TK MD Ii Manual
TK MD Ii Manual
TK MD Ii Manual
w/TK 3.74
TK 41013-1-MM (Rev. 1,10/03)
This manual is published for informational purposes only and the information so provided should
not be considered as all-inclusive or covering all contingencies. If further information is required,
Thermo King Corporation should be consulted.
Sale of product shown in this manual is subject to Thermo King’s terms and conditions
including, but not limited to, the Thermo King Limited Express Warranty. Such terms and
conditions are available upon request. Thermo King’s warranty will not apply to any
equipment which has been “so repaired or altered outside the manufacturer’s plants as,
in the manufacturer’s judgment, to effect its stability.”
R-404A
WARNING: Use only Polyol Ester-based refrigeration compressor oil in
R-404A. See Thermo King Parts Manual for part number.
Do not mix Polyol Ester and standard synthetic compressor oils. Keep Polyol
Ester compressor oil in tightly sealed containers. If Polyol Ester oil becomes
contaminated with moisture or standard oils, dispose of properly–DO NOT USE.
When servicing Thermo King R-404A unit, use only those service tools certified
for and dedicated to R-404A refrigerant and Polyol Ester compressor oils.
Residual non-HFC refrigerants or oils will contaminate R-404A systems.
Table of Contents
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Auto Start/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigeration Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Microprocessor Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Welding of Units or Truck Bodies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Engine—TK 3.74 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
R-134a Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
R-404A Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Air Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electric Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electrical Standby Compressor Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Standby Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Maintenance Inspection Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
X214 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Microprocessor Controller TG-V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Engine Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Electric Operation (Model 50 Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Defrost Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Serial Number Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Unit Photographs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
TG-V Unit Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ThermoGUARD V Microprocessor Controller (TG-V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Remote Control Box Outside (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Other Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Unit Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Unit Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Pretrip Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Starting the Unit—Auto Start Diesel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Manually Starting Units on Diesel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Starting the Unit—CYCLE-SENTRY Units on Diesel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Starting the Unit—Electric Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
After Start Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Loading Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Post Load Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Post Trip Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5
Table of Contents
Electronic Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
TG-V Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Single Temp In-Cab TG-V Controller (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Display Symbols and Control Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Display Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Control Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
General Display Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Displaying Operating Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Entering the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Displaying and Clearing Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Additional Operating Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Sensor Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Temperatures Outside of Display Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Guarded Access Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Testing the TG-V Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
TG-V Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Ice-Water Bath Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Sensor Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Preparing TG-V Module for Bench Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
TG-V Module Bench Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
TG-V Terminal Voltage Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
TG-V Terminal Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
TG-V Terminal Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
TG-V Terminal Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Sensor Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Electrical Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Alternator (Prestolite) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Excessive Voltage Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Electrical Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Charging System (12 Vdc) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Preheat Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
RPM Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Glow Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Engine Reset Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Low Oil Pressure Switch (LOP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Defrost Air Switch Checkout and Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
High Capacity TherMaxTM Heating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Cool Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Heat/Condenser Evacuation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Defrost Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Start Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
MD-II MAX Units Equipped with a Three-Phase Electric Motor and a Phase Converter
That Operates on Single-Phase Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Conversion System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Start System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Run System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Troubleshooting the Phase Conversion System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
In-Cab TG-V Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Field Test Procedure for Single Temperature In-Cab TG-V Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Connector Pins for Single Temperature In-Cab TG-V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
6
Table of Contents
7
Table of Contents
8
Table of Contents
9
Table of Contents
10
List of Figures
Figure 1: Roadside View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 2: Top View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 3: TG-V Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 4: TG-V In-Cab Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 5: X214 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 6: X214 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 7: Remote Light Indicator Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 8: TG-V Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 9: In-Range Temperature Differential Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Figure 10: Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Figure 11: Prestolite Terminal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Figure 12: Flywheel (RPM) Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 13: RPM+ and RPM- Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Figure 14: Glow Plug Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Figure 15: Testing Air Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Figure 16: Air Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Figure 17: First and Second-Phase Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Figure 18: Motor Start Contactor Control Coil Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 19: Third Phase Connection During a Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Figure 20: Third Phase Connection While Running Normally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Figure 21: Single Temperature In-Cab TG-V Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Figure 22: Connecting Tester to Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Figure 23: Connector on Back of Single Temperature In-Cab TG-V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Figure 24: Engine Oil Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Figure 25: Oil Filter Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Figure 26: Oil Bath Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Figure 27: Dry Air Cleaner (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Figure 28: Air Restriction Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Figure 29: Engine Cooling Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Figure 30: Water Pump Assembly and Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Figure 31: Fuel and Oil System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Figure 32: Electric Fuel Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Figure 33: Timing Marks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Figure 34: Individual Cylinder Timing and Firing Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Figure 35: Emission Control Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Figure 36: Integral Fuel Solenoid Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 37: Fuel Solenoid Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Figure 38: Wiring Diagram of Fuel Solenoid Timer Starting 4th Quarter 97 . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Figure 39: Fuel Solenoid Pin Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 40: Relay Socket Terminal Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Figure 41: Fuel Stop Solenoid Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Figure 42: Belt Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Figure 43: Belt Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Figure 44: Alternator Mounting and Belt Tension Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Figure 45: Evacuation Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Figure 46: Vacuum Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Figure 47: Leak . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Figure 48: Moisture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Figure 49: Unit Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Figure 50: X214 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Figure 51: High Pressure Cutout Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Figure 52: Install Gauge Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Figure 53: Compound Gauge Indicating 20 in. Vacuum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Figure 54: Three-way Valve Condenser Pressure Bypass Check Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Figure 55: Location of Expansion Valve Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Figure 56: Completely Wrap Bulb with Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Figure 57: Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Figure 58: Condenser Pressure Bypass Check Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
11
List of Figures
12
Safety Precautions
13
Safety Precautions
14
Safety Precautions
15
Safety Precautions
Low Voltage
Control circuits used in the temperature control
unit are low voltage (24 Vac and 12 Vdc). This
voltage potential is not considered dangerous, but
the large amount of current available (over
30 amps) can cause severe burns if shorted or
ground.
Do not wear jewelry, watch or rings when
working on the unit. If these items contact an
electrical circuit, severe burns may result.
