Starcool CI5
Starcool CI5
Starcool CI5
HiVg8ddagZ[g^\ZgVi^dcjc^iBdYZaH8B8>)%VcYH8B8>)%L8
Preface
This version of the manual is dated March 2008, edited by Maersk Container Industri AS.
All rights reserved.
This users manual is valid for software version 0240 or newer versions.
The information herein is subject to change without notice and does not represent a commitment
on any part of Maersk Container Industri AS
While the information herein is assumed to be accurate, Maersk Container Industri AS assumes no
responsibility for any errors or omissions that may appear in this documentation.
Model version
Warnings
Do not operate or maintain this refrigeration unit until you have familiarized
yourself completely with the equipment and operating of this unit by reading the
instruction in this manual.
Do not perform any welding on the unit before disconnecting the power plug.
Disconnect main power supply to unit before inspecting the interior of the con-
troller box.
The unit is charged with R134a and ester oil BSE 55. Do not use any other refrig-
erant or oil.
Do not release R134a into the atmosphere. Use recovery equipment according to
present legislation.
During maintenance please observe that R134a is operating with high and low
temperatures in combination with high pressures, which may cause personal
injuries if not handled properly.
Do not trap any liquid refrigerant inside pipes during soldering work. This may
lead to explosion of pipe.
1 of 221 pages
Item No. 810900B Operating and service manual
Contents
Preface ............................................................................................................................................................ 1
Warnings ......................................................................................................................................................... 1
Legend ............................................................................................................................................................ 6
2 of 221 pages
Item No. 810900B Operating and service manual
Indicator lights......................................................................................................................................... 26
Display.................................................................................................................................................... 26
Operation ...................................................................................................................................................... 31
Location of temperature sensors, humidity sensor and air exchange potentiometer ................................... 54
Location of pressure transmitters, high pressure switch and oil outlet port. ............................................... 55
3 of 221 pages
Item No. 810900B Operating and service manual
4 of 221 pages
Item No. 810900B Operating and service manual
5 of 221 pages
Item No. 810900B Operating and service manual
Legend
Short name Name Pfc Power used by Frequency Coverter
AirEx Air Exchange PhDir Phase Direction
Alarm Alarm Psuc Suction Pressure
AKS Danfoss pressure transmitter Ptot Power Total
Bat Battery PTI Pre Trip Inspection
CalAex Calibration value AirEx PTI Short Pre Trip Inspection Short
CalUs1 Calibration USDA sensor 1 Pwr Power
CalUs2 Calibration USDA sensor 2 RH Relative Humidity
CalUs3 Calibration USDA sensor 3 RHset Humidity Setpoint
CalCar Calibration Cargo sensor RMM Remote Monitoring Modem
(powerline communication)
CapAct Actual capacity
CapReq Requested capacity SHTV Superheat Thermo Valve
Com Communication Shp High pressure switch
ComQ Communication Quality FC SHReq Superheat Requested
Cpr Compressor T0 Calculated Evaporator
CT Cold Treatment Temperature
6 of 221 pages
Item No. 810900B Operating and service manual
Prefix Description
F Frequency
H Heater
I Current
M Motor
P Pressure
Q Power
RH Relative humidity
S Switch / contact / key
SH Super heat
T Temperature
T0 Saturated suction tem-
perature
U Voltage
V Valve
Suffix Specification
Act Actual
In Input
OH Overheat
Out Output
Req Requested
Set Setpoint
7 of 221 pages
Item No. 810900B Operating and service manual
General description
The units, models SC - MCI40 and SC - MCI40 - WC are electric powered picture
frames, cooling and heating units operating on refrigerant R134a.
The unit is designed to maintain cargo temperatures in a range from 30C (-22F) to
+30C (86F).
The unit is designed to operate in ambient temperatures from 30C (-22F) to +50C (122F).
The outer front frame is constructed of marine grade aluminium, 5000 and 6000 series, designed
to serve adequately as the container end wall.
The rear bulkhead is made of food-approved material.
The unit is designed to operate with satisfaction under sea going and environmental conditions as
specified below:
The unit consists of the following modules. Please see exploded view.
Frame module
Condenser / compressor module
Evaporator module
Evaporator fan module
The cooling system of the unit is equipped with a two stage compressor, electrically driven
through a FC.
The cooling system is also equipped with an economizer, which performs the task of sub-cooling
the liquid from receiver to evaporator, thereby increasing the cooling capacity of the cooling unit.
The evaporator and economizer are controlled by electronic expansion valves.
The equipment is designed to operate on a nominal 400/460V AC, 3 phase, 50/60 Hz, primary
power source.
An integrated dual winding transformer supplies the control circuit voltage. One winding for 24V
AC and another for 18V AC converted to 24V DC in the controller. The output voltage is dependent
on supply.
An automatic system, power supply sensing and correction, is provided to ensure the correct
direction of rotation for the fan motors. This is done regardless of the incoming phase sequence
from the primary power supply, provided that all fan motors are wired correctly.
An optional water-cooled condenser is mounted in series with the air-cooled condenser. This
water-cooled condenser allows operation of unit below deck, where no air ventilation is possible,
provided that water connections are present.
The air from the unit is delivered to the bottom of the container, with return air through the top of
the evaporator coil section (bottom air delivery).
The unit is equipped with a de-humidification function controlled by the electronic controller of
8 of 221 pages
Item No. 810900B Operating and service manual
the unit. The humidity setpoint can be set in the range from 95 65% (or 50 % with closed ven-
tilation) RH. The unit can control to the lowest level. The de-humidification function is active as
long as the temperature control is in set point range. The unit is equipped with heating elements,
mounted under the evaporator coil, for the de-humidification.
The de-humidification system is also active in economy mode.
The unit is equipped with a dual system for defrosting. There is installed a hot gas valve, in the
refrigeration system, for hot gas defrosting of the evaporator coil. Furthermore the heating ele-
ments, mounted under the evaporator coil, are energized during defrost.
This dual system for defrosting ensures a fast defrost sequence and thereby only a very small
input of heat to the container. This results in very small temperature variations for the transported
cargo, after a defrost sequence.
The dual system for defrost also ensures an even distribution of heat to the evaporator coil. The
result of this is that there is no building up of ice in corners or other places of the evaporator coil.
The two defrost systems, hot gas and heating elements, are independent. This ensures a defrost
sequence to be carried out, even with one system failing.
A demand defrost system is integrated in the software ensuring that the evaporator coil will not
ice up.
Function description
Start-up procedure
The start-up procedure ensures that the system is started safely after the following events:
Unit has been out of use
Main failures
Defrosting
PTI test
Service mode
Alarm mode
9 of 221 pages
Item No. 810900B Operating and service manual
Temperature Control
This function incorporates the container temperature controller.
This function has four modes: Pull down, Pull up, Cool, and Heat.
Gear Function
Off Everything is turned off.
Start up If cooling is required, the FC is starting at default frequency before shifting to
correct cooling mode.
PWM On/Off regulation of compressor.
CoolEco Maximum cooling capacity with use of economizer.
Heat Only the heaters are used. May also be active in hotgas mode.
Defrost Heaters are always used and hotgas valve is used if ambient temperature is
above 5C (41F).
The capacity of the unit is controlled between maximum cooling capacity (-100% capacity) and
maximum heating capacity (+100% capacity). This is done by regulation of the compressor speed
by means of the FC and the hotgas valve for minimum capacity control or on/off regulation. In
maximum capacity (+100% capacity) the unit uses the heating elements, by means of pulse width
modulation, to control the capacity.
10 of 221 pages
Item No. 810900B Operating and service manual
Below figure indicates the ranges for the capacity and compressor speed (frequency).
Compressor frequency, Hz
110 Hz (3300 rpm)
Set point Set point
line 1 line 3
20 Hz (600 rpm)
line 2
The limiter function secures that the controller operates with valid settings to protect the unit in
order to maintain the conditions for the cargo. To maintain the set point temperature, capacity
control constantly monitors and adjusts the capacity. The limiter acts as a brake to the capacity
change requests from capacity control and thereby controlling how fast the capacity can change,
so that safe operation of the unit constantly is ensured.
The limiter monitors the following parameters from the unit and generates a limiter factor for
each:
IFC, to limit the maximum current draw from the FC.
TFC, to limit the maximum internal FC temperature.
Tc, to limit the maximum condenser pressure (and temperature).
T0, to ensure a minimum evaporator pressure.
Teco, to ensure a minimum middle pressure in the compressor.
The largest of the factors is used as the active limiter. If the limiter factor is higher than the re-
quested capacity change, the capacity is actually reduced instead of increased.
If for example the ambient temperature is very high, the requested capacity may increase the FC
temperature over its limits and so the limiter will reduce the capacity until a safe and stable opera-
tion condition for the FC has been reached.
Expansion Valve
This function ensures optimum evaporator superheat (SH) and calculates the percentage of open-
ing (SHVod) and controls the valve. This function is active during compressor operation. Valve is
closed during compressor turn off.
MSS
This function searches for minimum stable superheat within the ranges SHmin and SHmax. With a
stable T0, SHset is reduced and with an unstable T0, SHset is raised.
SHact: = Tsuc T0
11 of 221 pages
Item No. 810900B Operating and service manual
Superheating
Function output is the expansion valve opening rate (Vexp).
At start-up the opening rate is 0%.
The electronic expansion valve is an on/off valve controlled on the basis of opening rate with a
constant cycle time.
MOP function
The MOP function prevents the suction pressure from getting too high.
Economizer Valve
This function ensures optimum subcooling of liquid to the evaporator and cooling of the FC.
In addition, the cooling capacity is increased, COP is enhanced and compressed gas temperature
is reduced.
Function output is the economizer valve opening rate (Veco).
Superheat control
Valve opening rate control is based on calculations.
FC cooler
This function is active during compressor operation.
Dehumidification
The dehumidification function dehumidifies air in the container by means of a heater.
This function is can only be activated if the temperature control function is active.
