
13.

Interrogator Connector (Front Left)


Temperature Recorder
Lower Fresh Air Makeup Vent Location
(Blank Cover Shown)
TIR (Transports Internationaux Routiers)
Sealing Provisions - Typical All Panels
Upper Fresh Air Makeup Vent
Access Panel (Evaporator Fan #2)/ Humidity
Sensor / Supply Temperature Sensor

Figure 2-1 Refrigeration Unit -- Front Section


2--1

T-354

The evaporator fans circulate air through the container


by pulling it from the bottom of the unit, directing it
through the evaporator coil where it is heated or cooled,
and discharging it at the top.

2.1.3 Evaporator Section


The evaporator section (Figure 2-2) contains the supply
temperature sensor, humidity sensor, thermostatic
expansion valve, dual-speed evaporator fans (EM1 and
EM2), evaporator coil and heaters, defrost temperature
sensor, heat termination thermostat, and heat
exchanger.

The evaporator components are accessible by


removing the upper rear panel (as shown in Figure 2-2).
6

5
4
2
1

16

14
13
12
11
10

9
15

1.
2.
3.
4.
5.
6.
7.
8.

TXV Bulb
(under Insulation)

Evaporator Fan Motor #1


9.
Heat Exchanger
Supply Recorder Sensor (SRS) /
10. Interrogator Connector (Rear)
Supply Temperature Sensor (STS)
11. USDA Probe Receptacle PR2
Humidity Sensor
12. USDA Probe Receptacle PR1
Evaporator Fan Motor #2
13. USDA Probe Receptacle PR3
Defrost Temperature Sensor
14. Cargo Probe Receptacle PR4
Heater Termination Thermostat
15. Evaporator Coil Heaters
Evaporator Coil
16. TXV Bulb Routing
Hermetic Thermostatic Expansion Valve (TXV)
Figure 2-2 Evaporator Section -- UPFLOW Units With Center Access Panel

T-354

2--2

discharge pressure regulating valve, discharge


temperature sensor, and discharge/suction pressure
transducers.
The return temperature sensor, return recorder sensor,
and ambient sensor are located at the right side of the
compressor.

2.1.4 Compressor Section


The reciprocating compressor section includes the
compressor (with high pressure switch), power cable
storage compartment, and autotransformer.
This section also contains the suction modulating valve,

1
5

11
10

12
13

21
22

16

14

17

20
19
1.
2.
3.
4.
5.
6.
7.
8
9.
10.
11.

15

18

12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.

Autotransformer
Power Cables and Plug
Compressor Sight Glass View Port
Compressor Guard
Return Temperature Sensor
Return Recorder Sensor
Ambient Sensor
Return Air Thermometer Port
Discharge Service Valve
Discharge Temperature Sensor
Discharge Pressure Regulating Valve

Suction Temperature Sensor


Quench Valve Temperature Bulb
Quench Valve
Access Valve
Suction Modulating Valve
Suction Service Valve
Compressor Crankcase Heater
Compressor Motor
Suction Pressure Transducer
High Pressure Switch
Discharge Pressure Transducer

Figure 2-3 Compressor Section

2--3

T-354

line valve, filter-drier, condenser pressure transducer,


and fusible plug.
The condenser fan pulls air in through the bottom of the
coil and discharges it horizontally out through the
condenser fan grille.

2.1.5 Air-cooled Condenser Section


The air-cooled condenser section (Figure 2-4) consists
of the condenser fan, condenser coil, receiver with sight
glass/moisture indicator, quench valve, manual liquid

6
7
5

8
9

15

10
11
12
13

14

1.
2.
3.
4.
5.
6.
7.
8.

Grille and Venturi Assembly


Condenser Fan
Key
Condenser Fan Motor
Condenser Coil Cover
Condenser Coil
Condenser Motor Mounting Bracket
Receiver

9.
10.
11.
12.
13.
14.
15.

Sight Glass
Fusible Plug (Rupture Disc -- Alternate)
Condenser Pressure Transducer
Sight Glass/Moisture Indicator
Filter-Drier
Liquid Line Service Valve
Quench Valve

Figure 2-4 Condenser Section


T-354

2--4

quench expansion valve, rupture disc, condenser


pressure transducer, filter-drier, water couplings, and
water pressure switch. The water-cooled condenser
replaces the standard unit receiver.

2.1.6 Water-cooled Condenser Section


The water-cooled condenser section (Figure 2-5)
consists of a water-cooled condenser, sight glass,

1
9

11

1.
2.
3.
4.
5.
6.

10

Sight Glass
7. Liquid Line Service Valve
Water-Cooled Condenser
8. Moisture/Liquid Indicator
Rupture Disc
9. Coupling (Water In)
Condenser Pressure Transducer
10. Self Draining Coupling (Water Out)
Quench Valve
11. Water Pressure Switch
Filter-Drier
Figure 2-5 Water-cooled Condenser Section

2--5

T-354

2.1.7 Control Box Section


The control box (Figure 2-6) includes the manual
operation switches, circuit breaker (CB-1), compressor,
fan and heater contactors, control power transformer,
fuses, keypad, display module, current sensor module,
controller module and the communications interface
module.
1

20

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

2.1.8 Communications Interface Module


The communications interface module is a slave
module, which allows communication with a master
central monitoring station. The module will respond to
communication, and return information over the main
power line. Refer to the master system technical manual
for further information.

19

18

17

16

15

14

12

13

Compressor Contactor
Heater Contactor
Display Module
Communications Interface Module
Controller/DataCORDER Module (Controller)
Key Pad
Emergency Defrost Light
Start-Stop Switch
Remote Monitoring Receptacle
Manual Defrost Switch

11.
12.
13.
14.
15.
16.
17.
18.
19.
20.

11

2--6

10

Controller Battery Pack


Interrogator Connector (Box Location)
Control Transformer
Evaporator Fan Contactor - E1
Evaporator Fan Contactor - S1
Evaporator Fan Contactor - S2 or EF
Evaporator Fan Contactor - E2 or ES
Condenser Fan Contactor
Circuit Breaker -- 460V
Current Sensor Module

Figure 2-6 Control Box Section

T-354

8 7

2.2 REFRIGERATION SYSTEM DATA

a. Compressor/Motor
Assembly

Number of Cylinders
Model
CFM
Weight (Dry)
Approved Oil
Oil Charge degrees
Oil Sight Glass

Verify at -18 C
(0F) container box
temperature
Opens
c. Heater Termination Thermostat
Closes
Cutout
d. High Pressure Switch
Cut-In
b. Expansion Valve Superheat

Unit Configuration
e. Refrigerant Charge

Water-Cooled
Condenser
Receiver

6
06DR
41
118 kg (260 lb)
Castrol Icematic
3.6 liters (7.6 U.S. pints)
The oil level range, with the compressor off,
should be between the bottom and one-eighth
level of the sight glass.
4.5 to 6.7C (8 to 12F)
54 (+/-) C = 130 (+/-) F
38 (+/- 4) C = 100 (+/- 7) F
25 (+/- 1.0) kg/cm@ = 350 (+/- 10) psig
18 (+/- 0.7) kg/cm@ = 250 (+/- 10) psig
Charge Requirements -- R-134a
3 row condenser
4.9 kg (10.75 lbs)

4.0 kg (8.75 lbs)


NOTE
When replacing the following components (f.), (g.) and (h.), refer to the installation instructions included with the
replacement part for additional information.
Melting point
99C = (210 F)
f. Fusible Plug*
Torque*
6.2 to 6.9 mkg (45 to 50 ft-lbs)
g. Sight Glass/Moisture Indicator Torque
8.9 to 9.7 mkg (65 to 70 ft-lbs)
Bursts at
35 +/- 5% kg/cm@ = (500 +/- 5% psig)
h. Rupture Disc
Torque
1.4 to 2 mkg (10 to 15 ft-lbs)
(P/N 14-00215-03)
The condenser fan will start if the condenser
pressure is greater than 14.06 kg/cm@ (200
Condenser Fan Starts psig) OR the condenser fan is OFF for more
than 60 seconds.
i. Condenser Pressure
Transducer
The condenser fan will stop if the condenser
pressure is less than 9.14 kg/cm@ (130 psig)
Condenser Fan Stops AND the condenser fan remains ON for at least
30 seconds.
Refer to unit model number plate.
0.5 +/- 0.2 kg/cm@
3-row condenser (7 +/- 3 psig)

j. Unit Weight
k. Water Pressure Switch

Cut-In
Cutout

l. Discharge Pressure
Regulating Valve

1.6 +/- 0.4 kg/cm@ (22 +/- 5 psig)

Factory Setting

32.7 +/- 2.5 kg/cm@ (72+/- 5.5 psig)

* Rupture Disc, part number 14 -00215 -04 may be installed as an alternate for the receiver mounted fusible plug.

2--7

T-354

2.3 ELECTRICAL DATA


CB-1 Trips at
CB-2 (50 amp) Trips at
a. Circuit Breaker
CB-2 (70 amp) Trips at
b. Compressor
Full Load Amps (FLA)
Motor

c. Condenser Fan
Motor

d. Evaporator Coil
Heaters

e. Evaporator Fan
Motor(s)

f. Fuses

Full Load Amps


Horsepower
Rotations Per Minute
Voltage and Frequency
Bearing Lubrication
Rotation
Number of Heaters
Rating
Resistance (cold)
Type
Full Load Amps
High Speed
Full Load Amps
Low Speed
Nominal Horsepower
High Speed
Nominal Horsepower
Low Speed
Rotations Per Minute
High Speed
Rotations Per Minute
Low Speed
Voltage and Frequency
Voltage & Frequency using power autotransformer
Bearing Lubrication
Rotation EF#1
Rotation EF#2
Control Circuit
Controller/DataCORDER
Emergency Defrost
Drain Line Heater
Humidity Power
Transformer

29 amps
62.5 amps
87.5 amps
17.6 amps @ 460 VAC
(with current limiting set at 21 amps)
380 VAC, Single Phase,
460 VAC, Single Phase,
50 Hz
60 hz
1.3 amps
1.6 amps
0.43 hp
0.75 hp
1425 rpm
1725 rpm
360 -- 460 VAC +/- 2.5 hz
400 -- 500 VAC +/- 2.5 hz
Factory lubricated, additional grease not required.
Counter-clockwise when viewed from shaft end.
6
750 watts +5/ -10% each @ 230 VAC
66.8 to 77.2 ohms @ 20C (68F)
Sheath
380 VAC/50 hz
460 VAC/60 hz
1.6

2.1

0.6

0.6

0.58

1.0

0.07

0.12

2850 rpm

3450 rpm

1425 rpm

1750 rpm

360 -- 460 VAC +/- 1.25 hz

400 -- 500 VAC +/- 1.5 hz

180 -- 230 VAC +/- 1.25hz

200 -- 250 VAC +/- 1.5 hz

Factory lubricated, additional grease not required


CW when viewed from shaft end
CCW when viewed from shaft end
7.5 amps (F3A, F3B)
5 amps (F1 & F2)
5 amps (FED)
5 amps (FDH)
5 amps (FH)
180 watts @ 460 VAC

g. Compressor Crankcase Heater

T-354

2--8

2.3 ELECTRICAL DATA (Continued)


Orange wire
Power
Red wire
Output
Brown wire
Ground
Input voltage
5 vdc
Output voltage
0 to 3.3 vdc
h. Humidity Sensor
Output voltage readings verses relative humidity (RH) percentage:
30%
0.99 V
50%
1.65 V
70%
2.31 V
90%
2.97 V
i. Controller

Setpoint Range

-30 to +30C ( -22 to +86F)

2.4 SAFETY AND PROTECTIVE DEVICES


Unit components are protected from damage by safety and protective devices listed in the following table. These
devices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition occurs.
Table 2-1 Safety and Protective Devices
UNSAFE CONDITION

Excessive current draw

Excessive current draw in the


control circuit

SAFETY DEVICE

DEVICE SETTING

Circuit Breaker (CB-1) -- Manual Reset

Trips at 29 amps (460 VAC)

Circuit Breaker (CB-2, 50 amp) --Manual Reset

Trips at 62.5 amps (230


VAC)

Circuit Breaker (CB-2, 70 amp) --Manual Reset

Trips at 87.5 amps (230


VAC)

Fuse (F3A & F3B)

7.5 amp rating

Excessive current draw by the


Fuse (F1 & F2)
controller

5 amp rating

Excessive current draw by the


Fuse (FED)
emergency defrost circuit

5 amp rating

Excessive condenser fan


motor winding temperature

Internal Protector (IP-CM) -- Automatic Reset

N/A

Excessive compressor motor


winding temperature

Internal Protector (IP-CP) -- Automatic Reset

N/A

Excessive evaporator fan


motor(s) winding temperature

Internal Protector(s) (IP-EM) -- Automatic Reset

N/A

Abnormal pressures /
temperatures in the high
refrigerant side
Abnormally high discharge
pressure

Fusible Plug -- Used on the Receiver

99C = (210F)

Rupture Disc -- Used on the Water-Cooled


Condenser

35 kg/cm@ = (500 psig)

High Pressure Switch (HPS)

Opens at 25 kg/cm@
(350 psig)

2--9

T-354

2.5 REFRIGERATION CIRCUIT


Starting at the compressor (see Figure 2-7, upper
schematic), the suction gas is compressed to a higher
pressure and temperature.
The gas flows through the discharge service valve into
the pressure regulating valve. During periods of low
ambient operation, the discharge pressure regulating
valve modulates the flow of refrigerant to maintain a pre
-set minimum discharge pressure. Refrigerant gas then
moves into the air-cooled condenser. When operating
with the air-cooled condenser active, air flowing across
the coil fins and tubes cools the gas to saturation
temperature. By removing latent heat, the gas
condenses to a high pressure/high temperature liquid
and flows to the receiver, which stores the additional
charge necessary for low temperature operation.
When operating with the water-cooled condenser active
(see Figure 2-7, lower schematic), the refrigerant gas
passes through the air-cooled condenser and enters the
water-cooled condenser shell. The water flowing inside
the tubing cools the gas to saturation temperature in the
same manner as the air passing over the air-cooled
condenser. The refrigerant condenses on the outside of
the tubes and exits as a high temperature liquid. The
water-cooled condenser also acts as a receiver, storing
excess refrigerant.
The liquid refrigerant continues through the liquid line
service valve, the filter-drier (which keeps refrigerant
clean and dry), and a heat exchanger (that increases
subcooling of the liquid) to the thermostatic expansion
valve (TXV). As the liquid refrigerant passes through the
variable orifice of the expansion valve, some of it
vaporizes into a gas (flash gas). Heat is absorbed from
the return air by the balance of the liquid, causing it to
vaporize in the evaporator coil. The vapor then flows
through the suction modulating valve to the compressor.
The thermostatic expansion valve is activated by the
bulb strapped to the suction line near the evaporator

T-354

outlet. The valve maintains a constant superheat at the


coil outlet regardless of load conditions.
During periods of low load, the suction modulating valve
decreases flow of refrigerant to the compressor. This
action balances the compressor capacity with the load
and prevents operation with low coil temperatures. In
this mode of operation, the quench valve will open as
required to provide sufficient liquid refrigerant flow into
the suction line for cooling of the compressor motor. The
quench valve senses refrigerant condition entering the
compressor and modulates the flow to prevent entrance
of liquid into the compressor.
The refrigeration system is also fitted with a condenser
pressure transducer, which feeds information to the
controller. When operating on the air-cooled condenser,
the controller programming will operate the condenser
fan so as to attempt to maintain discharge pressures
above 130psig in low ambients. At ambients below 27C
(80F), the condenser fan will cycle on and off
depending on condenser pressure and operating times.
1 The condenser fan will start if the condenser pressure is greater than 200psig OR the condenser fan
has been OFF for more than 60 seconds.
2 The condenser fan will stop if the condenser pressure is less than 130psig AND the condenser fan has
been running for at least 30 seconds.
At ambients above 27C (80F), condenser pressure
control is disabled and the condenser fan runs
continuously.
On systems fitted with a water pressure switch, the
condenser fan will be off when there is sufficient
pressure to open the switch. If water pressure drops
below the switch cut out setting, the condenser fan will
be automatically started. When operating a system
fitted with a condenser fan switch, the condenser fan will
be off when the switch is placed in the O position. The
condenser fan will be on when the switch is placed in the
I position.

2--10

EVAPORATOR

THERMOSTATIC
EXPANSION VALVE
(TXV)

TXV BULB

CONDENSER

HEAT EXCHANGER

DISCHARGE PRESSURE
REGULATING VALVE

QUENCH
VALVE BULB

SERVICE VALVE

MODULATING
VALVE

FUSIBLE PLUG

QUENCH VALVE

SIGHT GLASS
FILTER DRIER

Suction
Liquid
Discharge

PRESSURE TRANSDUCER
SIGHT GLASS /
MOISTURE INDICATOR

SERVICE
VALVE
RECEIVER

Circuit with Receiver


EVAPORATOR

THERMOSTATIC
EXPANSION VALVE
(TXV)

TXV BULB

CONDENSER
HEAT EXCHANGER

DISCHARGE PRESSURE
REGULATING VALVE

RUPTURE DISC
MODULATING VALVE

SERVICE VALVE

MOISTURE
INDICATOR

QUENCH
VALVE BULB

WATER-COOLED
CONDENSER

SIGHT GLASS

Suction
Liquid
Discharge

SERVICE VALVE
QUENCH VALVE

FILTER DRIER

Circuit with Water-Cooled Condenser


Figure 2-7 Refrigeration Circuit Schematic
2--11

T-354

2.6 ARCTIC OPTION


The arctic option consists of the crankcase heater
(CCH) installed onto the compressor, which warms the

refrigerant oil and evaporates any liquid refrigerant


which may have migrated to the compressor crankcase.

1. Compressor Crankcase Heater (CCH)


Figure 2-8 Arctic Option

T-354

2--12

SECTION 3
MICROPROCESSOR
operating parameters and cargo temperature
parameters for future retrieval. Coverage of the
temperature control software begins with paragraph
3.2. Coverage of the DataCORDER software is
provided in paragraph 3.6.

3.1 TEMPERATURE CONTROL


MICROPROCESSOR SYSTEM
The temperature control Micro-Link 3 microprocessor
system (see Figure 3-6) consists of a keypad, display
module,
control
module
(controller),
and
interconnecting wiring. The controller houses the
temperature control software and the DataCORDER
Software. The temperature control software functions to
operate the unit components as required to provide the
desired cargo temperature and humidity. The
DataCORDER software functions to record unit

The keypad and display module serve to provide user


access and readouts for both of the controller functions,
temperature control, and DataCORDER. The functions
are accessed by keypad selections and viewed on the
display module. The components are designed to
permit ease of installation and removal.

DISPLAY MODULE

CONTROL MODULE

TEMPERATURE CONTROL SOFTWARE


KEYPAD

CONFIGURATION
SOFTWARE

CONFIGURATION
VARIABLE
(CnF##)

OPERATIONAL
SOFTWARE

FUNCTION
CODE (Cd)

ALARMS
(AL<70)

PRE--TRIP
INTERROGATION
CONNECTOR

TO
DISPLAY

DATAREADER

DataCORDER SOFTWARE

CONFIGURATION
SOFTWARE

OPERATIONAL
SOFTWARE

CONFIGURATION
VARIABLE
(dCF## read only)

FUNCTION
CODE (dC)

DATA
STORAGE
MEMORY

ALARMS
(AL>68)

TO
DISPLAY
(Scrollback)

TO
DISPLAY

Computer Device
With DataLine
Software

PCMCIA CARD

Figure 3-6 Temperature Control System


3--1

T-354

Table 3-1 Keypad Function

3.1.1 Keypad
The keypad (Figure 3-7) is mounted on the right-hand
side of the control box. The keypad consists of 11 push
button switches that act as the users interface with the
controller. Descriptions of the switch functions are
provided in Table 3-1.

CODE
SELECT

PRE
TRIP

ALARM
LIST

MANUAL
DEFROST/
INTERVAL

KEY

FUNCTION

Code Select Accesses function codes.


Pre-Trip

Displays the pre-trip selection menu.


Discontinues pre-trip in progress.

Alarm List

Displays alarm list and clears the


alarm queue.

Manual
Defrost/
Interval

Enter
Arrow Up

ENTER

Displays selected defrost mode. Depressing and holding the Defrost interval key for five seconds will initiate
defrost using the same logic as if the
optional manual defrost switch was
toggled on.
Confirms a selection or saves a
selection to the controller
Change or scroll a selection upward.
Pre-trip advance or test interruption.

Change or scroll a selection downArrow Down ward. Pre-trip repeat backward


Return/
Supply
RETURN
SUPPLY

_C
_F

BATTERY
POWER

ALT.
MODE

Figure 3-7 Keypad

COOL

HEAT DEFROST IN RANGE ALARM

SETPOINT/Code

Battery
Power

Initiate battery backup mode to allow


set point and function code selection
if AC power is not connected.

ALT. Mode

This key is pressed to switch the


functions from the temperature software to the DataCORDER Software.
The remaining keys function the
same as described above except the
readings or changes are made to the
DataCORDER programming.

NOTE
The controlling probe in the perishable range
will be the SUPPLY air probe and the controlling
probe in the frozen range will be the RETURN
air probe.

Figure 3-8 Display Module


3.1.2 Display Module

5. Supply -- Yellow LED: Energized when the supply air


probe is used for control. When this LED is illuminated,
the temperature displayed in the AIR TEMPERATURE
display is the reading at the supply air probe. This LED
will flash if dehumidification or humidification is
enabled.
6. Return -- Yellow LED: Energized when the return air
probe is used for control. When this LED is illuminated,
the temperature displayed in the AIR TEMPERATURE
display is the reading at the return air probe. This LED
will flash if dehumidification or humidification is
enabled.
7. Alarm -- Red LED: Energized when there is an active
or an inactive shutdown alarm in the alarm queue.

The display module (Figure 3-8) consists of two 5--digit


displays and seven indicator lights. The indicator lights
include:
1. Cool -- White LED: Energized when the refrigerant
compressor is energized.
2. Heat -- Orange LED: Energized to indicate heater operation in the heat or defrost mode.
3. Defrost -- Orange LED: Energized when the unit is in
the defrost mode.
4. In-Range -- Green LED: Energized when the controlled temperature probe is within specified tolerance
of set point.
T-354

Degrees C/
Degrees F

Displays alternate English/Metric


scale (momentary display). When set
to degrees Fahrenheit, pressure is
displayed in psig and vacuum in /hg.
P appears after the value to indicate psig and i appears for inches
of mercury.
When set to degrees Celsius, pressure readings are in bars. b appears after the value to indicate bars.

SUPPLY RETURN

AIR TEMPERATURE/Data

Displays non-controlling probe temperature (momentary display).

3--2

1.
2.
3.
4.

Mounting Screw
Micro-Link 3
Controller
Connectors
Test Points

5.
6.

Fuses
Control Circuit Power Connection
(Location: In back of controller)
7. Software Programming Port
8. Battery Pack
Figure 3-9 Micro-Link 3 Controller
c. Provide ability to read, and if applicable, modify the
configuration software variables, operating software
function codes, and alarm code indications.

3.1.3 Controller

CAUTION

d. Provide a pre-trip step-by-step checkout of refrigeration unit performance, including proper component
operation, electronic and refrigeration control operation, heater operation, probe calibration, pressure
limiting, and current limiting settings.

Do not remove wire harnesses from controller unless you are grounded to the unit
frame with a static safe wrist strap.

e. Provide battery-powered ability to access or change


selected codes and set points without AC power
connected.

CAUTION
Unplug all controller wire harness connectors before performing arc welding on any
part of the container.

f. Provide the ability to reprogram the software through


the use of a memory card.
3.2.1 Configuration
Variables)

NOTE
Do not attempt to service the controller. Breaking the seal will void the warranty.

Software

(Configuration

The configuration software is a variable listing of the


components available for use by the operational
software. This software is factory-installed in
accordance with the equipment fitted and options listed
on the original purchase order. Changes to the
configuration software are required only when the
original software has been lost or a physical change has
been made to the unit, such as the addition or removal of
an option. A configuration variable list is provided in
Table 3-4 (page 3--13). A change to the factory-installed
configuration software is achieved via a configuration
card.

NOTE
Do not attempt to use an ML2i PC card in an
ML3 equipped unit. The PC cards are physically
different and will result in damage to the
controller.
The Micro-Link 3 controller is a single module
microprocessor as shown in Figure 3-9. It is fitted with
test points, harness connectors and a software card
programming port.

3.2.2 Operational Software (Function Codes)

3.2 CONTROLLER SOFTWARE

The operational software is the actual operation


programming of the controller, which activates or
deactivates components in accordance with current unit
operation conditions and operator selected modes of
operation.

The controller software is a custom designed program


that is subdivided into the configuration software and the
operational software. The controller software performs
the following functions:
a. Control supply or return air temperature to required
limits, provide modulated refrigeration control, electric heat control and defrost. Defrost is performed to
clear buildup of frost and ice from the coil to ensure
continuous conditioned air delivery to the load.

The programming is divided into function codes. Some


of the codes are read only while the remaining codes
may be user configured. The value of the user
configurable codes can be assigned in accordance with
user desired mode of operation. A list of the function
codes is provided in Table 3-5 (page 3--14)

b. Provide default independent readouts of set point and


supply or return air temperatures.
3--3

T-354

To access the function codes, perform the following:

below the frozen setpoint and then adjust to 24 hours


thereafter.

a. Press the CODE SELECT key, then press an arrow


key until the left window displays the desired code
number.

All defrost interval times reflect the number of


compressor runtime hours since the last defrost de-ice
cycle. The minimum defrost interval under the
automatic setting is three hours, while the maximum is
24. In frozen mode, the amount of wall-clock time
necessary to accumulate a given amount of defrost
interval time will exceed the defrost interval time by a
factor of two to three depending on the compressor
duty-cycle. Defrost interval time is not accumulated in
any mode until the defrost termination sensor reads less
than 10C (50F).

b. The right window will display the value of this item for
five seconds before returning to the normal display
mode.
c. If a longer time is desired, press the ENTER key to
extend the time to 30 seconds.
3.3 MODES OF OPERATION
The operational software responds to various inputs.
These inputs come from the temperature and pressure
sensors, the temperature set point, the settings of the
the configuration variables, and the function code
assignments. The action taken by the operational
software will change if any one of the inputs changes.
Overall interaction of the inputs is described as a mode
of operation. The modes of operation include perishable
(chill) mode and frozen mode. Descriptions of the
controller interaction and modes of operation are
provided in the following sub paragraphs.

3.3.4 Failure Action


Function code Cd29 may be operator set to allow
continued operation in the event the control sensors are
reading out of range. The factory default is full system
shutdown (refer to Table 3-5, page 3--14).
3.3.5 Generator Protection
Function codes Cd31 and Cd32 may be operator set to
control start-up sequence of multiple units and
operating current draw. The factory default allows on
demand starting of units and full current draw (refer to
Table 3-5, page 3--14).

3.3.1 Temperature Control -- Perishable Mode


With configuration variable CnF26 (Heat Lockout
Temperature) set to -10C, the perishable mode of
operation is active with set points above -10C (+14F).
With the variable set to -5C, the perishable mode is
active above -5C (+23F). Refer to Table 3-4, page
3--13.

3.3.6 Condenser Pressure Control


When configuration variable CnF14 is set to In, the
condenser pressure control logic is activated to
maintain discharge pressures above 130 psig in low
temperature ambients. The logic turns the condenser
fan on or off in accordance with the condenser pressure
transducer reading (refer to Table 3-4, page 3--13.) The
function is enabled when the following conditions are
met:

When in the perishable mode, the controller maintains


the supply air temperature at set point, the SUPPLY
indicator light will be illuminated on the display module,
and the default reading on the display window will be the
supply temperature sensor reading.
When the supply air temperature enters the in-range
temperature tolerance (as selected at function code
Cd30), the in-range light will energize.

1. The ambient sensor reading is less than or equal to


27C (80F), and
2. Voltage/Frequency ratio is less than or equal to 8.38.
When the above conditions are met, either pressures or
timers may dictate a change of state from OFF to ON or
ON to OFF. If the condenser fan is OFF, it will be
energized if saturated condensing pressure is greater
than 200psig OR if the condenser fan has been OFF for
a variable time period of up to 60 seconds depending on
the ambient temperature. As the ambient temperature
increases, the amount of time that the condenser fan is
energized will correspondingly increase towards the
maximum.

3.3.2 Evaporator Fan Operation


Opening of an evaporator fan internal protector will shut
down a unit with Normal Evaporator Fan Operation.
(CnF32 set to 2EFO). On units equipped with Single
Evaporator Fan Capability (CnF32 set to 1EFO),
additional relays are installed to allow the unit to
continue to operate on a single fan (refer to Table 3-4,
page 3--13).
3.3.3 Defrost Interval

If the condenser fan is ON, it will de-energize only if the


saturated condensing pressure is less than 130psig and
the condenser fan has been running for a minimum of
thirty seconds depending on the ambient temperature.

Controller function code Cd27 sets two modes for


defrost initiation -- either user-selected timed intervals or
automatic control. The user-selected values are 3, 6, 9,
12, or 24 hours and the factory default for the timed
interval is 12 hours (some units may be configured to
allow defrost to be disabled altogether; in this case a
user-selected value of OFF will be available). Refer to
Table 3-5.

3.3.7 Arctic Mode


With arctic mode enabled (configuration variable CnF29
set to In), there will be a 30-minute time delay at
startup if the ambient is colder than -10.0C (14F).
When the START/STOP switch is placed in the I (ON)
position, the controller will energize the compressor
crankcase heater. Operation of the heater will warm the
oil and boil off any liquid refrigerant that may be present
in the crankcase.

In perishable mode, perishable-pulldown mode, or


frozen-pulldown mode, automatic defrost starts with an
initial defrost set to three hours and then adjusts the
interval to the next defrost based on the accumulation of
ice on the evaporator coil. In this way, defrosts are
scheduled to occur only when necessary.

If Pre-Trip is initiated during the 30 minute time period,


Pre-Trip will be allowed to run normally. Once Pre-Trip is
over, the controller will revert to its normal control mode
logic (refer to Table 3-4, page 3--13).

Once setpoint has been reached in frozen operation, the


automatic selection will set the time interval to 12 hours
for the first two defrosts once the return probe is reading
T-354

3--4

1. The humidity sensor reading is above the set point.


2. The supply air temperature is less than 0.25C
above set point.
3. The heater debounce timer (three minutes) has
timed out.

3.3.8 Perishable Mode -- Conventional


The unit is capable of maintaining supply air
temperature to within +/- 0.25C (+/- 0.5 F) of set point.
Supply air temperature is controlled by positioning of the
suction modulation valve (SMV), cycling of the
compressor, and cycling of the heaters.

4. Heater termination thermostat (HTT) is closed.


If the above conditions remain true for at least one hour,
the evaporator fans will switch from high to low speed
operation. The evaporator fan speed will switch every
hour thereafter as long as all conditions are met (see
Bulb Mode section for different evaporator fan speed
options). If any condition except for item (1) becomes
false OR if the relative humidity sensed is 2% below the
dehumidification set point, the high speed evaporator
fans will be energized.

When pulling down from a temperature that is more than


5C (9F) above set point, the SMV will open to reduce
the pulldown time. However, pressure and current limit
functions may restrict the valve if either exceeds the
preset value.
The operational software is designed so the SMV will
begin to close as the set point is reached. The SMV will
continue to close and restrict refrigerant flow until the
capacity of the unit and the load are balanced.

In the dehumidification mode, power is applied to the


defrost and drain pan heaters. This added heat load
causes the controller to open the suction modulating
valve to match the increased heat load while still holding
the supply air temperature very close to the set point.

If the temperature drops below the set point, the


compressor will remain running for a few minutes. This
is to accommodate any initial undershoot which might
occur. After this time has expired and the temperature is
0.2C (0.4F) or greater below the set point, the
compressor will be turned OFF.

