Carrier x4 7300 Operator's Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21
At a glance
Powered by AI
The key takeaways are how to operate the display unit, start and stop the refrigeration unit, check alarms and hour meters. Tips are also provided for pre-trip inspection.

The main components of the display unit include the LCD display, menu key, alarm key, arrow keys, start/run-off switch and soft keys.

To start the unit, place the start/run switch in the start/run position. The unit will go through a start sequence and start automatically. If alarms are present, they must be cleared first.

EASY TO RUN

X4t 7300/7500
Trailer & Rail Refrigeration Units

S Display
S Display Screens
S Starting Unit
S IntelliSett
S Pretrip
S Changing Setpoint
S Start-Stop or
Continuous Operation
S Data Recorder/Trip Start
S Manual Defrost
S Language Selection
S Unit Data
S Alarm List - View Alarms
S View Hour Meters
S Stopping Unit

©Carrier Corporation, 2015 D Printed in U. S. A. May 2015


EASY TO USE

DISPLAY
1 2 3 4 5 6

ALARM

START/STOP

CONTINUOUS

DEFROST
7

MENU

I START/RUN

O OFF

11 10 9 8

1. MENU Key
2. DEFROST Key
3. START/STOP - CONTINUOUS Key
4. Alarm LED
5. ALARM Key
6. “=” (Select) Key
7. Arrow Keys
8. START/RUN-OFF Switch
9. Soft Keys
10. USB Interface Port
11. LCD Display

1
EASY TO USE

Display Screens
LCD DISPLAY SCREENS
START/STOP DIESEL COOL START/STOP DIESEL COOL
1

36.2
5 Viewing Menu Soft Key
3
36
Selections
2 Press Menu Key to Scroll
BOX TEMPERATURE 5F SETPOINT 5F
4 INTELLISET PRETRIP HOUR UNIT
STATUS OK 6 METERS DATA

1. Status Bar 5. Operator Message Panel


2. Box Temperature 6. Soft Key Descriptions
3. Setpoint (Order of presentation may
4. MessageCenter not be as shown.)

DEFAULT SCREEN TYPICAL MENU SCREEN

SAMPLE SCREEN (1 OF 3)
7
DISPLAYED ITEM #1
DISPLAYED ITEM #2 10
DISPLAYED ITEM #3
END OF LIST
8
BACK EXIT

7. Highlight -White letters on a black background.


8. BACK Key - Used to return to the previous screen.
9. EXIT Key - Used to return to the default screen.
10. The position of the highlighted item and total number of
items in the list is displayed in the status bar. Up to 5 items may
be displayed at a time. Press the B key to view the additional
items, or Y key to scroll back up the list. “END OF LIST” will be
displayed after the last item in the list.

2
EASY TO START

STARTING UNIT

WARNING
Under no circumstances should ether or any
other starting aids be used to start the engine.

ALARM
3

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

36 .2
DEFROST

MENU
BOX TEMPERATURE 5F
36
SETPOINT 5F

STATUS OK
4

I START/RUN

O OFF
1
1. Place the START/RUN-OFF switch in the START/RUN position.
2. The system will display the Carrier Transicold logo, display the
default screen, present language selection and the hour meter
readings (if configured to do so) along with a test flash of the
alarm light. The system will then perform a start sequence, ener-
gize the buzzer, and then start the unit automatically.
3. If there is an alarm present, the alarm message will be displayed
in the MessageCenter and the alarm LED will flash for 5 seconds.
If one or more shutdown alarms are present, the alarm(s) must
be cleared before the unit will start.
4. Observe the MessageCenter. If the word “ACTIVE” or “MOD-
IFIED” is displayed at the right, the unit is equipped with Intelli-
Set. Proceed to page 4. If “ACTIVE” or “MODIFIED” is not dis-
played, proceed to page 6.
5. If the LCD Display does not illuminate, check:
S Battery voltage. A booster battery may be needed.
S Check for blown fuse(s).
S Verify the harness connector at the back of the display module
and all other module connectors are securely attached.