Dehumidification: Off
The dehumidification function is in the OFF position.
Dehumidification: Active
The heater (Hevap) is activated when RH is more than (>) RHSet and deactivated when RH is less
than (<) RHSet 3%.
The humidity set point can be set in the range 50% to 95% relative humidity. The range 50% to
64% is only possible with no fresh air - evap. ventilation in low speed. The range 65% - 95% is
possible to run with fresh air - evap. ventilation in high speed.
Dehumidification: Override
Accessing override mode if:
- Cooling demand exceeds 80% capacity.
- Large demand for heating.
- PTI
- A fatal alarm is active.
- When operating without FC.
- Manual operation is active.
- Defrosting
Other comments
12 of 221 pages
Item No. 810900B Operating and service manual
Condenser Fan
Condenser fan control will reduce condenser pressure through condenser ventilation.
The condenser pressure control also monitors the compressor outlet pressure in case of water-
cooling.
This function is activated when control is being in the automatic mode.
Air-cooled
In the air-cooled mode ventilation takes place in the following way:
Depending on the compressor outlet pressure, the fan is Off or runs in 2 different speeds: High
and Low.
The fan runs in 4 modes: Off, low-speed, high-speed and a cyclus shifting between high and low-
speed in two minutes intervals.
If Tamb is more than (>) 48C (118F) or the compressor outlet pressure remains constantly high,
the condenser fan constantly runs at high speed.
Water-cooled
If the condenser fan is constantly on for more than 1 hour, an alarm will be given.
The fan runs in 4 modes: Off, low-speed, high-speed and a cyclus shifting between high and low-
speed in two minutes intervals.
Evaporator Fan
The evaporator fan function ensures correct fan speed (high or low).
The function is active in the automatic mode.
Normal
Low speed when: In the frozen mode or
Tset is more than or equal () to 0C (32F)
No fresh air exchange
Dehumidification is turned off
Economy
The fans run at a constant low speed.
Defrost Function
Defrost function ensures regular evaporator defrosting. The function is active in automatic mode.
13 of 221 pages
Item No. 810900B Operating and service manual
In the wait mode the time is refreshed for the next defrost provided that the following conditions
are satisfied:
Compressor is running
T0 is less than (<) T0min.
Initialize
Wait until condenser temperature is above 50C (122F), however no more than 300 sec.
Execute
In this mode the actual evaporator defrosting takes place:
A Defrost start event is made in the trip log.
Cooling system termination results in compressor initiation, only ramp up mode is executed.
Evaporator fan is stopped.
Evaporator and tray heating elements are turned on.
Compressor runs at a constant frequency at 83% of full speed.
Expansion valve control is deactivated.
Hotgas valve is used to heat the evaporator from the inside with the hot gas from the compressor.
Evaporator defrosting terminates when evaporator temperature, Tevap, is above defrost termina-
tion temperature for 2 min. or upon elapse of max. defrost time.
A defrost stop event is made in the data log with the current interval and Tevap temperature.
Terminate
Terminate mode is divideable into two parts:
Evaporator re freezing preventing remaining water drops on evaporator from blowing into
container upon evaporator fan initiation.
Termination ensuring low evaporator fan speed to prevent shock boiling and to ensure that
the temperature controller takes over in a controlled way.
After termination, the unit continues normal operation again with the same setpoint temperature
as before defrost start.
General information
If the Tevap sensor is not ok, adaptive defrosting uses a reduced defrost interval compared to nor-
mal calculated defrost intervals.
Set-point alteration leads to a new calculated defrost interval, and defrost starts when the defrost
criteria is reached.
With manual defrost initiation the current defrost interval is set to default defrost interval.
Other comments
If service mode or PTI mode is selected during a defrost, the defrost mode is terminated and the
time for the next defrosting is set to the preset value as if a normal defrost end had occurred.
If the unit is shut off for some reason during a defrost and the power disappears for less than (<)
12 hours, the unit will start and try to finish the defrost again when the power returns.
If the unit is shut off for more than 12 hours, the active defrost is terminated and the defrost
function enters the wait state.
14 of 221 pages
Item No. 810900B Operating and service manual
QUEST (optional)
QUEST is a program based on a fixed protocol designed to reduce the energy consumption of the
unit, when operating in the interval -1C to +30C (30F to 86F). This energy saving is mainly
obtained by regulating the compressors on/off time and the evaporator fan speed.
Please note that when Tsup is in in the range -1C to +15C (30F to 59F) its value can vary -2C
- +1C (28F to 34F) from setpoint.
Please note that when Tsup is in in the range +15C to +30C (30F to 86F) its value can vary
-4C - +1C (25F to 34F) from setpoint.
Quest is, as default, set to either AUTO or OFF depending on customer requirements.
To deactivate QUEST:
1. Press
2. Use or to select O02 QUEST and press
3. Select OFF by using or and press
To activate QUEST:
1. Press
2. Use or to select O02 QUEST and press
3. Select AUTO by using or and press
Tests
The unit has 2 (3) test functions:
Function test.
PTI (Pre-Trip Inspection) test.
PTI short (optional)
The PTI test is a function test followed by a capacity test where the requested temperature must
be reached within the time limit.
During function and PTI test the normal alarm system remains active. If an alarm is triggered dur-
ing test operation, it appears in the display and will be written in the log as it is the case during
normal operation.
In case of a fatal alarm during testing the test is terminated and the unit remains off.
Clear the alarm list before starting a test. If there should be any active alarms in the alarm list
when a function or a PTI test is started, the test will always fail even if all the individual test steps
PASS without failures.
PTI menu has a primary status and a status for each sub-test with own indexes.
Only the primary status for a PTI test is memorized when supply voltage is removed.
When PTI is initiated a Trip start is set in the data log.
15 of 221 pages
Item No. 810900B Operating and service manual
Function test
Function test is a unit component test. (Non destructive)
Test is based on a GO/NO GO procedure. All tests must be executed without failure one by one for
the function test result to be PASS.
Note: The tests can also be performed individually
NOTE: At ambient temperature above 40C (104F) and below 20C (-4F) the unit has
to be running in normal operating mode at setpoint of 0C (32F) for of 10 minutes with
compressor running before executing a function test or PTI test.
The reason for this is to ensure correct function of unit during PTI test or function test.
PTI Test:
The purpose of the PTI test is to verify the presence of cooling performance.
The test is based on a GO/NO GO procedure. All tests must be executed without failure one by one
for the PTI test results to be PASS.
PTI test includes the following test items:
Full PTI
1. Function test
2. 5C (41F) test
3. 0C (32F) test
4. -18C (-0.4F) test
5. Defrosting
6. Test completion / status
Short PTI
Short PTI includes the following test items:
1. Function test
2. 5C (41F) test
3. 0C (32F) test
4. Defrosting
5. Test completion / status
Data Log
The controller has a data log to record operation of the unit. The data log includes 4 items:
Data.
Extended data.
Alarms.
Event data.
16 of 221 pages
Item No. 810900B Operating and service manual
Header
F3 Controller ID
F4 Controller Software
F5 Retriever Software
F6 Extraction date
F7 Comments
Data log
D1 DT Date
Stamp
D2 Time
D3 Log Type [Event, Data, Log]
D4 Event ID
Events + Alarms
D5 Param. 1
D6 Param. 2
D7 Param. 3
D8 Param. 4
D9 Param. 5
D10 Tsup Supply Air Temperature [C]
D11 Tret Return Air Temperature [C]
D12 Tusda1 USDA 1 Temperature [C]
D13 Tusda2 USDA 2 Temperature [C]
Short Log
D14 Tusda3 USDA 3 Temperature [C]
D15 Tcargo Cargo Temperature [C]
D16 Tset Temperature Set Point [C]
D17 Humidity Relative Humidity [%]
D18 AirEx Air Exchange [m3/h]
D19 Psuc Suction Pressure [BarE]
D20 Pdis Discharge Pressure [BarE]
D21 Fpower Net frequency [Hz]
D22 Upower Highest power voltage of U1, U2, U3
Extended Log Type 1
17 of 221 pages
Item No. 810900B Operating and service manual
D33
D34
D35
Header can be retrieved by Refcon, Logman, StarView and can be viewed in Refcon, LogView and
StarView.
Extended Log Type 1 can only be retrieved by Logman and StarView and shown in LogView and
StarView.
Extended Log Type 2 can only be retrieved by StarView and viewed in StarView.
StarView is the unique program designed for communication with a Star cool unit through a serial
connection to a PC.
Temperature control
Chill mode
Defect sensor(s) Substitution sensor / Action Alarm
Tsup1 (2) Tact = Tsup2 (1)
Tsup1 and Tsup2 Tact = Tret + constant 611, Too many sensor err
Tsup1, Tsup2 and Tret Tact = Tevap + constant
Tsup1, Tsup2, Tret and Tevap ** 600, No control sensor
Freeze mode
Defect sensor(s) Substitution sensor / Action Alarm
Tret Tact = Tevap + constant
Tret and Tevap Tact = Tsup1 + constant 611, Too many sensor err
Tret, Tevap and Tsup1 Tact = Tsup2 + constant
Tret, Tevap, Tsup1 and Tsup2 ** 600, No control sensor
** = no more available sensors for substitution.
18 of 221 pages
Item No. 810900B Operating and service manual
Dehumidification control
If dehumidification is active:
Defect sensor(s) Substitution sensor / Action Alarm
RH Stop dehumidification 614, Humidity deactivated
Defrost control
Defect sensor(s) Substitution sensor / Action Alarm
Tevap Tsuc
Tc Tc = constant
Psuc(T0) T0 = Tevap
Psuc (T0) and Tevap Only electrical defrosting.