Opening the modulating valve reduces the temperature


of the evaporator coil surface, which increases the rate
at which water is condensed from the passing air.
Removing water from the air reduces the relative
humidity. When the relative humidity sensed is 2%
below the set point, the controller de-energizes the heat
relay. The controller will continue to cycle heating to
maintain relative humidity below the selected set point.
If the mode is terminated by a condition other than the
humidity sensor, e.g., an out-of-range or compressor
shutdown condition, the heat relay is de-energized
immediately.

If the temperature drops to 0.5C (0.9F) below set


point, the heaters will be energized. The heaters will
de-energize when the temperature rises to 0.2C
(0.4F) below the set point. The compressor will not
restart until the temperature rises to 0.2C (0.4F)
above the set point and three minutes have elapsed
since the last compressor turn off.
3.3.9 Perishable Mode -- Economy
The economy mode is an extension of the conventional
mode and is applicable to units with two speed
evaporator fan motors. The mode is activated when the
setting of function code Cd34 is ON. Economy mode is
provided for power saving purposes. Economy mode
could be utilized in the transportation of temperature
tolerant cargo or non-respiration items that do not
require high airflow for removing respiration heat. There
is no active display indicator that economy mode has
been activated. To check for economy mode, perform a
manual display of code Cd34.

Two timers are activated in the dehumidification mode


to prevent rapid cycling and consequent contactor wear.
They are:
S
S

Heater debounce timer (three minutes)


Out-of-range timer (five minutes)

The heater debounce timer is started whenever the


heater contactor status is changed. The heat contactor
remains energized (or de-energized) for at least three
minutes even if the set point criteria is satisfied.

In order to achieve economy mode, a perishable set


point must be selected prior to activation. When
economy mode is active, the evaporator fans will be
controlled as follows:

The out-of-range timer is started to maintain heater


operation during a temporary out-of-range condition. If
the supply air temperature remains outside of the user
selected in-range setting for more than five minutes, the
heaters will be de-energized to allow the system to
recover. The out-of-range timer starts as soon as the
temperature exceeds the in-range tolerance value set
by function code Cd30.
3.3.11 Perishable, Dehumidification -- Bulb Mode

At the start of each cooling or heating cycle, the


evaporator fans will be run in high speed for three
minutes. They will then be switched to low speed any
time the supply air temperature is within +/-0.25C
(0.45F) of the set point and the return air temperature is
less than or equal to the supply air temperature +3C
(5.4F). The fans will continue to run in low speed for
one hour. At the end of the hour, the evaporator fans will
switch back to high speed and the cycle will be repeated.

Bulb mode is an extension of the dehumidification


mode, which allows changes to the evaporator fan
speed and/or defrost termination set points.

3.3.10 Perishable Mode -- Dehumidification

Bulb mode is active when function code Cd35 is set to


Bulb. Once the bulb mode is activated, the user may
then change the dehumidification mode evaporator fan
operation from the default (speed alternates from low to
high each hour) to constant low or constant high speed.
This is done by toggling function code Cd36 from its
default of alt to Lo or Hi as desired. If low speed
evaporator fan operation is selected, the user has the
additional capability of selecting dehumidification set
points from 60 to 95% (instead of the normal 65 to 95%).

The dehumidification mode is provided to reduce the


humidity levels inside the container. The mode is
activated when a humidity value is set at at function
code Cd33. The display module SUPPLY LED will flash
ON and OFF every second to indicate that the
dehumidification mode is active. Once the mode is
active and the following conditions are satisfied, the
controller will activate the heat relay to begin
dehumidification.
3--5

T-354

In addition, if bulb mode is active, function code Cd37


may be set to override the previous defrost termination
thermostat settings (refer to paragraph 4.10.4) The
temperature at which the defrost termination thermostat
will be considered open may be changed [in 0.1C
(0.2F) increments] to any value between 25.6C (78F)
and 4C (39.2F). The temperature at which the defrost
termination thermostat is considered closed for interval
timer start or demand defrost is 10C (50F) for open
values from 25.6C down to a 10C setting. For open
values lower than 10C, the closed values will
decrease to the same value as the open setting.

compressor will restart. Under a condition of rapidly


changing return air temperature, the time delay may
allow the return air temperature to rise slightly above set
point temperature before the compressor can restart.
3.3.14 Frozen Mode -- Economy
In order to activate economy frozen mode operation, a
frozen set point temperature must be selected. The
economy mode is active when function code Cd34 is set
to ON. When economy mode frozen is active, the
system will perform normal frozen mode operations
except that the entire refrigeration system, excluding
the controller, will be turned off when the control
temperature is less than or equal to the set point
-2C. After an off-cycle period of 60 minutes, the unit will
turn on high speed evaporator fans for three minutes
and then check the control temperature. If the control
temperature is greater than or equal to the set point
+0.2C, the unit will restart the refrigeration system and
continue to cool until the previously mentioned off-cycle
temperature criteria are met. If the control temperature
is less than the set point +0.2C, the unit will turn off the
evaporator fans and restart another 60 minute off-cycle.

Bulb mode is terminated when:


1. Bulb mode code Cd35 is set to Nor.
2. Dehumidification code Cd33 is set to Off.
3. The user changes the set point to one
that is in the frozen range.
When bulb mode is disabled by any of the above, the
evaporator fan operation for dehumidification reverts to
alt and the DTS termination setting resets to the value
determined by controller configuration variable CnF41.
3.3.12 Temperature Control -- Frozen Mode
With configuration variable CnF26 set to -10C, the
frozen mode of operation is active with set points at or
below -10C (+14F). With the variable set to -5C, the
frozen mode is active at or below -5C (+23F).

3.4 CONTROLLER ALARMS

When in the frozen mode, the controller maintains the


return air temperature at set point, the RETURN
indicator light will be illuminated on the display module,
and the default reading on the display window will be the
return air probe reading.

Alarm display is an independent controller software


function. If an operating parameter is outside of
expected range or a component does not return the
correct signals back to the controller, an alarm is
generated. A listing of the alarms is provided in
Table 3-6, page 3--18.

When the return air temperature enters the in-range


temperature tolerance as selected at function code
Cd30, the in-range light will energize.

The alarm philosophy balances the protection of the


refrigeration unit and that of the refrigerated cargo. The
action taken when an error is detected always considers
the survival of the cargo. Rechecks are made to confirm
that an error actually exists.

3.3.13 Frozen Mode -- Conventional


Frozen range cargoes are not sensitive to minor
temperature changes. The method of temperature
control employed in this range takes advantage of this
fact to greatly improve the energy efficiency of the unit.
Temperature control in the frozen range is
accomplished by cycling the compressor on and off as
the load demand requires. The unit will operate in the
conventional frozen mode when the controller set point
is at or below the frozen range and function code CD34
is set to OFF.

Some alarms requiring compressor shutdown have


time delays before and after to try to keep the
compressor on line. An example is alarm code LO,
(low main voltage), when a voltage drop of over 25%
occurs, an indication is given on the display, but the unit
will continue to run.

If the return air temperature in the container drops 0.2C


(0.4F) below the set point, the compressor is cycled off.
When the temperature is greater than 0.2C (0.4F)
above the set point and the three minute time delay has
been met, the compressor will restart. The unit will
always operate at full capacity and the suction
modulation valve will open as allowed by current and
pressure limiting.

An alarm is indicated by flashing an alarm code on the


display panel, and for some alarms, by the alarm light
illuminating.
When an Alarm Occurs:
a. The red alarm light will illuminate for 20 series
alarms.

NOTE
On start up of the unit, SMV will reset to a known
open position. This is accomplished by assuming the valve was fully open, driving it fully
closed, resetting the percentage open to zero,
then opening to a known 21% staging position.

b. If a detectable problem is found to exist, its alarm


code will be alternately displayed with the set point on
the left display.
c. The user should scroll through the alarm list to determine what alarms exist or have existed. Alarms must
be diagnosed and corrected before the Alarm List can
be cleared.

To prevent rapid cycling of the compressor, a three


minute compressor off time must be satisfied before the
T-354

3--6

To Display Alarm Codes:

A detailed description of the pre-trip tests and test codes


is provided in Table 3-7, page 3--22. Detailed operating
instructions are provided in paragraph 4.8.

a. While in the Default Display mode, press the ALARM


LIST key. This accesses the Alarm List Display Mode,
which displays any alarms archived in the Alarm
Queue.

3.6 DataCORDER

b. The alarm queue stores up to 16 alarms in the sequence in which they occurred. The user may scroll
through the list by depressing an ARROW key.

3.6.1 Description
The Carrier Transicold DataCORDER software is
integrated into the controller and serves to eliminate the
temperature recorder and paper chart. The
DataCORDER functions may be accessed by keypad
selections and viewed on the display module. The unit is
also fitted with interrogation connections (see
Figure 3-6), which may be used with the Carrier
Transicold Data Reader to download data. A personal
computer with Carrier Transicold Data View software
may also be used to download data and configure
settings. The resulting file uses a proprietary file format
that protects it from potential tampering or altering of
data. Therefore, once downloaded, all dcx files shall be
considered secured. The DataCORDER consists of:

c. The left display will show AL##, where ## is the


alarm number sequentially in the queue.
d. The right display will show the actual alarm code.
AA## will display for an active alarm, where ## is
the alarm code. Or IA## will display for an inactive
alarm (refer to Table 3-6, page 3--18).
e. END is displayed to indicate the end of the alarm list
if any alarms are active.
f. CLEAr is displayed if all alarms are inactive. The
alarm queue may than be cleared by pressing the
ENTER key. The alarm list will clear and -- -- -- -- --
will be displayed.

S Configuration Software
S Operational Software
S Data Storage Memory
S Battery Low (Battery Pack)
S Real--Time Clock (with internal battery backup)
S Six thermistor inputs
S Interrogation Connections
S Power Supply (battery pack)

NOTE
AL26 is active when all of the sensors are not responding. Check the connector at the back of the
controller, if it is loose or unplugged, reconnect it.
Then run a pretrip test (P5) to clear AL26.
3.5 UNIT PRE-TRIP DIAGNOSTICS

The DataCORDER performs the following functions:

Pre-trip diagnostics is an independent controller


function that will suspend normal refrigeration controller
activities and provide preprogrammed test routines.
The test routines include Auto Mode testing, which
automatically preforms a pre programmed sequenced
of tests or Manual Mode testing, which allows the
operator to select and run any of the individual tests.

a. Logs data at 15, 30, 60 or 120 minute intervals and


stores two years of data (based on one hour interval).
b. Records and displays alarms on the display module.
c. Records results of pre-trip testing.
d. Records DataCORDER and temperature control
software generated data and events as follows:

CAUTION

S
S
S
S
S
S
S
S
S
S

Pre-trip inspection should not be performed with critical temperature cargoes in


the container.

CAUTION

S
S
S
S

When Pre-Trip key is pressed, dehumidification and bulb mode will be deactivated. At
the completion of Pre-Trip activity, dehumidification and bulb mode must be
reactivated.

S
S
S

Testing may be initiated by use of the keypad or via


communication, but when initiated by communication,
the controller will execute the entire battery of tests
(auto mode).

S
S
S
S
S
S
S
S

At the end of a pre-trip test, the message P, rSLts


(pretest results) will be displayed. Pressing the ENTER
key will allow the user to see the results for all subtests.
The results will be displayed as PASS or FAIL for all
the tests run to completion.
3--7

Container ID Change
Software Upgrades
Alarm Activity
Battery Low (Battery Pack)
Data Retrieval
Defrost Start and End
Dehumidification Start and End
Power Loss (w/wo battery pack)
Power Up (w/wo battery pack)
Remote Probe Temperatures in the Container
(USDA cold treatment and cargo probe recording)
Return Air Temperature
Set Point Change
Supply Air Temperature
Real Time Clock Battery (Internal Battery)
Replacement
Real--Time Clock Modification
Trip Start
ISO Trip Header (When entered via Interrogation
program)
Economy Mode Start and End
Auto 2 Pre-Trip Start and End
Bulb Mode Start
Bulb Mode changes
Bulb Mode End
USDA Trip Comment
Humidification Start and End
USDA Probe Calibration
T-354

The six thermistor inputs (supply, return, USDA #1, #2,


#3, and cargo probe) and the humidity sensor input will
be generated by the DataCORDER. An example of a
report using a standard configuration is shown in
Figure 3-10.
NOTE
The DataCORDER software uses the supply
and return recorder sensors. The temperature
control software uses the supply and return
temperature sensors.

3.6.2 DataCORDER Software


The DataCORDER Software is subdivided into the
configuration software, operational software and the
Data Memory.
a. Operational Software
The operational software reads and interprets inputs for
use by the configuration software. The inputs are
labeled Function Codes. There are 35 functions (see
Table 3-8, page 3--26), which the operator may access to
examine the current input data or stored data. To access
these codes, do the following:
1. Press the ALT. MODE & CODE SELECT keys.
2. Press an arrow key until the left window displays the
desired code number. The right window will display
the value of this item for five seconds before returning
to the normal display mode.
3. If a longer time is desired, press the ENTER key to
extend the time to 30 seconds.

b. Generic Mode
The generic recording mode allows user selection of the
network data points to be recorded. The user may select
up to a total of eight data points for recording. A list of the
data points available for recording follows. Changing the
configuration to generic and selecting which data points
to record may be done using the Carrier Transicold Data
Retrieval Program.
1. Control mode
2. Control temperature
3. Frequency
4. Humidity
5. Phase A current
6. Phase B current
7. Phase C current
8. Main voltage
9. Suction modulation valve percentage
10. Discrete outputs (See Note )
11. Discrete inputs (See Note )
12. Ambient sensor
13. Compressor suction sensor
14. Compressor discharge sensor
15. Return temperature sensor
16. Supply temperature sensor
17 Defrost temperature sensor
18. Discharge pressure transducer
19. Suction pressure transducer
20. Condenser pressure transducer

b. Configuration Software
The configuration software controls the recording and
alarm functions of the DataCORDER. Reprogramming
to the factory-installed configuration is achieved via the
same configuration card as the unit control module
software. Changes to the software may be made made
using the Data View integration device. A listing of the
configuration variables is provided in Table 3-2.
Descriptions of DataCORDER operation for each
variable setting are provided in the following
paragraphs.
3.6.3 Sensor Configuration (dCF02)
Two modes of operation may be configured, the
Standard Mode and the Generic Mode.
a. Standard Mode
In the standard mode, the user may configure the
DataCORDER to record data using one of seven
standard configurations. The seven standard
configuration variables, with their descriptions, are
listed in Table 3-3.

Note: Bitmapped -- require special handling if used

Table 3-2 DataCORDER Configuration Variables


CONFIGURATION NO.
dCF01
dCF02
dCF03
dCF04
dCF05
dCF06
dCF07
dCF08
dCF09
dCF10

T-354

TITLE
(Future Use)
Sensor Configuration
Logging Interval (Minutes)
Thermistor Format
Thermistor Sampling Type
Controlled Atmosphere/Humidity Sampling Type
Alarm Configuration USDA Sensor 1
Alarm Configuration USDA Sensor 2
Alarm Configuration USDA Sensor 3
Alarm Configuration Cargo Sensor

3--8

DEFAULT
---2
60
Short
A
A
A
A
A
A

OPTION
---2,5,6,9,54,64,94
15,30,60,120
Low, Normal
A,b,C
A,b
Auto, On, Off
Auto, On, Off
Auto, On, Off
Auto, On, Off

If a probe alarm is configured to OFF, then the alarm for


this probe is always disabled.
If a probe alarm is configured to ON, then the associated
alarm is always enabled.
If the probes are configured to AUTO, they act as a
group. This function is designed to assist users who
keep their DataCORDER configured for USDA
recording, but do not install the probes for every trip. If all
the probes are disconnected, no alarms are activated.
As soon as one of the probes is installed, then all of the
alarms are enabled and the remaining probes that are
not installed will give active alarm indications.

Table 3-3 DataCORDER Standard Configurations

Standard
Config.
2 sensors
(dCF02=2)
5 sensors
(dCF02=5)
6 sensors
(dCF02=6)
9 sensors
(dCF02=9)

Description
2 thermistor inputs(supply & return)
2 thermistor inputs(supply & return)
3 USDA thermistor inputs
2 thermistor inputs(supply & return)
3 USDA thermistor inputs
1 humidity input
Not Applicable

The DataCORDER will record the initiation of a pre-trip


test (refer to paragraph 3.5) and the results of each of
the tests included in pre-trip. The data is time-stamped
and may be extracted via the Data Retrieval program.
Refer to Table 3-9, page 3--27 for a description of thedata
stored in the DataCORDER for each corresponding
pre-trip test.

6 sensors 2 thermistor inputs(supply & return)


(dCF02=54) 3 USDA thermistor inputs
1 cargo probe (thermistor input)
2 thermistor inputs(supply & return)
7 sensors 3 USDA thermistor inputs
(dCF02=64) 1 humidity input
1 cargo probe (thermistor input)

3.6.8

DataCORDER Power-Up

The DataCORDER may be powered up in any one of


four ways:
1. Normal AC power: The DataCORDER is powered
up when the unit is turned on via the stop-start
switch.
2. Controller DC battery pack power: If a battery pack is
installed, the DataCORDER will power up for communication when an interrogation cable is plugged
into an interrogation receptacle.
3. External DC battery pack power: A 12--volt battery
pack may also be plugged into the back of the
interrogation cable, which is then plugged into an
interrogation port. No controller battery pack is
required with this method.
4. Real-time Clock demand: If the DataCORDER is
equipped with a charged battery pack and AC power
is not present, the DataCORDER will power up when
the real-time clock indicates that a data recording
should take place. When the DataCORDER is finished recording, it will power down.
During DataCORDER power-up, while using
battery-pack power, the controller will perform a
hardware voltage check on the battery. If the hardware
check passes, the Controller will energize and perform a
software battery voltage check before DataCORDER
logging. If either test fails, the real-time clock battery
power-up will be disabled until the next AC power cycle.
Further DataCORDER temperature logging will be
prohibited until that time.

2 thermistor inputs(supply & return)


3 USDA thermistor inputs
10 sensors
humidity input
(dCF02=94) 1
1 cargo probe (thermistor input)
3 CA inputs (NOT APPLICABLE)
3.6.4 Logging Interval (dCF03)
The user may configure four time intervals between
data recordings. Data is logged at exact intervals in
accordance with the real-time clock. The clock is factory
set at Greenwich Mean Time.
3.6.5 Thermistor Format (dCF04)
The user may configure the format in which the
thermistor readings are recorded. The low resolution is
a 1 byte format and the normal resolution is a 2 byte
format. The low resolution requires less memory and
records temperature in 0.25C (0.45F) increments
when in perishable mode or 0.5C (0.9F) increments
when in the frozen mode. The normal resolution records
temperature in 0.01C (0.02F) increments for the entire
range.
3.6.6 Sampling Type (dCF05 & dCF06)
Three types of data sampling are available --average,
snapshot, and USDA. When configured to average, the
average of readings taken every minute over the
recording period is recorded. When configured to
snapshot, the sensor reading at the log interval time is
recorded. When USDA is configured, the supply and
return temperature readings are averaged and the three
USDA probe readings are snapshot.

An alarm will be generated when the battery voltage


transitions from good to bad indicating that the battery
pack needs recharging. If the alarm condition persists
for more than 24 hours on continuous AC power, the
battery pack needs replacement.

3.6.7 Alarm Configuration (dCF07 -- dCF10)


The USDA and cargo probe alarms may be configured
to OFF, ON or AUTO.

3--9

T-354

Raw Data Report for ABC1234567


May 31, 2003 to Jun 04, 2003

System Configuration at the Time of Interrogation:


Interrogated On Sept 05, 2003
Extracted by DataLine Rev 1.0.0
Controller Software: 5120
Controller Serial #: 04163552
Bill of Lading #: 1
Origin:
Origin Date:
Destination:
Discharge Date:
Comment: DataLine Tool
Probe Calibration Readings: USDA1: 0.0 USDA2: 0.0 USDA3: 0.0 Cargo: 0.0
Temperature Units: Centigrade
_______________________________________________________________________________________
May 31, 2001
Setpoint: 1.66, Container :

Serial : 04189552

9 Sensors Logged at 15 Minute Interval


Sensor

Format

Resolution

Figure 3-10 Standard Configuration Report


T-354

3--10

3.6.9 Pre-Trip Data Recording

c DataLine

The DataCORDER will record the initiation of a pre-trip


test (refer to paragraph 3.5) and the results of each of
the tests included in pre-trip. The data is time-stamped
and may be extracted via the Data Retrieval program.
Refer to Table 3-9 for a description of the data stored in
the DataCORDER for each corresponding pre-trip test.

The DataLINE software for a personal computer is


supplied on both floppy disks and CD. This software
allows interrogation, configuration variable assignment,
screen view of the data, hard copy report generation,
cold treatment probe calibration, and file management.
Refer to Data Retrieval manual 62-10629 for a more
detailed explanation of the DataLINE interrogation
software. The DataLine manual may be found on the
Internet at www.container.carrier.com.

3.6.10 DataCORDER Communications


Data retrieval from the DataCORDER can be
accomplished by using one of the following;
DataReader, DataLine/DataView or a communications
interface module.
NOTE
A DataReader, DataLine/DataView, or a communications interface module display of Communication Failed is caused by faulty data
transfer between the datacorder and the data
retrieval device. Common causes include:
1.

d. Communications Interface Module


The communications interface module is a slave
module which allows communication with a master
central monitoring station. The module will respond to
communication and return information over the main
power line. With a remote monitoring unit installed, all
functions and selectable features that are accessible at
the unit may be performed at the master station.
Retrieval of all DataCORDER reports may also be
performed. Refer to the master system technical
manual for further information.

Bad cable or connection between


DataCORDER and data retrieval device.

2. PC communication port(s) unavailable or


misassigned.
3. Chart Recorder Fuse (FCR) blown.

3.6.11 USDA Cold Treatment


Sustained cold temperature has been employed as an
effective postharvest method for the control of
Mediterranean and certain other tropical fruit flies.
Exposing infested fruit to temperatures of 2.2C (36F)
or below for specific periods results in the mortality of
the various stages of this group of insects.
In response to the demand to replace fumigation with
this environmentally sound process, Carrier has
integrated Cold Treatment capability into its
microprocessor system. These units have the ability to
maintain supply air temperature within one-quarter
degree Celsius of setpoint and record minute changes
in product temperature within the DataCORDER
memory, thus meeting USDA criteria. Information on
USDA is provided in the following subparagraphs

Communication identification for the models


covered herein may be obtained on the Container Products Group Information Center by
authorized Carrier Transicold Service Centers.
a. DataReader
The Carrier Transicold Data Reader (see Figure 3-11) is
a simple to operate hand held device designed to extract
data from the DataCORDER and then upload it to a
personal computer. The Data Reader has the ability to
store multiple data files. Refer to Data Retrieval manual
62-10629 for a more detailed explanation of the
DataReader.

a. USDA Recording
A special type of recording is used for USDA cold
treatment purposes. Cold treatment recording requires
three remote temperature probes be placed at
prescribed locations in the cargo. Provision is made to
connect these probes to the DataCORDER via
receptacles located at the rear left-hand side of the unit.
Four or five receptacles are provided. The four three-pin
receptacles are for the probes and fifth, five-pin,
receptacle is the rear connection for the the Interrogator.
The probe receptacles are sized to accept plugs with
tricam coupling locking devices. A label on the back
panel of the unit shows which receptacle is used for
each probe.
The standard DataCORDER report displays the supply
and return air temperatures. The cold treatment report
displays USDA #1, #2, #3, and the supply and return air
temperatures. Cold treatment recording is backed up by
a battery so recording can continue if AC power is lost.
b. USDA Message Trip Comment
A special feature is incorporated which allows the user
to enter a USDA (or other) message at the head of a
data report. The maximum message length is 78
characters. Only one message will be recorded per day.

DataReader

Figure 3-11 Data Reader


b. DataBANKTM Card
The DataBANKTM card is a PCMCIA card that
interfaces with the controller through the programming
slot and can download data at a much faster rate when
compared to the PC or DataReader. Files downloaded
to the DataBANK card files are accessible through an
Omni PC Card Drive. The files can then be viewed using
the DataLine software.
3--11

T-354

3.6.12 USDA Cold Treatment Procedure


The following is a summary of the steps required to
initiate a USDA Cold Treatment:
a. Calibrate the three USDA probes by ice bathing the
probes and performing the calibration function with
the DataReader or a personal computer. This calibration procedure determines the probe offsets and
stores them in the controller for use in generating the
cold treatment report. Refer to the Data Retrieval
manual 62-10629 for more details.
b. Pre-cool the container to the treatment temperature
or below.
c. Install the DataCORDER module battery pack (if not
already installed).
d. Place the three probes. The probes are placed into
the pulp of the fruit (at the locations defined in the following table) as the product is loaded.
Place in pulp of the product located next
to the return air intake.
Place in pulp of the product five feet
from the end of the load for 40--foot conor three feet from the end of the
Sensor 2 tainers,
load for 20--foot containers. This probe
should be placed in a center carton at
one-half the height of the load.
Place in pulp of product five feet from
the end of the load for 40--foot containor three feet from the end of the load
Sensor 3 ers
for 20--foot containers. This probe
should be placed in a carton at a side
wall at one-half the height of the load.
e. To initiate USDA Recording, connect the personal
computer and perform the configuration as follows:
1. Fill in ISO header information
2. Add a trip comment if desired
3. Configure for five probes (s, r, P1, P2, P3)
4. Configure for one--hour logging interval
5. Set the sensor configuration at USDA
6. Configure for two byte memory storage format
7. Perform a trip start
Sensor 1

T-354

3.6.13 DataCORDER Alarms


Alarm display is an independent DataCORDER
function. If an operating parameter is outside of the
expected range or a component does not return the
correct signals back to the DataCORDER an alarm is
generated. The DataCORDER contains a buffer of up to
eight alarms. A listing of the DataCORDER alarms is
provided in Table 3-10, page 3--28. Refer to paragraph
3.6.7 for configuration information.
To display alarm codes:
a. While in the Default Display mode, press the ALT.
MODE & ALARM LIST keys. This accesses the DataCORDER Alarm List Display Mode, which displays
any alarms stored in the Alarm Queue.
b. To scroll to the end of the alarm list, press the UP ARROW. Depressing the DOWN ARROW key will scroll
the list backward.
c. The left display will show AL# where # is the alarms
number in the queue. The right display will show
AA##, if the alarm is active, where ## is the alarm
number. IA##, will show if the alarm is inactive
d. END is displayed to indicate the end of the alarm list
if any alarms are active. CLEAr is displayed if all the
alarms in the list are inactive.
e. If no alarms are active, the Alarm Queue may be
cleared. The exception to this rule is the DataCORDER Alarm Queue Full alarm (AL91), which does not
have to be inactive in order to clear the alarm list. To
clear the alarm list:
1. Press the ALT. MODE & ALARM LIST keys.
2. Press the UP/DOWN ARROW key until CLEAr is
displayed.
3. Press the ENTER key. The alarm list will clear and
-- -- -- -- -- will be displayed.
4. Press the ALARM LIST key. AL will show on the left
display and -- -- -- -- -- on the right display when
there are no alarms in the list.
5. Upon clearing of the Alarm Queue, the Alarm light will
be turned off.

3--12

Table 3-4 Controller Configuration Variables


CONFIGURATION
NUMBER

TITLE

DEFAULT

OPTION

CnF01
Bypass Valve Enable
In
Out
CnF02
Evaporator Fan Speed
dS (Dual)
SS (Single)
CnF03
Control Sensors
FOUr
duAL
CnF04
Dehumidification Mode
On
OFF
CnF05
Reserved for future use
---------n/a
CnF06
Condenser Fan Speed Select
OFF (Single)
On (Variable)
CnF07
Unit Selection, 20FT/ 40FT/45FT
40ft
20ft,45
CnF08
Single Phase/Three Phase Motor
1Ph
3Ph
CnF09
Refrigerant Selection
r134a
r12, r22, bLEnd
CnF10
Two Speed Compressor Logic
Out (Single)
In (Dual)
CnF11
Defrost Off Selection
noOFF
OFF
CnF12
TXV/Solenoid Quench Valve
Out (TXV)
In (Solenoid)
CnF13
Unloader
Out
In
CnF14
Condenser Pressure Control (CPC)
In
Out
CnF15
Discharge Temperature Sensor
Out
In
CnF16
DataCORDER Present
On (Yes)
OFF (No)
CnF17
Discharge Pressure Sensor
Out (No)
In (Yes)
CnF18
Heater
Old (Low Watt)
nEW (High Watt)
CnF19
Controlled Atmosphere
Out (No)
In (Yes)
CnF20
Suction Pressure Sensor
Out (No)
In (Yes)
CnF21
Autotransformer
Out
In
CnF22
Economy Mode Option
OFF
Standard, Full
CnF23
Defrost Interval Timer Save Option
noSAv
SAv
CnF24
Advanced Pre-Trip Enhanced Test Series Option
Auto
Auto2, Auto 3
CnF25
Pre-Trip Test Points/Results Recording Option
rSLtS
dAtA
CnF26
Heat Lockout Change Option
Set to -10C
Set to -5C
CnF27
Suction Temperature Display Option
Out
In
CnF28
Bulb Mode Option
NOr
bULb
CnF29
Arctic Mode
Out
In
CnF30
Compressor Size
41 CFM
37 CFM
CnF31
Probe Check Option
Standard
SPEC
CnF32
Single Evaporator Fan Option
2EF0
1EF0
CnF33
Snap Freeze Option
OFF
SnAP
CnF34
Degree Celsius Lockout Option
bOth
F
CnF35
Humidification Mode
OFF
On
CnF36
SMV Type
1 (standard)
2, 3 (stepper)
CnF37
Electronic Temperature Recorder
rEtUR
SUPPL, bOth
CnF38
Quench Bypass Valve
Out
In
CnF39
Expanded Current Limit Range
Out
In
CnF40
Demand Defrost
Out
In
CnF41
Lower DTT Setting
Out
In
CnF42
Auto Pre-trip Start
Out
In
CnF47
Fresh Air Vent Position Sensor
OFF
UPP, LOW
CnF48
CFS Override
OFF
On
CnF49
Datacorder Configuration Restore
OFF
On
CnF50
Enhanced Bulb Mode Selection
OFF
Bulb, dEHUM
CnF51
Timed Defrost Disable
0
0-out, 1-in
Note: Configuration numbers not listed are not used in this application. These items may appear when loading
configuration software to the controller but changes will not be recognized by the controller programming.
3--13

T-354

Table 3-5 Controller Function Codes (Sheet 1 of 4)


Code
No.

TITLE

DESCRIPTION

Note: If the function is not applicable, the display will read -- -- -- -- --

Display Only Functions


Suction Modulation
Cd01 Valve Opening (%)

Displays the SMV percent open. The right display reads 100% when the valve
is fully open and 0% when the valve is fully closed. The valve will usually be at
21% on start up of the unit except in very high ambient temperatures.

Cd02 Quench Valve

Displays state of the solenoid quench valve, open or closed.

Cd03 Not Applicable

Not used

Cd04 Line Current,


Phase A
Cd05 Line Current,
Phase B
Cd06 Line Current,
Phase C
Cd07 Main Power Voltage

The current sensor measures current on two legs. The third unmeasured leg is
calculated based on a current algorithm. The current measured is used for control and diagnostic purposes.
For control processing, the highest of the Phase A and B current values is
used for current limiting purposes. For diagnostic processing, the current draws
are used to monitor component energization.
Whenever a heater or a motor is turned ON or OFF, the current draw increase/
reduction for that activity is measured. The current draw is then tested to determine if it falls within the expected range of values for the component.
Failure of this test will result in a pre-trip failure or a control alarm indication.
The main supply voltage is displayed.

The value of the main power frequency is displayed in Hertz. The frequency
Cd08 Main Power Frequency displayed will be halved if either fuse F1 or F2 is bad (alarm code AL21).
Cd09 Ambient Temperature

The ambient sensor reading is displayed.

Compressor Suction
Cd10 Temperature

Compressor suction temperature sensor reading is displayed.

Compressor Discharge
Cd11 Temperature
Compressor discharge temperature sensor reading is displayed.
Compressor Suction
Cd12 Pressure

Compressor suction pressure transducer reading is displayed.