16
Specifications
Engine—TK 3.74
Engine TK 3.74
Fuel Type No. 2 Diesel fuel under normal conditions
No. 1 Diesel fuel is acceptable cold weather fuel
Oil Capacity:
Crankcase & Oil Filter 9 quarts (8.6 liters)
w/Bypass Oil Filter 10 quarts (9.6 liters)
Fill to full mark on dipstick
Oil Type* API Type CF-4 or CG-4 or better multigrade oil
API Synthetic Type CF-4, CG-4 or better after first 500
hours (optional)
Oil Viscosity* -15 to 40 C (5 to 104 F): SAE 15W-40
-20 to 40 C (-4 to 104 F): SAE 10W-40
-20 to 30 C (-4 to 86 F): SAE 10W-30
-30 to 30 C (-22 to 86 F): SAE 5W-30
Engine RPM:
Low Speed Operation 1625 ± 25 RPM
High Speed Operation 2425 ± 25 RPM
Engine Oil Pressure 35 to 60 psig (241 to 414 kPa)
Intake Valve Clearance 0.0079 in. (0.20 mm)
Exhaust Valve Clearance 0.0079 in. (0.20 mm)
Valve Setting Temperature Room temperature
Timing Injection Pump 14 degrees BTDC
Injection Nozzle Pressure 1700 psig (11721 kPa)
Low Oil Pressure Switch (Normally Closed) 10 ± 2 psig (69 ± 14 kPa)
High Coolant Temperature Switch:
Closes 220 ± 5 F (104 ± 3 C)
Opens 190 F (88 C)
Engine Thermostat 180 to 190 F (82 to 88 C)
Coolant System Capacity 4 quarts (3.8 liters) with overflow tank
Radiator Cap Pressure 10 psig (69 kPa)
Drive Belts to compressor, fans, 12 V alternator, water pump
and electric motor (jackshaft)
CYCLE-SENTRY Block Temperature:
Start 30 ± 18 F (0 ± 10 C)
Off 90 ± 8 F (32 ± 4.4 C)
* Multi-viscosity weight oil with the recommended API classification may be used based on the ambient temperature. The
above recommendations are written for mineral oil based lubricants.
17
Specifications
18
Specifications
Air Switch
Air Switch Setting: 0.7 ± 0.05 in. (17.78 ± 1.3 mm) H20
Belt Tension
Tension No. on TK Gauge 204-427
New Belt Field Reset
Engine/Compressor 75 ± 3 70 ± 3
Compressor/Jackshaft (Electric Motor) 72 ± 3 67 ± 3
Compressor/Evaporator Fan/Alternator 1/2 in. (13 mm) deflection
Alternator/Evaporator Fan 1/2 in. (13 mm) deflection
Water Pump 1/2 in. (13 mm) deflection
NOTE: These are the original factory settings. Because it is difficult to use the
TK gauge 204-427 in the field, adjust each belt to allow 1/2 inch (13 mm)
deflection at the center of the longest span.
NOTE: Belts should be tensioned cold and again tensioned cold after 10 hours
of unit running.
Electrical Components
Current Draw (Amps) Resistance—
at 12.5 Vdc (Ohms)
Glow Plug 7 to 8.3 1.5 ± 0.15
Fuel Solenoid:
Pull In 30 to 40 0.41 to 0.31
Hold In 0.97 12.8
Pilot Solenoid 0.657 19
Starter Motor 90 to 105 (cranking)
Damper Solenoid 5.68 2.2
DC Circuit Breakers 50 amp 10.4
20 amp
High Speed Solenoid 5 amp (approx.) 2.5 (approx.)
19
Specifications
Thermostat
Type Solid state THERMOGUARD V Thermostat
Range -20 to 80 F (-29 to 27 C)
Heat Lockout:
Continuous Run Operation High Speed Heat locked out below 15 ± 3 F (-9.4 ± 1.7 C)
CYCLE-SENTRY Operation (Optional Equipment) All Heat locked out below 15 ± 3 F (-9.4 ± 1.7 C)
Electric Standby Operation (Optional Equipment) All Heat locked out below 15 ± 3 F (-9.4 ± 1.7 C)
Electric Standby
Electric Motor 5 hp, 230 V, 60 Hz
RPM 1750
Full Load Amps 14.4 (230)
Locked Rotor Amps 58
Power Requirements 230/3/60 30 Amp, Power Cord Size 10 (AWG) for 50’, 8 for 75’
* w/Heater Strips
Electric Heater Strips (Optional): Number 3
Watts (each) 750
Evaporator High Temperature Cutout Switch: Opens: 150 ± 5.0 F (66 ± 3 C)
Closes: 120 ± 5.0 F (49 ± 3 C)
20
Maintenance Inspection Schedule
A closely followed maintenance program will
help to keep your Thermo King unit in top
operating condition. The following general
schedule is provided to assist in monitoring that
maintenance.
Pre 750 Annual/ Inspect/Service These Items
trip Hours 3,000
Hours NOTE: The 750 hour maintenance interval may be extended to 1,000 hours
or 1 year when equipped with a bypass oil filter.
Microprocessor
• Run pretrip test (see “Pretrip Test” in the Operating Manual).
Engine
• Check fuel supply.
• • Check engine oil level.
• • • Check engine coolant level.
CAUTION: Do not remove radiator cap while coolant is hot.
• • Inspect belts for condition and proper tension.
• • Check engine oil pressure hot, on high speed. Minimum 40 psig (276 kPa) (oil
pressure gauge option).
• • • Listen for unusual noises, vibrations, etc.
• Change engine oil and filters (hot).
• Change oil bath air cleaner element, replace dry type element, clean and service
crankcase breather and check air cleaner hose for damage.
• Change fuel filter.
• Drain water from fuel tank and check vent.
• Inspect/clean fuel sediment bowl and electric fuel pump filter.
• Check and adjust engine speeds (high and low speed).
• Check condition of engine mounts.
• Maintain year round antifreeze protection at –30 F (–34 C).
— Change engine coolant every 2 years.
Electrical
• Check defrost initiation and termination.
• Check thermostat cycle sequence.
• Inspect battery terminals and electrolyte level.
• Check operation of protection shutdown circuits.
• Inspect electrical contacts for pitting or corrosion.
• Inspect wire harness for damaged wires or connections.
• Check calibration of return and discharge air sensor, and optional air sensors, in 32 F
(0 C) ice water.
• Check air switch setting.
• Inspect electric motor bearings.*
• Inspect DC (battery charging) alternator bearings* and brushes.
21
Maintenance Inspection Schedule
22
Unit Description
23
Unit Description
Refer to the Operating Instructions for detailed With the Auto Start/Stop-Continuous Run switch
description of the controller functions. in the Auto Start/Stop position, the
CYCLE-SENTRY system starts the unit on
Operating Modes thermostat demand and shuts down the unit when
the box temperature reaches the thermostat
The MD-II MAX uses a ThermoGUARD V setpoint.
microprocessor controller for operational control
of the unit. On CYCLE-SENTRY equipped units, unit
start-ups may also be initiated by Defrost cycle
Engine Operation initiation or engine block temperature thermostat
demand. In cold ambients, the CYCLE-SENTRY
Continuous Run Operation system demand automatically maintains engine
temperature by restarting the unit if the engine
When the unit is started with the box temperature block temperature drops to 30.0 F (0 C). When the
higher than 3.4 F (1.9 C) above the thermostat unit starts because of low engine block
setpoint, the unit will run on High Speed Cool. temperature, it will run in the operating mode
When the temperature drops to 3.4 F (1.9 C) called for by the unit thermostat until the battery
above setpoint, the thermostat de-energizes the is fully charged and the engine block temperature
High Speed engine solenoid circuit, placing the reaches 90.0 F (32.2 C)
unit on Low Speed Cool. After the unit starts, a Battery Sentry module
When the box temperature reaches the thermostat monitors the voltage across the field of the
setpoint, the pilot solenoid is energized. The alternator and will keep the unit running if the
three-way valve shifts to the Heat position, battery is not sufficiently recharging. The
placing the unit on Low Speed Heat. ThermoGUARD thermostat controls unit
operating mode to maintain the box temperature
If the temperature continues to fall, the thermostat thermostat setpoint. The unit runs in whichever
will shift the unit to High Speed Heat at 3.4 F operating mode the thermostat is calling for to
(1.9 C) below setpoint. The unit will remain on properly maintain the box temperature.