T0 = constant
Tsuc Only electrical defrosting
T0 = constant
Tamb Tcontrol + constant
Tamb and Tinternal Always electrical defrosting
Electrical control
Following graphical illustration shows the accepted volt/Hz range and the set off values for the
alarms AL 414 (Fatal Alarm), AL 415 (Fatal Alarm), AL 416 (Fatal Alarm), AL 417, AL 418, AL
419, AL 427, AL 428 and AL 429 (Fatal Alarm), based on the table below
Volt
max. voltage - AL414, AL415, AL416
600
500
400
300
100
0
40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70
Hz
19 of 221 pages
Item No. 810900B Operating and service manual
General specification
Total unit weight 460 kg or 420 kg or 415 kg dependend on model
Dimensions Height: Width:
2235 mm 2025 mm
Noise level Less than 75 db(A) in 250 Hz band.
Measured 1.5 m in front of unit and 1.2 m above the ground, with the
unit operating at 50 Hz.
20 of 221 pages
Item No. 810900B Operating and service manual
Economizer
Manufacturer SWEP / WTT / Danfoss
Type Brazed plate heat exchanger
Material Stainless steel, AISI 316 L
Evaporator coil
Manufacturer ECO / DunAn
Tube material Copper, inner grooved
Fin Material Aluminium, Hydrophilic treated
Fin spacing 3.4 mm
Attitude 45 from horizontal
Condenser coil
Manufacturer ECO / DunAn
Tube material Copper, inner grooved
Fin Material Copper
21 of 221 pages
Item No. 810900B Operating and service manual
Evaporator fan
Material Polypropylen, glass fibre reinforced
Type Axial
Number of fans 2
Number of blades 7/8
Pitch 25
Diameter 315 mm
Drive Direct on motor shaft
Condenser fan
Material Polypropylen, glass fibre reinforced
Type Axial
Number of fans 1
Number of blades 4
Pitch 30
Diameter 400 mm
Drive Direct on motor shaft
Defrosting
Defrost initiation
On demand defrost.
Defrosting interval
The on demand defrost system is constantly monitoring the temperatures for the evaporator
in order to prevent that the evaporator will block up with ice.
If a blocking up of the evaporator is registered by the system, a demand defrost will be initi
ated.
The minimum time between defrost is always 4 hours, but it is adjusted to the actual set
point.
Defrosting method: Hot gas, combined with electrical heaters.
22 of 221 pages
Item No. 810900B Operating and service manual
Refrigeration controls
Expansion valves 2 solenoid valves, electronically controlled from
controller
Filter Drier Danfoss DML 164 with O ring or equivalent
Hot gas valve Solenoid valve electronically controlled from
controller
Moisture indicator Incorporated in receiver sight glass.
Material: Brass acc. to EN 12164 / CW602N.
Piping Solid copper tubes according to EN 12735 1
Pipe coating Primer: Epoxy resin zf a120.
Top coat: Polyurethane resin Hipon 50.
Electrical data
Input power 3 x 350 V - 460 V 50Hz / 3 x 400 V - 500 V 60
Hz
Control circuit voltage AC 24 Vac Nominal (varies with power supply).
18 Vac (350 V) 30 Vac (500 V).
Control circuit voltage DC 24 V DC Nominal (varies with power supply).
15 V DC (350 V) 30.5 V DC (500 V).
Circuit Breaker
Main power ampere 25 A or 16 A
Contactors
Nominal 9 amp at 40C (104F) & 400 volt
Max 7 amp at 70C (158F) & 520 volt
Start current 6 x nominal
Fuses
Secondary main fuses 10 A, tube fuse
Control circuit supply 0.4 A, tube fuse
24 V AC circuit 6.3 A, tube fuse
Power plug
Type CEE 17.4 pole, with earth. 32 amp
400/460 V / 50/60 Hz
23 of 221 pages
Item No. 810900B Operating and service manual
Power Cable
Type 4 x (2.5 4) mm2, 450 / 750 V, PU sheath
Length 18 m
Colour Yellow
Temperature Range -37C to +90C (-34.6F to 194F)
24 of 221 pages
Item No. 810900B Operating and service manual
Pressure transmitters
Manufacturer Danfoss AKS 32R SAGInoMIYA NSK
Range 0 32 BarE High pressure side. 0 30 BarE High pressure
-1.0 12.0 BarE Low and inter- side.
mediate pressure side -0.69 9.8 BarE Low and
intermediate pressure side
Type Ratiometric pressure transmitter, with sealed gauge measur-
ing principle.
in. female flare connection with deflator
Miscellaneous
Tin plated electrical wires
Tin plated cables.
2 pieces of incorporated hinges.
2 pieces of removable evaporator hatches.
Bolts, screws and nuts in stainless steel.
Single viper peripheral seal.
Front frame is painted with polyester powder, colour Ral 9003.
Fresh air exchange is measured and logged in m3/h, definition 5 m3/h.
25 of 221 pages
Item No. 810900B Operating and service manual
User Interface
Indicator lights
Both lights only active when the container is connected to a power supply line.
During power up both lights are shortly illuminated to verify their function.
A Slow flash is a short flash every 3 sec. A Quick flash is a flash every 1 sec. A NORMAL FLASH
is a flash every 1 sec.
Display
Setpoint temperature Setpoint control Control sensor temperature Secondary information
SETPOINT CT SUPPLY
Icons
C
______ RET ______
Defrosting is running
26 of 221 pages
Item No. 810900B Operating and service manual
Key pad
Navigation keys Use these keys to move menu display up / down and to
change parameter values
Cancel Leave active sub menu
Cancel active parameter adjustment
Up Move menu one line up
Increment parameter value in menu
Increment setpoint on main display page
Down Move menu one line down
Decrement parameter value in menu
Decrement setpoint on main display page
Enter Select a sub menu
Activate a function (press twice)
Initiate parameter adjustment
Accept parameter adjustment when done
Menu keys Press key to select menu display
Press again to move menu one full page down
Wake-up Turn on and off battery powered display operation
No display backlight will be active
27 of 221 pages
Item No. 810900B Operating and service manual
PTI Show PRE TRIP INSPECTION menu (Start/stop test and view
results)
Info Show INFORMATION menu (Actual data read out)
Water Cool Press 3 sec. to activate and deactivate water cooled condenser
Menu overview
Menus are selected by pressing a menu key or by pressing the Enter key on a sub menu line
shown in the display.
28 of 221 pages
Item No. 810900B Operating and service manual
|
OPERATION 2/ 5
Cursor
O01 Setpoint -9.9 C
O02
O03 Airflow mode NORMAL
O04 Humidity setpoint OFF %
O05 Datalog interval 15 m
O06 Programs >
Activating a function
1. First move cursor Up press or Down press to the line of the function to be activated.
2. Then press the Enter key . The cursor will now highlight the function value instead of the
ID.
3. Do the activation by pressing the Enter key once more.
4. If not pressing any key for 5 sec. or if pressing the Cancel key , no function will be
activated.
5. The cursor returns to the ID column and can now be moved to other lines.
29 of 221 pages
Item No. 810900B Operating and service manual
i | Air exchange 1/ 1
3
m/h
Press (X) to leave
This page is automatically displayed when the user starts changing the air exchange valve posi-
tion.
The display returns to the main page after 10 min. or when the Cancel key is pressed.
30 of 221 pages
Item No. 810900B Operating and service manual
Operation
Menu Structure
INFORMATION PROGRAMS
I01 Relative humidity P01 Active program
I02 Air exchange P02 Multi. Temp setp. >
I03 Last defr interval P03 Cold treatment >
I04 USDA 1 temp
I05 USDA 2 temp
I06 USDA 3 temp
I07 Cargo temp
I08 Time to defrost
I09 Ambient temp COLD TREATMENT
I10 Supply air 1 temp
B01 Duration
I11 Supply air 2 temp
B02 Maximum USDA temp.
I12 Return air temp
B03 Treatment setpoint
I13 Evaporator temp
B04 Final temperature
I14 Suction temp
B05 CT status
AIR EXCHANGE I15
I16 Suction press
I17
888m3/h
I18 Discharge press
I19 Expansion valve
I20 Evap superheat MULTI. TEMP. SETP.
I21 Compressor freq
Hour Set %Rh
Press (X) to leave I22 Power frequency
D01 OFF 0.0 OFF
I23 Current phase 1
D02 OFF 0.0 OFF
I24 Current phase 2
D03 OFF 0.0 OFF
I25 Current phase 3
D04 OFF 0.0 OFF
I26 Voltage phase 1-2
D05 OFF 0.0 OFF
I27 Voltage phase 2-3
D06 OFF 0.0 OFF
I28 Voltage phase 1-3
I29 Phase direction
I30 Battery voltage
I31 FC temp
I32 Condenser fan
I33 Evaporator fan
I34 Evaporator heater
31 of 221 pages
Item No. 810900B Operating and service manual
General Operation
The following text is a general description of operating menus and editing parameters.
By pressing a menu key the menu is selected and its icon is illuminated.
The lower part of the display shows parameter number, parameter value and a short information
text in English.
After 30 sec. with no keyboard activities, the display returns to the main display menu. By press-
ing
the display returns to the previous menu level in the menu structure.
If one of the other menu keys is pressed, menu selection changes.
By pressing the and keys the individual parameters are scroll able.
For parameter change, press and the parameter is highlighted in inverse writing. By pressing
and keys parameter values are changeable.
When desired value is set, press to accept value and parameter is shown in normal writing
again.
As long as the parameter value is shown in inverse writing, setting is erasable by pressing and
the previous parameter value is shown again.
If the keys , or are not pressed for 5 sec., setting is cancelled and the previous param-
eter value is shown again.
Temperature Setting
Temperature set-point adjustment is made from the operating menu.
By pressing or the set-point is adjusted 0.1C (0.1F) and the set-point digits are highlight-
ed in inverse writing.
If the key is held, the set-point will automatically be incremented by 0.1C (0.1F) until the key is
no longer held. After approximately 3 sec. the set-point will be incremented by 1C (1F). Upon
reaching desired temperature, press and hold for 3 seconds. The set-point will be accepted and
shown in normal writing again.
During inverse writing, the new temperature set-point is erasable by pressing and the previous
set-point is shown again.