Cd13 Condenser Pressure

Condenser pressure transducer reading is displayed.

Compressor
Cd14 Discharge Pressure

Compressor discharge pressure transducer reading is displayed.

Unloader Valve (OnCd15 Off)

Not used in this application

Compressor Motor
Cd16 Hour Meter / Switch
On Time

Records total hours of compressor run time. Total hours are recorded in increments of 10 hours (i.e., 3000 hours is displayed as 300).
/ Press Enter to display Start Switch ON time.

Cd17 Relative Humidity (%)

Humidity sensor reading is displayed. This code displays the relative humidity,
as a percent value.

Cd18 Software Revision #

The software revision number is displayed.

Cd19 Battery Check

This code checks the Controller/DataCORDER battery pack. While the test is
running, btest will flash on the right display, followed by the result. PASS will
be displayed for battery voltages greater than 7.0 volts. FAIL will be displayed
for battery voltages between 4.5 and 7.0 volts, and -- -- -- -- -- will be displayed for battery voltages less than 4.5 volts. After the result is displayed for
four seconds, btest will again be displayed, and the user may continue to
scroll through the various codes.

Cd20 Config/Model #

This code indicates the dash number of the model for which the Controller is
configured (i.e., if the unit is a 69NT40-541-100, the display will show 41100).

Humidity Water Pump/


Cd21 Atomizer Status

This code displays the status of the humidity water pump (-- -- -- -- -- , forward,
reverse or off). If not configured, the mode is permanently deactivated and will
display -- -- -- -- -- .

Cd22 Compressor Speed

The status of the compressor is displayed (high, low or off).

Cd23 Evaporator Fan

Displays the current evaporator fan state (high, low or off).

T-354

3--14

Table 3-5 Controller Function Codes (Sheet 2 of 4)


Code
No.

TITLE

Controlled
Cd24 Atmosphere State
Compressor Run
Cd25 Time Remaining
Until Defrost
Defrost Temperature
Cd26 Sensor Reading

DESCRIPTION
Not used in this application
This code displays the time remaining until the unit goes into defrost (in tenths of
an hour). This value is based on the actual accumulated compressor running
time.
Defrost temperature sensor reading is displayed.

Configurable Functions
NOTE
Function codes Cd27 through Cd37 are user-selectable functions. The operator can change the value of
these functions to meet the operational needs of the container.
There are two modes for defrost initiation, either user-selected timed intervals or
automatic control. The user-selected values are (OFF), 3, 6, 9, 12, or 24 hours
while the factory default is 12 hours.
Automatic defrost starts with an initial defrost at three hours and then adjusts the
interval to the next defrost based on the accumulation of ice on the evaporator
coil. Following a start-up or after termination of a defrost, the time will not begin
counting down until the defrost temperature sensor (DTS) reading falls below set
point. If the reading of DTS rises above set point any time during the timer count
down, the interval is reset and the countdown begins over.
Defrost Interval
Cd27 (Hours or Automatic) If DTS fails, alarm code AL60 is activated and control switches over to the the
return temperature sensor. The controller will act in the same manner as with the
DTS except the return temperature sensor reading will be used.
Defrost Interval Timer Value (Configuration variable CnF23):
If the software is configured to SAv (save) for this option, then the value of the
defrost interval timer will be saved at power down and restored at power up. This
option prevents short power interruptions from resetting an almost expired defrost
interval, and possibly delaying a needed defrost cycle.
NOTE
The defrost interval timer counts only during compressor run time.
Temperature Units
Cd28 (Degrees C or
Degrees F)

Failure Action
Cd29 (Mode)

Cd30 In-Range Tolerance

This code determines the temperature units (C or F) which will be used for all
temperature displays. The user selects C or F by selecting function code Cd28
and pushing the ENTER key. The factory default value is Celsius units.
NOTE
This function code will display --- --- --- --- --- if Configuration Variable CnF34 is
set to F.
If all of the control sensors are out of range (alarm code AL26) or there is a probe
circuit calibration failure (alarm code AL27), the unit will enter the shutdown state
defined by this setting. The user selects one of four possible actions as follows:
A -- Full Cooling (stepper motor SMV at maximum allowed opening)
B -- Partial Cooling (stepper motor SMV 11% open)
C -- Evaporator Fan Only
D -- Full System Shutdown -- Factory Default
The in-range tolerance will determine the band of temperatures around the set
point which will be designated as in-range. If the control temperature is in-range,
the in-range light will be illuminated. There are four possible values:
1 = +/- 0.5C (+/-0.9F)
2 = +/- 1.0C (+/-1.8F)
3 = +/- 1.5C (+/-2.7F)
4 = +/- 2.0C (+/-3.6F) -- Factory Default

3--15

T-354

Table 3-5 Controller Function Codes (Sheet 3 of 4)


Code
No.

TITLE

Stagger Start Offset


Cd31 Time (Seconds)

Current Limit
Cd32 (Amperes)

Perishable Mode
Dehumidification /
Cd33 Humidification
Control (% RH)

DESCRIPTION
The stagger start offset time is the amount of time that the unit will delay at startup, thus allowing multiple units to stagger their control initiation when all units are
powered up together. The eight possible offset values are:
0 (Factory Default), 3, 6, 9, 12, 15, 18 or 21 seconds
The current limit is the maximum current draw allowed on any phase at any time.
Limiting the units current reduces the load on the main power supply. This is accomplished by reducing the SMV position until current draw is reduced to the set
point. When desirable, the limit can be lowered. Note, however, that capacity is
also reduced. The five values for 460VAC operation are:
15, 17, 19, 21 (Factory Default), 23
Relative humidity set point is available only on units configured for dehumidification. When the mode is activated, the control probe LED flashes on and off every
second to alert the user.
If not configured, the mode is permanently deactivated and -- -- -- -- -- will display. The value can be set to OFF. TEST, or a range of 65 to 95% relative humidity in increments of 1%. [If bulb mode is active (code Cd35) and Lo speed
evaporator motors are selected (code Cd36) then set point ranges from 60 to
95%].
When TEST is selected or test set point is entered, the heat LED should illuminate, indicating that dehumidification mode is activated. After a period of five minutes in the TEST mode has elapsed, the previously selected mode is reinstated.
NOTE
If humidification (CnF35) is enabled, then humidification will be enabled and
dehumidification locked out at set points of 75% and above. At set points below 75%, dehumidification will be enabled and humidification locked out.

Economy Mode
Cd34 (On--Off)

Economy mode is a user selectable mode of operation provided for power saving
purposes.

Cd35 Bulb Mode

Bulb mode is a user selectable mode of operation that is an extension of dehumidification control (Cd33). If dehumidification is set to Off, code Cd35 will display Nor and the user will be unable to change it.
After a dehumidification set point has been selected and entered for code Cd33,
the user may then change code Cd35 to bulb. After bulb has been selected and
entered, the user may then utilize function codes Cd36 and Cd37 to make the
desired changes.

Evaporator Speed
Cd36 Select

Defrost Termination
Cd37 Temperature Setting
(Bulb Mode)

T-354

This code is enabled only if in the dehumidification mode (code Cd33) and bulb
mode (Cd35) has been set to bulb. If these conditions are not met, alt will be
displayed (indicating that the evaporator fans will alternate their speed) and the
display cannot be changed.
If a dehumidification set point has been selected along with bulb mode then alt
may be selected for alternating speed, Lo for low speed evaporator fan only, or
Hi for high speed evaporator fan only.
If a setting other than alt has been selected and bulb mode is deactivated in any
manner, then selection reverts back to alt.
This code, as with function code Cd36, is used in conjunction with bulb mode and
dehumidification. If bulb mode is active, this code allows the user to change the
defrost termination thermostat settings. If bulb mode is deactivated, the DTS setting returns to the default.

3--16

Table 3-5 Controller Function Codes (Sheet 4 of 4)


Code
No.

TITLE

DESCRIPTION

Supply Recorder
Cd38 Sensor (SRS)

Code Cd38 will display the current secondary supply temperature sensor reading
for units configured for four probes. If the unit is configured with a DataCORDER,
Cd38 will display -- -- -- -- -- . If the DataCORDER suffers a failure, (AL55) Cd38
will display the supply recorder sensor reading.

Return Recorder
Cd39 Sensor (RRS)

Code Cd39 will display the current secondary return temperature sensor reading
for units configured for four probes. If the unit is configured with a DataCORDER,
Cd39 will display -- -- -- -- -- . If the DataCORDER suffers a failure, (AL55) Cd39
will display the return recorder sensor reading.

Container
Cd40 Identification
Number
Cd41
Cd42 Not Applicable

Code Cd40 is configured at commissioning to read a valid container identification


number. The reading will not display alpha characters, only the numeric portion of
the number will display.
Scroll Units Only

Code Cd43 is a user selectable mode of operation that allows the opening and
closing of a mechanical air vent door via a stepper motor. These selection modes
are as follows:
OFF -- Air makeup vent will remain closed.
User -- Allows for manual selection of the setting.
Delay --The opening of the door is based on selected time, return temperature
and flow rate (percent opened).
Cd43 AutoFresh Mode
gASLM -- The opening is based percent open and CO2 and O2 selectable limits
(LM). This selection is only active if the unit has a CO2 sensor.
TEST / CAL (CO2 sensor option units only) -- The door will fully open and close
to allow the user to inspect its operation. If CAL is selected, the controller will
zero calibrate the CO2 sensor input.
If the unit is not configured with AutoFresh, the CD43 will display --------
Code Cd44 will display CO2 and O2 concentrations and limits. If the unit is not
configured for AutoFresh or a CO2 sensor is not installed, CD44 will display
Cd44 AutoFresh Values
--------
Code Cd45 will display whenever the control detects movement via the sensor
Vent Position Sensor unless alarm 50 is active. The code will display for 30 seconds, then time out and
Cd45 (VPS)
return to the normal display mode. If the Temperature unit is degrees F, the VPS
units will be CFM and in degrees C the VPS units shall be CMH.
Cd46 Not Used
Variable Economy
Cd47 Temperature Setting

-The variable temperature degrees C or degrees F setting is used with economy


mode. Function code is -------- when unit is not configured for economy mode.

Dehumidification/
Cd48 Bulb Mode
Parameter Selection
Days Since Last
Cd49 Successful Pre-trip

Code CD48 is used to determine limits (between 60%-95%) for dehumidification


and/or bulb mode (CNF28) when active.
Code CD49 will display the number of days since the last successful Auto1,
Auto2 or Auto3 pre-trip sequence.

3--17

T-354

Table 3-6 Controller Alarm Indications (Sheet 1 of 4)


Code
No.

TITLE

DESCRIPTION

Manual Defrost
AL05 Switch Failure

Alarm 05 is triggered if the controller detects continuous Manual Defrost Switch


action for five minutes or more. The alarm will only trigger off when the unit is
power cycled.

Keypad or Harness
AL06 Failure

Alarm 06 is triggered if the controller detects continuous keypad button activity


for five minutes or more. The alarm will only trigger off when the unit is power
cycled.

Alarm 07 is triggered if the VPS is reading greater than 0 CMH based on the
Fresh Air Vent Open function code display value and a frozen set point is active.
If AL 50 is active, AL 07 will not be generated.
AL07 with Frozen Set
The alarm will go inactive if the VPS reading transitions to 0 CMH, the set point
Point
transitions to the perishable range, or an AL50 is active.
AL10 CO2 Sensor Failure

Alarm 10 is triggered when the CO2 sensor voltage is operating outside of the 0.9
v to 4.7 v range, or if the sensor is out of range. This is a display alarm and has
no associated failure action.

Evaporator Motor 1
AL11 IP Trip

Alarm 11 is applicable to units with Single Evaporator Fan Capability (CnF32 set
to 1EFO) only. The alarm is triggered if the evaporator fan motor #1 internal protector opens. If the alarm is active, probe check is deactivated.

Evaporator Motor 2
AL12 IP Trip

Alarm 12 is applicable to units with Single Evaporator Fan Capability (CnF32 set
to 1EFO) only. The alarm is triggered if the evaporator fan motor #2 internal protector opens. If the alarm is active, probe check is deactivated.

AL15 Loss of Cool

Alarm 15 is activated when SMV is greater than 15%, unit is in economized or


standard operating modes and Return -- Supply Temperature Difference is less
than 0.5C after 4 minutes of compressor run time. The alarm triggers failure action C ( evaporator fan only) or D ( all machinery off ) if in perishable mode and
failure action D ( all machinery off ) if a frozen set point has been selected.. The
alarm remains active until the unit is power cycled.

Control Circuit Fuse


AL20 Open (24 vac)

Alarm 20 is triggered by control power fuse (F3A, F3B) opening and will cause
the software shutdown of all control units. This alarm will remain active until the
fuse is replaced.

Micro Circuit Fuse


AL21 Open (18 vac)

Alarm 21 is triggered by one of the fuses (F1/F2) being opened on 18 volts AC


power supply to the Controller. The suction modulation valve (SMV) will be
opened and current limiting is halted. Temperature control will be maintained by
cycling the compressor.

Evaporator Fan
AL22 Motor Safety

Alarm 22 responds to the evaporator motor internal protectors. On units with Normal Evaporator Fan Operation (CnF32 set to 2EFO) the alarm is triggered by
opening of either internal protector. It will disable all control units until the motor
protector resets. On units with Single Evaporator Fan Capability (CnF32 set to
1EFO), the alarm is triggered by opening of both internal protectors. It will disable
all control units until a motor protector resets.

Compressor Motor
AL24 Safety

Alarm 24 is triggered by the opening of the compressor motor internal protector.


This alarm will disable all control units except for the evaporator fans and will remain active until the motor protector resets. This alarm triggers the failure action
code set by Function Code Cd29.

Condenser Fan
AL25 Motor Safety

Alarm 25 is triggered by the opening of the condenser motor internal protector


and will disable all control units except for the evaporator fans. This alarm will
remain active until the motor protector resets. This alarm is deactivated if the unit
is operating on water cooled condensing.

All Supply and Return temperature


AL26 Control Sensors
Failure

Alarm 26 is triggered if the Controller determines that all of the control sensors
are out-of-range. This can occur for box temperatures outside the range of -50C
to +70C (-58F to +158F). This alarm triggers the failure action code set by
Function Code Cd29.

Probe Circuit
AL27 Calibration Failure

The Controller has a built-in Analog to Digital (A-D) converter, used to convert
analog readings (i.e. temperature sensors, current sensors, etc.) to digital readings. The Controller continuously performs calibration tests on the A-D converter.
If the A-D converter fails to calibrate for 30 consecutive seconds, this alarm is
activated.This alarm will be inactivated as soon as the A-D converter calibrates.

T-354

3--18

Table 3--6 Controller Alarm Indications (Sheet 2 of 4)


Code
No.

TITLE

AL29 AutoFresh Failure

Fresh Air Position


AL50 Sensor (VPS)

AL51 Alarm List Failure

AL52 Alarm List Full

AL53 Battery Pack Failure

Primary Supply
AL54 Temperature Sensor
Failure (STS)

DESCRIPTION
Alarm 29 is triggered if CO2 or O2 level is outside of the limit range and the vent
position is at 100% for longer than 90 minutes. Alarm LED will be activated and
user intervention is required. The alarm is triggered off when atmospheric conditions are within limit settings.
Alarm 50 is activated whenever the sensor is outside the valid range. There is a
five minute adjustment period where the user can change the vent position without generating an alarm event. The sensor requires five minutes of no movement
to confirm stability. If the vent position changes at any point beyond the five minute adjustment period, the sensor will generate an alarm event. The alarm is triggered off when the unit power cycles and the sensor is within valid range.
During start-up diagnostics, the EEPROM is examined to determine validity of its
contents. This is done by testing the set point and the alarm list. If the contents
are invalid, Alarm 51 is activated.
During control processing, any operation involving alarm list activity that results in
an error will cause Alarm 51 to be activated. Alarm 51 is a display only alarm
and is not written into the alarm list.
Pressing the ENTER key when CLEAr is displayed will result in an attempt to
clear the alarm list. If that action is successful (all alarms are inactive), Alarm 51
will be reset.
Alarm 52 is activated whenever the alarm list is determined to be full; at start-up
or after recording an alarm in the list. Alarm 52 is displayed, but is not recorded in
the alarm list. This alarm can be reset by clearing the alarm list. This can be done
only if all alarms written in the list are inactive.
Alarm 53 is caused by the battery pack charge being too low to provide sufficient
power for battery-backed recording. Renew replaceable batteries.
If this alarm occurs on start up, allow a unit fitted with rechargeable batteries to
operate for up to 24 hours to charge rechargeable batteries sufficiently to deactivate the alarm
Alarm 54 is activated by an invalid primary supply temperature sensor reading
that is sensed outside the range of -50 to +70C (-58F to +158F) or if the probe
check logic has determined there is a fault with this sensor.
If Alarm 54 is activated and the primary supply is the control sensor, the secondary supply sensor will be used for control if the unit is so equipped. If the unit
does not have a secondary supply temperature sensor, and AL54 is activated,
the primary return sensor reading, minus 2C will be used for control.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm

Primary Return
AL56 Temperature Sensor
Failure (RTS)

Alarm 56 is activated by an invalid primary return temperature sensor reading


that is outside the range of -50 to +70C (-58F to +158F). If Alarm 56 is activated and the primary return is the control sensor, the secondary return sensor
will be used for control if the unit is so equipped. If the unit is not equipped with a
secondary return temperature sensor or it fails, the primary supply sensor will be
used for control.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm.

Ambient
AL57 Temperature Sensor
Failure

Alarm 57 is triggered by an ambient temperature reading outside the valid range


from -50 to +70C (-58F to +158F).

Compressor High
AL58 Pressure Safety

Alarm 58 is triggered when the compressor high discharge pressure safety switch
remains open for at least one minute. This alarm will remain active until the pressure switch resets, at which time the compressor will restart.
Alarm 59 is triggered by the opening of the heat termination thermostat and will
result in the disabling of the heater. This alarm will remain active until the thermostat resets.

Heat Termination
AL59 Thermostat

3--19

T-354

Table 3--6 Controller Alarm Indications (Sheet 3 of 4)


Code
No.

TITLE

DESCRIPTION

Alarm 60 is an indication of a probable failure of the defrost temperature sensor


(DTS). It is triggered by the opening of the heat termination thermostat (HTT) or
the failure of the DTS to go above set point within two hours of defrost initiation.
Defrost Temperature After one-half hour with a frozen range set point, or one-half hour of continuous
compressor run time, if the return air falls below 7C (45F), the Controller
AL60 Sensor Failure
checks to ensure the DTS reading has dropped to 10C or below.
If not, a DTS failure alarm is given and the defrost mode is operated using the
return temperature sensor. The defrost mode will be terminated after one hour by
the Controller.
Alarm 61 is triggered by detection of improper amperage resulting from heater
activation or deactivation. Each phase of the power source is checked for proper
AL61 Heaters Failure
amperage.This alarm is a display alarm with no resulting failure action, and will
be reset by a proper amp draw of the heater.
Alarm 62 is triggered by improper current draw increase (or decrease) resulting
from compressor turn on (or off). The compressor is expected to draw a minimum of 2 amps; failure to do so will activate the alarm.This is a display alarm
with no associated failure action and will be reset by a proper amp draw of the
compressor.
Alarm 63 is triggered by the current limiting system. If the compressor is ON and
current limiting procedures cannot maintain a current level below the user selected limit, the current limit alarm is activated.
AL63 Current Over Limit
This alarm is a display alarm and is inactivated by power cycling the unit, changing the current limit via the code select Cd32, or if the suction modulation valve
(SMV) is open beyond the controller desired point.
Discharge
Alarm 64 is triggered if the discharge temperature sensed is greater than 135C
(275F) for three continuous minutes, if it exceeds 149C (300F), or if the senAL64 Temperature
Over Limit
sor is out of range. This is a display alarm and has no associated failure action.
Alarm
65 is triggered by a compressor discharge transducer reading outside the
Discharge Pressure
valid range of 73.20cm Hg (30in Hg) to 32.34Kg/cm2 (460psig). This is a display
AL65 Transducer Failure
alarm and has no associated failure action.
Alarm 66 is triggered by a suction pressure transducer reading outside the valid
Suction Pressure
range of 73.20cm Hg (30in Hg) to 32.34Kg/cm2 (460psig). This is a display alarm
AL66 Transducer Failure
and has no associated failure action.
Alarm 67 is triggered by a humidity sensor reading outside the valid range of 0%
Humidity Sensor
to 100% relative humidity. If alarm AL67 is triggered when the dehumidification
AL67 Failure
mode is activated, then the dehumidification mode will be deactivated.
68 is triggered by a condenser pressure transducer reading outside the
Condenser Pressure Alarm
valid range of 73.20cm Hg (30in Hg) to 32.34Kg/cm2 (460psig). This is a display
AL68 Transducer Failure
alarm and has no associated failure action.
Suction Temperature Alarm 69 is triggered by a suction temperature sensor reading outside the valid
range of -60C (-76F) to 150C (302F). This is a display alarm and has no
AL69 Sensor Failure
associated failure action.
NOTE
If the controller is configured for four probes without a DataCORDER, the DataCORDER alarms AL70 and
AL71 will be processed as Controller alarms AL70 and AL71.
Compressor Circuit
AL62 Failure

T-354

3--20

Table 3--6 Controller Alarm Indications (Sheet 4 of 4)


Code
No.

TITLE

DESCRIPTION
The controller performs self-check routines. If an internal failure occurs, an ERR
alarm will appear on the display. This is an indication the controller needs to be
replaced.
ERROR
DESCRIPTION
Indicates that the controller working memory has
ERR 0 -- RAM failure
failed.
EER 1 -- Program Memory
Indicates a problem with the controller program.
failure
EER 2 -- Watchdog
The controller program has entered a mode whereby
time-out
the controller program has stopped executing.
EER 3 -- N/A
EER 4 -- N/A

N/A
N/A
The Controllers Analog to Digital (A-D) converter
has failed.
Internal program/update failure.
Internal version/firmware incompatible.

EER 5 -- A-D failure


ERR
#

Internal
Microprocessor
Failure

Entr
StPt

Enter Setpoint
(Press Arrow &
Enter)
Low Main Voltage
(Function Codes
Cd27-38 disabled
and NO alarm
stored.)

LO

EER 6 -- IO Board failure


EER 7 -- Controller failure
EER 8 -- DataCorder
Internal DataCorder memory failure.
failure
EER -- 9 Controller failure Internal controller memory failure.
In the event that a failure occurs and the display cannot be updated, the status
LED will indicate the appropriate EER code using Morse code as shown below.
E R R 0 to 9ERR0 = . .--. .--. ---------ERR1 = . .--. .--. . -------ERR2 = . .--. .--. . . -----ERR3 = . .--. .--. . . . ---ERR4 = . .--. .--. . . . . -ERR5 = . .--. .--. . . . . .
ERR6 = . .--. .--. -- . . . .
ERR7 = . .--. .--. ---- . . .
ERR8 = . .--. .--. ------ . .
ERR9 = . .--. .--. -------- .
The controller is prompting the operator to enter a set point.

This message will be alternately displayed with the set point whenever the supply
voltage is less than 75% of its proper value.

3--21

T-354

Table 3-7 Controller Pre-Trip Test Codes (Sheet 1 of 4)


NOTE
Auto or Auto1 menu includes: P, P1, P2, P3, P4, P5, P6 & rSLts. Auto2 menu includes P, P1, P2, P3,
P4, P5, P6, P7, P8, P9, P10 & rSLts.Auto3 menu includes P, P1, P2, P3, P4, P5, P6, P7, P8 & rSLts
All lights and display segments will be energized for five seconds at the start of
the pre-trip. Since the unit cannot recognize lights and display failures, there are
P
Pre-Trip Initiated
no test codes or results associated with this phase of pre-trip.
Setup: Heater must start in the OFF condition, and then be turned on. A current
P1-0
Heaters Turned On draw test is done after 15 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
Setup: Heater must start in the ON condition, and then be turned off. A current
P1-1
Heaters Turned Off draw test is done after 10 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
Requirements: Water pressure switch (WP) input must be closed.
Setup: Condenser fan is turned ON, a current draw test is done after
P2-0
Condenser Fan On 15 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
P2-1

Condenser Fan Off

P3

Low Speed
Evaporator Fans

P3-0

Low Speed
Evaporator Fan
Motors On

P3-1

Low Speed
Evaporator Fan
Motors Off

Setup: Condenser fan is turned OFF, a current draw test is done after
10 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
Requirements: The unit must be equipped with a low speed evaporator fan, as
determined by the Evaporator Fan speed select configuration variable.
NOTE
If the unit is configured for single evaporator fan operation, Pre-Trip tests
P3-0, P3-1, P4-0 and P4-1 will fail immediately if Controller alarm codes
AL11 or AL12 are active at the start of testing.
Setup: The high speed evaporator fans will be turned on for 10 seconds, then off
for two seconds, then the low speed evaporator fans are turned on. A current
draw test is done after 60 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range specified. Fails if AL11 or AL12 activates during test.
Setup: The low speed Evaporator Fan is turned off, a current draw test is done
after 10 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range specified. Fails if AL11 or AL12 activates during test.

P4-0

High Speed
Evaporator Fan
Motors On

Setup: The high speed Evaporator Fan is turned on, a current draw test is done
after 60 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range specified. Fails if AL11 or AL12 activates during test.

P4-1

High Speed
Evaporator Fan
Motors Off

Setup: The high speed Evaporator Fan is turned off, a current draw test is done
after 10 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range specified. Fails if AL11 or AL12 activates during test.

P5-0

Supply/Return
Probe Test

P5-1

Supply Probe Test

T-354

Setup: The High Speed Evaporator Fan is turned on and run for eight minutes,
with all other outputs de-energized.
Pass/Fail Criteria: A temperature comparison is made between the return and
supply probes.
NOTE
If this test fails, P5-0 and FAIL will be displayed. If both Probe tests (this test
and the PRIMARY/ SECONDARY) pass, the display will read P5 PASS.
Requirements: For units equipped with secondary supply probe only.
Pass/Fail Criteria: The temperature difference between primary and secondary
probe (supply) is compared.
NOTE
If this test fails, P5-1 and FAIL will be displayed. If both Probe tests (this
and the SUPPLY/ RETURN TEST) pass, because of the multiple tests, the
display will read P 5 PASS.

3--22

Table 3-7 Controller Pre-Trip Test Codes (Sheet 2 of 4)


Code
No.

TITLE

DESCRIPTION
Requirements: For units equipped with secondary return probe only.
Pass/Fail Criteria: The temperature difference between primary and secondary
probe (return) is compared.
NOTES

P5-2

Return Probe Test

1. If this test fails, P5-2 and FAIL will be displayed. If both Probe tests
(this test and the SUPPLY/ RETURN) pass, because of the multiple
tests, the display will read P 5, PASS.

2. The results of Pre-Trip tests 5-0, 5-1 and 5-2 will be used to activate or

clear control probe alarms.


Requirements: Test P5--9 must pass before this test is run.
Test is skipped if controller is not configured for the humidity sensor and the
Humidity Sensor
is less than 0.20 volts.
P5-10 Controller Configura- voltage
tion Verification Test Pass/Fail Criteria: Passes if controller configuration has the humidity sensor installed. Fails if controller is not configured for humidity sensor and the voltage is
greater than 0.20 volts.
Humidity Sensor
Requirements: Test P5--10 must pass before this test is run.
P5-11 Installation Verifica- Pass/Fail Criteria: Passes if voltage is greater than 0.20 volts for the humidity
tion Test
sensor. Fails if voltage is less than 0.20 volts for the humidity sensor.
Requirements: Test P5--11 must pass before this test is run.
Humidity Sensor
P5-12 Range Check Test Pass/Fail Criteria: Passes if the voltage for the humidity sensor is between 0.66
volts and 4 volts. Fails if voltage is outside of the 0.66 volt to 4 volt range.
P-6
Not Applicable
Setup: A current draw test is performed before the compressor is started. The
compressor is started. SMV is opened and another current draw test is performed.
P6-0
Compressor On
Pass/Fail Criteria: Passes if the change in compressor current draw is within the
specified range.
P6-H & P6L
Not Applicable
Setup: The compressor and fans continue to run from the previous test. The
quench valve (if configured) will operate as in normal control mode. The SMV is
closed to 0% open, current and condenser pressure readings are taken. The
SMV is opened to 50% with continuous current and condenser pressure readSuction Modulation ings taken to establish maximum values. The SMV is returned to 0% open and
Valve (Open and
P6-2
final readings are taken.
Closed)
Pass/Fail Criteria: Passes if the calculated difference in current at the 50%
open position are above a specified value before and after opening of the SMV,
OR the calculated difference in condenser pressure at the 50% open position are
above a specified value before and after opening of the SMV
P6-3

Quench Valve Test

P6-4
P6-5

Not Applicable
Not Applicable

Setup: The compressor suction temperature is measured with the Quench valve
closed. The Quench valve is energized and the suction temperature drop is
checked.
Pass/Fail Criteria: Passes if suction temperature is within the valid range.
Not Used
Not Used

3--23

T-354

Table 3-7 Temperature Controller Pre-Trip Test Codes (Sheet 3 of 4)


Code
No.

TITLE

DESCRIPTION

NOTE
P7-0 & P8 are included with the Auto2 & Auto 3 only. P9-0 through P10 are included with Auto2 only
Setup: When the unit is running, the condenser fan is de-energized, and a
15 minute timer is started. The right display shows discharge pressure if the unit
is equipped with a discharge pressure transducer (DPT). If no DPT is installed,
the condenser pressure transducer (CPT) reading will be displayed.
Pass/Fail Criteria: The test fails if high pressure switch fails to open in
15 minutes.
Note, this test is skipped if the unit does NOT have:
A compressor discharge sensor (CPDS).
A discharge pressure transducer (DPT).
Condenser pressure transducer (CPT).
In addition, this test is skipped if:
The sensed ambient temperature is less than 7C (45F).
The return air temperature is less than -17.8C (0F).

P7-0

High Pressure
Switch Closed

The water pressure switch (WP) is open, indicating that the unit is operating
with a water-cooled condenser.
Pass/Fail Criteria: Under conditions of the above NOTE; the test immediately
fails if the following inputs are sensed to be invalid:
Compressor discharge sensor (CPDS).
Discharge pressure transducer (DPT).
Condenser pressure transducer (CPT).
OR, if any one of the following inputs are sensed to be invalid:
Return temperature sensor (RTS).
Ambient sensor (AMBS).
In addition, the test will fail if:
The high pressure switch (HPS) fails to open within 15 minutes.
The discharge temperature exceeds 138C (280F).
The discharge temperature is less than or equal to ambient temperature
plus 5C (9F).

P7-1

P8-0

T-354

High Pressure
Switch Open

Perishable Mode
Heat Test

The condenser pressure transducer (CPT) or discharge pressure transducer (DPT) pressure exceeds 27.42kg/cm2 (390psig).
Requirement: Test P7-0 must pass for this test to execute. Setup: The condenser fan is started and a 60 second timer is started.
Pass/Fail Criteria: Passes the test if the high pressure switch (HPS) closes
within the 60--second time limit, otherwise, it fails.
Setup: If the container temperature is below 15.6C (60F), the set point is
changed to 15.6C, and a 60--minute timer is started. The left display will read
P8-0. The control will then heat the container until 15.6C is reached. If the
container temperature is above 15.6C at the start of the test, then the test proceeds immediately to test P8-1 and the left display will change to P8-1.
Pass/Fail Criteria: The test fails if the 180--minute timer expires before the control temperature reaches set point. The display will read P8-0, FAIL.

3--24

Table 3-7 Controller Pre-Trip Test Codes (Sheet 4 of 4)


Code
No.

P8-1

P8-2

P9-0

P10-0

P10-1

P10-2

TITLE

DESCRIPTION

Perishable Mode
Pull Down Test

Requirements: Control temperature must be at least 15.6C (60F).


Setup: The set point is changed to 0C (32F), and a 180--minute timer is
started. The left display will read P8-1, the right display will show the supply air
temperature. The unit will then start to pull down the temperature to the 0C set
point.
Pass/Fail Criteria: The test passes if the container temperature reaches set
point before the 180--minute timer expires.