High Speed Heat until the box temperature rises
to 1.7 F (0.9 C) below setpoint. Electric Operation (Model 50 Units)
If the temperature continues to rise to 1.7 F When the unit switch is turned On with the box
(0.9 C) above setpoint, the thermostat temperature higher than 3.4 F (1.9 C) above
de-energizes the pilot solenoid. The three-way thermostat setpoint, the unit will run on Cool.
valve shifts back to the Cool position, placing the
unit on Low Speed Cool. When the temperature drops to setpoint, the
thermostat de-energizes the electric motor
If the temperature continues to rise to 5.1 F contactor, placing the unit on Null.
(2.9 C) above setpoint, the thermostat will
energize the engine solenoid high speed circuit, If the box temperature continues to fall, the
placing the unit on High Speed Cool. thermostat energizes both the electric motor
contactor and the heat contactor (optional) to
CYCLE-SENTRY Operation (Optional) place the unit on Heat at 3.4 F (1.9 C) below
setpoint. The unit will remain on Heat until the
WARNING: With the selector switch in box temperature rises to 1.7 F (0.9 C) below
the Auto Start/Stop position and unit setpoint. The thermostat will then de-energize the
On/Off switch in the On position, the unit electric motor contactor and optional heat
may start at any time without prior contactor, placing the unit on Null.
warning.
If the temperature continues to rise to 5.1 F
(2.9 C) above setpoint, the thermostat will
energize the electric motor contactor, placing the
unit on Cool.
24
Unit Description
25
Unit Description
Protection Devices
• Engine Coolant High Temperature Cutout
Switch
• Engine Low Oil Pressure Cutout Switch
• Evaporator High Temperature Cutout Switch
(Model 50 only) with Heater Option
• Refrigerant High Pressure Cutout
• Refrigerant High Pressure Relief Valve
• 20 Ampere Circuit Breaker in Control Circuit
• 12 V Fuse Link (50 Ampere) (Current
Limiter)
• Overload Relay Protection for Electric
Standby Motor (Model 50)
• 50 Ampere Circuit Breaker in Starting Circuit.
26
Unit Description
Unit Photographs
27
Unit Description
5 6 7 8 9
4 10
11
3
12
15 14 13
28
Unit Description
1 2 3
4 12
14
13
11 10 9 8
29
Unit Description
1 2 3 4 5 6
10 9
30
Unit Description
AEA04
31
Unit Description
8
9
5
10
3
11
2
AEA05
32
Operating Instructions
Start/Stop Light (Optional): When this green light
WARNING: Do not operate the unit until
is On, the CYCLE-SENTRY system is
you are completely familiar with the
functioning normally. A malfunction is indicated
location and function of each control,
if the Auto Start/Stop-Continuous Run Switch is
gauge and indicator on the panels.
set to Auto Start/Stop and the light is off. In this
situation, the unit will not run. The Engine Reset
Unit Controls may be tripped.
Engine Reset: The Engine Reset is a pushbutton
TG-V Unit Control Box switch behind a flexible weatherproof cap. When
Auto Start/Stop - Continuous Run Switch this switch “opens”, the button pops out. It
(Optional): This switch selects Continuous Run remains open until it is manually pushed in to
operation or CYCLE-SENTRY operation. reset the circuits.
• Cont. Run position: The unit will be started When the Engine Reset is open (tripped), the
manually with the On/Off switch and the diesel engine cannot be started. If the reset trips
Preheat/Start switch. After start-up, the unit while the engine is running, the engine will
operates continuously until the On/Off switch shutdown. Four conditions can cause the engine
is turned Off or a protection circuit shutdown reset to trip:
occurs due to a malfunction in the fuel, engine
oil, engine coolant or refrigeration system. • Engine oil pressure drops below 7 to 13 psi
(48 to 90 kPa) while the On/Off switch is
• Auto Start/Stop position: All unit starting switched to On. This includes any situation
operations are performed automatically on which causes the engine to stop or not start
demand. Starting functions such as glow plug within a short period of time.
preheat, fuel and throttle solenoid control and
cranking are performed automatically when • Engine coolant temperature rises above 215 to
operation is required. The engine will start 225 F (102 to 107 C).
automatically for one or a combination of the • Engine oil pressure drops too low.
following conditions:
• The starter exceeds the cranking limit in
a. The Microprocessor Controller calls for CYCLE-SENTRY operation (optional).
heating or cooling.
Some situations which may cause the Engine
b. Manual Defrost initiated. Reset to open are:
c. Engine block temperature drops below a. Engine runs out of fuel.
35 F (2 C).
b. On/Off switch is left On accidentally
Once started, the engine will run until: without the engine being started.
a. Microprocessor Controller demands are c. Engine does not start after cranking in
satisfied, CYCLE-SENTRY mode.
b. The block temperature reaches 90 F d. High refrigerant pressure causes the high
(32 C), pressure cutout to stop the engine.
c. The Defrost cycle is complete. Defrost Light: When this orange light is On, the
The engine is then automatically stopped by unit is operating in the Defrost mode.
the CYCLE-SENTRY control system. Engine Light: When this red light is On, the
Engine Reset switch has been tripped.
33
Operating Instructions
DC Alt Light: When this yellow light is On, there Ammeter (Optional): The Ammeter indicates
is no current output from the alternator. whether the battery is being charged or
On/Off Switch: This switch supplies power to the discharged. The amount of discharge shows
circuits of the unit. whether the glow plugs are functioning properly
during preheat.
• On position: This switch energizes the
electrical system for the unit. ThermoGUARD V Microprocessor
• Off position: This switch de-energizes the Controller (TG-V)
electrical system and the unit will not operate. WARNING: Do not operate the TG-V
NOTE: If the unit is also equipped with an until you are completely familiar with the
In-Cab Control Box. All On/Off switches must meaning of each display symbol, and the
be in the On position before the unit will operate. function of each control key.