If the keys , or are not pressed for 5 sec., current setting will be cancelled and previous
set-point shown again.
Wake-up Mode
When no main power is present the controller is switched off.
The controller includes a battery for Star Cool operation when no external voltage supply is
present.
For battery saving in this situation, controller will turn itself off upon disappearance of external
voltage supply.
By pressing controller is enabled and controller operation will be possible. In case of no key-
board activities for 30 sec., controller will be turned off again.
Controller may be manually turned off in this mode by pressing again.
32 of 221 pages
Item No. 810900B Operating and service manual
For a short PTI test START must be highlighted by pressing at menu item T01. Press keys or
to scroll the menu to select SHORT. Pressing once more initiates the test.
A complete PTI test may take several hours: First a complete function test with menu items T04 to
T12 and then performance testing in menu items T13 to T17.
Function test is initiated in the same way by selecting menu T02. A function test performs menu
items T04 to T12, without performance testing and takes about 10 15 min. to complete. The
function test will continue through all the steps even if failures should occur.
A PTI or function test can be aborted at T03.
A single item can be tested by highlighting the item, ex. T09. When START is shown in inverse
writing, pressing again will start the test. Only the selected item is tested.
The PTI test is automatically terminated in case of no errors. Finally, temperature set-point will be
set to the same value as before test initiation.
If any error occurs during the test, alarms will be shown in the alarm list. Active alarms in the
alarm list before start of the PTI test will lead to failure of the PTI test:
1. One alarm for PTI or function test failure. Status are also listed in the menu items T04
T12(FT)/T18(PTI).
2. One or more alarms for a specific error during the test. Only listed in alarm list.
Failures found during the tests are listed in the alarm list and the results of the separate PTI test
steps are in menu items T04 to T18. Alarms found are logged in the datalog.
A detailed description and trouble shooting of an alarm can be found in this manual chap. De-
tailed alarm description p.56, together with a description of the specific test alarms (Test
alarms, p.149). When the PTI test completes or is aborted, all alarms found during the test are
set inactive in the alarm list.
If the alarm list is empty, the unit is completely ok.
If the controller is switched off, only the main status of a PTI test is remembered in menu item
T04.
33 of 221 pages
Item No. 810900B Operating and service manual
For starting function test, START must be highlighted by pressing . Pressing once more initi-
ates the test.
34 of 221 pages
Item No. 810900B Operating and service manual
T13 Test result: 100 Temperature set point 5C (100 T set 5C)
Function:
Shows the status of the performance test with temperature set point of 5C (41F)
Value:
- if not done yet. RUN if still running test. PASS if test finished successfully. FAIL if the test
failed. ABORT if the test was aborted by the user. See specific description for alarm 855 in Test
alarms p.160
T14 Test result: 110 Temperature set point 0C (110 T set 0C)
Function:
Shows the status of the performance test with temperature set point of 0C (32F).
Value:
- if not done yet. RUN if still running test. PASS if test finished successfully. FAIL if the test
failed. ABORT if the test was aborted by the user. See specific description for alarm 860 in Test
alarms p.161
35 of 221 pages
Item No. 810900B Operating and service manual
36 of 221 pages
Item No. 810900B Operating and service manual
Value:
I15
Function:
Reserved for future use.
37 of 221 pages
Item No. 810900B Operating and service manual
Value:
Shown in units of Bar or PSI relative to atmosphere pressure. Switch by pressing (at C pres-
sure is shown in BarE, at F in PSI).
I17
Function:
Reserved for future use.
Value:
Shown in units of Bar or PSI relative to atmosphere pressure. Switch by pressing (at C pres-
sure is shown in BarE, at F in PSI).
38 of 221 pages
Item No. 810900B Operating and service manual
39 of 221 pages
Item No. 810900B Operating and service manual
40 of 221 pages
Item No. 810900B Operating and service manual
Programs:
Shown as None, CT or MTS. Press for 3 seconds to activate selected program or stop an active
program by selecting None.
Values: NONE, CT and MTS.
Set: The set point temperature to use for this step. This set point will be used as the main set
point even if the program is aborted. Temperature change per hour (ramp) is fixed for cool
ing, and change is done with maximum cooling capacity available. Heat up is fixed to be
done by 0.1C temperature increase per hour.
%RH: De-humidification - humidity set point. Values: Off, 50% 95%. Off means the controller
maintains as high humidity as possible, at all other values the controller will use the
humidity set point to maintain de-humidification. De-humidification is active immediately
when the step starts including under temperature ramps.
The Multiple Temperature Set points program stops automatically if the unit has been powered off
for more than 48 hours.
41 of 221 pages
Item No. 810900B Operating and service manual
Loading cargo
42 of 221 pages
Item No. 810900B Operating and service manual
USDA
Function:
The bottom line shows the temperatures of USDA sensors 1 3 and the cargo sensor.
Value:
Actual temperature measured of the sensor.
-70C indicates that the sensor is not mounted! Check alarm list to see if there should be an USDA
alarm.
Alarms
The alarm list holds all active and inactive alarms.
By pressing the alarm menu is opened. The icon is displayed in upper left corner of the display.
With any alarms in the list the icon is displayed on the main menu.
Alarm handling is to protect the unit with cargo and inform the user in case of error conditions.
The main priority is to keep cargo safe.
All errors in the 4 levels can have two states: Active or Inactive.
- Active: The alarm is active.
- Inactive: The alarm is no longer active. The alarm can be acknowledged from the
alarm list.
The 4 alarm levels will be treated by the controller in the following way:
43 of 221 pages
Item No. 810900B Operating and service manual
Alarm handling is made to detect abnormal situations, possibly solve problems and report the
problems. The alarm types indicate for the operator how severe the problem is for the safety of
the cargo.
Some problems are fluctuant where the problem may be fixed if the unit restarts. Some of the
alarms are only warnings but will restart the unit to try to solve the problem. There is an individual
time out period for the alarms. A warning will not stop the unit permanently!
If a problem with warning type continues to be active over a period, the problem seems to be of a
more stable and therefore more severe character and another alarm is triggered with alarm type
Alarm.
The AAS - Alarm Action System will substitute a missing or malfunctioning sensor with one of the
other sensors and thereby try to keep the cargo safe and well as long as absolutely possible. The
substitution may lead to a deteriorated control precision, especially in the freeze mode, but the
unit is not stopped fully until there are no further sensors to substitute with. The unit may try to
restart to see if the malfunctioning is fluctuant.
For example if there is no substitution for a sensor or the substitute sensor is also faulty, alarm
611 Too many sensor err is raised and the specific sensor(s) are listed separately in the alarm
list.
An active alarm is shown as Acc AAnnn, where cc is the list number from 01 to 16, and nnn is the
actual alarm number.
An inactive alarm is shown as Acc IAnnn, where cc is the list number from 01 to 16, and nnn is the
actual alarm number.
An active alarm is not deletable from the list, but may change to inactive state by eliminating the
cause of the alarm.
An inactive alarm is deletable from the list by pressing during alarm displaying.
44 of 221 pages
Item No. 810900B Operating and service manual
Manual operations:
M01 Operating mode (Operating mode)
Function:
Start/stop of operating mode.
If operating mode is MANUAL, controller stops, and by means of menu items M02 to M08 heaters,
motors and valves may be manually operated. In menu item M05 compressor frequency is set.
In case of no keyboard activities for 5 min., manual mode is automatically deactivated and unit
starts automatically up.
Note that the Star Cool should only be set in the manual mode by trained service
personnel!
Value:
Set to MANUAL or AUTOMATIC.
The bottom line on the menu shows the current consumption in the three phases (motor and
heater) and for the frequency converter I1, I2, I3, FC.
45 of 221 pages
Item No. 810900B Operating and service manual
Datalog view:
Press to toggle between stored set of temperatures: Setpoint temperature + supply air tem-
perature, return air temperature, relative humidity%, air exchange and the other set of tempera-
tures: USDA 1 +2 + 3 temperatures and cargo temperature.
To move one page up, press , or down, press , to list the previous or next page of stored
set of values from the data log.
Viewing of logged temperatures. Press on the main menu to get directly to this menu.
Value:
The following data can be viewed: Setpoint temperature, supply air temperature, return air tem-
perature, USDA 1 +2 + 3 temperatures and cargo temperature.
When entering the menu, the newest logged temperatures are always shown.
The number under the text Ref shows the temperature at the mark, ex. 5C.
Press to toggle between stored set of temperatures: Setpoint temperature + supply air tem-
perature, return air temperature and the other set of temperatures: USDA 1 +2 + 3 temperatures
and cargo temperature.
Press up or down to show newer or older stored set of values from the data log.
Press to change between the 4 zooming levels. The blank and black bar at the right-most
edge shows a scale of
1C per bar.
Time adjust:
C01 Setting of year (GMT-Year)
Function:
Setting of year.
Value:
46 of 221 pages
Item No. 810900B Operating and service manual
47 of 221 pages
Item No. 810900B Operating and service manual
Configuration:
F01 Container ID viewing (Container)
Function:
Viewing of container ID.
Value:
Shown in the lower display line. E.g. MCID 000 001 2
48 of 221 pages
Item No. 810900B Operating and service manual
Water-cooling Activation/Deactivation
The following only applies for Model SC-MCI40-WC
If the water supply is insufficient (the water hose is jammed, the water is not running or the water
temperature is too high), the temperature in the condenser will rise and cooling capacity is de-
creasing and thereby threatening the cargo.
If the condenser temperature rises above 58C (136F), the system will automatically switch to air-
cooling of condenser by turning the condenser fan on. If the water flow is restored, the controller
stops air-cooling of the condenser.
49 of 221 pages
Item No. 810900B Operating and service manual
If the temperature stays at the high temperature for more than 1 hour, an alarm is given.
The actual setting of water-cooling is remembered if the unit is switched off or there should be a
power loss.
Water-cooling is only turned off when the set point temperature is changed or when water-cooling
is turned off manually.