3
EASIEST TO SET

INTELLISET
Products carried or stored in a refrigerated compartment require a
multitude of refrigerant unit settings that must be checked and, if
required, reset each time a new product is loaded. The APX Control
System offers the settings necessary to meet these requirements.
IntelliSet is a feature that allows pre-selection and naming of the
necessary settings for up to 40 different products. The operator may
then call up the settings by simply selecting the assigned IntelliSet
name.
For example: a load of apples may require continuous operation at 35°F
(1.7°C ) with a defrost every 3 hours while a load of cheese may require
the same operation with setpoints ranging from 35°F to 42°F (1.7°C to
5.6°C) and a load of ice cream requires start-stop operation at -22°F
(-30°C) with defrost at 12 hour intervals. The settings required for each
product may be entered into the system and locked so that they cannot
be changed, and they can be given an appropriate name. In the case
of cheese, the range of setpoints may be locked, leaving the operator
the ability to change the setpoint within the locked range.
When a load of apples is going to be picked up, the operator simply
selects “APPLES” from the IntelliSet menu; for cheese, “CHEESE” is
selected and the setpoint reset as required; for ice cream, “ICE CREAM”
is selected. With each selection, the system automatically re-programs
the settings to provide the best temperature control, fuel economy, and
performance for that particular product.
NOTE: The above settings are examples of possible settings.
Units leave the factory with default IntelliSets. However, most
customers develop their own set.
An IntelliSet may be pre-programmed as “IntelliSleep” which allows
Sleep Mode to be entered by simply changing to that IntelliSet. Range
Protect may be applied to any single IntelliSet. Range Protect offers
increased fuel savings over normal Start-Stop Operation for
commodities that can use less restrictive temperature control.

4
EASY TO SET INTELLISET

CHANGING INTELLISET SELECTION


1. With the system powered up (START/RUN-OFF switch in the
START/RUN position) and the default screen displayed, press the
“=” key. If the screen shown just above step 3 below is displayed,
proceed to step 3. Otherwise, proceed to step 2.

ALARM

START/STOP
3
START/STOP DIESEL COOL
CONTINUOUS

DEFROST
Viewing Menu Soft Key 1&4
Selections
MENU
Press Menu Key to Scroll 3
INTELLISET PRETRIP HOUR UNIT
METERS DATA

2. Press the MENU key until INTELLISET is displayed. Then, press


the INTELLISET soft key to display the IntelliSet screen.
IntelliSets
IntelliSet Off
Banana Active
Flowers 5
Lettuce
Cheese
BACK EXIT

3. The IntelliSet screen will display with a 15 second timeout. The cur-
rent IntelliSet will have the word “ACTIVE” or “MODIFIED” to the
right. Press the Y or B key to scroll through the list of available In-
telliSets.
4. With the desired IntelliSet highlighted, press the “=” key. The high-
lighted IntelliSet will become active and an “INTELLISET
CHANGED” message will display.
5. Press the EXIT soft key to return to the default display.
NOTE: if setpoint change is allowed, refer to Page 8 for set-
point change instruction.

5
EASY TO CHECK

PRETRIP
Pretrip is a set of tests run by the system to check unit operation. It is re-
commended that a Pretrip is run prior to loading the refrigerated compart-
ment. It will indicate a failure if one is detected.

ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

DEFROST
Viewing Menu Soft Key
Selections
Press Menu Key to Scroll
MENU

INTELLISET PRETRIP HOUR UNIT


METERS DATA
1

1. With the system powered up (START/RUN-OFF switch in the


START/RUN position) press the MENU key until PRETRIP is dis-
played.
2. Press the PRETRIP soft key to display the Pretrip screen.
Pretrip Menu
Start Pretrip
View Results of Last Pretrip

BACK EXIT

3. The Pretrip screen will display with a 15 second timeout. Press the
Y or B key to scroll through the available selections. With the de-
sired selection highlighted, press the “=” key.
4. If “Start Pretrip” is selected, Pretrip will begin and the Pretrip Status
screen will be displayed. Immediately following Pretrip OR if “View
Results of Last Pretrip” is selected the Pretrip Summary Screen will
be displayed.
NOTE: At any time during Pretrip, the UNIT DATA soft key may
be pressed to allow the user to view the unit data screen (refer
to page 14). To return to Pretrip, press the BACK soft key.