Preheat/Start Switch: When held on Preheat, this The programmable TG-V displays temperature
switch energizes the glow plugs in the diesel and alarm conditions. It also functions as a
engine to aid in starting. thermostat and a defrost timer for the unit.
When held on Start, this switch energizes both the The TG-V In-Cab Remote Control Box provides
glow plugs and the starter which cranks the convenient on-the-road unit control from inside
engine. the truck cab. It includes the following:
Manual Defrost Switch: When pushed, the Manual Temperature Display: This digital temperature
Defrost switch starts the Defrost cycle. However, display indicates the temperature of the air
the evaporator coil must be below 42 F (6 C) for returning from the cargo box to the evaporator.
the unit to go into Defrost. A thermal switch on Power Cord Indicator Light (Model 50): When this
the evaporator coil senses this temperature. red light is On, the Electric/Diesel switch is in the
NOTE: The unit will remain in Defrost mode Electric Standby position and the truck ignition is
until the coil temperature rises to 52 F (11 C). on.
Run Hourmeter (Optional on Model 50): The Run OFF Key: Used to turn off the controller and stop
Hourmeter records the total number of hours that the engine or standby motor.
the unit has been in operation. ON Key: Used to turn on the condensing unit and
Engine Hourmeter: The Engine Hourmeter records the controller.
the total number of hours that the diesel engine NOTE: The main unit On/Off switch must be set
has been in operation. This meter can be used to to On before the In-Cab Controller can be
determine proper maintenance intervals. turned On. The unit will automatically start.
Electric Operation Hourmeter (Optional on Model Also, the In-Cab Controller must be On before
50): The Electric Operation Hourmeter records the the main unit can be started.
total number of hours that the electric motor has
SELECT Key: Used to select the various displays
been in operation. This meter can be used to
which can appear on the screen.
determine proper maintenance intervals.
UP Key: Used to increase setpoint temperature
Coolant Temperature Gauge (Optional): The
when the setpoint symbol is on the screen.
Coolant Temperature Gauge indicates the
temperature of the coolant in the engine block. DOWN Key: Used to decrease setpoint temperature
when the setpoint symbol is on the screen.
Oil Pressure Gauge (Optional): The Oil Pressure
gauge shows the engine oil pressure. This DEFROST Key: Used to start the Defrost cycle of the
pressure should rise immediately after the engine evaporator.
starts. ENTER Key: Used to enter new information into the
Suction Pressure Gauge (Optional): The Suction controller.
Pressure gauge indicates the pressure of the
refrigerant gas returning to the compressor.
34
Operating Instructions
NOTE: The ENTER key must be pressed within 6 Remote Control Box Outside
seconds after releasing the UP or DOWN key to (Optional)
complete the setpoint change.
The switches in the remote control box energize
LOW NOISE Key: Used to lock out high speed relays on the option board to control the operation
operation to maintain low speed (low noise) of the unit. The remote On/Off switch and the unit
operation. On/Off switch must both be in the On position for
With the unit switched off, the controller screens the unit to operate. Either switch will turn the unit
will be dark; nothing will be on the display. When off.
the unit is switched On, all symbols and readouts The remote control box mounts on the truck body
will be displayed for about 10 seconds. Make sure beneath the unit to offer easier accessibility to unit
that all display segments are operational. controls. This box offers the following functions:
Standard Display is set to Return Air Temperature Preheat/Start Switch: When pressed to Preheat,
at the factory. Each controller can be programmed the switch energizes the glow plugs to aid in
to show return air or setpoint as the Standard starting. When pressed to Start, it energizes both
Display. the glow plugs and the starter motor.
When unit is switched off, it is normal for display On/Off Switch: The On/Off switch energizes the
to remain On for about 30 seconds. On relay, activating the unit electrical system. The
control panel On/Off switch and the remote
With power off or battery disconnected, all On/Off switch must both be On in order for the
settings are saved in the controller memory and unit to operate. Either switch can stop the unit.
become active when unit is switched On.
Manual Defrost: Pressing the Manual Defrost
During the normal operation, the Standard switch will initiate a Defrost cycle if the
Display is on the screen. evaporator coil temperature is below
Return Air Temperature is factory Standard 42.0 F(5.6 C).
Display setting (can be changed). Other operating Diesel/Electric Switch (Model 50 only): Switches
data can be displayed. the unit to electric motor standby power when
placed in Electric position and power cord is
To view other operating data, repeatedly press and
connected to the box.
release the SELECT key.
The following data may be displayed: Other Controls
• Discharge Air Temperature Defrost Termination Switch: A temperature
• Setpoint Temperature sensitive switch is mounted on the evaporator
coil. It is used to control Defrost. The switch
• Press SELECT key for next display. closes when the evaporator temperature drops to
The remote control box is replaced with an 42 F (6 C). This enables Defrost.
electric standby power receptacle on units that are Defrost Air Switch: The Defrost Air switch senses
equipped with the cab control box. the air pressure difference between the evaporator
coil inlet and outlet. The switch automatically
places the unit on Defrost when the evaporator
temperature is below 42.0 F (5.6 C) and frost
builds up on the coil to a point where the air flow
across the coil is restricted.
35
Operating Instructions
36
Operating Instructions
Control System Circuit Breaker: The control Preheat Buzzer (CYCLE-SENTRY Units): The
system remote reset circuit breakers are located in preheat buzzer sounds when the
the control box. They are designed to protect the CYCLE-SENTRY system causes the glow plugs
12 volt DC control circuit from overloads. To to preheat.
reset the circuit breakers, turn the unit On/Off
switch to the Off position for 30 seconds. Unit Operation
Control Circuit Fuse: Located between the battery
and the unit control circuits (typically inside the Pretrip Inspection
battery box). At about 60 amps, the fuse will melt
Pretrip inspections are a very important part of
and cut battery power to the unit.
regularly scheduled preventive maintenance
Engine Coolant High Temperature Cutout: The programs designed to minimize operating
engine coolant high temperature cutout is a problems and breakdowns before they happen.
temperature sensitive switch located in the engine While pretrips are not intended to take the place
cooling system. of regular maintenance inspections, the following
The engine coolant high temperature switch will suggested pretrip inspection should be performed
close and trip the engine reset if the engine before every trip involving refrigerated cargo.
coolant temperature is greater than 215 to 225 F Fuel: The diesel fuel supply must be adequate to
(102 to 107 C). guarantee the operation of the engine to at least
Evaporator High Temperature Protection Switch
the next check point.
(Model 50): A high temperature protective switch Engine Oil: The
engine oil level should be at the
is located above the evaporator coil to interrupt FULL mark on the dipstick. Never overfill.
the Heat cycle if the temperature above the coil
Coolant: Check coolant level gauge for the correct
exceeds 150 F (66.0 C) during electric standby
amount of coolant. The indicator should be in the
operation.