Emergency Operation
Warning: High Voltage. Unit must be disconnected from power. Only to be done by
trained personnel.
FC dismounted.
If FC is defective and no replacement part is available, compressor may be run in the on / off
mode.
Defective FC is dismounted and the 3 phases are directly applied to the compressor supply termi-
nals.
Also a wire-jumper has to be fitted on the remaining 3 terminals, see below figure.
In the service menu, F03 FC TYPE, the parameter NONE is selected. Unit will then run in the on /
off mode with deteriorated temperature controlling performance.
Z 1
1
U
X 100
2
4
Communication cable from
3 CONTROLLER BOX
Bottom 2
815591C
50 of 221 pages
Item No. 810900B Operating and service manual
External interfaces
StarCool Unit
RefCon
RMM RefCon
RS 232 Powerline logfile
modem PC
RCCU-5
Controller
&
Datalogger Binary
Retriever LogMan LogView
RS 232 RS 232 logfile
socket PDA PC
RS 232
CSV-text Software
Logfile StarView HEX file
With signature PC With CRC
General requirements
1. Serial port setup is 19200, 8, N, 1
2. Unless otherwise stated, byte order is low byte first
51 of 221 pages
Item No. 810900B Operating and service manual
Functions overview
It is defined in the table below, which Star Cool functions each device and system will support.
Function LogMan LogView RefCon StarView Controller
Display basic data 1 x x x
Change container ID x x x
Acknowledge alarms x x
52 of 221 pages
Item No. 810900B Operating and service manual
Location of valves
1 2 3
7 6 5 4
2 3 4
1 7 6 5
Position Description
1 Discharge pressure stop valve
2 Intermediate pressure stop valve
3 Hot gas valve
4 Service valve, economizer
5 Electronical expansion valve, evaporator
53 of 221 pages
Item No. 810900B Operating and service manual
100mm
54 of 221 pages
Item No. 810900B Operating and service manual
The unit is wired for emergency operation but the parameter F03 FC type under service
menu, is not set to NONE.
The menu F03 under service menu, is set to NONE for emergency operation but the wires
55 of 221 pages
Item No. 810900B Operating and service manual
3. Unit is running but is not bringing the temperature down to temperature setpoint.
The cargo is very warm it takes a long time to cool it down.
The ambient temperature is very high the condenser can only cool a little so the cooling
capacity is small and the cool down process takes longer time.
The hotgas valve may be leaking so that the hot gas is by-passing the condenser and is
pumped into the evaporator and heating it up.
The expansion valve is not opening and no cooling refrigerant is pumped into the evaporator.
The condensor pressure will be very high.
The unit has been put in manual phase detecting mode and all motors are running the wrong
way. The compressor will pump correctly but there is very little cooling capacity in the con
denser and the air flow is wrong inside in the unit.
One of the motors (condenser or evaporator) is running in the opposite direction.
5. Display is blank.
Adjust contrast (see Contrast adjustment of the display p.32)
1. Set unit to Manual Operation Mode by choosing Service Menu and Operation Mode and
changing Auto to Manual.
2. Disconnect the X1 cable from the controller door.
3. After a while enter the Information Menu. In here the following values shall appear:
a. Temperature drops to -70C
b. Psuc shows: 12.0 BarE (if AKS) or 9.8 BarE (if NSK)
c. Pdis shows: 32.0 BarE (if AKS) or 30.0 BarE (if NSK)
d. AirEx must read: 220 m3
e. Humidity: 0%
4. If one of these listed values does not appear, the controller door must be replaced.
Alarm list
In the following all alarms are listed with a description and their causes.
56 of 221 pages
Item No. 810900B Operating and service manual
Slow flash indicates that the diodes are turned on shortly every 3 sec. and that there are
active alarm(s),
Quick flash that the diodes are turned on 0.8 sec. every 1 sec. and that there is an active
fatal alarm(s).
When troubleshooting several alarms, it is generally advisable to start with the active alarm that
has the lowest number and then go on to the active alarms with higher numbers. Remember that
some alarms have a time out of 30 sec. and more.
Alarm list
The following list includes a view of all alarms as listed on the display and a longer text.
57 of 221 pages
Item No. 810900B Operating and service manual
58 of 221 pages
Item No. 810900B Operating and service manual
59 of 221 pages
Item No. 810900B Operating and service manual
60 of 221 pages
Item No. 810900B Operating and service manual
61 of 221 pages
Item No. 810900B Operating and service manual
62 of 221 pages
Item No. 810900B Operating and service manual
63 of 221 pages
Item No. 810900B Operating and service manual
64 of 221 pages
Item No. 810900B Operating and service manual
65 of 221 pages
Item No. 810900B Operating and service manual
66 of 221 pages
Item No. 810900B Operating and service manual
67 of 221 pages
Item No. 810900B Operating and service manual
68 of 221 pages
Item No. 810900B Operating and service manual
69 of 221 pages
Item No. 810900B Operating and service manual
70 of 221 pages
Item No. 810900B Operating and service manual
71 of 221 pages
Item No. 810900B Operating and service manual
72 of 221 pages
Item No. 810900B Operating and service manual
73 of 221 pages
Item No. 810900B Operating and service manual
74 of 221 pages
Item No. 810900B Operating and service manual
75 of 221 pages
Item No. 810900B Operating and service manual
76 of 221 pages
Item No. 810900B Operating and service manual
77 of 221 pages
Item No. 810900B Operating and service manual
78 of 221 pages
Item No. 810900B Operating and service manual
79 of 221 pages
Item No. 810900B Operating and service manual
80 of 221 pages
Item No. 810900B Operating and service manual
81 of 221 pages
Item No. 810900B Operating and service manual
82 of 221 pages
Item No. 810900B Operating and service manual
83 of 221 pages
Item No. 810900B Operating and service manual
84 of 221 pages
Item No. 810900B Operating and service manual
85 of 221 pages
Item No. 810900B Operating and service manual
86 of 221 pages
Item No. 810900B Operating and service manual
87 of 221 pages
Item No. 810900B Operating and service manual
88 of 221 pages
Item No. 810900B Operating and service manual
89 of 221 pages
Item No. 810900B Operating and service manual
1 Supply
3 Output
2 Ground
90 of 221 pages
Item No. 810900B Operating and service manual
1 Supply
3 Output
2 Ground
91 of 221 pages
Item No. 810900B Operating and service manual
Elimination When sensor value becomes valid, it is marked as inactive in alarm list and may then be
deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Current
92 of 221 pages
Item No. 810900B Operating and service manual
1 Supply
3 Output
2 Ground
Criteria Value below alarm limit 0.1 BarE (2 Psi) or above 31.9 BarE (462 Psi). Value invalid for
30
sec. for alarm activation.
Replacement by new value from AAS system
Controller
action
Log X Alarm X Alarm light Off
Consequence
Elimination When sensor value becomes valid, it is marked as inactive in alarm list and may then be
deleted. Value must be valid for 60 sec. to set alarm inactive.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
93 of 221 pages
Item No. 810900B Operating and service manual
1 Supply
3 Output
2 Ground
Criteria Value above high alarm limit 11.9 BarE (172 Psi)
Replacement by new value from AAS system
Controller
action
Log X Alarm X Alarm light Off
Consequence
94 of 221 pages
Item No. 810900B Operating and service manual
Elimination When sensor value becomes valid, it is marked as inactive in alarm list and may then be
deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Current
1 Supply
3 Output
2 Ground
Criteria Value below low alarm limit -0.9 BarE (-13 Psi)
95 of 221 pages
Item No. 810900B Operating and service manual
96 of 221 pages
Item No. 810900B Operating and service manual
1 Supply
3 Output
2 Ground
1
Figure for AKS Figure for NSK
1) Check the cable (measure the resistance in the cable).
If the cable is defect, replace cable.
2) Mount the cable for Psuc in controller cabinet and on the sensor.
Disconnect signal wire on interface/terminal block PCB.
Measure voltage between wire and GND on interface/terminal block PCB.
AKS: If voltage is below 0.5V DC, sensor or connection between sensor and cable is
defect.
If voltage is between 0.5V DC and 4.5V DC, continue to 4).
NSK: If voltage is below 0.37V DC, sensor or connection between sensor and cable is
defect.
If voltage is between 0.37V DC and 4.0V DC, continue to 4).
3) Mount signal wire.
Measure voltage between SIGNAL and GND.
AKS: If voltage is between 0.5V DC and 4.5V DC and this alarm is still active, replace
controller door.
NSK: If the voltage is between 0.37V DC and 4.0V DC and this alarm is still active,
replace controller door.
Before replacing controller door see Trouble shooting for Star Cool Controller
p.56
Criteria Value below alarm limit -0.9 BarE (-13 Psi) or above 11.8 BarE (171 Psi). Value invalid
for 30 sec. for alarm activation.
Replacement by new value from AAS system.
Controller
action
Log X Alarm X Alarm light Off
Consequence
Elimination When sensor value becomes valid, it is marked as inactive in alarm list and may then be
deleted. Value must be valid for 60 sec. to set alarm inactive
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Current
97 of 221 pages
Item No. 810900B Operating and service manual
Accompanied alarms:
AL 207
AL 611
Trouble shooting:
1. Manually select the type of pressure transmitters in the configuration
on menu F07 and F08.
Criteria The saved Frecuency Converter I does not match saved Frecuency Converter ID in the
controller.
Replacement by new value from AAS system.
Controller
action
Log X Alarm X Alarm light On
Consequence The unit will continue operation with AAS value.