6
EASY TO CHECK

PRETRIP - CONTINUED
PRETRIP STATUS
Pretrip Type: Cool - Ambient 755F
Test 2 of 10 - Current Test
SV1
Current Draw - 2 Amps
23%
UNIT TEST STOP
DATA RESULTS PRETRIP

NOTE: During Pretrip the ALARM light will illuminate to indic-


ate there is no temperature control.
5. During Pretrip Test 1, verify that both lights on the light bar are illu-
minated. During Pretrip Test 2, verify that the buzzer is energized
and the AutoFresh air port opens and closes (if equipped).
6. The remainder of the Pretrip tests will run automatically and take 7
to 15 minutes. The percent of Pretrip that has been completed is
displayed in the status bar under the test description information.
7. “PRETRIP PASS”, “PRETRIP FAIL IN TEST ##” or “PRETRIP
FAILED AND COMPLETE” will be displayed at the end of the test-
ing. To end Pretrip at any time, press the STOP PRETRIP soft key.
PRETRIP SUMMARY
Pretrip Type: Cool - Ambient 755F
Start Time - (date) (time)
End Time - (date) (time)
Pretrip Complete (or fail notice)
VIEW TEST BACK EXIT
ALARMS RESULTS
8

9
8. Press the VIEW ALARMS soft key to move to the Alarm Screen
(refer to page 16) and review any alarms activated during the test.
9. Press the TEST RESULTS soft key to view details of the test res-
ults. Press the Y or B key to scroll through the results.

PRETRIP TEST RESULTS (1 OF 16)


Test 1: Display Passed
Test 2: Electrical Current Passed
Test 3: Sensors Failed
Test 4: Speed Passed

7
EASY TO SET

CHANGING SETPOINT

ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

36.2
DEFROST
2

MENU
BOX TEMPERATURE 5F
36
SETPOINT 5F
3
STATUS OK
2

1. With the system powered up (START/RUN-OFF switch in the


START/RUN position) and the default screen displayed (press the
Back button if required):
2. Press the Y or B key to bring the displayed setpoint to the desired
value.
TIP: The setpoint will change one degree with each press and
release of an arrow key or the setpoint will scroll if the key is
pressed and held.
3. Press the “=” key to save the new setpoint. The MessageCenter
will display “SETPOINT CHANGED” for 10 seconds.
4. If the “=” key is not pressed the setpoint screen will flash, the Mes-
sageCenter will display “SETPOINT NOT CHANGED” and then
return to original setpoint.
NOTE: The setpoint range is from -22°F to +90°F (-30°C to +32°C).
This range may not be fully accessible, depending on the settings
for this system. If the message “MAX SETPOINT HAS BEEN
REACHED” or “MIN SETPOINT HAS BEEN REACHED” is dis-
played, the setpoint range has been locked and can not be
changed outside the range.

8
EASY TO RUN

START-STOP OR CONTINUOUS OPERATION

1&3

ALARM

START/STOP

START/STOP DIESEL COOL


1 CONTINUOUS

36.2
DEFROST

MENU
BOX TEMPERATURE 5F
36
SETPOINT 5F
START/STOP MODE SELECTED

1. With the system powered up (START/RUN-OFF switch in the


START/RUN position) press the START-STOP/CONTINUOUS
key until the desired operation (Start/Stop or Continuous) high-
lighted.
2. The message (“START/STOP MODE SELECTED” or “CON-
TINUOUS RUN MODE SELECTED”) will be displayed in the
MessageCenter for 10 seconds.
3. The operation indication in the status bar will no longer be high-
lighted. The unit is now in the displayed operation.
NOTE: If the message “CONTINUOUS LOCKED” or “START/
STOP LOCKED” is displayed, the system is currently locked
into the displayed operation and cannot be changed using the
“START/STOP - CONTINUOUS” key.

9
EASY TO MONITOR

DATA RECORDER/TRIP START

ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

DEFROST Viewing Menu Soft Key


Selections
Press Menu Key to Scroll
MENU

LANGUAGE DATA EXIT


RECORDER
1

1. With the system powered up (START/RUN-OFF switch in


the START/RUN position), press the MENU key until DATA
RECORDER is displayed.
2. Press the DATA RECORDER soft key to display the sub
menus.
DATA RECORDER
MARK TRIP START
PRINT TO SCREEN NOTE: Choices may
PRINT TO PRINTER vary based on soft-
SCREEN SETUP
PRINTER SETUP
ware revision and
BACK EXIT model type.

3. The Data Recorder screen will display with a 15 second


timeout. Press the Y or B key to scroll through the available
sub menus. With the desired sub-menu highlighted, press the
“=” key to enter the menu.