FULL (white) range. If the coolant level is in the
Engine Low Oil Pressure Cutout: The engine low ADD (red) range, add coolant to the expansion
oil pressure cutout is a pressure sensitive switch tank. The coolant should be a 50/50 mixture of
located in the engine oiling system. This switch ethylene glycol and water and provide protection
will trip the Engine Reset and stop the engine if to -30 F (-34 C).
the oil pressure drops below 8 to 12 psi
(55 to 83 kPa). CAUTION: Do not remove the expansion
Refrigerant High Pressure Cutout: The high tank cap while the coolant is hot.
pressure cutout is a pressure sensitive switch
Battery: The terminals must be tight and free of all
located in the compressor head. If the refrigerant
discharge pressure exceeds the current setting, corrosion. Electrolyte should be at full mark.
this switch opens the circuit to the fuel solenoid, Belts: The belts must be in good condition and
stopping the engine. Within 30 to 50 seconds, the adjusted to the proper tension. Allow 1/2 inch
engine reset will also trip because of low oil (13 mm) deflection at the center of the span
pressure in the engine. For Model 50 units, this between pulleys.
switch also shuts down electric motor operation. Electrical: Check all electrical connections to
Refrigerant High Pressure Relief Valve: This valve make certain they are securely fastened. Wires
is designed to relieve excess pressure within the and terminals should be free of corrosion, cracks
refrigeration system. Located on a high pressure or moisture.
line near the condenser, it is non-repairable and Structural: Visuallyinspect the unit for leaks,
requires no adjustment. When pressure is released loose or broken parts and other damage.
from the valve, it is directed away from anyone
servicing the unit. Gasket: The unit mounting gasket should be
tightly compressed and in good condition.
Coils: The condenser and evaporator coils should
be clean and free of debris.
37
Operating Instructions
Cargo Box: Inspect the interior and exterior of the Manually Starting Units on Diesel
box for damage. Any damage to the walls or Operation
insulation must be repaired.
1. Place the Diesel/Electric switch in the Diesel
Defrost Drain: Check the defrost drain hoses and position and place the power receptacle
fittings to be sure they are open. On/Off switch in the On position.
Doors: Be sure doors and weather seals are in 2. Hold the Preheat/Start switch in the Preheat
good condition, door latches securely and weather position for the required time.
seals fit tightly.
Ambient Temperature Preheat Time
Starting the Unit—Auto Start Diesel
32 to 60 F (0 to 16 C) 30 seconds
Operation
0 to 32 F (-18 to 0 C) 60 seconds
Auto Start is included with the cab control box.
Below 0 F (-18 C) 90 seconds
1. Place the Diesel/Electric switch in the Diesel
position and place the power receptacle
3. Place the control box On/Off switch in the On
On/Off switch in the On position.
position.
2. Place the control box On/Off switch in the On
4. Press the ON key in the cab control box.
position.
5. Hold the Preheat/Start switch in the Start
3. Press the ON key in the cab control box.
position to crank the engine. Release when the
4. The unit should preheat and start engine starts. Do not release the switch
automatically. If the unit fails to start, press prematurely when the engine is extremely
the OFF key and place the On/Off switches in cold.
the Off position. Determine and correct the
6. Turn the control box On/Off switch to Off,
cause of the failure. Push in the reset button
and repeat steps 2 through 5 if the engine fails
and repeat the starting procedure.
to start.
NOTE: The Auto Start system, included with
the cab control box option, functions like the CAUTION: Never use starting fluid.
CYCLE-SENTRY system except that once
started the unit does not shut down on
thermostat demand. The unit runs
continuously until it is turned Off manually. Starting the Unit—CYCLE-SENTRY
Units on Diesel Operation
The start sequence, once initiated, is the
same for both systems. Refer to the Selection of Operating Modes on
CYCLE-SENTRY sections of this manual for CYCLE-SENTRY Equipped Units
further information on the start sequence, as
The Thermo King CYCLE-SENTRY system is
it applies to the Auto Start system.
designed to save refrigeration costs. The savings
vary with the commodity, ambient temperatures
and truck insulation. However, not all temperature
controlled products can be properly transported
without continuous air circulation.
38
Operating Instructions
39
Operating Instructions
NOTE: A unit that is equipped with 7. At the end of the preheat period, the engine
CYCLE-SENTRY should be manually started if will begin cranking. The glow plugs remain
it has been turned Off long enough for the energized during the cranking period. If the
engine to become cold soaked at temperatures engine RPM does not exceed 50 RPM during
below 30 F (-1 C). Place the Auto Start/Stop - the first 4 seconds of cranking, or if the engine
Continuous Run switch in the Cont Run position does not start after 30 seconds of cranking, the
and refer to “Manually Starting Units on Diesel cranking cycle terminates.
Operation” on page 38. After this initial cold
NOTE: If the engine fails to start, the unit
start, the Auto Start/Stop - Continuous Run
reset switch will open, interrupting current to
switch can be switched to the CYCLE-SENTRY
the control system about 40 seconds after
position. CYCLE-SENTRY sensors will then
cranking cycle terminates.
automatically maintain temperatures and
provide reliable unit restarts on demand. 8. If the engine fails to start, place the control
box On/Off switch in the Off position.
Fully charged batteries in good condition are
Determine and correct the cause of the failure,
essential for reliable unit operation. This is
then push in the reset button and repeat the
especially true on CYCLE-SENTRY equipped
starting procedure.
units in cold weather.
1. Place the Diesel/Electric switch in the Diesel Starting the Unit—Electric
position and place the power receptacle Operation
On/Off switch in the On position.
1. Place the Diesel/Electric switch in the Electric
2. Place the CYCLE-SENTRY switch in the position.
CYCLE-SENTRY position.
2. Make sure that an On/Off switch is in the Off
3. Place the control box On/Off switch in the On position and that the electric standby power
position. supply is turned off.
4. Press the ON key in the cab control box. The
CYCLE-SENTRY indicator light will come CAUTION: Always turn Off the electric
On. (This light must be On at all times while power supply when handling, connecting,
the unit is in CYCLE-SENTRY operation.) If or disconnecting high voltage power
a malfunction occurs preventing a restart, the cords.
fact that this light is Off is the only indication 3. Connect the power receptacle to the power
a malfunction has occurred. supply. Make sure that the power supply is the
5. Set each thermostat at the required correct voltage, phase, and frequency.
temperature. Do not set a thermostat lower 4. Turn the high voltage power supply On.
than required (lowering the thermostat
setpoint does not make the unit cool faster). CAUTION: Do not start the electric motor
6. If a thermostat calls for Cool or Heat, the glow unless the diesel engine is completely
plugs will automatically heat for the required stopped.
amount of time depending on the engine
5. Place the On/Off switches in the On position
temperature (5 seconds at 150 F [66 C] to
and press the ON key.