Elimination The operator has to manually select the type of pressure transmitters in the
configuration on meny F07 and F08
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive T0 Tc Type Low Type High
98 of 221 pages
Item No. 810900B Operating and service manual
99 of 221 pages
Item No. 810900B Operating and service manual
Controller
action
Log X Alarm X Alarm light Off
Consequence
Elimination When sensor value becomes valid, it is marked as inactive in alarm list and may then be
deleted. Value must be valid for 60 sec. to set alarm inactive.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
This alarm is used for service purposes, the fuses are protecting the unit
This alarm is used for service purposes. The fuses are protecting the unit
This alarm is used for service purposes. The fuses are protecting the unit
This alarm is used for service purposes. The fuses are protecting the unit
None
Controller
action
Log Alarm Alarm light Slow flash
Consequence None
Elimination Alarm will be marked as inactive in alarm list when proper supply is established.
Alarm may then be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
U1 2 U2 3 U1 3 NetFreq n/a
Elimination Alarm will be marked as inactive in alarm list when reset by FC. Alarm
may then be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Freq FC I FC
None
Controller
action
Log X Alarm X Alarm light Off
Consequence If not solved, this problem can cause FC to stop due to alarm 515
Elimination Warning will be marked as inactive in alarm list when reset by FC.
Alarm may then be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Freq FC I FC Psuc Pdis
Elimination Warning will be marked as inactive in alarm list when reset by FC.
Alarm may then be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Freq FC FC AL number Psuc Pdis
Controller
action
Log X Alarm X Alarm light Quick flash
Consequence Unit stop
Elimination When one of the control sensor values enters into the valid area, it is again possible to
control container temperature. For reliability reasons at least one of the control sensor
values must be valid for 30 sec. before sensor may be used as control reference again.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
Elimination Alarm will be marked as inactive in alarm list next time water-cooling is activated. Alarm
may then be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Tc Wc off
Cause Hot gas valve, expansion valve and economizer valves are all closed and
compressor is running
Trouble Possible causes:
shooting
Repeated high pressure alarms.
Accompanied alarms:
Alarm AL 306.
Trouble shooting:
1) See and clear error for alarm AL 306
Criteria AL 306 has been active 3 times within 30 min
Control not possible
Controller
action
Log X Alarm X Alarm light Quick flash
Consequence Unit stop
Elimination Alarm 604 will be marked as inactive in alarm list when alarm 306 disappears.
After 30 min restart delay unit starts again and alarm may then be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
Controller
action
Log X Alarm X Alarm light Quick flash
Consequence Deteriorated control precision in the frozen mode
Elimination Alarm will be marked as inactive in alarm list when air exchange is closed and may then
be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
Elimination When a sensors slot value enters valid range, it is marked as inactive in alarm list and
may then be deleted. Values must be valid for 120 sec. to set alarm inactive.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Restart time for the FC is extended to 15 min.
Elimination When the FC has been without errors for more than 1 hours, this alarm is marked
inactive and can be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
Cause
Trouble
shooting
Criteria
None
Controller
action
Log X Alarm X Alarm light Quick flash
Consequence No cooling of the cargo
Elimination
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
Accompanied alarms:
Check for AL 951 up to AL 996
There may be other accompanied alarms.
Trouble shooting:
1) See trouble shooting for accompanied alarms. If none appears, then
proceed with 3).
2) Clear other active alarms with sensors.
3) The power supply or power-cable for controller PCB defect.
Measure voltage for the controller PCB.
a. If voltage is ok, the controller PCB is defect and controller door
must be replaced.
b. Measure voltage for all sensors. Should be between 4.80V DC and
5.20V DC for temperature and pressure sensors. Humidity sensor
must be between 12.00V DC and 34.00V DC.
If not ok, the sensor or cable is defect. Replace sensor.
c. Measure outlet on transformer between T3 and T4. Correct range
15.30V AC 24.30V AC. Measure between T5 and T6. Correct
range 18.86V AC 30.00V AC. If within range transformer is ok.
d. Replace controller door.
Criteria One or more of the internal reference voltages are out of limits
FC will soon trip with error 516 and stop compressor
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Test failed
Elimination Alarm may then be deleted after test completed
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Step no.
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Data logging unreliable. Temperature control is functioning
Elimination
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive 1 = R, W = 2
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Invalid date/time setting in datalog
Elimination Check / replace real-time clock battery. Set time. Alarm may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Invalid date/time setting in datalog
Elimination Check / replace real-time clock battery. Set time. Alarm may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
Controller
action
Log X Alarm X Alarm light Off
Consequence Cannot show data for user (use PC-program or RMM). Every 30 sec. retry to reinitiate
the display is made.
Elimination Alarm will be marked as inactive in alarm list if the error disappears. Alarm may then be
deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive
The measured voltage is internal on the controller PCB and cannot easily be measured
The measured voltage is internal on the controller PCB and ca not easily be measured
The measured voltage is internal on the controller PCB and cannot easily be measured
Elimination
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Actual value A/D channel
The measured voltage is internal on the controller PCB and cannot easily be measured
The measured voltage is internal on the controller PCB and cannot easily be measured
Controller
action
Log X Alarm Alarm light Off
Consequence
Elimination
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Actual value A/D channel
The measured voltage is internal on the controller PCB and cannot easily be measured
The measured voltage is internal on the controller PCB and cannot easily be measured
The measured voltage is internal on the controller PCB and cannot easily be measured
The measured voltage is internal on the controller PCB and cannot easily be measured
The measured temperature is internal on the controller PCB and cannot be measured
The measured temperature is internal on the controller PCB and cannot be measured
Replacing of unit
Handling of unit during replacement is done by means of a special yoke, see below sketch.
Depending on the model, use either position 1, 2 or 3 for the yoke.
Pos. 1
Pos. 2
Pos. 3
Note: Turn off main power supply for unit before replacing evaporator motor and fan.
Note: Due to high aerodynamic requierements (decreased energy consumption) sharp
edges is located in this area!
Note: The displayed model may be different from the acual model.
Disconnect the power supply to the motor by removing the motor cover and unscrew the
earthwire placed directly on the motor.Do not disconnect the other cable connection which is con-
nected directly in the motor cover. Remove the 4 x M8 bolts that hold the evaporator motor brack-
et, incl. motor and fan.
Then the evaporator motor bracket with motor and fan can slide right through the inspection hatch
of the unit, by dragging it towards yourself.
The evaporator bracket has to be tilted slightly downwards, to pass by the gasket.
Replace the defect parts and reinstall the evaporator fan module.
Prior to mounting the motor cover, check the sealing for any damages. If damaged, the sealing
must be replaced.
Note: Turn off main power supply for unit before replacing condenser motor and fan.
Remove the condenser grill and disconnect the power supply to the motor by removing the motor
cover and unscrew the earth wire, which is placed directly on the motor.
Do not disconnect the other cable connection which is connected directly in the motor cover.
Replace the defect parts and reinstall the parts.
Prior to mounting the motor cover, check the sealing for any damages, if damaged the sealing
must be replaced.
Replacement of evaporator
Old model
In order to replace the evaporator the unit has to be dismounted from the container, as described
in this manual.
After dismounting the unit there is free access to all parts on the backside of the unit.
Position Description
1 Back plate, unit
2 Evaporator fan module, complete
3 Evaporator back plate
4 Fan grill
5 Side cover, left and right
6 Evaporator
New model
Position Description
1 Back plate, unit
2 Evaporator
Dismount the back plate for the unit and replace the defect heating element.
After replacing heating elements reinstall back plate for unit.
Pleaase note that the illustrated model may be different from the actual model.
Replacement of FC
Position Description
1 Cover for FC
2 FC
3 Motor cable
4 Cable room cover
Replacement of compressor
Position Description
1 Compressor
2 Bracket for compressor
3 Cover for FC
4 FC
5 Motor cable
6 Cable room cover
Evacuation of refrigerant
Evacuation of refrigerant for the unit is done by the following procedure:
1. Install a service gauge manifold on the unit to the two evacuation points, pos. 6 and 27 (P & I
diagram)
2. Connect the recovery station with weight measurement to the service gauge manifold.
3. Remove the electrical coils and mount permanent magnet on the two electronically expansion
Note: refer to operating and service manuals for the recovery equipment.
1. Connect the vacuum pump to the two evacuation points, pos. 6 & 27 (P & I diagram).
2. Ensure that the valves on the vacuum pump are closed.
3. Close the compressor suction pressure stopvalve and compressor intermediate pressure
stopvalve, pos. 26 & 30 (P & I diagram).
4. Close the compressor discharge pressure stopvalve, pos. 5 (P & I diagram), approx. 4 turns.
5. Run the compressor in manual operation on 50 Hz, as described in manual operation section.
6. Observe the pressure indication on the display for the suction pressure, when the suction
pressure reaches 0.5 BarE (-7.3 Psi) in value. Close the compressor discharge pressure
stopvalve entirely and turn off the power to the unit.
SETPOINT CT SUPPLY
1. Connect a vacuum pump with a service gauge manifold to the two evacuation points, pos. 6 &
27 (P & I diagram).
2. Close the compressor discharge and compressor suction servicevalves, pos. 5 & 26, (P & I
diagram).
3. Pump down the pressure in the compressor to vacuum, indicated on the gauges of the service
gauge manifold.
4. Continue vacuum pumping for at least 2 hours.
5. Switch off the vacuum pump and close the stopvalve for the suction line to the vacuum pump
on the service gauge manifold. Observe the vacuum for minimum hour.
6. If the vacuum is maintained, then the compressor discharge servicevalve and compressor
suction servicevalve, pos. 5 & 26, (P & I diagram), can be fully opened.
If the vacuum pressure is not maintained, there is a possible leak somewhere. Check all hose
connections between compressor and vacuumpump. If these are ok, check the compressor.
7. Disconnect the service gauge manifold and operate the unit as normal.
Pressure Test
After performing a major repair to the unit piping system, it is recommended to perform a pres-
sure test.
Pressure test has the purpose of checking the piping system for leakages.
The pressuretest is done by means of a high pressurized gas, ex. N2, which is let into the piping
system through the two evacuation points, pos. 6 & 27 (P & I diagram). The procedure for this is
as follows:
1. Install a service gauge manifold on the unit to the two evacuation points, pos. 6 & 27
(P & I diagram).