10
EASY TO MONITOR

DATA RECORDER/TRIP START - CONTINUED


MARK TRIP START
Trip Start places the present time and date as a stamp in the
data recorder memory to allow easy review of the data from the
last trip, and to allow downloading data from a specific trip. A trip
begins at a Trip Start and ends at the next Trip Start.
To enter a Trip Start: with MARK TRIP START highlighted,
press the “=” key. If trip start is acknowledged by the data re-
corder, “TRIP START ENTERED“ will be displayed for 15 sec-
onds and then the display will return to the Data Recorder
screen. In the unlikely situation that the data recorder is not
functioning properly “CANNOT ENTER TRIP START” will flash
and then the display will revert back to the Data Recorder menu.
PRINT TO SCREEN
PRINT TO SCREEN displays a graphical representation of the
recorded data. To display the data: with PRINT TO SCREEN
highlighted, press the “=” key.

75 SETPOINT
RAT
Collecting Data, Please Wait 60
SP
45
Up Key = Next Day 30 SAT
Down Key = Previous Day
Equal Key = Event Toggle 15

EXIT 10:22 2/24/11 EXIT

Once the graphical display is presented, press the Y, B or


“=” keys to move through the recorded data.
When viewing events, the following acronyms will be used:
c = Door Close o = Door Open
d = Defrost start p = Power up
e = Defrost end r = Real time clock change
f = Power down t = Trip Start

11
EASY TO DEFROST

MANUAL DEFROST
2

ALARM

START/STOP

START/STOP DIESEL DEFROST


CONTINUOUS

1 DEFROST

MENU
DEFROST 25
SETPOINT 5F
DEFROST CYCLE STARTED

1. With the system powered up (START/RUN-OFF switch in the


START/RUN position) press the MANUAL DEFROST key.
2. If the conditions for defrost are met, the status bar and the Box
Temperature display will change to the word “DEFROST”. The
MessageCenter will display “DEFROST CYCLE STARTED” for
10 seconds. At the completion of any defrost cycle, the Mes-
sageCenter will return to the default display.
3. If the conditions for defrost are not met, the MessageCenter will
display “CANNOT START DEFROST CYCLE” for 5 seconds.
This message will be activated when:
S The box temperature is too warm. Defrost may be entered
when the defrost termination temperature sensor (DTT) is
below 40°F (4°C) or the supply air temperature sensor
(SAT) is below 45°F (7.2°C) OR
S The engine has not run 15 seconds after starting OR
S The unit is in PC Mode OR
S The unit is in Pretrip OR
S There is an active shutdown Alarm.

12
EASY TO CHANGE

LANGUAGE SELECTION

ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

DEFROST Viewing Menu Soft Key


Selections
Press Menu Key to Scroll
MENU

LANGUAGE DATA EXIT


RECORDER
1

NOTE: Language Selection may not be


available on early software revisions.
1. With the system powered up (START/RUN-OFF switch in the
START/RUN position) press the MENU key until LANGUAGE is
displayed.
2. Press the LANGUAGE soft key to display the language screen.

LANGUAGE
English English
Espanol Spanish

BACK EXIT

3. The language screen will display with a 10 second timeout. Press


the Y or B key to scroll through the available selections.
4 With the desired language highlighted, press the “=” key. The high-
lighted language will become active and “LANGUAGE
CHANGED” will be displayed.

13
EASY TO READ

UNIT DATA

ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

DEFROST Viewing Menu Soft Key


Selections
Press Menu Key to Scroll
MENU

INTELLISET PRETRIP HOUR UNIT


METERS DATA
1 2

1. With the system powered up (START/RUN-OFF switch in the


START/RUN position) press the MENU key until UNIT DATA is
displayed.
2. Press the UNIT DATA soft key to display the unit data screen.

UNIT DATA
Engine
Refrigeration Sensors
Refrigeration System
END OF LIST

BACK EXIT

3. The Unit Data screen will display with a 15 second timeout. Press
the Y or B key to scroll through the available unit data sub menus.
With the desired sub-menu highlighted, press the “=” key to view the
data.
4. The selected sub-menu data will be displayed. For example, the Re-
frigeration Sensor display may include:

14
EASY TO READ

UNIT DATA - CONTINUED

REFRIGERATION SENSORS
Ambient Air Temp: 75.05F
Return Air Temp: 38.05F
Supply Air Temp: 37.05F
Delta T: 1.05F
Defrost Term Temp: 39.05F
LOCK BACK EXIT
SCREEN