120 seconds at -20 F [-29 C]).
6. Set each thermostat setpoint at the required
temperature. Do not set a thermostat lower
than necessary. Setting the thermostat below
the required setpoint will not make the unit
cool faster.
40
Operating Instructions
9. If the fan rotation is correct, leave the unit 3. Load product so that there is adequate space
turned On. for air circulation completely around the load.
Do not block the evaporator inlet or outlet.
10. If the rotation is incorrect, the phase of the
power supply is wrong and must be corrected. 4. Products should be pre-cooled before loading.
Turn Off the power to the cable and reverse Thermo King units are designed to maintain
the position of any two power leads from the loads at the temperature at which they were
power cable plug. Do not disturb the green loaded. Transport refrigeration units are not
ground wire. (Refer this procedure to a designed to pull hot loads down to
qualified electrical repairman). temperature.
Defrost: When the unit has finished pre-cooling 3. Check for loose or missing hardware.
the truck interior (evaporator coil temperature 4. Check for physical damage to the unit.
below 42 F [6 C]), initiate Defrost cycle with the
MANUAL DEFROST key. The Defrost cycle should end
automatically.
41
Operating Instructions
42
Electronic Controls
TG-V Thermostat 1
The TG-V is a programmable microprocessor
controller that uses external relays. The TG-V
module is replaced as an assembly, no internal
repair is available.
For complete details, see the Microprocessor
Controller TG-V Operating and Setup Manual TK
40284.
Features of the TG-V Thermostat include:
Thermometer: It displays the return air
temperature, and can be programmed to display
the optional discharge air temperature with 0.1
degree accuracy.
Thermostat: It provides temperature control from
-20 to 80 F (-28 to 28 C), in 0.5 degree
increments.
9072a
Defrost Control: When the evaporator coil is cold
enough for frost to form, defrost is automatically
2
initiated every 4 hours during pull-down until the
return air temperature is in range. At in-range 1. LCD
temperatures (between approximately 7 degrees 2. Keypad
above and 7 degrees between point), the controller
is programmable for 2 to 16 hours in 2 hour Figure 8: TG-V Thermostat
increments. Defrost interval is set at the factory
but can be reprogrammed by your Thermo King The keypad and the Liquid Crystal Display (LCD)
Dealer. It can also be programmed to terminate allow the operator to operate the TG-V. The input
defrost at 30 or 45 minutes. and output terminals on the back of the TG-V
monitor unit conditions and control unit functions.
Fuel Saver: It can be programmed to delay high
speed operation for optimum fuel economy.
Alarm: It can detect and display up to four alarm
conditions including sensor, microprocessor, and
defrost termination failures.
43
Electronic Controls
44
Electronic Controls
Display Symbols
Return Air Symbol
(Arrow returning from thermometer to unit.)
Indicates that the return air temperature is being
displayed.
Setpoint Symbol
(Hand pointing to thermometer.) Indicates that the
setpoint temperature is being displayed.
Fahrenheit Symbol
(Degree symbol and letter F.) Indicates that the
temperature being displayed is in Degrees
Fahrenheit.
Minus Sign
Indicates that the temperature being displayed is
below zero.
45
Electronic Controls
Celsius Symbol
(Degree symbol and letter C.) Indicates that the
temperature being displayed is in Degrees
Celsius.
Temperature
When a temperature symbol is displayed:
• Large numbers indicate the temperature in
whole degrees.
• A decimal point and 1/2 size number indicates
temperature in tenths of a degree.
Alarm Symbol
(Exclamation point within a triangle.) When this
flashing symbol is displayed, an alarm (fault)
condition has been detected by the controller.
Alarm Code
When an alarm has been sensed and an alarm
screen has been selected by pressing the SELECT
key, this two-digit code indicates the type of
alarm.
46
Electronic Controls
Control Keys
SELECT Key
(Cycling arrows) is used to select the various
displays which can appear on the screen.
ENTER Key
(Equals sign) is used to enter new information
into the controller.
UP Key
(Arrow pointing upward) When the setpoint
symbol is on the screen, this key is used to
increase the setpoint temperature.
DOWN Key
(Arrow pointing downward) When the setpoint
symbol is on the screen, this key is used to
decrease the setpoint temperature.
47
Electronic Controls
48
Electronic Controls
49
Electronic Controls
• Setpoint Temperature
50
Electronic Controls
• Alarms
(Can be displayed only when an alarm
condition has been sensed by the controller).
When viewing a display...If no keys are pressed,
the Standard Display will automatically reappear
on the screen in about 10 seconds.
51
Electronic Controls
1. Setpoint Symbol
2. Setpoint Temperature
3. New Setpoint Temperature
52
Electronic Controls
53
Electronic Controls
54
Electronic Controls
Additional Operating
Information
Sensor Failure
In addition to generating an alarm, the failure of a
sensor will cause the display screen for that sensor
to show a minus sign and dashes in place of
temperature. The alarm symbol, the minus sign
and the dashes will blink continuously.
55
Electronic Controls
Programming
Programming is done through the Guarded Access
mode.
The Guarded Access mode consists of 5 screens
numbered 1 through 5. Screen numbers are
indicated by a 1/2 size digit.
The Microprocessor Controller is programmed by
entering a two digit set-up code into each screen.
Thermostat Set-Up Codes Set-up code 68 is the standard set-up code for
Screen 1 on CD-II MAX (NAD) units.
Left Digit Right Digit Screen
USA EEC Programming the controller requires the
following:
6 8 9 1
1 1 1 2 • Choosing the desired set-up code for each
screen.
0 0 0 3
0 0 0 4
• Entering the Guarded Access mode.
0 1 1 5 • Changing the set-up codes as required.
56
Electronic Controls
57
Electronic Controls
1. Setpoint Symbol
58
Electronic Controls
59
Electronic Controls
60
Electronic Controls
61
Electronic Controls
62
Electronic Controls
Set-up Code—Screen #1
Save Defrost High Code
Elapsed Terminate Speed
Time Time Delay
No 30 min No 0
No 30 min Yes 1
No 45 min No 2
No 45 min Yes 3
Yes 30 min No 4
Yes 30 min Yes 5
Yes 45 min No 6
Yes 45 min Yes 7
63
Electronic Controls
Screen #2
Defrost intervals are set with Screen #2. A defrost
interval is the period of time between the end of
one Defrost cycle and the beginning of the next.
During pull-down the defrost interval is 4 hours.
Once the unit is in-range, the defrost interval
becomes the interval set with this screen.