2. Close the compressor discharge stopvalve and compressor suction stopvalve, pos. 5 & 26
(P & I diagram), 4 turns
3. Connect the pressurized gas bottle (ex. N2) to the discharge stopvalve of the service gauge
manifold.
4. Remove the electrical coils and mount permanent magnet on the two electronically expansion
valves, pos. 16 & 18 (P & I diagram).
5. Open the discharge stopvalve of the service gauge manifold.
6. Carefully open the hand valve of the pressurized gas bottle until the two gauges of the ser-
vice gauge manifold show a pressure of 12 BarE.
7. Close the discharge stopvalve of the service gauge manifold.
8. Do a leakage detection as described in this manual.
9. Leave the unit pressurized for minimum 2 hours. If the pressure gauges still show 12 BarE
after 2 hours, the unit is without any leakages.
10. If the pressure gauges are below 12 BarE, perform a leakage detection as described in this
manual
11. Disconnect the pressurized gas bottle.
12. Open the discharge stopvalve on the service gauge manifold to release the pressure from the
unit.
13. Do a pump down of unit as described in this manual.
14. Charge the unit as described in this manual.
Charging of refrigerant
1. The red balls in the sight glass for the receiver are constantly at bottom level.
2. Veco is more than (>) 80% open for hour.
3. Vexp will steadily increase to 100%.
4. Psuc (T0) is steadily going down
If based on the above, it is determined that the unit is too low on refrigerant charge, additional
refrigerant may be charged by following this procedure:
1. Install a service gauge manifold on the unit to the two evacuation points, pos.6 & 27 (P & I
diagram).
2. Connect the low pressure valve of the service gauge manifold to the suction stop valve, pos.
26 (P & I diagram).
3. Connect the service gauge manifold to the refrigerant bottle. Purge as needed.
4. Close the compressor suction stop valve, pos. 26 (P & I diagram) fully and open approx. 4
turns.
5. Set the refrigerant bottle for liquid charging.
6. Operate compressor in manual mode, as described in this manual, compressor speed 25 Hz.
7. Open the low pressure valve of the service gauge manifold.
8. Read the suction pressure.
9. Open hand valve on refrigerant bottle slowly, allowing the suction pressure to increase with
1.5 Bar.
10. Add refrigerant until the sight glass balls float in top of the sight glass.
11. Close hand valve on refrigerant bottle.
12. Open the compressor suction stop valve, pos. 26 (P & I diagram), fully.
13. Set the unit for automatic operation, as described in this manual.
14. Observe the unit running in a stable condition. Add or remove refrigerant if necessary.
15. When refrigerant charge is correct, remove service gauge manifold and cap the two
evacuation points, pos. 6 & 27 (P & I diagram).
Leakage detection is also done during pump down of unit or compressor, as described in this
manual.
Fan motors
In order to prevent a single wire from getting caught between Ground screw and junction box
cover, a cable tie collecting all wires except ground wire, needs to be placed in the center of the
junction box. Furthermore is insulation tape applied on top of the Ground screw. This reduces the
possibility of sharp edges on the top of the Ground Screw to damage nearby wiring.
Drying filter
The drying filter has to be changed every time the compressor is changed or if the moisture indi-
cators indicate too much moisture is in the refrigerant circuit.
To change the drying filter, follow the following procedure:
Compressor
Check of oil level
The oil level can be checked on the sight glass of the compressor.
During normal operation the oil level should be between 1/3 and 2/3 sight glass full.
Normal operation is when the unit has been running on setpoint in a steady condition for minimum
6 hours.
If the oil level is below sight glass after a period of minimum 6 hours normal operation, additional
oil may be added, as decribed in this manual
Due to dissolved refrigerant the oil level shown in the compressor sight glass may be too high if
the unit has not been running for a longer period of time. In that case:
Let the unit run for 20 minutes with set point below cargo set point.
Turn off the compressor and check the sight glass.
If the oil level is still too high, remove oil until 1/3 to 2/3 sight glass full is obtained.
Charging of oil
If during normal operation is has been observed that there is too little oil charge on the compres-
sor, additional oil may be charged.
The compressor is filled with 1,5 liter Reniso Triton SEZ 55 or equivalent oil from the factory.
The procedure for adding oil is as follows:
1. The two oil outlets are placed on a tee-piece located on the compressor end opposite of the
FC end. Please observe that only one of the oil outlet ports is equipped with a schrder valve.
2. Connect a service gauge manifold to the outlet port with schrder valve of the oil pump.
3. Only connect the discharge hose to the outlet port of the oil pump.
Make sure that all stopvalves on the service gauge manifold are closed.
4. Open the discharge gauge stopvalve on the service gauge manifold.
5. Insert the hose from the suction gauge on the service gauge manifold into a small measuring
cup.
6. Run the compressor in manual operation on 25 Hz.
7. Carefully open the suction gauge stopvalve on the service gauge manifold.
8. While observing the oil level in the sight glass of the compressor, carefully let out oil, until the
oil level in the sight glass has reached a mid level.
9. Close the suction gauge stopvalve and discharge gauge stopvalve on the service gauge mani-
fold.
10. Disconnect the service gauge manifold.
11. Cap the oil outlet from the oil pump.
12. Set the controller to AUTOMATIC operation.
13. Run the unit in normal operation.
14. Observe the oil level when the unit is running minimum 6 hours in a stable condition.
Soldering
When soldering and desoldering components on the unit, please observe the following:
Example for product name: Chem - weld product 550 or Castolin RB 5283
Soldering flux: Due to the high content of Phosphor in the
soldering rod no flux is needed.
For Copper - Stainless (connections for water cooled condenser and economiz-
er):
Example for product name: Chem - weld product 511B or Castolin 1802 or
1802 F.
Example for product name: Chem - weld product 110 or Castolin 1802
N - Atmosin.
2. Use wet cloths to protect sensitive valves and other equipment against heat
input during soldering and desoldering.
3. Use inert back gas as Nitrogen (N2) during soldering and desoldering.
Tables
Datalog description
Explanations of datalog loggings:
Temperatures are stored in C and are converted to Fahrenheit on retrieval or listing on the dis-
play.
Pressures are stored in BarE and are converted to Psi on retrieval.
Data:
Extended data:
Alarms:
Alarms which may occur and a detailed explanation and troubleshooting are described later in this
manual.
Events:
43 CT ramp up Actual temp. USDA1 temp USDA2 temp USDA3 temp Final setpoint
temp.
44 Multiple Temperature Set Step number Step duration Step setpoint Step temp. chg. Step humid-
points (MTS) start /hour ity setpoint
45 MTS step stop Step number 0: Normal Step setpoint Step temp. chg. Step humid-
1: Aborted /hour ity setpoint
47 CT Done Number of Duration CT setpoint CT high temp. Final setpoint
valid USDA [min.] temp. limit temp.
sensors
48 CT Failed 0: Sensor CT high USDA sensor 1 USDA sensor USDA sensor
error temp. limit temp 2 temp 3 temp
1: Aborted
50 Controller Internal Tempera- T n/a n/a n/a n/a
ture
90 Debug (intern. use) 1 Alarm count Expected alarm n/a n/a
count
91 FC status Communica- n/a Last alarm code Protokol state Bus state