Perishable Mode
Maintain
Temperature Test

Requirements: Test P8-1 must pass for this test to execute.


Setup: The left display will read P8-2, and the right display will show the supply
air temperature. A 60--minute timer is started. The unit will be required to maintain the 0C temperature to within +/-0.5C (0.9F) of set point until a DataCORDER recording is executed.
The recorder supply probe temperature running total (and its associated readings counter) will be zeroed out for the remainder of the recording period at the
start of this test, so that the actual value recorded in the DataCORDER will be an
average of only this tests results.
Once a recording interval is complete, the average recorder supply temperature
will be recorded in the DataCORDER, as well as stored in memory for use in
applying the test pass/fail criteria.
Pass/Fail Criteria: If the recorded temperature is within +/-0.5C. of set point
from test start to DataCORDER recording, the test passes. If the average temperature is outside of the tolerance range at the recording, the test fails.

Defrost Test

Setup: The defrost temperature sensor (DTS) reading will be displayed on the
left display. The right display will show the supply air temperature. The unit will
run FULL COOL for 30 minutes maximum until the DTT is considered closed.
Once the DTT is considered closed, the unit simulates defrost by running the
heaters for up to two hours, or until the DTT is considered open.
Pass/Fail Criteria: The test fails if: the DTT is not considered closed after the
30 minutes of full cooling, HTT opens when DTT is considered closed or if return
air temperature rises above 248C (120F).

Frozen Mode
Setup Test

Setup: After completion of the defrost test, the testing proceeds directly to test
P10-1 if the container temperature is above 7C (45F). If the container temperature is below 7C, a 180--minute timer will be started, the set point will be set to
7C and the control will be placed in normal heat. The left display will read
P10-0 and the unit will continue in operation until the temperature is raised to
set point.
Pass/Fail Criteria: If the temperature does not reach set point (less -0.3C or
6.7F) before the timer times out display will read P100, FAIL. The test will
not auto-repeat.

Frozen Mode
(Pull Down) Test

Setup: When the container temperature is greater than or equal to the 7.2C
(45F) set point which was set in the Frozen Mode Setup Test, the left display
will read P10-1 and the right display will show the return air temperature. The
set point will then be changed to -17.7C (0F). The unit will then have a maximum of three hours to pull the container temperature down to the -17.7C set
point.
Pass/Fail Criteria: If this occurs within the three hour time limit, the test passes.
If pulldown is not completed within the three hour time, the test fails.

Frozen Mode
Maintain
Temperature Test

Setup: After the unit has successfully completed frozen pulldown test, the left
display will read P10-2 and the right display will show return air temperature.
The unit will then be required to maintain -17.7C (0F) temperature within
+/-0.5C (0.9F) of set point until a DataCORDER recording is executed.
The recorder return probe temperature running total (and its associated counter)
will be zeroed for the remainder of the recording period at the start of this test, so
that the actual recorded value will be an average of only this tests results.
Once the recording interval is complete, the average return temperature will be
recorded in the DataCORDER, and stored in memory for use in applying the test
pass/fail criteria.
Pass/Fail Criteria: If the recorded temperature is within +/-0.5C of set point
from test start to DataCORDER recording, the test passes. If temperature is outside of the tolerance range at the DataCORDER recording, the test fails.
3--25

T-354

Table 3-8 DataCORDER Function Code Assignments


NOTE
Inapplicable Functions Display -- -- -- -- --
To Access: Press ALT. MODE key
Code
No.

TITLE

DESCRIPTION

dC1

Recorder Supply
Temperature

Current reading of the supply recorder sensor.

dC2

Recorder Return
Temperature

Current reading of the return recorder sensor.

dC3-5

USDA 1,2,3
Temperatures

Current readings of the three USDA probes.

dC6-13

Network Data
Points 1-8

Current values of the network data points (as configured). Data point 1 (Code
6) is generally the humidity sensor and its value is obtained from the Controller once every minute.

dC14

Cargo Probe 4
Temperature

Current reading of the cargo probe #4.

dC15-19 Future Expansion


Temperature
dC20-24 Sensors 1-5
Calibration
dC25
Future Expansion
dC26,27

S/N, Left 4, Right 4

dC28

Minimum Days Left

dC29

Days Stored

dC30
dC31
dC32
dC33
dC34
dC35

T-354

These codes are for future expansion, and are not in use at this time.
Current calibration offset values for each of the five probes: supply, return,
USDA #1, #2, and #3. These values are entered via the interrogation program.
This code is for future expansion, and is not in use at this time.
The DataCORDER serial number consists of eight characters. Function code
dC26 contains the first four characters. Function code dC27 contains the last
four characters. (This serial number is the same as the Controller serial
number)
An approximation of the number of logging days remaining until the DataCORDER starts to overwrite the existing data.

Number of days of data that are currently stored in the DataCORDER.


The date when a Trip Start was initiated by the user. In addition, if the system
Date of last Trip start goes without power for seven continuous days or longer, a trip start will automatically be generated on the next AC power up.
Shows the current status of the optional battery pack.
PASS: Battery pack is fully charged.
Battery Test
FAIL: Battery pack voltage is low.
Time: Hour, Minute
Current time on the real-time clock (RTC) in the DataCORDER.
Date: Month, Day
Current date (month and day) on the RTC in the DataCORDER.
Date: Year
Current year on the RTC in the DataCORDER.
Cargo Probe 4
Current calibration value for the Cargo Probe. This value is an input via the
Calibration
interrogation program.

3--26

Table 3-9 DataCORDER Pre-Trip Result Records


Test
No.
1-0
1-1

Heater On
Heater Off

2-0

Condenser Fan On

2-1

6-4
6-5

Condenser Fan Off


Low Speed Evaporator Fan
On
Low Speed Evaporator Fan
Off
High Speed Evaporator Fan
On
High Speed Evaporator Fan
Off
Supply/Return Probe Test
Secondary Supply Probe Test
Secondary Return Probe Test
Compressor On
Not Applicable
Suction Modulation Valve
Open and Closed
Not Applicable
Not Applicable

7-0

High Pressure Switch Closed

7-1

High Pressure Switch Open

8-0
8-1

Perishable Heat
Perishable Pull Down

8-2

Perishable Maintain

9-0

Defrost Test

10-0
10-1

Frozen Mode Set-up


Frozen Mode Pull Down

10-2

Frozen Mode Maintain

3-0
3-1
4-0
4-1
5-0
5-1
5-2
6-0
6-1
6-2

TITLE

DATA
Pass/Fail/Skip Result, Change in current for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Water pressure switch (WPS) -- Open/Closed,
Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, STS, RTS, SRS and RRS
Pass/Fail/Skip Result
Pass/Fail/Skip Result
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Not Used
Pass/Fail/Skip Result, Is current or pressure limit in effect (Y,N)
Not Used
Not Used
Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens
Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes
Pass/Fail/Skip Result, STS, time it takes to heat to 16C (60F)
Pass/Fail/Skip Result, STS, time it takes to pull down to 0C (32F)
Pass/Fail/Skip Result, Averaged DataCORDER supply temperature
(SRS) over last recording interval.
Pass/Fail/Skip Result, DTS reading at end of test, line voltage, line
frequency, time in defrost.
Pass/Fail/Skip Result, STS, time unit is in heat.
Pass/Fail/Skip Result, STS, time to pull down unit to -17.8C (0F).
Pass/Fail/Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.

3--27

T-354

Table 3-10 DataCORDER Alarm Indications


Code No.

TITLE

To Access: Press ALT. MODE key


DESCRIPTION
The supply recorder sensor reading is outside of the range of -50 to 70C
(-58F to +158F) or, the probe check logic has determined there is a fault
with this sensor.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm.

dAL70

Recorder Supply
Temperature Out of
Range

dAL71

Recorder Return
Temperature Out of
Range

The return recorder sensor reading is outside of the range of -50 to 70C
(-58F to +158F) or, the probe check logic has determined there is a fault
with this sensor.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm.

dAL72-74

USDA Temperatures
1, 2, 3 Out of Range

The USDA probe temperature reading is sensed outside of -50 to 70C


(-58 to 158F) range.

dAL75

Cargo Probe 4 Out of


Range

The cargo probe temperature reading is outside of -50 to 70C


(-58 to 158F) range.

dAL76, 77

Future Expansion

dAL78-85

Network Data Point


1 -- 8 Out of Range

dAL86

RTC Battery Low

These alarms are for future expansion, and are not in use at this time.
The network data point is outside of its specified range. The DataCORDER is configured by default to record the supply and return recorder sensors.
The DataCORDER may be configured to record up to 8 additional network
data points. An alarm number (AL78 to AL85) is assigned to each configured point.
When an alarm occurs, the DataCORDER must be interrogated to identify
the data point assigned.
When a humidity sensor is installed, it is usually assigned to AL78.
The Real Time Clock (RTC) backup battery is too low to adequately
maintain the RTC reading.

dAL87

RTC Failure

An invalid date or time has been detected. This situation may be corrected
by changing the Real Time Clock (RTC) to a valid value using DataLINE.

dAL88

DataCORDER
EEPROM Failure

A write of critical DataCORDER information to the EEPROM has failed.

dAL89

Flash Memory Error

An error has been detected in the process of writing daily data to the nonvolatile FLASH memory.

dAL90
dAL91

Future Expansion
Alarm List Full

This alarm is for future expansion, and is not in use at this time.
The DataCORDER alarm queue is determined to be full (eight alarms).

T-354

3--28

SECTION 4
OPERATION
4.1 INSPECTION (Before Starting)

4.2.1 Connection To 380/460 VAC Power


1. Make sure start-stop switch (ST, on control panel)
and circuit breaker (CB-1, in the control box) are in
position O (OFF).

WARNING
Beware of unannounced starting of the
evaporator and condenser fans. The unit
may cycle the fans and compressor unexpectedly as control requirements dictate.

2. Plug the 460VAC (yellow) cable into a de-energized


380/460VAC, 3-phase power source. Energize the
power source. Place circuit breaker (CB-1) in position I (ON). Close and secure control box door.

a. If container is empty, check inside for the following:

4.2.2 Connection to190/230 VAC Power

1. Check channels or T bar floor for cleanliness.


Channels must be free of debris for proper air
circulation.
2. Check container panels, insulation, and door
seals for damage. Make permanent or temporary
repairs.
3. Visually check evaporator fan motor mounting
bolts for proper securement (refer to paragraph
6.16).
4. Check for dirt or grease on evaporator fan or fan
deck and clean if necessary.
5. Check evaporator coil for cleanliness or
obstructions. Wash with fresh water.
6. Check defrost drain pans and lines for
obstructions and clear if necessary. Wash with
fresh water.
7. Check panels on refrigeration unit for loose bolts
and condition of panels. Make sure T.I.R. devices
are in place on access panels.
b. Check condenser coil for cleanliness. Wash with
fresh water.
c. Open control box door. Check for loose electrical connections or hardware.
d. Check color of moisture-liquid indicator.
e. Check oil level in compressor sight glass.

An autotransformer (Figure 4-1) is required to allow


operation on nominal 230 volt power. It is fitted with a
230VAC cable and a receptacle to accept the standard
460VAC power plug. The 230 volt cable is black in color
while the 460 volt cable is yellow. The transformer may
also be equipped with a circuit breaker (CB-2). The
transformer is a step-up transformer that will provide
380/460VAC, 3-phase, 50/60 hertz power to the unit
when the 230VAC power cable is connected to a
190/230VAC, 3-phase power source.
1. Make sure that the start-stop switch (ST, on control
panel) and circuit breakers CB-1 (in the control box
and CB-2 (on the transformer) are in position O
(OFF). Plug in and lock the 460VAC power plug at the
receptacle on the transformer.
2. Plug the 230VAC (black) cable into a de-energized
190/230VAC, 3-phase power source. Energize the
power source. Set circuit breakers CB-1 and CB2 to
position I (ON). Close and secure control box door.

4.2 CONNECT POWER


1

WARNING
Do not attempt to remove power plug(s) before turning OFF start-stop switch (ST), unit
circuit breaker(s) and external power
source.

WARNING

1. Dual Voltage Modular Autotransformer


2. Circuit Breaker (CB-2) 230V
3. 460VAC Power Receptacle

Make sure the power plugs are clean and


dry before connecting to any power receptacle.

Figure 4-1 Autotransformer

4--1

T-354

Data Recording of the Sensor Position -- The position of


the vent will be recorded in the DataCorder whenever
the unit is running under AC power and any of the
following:
S Trip start
S On every power cycle
S Midnight
S Manual change greater than 5CMH (3CFM) and
remains in that position for four minutes

4.3 ADJUST FRESH AIR MAKEUP VENT


The purpose of the fresh air makeup vent is to provide
ventilation for commodities that require fresh air
circulation. The vent must be closed when transporting
frozen foods.
Air exchange depends on static pressure differential,
which will vary depending on the container and how the
container is loaded.
Units may be equipped with a vent position sensor
(VPS). The VPS determines the position of the fresh air
vent and sends data to the controller display.
4.3.1 Upper Fresh Air Makeup Vent
Two slots and a stop are designed into the disc for air
flow adjustments. The first slot allows for a 0 to 30% air
flow and the second slot allows for a 30 to 100% air flow.
To adjust the percentage of air flow, loosen the wing nut
and rotate the disc until the desired percentage of air
flow matches with the arrow. Tighten the wing nut.

NOTE
The user has four minutes to make necessary
adjustments to the vent setting. This time
begins on the initial movement of the sensor.
The vent can be moved to any position within
the four minutes.
On completion of the first four minutes, the vent
is required to remain stable for the next four
minutes. If vent position changes are detected
during the four minutes stability period, an
alarm will be generated. This provides the user
with the ability to change the vent setting
without generating multiple events in the
DataCorder.

To clear the gap between the slots, loosen the wing nut
until the disc clears the stop. Figure 4-2 gives air
exchange values for an empty container. Higher values
can be expected for a fully loaded container.
69NT40 FRESH AIR MAKEUP
AIR
FLOW
(CMH)
240

ZERO EXTERNAL STATIC 50HZ

T-BAR

4.4 CONNECT WATER-COOLED CONDENSER

T-BAR

The water-cooled condenser is used when cooling


water is available and heating the surrounding air is
objectionable, such as in a ships hold. If water-cooled
operation is desired, connect in accordance with the
following:

1-!/2

210

2-%/8

180

T-BAR

150

a. Connect the water supply line to the inlet side of condenser and the discharge line to the outlet side of the
condenser (see Figure 2-5).

120

b. Maintain a flow rate of 11 to 26 liters per minute (3 to 7


gallons per minute). The water pressure switch will
open to de-energize the condenser fan relay. The
condenser fan motor will stop until the water pressure
switch closes.

90
60
30
0

NOTE
If controller configuration variable CNF48 is activated the condenser fan motor will activate if
the HPS opens twice in less than seven minutes. Power cycling the unit resets the counter.

0 10 20 30 40 50 60 70 80 90 100
PERCENT OPEN
For 60Hz operation multiply curves by 1.2

Figure 4-2 Make Up Air Flow Chart


4.3.2 Fresh Air Position Sensor
The VPS allows the user to determine position of the
fresh air vent via function code 45. This function code is
accessible via the code select key.
The vent position will display for 30 seconds whenever
motion corresponding to 5CMH (3CFM) or greater is
detected. It will scroll in intervals of 5CMH (3CFM).
Scrolling to Function Code 45 will display the Fresh Air
Vent Position.

T--354

c. To shift to air-cooled condenser operation, disconnect the water supply and the discharge line to the
water-cooled condenser.
The refrigeration unit will shift to air-cooled condenser
operation when the water pressure switch closes or if
the controller configuration variable CNF48 is activated, the condenser fan motor will activate if the
HPS opens twice in less than seven minutes. Power
cycling the unit resets the count.

4--2

4.5 CONNECT REMOTE MONITORING


RECEPTACLE
If remote monitoring is required, connect remote
monitor plug at unit receptacle (see item 9, Figure 2-6).
When the remote monitor plug is connected to the
remote monitoring receptacle, the following remote
circuits are energized:
CIRCUIT
Sockets B to A
Sockets C to A
Sockets D to A

DataCORDER
a. Check, and if required, set the DataCORDER Configuration in accordance with desired recording parameter (refer to paragraph 3.6.3).
b. Enter a Trip Start. To enter a Trip Start, do the
following:

FUNCTION
Energizes remote cool light
Energizes remote defrost light
Energizes remote in-range light

1. Depress the ALT MODE key and scroll to Code


dC30.
2. Depress and hold the ENTER key for five
seconds.

4.6 STARTING AND STOPPING INSTRUCTIONS

WARNING

3. The Trip Start event will be entered in the


DataCORDER.

Make sure that the unit circuit breaker(s)


(CB-1 & CB-2) and the START-STOP switch
(ST) are in the O (OFF) position before
connecting to any electrical power source.

4.7.4 Complete Inspection


Allow unit to run for five minutes to stabilize conditions
and perform a pre-trip diagnosis in accordance with the
following paragraph.

4.6.1 Starting the Unit


1. With power properly applied, the fresh air damper set,
and if required, the water-cooled condenser connected (refer to paragraphs 4.2, 4.3, & 4.4), place the
START-STOP switch to I (ON).
2. Continue with Start Up Inspection (refer to paragraph
4.7).
4.6.2 Stopping the Unit
To stop the unit, place the START-STOP switch in
position O (OFF).

4.8 PRE-TRIP DIAGNOSIS

CAUTION
Pre-trip inspection should not be performed with critical temperature cargoes in
the container.

4.7 START-UP INSPECTION


4.7.1 Physical Inspection
a. Check rotation of condenser and evaporator fans.
b. Check compressor oil level (refer to paragraph 6.8.6).
4.7.2 Check Controller Function Codes
Check and, if required, reset controller Function Codes
(Cd27 through Cd39) in accordance with desired
operating parameters (refer to paragraph 3.2.2).
4.7.3 Start Temperature Recorder
a. Open recorder door and wind mechanical clock or
check battery of electronic recorder. Be sure key is returned to storage clip of mechanical recorder.
b. Lift stylus (pen) by pulling the marking tip outward until the stylus arm snaps into its retracted position.

CAUTION
When Pre-Trip key is pressed, dehumidification and bulb mode will be deactivated.
At the completion of Pre-Trip activity, dehumidification and bulb mode must be
reactivated.
Pre-Trip diagnosis provides automatic testing of the unit
components using internal measurements and
comparison logic. The program will provide a PASS or
FAIL display to indicate test results.

c. Install new chart making sure chart is under the four


corner tabs. Lower the stylus until it has made contact
with the chart. Close and secure door.

4--3

T-354

a. Press the PRE-TRIP key. This accesses a test selection menu.


b. TO RUN AN AUTOMATIC TEST: Scroll through the
selections by pressing the UP ARROW or DOWN
ARROW keys to display AUTO, AUTO 2 or AUTO 3
as desired and then press the ENTER key.
1.The unit will execute the series of tests without
any need for direct user interface. These tests
vary in length, depending on the component under test.

The testing begins with access to a pre-trip selection


menu. The user may have the option of selecting one of
three automatic tests (depending on software revision
installed).
These tests will automatically perform a series of
individual pre-trip tests. The user may also scroll down
to select any of the individual tests. The contents of the
menus are as follows:
PRE-TRIP SELECTION MENU
Auto or Auto 1 Auto 2

Auto 3

P1, P2, P3, P4,


P5, P6, rSLts

P, P1, P2, P3,


P4, P5, P6, P7,
P8, rSLts

P, P1, P2, P3,


P4, P5, P6, P7,
P8, P9, P10,
rSLts

2.While tests are running, P#-# will appear on the


left display, where the #s indicate the test number and sub-test. The right display will show a
countdown time in minutes and seconds, indicating the amount of time remaining in the test.

CAUTION

A detailed description of the pre-trip test codes is listed


in Table 3-7, page 3--22. If no selection is made, the
pre-trip menu selection process will terminate
automatically. However, dehumidification and bulb
mode must be reactivated manually if required.

When a failure occurs during automatic


testing the unit will suspend operation
awaiting operator intervention.
When an automatic test fails, it will be repeated
once . A repeated test failure will cause FAIL to
be shown on the right display, with the corresponding test number to the left.
The user may then press the DOWN ARROW to
repeat the test, the UP ARROW to skip to the
next test or the PRE-TRIP key to terminate testing. The unit will wait indefinitely until the user
manually enters a command.

Scrolling down to the rSLts code and pressing ENTER


will allow the user to scroll through the results of the last
pre-trip testing run. If no pre-testing has been run (or an
individual test has not been run) since the unit was
powered up, -------- will be displayed.
To start a pre-trip test, do the following:
NOTE
1. Prior to starting tests, verify that unit
voltage (Function Code Cd 07) is within
tolerance and unit amperage draw
(Function Codes Cd04, Cd05, Cd06) is
within expected limits. Otherwise, tests
may fail incorrectly.

CAUTION
When Pre-Trip test Auto 2 runs to
completion without being interrupted,
the unit will terminate pre-trip and
display Auto 2 end. The unit will
suspend operation until the user
depresses the ENTER key!

2. All alarms must be rectified and cleared


before starting tests.

3.. Pre-trip diagnosis may also be initiated via

communications. The operation is the


same as for the key pad initiation described
below except that should a test fail, the
pre-trip mode will automatically terminate.
When initiated via communications, a test
may not be interrupted with an arrow key,
but the pre-trip mode can be terminated
with the PRE-TRIP key.

T--354

When an Auto test runs to completion without a


failure, the unit will exit the pre-trip mode and return to normal control operation. If configuration
variable CnF42 is set to IN, a datacorder trip start
will be entered. If CnF42 is set to OUT, the trip start
will not be entered. However, dehumidification
and bulb mode must be reactivated manually if
required.

4--4

c.TO RUN AN INDIVIDUAL TEST: Scroll through the


selections by pressing the UP ARROW or DOWN
ARROW keys to display an individual test code.
Pressing ENTER when the desired test code is
displayed.

4.9.2 Probe Check


If the DataCORDER is off or in alarm mode, the
controller will revert to a four probe configuration, which
includes the DataCORDER supply and return air probes
as the secondary controller probes. The controller
continuously performs probe diagnosis testing, which
compares the four probes. If the probe diagnosis result
indicates a probe problem exists, the controller will
perform a probe check to identify the probe(s) in error.
a. Probe Diagnostic Logic -- Standard
If the probe check option (controller configuration code
CnF31) is configured for standard, the criteria used for
comparison between the primary and secondary
control probes is:
1C (1.8F) for perishable set points or 2C (3.6F)
for frozen set points.
If 25 or more of 30 readings taken within a 30--minute
period are outside of the limit, then a defrost is initiated and a probe check is performed.
In this configuration, a probe check will be run as a part
of every normal (time initiated) defrost.
b. Probe Diagnostic Logic -- Special
If the probe check option is configured for special, the
above criteria are applicable. A defrost with probe check
will be initiated if 25 of 30 readings or 10 consecutive
readings are outside of the limits
In this configuration, a probe check will not be run as a
part of a normal defrost, but only as a part of a defrost
initiated due to a diagnostic reading outside of the limits.
c. The 30--minute timer will be reset at each of the following conditions:
S At every power up
S At the end of every defrost
S After every diagnostic check that does not fall outside of the limits as outlined above.
d. Probe Check:
A defrost cycle probe check is accomplished by
energizing just the evaporator motors for eight minutes
at the end of the normal defrost. At the end of the eight
minute period, the probes will be compared to a set of
predetermined limits. The defrost indicator will remain
on throughout this period.
Any probe(s) determined to be outside the limits will
cause the appropriate alarm code(s) to be displayed to
identify the probe(s) that needs to be replaced. The P5
Pre-Trip test must be run to inactivate alarms.

1.Individually selected tests, other than the LED/


Display test, will perform the operations necessary to verify the operation of the component. At
the conclusion, PASS or FAIL will be displayed.
This message will remain displayed for up to three
minutes, during which time a user may select
another test. If the three minute time period expires, the unit will terminate pre-trip and return to
control mode operation.
2.While the tests are being executed, the user may
terminate the pre-trip diagnostics by pressing and
holding the PRE-TRIP key.
The unit will then resume normal operation. If the
user decides to terminate a test but remain at the
test selection menu, the user may press the UP
ARROW key. When this is done all test outputs will
be de-energized and the test selection menu will
be displayed.
3.Throughout the duration of any pre-trip test except
the P-7 high pressure switch tests, the current and
pressure limiting processes are active.
d. Pre-Trip Test Results
At the end of the pre-trip test selection menu, the
message P, rSLts (pre-trip results) will be displayed.
Pressing the ENTER key will allow the user to see the
results for all subtests (i.e., 1-0, 1-1, etc).
The results will be displayed as PASS or FAIL for all
the tests run to completion since power up. If a test has
not been run since power up, -- -- -- -- -- will be
displayed.
Once all pre-test activity is completed, dehumidification
and bulb mode must be reactivated manually if required.
4.9 OBSERVE UNIT OPERATION
4.9.1 Crankcase Heater
When the crankcase heater is installed, it will be
operational whenever the compressor is off and there is
power to the unit. The heater is connected to a set of
normally closed auxiliary contacts on the compressor
contactor.

4--5

T-354

FALLING
TEMPERATURE

+2.5C (4.5F)

RISING
TEMPERATURE

+1.5C (2.7F)
MODULATING
COOLING

+1C (1.8F)

MODULATING
COOLING

+0.5C (0.9F)
+0.20C

AIR CIRCULATION

SET POINT
-0.20C
-0.5C (0.9F)

AIR CIRCULATION

-1C (1.8F)
HEATING

-1.5C (2.7F)

HEATING

Figure 4-3 Controller Operation -- Perishable Mode

FALLING
TEMPERATURE

RISING
TEMPERATURE
+1.5C (2.7F)

COOLING

+1C (1.8F)

COOLING

+0.5C (0.9F)
+0.20C
SET POINT
-0.20C
-0.5C (0.9F)
AIR
CIRCULATION
ONLY

-1C (1.8F)

AIR
CIRCULATION
ONLY

-1.5C (2.7F)

Figure 4-4 Controller Operation -- Frozen Mode

T--354

4--6

from the supply air and multiplying the result by the


time reading. The result is negative number.
e. When the calculation reaches -250, contacts TC and
TN are opened to de-energize compressor and condenser fan motors. The cool light is also de-energized.
f. The evaporator fan motors continue to run to circulate
air throughout the container. The in-range light remains illuminated as long as the supply air is within
tolerance of set point.
g. When the supply air temperature increases to 0.2C
(0.4F) above set point and the three minute off time
has elapsed, relays TC and TN are energizes to restart the compressor and condenser fan motors. The
cool light is also illuminated.

4.10 SEQUENCE OF OPERATION


General operation sequences for cooling, heating, and
defrost are provided in the following subparagraphs.
Schematic representation of controller action are
provided in Figure 4-3 and Figure 4-4. Refer to Section
3 for detailed descriptions of special events and timers
that are incorporated by the controller in specific modes
of operation.
4.10.1 Sequence of Operation -- Perishable Mode
Cooling
NOTE
In the conventional Perishable Mode of
Operation, the evaporator motors run in high
speed. In the economy Perishable Mode, the
fan speed is varied.

4.10.2 Sequence of Operation -- Perishable Mode


Heating

NOTE
In low temperature ambients, the condenser
fan will be cycled by the controller to maintain
proper condensing pressure.

NOTE
The unit will heat only when in the Perishable
Mode, relay TH is electronically locked out
when in the Frozen Mode.

a. With supply air temperature above set point and decreasing, the unit will be cooling with the condenser
fan motor (CF), compressor motor (CH), evaporator
fan motors (EF) energized, and the COOL light illuminated (see Figure 4-5).
ENERGIZED
DE--ENERGIZED
FOR FULL DIAGRAM AND
LEGEND, SEE SECTION 7

a. If the air temperature decreases 0.5C (0.9F) below


set point, the system enters the heating mode (see
Figure 4-3). The controller closes contacts TH (see
Figure 4-6) to allow power flow through the heat termination thermostat (HTT) to energize the heaters
(HR). The HEAT light is also illuminated. The evaporator fans continue to run to circulate air throughout
the container.
b. When the temperature rises to 0.2C (0.4F) below
set point, contact TH opens to de-energize the heaters. The HEAT light is also de-energized. The evaporator fans continue to run to circulate air throughout
the container.
c. A safety heater termination thermostat (HTT), attached to an evaporator coil support, will open the
heating circuit if overheating occurs.

CONTROL TRANSFORMER

POWER TO
CONTROLLER

SIGNAL TO
CONTROLLER

ENERGIZED
DE-ENERGIZED
FOR FULL DIAGRAM AND
LEGEND, SEE SECTION 7

CONTROL TRANSFORMER

POWER TO
CONTROLLER

SIGNAL TO
CONTROLLER

SIGNAL TO
CONTROLLER

NOTE: HIGH SPEED EVAPORATOR FAN SHOWN. FOR LOW SPEED


CONTACT TE IS DE-ENERGIZED AND CONTACT TV IS ENERGIZED

Figure 4-5 Perishable Mode Cooling


b. When the air temperature decreases to a predetermined tolerance above set point, the in-range light is
illuminated.
c. As the air temperature continues to fall, modulating
cooling starts at approximately 2.5C (4.5F) above
set point (see Figure 4-3).

SIGNAL TO
CONTROLLER

d. The controller monitors the supply air. Once the supply air falls below set point and 0% SMV position is
reached, the controller periodically records the supply air temperature, set point, and time. A calculation
is then performed by subtracting the set point reading

Figure 4-6 Perishable Mode Heating


4--7

T-354

4.10.3 Sequence of Operation -- Frozen Mode


Cooling

4.10.4 Sequence of Operation -- Defrost


The defrost cycle may consist of up to three distinct
operations. The first is de-icing of the coil, the second is
a probe check cycle, and the third is snap freeze.
Defrost may be requested by any one of the following
methods:
The manual defrost function (also manual defrost switch
function if equipped) is initiated and ended by the user
using the keypad or manual defrost switch (if equipped).

NOTES
1.. In the Frozen Mode of operation the
evaporator motors run in low speed.
2.. In low temperature ambients, the
condenser fan will be cycled by the
controller to maintain proper condensing
pressure.

NOTE
The Manual Defrost / Interval key can be used
to initiate a manual defrost. Minimum Software
release version #5126 is required in order to
use this function.

a. With supply air temperature above set point and decreasing, the unit will be cooling with the condenser
fan motor (CF), compressor motor (CH), evaporator
fan motors (ES) energized and the COOL light illuminated (see Figure 4-7).
b.When the air temperature decreases to a predetermined tolerance above set point, the in-range light is
illuminated.
ENERGIZED
DE-ENERGIZED
FOR FULL DIAGRAM AND
LEGEND, SEE SECTION 7

Manual Defrost/Interval Key Operation:


1. Depressing and holding the Manual Defrost/Interval
Key for five seconds will initiate defrost. If the Manual
Defrost/Interval Key is released in less than five seconds, defrost interval (code 27) shall be displayed.
2. The user sends a defrost request by
communications.
3. The defrost interval timer (controller function code
Cd27) reaches the defrost interval set by the user.
4. The controller probe diagnostic logic determines that
a probe check is necessary based on the temperature values currently reported by the supply and return probes.
5. The controller Demand Defrost configuration variable (CnF40) is set to In and the unit has been in
pull down operation for over 2.5 hours without reaching set point.

CONTROL TRANSFORMER

POWER TO
CONTROLLER

SIGNAL TO
CONTROLLER

ENERGIZED
DE-ENERGIZED
FOR FULL DIAGRAM AND
LEGEND, SEE SECTION 7
SIGNAL TO
CONTROLLER

POWER TO
CONTROLLER

SIGNAL TO
CONTROLLER

Figure 4-7 Frozen Mode


c. Contacts TC and TN are opened to de-energize the
compressor and condenser fan motors when the return air temperature decreases to 0.2C (0.4F) below set point. The cool light is also de-energized.
d. The evaporator fan motors continue to run to circulate
air throughout the container. The in-range light remains illuminated as long as the return air is within tolerance of set point.
e. When the return air temperature increases to
0.2C (0.4F) above set point and the three minute off
time has elapsed, relays TC and TN are energized to
restart the compressor and condenser fan motors.
The cool light is also illuminated.