64
Electronic Controls
Set-Up Code—Screen #2
Defrost Code
Time Above
Lockout
2 Hours 0
4 Hours 1
Left Digit
6 Hours 2
8 Hours 3
10 Hours 4
12 Hours 5
14 Hours 6
16 Hours 7
1 Hour 8
Defrost Code
Time Below
Lockout
2 Hours 0
4 Hours 1
6 Hours 2
8 Hours 3
10 Hours 4
12 Hours 5
14 Hours 6
16 Hours 7
1 Hour 8
65
Electronic Controls
66
Electronic Controls
Set-Up Code—Screen #3
Discharge Code
Sensor
Grade
0 0
1 1 Left Digit
2 2
3 3
4 4
5 5
Return Code
Sensor
Grade
0 0
1 1
2 2
3 3
4 4
5 5
67
Electronic Controls
Screen #4
The “Standard Display” is set with Screen #4.
Standard Display
The Standard Display normally appears on the
screen. The screen automatically returns to the
Standard Display when viewing of other screens
is complete and no keys are pressed for about 10
seconds.
Settings:
• Return Air Temperature
• Setpoint Temperature
• Discharge Air Temperature (optional).
NOTE: This screen is available only when the NOTE: The Left Digit is always zero.
Discharge Sensor setting (Screen #1) is set to
YES.
• Alternate between Return Air Temperature
and Setpoint Temperature (Return Air 30
seconds, Setpoint 5 seconds).
• Alternate between Discharge Air Temperature
and Setpoint Temperature (Discharge Air 30
seconds, Setpoint 5 seconds). This screen is
available only when the Discharge Sensor
setting (Screen #1) is set to YES, and the
discharge sensor is installed.
NOTE: This screen is available only when the
Discharge Sensor setting (Screen #1) is set to
YES.
68
Electronic Controls
Screen 4 Selection
Default Display Left Digit Right Digit
Code Code
Return Air Temperature 0 0
Setpoint Temperature 00 1
Discharge Air 00 2
Temperature
Alternate Return Air 00 3
Temperature and
Setpoint Temperature
Alternate Discharge Air 00 4
Temperature and
Setpoint Temperature
69
Electronic Controls
70
Electronic Controls
71
Electronic Controls
Code
0
Left Digit
72
Electronic Controls
Directions:
To determine the setting for Screen 5, choose the
temperature differential desired for the in-range
temperature interval.
Example:
To set an in-range temperature differential of 6
degrees above and below the setpoint, select the
number 6.
NOTE: The settings available automatically
correspond to the scale (F or C) chosen in
Display 1.
73
Electronic Controls
74
Electronic Controls
75
Electronic Controls
76
Electronic Controls
77
Electronic Controls
78
Electronic Controls
79
Electronic Controls
2 3 4 5 6 7 8
aea957
80
Electronic Controls
2 3 4 5 6 7 8
aea958
81
Electronic Controls
2 3 4 5 6 7 8
aea959
82
Electronic Controls
AEA617
1. Band Wraps—if Used, The Return Air Sensor Has Yellow Band
Wraps And The Discharge Air Sensor Has Red Band Wraps.
2. Sensor Lead Terminals
83
Electronic Controls
84
Electrical Maintenance
3
1
6 AJA1520
85
Electrical Maintenance
NOTE: All voltage readings should be taken b. If there is low or no output, the alternator
between the negative battery terminal, or a good is probably faulty. However, the following
chassis ground, and the terminals indicated, items are potential causes for not charging:
unless stated otherwise.
• Check the alternator brushes
1. Set the unit for Continuous Run operation and
• Check the 2A circuit from the
place the On/Off switch in the Off position.
alternator to the battery
2. Check the battery voltage. If the battery
• Properly tension the alternator belt
voltage is less than 12 volts, the battery must
be charged or tested to determine if it should • Check battery cable connections and
be replaced. the alternator ground. They must be
clean and tight
3. Check the voltage at the B+ terminal on the
alternator. Battery voltage must be present. If • The battery must be in good condition
not, check the 2A circuit. and must accept a charge
4. Check the voltage at the VOLT SENSE • Check for excessive or unusual
terminal on the alternator. Battery voltage amperage draw by the unit control
must be present. If not, check the 2 circuit. circuits.
5. Set the unit for continuous run operation and
place the main On/Off switch in the On Excessive Voltage Output
position. 12 Volt Alternators With Internal Regulator
Setting: When a Thermo King unit is installed on
6. Wait 20 seconds for the unloading timer to
a truck, it is often connected to a truck battery.
de-energize the unloading relay and check the
When both the Thermo King unit and the truck
voltage at the EXC terminal on the alternator.
engine are running on the truck battery, the
Battery voltage must be present. If not, check
charging system with the higher voltage may
the EXC circuit.
automatically turn Off the charging system with
7. Attach a clamp-on ammeter to the 2A wire the lower voltage output.
connected to the B+ terminal on the alternator.
If it is determined that the Thermo King regulator
8. Connect a voltmeter between the B+ terminal setting is higher than the truck charging system or
and a chassis ground. the batteries are consuming more water than
normal the following solution may help solve the
9. Start the unit and run it in high speed.
problem.
10. Connect a jumper wire between the F2
• Remove the wire labeled SENSE and tape off.
terminal and a chassis ground. This will full
field the alternator. • Add a jumper wire from 2A to the SENSE
terminal on the back of the alternator.
CAUTION: Never apply battery voltage to This should reduce the voltage to the battery by
terminal F2 or voltage regulator failure 0.2 to 0.3 of a volt.
will occur.
a. Full alternator output (the alternators rated
output) indicates the alternator is good but
the voltage regulator needs replacement.
86
Electrical Maintenance
87
Electrical Maintenance
Glow Plugs
Glow plugs heat the combustion chamber to aid in
quick starting. The glow plugs are energized when
the microprocessor initiates unit start-up. A
defective glow plug (burned out) can be detected
Figure 13: RPM+ and RPM- Wires
by placing an external ammeter in series with the
plugs. Normal current draw is approximately
3. Place the unit in Continuous Run. Run the unit 21 to 25 amps when preheating. A current draw of
on low speed and high speed. Check the AC 21 to 25 amps means all three glow plugs are
voltage output across the sensor terminals. working. If the current draw is less than 21 amps
Use a meter with a high ohms per volt internal on Preheat, at least one glow plug is bad.
resistance. A Simpson 260, Fluke digital or
To isolate an open circuit glow plug, remove the
any good VOM will work. However, an
jumper bar and test each glow plug individually
automotive type meter may not give an
with an ohmmeter or a jumper wire and ammeter.
accurate reading because the meter may load
Each glow plug should have a resistance of
the circuit heavily and cause the voltage level
approximately 1.5 ohms or a current draw of
to appear lower than it actually is.
about 8 amps.
a. The output voltage should be 1.0 to
2.0 Vac on low speed.
b. The output voltage should be 2.0 to
2.5 Vac on high speed.
NOTE: If the voltage is slightly off, the
voltage may be increased by turning the
sensor in more, and the voltage may be
lowered by turning the sensor out more.