tion rate [%] 0: Clear 0: off
1: Time out 1: error
2: No reply 2: connect
3: Recieved 3: run
stopped
4: CRC
5: Lngde
6: Data format
(*) The time is stored as minutes: 360 min = 6 * 60 min. = 6 hours
1.1 -8.84 4.8 20.47 8.5 37.53 12.2 50.19 15.9 60.48 19.6 69.27 23.3 76.99
1.2 -7.64 4.9 21.02 8.6 37.92 12.3 50.50 16.0 60.74 19.7 69.49 23.4 77.19
1.3 -6.49 5.0 21.57 8.7 38.30 12.4 50.80 16.1 60.99 19.8 69.71 23.5 77.39
1.4 -5.37 5.1 22.12 8.8 38.68 12.5 51.10 16.2 61.24 19.9 69.93 23.6 77.58
1.5 -4.29 5.2 22.65 8.9 39.06 12.6 51.40 16.3 61.49 20.0 70.15 23.7 77.78
1.6 -3.24 5.3 23.18 9.0 39.43 12.7 51.70 16.4 61.74 20.1 70.36 23.8 77.97
1.7 -2.22 5.4 23.70 9.1 39.81 12.8 51.99 16.5 61.99 20.2 70.58 23.9 78.17
1.8 -1.23 5.5 24.22 9.2 40.17 12.9 52.29 16.6 62.24 20.3 70.80 24.0 78.36
1.9 -0.26 5.6 24.73 9.3 40.54 13.0 52.58 16.7 62.49 20.4 71.01 24.1 78.55
2.0 0.67 5.7 25.24 9.4 40.90 13.1 52.87 16.8 62.74 20.5 71.23 24.2 78.75
2.1 1.59 5.8 25.74 9.5 41.27 13.2 53.16 16.9 62.98 20.6 71.44 24.3 78.94
2.2 2.48 5.9 26.23 9.6 41.63 13.3 53.45 17.0 63.23 20.7 71.66 24.4 79.13
2.3 3.35 6.0 26.72 9.7 41.98 13.4 53.74 17.1 63.47 20.8 71.87 24.5 79.32
2.4 4.20 6.1 27.20 9.8 42.34 13.5 54.02 17.2 63.71 20.9 72.08 24.6 79.51
2.5 5.03 6.2 27.68 9.9 42.69 13.6 54.30 17.3 63.95 21.0 72.30
2.6 5.84 6.3 28.16 10.0 43.04 13.7 54.59 17.4 64.19 21.1 72.51
2.7 6.64 6.4 28.62 10.1 43.38 13.8 54.87 17.5 64.43 21.2 72.72
30.46 34.86 84.12 78.33 137.79 106.29 191.45 127.69 245.11 145.36 298.78 160.59 352.44 174.09
31.91 36.46 85.57 79.21 139.24 106.93 192.90 128.21 246.56 145.81 300.23 160.99 353.89 174.43
33.36 38.03 87.02 80.10 140.69 107.56 194.35 128.73 248.01 146.25 301.68 161.37 355.34 174.78
34.81 39.56 88.47 80.96 142.14 108.21 195.80 129.24 249.46 146.68 303.13 161.74 356.79 175.12
36.26 41.05 89.92 81.82 143.59 108.84 197.25 129.74 250.92 147.11 304.58 162.14
37.71 42.51 91.37 82.69 145.04 109.47 198.70 130.26 252.37 147.54 306.03 162.52
39.16 43.95 92.82 83.52 146.49 110.08 200.15 130.77 253.82 147.97 307.48 162.90
Tightening torques
Description Type Torque [Nm] 5%
General
Hex Head Bolt + Nut, M5 5,5
Hex Head Bolt + Nut, M6 9
Hex Head Bolt + Nut, M8 23
Hex Head Bolt + Nut, M10 47
Hex Socket Counters. Head Bolt, M6 9
Hex Socket Counters. Head Bolt, M8 23
Flare Nut , Brass 70
Schrder Valve, 1/8 24
Cable Gland, M12 Lock Nut 2
Cap Nut 1
Cable Gland, M16 Gland 5
Cap Nut 2
Cable Gland, M20 Gland 7
Lock Nut 4
Cap Nut 3
Cable Gland, M25 Lock Nut 6
Cap Nut 4
Cable Gland, M32 Lock Nut 8
Cap Nut 6
Fresh Air System
Air Exchange Potentiometer Slotted Cheese Head Screw, M3 1
Damper for Fresh Air Wing Screw, M6 5
FC
FC Mounting Slotted Cheese Head Screw, M6 9
FC Mounting Hex Lobular Socket Screw, M6 9
Compressor
Cylinder Head Hex Head, M10 70
Bearing Cover Hex Socket Counters. Head Bolt, M10 54
Oil Pump Cover Hex Head Bolt, M8 10
Sight Glass Hex Head 60
Terminal Plate Hex Socket Counters. Head Bolt, M6 14
Pressure Transmitter, AKS Hex Head 18
Pressure Transmitter, NSK Hex Head 14
High Pressure Switch Hex Head 14
Receiver
Water Inlet Coupling, Female 70
Water Outlet Coupling, Male Hex Head 70
Sight Glass Hex Head 60
Melt Fuse Hex Head 65
Air Release Valve Hex Head 65
Valves
Hot Gas Valve Special tool 80
Evaporator- and Economizer Valve Hex Head 45
Suction Gas Valve Hex Head Bolt, M10 54
Suction Gas Valve Flange Hex Socket Counters. Head Bolt, M10 50
Discharge- and Intermediate Valve Hex Head Bolt, M8 30
Evacuation Valve Hex Head 18
Unit Backside
Evaporator Cover Plate Hex Lobular Tapping Screw, 4.8 5
35 1 Compressor
34 2 Frequency Converter
37 3 Discharge Pressure Transmitter (P dis)
35
4 High Pressure Switch
5 Discharge Service Valve
32 6 Evacuation Point
20 20 33 RH 7 Discharge Line
8 Condenser Fan
M M 9 Air Cooled Condenser
10 Liquid Line
21 1/2"
11a Air Release Valve (old model)
8 Liquid Charging Valve (new model)
11b
12 Fusible Plug
M 1/2"
19 22 13 Receiver / Water Cooled Condenser
14 Service Valve, Economizer
18 1/2" 15 Drying Filter
23 16 Electronical Expansion Valve, Economizer (V eco)
17 Economizer
3/4" Electronical Expansion Valve, Evaporator (Vexp)
18
10 Evaporator
19
9
24 24 20 Evaporator Fan
1/2"
22 Evaporator Temperature Sensor (Tevap)
25 23 Heating Elements
10
24 Supply Air Sensors (Tsup1 + Tsup2)
14 25 Suction Temperature Sensor (Tsuc)
1/2" 26 Suction Service Valve
3/4" 1/2" 7 27 Evacuation Point
15 1/2"
1 1/8" 11b 28 Suction Pressure Transmitter (Psuc)
29 * 17 29 Economizer Suction Temperature Sensor (Teco) *
11a 30 Economizer Suction Service Valve
3/4" 31 Intermediate Pressure Transmitter (Peco) *
1/2"
30 12 32 Hot Gas Valve (Vhg)
1/2" 33 Humidity Sensor (RH)
13 Water Inlet 34 Controller
Water Outlet 35 Communication Slot
31 *
P
FC 2 3 4
27 P PS 6
P 28
Refrigerant: R134a Motor
* Note: Please be advised that the sensors Peco and Teco can appear in this diagram
26 5
eventhoug they are out of use for Units with software ver. 0240 and forward.
1
Legend Low Pressure Stage High Pressure Stage Cu pipes according to EN 12735-1.
Suction Gas Line Pipe size Wall dim. in mm
Liquid Line 1/2" 0,8
Hot Gas Line 3/4" 0,9
Electrical Line 1 1/8" 1,02
Item No. 810900B Operating and service manual
AWG 16 AWG 16
FC
F4 10A
L2 L2 [Black]
2 4 K1 X100
F3 10A 1 1 1
X51 (J3) X52 (J1) L1 L1 [Black] L1 2 1
3 3 FC-com
3 [Y/G] 3
1 1 GND 1 3 3 2
F2 0,4A
metering
metering
TR2 L2 4
Voltage
Current
J5
2 2 2 3
3 3
L3 F1 0,4A 5 5 2
4
1
RMM - York TR1 L3 6
1
AWG 18
J4
4 4 AWG 18
2
Power line L2 X42 K2
[Black]
[Black]
5 RX modem 5 10 1
1 1 1 1
J3 6 TX 6 L1 2
7 L1 T1
7 3 3
10 TRAFO Outside Box
L3 4
1
J2 X50 (J5) 1 5 5 Inside Box
RMM 0VAC
1 0VAC (GND) X34 2
L2 6
X36 X30
1 1 1 [Red] 1
2 1 1 3
J1 RMM 24VAC 2 2 [Red] 2 Hevap
3 24VAC 2 2 4
3
F6 6,3AT 3 [Red] 3 K3 Note: Heater element for Tray and
3 3 5 TRAFO T1 approx voltages X60
1 1 wires 13 and 14 are optional
4 24VAC 0VAC 4 [White] 4 Terminal 1-2 : 440V AC 2 2 2 1
4 4 6 1
Terminal 3-4 : 20V AC 3 1
York - RMM Slave [Y/G] 3 3 4 2 2
Terminal 5-6 : 24V AC 4 4 2
mk IV B, Rev. D X35 X35 4 3
Conn side view 4 3 5 4
[Red] RMM 24VAC 1 5 5 7 5
46 A 26 6 6 6 6 6
4 Hevap
[White] RMM 0VAC 2 FC-com 8 7
45 GND 25 6 9 8
1 3 5 11 (15 x 0,75mm2 / 9
74 RX B 24 Inside Box 2
(3 x 0,50mm2) 10 15 x AWG 18) 10
RMM-com 3 6 12 11
[Black]
[Black]
[Black]
75 GND Outside Box 13 12
2 1 RS232 7 13
Inside Box 76 TX LM front A 4
2 B 8 14 14
Outside Box 3 C Retriever plug Y/G Y/G
NOTES: Vexp 82 +24VDC D at front of unit K4
1) Please be advised the shown sensors Peco and Teco are Vexp V E 1 1
32 GND 1 2 1
out of use for units with software ver. 0240 and forward. RXD 27
Veco V +24VDC 78 1 1
30 GND
GND 77 2 2
1 3 3
1 1
Inside Box Pdis 3
15 +5VDC
2
A A
USDA1 K5B
2
3
4
Mcond 4
5
4
5
M
Pdis P 16 SIGNAL B B
AWG 16
1 5 6 6
Controller Hatch 2 SIGNAL 51 Tusda1 27 6 (9 x 0,75mm2 /
17 GND 2 1 28
GND 1 A A 7 9 x AWG 18) 7 7
1 8 8 8
65 +5VDC 1 2 USDA2 37
SIGNAL 52 B B Y/GR Y/GR
Peco 3 Tusda2 38
Peco P 66 SIGNAL 2
2 GND 2 1
NOTE 1) 67 GND A A
1
SW5 SWITCH PCB X21 1 SIGNAL 53 Tusda3 2 USDA3 K5
24VAC
4 18 +5VDC 2 B B 1 1
0VAC
X1 INTF5
INTERFACE
PCB
X8 X2 X32
10 X2 Me2OH Mevap2 - 7
Keypad KEYPAD 87
Mevap2 - 8 RCCU5 8851560103
37
X3 X33 Me1OH
86
Mevap1 - 7
Overall Wiring Schematic
X3 Mevap1 - 8
36
McOH Mcond - 7
[Y/G] 85
Mcond - 8 Lodam electronics a/s
35
P/N: 5251560403 Rev: 1.63
Item No. 810900B Operating and service manual
lll#hiVgXdda#Y`
')"]djg]dia^cZhjeedgi
8VaajhVi )*,(+)(*%%dghZcYjhVcZ"bV^aVi
hZgk^XZ5hiVgXdda#Y`# Djg hZgk^XZ YZeVgibZci ^h
VkV^aVWaZ')]djghVYVn!,YVnhVlZZ`egdk^Y^c\
ZVhnVXXZhhidi]ZVchlZghndjcZZY#
Bgh`8dciV^cZg>cYjhig^6H
7_ZgcYgjekZ_),
+(+%I^c\aZk ###8ddaI]^c`^c\
9ZcbVg`
Ia[/ )*,(+)()%%
;Vm/ )*,(+)(*+.
lll#bX^XdciV^cZgh#Xdb
KZgh^dc-&%.%%7 8deng^\]i'%%,Bgh`8dciV^cZg>cYjhig^6H
March 2008