T--354

CONTROL TRANSFORMER

SIGNAL TO
CONTROLLER

SIGNAL TO
CONTROLLER

Figure 4-8 Defrost

4--8

The processing of a defrost request is controlled by the


defrost termination thermostat. The defrost termination
thermostat is not a physical component. It is a software
point that acts as a thermostat, allowing defrost when it
is considered closed and preventing or terminating
defrost when it is considered open.
The actual temperatures used to make the open or
closed determinations are dependent on the type of
defrost request made and the operator setting of
configuration variable CnF41. Configuration variable
CnF41may be factory set at the default value of 25.6C
(78F) or a lower value of 18C (64F).
When a request for defrost is made by the use of the
Manual Defrost Switch or Communications, the unit will
enter defrost when the reading at the defrost
temperature sensor is at or below the CnF41 setting.
Defrost will terminate when the defrost sensor
temperature reading rises above the CnF41 setting.
When a request for defrost is made by probe check, the
unit will enter defrost when the defrost temperature
sensor reading is at or below 25.6C (78F). The unit will
terminate defrost when the Defrost Temperature
Sensor reading rises above 25.6C (78F)
When a request for defrost is made by demand defrost,
the unit will enter defrost when the reading at the defrost
temperature sensor is at or below 18C (64.4F).
Defrost will terminate when the defrost sensor
temperature reading rises above the CnF41 setting.
When a defrost has terminated, the defrost interval
timer will begin counting when the reading at the defrost
temperature sensor is at or below 10C (50F). Once
the timer has counted the required time, the unit will
enter defrost if the Defrost Temperature Sensor is at or
below 25.6C (78F). Defrost will terminate when the
defrost sensor temperature reading rises above the
CnF41 setting.
When the unit enters defrost, the controller opens
contacts TC, TN, and TE (or TV) to de-energize the
compressor, condenser fan and evaporator fans (see
Figure 4-8). The COOL light is also de-energized.
The controller then closes TH to supply power to the
heaters. The defrost light is illuminated.
When the defrost temperature sensor reading rises to
the applicable defrost termination thermostat opening
point, the de-icing operation is terminated.
If defrost does not terminate correctly and temperature
reaches the set point of the heat termination thermostat
(HTT), the thermostat will open to de-energize the
heaters. If termination does not occur within two hours,
the controller will terminate defrost. An alarm will be
given of a possible DTS failure.

4.11 EMERGENCY OPERATION (OPTION)


Operation by the refrigeration controller may be
overridden by use of the EMERGENCY BYPASS or by
use of the EMERGENCY DEFROST switch. The
EMERGENCY BYPASS switch functions to bypass the
controller in the event of controller failure. The
EMERGENCY DEFROST switch functions to bypass
the controller and place the unit in the defrost mode.
4.11.1 Emergency Bypass Operation
To place the unit in the emergency bypass mode, cut the
wire tie installed at the switch mounting and place the
EMERGENCY BYPASS switch in the BYPASS
position. This will in turn activate the Emergency Bypass
System (EBS) control module.
To operate the fans only, the MODE switch must be in
the FANS ONLY position and the EMERGENCY
BYPASS Switch must be in the ON position.
The EBS module uses the systems safety devices (high
pressure switch, motor internal protectors, and heat
termination thermostat) to protect the system while in
Emergency Bypass Mode.

CAUTION
The unit will remain in the full cooling mode
as long as the emergency bypass switch is
in the BYPASS position and the MODE
SWITCH is in the FULL COOL position.
If the cargo may be damaged by low temperatures, the operator must monitor container
temperature and manually cycle operation
as required to maintain temperature within
required limits.
In the ON position the EBS will be enabled. With the
MODE SWITCH in the FULL COOL MODE. The
following will occur simultaneously:
1. The EBS switch will enable EBS input.
2. The phase detection circuit will detect the phase
rotation and close to provide power to the compressor contactor.
3. The condenser fan contact will close to energize the
condenser contactor and provide power to the condenser fan motor.
4. The evaporator fan contact will close to energize the
high speed evaporator contactor and provide power
to the evaporator fan motor.

If probe check (controller function code CnF31) is


configured to special, the unit will proceed to the next
operation (snap freeze or terminate defrost). If the code
is configured to standard, the unit will perform a probe
check. The purpose of the probe check is to detect
malfunctions or drift in the sensed temperature that is
too small to be detected by the normal sensor out of
range tests. The system will run for eight minutes in this
condition. At the end of the eight minutes, probe alarms
will be set or cleared based on the conditions seen.

5. The EBS electronic module will open the SMV to


100%.
To return the unit to normal operation, place the EBS
switch in the NORMAL OPERATION position. When
emergency operation is no longer required, re-install the
wire tie at the switch mounting.

4--9

T-354

4.11.2 Emergency Defrost Operation

CAUTION

To place the unit in the emergency defrost mode of


operation, cut the wire tie installed at the switch
mounting (see Figure 2-6) and place the switch in the
EMERGENCY DEFROST position.

The unit will remain in the DEFROST mode


as long as the emergency defrost switch is
in the DEFROST position. To prevent cargo
damage, the operator must monitor
container temperature and manually cycle
operation as required to maintain
temperature within required limits.

NOTE
1. If the unit is in the emergency bypass
cooling mode, the emergency defrost
switch will override this mode and place the
unit in defrost.

To return the unit to normal operation, place the switch in


the NORMAL OPERATION position. When emergency
defrost is no longer required, re-install the wire tie at the
switch mounting.
4.12 ARCTIC MODE

2. The IN-RANGE LIGHT is de-energized


when in the emergency defrost mode.

With arctic mode enabled, if the ambient is colder than


-10.0C there is a 30--minute time delay at startup for
any of the components in the system, except for the
controller and the compressor crankcase heater (CCH),
which should be active at this point.
In arctic mode, the CCH is energized for 30 minutes to
warm the oil in the compressor and boil off any liquid
refrigerant that may be present in the crankcase.
If Pre-Trip is initiated during the 30--minute time period,
Pre-Trip will be allowed to run normally. Once Pre-Trip is
over, the controller will revert to its normal control mode
logic.
If ambient is warmer than -10.0C (14F), the system
will run its normal startup logic.
Arctic mode is configurable by using the configuration
variable #29, refer to Table 3-4.

The switch is a normally open four-pole switch, which is


placed in the EMERGENCY DEFROST position to:
a. De-energize the compressor, condenser fan and
evaporator fan contactors.
b. Illuminate the EMERGENCY DEFROST LIGHT.
c. Energize the heater contactor.
d. Illuminate the DEFROST LIGHT.

T--354

4--10

SECTION 5
TROUBLESHOOTING
CONDITION

POSSIBLE CAUSE

REMEDY/
REFERENCE
SECTION

5.1 UNIT WILL NOT START OR STARTS THEN STOPS

No power to unit

Loss of control power

Component(s) Not Operating

Compressor hums,
but does not start

External power source OFF


Start-Stop switch OFF or defective
Circuit breaker tripped or OFF
Autotransformer not connected
Circuit breaker OFF or defective
Control transformer defective
Fuses (F3A , F3B) blown
Start-Stop switch OFF or defective
Evaporator fan motor internal protector open
Condenser fan motor internal protector open
Compressor internal protector open
High pressure switch open
Heat termination thermostat open
Low line voltage
Single phasing
Shorted or grounded motor windings
Compressor seized

Turn on
Check
Check
4.2.2
Check
Replace
Check
Check
6.16
6.11
6.8
5.7
Replace
Check
Check
6.8
6.8

5.2 UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING


Container

Refrigeration System

Hot load (Failure to Pre--cool)


Defective box insulation or air leak
Shortage of refrigerant
Evaporator coil covered with ice
Evaporator coil plugged with debris
Evaporator fan(s) rotating backwards
Defective evaporator fan motor/capacitor
Air bypass around evaporator coil
Controller set too low
Compressor service valves or liquid line shutoff valve partially closed
Dirty condenser
Compressor worn
Current limit (function code Cd32) set to wrong value
Suction modulation valve malfunction

5--1

Normal
Repair
6.7.1
5.6
6.15
6.15/6.16
6.17
Check
Reset
Open valves
completely
6.10
6.8
3.3.5
6.19

T-354

CONDITION

POSSIBLE CAUSE

REMEDY/
REFERENCE
SECTION

5.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING


Compressor

Refrigeration System

Compressor valves defective


Abnormal pressures
Controller malfunction
Evaporator fan or motor defective
Suction modulation valve malfunction
Condenser Pressure Transducer defective
Shortage of refrigerant

6.8
5.7
5.9
6.16
6.19
Check
6.7.1

5.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING


No operation of any kind

No control power

Unit will not heat or has


insufficient heat

Start-Stop switch OFF or defective


Circuit breaker OFF or defective
External power source OFF
Circuit breaker or fuse defective
Control Transformer defective
Evaporator fan internal motor protector open
Heat relay defective
Heater termination switch open
Heater(s) defective
Heater contactor or coil defective
Evaporator fan motor(s) defective or rotating backwards
Evaporator fan motor contactor defective
Controller malfunction
Defective wiring
Loose terminal connections
Low line voltage

Check
Check
Turn ON
Replace
Replace
6.16
Check
6.15
6.15
Replace
6.15/6.16
Replace
5.9
Replace
Tighten
2.3

5.5 UNIT WILL NOT TERMINATE HEATING

Unit fails to stop heating

Controller improperly set


Controller malfunction
Heater termination thermostat remains closed along with
the heat relay

Reset
5.9
6.15

5.6 UNIT WILL NOT DEFROST PROPERLY


Defrost timer malfunction (Cd27)
Loose terminal connections
Defective wiring
Defrost temperature sensor defective or heat termination
thermostat open

Table 3-5
Tighten/
Replace

Will not initiate defrost


manually

Heater contactor or coil defective


Manual defrost switch defective
Defrost temperature sensor open

Replace
Replace
4.10.4

Initiates but relay (DR)


drops out

Low line voltage

2.3

Initiates but does not defrost

Heater contactor or coil defective


Heater(s) burned out

Replace
6.15

Will not initiate defrost


automatically

T-354

5--2

Replace

CONDITION

POSSIBLE CAUSE

REMEDY/
REFERENCE
SECTION

5.6 UNIT WILL NOT DEFROST PROPERLY --Continued


Frequent defrost

Wet load

Normal

5.7 ABNORMAL PRESSURES (COOLING)

High discharge pressure

Low suction pressure

Suction and discharge


pressures tend to equalize
when unit is operating

Condenser coil dirty


Condenser fan rotating backwards
Condenser fan inoperative
Refrigerant overcharge or noncondensibles
Discharge pressure regulator valve defective
Discharge service valve partially closed
Suction modulation valve malfunction
Suction service valve partially closed
Filter-drier partially plugged
Low refrigerant charge
Expansion valve defective
No evaporator air flow or restricted air flow
Excessive frost on evaporator coil
Evaporator fan(s) rotating backwards
Discharge pressure regulator valve defective
Suction modulation valve malfunction
Heat exchanger defective
Compressor valves defective
Compressor cycling/stopped

6.10
6.11
6.11
6.7.1
6.20
Open
6.19
Open
6.13
6.7.1
6.14
6.15
5.6
6.16
6.20
6.19
Replace
6.8
Check

5.8 ABNORMAL NOISE OR VIBRATIONS

Compressor

Condenser or Evaporator Fan

Loose mounting bolts


Worn bearings
Worn or broken valves
Liquid slugging
Insufficient oil
Bent, loose or striking venturi
Worn motor bearings
Bent motor shaft

Tighten
6.8
6.8
6.14
6.8.6
Check
6.11/6.16
6.11/6.16

5.9 CONTROLLER MALFUNCTION

Will not control

Defective Sensor
Defective wiring
Fuse (F1, F2) blown
Stepper motor suction modulation valve circuit malfunction

5--3

6.23
Check
Replace
6.19

T-354

CONDITION

POSSIBLE CAUSE

REMEDY/
REFERENCE
SECTION

5.10 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW


Evaporator coil blocked

No or partial evaporator air flow

Frost on coil
Dirty coil
Evaporator fan motor internal protector open
Evaporator fan motor(s) defective
Evaporator fan(s) loose or defective
Evaporator fan contactor defective

5.6
6.15
6.16
6.16
6.16
Replace

5.11 THERMOSTATIC EXPANSION VALVE MALFUNCTION

Low suction pressure with high


superheat

High suction pressure with low


superheat
Liquid slugging in compressor
Fluctuating suction pressure

Low refrigerant charge


External equalizer line plugged
Wax, oil or dirt plugging valve or orifice ice formation at
valve seat
Superheat too high
Power assembly failure
Loss of element/bulb charge
Broken capillary
Foreign material in valve
Superheat setting too low
External equalizer line plugged ice holding valve open
Foreign material in valve
Pin and seat of expansion valve eroded or held open by
foreign material
Improper bulb location or installation
Low superheat setting

6.7.1
Open
6.14
6.7.1
6.14
6.14
Open
6.14
6.14

5.12 AUTOTRANSFORMER MALFUNCTION

Unit will not start

Circuit breaker (CB-1 or CB-2) tripped


Autotransformer defective
Power source not turned ON
460 VAC power plug is not inserted into the receptacle

Check
6.21
Check
4.2.2

5.13 WATER-COOLED CONDENSER OR WATER PRESSURE SWITCH


High discharge pressure
Condenser fan starts and stops

T-354

Dirty coil
Noncondensibles
Water pressure switch malfunction
Water supply interruption

5--4

6.12
Check
Check

SECTION 6
SERVICE
NOTE
To avoid damage to the earths ozone layer, use a refrigerant recovery system whenever removing refrigerant. When working with refrigerants, you must comply with all local government environmental laws. In the
U.S., refer to EPA section 608.

WARNING
Never use air for leak testing. It has been determined that pressurized mixtures of refrigerant and air can undergo combustion
when exposed to an ignition source.

6.1 SECTION LAYOUT

OPENED (Backseated )
HAND VALVE

Service procedures are provided herein beginning with


refrigeration system service, then refrigeration system
component service, electrical system service,
temperature recorder service, and general service.
Refer to the Table Of Contents to locate specific topics.

C
CLOSED (Frontseated)
HAND VALVE

A. Connection to Low Side of System


B. Connection to either:
Refrigerant Cylinder or
Oil Container
C. Connection to High Side of System

6.2 SERVICE VALVES


The compressor suction, compressor discharge, and
liquid line service valves (see Figure 6-1) are provided
with a double seat and a gauge connection, which
enables servicing of the compressor and refrigerant
lines. Turning the valve stem clockwise (all the way
forward) will frontseat the valve to close off the suction,
discharge or liquid line and open the gauge port to the
compressor or low side. Turning the valve stem
counterclockwise (all the way out) will backseat the
valve to open the connections and close off the port.

Figure 6-2 Manifold Gauge Set


6.3 MANIFOLD GAUGE SET
The manifold gauge set (see Figure 6-2) is used to
determine system operating pressure, add refrigerant
charge, and to equalize or evacuate the system.
When the suction pressure hand valve is frontseated
(turned all the way in), the suction (low) pressure can be
checked. When the discharge pressure hand valve is
frontseated, the discharge (high) pressure can be
checked. When both valves are open (turned
counter-clockwise all the way out), high pressure vapor
will flow into the low side. When the suction pressure
valve is open and the discharge pressure valve shut, the
system can be charged. Oil can also be added to the
system.
A R-134a manifold gauge/hose set with self-sealing
hoses (see Figure 6-3) is required for service of the
models covered within this manual. The manifold
gauge/hose set is available from Carrier Transicold.
(Carrier Transicold P/N 07-00294-00, which includes
items 1 through 6, Figure 6-3). To perform service using
the manifold gauge/hose set, do the following:
a. Preparing Manifold Gauge/Hose Set For Use
If the manifold gauge/hose set is new or was exposed to
the atmosphere, it will need to be evacuated to remove
contaminants and air as follows:
1. Back seat (turn counterclockwise) both field service
couplings (see Figure 6-3) and midseat both hand
valves.
2. Connect the yellow hose to a vacuum pump and refrigerant 134a cylinder.
3. Evacuate to 10 inches of vacuum and then charge
with R-134a to a slightly positive pressure of
0.1kg/cm@ (1.0psig).

With the valve stem midway between frontseat and


backseat, the lines are open to both the connections and
the gauge connection.
For example, the valve stem is first fully backseated
when connecting a manifold gauge to measure
pressure. Then, the valve is opened 1/4-- to 1/2--turn to
measure the pressure.
2
3
1

VALVE
FRONTSEATED
(Clockwise)

DISCHARGE
PRESSURE
GAUGE

SUCTION
PRESSURE
GAUGE

5
4
VALVE
BACKSEATED
(Counterclockwise)

1. Suction, Discharge or 3. Stem Cap


Liquid Line
4. Valve stem
Connection
5. Compressor Or Filter
2. Service Port
Drier Inlet Connection
Figure 6-1 Service Valve
6--1

T--354

4. Front seat both manifold gauge set valves and disconnect from cylinder. The gauge set is now ready
for use.

To Low Side
Service Port

To High Side
Service Port
2

3
Blue

4
6
Blue Knob

13

3 - Red

11

3 - Yellow 4

12

10

5
Red Knob

1. Manifold Gauge Set


2. Hose Fitting (0.5-16 Acme)
3. Refrigeration and/or Evacuation Hose
(SAE J2196/R-134a)
4. Hose Fitting w/O-ring (M14 x 1.5)
5. High Side Field Service Coupling
6. Low Side Field Service Coupling
Figure 6-3 R-134a Manifold Gauge/Hose Set

1. Discharge Service
7.
8.
Valve
9.
2. Compressor
3. Suction Service Valve 10.
4. Receiver or Water
11.
Cooled Condenser
5. Liquid Service Valve 12.
13.
6. Vacuum Pump

b. Connecting Manifold Gauge/Hose Set


Connection of the manifold gauge/hose set (see
Figure 6-4) is dependent on the component being
serviced. If only the compressor is being serviced, the
high side coupling is connected to the discharge service
valve. For service of the low side (after pump down), the
high side coupling is connected to the liquid line service
valve. The center hose connection is brought to the tool
being used. To connect the manifold gauge/hose set, do
the following:
1. Remove service valve stem caps and check to make
sure they are backseated. Remove service port caps
(See Figure 6-1).
2. Connect the high side field service coupling (see
Figure 6-3) to the discharge or liquid line valve service valve port.
3. Turn the high side field service coupling knob (red)
clockwise, which will open the high side of the system to the gauge set.
4. Connect the low side field service coupling to the
suction service valve port.
5. Turn the low side field service coupling knob (blue)
clockwise, which will open the low side of the system
to the gauge set.
6. To read system pressures, slightly midseat the high
side and suction service valves.

T--354

5
7-BLUE
8-YELLOW
9-RED

S D

Low Side Hose


Center Hose
High Side Hose
Electronic Vacuum
Gauge
Manifold Gauge Set
Refrigerant Cylinder
Reclaimer

Figure 6-4 Refrigeration System Service


Connections

CAUTION
To prevent trapping liquid refrigerant in the
manifold gauge set, be sure set is brought
to suction pressure before disconnecting.
c. Removing the Manifold Gauge Set
1. While the compressor is still ON, backseat the high
side service valve.
2. Midseat both hand valves on the manifold gauge set
and allow the pressure in the manifold gauge set to
be drawn down to suction pressure. This returns any
liquid that may be in the high side hose to the system.
3. Backseat the suction service valve. Backseat both
field service couplings and frontseat both manifold
set valves. Remove the couplings from the service
ports.
4. Install both service valve stem caps and service port
caps (finger-tight only).

6--2

6.4 PUMPING THE UNIT DOWN

6.6 EVACUATION AND DEHYDRATION

To service the filter-drier, moisture-liquid indicator,


expansion valve, suction modulation valve, quench
valve, or evaporator coil, pump the refrigerant into the
high side as follows:

6.6.1 General
Moisture is the deadly enemy of refrigeration systems.
The presence of moisture in a refrigeration system can
have many undesirable effects. The most common are
copper plating, acid sludge formation, freezing-up of
metering devices by free water, and formation of acids,
resulting in metal corrosion.

a. Attach manifold gauge set to compressor service


valves (refer to paragraph 6.3).
b. Start the unit and run in a cooling mode for 10 to 15
minutes. Frontseat the liquid line service valve. Place
start-stop switch in the OFF position when the suction
reaches a positive pressure of 0.1kg/cm@ (1.0psig).

6.6.2 Preparation
a. Evacuate and dehydrate only after pressure leak test
(refer to paragraph 6.5).

c. Frontseat the suction service valve. The refrigerant


will be trapped between the compressor suction service valve and the liquid line valve.

b. Essential tools to properly evacuate and dehydrate


any system include a vacuum pump (8m3/hr = 5cfm
volume displacement) and an electronic vacuum
gauge. The pump is available from Carrier Transicold
(P/N 07-00176-11).

d. Before opening up any part of the system, a slight


positive pressure should be indicated on the pressure
gauge. If a vacuum is indicated, emit refrigerant by
cracking the liquid line valve momentarily to build up a
slight positive pressure.

c. If possible, keep the ambient temperature above


15.6_C (60_F) to speed evaporation of moisture. If
the ambient temperature is lower than 15.6_C
(60_F), ice might form before moisture removal is
complete. Heat lamps or alternate sources of heat
may be used to raise the system temperature.

e. When opening up the refrigerant system, certain


parts may frost. Allow the part to warm to ambient
temperature before dismantling. This avoids internal
condensation, which puts moisture in the system.
f. After repairs have been made, be sure to perform a
refrigerant leak check (refer to paragraph 6.5), and
evacuate and dehydrate the low side (refer to
paragraph 6.6).

d. Additional time may be saved during a complete system pump down by replacing the filter-drier with a
section of copper tubing and the appropriate fittings.
Installation of a new drier may be performed during
the charging procedure.

g. Check refrigerant charge (refer to paragraph 6.7).


6.5 REFRIGERANT LEAK CHECKING

6.6.3 Procedure - Complete System

WARNING

a. Remove all refrigerant using a refrigerant recovery


system.

Never use air for leak testing. It has been


determined that pressurized, air-rich mixtures of refrigerants and air can undergo
combustion when exposed to an ignition
source.

b. The recommended method to evacuate and dehydrate the system is to connect three evacuation
hoses (see Figure 6-5) to the vacuum pump and
refrigeration unit. Be sure the service hoses are
suited for evacuation purposes.

a. The recommended procedure for finding leaks in a


system is with a R-134a electronic leak detector.
Testing joints with soapsuds is satisfactory only for
locating large leaks.

c. Test the evacuation setup for leaks by backseating


the unit service valves and drawing a deep vacuum
with the vacuum pump and gauge valves open. Shut
off the pump and check to see if the vacuum holds.
Repair leaks if necessary.

b. If the system is without refrigerant, charge the system


with refrigerant 134a to build up pressure between 2.1
to 3.5kg/cm@ (30 to 50psig). Remove refrigerant cylinder and leak-check all connections.

d. Midseat the refrigerant system service valves.


e. Open the vacuum pump and electronic vacuum
gauge valves, if they are not already open. Start the
vacuum pump. Evacuate unit until the electronic vacuum gauge indicates 2000 microns. Close the electronic vacuum gauge and vacuum pump valves. Shut
off the vacuum pump. Wait a few minutes to be sure
the vacuum holds.

NOTE
Only refrigerant 134a should be used to pressurize the system. Any other gas or vapor will
contaminate the system, which will require
additional purging and evacuation of the
system.

f. Break the vacuum with clean dry refrigerant 134a


gas. Raise system pressure to approximately
0.2kg/cm@ (2psig), monitoring it with the compound
gauge.

c. If required, remove refrigerant using a refrigerant


recovery system and repair any leaks.
d. Evacuate and dehydrate the unit (refer to paragraph
6.6).

g. Remove refrigerant using a refrigerant recovery


system.

e. Charge unit per paragraph 6.7.

h. Repeat steps e.and f. one time.


6--3

T--354

6.7 REFRIGERANT CHARGE

6.7.1 Checking the Refrigerant Charge


NOTE
To avoid damage to the earths ozone layer, use
a refrigerant recovery system whenever removing refrigerant. When working with refrigerants
you must comply with all local government environmental laws. In the U.S., refer to EPA
section 608.

1
S D

a. Connect the gauge manifold to the compressor discharge and suction service valves. For units operating on a water cooled condenser, change over to aircooled operation.
b. Bring the container temperature to approximately
1.7 C (35_F) or -17.8_C (0_F). Set the controller set
point to -25_C (-13_F) to ensure that the suction modulation valve is at maximum allowed open position.
c. Partially block the condenser coil inlet air. Increase
the area blocked until the compressor discharge
pressure is raised to approximately 12kg/cm@
(175psig).
d. On units equipped with a receiver, the level should be
between the glasses. On units equipped with a watercooled condenser, the level should be at the center of
the glass. If the refrigerant level is not correct, continue with the following paragraphs to add or remove refrigerant as required.
6.7.2 Adding Refrigerant to System (Full Charge)
a. Evacuate unit and leave in deep vacuum (refer to
paragraph 6.6).
b. Place cylinder of R-134a on scale and connect charging line from cylinder to liquid line valve. Purge charging line at liquid line valve and then note weight of cylinder and refrigerant.
c. Open liquid valve on cylinder. Open liquid line valve
half-way and allow the liquid refrigerant to flow into
the unit until the correct weight of refrigerant (refer to
paragraph 2.2) has been added as indicated by
scales.

9
7

10

1. Reclaimer
6.
2. Discharge Service
7.
Valve
8.
3. Compressor
4. Suction Service Valve 9.
5. Receiver or Water
10.
Cooled Condenser

Liquid Service Valve


Vacuum Pump
Electronic Vacuum
Gauge
Manifold Gauge Set
Refrigerant Cylinder

Figure 6-5 Compressor Service Connections


i. Remove the copper tubing and change the filter-drier.
Evacuate unit to 500 microns. Close the electronic
vacuum gauge and vacuum pump valves. Shut off the
vacuum pump. Wait five minutes to see if vacuum
holds. This procedure checks for residual moisture
and/or leaks.
j. With a vacuum still in the unit, the refrigerant charge
may be drawn into the system from a refrigerant container on weight scales. Continue to paragraph 6.7.

NOTE
It may be necessary to finish charging unit
through suction service valve in gas form, due
to pressure rise in high side of the system (refer
to section paragraph 6.7.3).

6.6.4 Procedure - Partial System


a. If the refrigerant charge has been removed from the
compressor for service, evacuate only the compressor by connecting the evacuation set-up at the compressor service valves. Follow evacuation procedures of the preceding paragraph except leave
compressor service valves frontseated until evacuation is completed.

d. Backseat manual liquid line valve (to close off gauge


port). Close liquid valve on cylinder.
e. Start unit in cooling mode. Run approximately
10 minutes and check the refrigerant charge.
6.7.3 Adding Refrigerant to System (Partial
Charge)
a. Examine the unit refrigerant system for any evidence
of leaks. Repair as necessary (refer to paragraph
6.5).
b. Maintain the conditions outlined in paragraph 6.7.1
c. Fully backseat the suction service valve and remove
the service port cap.
d. Connect charging line between suction service valve
port and cylinder of refrigerant R-134a. Open VAPOR
valve.

b. If refrigerant charge has been removed from the low


side only, evacuate the low side by connecting the
evacuation set-up at the compressor service valves
and liquid service valve except leave the service
valves frontseated until evacuation is completed.
c. Once evacuation has been completed and the pump
has been isolated, fully backseat the service valves to
isolate the service connections and then continue
with checking and, if required, adding refrigerant in
accordance with normal procedures.
T--354

6--4

e. Partially frontseat (turn clockwise) the suction service


valve and slowly add charge until the refrigerant
appears at the proper level.

16

6.8 COMPRESSOR

15

WARNING

14

Make sure power to the unit is OFF and


power plug disconnected before replacing
the compressor.

13

12

NOTES

11
10

1. The compressor should not operate in a


vacuum greater than 500mm/hg
(20 inches/hg).

6
9

1. Discharge Valve
Flange
2. High Side Pressure
Connection
3. Low Side Pressure
Connection
4. Suction Valve Flange
5. Motor End Cover
6. Serial/Model No. Plate
7. Crankcase Heater

2. The service replacement compressor is


sold without shutoff valves (but with valve
pads), and without terminal box and cover.
Customer should retain the original
terminal box, cover, and high pressure
switch for use on replacement compressor.
3. Check oil level in service replacement
compressor (refer to paragraph 6.8.6).
4. A compressor terminal wiring kit must be
ordered as a separate item when ordering
replacement compressor. Appropriate
installation instructions are included with
kit.

8.
9.
10.
11.
12.
13.
14.
15.
16.

Bottom Plate
Sight Glass
Oil Drain Plug
Oil Charging Valve
Bearing Head
Oil Pump
Oil Fill Plug
Cylinder Head
Valve Plate

Figure 6-6 Compressor


h. Remove compressor mounting bolts from mounting
plate and install mounting plate on replacement compressor.

5. Refer to Table 6-6 and Table 6-7 for


applicable compressor wear limits and
torque values.

i. Install replacement compressor terminal wiring kit,


following instructions included with kit.

6. Refer to Figure 6-36 for charts on


compressor pressure, temperature and
motor current curves.

k. Install compressor and mounting plate in unit.

j. Install high pressure switch on compressor.


l. Connect junction box(es) to compressor and connect
all wiring per wiring diagram. Install junction box
cover(s).

6.8.1 Removal and Replacement of Compressor

m. Install new gaskets on service valves.

a. Remove the protective guard from lower section of


the unit.

n. Install mounting bolts in service valves and torque to


2.77 to 4.15mkg (20-30ft/lb).

b. Pump down low side (refer to paragraph 6.4) or frontseat compressor service valves and remove refrigerant from compressor using a refrigerant recovery
system.

o. Attach two hoses (with hand valves near vacuum


pump) to the suction and discharge service valves.
Dehydrate and evacuate compressor to 500 microns
(75.9cm Hg vacuum = 29.90 inches Hg vacuum).
Turn off valves on both hoses to pump.

c. Locate the compressor junction box. Tag and disconnect wiring from compressor terminals and remove
compressor junction box.

p. Fully backseat (open) both suction and discharge


service valves.

d. Loosen service valve mounting bolts, break seal, and


then remove bolts.

q. Remove vacuum pump lines.


r. Start unit and check refrigerant charge (refer to paragraph 6.7).

e. Remove compressor plate mounting bolts.


f. Remove compressor and mounting plate. Refer to
paragraph 2.2 for weight of compressor.

s. Check moisture-liquid indicator for wetness. Change


filter-drier if necessary (refer to paragraph 6.13).

g. Remove high pressure switch (HPS) from compressor and check operation of switch (refer to paragraph
6.9.2).

t. Check compressor oil level per paragraph 6.8.6. Add


oil if necessary.
6--5

T--354

6.8.2 Compressor Disassembly


2
3

WARNING

Before disassembly of any external compressor component make sure to relieve


possible internal pressure by loosening the
bolts and tapping the component with a
soft hammer to break the seal.

5
4

1. Oil Pressure Relief


Valve
2. Oil Return Check
Valve

CAUTION
Removing the compressor motor press-fit
stator in the field is not recommended. The
rotor and stator are a matched pair and
should not be separated.

Figure 6-8 Bottom Plate Removed


b. Loosen cylinder head cap screws. If the cylinder head
is stuck, tap the center of the cylinder head with a
wooden or lead mallet. Do not strike the side of the
cylinder head. Be careful not to drop the head or damage the gasket sealing surface. Remove cylinder
head bolts and gasket (see Figure 6-7).