5. Press the Y or B key to scroll through the sub-menu data list.


6. To lock the present LCD display press the LOCK SCREEN soft
key. The screen will highlight (white lettering on a black back-
ground) to indicate it is locked and the soft key will change to
UNLOCK SCREEN.
7. Press the UNLOCK SCREEN soft key to unlock the screen or
press the Y or B key to unlock the screen and scroll through the
sub-menu data selections. Press the BACK soft key to return to
the sub-menu selection screen or the EXIT soft key to return to
the default screen.
UNIT DATA LIST
ENGINE REMOTE SENSORS
Fuel level (Optional)
Battery: OK Remote Sensor 1
Amp Draw Remote Sensor 2
Engine Coolant Temperature
REFRIGERATION SYSTEM
REFRIGERATION SENSORS Compressor Suction Pressure
Ambient Air Temp
Return Air Temp
Supply Air Temp
Delta T
Defrost Term Temp

15
EASY TO CHECK

ALARM LIST - VIEW ALARMS

2 1

ALARM

3
START/STOP
ACTIVE ALARMS (2 ALARMS)
CONTINUOUS

DEFROST A13 High Discharge Pressure


A97 Check SV2 Circuit 3
END OF LIST
MENU

CLEAR BACK
ALARMS

1. With the system powered up (START/RUN-OFF switch in the


START/RUN position) press the ALARM key.
2. If there are active alarms, the alarm number will be displayed pre-
ceded by the letter “A” (active alarm). The system may also be
Configured to display an alarm description, following the alarm
number. The last alarm that occurred will be the first alarm dis-
played and so on.
3. Press the Y or B key to scroll through the list of alarms.
4. To clear the alarms, press the CLEAR ALARMS soft key. The
LCD Display will provide an “ACTIVE ALARMS CLEARED” mes-
sage and then return to the default display after 10 seconds.
5. If there are no active alarms, the LCD Display will provide a “NO
ACTIVE ALARMS” message and then return to the default dis-
play after 5 seconds.

16
EASY TO CHECK

VIEW HOUR METERS

ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

DEFROST Viewing Menu Soft Key


Selections
Press Menu Key to Scroll
MENU

INTELLISET PRETRIP HOUR UNIT


METERS DATA
1

1. With the system powered up (START/RUN-OFF switch in the


START/RUN position) press the MENU key until HOUR METERS
is displayed.
2. Press the HOUR METERS soft key to display the hour meter
screen. STANDARD HOUR METERS
Engine Hours 1050 Hours
Switch On Hours 1400 Hours
Total Run Hours 1050 Hours
END OF LIST

BACK EXIT

3. The hour meter screen will display with a 15 second timeout. Press
the EXIT soft key to return to the default screen.

17
EASY TO STOP

STOPPING UNIT

ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

36.2
DEFROST

MENU
BOX TEMPERATURE 5F
36
SETPOINT 5F
STATUS OK

I START/RUN

O OFF

To stop the unit, place the START/RUN-OFF switch in the


OFF position. The unit will shut down immediately while the
system completes a shut down sequence and then the
LCD display will go blank.

18
TIPS
Carrier Transicold wants you to get optimum performance from
your trailer refrigeration unit. The way to get that performance
is to review the following checklist before each trip. Do this and
you’ll be well on your way to ensuring maximum refrigeration
efficiency with a minimum of trouble.

• Examine interior and exterior of the


refrigerated compartment for door, door
seal and wall damage.
• Floor and floor drains should be clear of
debris and drain kazoos installed.
• Evaporator drains should be clear of debris
and drain kazoos installed.
• Use pallets and follow proper loading
instructions, such as the United States
Department of Agriculture Handbook 669,
for maximum air circulation.
• Run Pretrip.
• Precool refrigerated compartment and
cargo. Initiate a manual defrost before
loading.
In an emergency, call Carrier Transicold
Action Line 1-800-448-1661.

Carrier Transicold Division,


Carrier Corporation
P.O. Box 4805
Syracuse, N.Y. 13221 U.S A

www.carrier.transicold.com

North America Central America


Carrier Transicold and Mexico
700 Olympic Drive Ejercito Nacional 253−A Piso 5
Athens, GA 30601 USA Colonia Anahuac
Tel: 1−706−357−7223 11320 Mexico, D.F.
Fax: 1−706−355−5435 Tel: 55315010
Fax: 55315010 ext. 1005

A member of the United Technologies Corporation family.


Stock symbol UTX

Form 62−11643 Rev A

You might also like