When disassembling compressor, matchmark parts so


they may be replaced in their same relative positions
(see Figure 6-6). Refer to Table 6-6 and Table 6-7 for
compressor wear limits and bolt torque values.

c. Remove valve stops and valves. After they have been


removed, free the valve plate from the cylinder deck
by using the outside discharge valve hold-down cap
screw as a jack screw through the tapped hole of the
valve plate. Remove the valve plate gasket.

a. Place the compressor in a position where it will be


convenient to drain the oil. Remove the oil fill plug
(see Figure 6-6) to vent the crankcase. Loosen the
drain plug in bottom plate and allow the oil to drain out
slowly. Remove the plug slowly to relieve any crankcase pressure. Some units have a plug in the bottom
center of the crankcase, which may be removed for
draining the motor end more quickly.

3. Oil Suction Tube


4. Cap screw
5. Connecting Rod and
Cap Assembly

d. Turn the compressor on its side and remove the bottom plate oil suction screen and screen hold down
plate. Inspect the screen for holes or an accumulation
of dirt. The screen can be cleaned with a suitable solvent.
e. Match mark each connecting rod cap (see Figure 6-8)
and connecting rod for correct reassembly. Remove
the bolts and connecting rod caps. Push the piston
rods up as far as they will go without having the piston
rings extend above the cylinders.

CAUTION
The copper tube, which connects to the oil
suction strainer extends out the bottom
with the bottom plate removed. Take precautions to avoid bending or breaking it
while changing crankcase positions.

JACK HERE
6

1. Cylinder Head Gasket


2. Discharge Valve
Screw & Lockwasher
3. Discharge Valve Stop

4.
5.
6.
7.

f. If necessary, remove the oil return check valve (see


Figure 6-8). Inspect it for proper operation (flow in
one direction only). Replace the assembly with a new
unit if check valve operation is impaired.

Discharge Valve
Valve Plate
Valve Plate Assembly
Valve Plate Gasket

g. To remove the oil pump (see Figure 6-9) remove eight


cap screws, oil pump bearing head assembly, gasket,
and thrust washer.

Figure 6-7 Exploded View of Valve Plate


T--354

6--6

h. Be very careful not to damage the motor windings


when removing the motor end cover (see
Figure 6-11), as the cover fits over the winding coils.
Loosen the cap screws, break the seal, and then remove all cap screws except one in the top of the
cover. While holding the cover in place, remove the
remaining cap screw. Do not allow the cover to drop
from its own weight. To prevent striking the winding,
remove the cover horizontally and in line with the
motor axis.

Set screw must be removed.


1

6
5

1. Oil Pump & Bearing


Head
2. Thrust Washer

2
3

3. Oil Pickup Tube


4. Oil Inlet Port
5. Oil Pump Inlet

2
1

Figure 6-9 Oil Pump and Bearing Head


NOTE
If the oil pump was not operating properly, the
entire oil pump & bearing head assembly must
be replaced. Individual parts are not available. If
the pump requires inspection or cleaning, disassemble and reassemble by referring to
Figure 6-10. Clean all parts and coat all moving
parts with compressor oil before proceeding
with reassembly.

1. Strainer Screws and


Washers
2. Suction Strainer
3. Motor End Cover
Gasket

7
11

1.
2.
3.
4.
5.
6.

Cap screws
Cover
Reversing Assembly
Pinion
Gear
Drive

Motor End Cover


Valve Gasket
Suction Service Valve
Valve Cap screw

Figure 6-11 Motor End Cover


i. Remove the refrigerant suction strainer. If it is
removed with ease, it may be cleaned with solvent
and replaced. If the strainer is broken, corroded or
clogged with dirt that is not easily removed, replace
the strainer. Install new gaskets upon reassembly.
j. Block the compressor crankshaft so that it cannot
turn. Use a screwdriver to bend back the tabs on the
lockwasher, and remove the equalizer tube and lock
screw assembly (see Figure 6-12). The slingers at
the end of the tube draw vapor from the crankcase.
Remove the rotor using a jack bolt. Insert a brass plug
into the rotor hole to prevent damage to the end of the
crankshaft.
k. If the piston rings extend beyond the cylinder tops, the
pistons can be pulled through the bottom plate opening after the piston rings are compressed. A piston
ring compresser will facilitate removal. Each piston
pin is locked in place by lock rings, which are snapped
into grooves in the piston wall (see Figure 6-13).
l. Since the stator cannot be replaced in the field, the
terminal plate assembly need not be disturbed unless
a leak exists and the plate assembly needs to be replaced. If no terminal plate repair is required, proceed
with reassembly.

12

4.
5.
6.
7.

10
9

7. O-Ring
8. Oil Pump & Bearing
9. Set Screw
10. Relief Valve
11. Pin
12. Gasket

Figure 6-10 Low Profile Oil Pump

6--7

T--354

difficult to reinstall used valves so that they will seat as


before removal. Any valve wear will cause leakage.
1
1

1. Equalizer Tube and


Lock Screw Assembly
2. Lockwasher

3. Counterweight Motor End

Figure 6-12 Equalizing Tube and Lock Screw


Assembly
6

1. Suction Valve
2. Suction Valve
Positioning Spring

3. Valve Plate Dowel


Pin

Figure 6-14 Suction Valve & Positioning Springs


Suction valves are positioned by dowel pins (see Figure
Figure 6-14). Do not omit the suction valve positioning
springs. Place the springs so that the ends bear against
the cylinder deck (middle bowed away from cylinder
deck). Use new gaskets when reinstalling valve plates
and cylinder heads.
b. Compression Rings
The compression ring is chamfered on the inside
circumference. This ring is installed with the chamfer
toward the top. Stagger the ring end gaps so they are
not aligned.

8
4
3
2
10
1

1.
2.
3.
4.
5.

Cap screw
Cap
Crankshaft
Thrust Washer
Rotor Drive Key

6.
7.
8.
9.
10.

Connecting Rod
Compression Ring
Piston
Pin
Retainer

Figure 6-13 Crankshaft Assembly


Figure 6-15 Piston Ring
The gap between the ends of the piston rings can be
checked with a feeler gauge by inserting the ring into the
piston bore approximately one inch below the top of the
bore. Square the ring in the bore by pushing it slightly
with a piston. The maximum and minimum allowable
ring gaps are 0.33 and 0.127mm (0.013 and 0.005 inch)
respectively.

6.8.3 Compressor Reassembly


Clean all compressor parts, using a suitable solvent with
proper precautions. Coat all moving parts with the
proper compressor oil before assembly. Refer to
Table 6-7 for applicable compressor torque values.
6.8.4 Preparation
a. Suction and Discharge Valves
If the valve seats look damaged or worn, replace valve
plate assembly. Always use new valves because it is

T--354

6--8

a. Checking the Oil Level in the Compressor


1. Operate the unit in cooling mode for at least 20 minutes.
2. Check the front oil sight glass on the compressor to
ensure that no foaming of the oil is present after 20
minutes of operation. If the oil is foaming excessively
after 20 minutes of operation, check the refrigerant
system for flood-back of liquid refrigerant. Correct
this situation before performing step 3.
3. Turn unit off to check the oil level. The correct oil level
range should be between the bottom to one-eighth
level of the sight glass. If the level is above oneeighth, oil must be removed from the compressor. To
remove oil from the compressor, follow step d in this
section. If the level is below the bottom of the sight
glass, add oil to the compressor following step b
below.
b. Adding Oil with Compressor in System
1. The recommended method is to add oil using an oil
pump at the oil fill valve (see item 11, Figure 6-6).
2. In an emergency where an oil pump is not available,
oil may be drawn into the compressor through the
suction service valve.
Connect the suction connection of the gauge manifold to the compressor suction service valve port,
and immerse the common connection of the gauge
manifold in an open container of refrigeration oil.
Extreme care must be taken to ensure the manifold
common connection remains immersed in oil at all
times. Otherwise air and moisture will be drawn into
the compressor. Crack the suction service valve and
gauge valve to vent a small amount of refrigerant
through the common connection and the oil to purge
the lines of air. Close the gauge manifold valve.
With the unit running, frontseat the suction service
valve and induce a vacuum in the compressor crankcase. SLOWLY crack the suction gauge manifold
valve and oil will flow through the suction service
valve into the compressor. Add oil as necessary.
c. Adding Oil to Service Replacement Compressor
Service replacement compressors are shipped without
oil. If oil is present in the crankcase, it must be tested to
ensure it is the correct oil and that the moisture level is
acceptable.
When adding oil to a service replacement compressor
add three liters (6.3 pints) using an oil pump at the oil fill
valve (see item 11, Figure 6-6). This quantity is
recommended to allow for return of any oil that may be in
the refrigerant system. Install compressor and check oil
level after it is placed in operation (refer to paragraph
6.8.6).
d. Removing Oil from the Compressor
1. If the oil level is above one-eighth sight glass, oil
must be removed from the compressor.
2. Close (frontseat) suction service valve and pump
unit down to 1.2 to 1.3kg/cm@ (2 to 4psig). Frontseat
discharge service valve and remove remaining refrigerant.
3. Loosen the oil drain plug on the bottom plate of the
compressor and drain the proper amount of oil from
the compressor to obtain the correct level. Backseat
the suction and discharge service valves.
4. Repeat step a to ensure proper oil level.

6.8.5 Installing the Components


a. Push pistons from the inside of the crankcase through
the cylinders, being careful not to break the rings.
Place rods so that the chamfered side will be against
radius of crankpins. Install the crankshaft and thrust
washer through the pump end of the compressor. Ensure thrust washer is fitted on locating pin. Do not
damage main bearings. Bring rods in position against
crank bearings.
b. Install the pump end thrust washer on the two dowel
pins located on the bearing head (see Figure 6-9).

CAUTION
Ensure that thrust washer does not fall off
dowel pins while installing oil pump.

CAUTION
The set screw on the crankshaft must be
removed for this type of oil pump (see
Figure 6-9).
c. Install the bearing head assembly with a new gasket
on the compressor crankshaft. Carefully push oil
pump on by hand, ensuring that the thrust washer remains on the dowel pins. The tang on the end of the
drive engages the slot in the crankshaft, and the oil
inlet port on the pump is aligned with the oil pickup
tube in the crankcase. The pump should mounted
flush with the crankcase, and should be oriented with
the oil pick up tube and oil inlet port aligned as shown
in Figure 6-9.
d. Align the gasket and install the eight cap screws in the
mounting flange. Refer to Table 6-7 for applicable
torque values.
e. Install matching connecting rod caps Be sure rod is
not bound and crankshaft will turn correctly as each
set of rod bolts is torqued.
f. Be sure key fits properly when installng rotor on shaft.
Screw on equalizer tube and lock screw assembly
with lock washer and bend over tabs of lock washer.
Assemble suction strainer to motor and cover, and
bolt cover to crankcase. Assemble valve plates and
gaskets. Assemble cylinder heads and gaskets. Turn
the shaft by hand to see that it moves freely.
g. Install the oil suction screen, the oil suction screen
hold down plate, and the bottom plate.
6.8.6 Compressor Oil Level

CAUTION
Use only Carrier Transicold approved
Polyol Ester Oil (POE) -- Castrol-Icematic
SW20 compressor oil with R-134a. Buy in
quantities of one quart or smaller. When
using this hygroscopic oil, immediately
reseal. Do not leave container of oil open or
contamination will occur.
6--9

T--354

6.9 HIGH PRESSURE SWITCH

6.10 CONDENSER COIL

6.9.1 Replacing High Pressure Switch

The condenser consists of a series of parallel copper


tubes expanded into copper fins. The condenser coil
must be cleaned with fresh water or steam so the air flow
is not restricted. To replace the coil, do the following:

a. Turn unit start-stop switch OFF. Frontseat both suction and discharge service valves to isolate compressor. Remove the refrigerant from the compressor.
b. Disconnect wiring from defective switch. The high
pressure switch is located on the center head and is
removed by turning counterclockwise
(see Figure 2-3).

WARNING
Do not open the condenser fan grille before
turning power OFF and disconnecting
power plug.

c. Install a new high pressure switch after verifying


switch settings (refer to paragraph 6.9.2).

a. Using a refrigerant reclaim system, remove the refrigerant charge.


b. Remove the condenser coil guard.
c. Unsolder discharge line and remove the line to the
receiver or water-cooled condenser.
d. Remove coil mounting hardware and remove the coil.
e. Install replacement coil and solder connections.

d. Evacuate and dehydrate the compressor per


paragraph 6.6.
6.9.2 Checking High Pressure Switch

WARNING
Do not use a nitrogen cylinder without a
pressure regulator. Do not use oxygen in or
near a refrigeration system as an explosion
may occur.

f. Leak-check the coil connections per paragraph paragraph 6.5. Evacuate the unit per paragraph 6.6 then
charge the unit with refrigerant per paragraph 6.7.
6.11 CONDENSER FAN AND MOTOR ASSEMBLY

NOTE
The high pressure switch is non-adjustable.

WARNING

a. Remove switch as outlined in paragraph 6.9.1

Do not open condenser fan grille before


turning power OFF and disconnecting
power plug.

b. Connect ohmmeter or continuity light across switch


terminals. Ohm meter will indicate no resistance or
continuity light will be illuminated if the switch closed
after relieving compressor pressure.

The condenser fan rotates counter-clockwise (viewed


from front of unit), pulls air through the the condenser
coil and discharges horizontally through the front of the
unit. To replace motor assembly:
a. Open condenser fan screen guard.
b. Loosen two square head set screws on fan (thread
sealer has been applied to set screws at installation).
Disconnect wiring from motor junction box.

c. Connect hose to a cylinder of dry nitrogen


(see Figure 6-16).
d. Set nitrogen pressure regulator at 26.4kg/cm@
(375psig) with bleed-off valve closed.
e. Close valve on cylinder and open bleed-off valve.
f. Open cylinder valve. Slowly close bleed-off valve to
increase pressure on switch. The switch should open
at a static pressure up to 25kg/cm@ (350psig). If a light
is used, light will go out. If an ohmmeter is used, the
meter will indicate open circuit.

CAUTION
Take necessary steps (place plywood over
coil or use sling on motor) to prevent motor
from falling into condenser coil.

g. Slowly open bleed-off valve to decrease the pressure. The switch should close at 18kg/cm@
(250psig).
1

4
5

c. Remove motor mounting hardware and replace the


motor. It is recommended that new locknuts be used
when replacing motor. Connect wiring per wiring diagram.
d. Install fan loosely on motor shaft (hub side in). DO
NOT USE FORCE. If necessary, tap the hub only, not
the hub nuts or bolts. Install venturi. Apply Loctite H
to fan set screws. Adjust fan within venturi so that the
outer edge of the fan projects 3.2 to 6.4mm (3/16
1/16) back from edge of the venturi. Spin fan by
hand to check clearance.
e. Close and secure condenser fan screen guard.
f. Apply power to unit and check fan rotation. If fan motor
rotates backward, reverse wire numbers 5 and 8.

1. Cylinder Valve
and Gauge
2. Pressure Regulator
3. Nitrogen Cylinder
4. Pressure Gauge
(0 to 36 kg/cm@ =
0 to 400 psig)
5. Bleed-Off Valve
6. 1/4 inch Connection

Figure 6-16 High Pressure Switch Testing


T--354

6--10

8 Put unit back in service under normal load and check


head (discharge) pressure.
Detailed Procedure:
1. Drain and flush the water circuit of the condenser
coil. If scale on the tube inner surfaces is accompanied by slime, a thorough cleaning is necessary
before de-scaling process can be accomplished.
2. To remove slime or mud, use Aluminum Cleaner
164. Mix 170 grams (6 ounces) per 3.785 liters (1
U.S. gallon) of water. Mix cleaner in one half the
volume of water, while stirring, and then add remaining water. Warm this solution and circulate through
the tubes until all slime and mud has been removed.
3. After cleaning, flush tubes thoroughly with fresh
clean water.
4. Prepare a 15% by volume solution for de-scaling by
diluting Oakite compound No. 32 with water. This is
accomplished by slowly adding 0.47 liter (1 U.S. pint)
of the acid (Oakite No. 32) to 2.8 liters (3 U.S. quarts)
of water.

6.12 WATER-COOLED CONDENSER CLEANING


The water-cooled condenser is of the shell and coil type
with water circulating through the cupro-nickel coil. The
refrigerant vapor is admitted to the shell side and is
condensed on the outer surface of the coil.
Rust, scale, and slime on the water-cooling surfaces
inside of the coil interfere with the transfer of heat,
reduce system capacity, cause higher head pressures
and increase the load on the system.
By checking the leaving water temperature and the
actual condensing temperature, it can be determined if
the condenser coil is becoming dirty. A larger than
normal difference between leaving condensing water
temperature and actual condensing temperature,
coupled with a small difference in temperature of
entering and leaving condensing water, is an indication
of a dirty condensing coil.
To find the approximate condensing temperature, with
the unit running in the cooling mode, install a gauge 0 to
36.2kg/cm@ (0 to 500psig) on the compressor discharge
service valve.
Example: Discharge pressure is 10.3kg/cm2
(146.4psig). Referring to Table 6--8 (R-134a pressure/
temperature chart), the 10.3kg/cm2 (146.4psig) value
converts to 43_C (110_F).
If the water-cooled condenser is dirty, it may be cleaned
and de-scaled by the following procedure:
a. Turn unit off and disconnect main power.
b. Disconnect water pressure switch tubing by loosening the two flare nuts. Install one-quarter inch flare
cap on water-cooled condenser inlet tube (replaces
tubing flare nut). De-scale tubing if necessary.

WARNING
Oakite No. 32 is an acid. Be sure that the
acid is slowly added to the water. DO NOT
PUT WATER INTO THE ACID -- This will
cause spattering and excessive heat.

WARNING
Wear rubber gloves and wash the solution
from the skin immediately if accidental contact occurs. Do not allow the solution to
splash onto concrete. PUT WATER INTO
THE ACID -- this will cause spattering and
excessive heat.

What You Will Need:


1. Oakite Aluminum Cleaner 164, available as a powder in 20kg (44lb) pails and 205kg (450lb) drums.
2. Oakite composition No. 32, available as a liquid in
cases, each containing 3.785 liters (4 U.S. gallon)
bottles and also in carboys of 52.6kg (116lbs) net.
3. Fresh clean water.
4. Acid proof pump and containers or bottles with rubber hose.
NOTE
When Oakite compound No. 32 is being used
for the first time, the local Oakite Technical Service representative should be called in for assistance in planning the procedure. They will
advise the reader on how to do the work with a
minimum dismantling of equipment, estimate
the time and amount of compound required,
preparation, how to control and conclude the
de-scaling operation by rinsing and neutralizing
equipment before putting it back into service.

5. Fill the tubes with this solution by filling from the bottom. See Figure 6-17.
NOTE
It is important to provide a vent at the top for
escaping gas.
6. Allow the Oakite No. 32 solution to soak in the tube
coils for several hours, periodically pump-circulating
it with an acid-proof pump.
An alternate method may be used whereby a pail
(see Figure 6-18) filled with the solution and attached to the coils by a hose can serve the same purpose by filling and draining. The solution must contact the scale at every point for thorough de-scaling.
Air pockets in the solution should be avoided by regularly opening the vent to release gas. Keep flames
away from the vent gases.
7. The time required for de-scaling will vary, depending
upon the extent of the deposits. One way to determine when de-scaling has been completed is to
titrate the solution periodically, using titrating equipment provided free by the Oakite Technical Service
representative. As scale is being dissolved, titrate
readings will indicate that the Oakite No. 32 solution
is losing strength. When the reading remains
constant for a reasonable time, this is an indication
that scale has been dissolved.

Summary of Procedure:
1 Drain water from condenser tubing circuit.
2. Clean water tubes with Aluminum Cleaner 164 to
remove mud and slime. Clean water tubes with
Oakite No. 22 to remove mud and slime.
3 Flush.
4 De-scale water tubes with Oakite No. 32 to remove
scale.
5 Flush.
6 Neutralize.
7 Flush.
6--11

T--354

Oakite Aluminum Cleaner 164 thru the tubes to


neutralize. Drain this solution.
10.Flush the tubes thoroughly with fresh water.
NOTE
If the condenser cooling water is not being used
as drinking water or is not re-circulated in a
closed or tower system, neutralizing is not
necessary.

7
6
4

3
9

11. Put the unit back in service and operate under normal load. Check the head pressure. If normal, a thorough de-scaling has been achieved.

10
1

What You Can Do For Further Help:

11
12

1. Pump support
2. Tank
3. Suction
4. Pump
5. Priming Connection
(Centrifugal pump
50 gpm at 35 head)
6. Globe valves

7. Vent
8. Close vent pipe valve
when pump is running
9. Condenser
10. Remove water
regulating valve
11. Return
12. Fine mesh screen

Figure 6-17 Water-Cooled Condenser Cleaning -Forced Circulation

On units equipped with a water-cooled condenser, if the


sight glass appears to be flashing or bubbles are
constantly moving through the sight glass when the
suction modulation valve is fully open, the unit may have
a low refrigerant charge or the filter-drier could be
partially plugged.
1. Test for a restricted or plugged filter-drier by feeling
the liquid line inlet and outlet connections of the drier
cartridge. If the outlet side feels cooler than the inlet
side, then the filter-drier should be changed.
2. Check the moisture-liquid indicator if the indicator
shows a high level of moisture, the filter-drier should
be replaced.

b. To Replace Filter-Drier:

1. Pump down the unit (refer to paragraph 6.4 and


replace filter-drier.

2. Evacuate the low side in accordance with paragraph


6.6.
3. After unit is in operation, inspect for moisture in system and check charge.

3 to 4

6.14 THERMOSTATIC EXPANSION VALVE (TXV)

2.
3.
4.
5.

The thermostatic expansion valve (see Figure 2-2) is an


automatic device that maintains constant superheat of
the refrigerant gas leaving the evaporator, regardless of
suction pressure.
The valve functions are:

Approximately 5
Condenser
Vent pipe
1 pipe

1. Automatic control of the refrigerant flow to match the


evaporator load.
2. Prevention of liquid refrigerant entering the
compressor.
Unless the valve is defective, it seldom requires
maintenance other than periodic inspection to ensure
that the thermal bulb is tightly secured and properly
insulated. See Figure 6-19.

Figure 6-18 Water-Cooled Condenser Cleaning -Gravity Circulation


8. When de-scaling is complete, drain the solution and
flush thoroughly with water.
9. Following the water flush, circulate a 56.7 gram (2
ounce) per 3.785 liter (1 U.S. gallon) solution of
T--354

6.13 FILTER-DRIER

a. To Check Filter-Drier:

1. Fill condenser with


cleaning solution. Do
not add solution more
rapidly than vent can
exhaust gases caused
by chemical action.

Contact the Engineering and Service Department of the


OAKITE PRODUCTS CO., 675 Central Avenue, New
Providence, NJ 07974 U.S.A. (or visit www.oakite.com)
for the name and address of the service representative
in your area.

NOTE
TXV Bulb Clamp is soldered to the suction line.
6--12

The difference is the superheat of the suction gas.


Determine the average superheat It should be 4.5 to
6.7_C (8 to 12_F).

6.14.2 Expansion Valve Replacement


a. Removing the Expansion Valve
NOTES
1.
2.
3.
4.
5

Suction Line
Thumbscrew
TXV Bulb Clamp
TXV Bulb
Foam Insulation

1. The TXV is a hermetic valve and does not


have
adjustable
superheat
(See
Figure 6-20).
5

2. All connections on the hermetic TXV are


bi-metallic, copper on the inside and
stainless on the outside.

Figure 6-19 Thermostatic Expansion Valve Bulb

3. All joints on the hermetic TXV (inlet, outlet


and equalizer lines) are brazed.

6.14.1 Checking Superheat


NOTE
Proper superheat measurement should be
completed at -18_C (0_F) container box temperature where possible.

4. Bi-metallic connections heat up very quickly.

a. Open the upper right (EFM#1) access panel (see


Figure 2-1) to expose the expansion valve.
b. Attach a temperature sensor near the expansion
valve bulb and insulate. Make sure the suction line is
clean and that firm contact is made with the sensor.
c. Connect an accurate gauge to the service port directly upstream of the suction modulating valve
d. Set the temperature set point to -18_C (0_F) and run
unit until conditions stabilize.
e. The readings may cycle from a high to a low reading.
Take readings of temperature and pressure every
three to five minutes for a total of 5 or 6 readings
f. From the temperature/pressure chart (Table 6-8), determine the saturation temperature corresponding to
the evaporator outlet test pressures at the suction
modulation valve.
g. Subtract the saturation temperatures determined in
step f from the temperatures measured in step e.

6
1
2
5
3
4
1.
2.
3.
4.
5.
6.

Hermetic Thermostatic Expansion Valve (TXV)


Non-adjustable Superheat Stem
Equalizer Connection
Inlet Connection
Outlet Connection
Hermetic Expansion Valve Bulb
Figure 6-20 Thermostatic Expansion
Valve

Braze Rod (Sil-Phos = 5.5% Silver, 6% Phosphorus)


Copper Tube
(Apply heat for 10-15 seconds)

Use of a wet cloth is not necessary due to rapid


heat dissipation of the bi-metallic connections

Bi-metallic Tube Connection


(Apply heat for 2-5 seconds)

Figure 6-21 Hermetic Thermostatic Expansion Valve Brazing Procedure

6--13

T--354

1. Pump down the unit per paragraph 6.4.


2. If TXV replacement is to be performed from the front
of the unit, open the upper right (EFM#1) access
panel (see Figure 2-1) and remove the evaporator
fan motor.
3. Remove cushion clamp that secures the valve body
to the bracket.
4. Unbraze the equalizer connection (1/4), the outlet
connection (5/8), and then the inlet connection
(3/8). See Figure 6-21. Be careful to protect the insulation on the heaters and their wires.
5. If TXV replacement is being performed from the front
of the unit, remove the access panel for the bulb.
6. Open the insulation flap. Flap is secured with Velcro
(Item 3, Figure 6-22).
7. Loosen the thumb screw and slide the bulb, out by
pulling it towards the front of the unit.

6.15.1 Evaporator Coil Replacement


a. Pump unit down (refer to paragraph 6.4).
b. With power OFF and power plug removed, remove
the screws securing the panel covering the evaporator section (upper panel).
c. Disconnect the defrost heater wiring.
d. Disconnect the defrost temperature sensor (see
Figure 2-2) from the coil.
e. Remove middle coil support.
f. Remove the mounting hardware from the coil.

g. Unsolder the two coil connections, one at the distributor and the other at the coil header.
3

h. After defective coil is removed from unit, remove


defrost heaters and install on replacement coil.
i. Install coil assembly by reversing above steps.

2
5

j. Leak check connections per paragraph 6.5. Evacuate


the unit per paragraph 6.6, and add refrigerant charge
per paragraph 6.7.

6.15.2 Evaporator Heater Replacement

1. Hermetic Expansion Valve Bulb


2. Insulation
3. Insulation Flap
4. Velcro strip
5. Bulb Clamp
6. Thumb Screw
Figure 6-22 Hermetic Thermostatic Expansion
Valve Bulb Location
b. Installing the Expansion Valve
1. Braze inlet connection to inlet line (see Figure 6-21).
2. Braze outlet connection to outlet line.
3. Braze the equalizer connection to the equalizer line.
4. Reinstall the cushion clamp.
5. Thread the thermal bulb through the opening above
the evaporator coil (see Figure 2-2), and slide it under the strap and secure the thumb screw. Close the
insulation flap. Reinstall bulb access panel.
6. Check superheat (refer to step 6.14.1).

The heaters are wired directly back to the contactor. If a


heater failure occurs during a trip, the heater set
containing that heater may be disconnected at the
contactor.
The next pre-trip will detect that a heater set has been
disconnected and indicate that the failed heater should
be replaced. To replace a heater, do the following:
a. Before servicing unit, make sure the unit circuit breakers (CB-1 & CB-2) and the start-stop switch (ST) are
in the OFF position, and that the power plug is
disconnected.
b. Remove the upper back panel.
c. Determine which heater(s) need replacing by checking resistance of each heater set. Refer to paragraph
2.3 for heater resistance values. Once the set containing the failed heater is determined, cut the splice
connection and retest to determine the actual failed
heater(s).

6.15 EVAPORATOR COIL AND HEATER


ASSEMBLY
The evaporator section, including the coil, should be
cleaned regularly. The preferred cleaning fluid is fresh
water or steam. Another recommended cleaner is
Oakite 202 or similar, following manufacturers
instructions.
The drain pan hose is routed behind the condenser fan
motor and compressor. The drain pan line must be open
to ensure adequate drainage.

T--354

d. Remove hold-down clamp securing heater(s) to coil.


e. Lift the bent end of the heater (with the opposite end
down and away from coil). Move heater to the side
enough to clear the heater end support and remove.

6--14

6.16 EVAPORATOR FAN AND MOTOR ASSEMBLY


The evaporator fans circulate air throughout the
container by pulling air in through the bottom of the unit.
The air is forced through the evaporator coil where it is
either heated or cooled and then discharged out the top
of the refrigeration unit into the container. The fan motor
bearings are factory lubricated and do not require
additional grease.

5
1

WARNING
Always turn OFF the unit circuit breakers
(CB-1 & CB-2) and disconnect main power
supply before working on moving parts.
8

a. Remove upper access panel (See Figure 2-1) by removing mounting bolts and T.I.R. locking device.
Reach inside of unit and remove Ty-Rap securing
wire harness loop.

b. Remove the two lower mounting bolts that secure the


motor-fan assembly to the unit. Loosen the two upper
bolts as the motor mount upper holes are slotted.

4
(STS / SRS)
1--- probe; 3--- wire

c. Remove motor, fan, and wiring from unit. Place fan


motor and fan on a support. Remove the wiring and
fan.
d. Lubricate fan motor shaft with a graphite-oil solution
(Never-Seez). Apply thread sealer (Loctite H, brown
in color) to the two fan set screws. Install fan on motor.
The evaporator fan locating dimension is shown in
Figure 6-23.
8.74 CM
(3.44 INCHES)

Figure 6-23 Evaporator Fan Locating Dimension

1. Bracket Motor Mount


2. Bolt, Hex Head,
3/8-16 x 1.00 lg
3. Washer, Lock, 3/8
4. Washer, Flat, 3/8

e. Connect wiring per applicable wiring diagram and


install motor and fan assembly in unit. Apply power,
momentarily, to check fan rotation. If fan spins backwards, refer to section 2.3 for two-speed motors.
f. Replace access panel, making sure panel does not
leak. Make sure that the T.I.R. locking device is lockwired.

5. Key, 3/16 square x


1--3.8 x 1.00 lg -- SST
6. Evaporator Fan
7. Bracket, Mounting
8. Shim (if required)
9. Evaporator Motor

Figure 6-24 Evaporator Fan Assembly

6--15

T--354

is good, the needle will make a rapid swing toward zero


resistance and then gradually swing back toward a very
high resistance reading.
If the capacitor has failed open, the ohmmeter needle
will not move when the meter probes touch the
terminals. If the capacitor is shorted, the needle will
swing to zero resistance position and stay there.
2. Capacitor analyzer:
The function of the analyzer is to read the microfarad
value of a capacitor and to detect insulation breakdown
under load conditions. The important advantages of an
analyzer are its ability to locate capacitors that have
either failed to hold their microfarad ratings or those that
are breaking down internally during operation. It is also
useful in identifying capacitors when their microfarad
rating marks have become unreadable.

6.17 EVAPORATOR FAN MOTOR CAPACITORS


The evaporator fan motors are of the permanent-split
capacitor type. The motor is equipped with one
capacitor used in the high speed circuit, and another
capacitor is used for the low speed circuit.
6.17.1 When To Check For a Defective Capacitor
a. Fan motor will not change speed. For example: in the
conventional perishable mode, the motors should run
in high speed. In the economy perishable mode they
should switch speeds and in the frozen mode, the motors should run in low speed.
NOTE
The evaporator fan motors will always start in
high speed.
b. Motor running in wrong direction (after checking for
correct wiring application).
c. Motor will not start and IP-EMs are not open.

6.18 EVAPORATOR SECTION CLEANING


Containers and Container units that are exposed to
certain fumigants may develop visible surface
corrosion. This corrosion will show up as a white powder
found on the inside of the container and on the reefer
unit evaporator stator and fan deck.
Analyses by Carrier Transicold environmental
specialists have identified the white powder as
consisting predominantly of aluminum oxide. Aluminum
oxide is a coarse crystalline deposit most likely the result
of surface corrosion on the aluminum parts within the
container. If left untreated over time, it may build up in
thickness and eventually flake as a light--weight white
powder.
The surface corrosion of aluminum is brought about by
exposure to chemicals such as sulfur dioxide and
possibly other fumigants that are commonly used for
fumigation and protection of some perishable cargo
such as grapes, for example. Fumigation is the process
by which a chemical is released into an enclosed area to
eliminate infestations of insects, termites, rodents,
weeds and soil--born disease.
Typically any aluminum oxide that becomes detached
from evaporator fan stators will be blown into the wet
evaporator coil where it will be caught and then flushed
out of the unit during routine defrost cycles.
However, it is still highly recommended that after
carrying cargo subject to fumigation procedures, that
the inside of the unit be thoroughly cleansed prior to
reuse.
Carrier Transicold has identified a fully biodegradable
and environmentally safe alkaline cleaning agent
(Tri--Powr HD) for the unit. This will assist in helping to
remove the corrosive fumigation chemicals and
dislodging of the corrosive elements.
This cleaner is available from the Carrier Transicold
Performance Parts Group (PPG) and can be ordered
through any of the PPG locations; Part Number
NU4371--88.
As a general safety precaution, before using this
product, refer to and retain the Material Safety Data
(MSDS) sheet. This document can be found at:

6.17.2 Removing the Capacitor

WARNING
Make sure power to the unit is OFF and
power plug disconnected before servicing
capacitor(s).

WARNING
With power OFF discharge the capacitor
before disconnecting the circuit wiring.
Capacitors must be discharged properly before testing.
To discharge the capacitor, first turn the unit power OFF
and disconnect the unit power plug. Then place a
20,000 ohm, 2 watt resistor across the terminals of the
capacitor for approximately 30 seconds.
The capacitors are located on the motor and may be
removed by two methods:
1. If container is empty, open upper rear panel of the
unit.
2. If container is full, turn the unit power OFF and disconnect power plug. Remove the evaporator fan
motor access panel (see Figure 2-1). For removal of
the evaporator fan assembly, refer to section 6.16.
6.17.3 Checking the Capacitor
If the capacitor is suspected of malfunction, you may
choose to simply replace it. Direct replacement requires
a capacitor of the same value. Two methods for
checking capacitor function are:
1. Volt-ohmmeter set on RX 10,000 ohms.
Connect ohmmeter leads across the capacitor
terminals and observe the meter needle. If the capacitor

T--354

www.nucalgon.com/products/coil_cleaners_tripower.htm

6--16

d. If capacity or control cannot be maintained, turn unit


OFF, then back ON. This will reset the valve in the
event the controller lost communication with the
valve, and may correct the problem.

Prior to Cleaning:
-- Always wear goggles, gloves and work boots.
-- Avoid contact with skin and clothing, and avoid
breathing mists.

NOTE
Carefully listen to the valve. During reset, the
valve will make a ratcheting noise that may be
heard or felt as it is attempting to close. If this
can be heard or felt, it indicates that the controller and drive module are attempting to close the
valve, and may serve as a quick indication that
the drive module is in working order.

-- When mixing, add water to the sprayer first, then the


cleaner.
-- ALWAYS provide for proper ventilation when cleaning
indoor evaporator coils (rear doors must be open).
-- Be aware of surroundings -- food, plants, etc., and the
potential for human exposure.
-- Always read directions and follow recommended
dilution ratios. More is not always better. Using
non--diluted cleaner is not recommended.

e. During the first few minutes of unit operation, compressor reliability enhancement logic (CREL) may be
in effect. This places the valve at a 21% staging position and is sufficient to drive the temperature of the
supply probe down several degrees during this interval.

Cleaning Procedure:
a. Remove the upper evaporator access panel inside of
the unit.
b. Spray the surface with water before applying the
cleaning solution. This helps the cleaner work better.

f. After the CREL time-out has been met, the valve will
start responding to the control logic and open or close
relative to the demand. Scrutinize the unit operation
for a few minutes. While in pulldown, the unit will open
the SMV to a maximum discharge pressure of 325
psig in high ambient conditions, or as much as the
current setting and control logic will allow. The current
level should be high. A lower discharge pressure will
be seen in lower ambient temperatures. Once the unit
has reached set point, the SMV will go into control
mode. Both the discharge/suction pressures, and
current draw will go significantly lower. Once below
set point, the suction pressure should go into a vacuum within several minutes. Should the operation differ as mentioned, the SMV, controller, or wiring, may
be faulty.

c. Liberally apply the prepared cleaner solution (5 parts


water and 1 part cleaner).
d. Allow the cleaner to soak in for 5 to 7 minutes.
e. Assess area for rinsing. Follow all local regulations regarding disposal of waste water.
f. Thoroughly rinse the cleaner and surrounding area,
floor, etc. When rinsing where heavy foaming solution
is present, it is very important to take the time to thoroughly rinse the equipment and surroundings.
g. Always rinse the empty coil cleaner bottle, cap tightly
and dispose of properly.

g. Check for correct wire location at the stepper motor


plug and the environmental connector (EC). Make
sure that the wires terminate in accordance with the
wire markings (addresses).

6.19 SUCTION MODULATION VALVE (SMV)


On start up of the unit, the valve will reset to a known
open position. This is accomplished by assuming the
valve was fully open, driving it fully closed, resetting the
percentage open to zero, then opening to a known 21%
staging position.

h. Attach a manifold gauge set (refer to paragraph 6.3).


If the unit is operating in the perishable mode, proceed to step i. If the unit is operating in the frozen
mode, proceed to step j.
i. Perishable operation: If the operation of the unit is in
question, place the set point to approximately 6_C
(11_F) less than the current box temperature, so the
unit goes into pulldown. Run the unit for approximately one minute. Record readings on gauges and current draw. The current draw and pressures should go
up. Place set point 0.5_C (0.9_F) above current box
temperature to fully modulate valve, and run for
approximately one minute.

2-1/8 inch Nut

NOTE
The unit may shut off for a short time. Wait until
the unit self starts and sufficient time has
elapsed to cause the valve to fully modulate.

Figure 6-25 Suction Modulation Valve (SMV)


6.19.1 Pre-check Procedure
a. Check unit for abnormal operation.
b. Check charge. If refrigerant is low repair as required
and again check operation.

Record new gauge readings and current draw. The


suction pressure should go into a vacuum and the
current draw should have gone down. If little or no
change to the suction pressure or current draw occurs, this is an indication of a malfunctioning SMV.

c. If sufficient capacity cannot be maintained or unit is


tripping excessively on high pressure switch (HPS) in
high ambients, check coils and clean if required.
6--17

T--354

j. Frozen operation: In frozen mode the valve tends to


stay open as much as possible. Again, this is dependent upon current limit setting and control logic. Turn
the unit OFF and ON, as in the perishable mode, and
watch the gauges. The valve will run at 21% open if
CREL logic is active, and will open to maximum allowable after this. Depending on ambient conditions,
there should be an increase in suction pressure and
current draw as the valve opens. However, at times,
this may be difficult to fully determine.

5. If the valve is determined to be faulty after completing the above steps, perform a low side pump down.
Remove valve powerhead assembly, and replace
with a NEW valve powerhead assembly, torque nut
to 35 ft-lb, evacuate low side, and open all service
valves.

k. If the unit still does not operate properly, stop unit and
proceed to the following step to check out the SMV
system.

DO NOT disassemble piston from NEW suction modulating valve powerhead assembly. Doing so may result in damage to piston.

CAUTION

6.19.2 Checking the Stepper Valve


a. Checking with ohmmeter

6.19.3 Checking the Controller

Disconnect the 4-pin connector to the stepper SMV.


With a reliable digital ohmmeter, check the winding
resistance. In normal ambient, the valve should have 72
to 84 ohms measured on the red/green (a-b terminals)
and on the white/black (c-d terminals) leads. If an infinite
or zero reading occurs, check connections and replace
the motor. If near normal or normal reading occurs,
proceed to step 6.19.3 to check out the controller.

a. Turn unit OFF.


b. With voltmeter set to read 20 volts DC, attach the positive lead to MC1 of the 4-pin connector and the negative lead to the TP9. Turn ON unit and watch the volt
meter. After a short delay, the reading should remain
unchanged at 0 volts. If 5VDC, check jumper wire
from MC1 to MC8 is in place; if not, install and retest.

b. Checking with SMA-12 portable stepper drive tester

6.19.4 Emergency Repair Procedures

The SMA-12 portable stepper drive tester (Carrier


Transicold P/N 07-00375-00) is a battery--operated
stepper drive that will open and close the SMV, allowing
a more thorough check of the motor.

In the event that the SMV system has a failure and


replacement components are not readily available, the
system can be bypassed by removing the valve piston.
To remove the piston, do the following:

To check operation:

a. Perform a low side pump down (refer to paragraph


6.4).

1. Stop the unit, disconnect the 4-pin connector from


the stepper module to the valve (see Figure 6-25)
and attach the SMA-12 stepper drive to the connector going to the valve.

b. Remove SMV powerhead by loosening the 2-1/8


inch diameter nut (see Figure 6-25) to relieve any
pressure and then sliding the powerhead out.

2. Set the SMA-12 pulse per second (PPS) to one PPS


and either open or close valve. Each LED should
light sequentially until all four are lit. Any LED failing
to light indicates an open on that leg, which indicates
a poor connection or an open coil. Repair or replace
as required to achieve proper operation.

c. Remove the piston by loosening the Allen screw and


removing the piston and screw.
d. Install the powerhead assembly (without the piston)
and torque to 35 to 40 foot-lbs.
e. Open all valves.

3. Restart unit, set the step rate to 200 PPS on SMA-12


for the valve, and close stepper valve while watching
the suction gauge. Within one minute the suction
pressure will go into a vacuum. This is an indication
that the valve is moving.

f. Start the unit.


g. Adjust the suction service valve so that the approximate temperature OR current limit is maintained.
For perishable loads, it is recommended that the adjustment be made so that the available capacity is
slightly larger than the load. The unit will cycle OFF
and ON.

4. If no change in suction pressure is detected, check


for resistance (refer to step 6.19.2), and check connections for proper continuity and retest. If the valve
is functioning, and all connections and motor resistance are good, check the drive module (refer to step
6.19.3).

T--354

h. Once repair parts become available, repair as


required.

6--18

6.21 AUTOTRANSFORMER
If the unit does not start, check the following:
a. Make sure the 460VAC (yellow) power cable is
plugged into the receptacle (item 3, Figure 4-1) and
locked in place.
b. Make sure that circuit breakers CB-1 and CB-2 are in
the ON position. If the circuit breakers do not hold in,
check voltage supply.

6.20 DPRV CHECK PROCEDURE


The discharge pressure regulating valve (DPRV) is
designed to maintain a minimal level of pressure within
the compressor. Refer to paragraph 2.2 for valve
setting.
The following procedure can be used to perform a
functional check:

c. There is no internal protector for this transformer design; therefore, no checking of the internal protector is
required.
d. Using a voltmeter and with the primary supply circuit
ON, check the primary (input) voltage (460VAC).
Next, check the secondary (output) voltage
(230VAC). The transformer is defective if output voltage is not available.

a. Install a high pressure gauge at the discharge service


valve.
b. Install another high pressure gauge at the liquid line
service valve.
c. Run unit with -18_C (0_F) set point.
d. After five minutes, read both gauges and subtract the
liquid line pressure from the discharge pressure. This
is the actual differential pressure.

6.22 CONTROLLER
6.22.1 Handling Controller

Replacement Differential

Pressure (psi)

e. Using the ambient temperature and the chart below,


determine the replacement differential pressure.

CAUTION
Do not remove wire harnesses from controller unless you are grounded to the unit
frame with a static safe wrist strap.

70
60

CAUTION

REPLACE DPRV

50

Unplug all controller connectors before


performing arc welding on any part of the
container.

40
30
20

DO NOT REPLACE DPRV

The guidelines and cautions provided herein should be


followed when handling the Controller/DataCORDER
module. These precautions and procedures should be
implemented when replacing the module, when doing
any arc welding on the unit, or when service to the
refrigeration unit requires handling and removal of the
controller.
Figure 6-27 Controller Section of the Control Box
a. Obtain a grounding wrist strap (Carrier Transicold PN
07-00304-00) and a static dissipation mat (Carrier
Transicold PN 07-00304-00). The wrist strap, when
properly grounded, will dissipate any potential buildup on the body. The dissipation mat will provide a static-free work surface on which to place and/or service
the controller.
b. Disconnect and secure power to the unit.
c. Place strap on wrist and attach the ground end to any
exposed unpainted metal area on the refrigeration
unit frame (bolts, screws, etc.).
d. Carefully remove the controller. Do not touch any of
the electrical connections if possible. Place the module on the static mat.

10
0
30

40

50

60

70

80

90

100

110

120

Ambient Temperature (F)

Figure 6-26 DPRV Replacement Value Chart


NOTE
1. This test should not be run below -1.1_C
(30_F) or above 49_C (120_F). If the actual
differential pressure is close to the
replacement differential pressure, it is
recommended that the readings be taken
several times at two minutes intervals.
2. If valve cap is found to be leaking it may be
replaced using cap & O-ring (Carrier Part
Number 40-50024-00).

e. The strap should be worn during any service work on


the controller, even when it is placed on the mat.

6--19

T--354

6.22.2 Controller Troubleshooting

TP 8
This test point is not applicable to the units covered
herein.
TP 9
This test point is the chassis (unit frame) ground
connection.
TP 10
This test point enables the user to check if the heat
termination thermostat (HTT) contact is open or closed.
6.22.3 Controller Programming Procedure
To load new software into the module, the programming
card (PCMIA) is inserted into the programming/
software port.

A group of test points (TP) (see Figure 6-27) are


provided on the controller for troubleshooting electrical
circuits (see schematic diagram, section 7). A
description of the test points follows:
1

CAUTION
The unit must be OFF whenever a programming card is inserted or removed from the
controller programming port.

1.

Controller Software
Programming Port
Mounting Screw

2.

3.

Controller

4.

Test Points

a. Procedure for loading operational software


1. Turn unit OFF via start-stop switch (ST).
2. Insert software/programming card containing the following (example) files into the programming/software port (see Figure 6-27):
menuDDMM.ml3 -- This file allows the user to select
a file/program to upload into the controller.
cfYYMMDD.ml3 -- Multi-configuration file.
3. Turn unit ON via start-stop switch (ST).
4. The display module will display the message ruN
COnFG. If a defective card is being used, the display
will blink the message bAd CArd. Turn start-stop
switch OFF and remove the card.
5. Press the UP or DOWN arrow key until display
reads, LOAd 51XX for Recip.
6. Press the ENTER key on the keypad. The display
will alternate to between PrESS EntR and rEV
XXXX.
7. Press the ENTER key on the keypad.
8. The display will show the message Pro SoFt. This
message will last for up to one minute.
9. Press the ENTER key on the keypad.
10.The display module will go blank briefly, then read
Pro donE when the software is loaded. If a problem
occurs while loading the software, the display will
blink the message Pro FAIL or bad 12V. Turn
start-stop switch OFF and remove the card.
11. Turn unit OFF via start-stop switch (ST).
12.Remove the programming card from the programming/software port and return the unit to normal operation by placing the start-stop switch in the ON
position.
13.Turn power on and wait 15 seconds. The status LED
will flash quickly and there will be no display. The
controller is loading the new software into memory.
This takes about 15 seconds.
When complete the controller will reset and power up
normally.

NOTE
Use a digital voltmeter to measure AC voltage
between TPs and ground (TP9), except for
TP8.
TP2
This test point enables the user to check if the internal
protector for the compressor motor (IP-CP) or high
pressure switch is open.
TP3
This test point enables the user to check if the water
pressure switch (WP) contact is open or closed.
TP 4
This test point enables the user to check if the internal
protector for the condenser fan motor (IP-CM) is open or
closed.
TP 5
This test point enables the user to check if the internal
protectors for the evaporator fan motors (IP-EM1 or
IP-EM2) are open or closed.
TP 6
This test point enables the user to check if the controller
water tank heater relay (TQ) is open or closed.
TP 7
This test point is not used in this application.
T--354

6--20

aging has been designed to protect the controller


from both physical and electrostatic discharge damage during storage and transit.

14 Wait for default display -- setpoint on the left and control temperature on the right.
15.Confirm software is correct using keypad code select 18 to view Cd18 XXXX.

b.Installation:

16.Turn power off. Operational software is loaded.

Install the module by reversing the removal steps.

b. Procedure for loading configuration software:

Torque values for mounting screws (item 2, see


Figure 6-27) are 0.23mkg (20 inch-pounds). Torque
value for the connectors is 0.12mkg (10 inch-pounds).

1. Turn unit OFF using start-stop switch (ST).


2. Insert software/programming PCMCIA card containing the following (example) files into the programming/software port (see Figure 6-27):

6.22.5 Battery Replacement


If required, use tool 07-00418-00.

menuDDMM.ml3 -- This file allows the user to select


the file/program to upload into the controller.

6.23 TEMPERATURE SENSOR SERVICE

cfYYMMDD.ml3 -- Multi-configuration file.

Procedures for service of the Return Recorder, Return


Temperature, Supply Recorder, Supply Temperature,
Ambient, Defrost Temperature, Compressor Discharge
and Compressor Suction temperature sensors are
provided in the following sub paragraphs.

recp51XX.ml3 -- Controller software program for


recip units.
3. Turn unit ON using start-stop switch (ST).

6.23.1 Sensor Checkout Procedure

4. The display module will display the message ruN


COnFG. If a defective card is being used, the display
will blink the message bAd CArd. Turn start-stop
switch OFF and remove the card.

To check a sensor reading, do the following:


a. Remove the sensor and place in a 0_C (32_F) ice-water bath. The ice-water bath is prepared by filling an
insulated container (of sufficient size to completely
immerse bulb) with ice cubes or chipped ice, then filling voids between ice with water and agitating until
mixture reaches 0_C (32_F) measured on a laboratory thermometer.

5. Press the ENTER key on the keypad.


6. The display module will go blank briefly and then display 541 00. Based on the operational software
installed.
7. Press the UP or DOWN ARROW key to scroll
through the list to obtain the proper model dash number. (If a defective card is being used, the display will
blink the message bAd CArd. Turn start-stop
switch OFF and remove the card.)

b. Start unit and check sensor reading on the control


panel. The reading should be 0_C (32_F). If the reading is correct, reinstall sensor; if it is not, continue with
the following:
c. Turn unit OFF and disconnect power supply.

8. Press the ENTER key on the keypad.

d. Refer to paragraph 6.22 and remove controller to gain


access to the sensor plugs.

9. When the software loading has successfully completed, the display will show the message EEPrM
donE. (If a problem occurs while loading the software, the display will blink the message Pro FAIL or
bad 12V. Turn start-stop switch OFF and remove
the card.)

e. Using the plug connector marked EC, that is connected to the back of the controller, locate the sensor
wires (RRS, RTS, SRS, STS, AMBS, DTS, CPDS
OR CPSS as required). Follow those wires to the connector and using the pins of the plug, measure the
resistance. Values are provided in Table 6-1.

10.Turn unit OFF using start-stop switch (ST).


11. Remove the programming card from the programming/software port and return the unit to normal operation by placing the start-stop switch in the ON
position.

Table 6-1 Sensor Temperature/Resistance Chart


Temperature
Centigrade

12.Confirm correct model configuration using the keypad to choose code select 20 (CD20). The model
displayed should match the unit serial number plate.

0
25

6.22.4 Removing and Installing the Controller


a. Removal:
1. Disconnect all front wire harness connectors and
move wiring out of way.
2 The lower controller mounting is slotted. Loosen the
top mounting screw (see Figure 6-27) and lift up and
out.
3 Disconnect the two back connectors (EC) and remove module.
4 When removing the replacement controller from its
packaging, note how it is packaged. When returning
the old controller for service, place it in the packaging
in the same manner as the replacement. The pack-

Temperature
Fahrenheit

Resistance
(Ohms)

RRS, RTS, SRS and STS:


32
32,650 +/--91
77
10,000 +/--50
AMBS and DTS

32

32,650 + 1720
- 1620

25

77

10,000 + 450
- 430

Due to the variations and inaccuracies in ohmmeters,


thermometers, or other test equipment, a reading
within 2% of the chart value would indicate a good
sensor. If a sensor is defective, the resistance reading will usually be much higher or lower than the resistance values given.
6--21

T--354

e. Strip back insulation on all wiring 6.3mm (1/4--inch).

6.23.2 Sensor Replacement


a. Turn unit power OFF and disconnect power supply.

f. Slide a large piece of heat shrink tubing over the


cable, and place small pieces of heat shrink tubing,
one over each wire, before adding crimp fittings as
shown in Figure 6-29.

b. For two wire sensors, cut cable 5cm (2 inches) from


shoulder of defective sensor and discard the defective sensor only. For 3-wire sensors, cut at 23cm (9
inches). Slide the cap and grommet off well mounted
sensor and save for possible reuse. Do not cut the
grommet.

g. If required, slide the cap and grommet assembly onto


the replacement sensor. If the replacement sensor is
of a larger diameter than the original, a different grommet may be required.

c. If required, prepare the replacement sensor by cutting sensor wire(s) back 40mm (1-1/2 inch). For
3-wire sensors, the black wire should be cut at the
middle length and the red/white wire cut to the shorter
length (See Figure 6-28).

h. Slip crimp fittings over dressed wires (keeping wire


colors together). Make sure wires are pushed into
crimp fittings as far as possible and crimp with crimping tool.

d. Prepare the cables by cutting wires to the opposite of


the sensor (See Figure 6-29).
When installing a single wire color two wire sensor,
cut one wire of existing two wire cable 40 mm (1-1/2
inch) shorter than the other wire.

i. Solder spliced wires with a 60% tin and 40% lead


Rosincore solder.

When replacing two single sensors with a combination (3-wire) sensor, the black wires of the cables
should be cut to the same length and the red wire of
one cable cut to the shorter length.

j. Slide heat shrink tubing over splice so that ends of


tubing cover both ends of crimp as shown in
Figure 6-29.
k. Heat tubing to shrink over splice. Make sure all seams
are sealed tightly against the wiring to prevent moisture seepage.

When replacing a original 3-wire sensor, cut the black


wire to the middle length and the red wire to the shorter length.
Sensor

l. Slide large heat shrink tubing over both splices and


shrink.

40mm (1--1/2 inch)

CAUTION

6.3mm (1/4--inch)

Mounting Stud Type

Do not allow moisture to enter wire splice


area as this may affect the sensor resistance.

40 mm (1-1/2 inches)
6.3--mm (1/4--inch)

m. Reinstall sensor, refer to paragraph 6.23.3.


Sensor

NOTE
The P5 Pre-Trip test must be run to inactivate
probe alarms (refer to paragraph 4.8).

Bulb Type
Figure 6-28 Sensor Types

REPLACEMENT 2--WIRE TO 2--WIRE OR 3--WIRE TO 3--WIRE

Cable

Sensor
REPLACEMENT FOR DUAL, SINGLE SENSOR CONFIGURATION

Sensor

Heat Shrink Tubing

Large Heat Shrink Tubing

Figure 6-29 Sensor and Cable Splice


T--354

6--22

Cables
RED
BLACK
RED/WHITE

6.23.3 Sensor Re-Installation

6.24 VENT POSITION SENSOR (VPS)

a. Sensors RTS/RRS

The vent position sensor (VPS) determines the position


of the fresh air vent in near real-time via the function
code 55.
The fresh air VPS alarm (AL50) will occur if the sensor
reading is not stable for five minutes or if the sensor is
outside of its valid range (shorted or open). This can
occur if the vent is loose or the panel is defective. To
confirm a defective panel, assure that the wing nut is
secure and then power cycle the unit.
The alarm should immediately go inactive. Check the
four-minute stability requirement. If the alarm reoccurs
after the four minutes and the panel was known to have
been stable, then the panel should be replaced.
If the alarm immediately reappears as active, the panel
should be replaced.
Upper VPS:
In order to replace the VPS, the panel must be removed
and replaced with another upper fresh air panel
equipped with VPS.
Upon installation, a new VPS assembly requires
calibration as follows:
1. Rotate the vent to the 0 CMH/ CFM position.
2. Code select 45 will automatically be displayed.
Press the Enter key and hold for five seconds.
3. After the enter key has been pressed, the display will
read CAL (for calibration).
4. Press the ALT MODE key and hold for five seconds.
5. After the calibration has been completed, Code 45
will display 0CMH / CFM.
6. Calibrate sensor:
a.Use a multi-meter set to 200k ohms. Connect lead to
VPS connector.
b.Turn the gear wheel on the motor all the way to the
right (clockwise) until it stops.
c.Adjust the gear wheel counter clockwise until the
meter reads 6.5k ohms (approximately).
d. Install the VPS slide door so that the door is flush
against the bottom rail, the motor gear and the door
teeth are meshed, and the gear wheel does not
move from the set position.
7. Position slide assembly back on to studs and reinstall two washers and two nuts that secure slide assembly.
8. Stake the ends of the two studs on panel assembly
with wire cutters so that nuts will not be easily removed.
9. Reinstall Partlow box assembly if equipped, or access panel.
10.Reinstall condenser fan guard.
If the optional DataCORDER battery pack is being used
and the charge is too low to enable recording during the
power off period of less than thirty days, the pen tip will
move to below the inner chart ring for the period when
NO data was recorded by the DataCORDER.
If the power has been OFF for more than thirty days, the
recorder will NOT re-synchronize (the chart will not
advance to present time), the pen tip will move to the
currently recorded temperature, and the recorder will
resume normal temperature recording.

To properly position a return sensor, the sensor must be


fully inserted into the probe holder. This positioning will
give the sensor the optimum amount of exposure to the
return air stream, and will allow the Controller to operate
correctly. Insufficient probe insertion into the probe
holder will result in poor temperature control due to the
lack of air flow over the sensor.
It is also necessary to ensure that the probe tip does not
contact the evaporator back panel. The design
minimum clearance of 6mm (1/4--inch) should be
maintained (see Figure 6-30).
Sensor
Wires

Cap and Grommet


Assembly
Evaporator
Back Panel

Probe
Holder
Return
Air
Stream

Return Sensor

6mm
(1/4--inch)

Figure 6-30 Return Sensor Positioning


b. Sensor STS/SRS
Reinstall the supply sensor as shown in Figure 6-31. For
proper placement of the supply sensor, be sure to
position the seal section of the sensor against the side of
the mounting clamp.
Evaporator Grille
Combination
Sensor (Mount in
Either Clamp)

Seal

Mounting
Clamp

Figure 6-31 Supply Sensor Positioning


c. Sensor DTS
The DTS sensor must have insulating material placed
completely over the sensor to insure the coil metal
temperature is sensed.
6--23

T--354

6.25 ELECTRONIC TEMPERATURE RECORDER

NOTE

The microprocessor based temperature recorder is


designed to interface with the DataCORDER to log
temperature with time. The electronic recorder will
automatically record the return air, supply air, or both,
based on the setting of temperature controller
configuration code CnF37, refer to Table 3-4. The
recorder reads and records data from the Controller in
present time, under normal operating conditions.
The recorder will STOP when the power is OFF, and the
pen tip will remain at the last recorded temperature on
the chart. When power is applied and the power off
period is less than thirty days, the recorder will retrieve
the logged data from the DataCORDER for the power
off period and record it onto the chart. Thereafter, the
recorder will resume normal temperature recording.
If the optional DataCORDER battery pack is being used
and the charge is too low to enable recording during the
power off period of less than thirty days, the pen tip will
move to below the inner chart ring for the period when
NO data was recorded by the DataCORDER.
If the power has been OFF for more than thirty days, the
recorder will NOT re-synchronize (the chart will not
advance to present time), the pen tip will move to the
currently recorded temperature, and the recorder will
resume normal temperature recording.
6.25.1Replacing the Recorder

Failure to press the change chart button when


changing a chart with the power OFF may result
in the chart advancing when power is applied.
d. Install a new chart. Make sure the chart center hole is
placed over the center hub and the chart edges are
behind the four hold down tabs (item 9).
e. Mark todays date, container number, and other required information on the new chart and install under
hold down tabs.
f. Replace the chart nut loosely. Rotate the chart until
the correct day is aligned with the start arrow and
hand tighten the chart nut.
g. Gently lower the stylus arm until the pen tip (item 4)
comes in contact with the chart.

CAUTION
Do not allow the recorder stylus to snap
back down. The stylus arm base is spring
loaded, and damage may occur to the chart,
or the stylus force may be altered.
DO NOT move the stylus arm up and down
on the chart face. This will result in damage
to the stylus motor gear.

a. Turn power to the unit OFF.


b. Open the recorder door (see Figure 6-32, item 1).
c. Locate the connector below the recorder, and
squeeze the ears together to disconnect the plug
(item 6).
d. Remove the four mounting screws (item 8) and remove the recorder.
e. Install the new recorder by reversing the above steps.

6.25.3Rezeroing the Recording Thermometer


NOTE
Use chart CTD P/N 09-00128-00 (F)
Use chart CTD P/N 09-00128-01 (C)
a. Press the Calibration button (item 7, Figure 6-32)
on the bottom of the recorder. The pen tip will drive
fully down scale, then move upscale to the chart ring
at 0 degrees C (32 degrees F), and stop.

6.25.2Changing the Chart


NOTE
To prevent recorder corrosion, it is important to
assure the door is securely closed at all times
after completing the chart change.

b. If the tip of the pen (item 4) is on the 0C (32F) chart


ring the recorder is in calibration, proceed to step c.
If the tip of the pen is NOT on the 0C (32F) chart
ring, the operator must loosen the two screws on the
bottom of the stylus arm to adjust the pen tip
manually to the 0C (32F) chart ring. Tighten the
screws when adjustment is complete.

a. Lift the stylus (item 5, Figure 6-32) by grasping the


arm near the base, and pulling the arm away from the
chart until it snaps into its retracted position.
b. Remove the chart retaining nut (item 10), remove the
used chart, and record todays date on the old chart.
c. Press the Change Chart button (item 2).

T--354

c.

6--24

Press the calibration button and the pen will position


itself to the correct temperature reading.

3
2

4
5

10
9
8
7
6

1.
2.
3.
4.
5.

Recorder Door
Change Chart Button
Recorder Box
Pen Tip
Stylus Arm

6. Connector
7. Calibration Button (Located underneath)
8. Mounting Screws, #10-24 x 7/16 inches long
9. Hold Down Tab
10. Chart Retaining Nut
Figure 6-32 Electronic Partlow Temperature Recorder

6--25

T--354

6.27.3 Chips and Holes


Chips and holes in the control box are repaired using a
piece of aluminum or stainless steel to cover the
damaged area. The material can be cut to suit and
riveted in place. An adhesive sealant must be used to
make the repair watertight. The adhesive sealant
(Sikaflex 221) is included in Crack Repair Kit Carrier
Transicold part number 76-00724-00SV (see
Table 6-2). Do not use an acetone based silicone
sealant, which can be identified by a vinegar-like odor.
a. To make up the patch, cut a piece of aluminum or
stainless steel so that it will overlap the damaged area
by at least 40mm (1--1/2) on all sides.
b. Choose rivet locations and drill the rivet holes in the
corresponding locations on the control box and patch
piece.
c. Apply the adhesive sealant around the damaged area
to form a seal between the control box and the patch
piece.
d. Rivet the patch piece in place.
e. File smooth any rough edges (including rivets) that
may come into contact with wires.
6.27.4 Inserts
The threaded brass inserts that are molded into the
control box will need to be replaced if the threads
become stripped or if the insert becomes loose. The
inserts and epoxy are contained in repair kit, Carrier
Transicold part number 76-50084-00 (see Table 6-3).
There are 6 different inserts used in the control box.
Refer to Figure 6-34 for the locations of the various
inserts.

6.26 MAINTENANCE OF PAINTED SURFACES


The refrigeration unit is protected by a special paint
system against the corrosive atmosphere in which it
normally operates. However, should the paint system
be damaged, the base metal can corrode. In order to
protect the refrigeration unit from the highly corrosive
sea atmosphere or if the protective paint system is
scratched or damaged, clean area to bare metal using a
wire brush, emery paper, or equivalent cleaning
method. Immediately following cleaning, spray or brush
on zinc-rich primer. After the primer has dried, spray or
brush on finish coat of paint to match original unit color.
6.27 COMPOSITE CONTROL BOX REPAIRS
6.27.1 Introduction
This procedure provides instructions for repair of the
Carrier Transicold composite control box. Damage to
the control box may be in the form of a chip or hole, a
crack, a damaged thread insert or damage to the door
hinge inserts. Generally, the object of the repair must be
to ensure sufficient strength is restored to the damaged
area and the repair must keep the box water tight.
Information on repair kits and repair procedures for each
type of damage is provided in the following paragraphs.
Ambient temperature must be above 7_C (45_F) for
proper curing of epoxy repairs.
6.27.2 Cracks
Cracks in the control box are repaired using a fiberglass
patch over the damaged area. Materials required are
included in the Fiberglass Patch Kit supplied with Crack
Repair Kit, Carrier Transicold part number
76-00724-00SV (see Table 6-2).

NOTE
An epoxy application gun is also needed,
Carrier Transicold part number 07-00391-00.

a. The surface must be clean and dry. Roughen the surface with sandpaper to ensure a good bond.

The damaged insert must be removed from the control


box. Table 6-4 identifies the drill size and drill depth to be
used for each insert. A stop ring should be used on the
drill bit to limit the depth.
a. Center the drill bit on the insert and drill to the prescribed depth.
b. Remove the chips from the drilled hole.
c. Mix the two component epoxy and fill the hole halfway
to the top with epoxy.
d. Press the insert in until it is flush with the surface.
e. Wipe away any excess epoxy. The part is ready for
service after the bond material has hardened and is
tack free (approximately 20 minutes).

b. Cut the fiberglass cloth to allow a 25mm (1 inch) overlap around the area to be repaired.
c. Stretch and position the cloth over the area to be repaired and secure it with masking tape.
d. Make up sufficient epoxy glue to cover the cloth by
mixing equal parts of resin and hardener. Saturate the
cloth with the epoxy glue, spreading evenly.
e. Remove the tape and overlap the edge of the cloth
approximately 6 to 12mm (1/4 to 1/2) with glue.
f. Epoxy will dry in 45-60 minutes. When completely
cured (12 hours), use sandpaper to smooth edges of
the patch.

T--354

6--26

6.27.5 Door Hinge Inserts


If the door hinges have been pulled from the control box,
drill and reinstall the hinge as shown in Figure 6-33 and
described in the following steps:
Materials needed:
1. Cut two square pieces of 3mm thick (1/8--inch) aluminum or stainless steel approximately 40mm (1-5/8) square. These squares will serve as backing
plates.
2. Two nuts, bolts (10-24 x 1) and washers for each insert that needs repair.
a. Drill a 1/4 hole in the center of each square backing
plate.
b. Pass the bolts through the bolts holes in the door
hinge, then through the control box at the location
where the hinge insert pulled out.
c. From inside the control box, slide the backing plates
over the bolts and secure in place with the washers
and nuts.
Figure 6-33 Door Hinge Repair
Table 6-2 Crack, Chip and Hole Repair Kit
ITEM

1
2
3
4

DESCRIPTION

PART NUMBER

Crack Repair Kit -- Includes


. . . Fiberglass Patch Kit (Loctite FK-98 or 80265)
. . . Sikaflex 221 Adhesive Sealant (Sikaflex 232-361)
. . . Instruction Sheet

76-00724-00SV
76-00724-00Z
02-00067-02Z
98-02339-00

Qty
1
10
10
10

Table 6-3 Insert Repair Kit


ITEM

1
2
3
4
5
6
7
8
9
10

DESCRIPTION

PART NUMBER

Insert Repair Kit -- Includes


. . . Insert - 17.53 x 9.91mm (..690 x .390in) 1/4-20 Threads
. . . Insert - 15.88 x 6.35mm (.625 x .250in) 10-24 Threads
. . . Insert - 25.15 x 7.54mm (.990 x .297in) 10-24 Threads
. . . Insert - 10.16 x 9.53mm (.400 x .375in) 10-24 Threads
. . . Insert - 12.7 x 9.91mm (.5 x .390in) 1/4-20 Threads
. . . Insert - 9.53 x 6.76mm (.375 x .266in) 10-24 Threads
. . . Durabond Epoxy E20-HP (Loctite 29314)
. . . Static Mixing Tube (Loctite 983440)
. . . Instruction Sheet

76-50084-00
34-06231-01
34-06231-03
34-06231-04
34-06231-05
34-06231-06
34-06231-07
02-00082-00
07-00390-00
98-02338-00

Qty
1
10
10
10
10
10
10
1
1
1

Note: Insert repair procedures require use of an Application Gun, Carrier part number 07-00391-00 (Loctite 983435).
Table 6-4 Drill Information
ITEM

INSERT PART NUMBER

1
2
3
4
5
6

34- 06231- 01
34- 06231- 03
34- 06231- 04
34- 06231- 05
34- 06231- 06
34- 06231- 07

DRILL SIZE AND DEPTH

10.3mm x 17.8mm deep (.404in. x .700in. deep)


6.8mm x 16.3mm deep (.266in. x .640in. deep)
7.9mm x 25.4mm deep (.3125in. x 1.0in. deep)
6.9mm (.270in.) Drill completely through.
10.3mm (.404in.) Drill completely through.
6.8mm (.266in.) Drill completely through.

6--27

T--354

Figure 6-34 Insert Location

T--354

6--28

07

03

03

04

05

06

INSERT PART NUMBERS 34-06231-## WHERE THE ## IS AS INDICATED

05

07

01

03

03

03

04

03

6.28 COMMUNICATIONS INTERFACE MODULE


INSTALLATION

6.29 POWER FACTOR CORRECTOR


CAPACITORS (PFC)
The power factor corrector capacitors are of the
permanent-split capacitor type. There are a total of
three capacitors with discharge resistors enclosed in a
single case.
a. When to check for a defective capacitor
The capacitors assist in correcting current draw by the
compressor. If one or more of the capacitors is faulty,
there will be an imbalance in current. In addition, the
power consumption of the unit will increase.
b. Removing the capacitor

CB1

WARNING

Communications
interface Module

Make sure power to the unit is OFF and


power plug disconnected before removing
capacitor(s).

Figure 6-35 Communications Interface Installation


Units with communication interface module provision
have the required wiring installed. The provision wiring
kit (part number 76-00685-00), includes three
pre-addressed wires installed between the circuit
breaker and communication interface module locations.
These wires are to be connected to the module and
circuit breaker to allow the module to communicate over
the power system. To install the module, do the
following:

WARNING
Before removing the capacitors the
terminals must be checked for voltage with
a multimeter. The discharge resistors
installed on the unit (capacitors) should
bring the voltage to a safe level in a minute.
However, there may be a broken resistor
that retains voltage for a longer period, it is
highly recommended to wait 15 minutes
and to check for voltage.

WARNING
The unit power plug must be disconnected
to remove power from circuit breaker CB1
a. CB1 is connected to the power system, see wiring
schematic. Ensure that the unit power is off AND that
the unit power plug is disconnected.
b. Open control box, see Figure 6-35 and remove low
voltage shield. Open high voltage shield.
c. Remove the circuit breaker panel, with circuit breaker, from the control box.
d. Locate wires CB21 / CIA3, CB22 / CIA5 and CB23 /
CIA7 that have been tied back in the wire harness.
Remove the protective heat shrink from the ends of
the wires.
e. Attach the three wires as addressed to the LOAD side
of the circuit breaker.
f. Refit the circuit breaker panel.
g. Fit the new RMU into the unit.

If the capacitors require discharging, first, turn the unit


power OFF and disconnect the unit power plug. Then,
place a 20,000 ohm, 2 watt resistor across the terminals
of the capacitor for approximately 30 seconds.
1. The capacitors are located on the unit sidewall
above the evaporator fan deck and may be removed
by two methods:
S

If container is empty -- Open upper rear panel of


the unit. The capacitors will be on the right and
may be serviced after checking discharge.

If container is full -- Remove the upper fresh air


makeup vent.

c. Checking the capacitor


If the capacitor is suspected of malfunction, you may
choose to simply replace it. Direct replacement requires
a capacitor of the same value. Two methods for
checking capacitor function are:

h. Remove plugs CIA, CIB and CID from the wiring harness and attach to the module.
i. Replace the low voltage shield.

6--29

T--354

Table 6-5 Recommended Bolt Torque Values

1. Volt-ohmmeter set on RX 10,000 ohms.


Connect ohmmeter leads across the capacitor
terminals and observe the meter needle. If the capacitor
is good, the needle will make a rapid swing toward zero
resistance and then gradually swing back toward a very
high resistance reading. The reading should read about
330,000 ohms (for a good capacitor) due to the
discharge resistors.
If the capacitor has failed open, the ohmmeter needle
will not move when the meter probes touch the
terminals. If the capacitor is shorted, the needle will
swing to zero resistance position and stay there.

TORQUE
BOLT DIA. THREADS
FREE SPINNING
#4
40
5.2in-lbs
#6
32
9.6in-lbs
#8
32
20in-lbs
#10
24
23in-lbs
1/4
20
75in-lbs
5/16
18
11ft-lbs
3/8
16
20ft-lbs
7/16
14
31ft-lbs
1/2
13
43ft-lbs
9/16
12
57ft-lbs
5/8
11
92ft-lbs
3/4
10
124ft-lbs

2. Capacitor analyzer:
The function of the analyzer is to read the microfarad
value of a capacitor and to detect insulation breakdown
under load conditions. The important advantages of an
analyzer are its ability to locate capacitors that have
failed to hold their microfarad ratings, or those that are
breaking down internally during operation. It is also
useful in identifying capacitors when their microfarad
rating marks have become unreadable.

N.m
.6
1.0
2.25
2.6
8.4
1.52
2.76
4.28
5.94
7.88
12.72
17.14

NONFREE SPINNING (LOCKNUTS ETC.)


1/4
20
82.5in-lbs
9.3
5/16
18
145.2in-lbs
16.4
3/8
16
22.0ft-lbs
30
7/16
14
34.1ft-lbs
46
1/2
13
47.3ft-lbs
64
9/16
12
62.7ft-lbs
85
5/8
11
101.2ft-lbs
137
3/4
10
136.4ft-lbs
168

Table 6-6 Wear Limits For Compressors

PART NAME
MAIN BEARING
Main Bearing Diameter
Main Bearing Journal Diameter
PUMP END
Main Bearing Diameter
Main Bearing Journal Diameter
CONNECTING ROD
Piston Pin Bearing
CRANKPIN DIAMETER
Throw
THRUST WASHER (Thickness)
CYLINDERS
Bore
Piston (Diameter)
Piston Pin (Diameter)
Piston Ring Gap
Piston Ring Side Clearance

T--354

FACTORY MAXIMUM
inches

mm

1.6268

41.3207

FACTORY MINIMUM
inches

1.6233
1.3760
1.3768

41.2318

34.9504
1.3735

34.8869

0.6878
1.3735
1.070
0.1520

17.4701
34.8869
27.1780
03.8608

34.9707

1.072
0.154

27.2288
3.9116

2.0010

50.8254

0.013
0.002

mm

00.3302
00.0508

6--30

1.9860
0.6873
0.0050
0.0010

50.4444
17.4574
00.1270
00.0254

MAXIMUM WEAR
BEFORE REPAIR
inches
mm
.0020
.0020

0.0508
0.0508

.0020
.0020
.0020
.0010
.0025

0.0508
0.0508
0.0508
0.0254
0.0635

.0250

0.6350

.0020
.0020
.0010
.0250
.0020

0.0508
0.0508
0.0254
0.6350
0.0508

Table 6-7 Compressor Torque Values


TORQUE RANGE

SIZE
DIAMETER
(inches)
1/16
1/8
1/4
1/4

THREADS
PER INCH
27 (pipe)
20 (pipe)
20 (pipe)
20

1/4

28

5/16

18

3/8

16

7/16
5/8
5/8
#10
1-1/2

14
11
18
32
18 NEF

USAGE
ft-lb

N.m

8 - 12
6 -- 10
20 -- 25
10 -- 12
12 -- 15
12 -- 16
6 -- 10
12 -- 16

11 -- 16
8 -- 13
27 -- 34
13 -- 16
16 -- 20
16 -- 22
8 -- 13
16 -- 22

16 -- 20

2 -- 27

20 -- 30

27 -- 41

40 -- 50

55 -- 70

55
25
60
4
35

76 -- 83
34 -- 41
83 -- 103
5 -- 8
48 -- 62

------

60
30
75
6
45

Pipe Plug -- Crankshaft


Oil Return Check Valve -- Crankcase
Pipe Plug -- Gauge Connection
Connecting Rod cap screw
Baffle Plate -- Crankcase
Side Shield
Oil Pump Drive Segment
Unloader Valve
Cover Plate -- Plate End
Bearing Head
Terminal Block Cap Screws
Suction Valve
Discharge Valve
Pump End Bearing Head
Bottom Plate -- Crankcase Compressor Foot
Cylinder Head
Motor End Cover -- Crankcase
Crankshaft
Oil Bypass Plug -- Crankcase
Oil Pump Drive Segment
Oil Level Sight Glass

NEF -- National Extra Fine

6--31

T--354

Table 6-8 R-134a Temperature - Pressure Chart


Temperature

Vacuum

/hg

-40

-40

14.6

49.4

-35

-37

12.3

-30

-34

-25

Pressure

bar

psig

kPa

kg/cm@

bar

37.08

0.49

28

-2

24.5

168.9

1.72

1.69

41.6

31.25

0.42

30

-1

26.1

180.0

1.84

1.80

9.7

32.8

24.64

0.33

32

27.8

191.7

1.95

1.92

-32

6.7

22.7

17.00

0.23

34

29.6

204.1

2.08

2.04

-20

-29

3.5

11.9

8.89

0.12

36

31.3

215.8

2.20

2.16

-18

-28

2.1

7.1

5.33

0.07

38

33.2

228.9

2.33

2.29

-16

-27

0.6

2.0

1.52

0.02

40

35.1

242.0

2.47

2.42

45

40.1

276.5

2.82

2.76

50

10

45.5

313.7

3.20

3.14

55

13

51.2

353.0

3.60

3.53

60

16

57.4

395.8

4.04

3.96

65

18

64.1

441.0

4.51

4.42

70

21

71.1

490.2

5.00

4.90

75

24

78.7

542.6

5.53

5.43

80

27

86.7

597.8

6.10

5.98

85

29

95.3

657.1

6.70

6.57

90

32

104.3

719.1

7.33

7.19

95

35

114.0

786.0

8.01

7.86

100

38

124.2

856.4

8.73

8.56

105

41

135.0

930.8

9.49

9.31

110

43

146.4

1009

10.29

10.09

115

46

158.4

1092

11.14

10.92

120

49

171.2

1180

12.04

11.80

125

52

184.6

1273

12.98

12.73

130

54

198.7

1370

13.97

13.70

135

57

213.6

1473

15.02

14.73

140

60

229.2

1580

16.11

15.80

145

63

245.6

1693

17.27

16.93

150

66

262.9

1813

18.48

18.13

155

68

281.1

1938

19.76

19.37

Temperature

cm/hg kg/cm@

Temperature

Pressure

psig

kPa

kg/cm@

bar

-14

-26

0.4

1.1

0.03

0.03

-12

-24

1.2

8.3

0.08

0.08

-10

-23

2.0

13.8

0.14

0.14

-8

-22

2.9

20.0

0.20

0.20

-6

-21

3.7

25.5

0.26

0.26

-4

-20

4.6

31.7

0.32

0.32

-2

-19

5.6

36.6

0.39

0.39

-18

6.5

44.8

0.46

0.45

-17

7.6

52.4

0.53

0.52

-16

8.6

59.3

0.60

0.59

-14

9.7

66.9

0.68

0.67

-13

10.8

74.5

0.76

0.74

10

-12

12.0

82.7

0.84

0.83

12

-11

13.2

91.0

0.93

0.91

14

-10

14.5

100.0

1.02

1.00

16

-9

15.8

108.9

1.11

1.09

18

-8

17.1

117.9

1.20

1.18

20

-7

18.5

127.6

1.30

1.28

22

-6

19.9

137.2

1.40

1.37

24

-4

21.4

147.6

1.50

1.48

26

-3

22.9

157.9

1.61

1.58

T--354

6--32

Note: Curves to be used as troubleshooting guide only for model series 69NT40 with
fresh air makeup vent closed, unit powered on 460VAC/60Hz and SMV 100% open.

(Bar) psig
(22.0) 320
(20.7) 300
(19.3) 280
(17.9) 260

35_F (1.7_C)
Box

(16.6) 240
(15.2) 220
(13.8) 200
(12.4) 180
(11.0) 160
(9.7) 140
(8.3) 120
(6.9) 100
(5.5)

80
60
(15.6)

70
(21.1)

80
(26.7)

90
(32.2)

100
(37.8)

110
(43.3)

120 (_F)
(48.9) (_C)

Ambient Air Temperature

(Bar) psig
(22.0) 320
(20.7) 300
(19.3) 280
(17.9) 260
(16.6) 240
(15.2) 220
(13.8) 200
(12.4) 180
(11.0) 160
(9.7) 140

0_F (-17.8_C)
Box

(8.3) 120
(6.9) 100
(5.5)

80
60
(15.6)

70
(21.1)

80
(26.7)

90
(32.2)

100
(37.8)

Ambient Air Temperature

110
(43.3)

120
(48.9)

(_F)
(_C)

Compressor Discharge Pressure Versus Ambient Air Temperature at Stable Box Temperature

Figure 6-36 R-134a Compressor Pressure and Motor Current Curves Versus Ambient Temperature
(Sheet 1 of 2)
6--33

T--354

(Bar)
(.97)

psig
14

(.83)

12

(.69)

10

(.55)

(.41)

(.28)

(.14)

(0)

(-.14)

--2

(-.28)

--4

(-.41)

--6
60
(15.6)

35_F (1.7_C) Box

0_F (-17.8_C) Box

70
(21.1)

80
(26.7)

90
(32.2)

100
(37.8)

110
(43.3)

120 (_F)
(48.9) (_C)

Ambient Air Temperature


Compressor Suction Pressure Versus Ambient Air Temperature at Stable Box Temperature

17
16
15

35_F (1.7_C) Box

14
13
12
11

0_F (-17.8_C) Box

10
9
8
60
(15.6)

70

80

90

100

(21.1)

(26.7)

(32.2)

(37.8)

110
(43.3)

120
(48.9)

(_F)
(_C)

Ambient Air Temperature


Compressor-Motor Current Versus Ambient Air Temperature At Stable Box Temperature

Figure 6-36 R-134a Compressor Pressure and Motor Current Curves Versus Ambient Temperature
(Sheet 2 of 2)
T--354

6--34

SECTION 7
ELECTRICAL WIRING SCHEMATICS
7.1 INTRODUCTION
This section contains Electrical Schematic and Wiring Diagrams, the diagrams are presented as follows:
Figure 7-1 provides the legend for use with all figures.
Figure 7-2 provides the basic schematic diagram for units with single evaporator fan capability and VPS.
Figure 7-3 & Figure 7-4 provide wiring diagrams for units with single evaporator fan capability and VPS.
Figure 7-5 provides the basic schematic diagram for units with normal evaporator fan capability, TransFresh and
Crankcase Heater.
Figure 7-6 & Figure 7-7 provide wiring diagrams for units with normal evaporator fan capability, TransFresh and
Crankcase Heater.

LEGEND
SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

AMBS
C
CB1
CB2

AMBIENT SENSOR (D--18)


CONTROLLER (C--16)
CIRCUIT BREAKER 460 VOLT (J--1)
OPTIONAL CIRCUIT BREAKER 230V (DVM OPTION)
TERMINAL BLOCK WHEN CB2 NOT PRESENT (D--1)

CCH
CF
CI

CRANKCASE HEATER (T--4)


CONDENSER FAN CONTACTOR (M--9, P--6)
COMMUNICATIONS INTERFACE MODULE
(OPTION) (A--4)
COMPRESSOR CONTACTOR (L--8, P--1, P--3)

F
HPS
HR
HS
HTT

FUSE (C--8, D--8, E--16, F--16, H--6, G--16)


HIGH PRESSURE SWITCH (H--8)
HEATER CONTACTOR (M--13, P--4)
HUMIDITY SENSOR (G--19)
HEAT TERMINATION THERMOSTAT (H--12)

IC
IP

INTERROGATOR CONNECTOR (OPTION) (T--19)


INTERNAL PROTECTOR (E--8, G--9, M--10, M--12)
(E--9, E--11, G--11, H--10)
IN--RANGE LIGHT (OPTION) (L--13)
PROBE RECEPTACLE (USDA OPTION)
(F--19, M--20, N--20, P--20)
REMOTE MONITORING RECEPTACLE
(OPTION) (L--8, L--9, L--13)
RETURN RECORDER SENSOR (L--19)
RETURN TEMPERATURE SENSOR (C--18)

CH

IRL
PR

C -- L
CM
CP
CPDS

COOL LIGHT (OPTION) (L--11)


CONDENSER FAN MOTOR (G--10, T--6)
COMPRESSOR MOTOR (E--8, T--2)
COMPRESSOR DISCHARGE SENSOR
(TEMP.) (OPTION) (C--18)

CPSS
CPT
CR
CS

COMPRESSOR SUCTION SENSOR


(TEMP.) (OPTION) (E--18)
CONDENSER PRESSURE TRANSDUCER (H--19)
CHART RECORDER (OPTION) (A--14)
CURRENT SENSOR (M--2)

DHBL
DHBR
DHML
DHMR

DEFROST HEATER -DEFROST HEATER -DEFROST HEATER -DEFROST HEATER --

DHTL
DHTR
DL
DPT

DEFROST HEATER -- TOP LEFT (R--3)


DEFROST HEATER -- TOP RIGHT (T--4)
DEFROST LIGHT (OPTION) (M--14 / L--8)
DISCHARGE PRESSURE TRANSDUCER
(OPTION) (K--19)

DTS
DVM
DVR
E

DEFROST TEMPERATURE SENSOR (D--18)


DUAL VOLTAGE MODULE (OPTION) (D--1)
DUAL VOLTAGE RECEPTACLE (OPTION) (F--2)
EVAPORATOR FAN CONTACTOR
(HIGH SPEED) (G--11, H--12, J--10, K--11, P--7, P--10)

TH
TI
TL
TN
TP

EM
S

EVAPORATOR FAN MOTOR (L--10, L--12, T--6, T--8)


EVAPORATOR FAN CONTACTOR
(LOW SPEED) (G--10, H--11, J--11, K--12, R--8, R--11)
EVAPORATOR FAN CONTACTOR
(HIGH SPEED) (L--11, M--10, P--7, P--8)

TR
TRANS
TRC
TV

EF
EM
ES

RM
RRS
RTS

BOTTOM LEFT (R--4)


BOTTOM RIGHT (T--4)
MIDDLE LEFT (R--4)
MIDDLE RIGHT (T--4)

SMV
SPT
SRS
ST
STS
TC
TCC
TE
TF
TFC

EVAPORATOR FAN MOTOR (D--11, F--11, T--8, T--10)


EVAPORATOR FAN CONTACTOR
(LOW SPEED) (M--11, R--7)

VPS
WCR
WP

STEPPER MOTOR SUCTION MODULATION


VALVE (T--14)
SUCTION PRESSURE TRANSDUCER (OPTION)
(J--20)
SUPPLY RECORDER SENSOR (OPTION) (B--18)
START -- STOP SWITCH (K--5)
SUPPLY TEMPERATURE SENSOR (B--18)
CONTROLLER RELAY -- COOLING (K--8)
TRANSFRESH COMMUNICATIONS CONNECTOR
(OPTION) (D--7)
CONTROLLER RELAY (HIGH SPEED
EVAPORATOR FANS) (F--10) (K--11)
DEFROST RELAY (K--14) (K--8)
TRANSFRESH CONTROLLER (OPTION) (G--7)
CONTROLLER RELAY (HEATING) (K--13)
INRANGE RELAY (K--13)
CONTROLLER RELAY (COOL LIGHT) (K--11)
CONTROLLER RELAY (CONDENSER FAN) (K--9)
TEST POINT (E--10, F--9, J--8, J--9, J--13, M--14)
(F--10, J--8, J--10, J--11, J--12, M--13)
TRANSFORMER (M--3)
AUTO TRANSFORMER 230/460 (OPTION) (D--2)
TRANSFRESH REAR CONNECTOR (OPTION) (E--7)
CONTROLLER RELAY (LOW SPEED
EVAPORATOR FANS (F--12) (K--11)
VENT POSITION SENSOR (UPPER) (OPTION) (N--14)
WETTING CURRENT RESISTER (OPTION) (J--10)
WATER PRESSURE SWITCH (OPTION) (E--9)

Figure 7-1 LEGEND


7--1

T-354

BASED ON 62--66686--00

Figure 7-2 SCHEMATIC DIAGRAM -- Units with Single Evaporator Fan Capability & VPS

T--354

7--2

BASED ON 62--66686--00

Figure 7-3 UNIT WIRING DIAGRAM -- Units with Single Evaporator Fan Capability & VPS
(Sheet 1 of 2)
7--3

T-354

BASED ON 62--66686--00

Figure 7-4 UNIT WIRING DIAGRAM -- Units with Single Evaporator Fan Capability & VPS.
(Sheet 2 of 2)
T--354

7--4

BASED ON 62--66680--00

Figure 7-5 SCHEMATIC DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &

Crankcase Heater
7--5

T-354

BASED ON 62--66680--00

Figure 7-6 UNIT WIRING DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater (Sheet 1 of 2)
T--354

7--6

BASED ON 62--66680--00

Figure 7-7 UNIT WIRING DIAGRAM -- Units with Normal Evaporator Fan Capability, TransFresh &
Crankcase Heater (Sheet 2 of 2)
7--7

T-354

INDEX

A
Air Cooled Condenser Section, 2--4
Alarm, 3--6, 3--9, 3--12, 3--18, 3--19, 3--20, 3--21,
3--28

Controller Software, 3--3


Controller Troubleshooting, 6--20
Cracks, 6--26
Crankcase Heater, 4--5

Aluminum oxide, 6--16


Ambient sensor (AMBS), 3--24

Arctic Mode, 3--4


ARCTIC OPTION, 2--12

B
Battery Replacement, 6--21
Bulb Mode, 3--5

C
Capacitors, 6--16
Checking Superheat, 6--13
Checking the Capacitor, 6--16
Checking the Controller, 6--18

Data Reader, 3--11


DataBANKTM Card , 3--11
DataCORDER, 3--7, 3--9, 4--3
DataCORDER Alarms, 3--12
DataCORDER Communications, 3--11
DataCORDER Software, 3--1, 3--8
DataCORDER Standard Configurations, 3--9
DataReader, 3--11
Defrost Interval, 3--4
Defrost Mode, 4--8

Checking the Stepper Valve, 6--18

Defrost temperature sensor (DTS), 3--25

Chips and Holes, 6--26

Discharge pressure transducer (DPT), 3--24

Communications Interface Module, 3--11, 6--29

Display Module, 3--2

Composite Control Box, 6--26

Display Only Functions, 3--14

Compressor, 6--5
Compressor Crankcase Heater, 2--12
Compressor discharge sensor (CPDS), 3--24

DPRV CHECK PROCEDURE, 6--19


DPRV Replacement Value Chart, 6--19

Compressor Section, 2--3

Condenser Coil, 6--10


Condenser Pressure Control, 3--4
Condenser pressure transducer (CPT), 3--24

Electrical Schematic, 7--1

Configurable Functions, 3--15

Emergency Bypass, 4--9

Configuration Software, 3--3, 3--8

Emergency Defrost, 4--10

Configuration Variables, 3--13


Controller, 3--3, 6--18, 6--19
Controller Configuration Variables, 3--13

Emergency Repair Procedures, 6--18


Evacuation, 6--3

Controller Function Codes, 3--14, 3--17

Evaporator, 6--14

Controller Pre-Trip Test Codes, 3--23

Evaporator Coil Replacement, 6--14

Controller Programming, 6--20

Evaporator Fan, 1--2, 3--4, 6--15

Index--1

T-354

INDEX -- Continued

Evaporator Heater Replacement, 6--14


Evaporator Section, 2--2
EVAPORATOR SECTION CLEANING, 6--16

Key Pad, 3--2

Expansion Valve, 6--12

Keypad Function, 3--2

Expansion Valve Replacement, 6--13

Leak Checking, 6--3

Failure Action, 3--4

Logging Interval, 3--9

Filter--Drier, 6--12

Lower Air, 1--2

Fresh Air Makeup, 2--1, 4--2


Frozen Mode, 4--8

Frozen Mode -- Conventional, 3--6


Frozen Mode -- Economy, 3--6

Manifold Gauge Set, 6--1

Fumigation, 6--16

Micro-Link 3 Controller, 3--3

Function Code, 3--14, 3--15, 3--26

Microprocessor System, 3--1

Modes Of Operation, 3--4


Motor Current, 6--33

General Description, 2--1

Generator Protection, 3--4


Generic Mode, 3--8

Oil Level , 6--9


Operational Software, 3--3, 3--8

Heat Lockout, 3--4

Heater, 6--14
Heating Mode, 4--7

Painted Surfaces, 6--26

Hermetic Thermostatic Expansion Valve Brazing


Procedure, 6--13

Perishable Mode, 4--7

High Pressure Switch, 6--10


High pressure switch (HPS), 3--24

Perishable Mode -- Conventional, 3--5


Perishable Mode -- Dehumidification, 3--5
Perishable Mode -- Economy, 3--5
Power, 4--1
Pre--Trip, 3--7, 3--11, 3--22, 3--27, 4--3

Inspection, 4--1, 4--3

Probe Check, 4--5

Introduction, 1--1

Pumping Down, 6--3

Index--2

T-354

INDEX -- Continued

Refrigerant Charge, 6--4

Temperature Control, 3--4, 3--6

Refrigeration Circuit, 2--10

Temperature Recorder, 4--3, 6--24

Refrigeration Circuit Schematic, 2--11


Refrigeration System Data, 2--7
Refrigeration Unit -- Front Section, 2--1
Removing the Capacitor , 6--16
Replacing the Recorder , 6--24

Temperature Sensor, 6--21


Thermistor Format, 3--9
Thermostatic Expansion Valve Bulb, 6--13
Torque Values, 6--30, 6--31

Return Recorder Sensor (RRS), 3--17


Return Sensor Positioning, 6--23

Return temperature sensor (RTS), 3--24

Upper Air, 1--2

S
Safety and Protective Devices, 2--9

USDA, 3--11
USDA Cold Treatment Procedure, 3--12

Sensor and Cable Splice, 6--22

USDA Recording, 3--11

Sensor Configuration, 3--8

USDA Message Trip Comment, 3--11

Sensor DTS, 6--23


Sensor Replacement, 6--22

Sensor STS/SRS, 6--23


Sensors RTS/RRS, 6--23

Valve functions, 6--12

Sequence Of operation, 4--7

Vent Position Sensor (VPS), 3--17, 6--23

Service Valves, 6--1


Standard Configuration Report, 3--10

Starting, 4--3
Stopping, 4--3
Suction Modulating Valve, 6--17
Suction Modulation Valve, 3--14
Supply Recorder Sensor (SRS), 3--17

Water Cooled Condenser, 6--11


Water pressure switch (WP), 3--24
Water--Cooled Condenser Cleaning, 6--12

Supply Sensor Positioning, 6--23

Water--Cooled Condenser Section, 2--5

Surface corrosion, 6--16

Wear Limits, 6--30

Switch functions, 3--2

Wiring Diagrams, 7--1

Index--3

T-354

Carrier Transicold Division,


Carrier Corporation
Container Products Group
P.O. Box 4805
Syracuse, N.Y. 13221 U.S.A.
www.carrier.transicold.com
A member of the United Technologies Corporation family. Stock symbol UTX
2010 Carrier Corporation D Printed in U. S. A. 1210

You might also like