4. Reconnect RPM+ and RPM- wires on RPM
sensor.
If the RPM sensor passes the above test, the
sensor may be considered good. 1. Ohmmeter
If the unit is not available, an alternate less 2. 1.5 Ohms
reliable test may be performed as follows: 3. Remove Bar
Disconnect the sensor from all wires, and measure Figure 14: Glow Plug Test
the resistance across the terminals and from each
terminal to the aluminum case. The resistance With an external ammeter connected in series, a
should be 250 to 300 ohms across the terminals, shorted glow plug will show excessive current
and there should be no continuity from each flow (more than 12 amps) when the Preheat is
terminal to the case. initiated. When fuse F6 is blown, check each plug.
88
Electrical Maintenance
89
Electrical Maintenance
90
Electrical Maintenance
line just past the receiver outlet check valve to the (7K) de-energized. This reduces the load. The
accumulator inlet. The receiver outlet check valve Start Up mode is used for both diesel and electric
is located in the liquid line near the drier/receiver operation.
outlet. This check valve prevents refrigerant from
migrating back into the receiver tank and MD-II MAX Units Equipped with
condenser during the Heat mode.
a Three-Phase Electric Motor
Cool Mode and a Phase Converter That
Operates on Single-Phase
The Cool mode has not been changed in the Power
TherMaxTM heating system. The TherMaxTM
solenoid, which is normally closed, is MD-II MAX units that are ordered with the
de-energized during the Cool mode. The single-phase 220 volt electric standby option are
TherMaxTM solenoid separates the high side from equipped with a three-phase electric motor and a
the low side. When the TherMaxTM solenoid is phase conversion system. This electric motor is
closed, it does not allow liquid refrigerant to flow the same 5/4.2 hp (3.7/3.1 kW) motor used in
from the liquid line, through the TherMaxTM MD-II MAX units with a three-phase electric
solenoid line, to the accumulator. standby option. The phase conversion system
enables the three-phase electric motor to operate
Heat/Condenser Evacuation Mode using power from a single-phase power source.
The unit will run in the Condenser Evacuation NOTE: The suction pressure regulator must be
mode for two minutes before entering the Heat set at a maximum of 19 psig (131 kPa) on these
mode. This is accomplished by opening single-phase units. A higher setting will overload
(energizing) the TherMaxTM solenoid while the the electric motor. To check the suction pressure
unit is running in cool. The pressure difference regulator setting, run the unit on Defrost and
between the high pressure in the condenser and observe the suction pressure.
the low pressure in the accumulator drives much The overload relay is set at 18 amps. A higher
of the refrigerant out of the condenser and setting may not provide adequate protection.
receiver into the accumulator. The refrigerant is
then available for improved heating capacity. The Voltage taps (230 volt or 208 volt) for the
unit is placed in the Heat mode by opening transformer are located on the test strip in the
(energizing) the hot gas solenoid and closing control panel. To make sure the unit operates
(energizing) the condenser inlet solenoid. The properly, wire L1A should be connected to the
TherMaxTM solenoid remains open while the unit voltage tap that matches the voltage of the power
is in the Heat mode. The receiver outlet check source. Wire L1A is normally connected to the
valve prevents the migration of refrigerant back 208 volt tap.
into the receiver tank and condenser.
Conversion System
Defrost Mode The phase conversion system itself consists of a
The Condenser Evacuation mode is not used start system and a run system. The start system is
before the Defrost mode. The TherMaxTM energized by the high current draw that is present
solenoid, the hot gas solenoid, and the condenser while the motor is starting under a load. Once the
inlet solenoid are all energized at the same time. motor is running at normal speed and the current
The TherMaxTM solenoid remains open while the draw has dropped, the start system is de-energized
unit is in the Defrost mode. and the run system is solely responsible for the
phase shift. The run system is always connected to
Start Up Mode the motor circuit, but it does not affect the circuit
while the start system is energized because the
For the first 20 seconds when the unit is started it start capacitors have much larger capacitance and
runs in the Cool mode with the TherMaxTM dominate the run capacitors.
solenoid open and the alternator excitation circuit
91
Electrical Maintenance
92
Electrical Maintenance
93
Electrical Maintenance
Run System
The components of the run system are:
• a run transformer
• two run capacitors (60 µF each)
• two run bleed down resistors (560 k ohms
each).
94
Electrical Maintenance
95
Electrical Maintenance
Troubleshooting the Phase If the run current is higher than 14.5 amps in all
Conversion System three wires, check the suction pressure regulator
setting before replacing the motor. Check the
If the electric motor does not run properly, first
setting of the suction pressure regulator by
check the line voltage, the motor contactor, and
observing the suction pressure while the unit is
the motor overload relay. if these are all
running in defrost. If the suction pressure is higher
acceptable, test the electric motor to narrow down
than 19 psig (131 kPa), the suction pressure
the possible causes for the problem. See the
regulator must be adjusted or replaced.
Troubleshooting Chart for the individual
component tests. Replace the motor if currents are out of these
ranges.
Electric Motor Tests
Test 2.Run the motor with single-phase power and
Test 1. Run the motor with three-phase power. the phase conversion system connected to the
motor.
Disconnect the T1, T2, T2A, T3E, and T3F wires
from the motor and connect three-phase power Remove the electrical connection box cover on
directly to the motor. Connect L1 to leads 1 and 7, the motor, and check and record the current
connect L2 to leads 2 and 8, and connect L3 to readings in the following chart.
leads 3 and 9. Start and run the unit. Check and
record the voltage and current readings in the Wire (Motor Lead) Start Run
Current Current
following chart. T1 (1)
Wires Voltage T1 (7)
L1-L2 T2 (3)
L2-L3 T2A (9)
L3-L1 T3E (2)
T3F (8)
Wire Start Current Run Current The electric motor has two sets of windings. This
L1 test separates the sets.
L2
L3 The start current should begin at 40 to 45 amps,
and then drop off to approximately 20 amps in 1
to 3 seconds (in wires T2 and T2A). After 3
The ideal voltage is 208 to 235 volts ac and the
seconds, the run current should stabilize at 4 to 8
voltage should not vary more than 10% between
amps (in each of the six wires).
the sets of wires. If the voltages are out of these
ranges, check the power source. Circuit T2A contains the current relay, which
controls the motor start contactor. If the start
The start current should be approximately 75
current is in the proper range but the motor does
amps.
not shift to run after 3 seconds, go to Test 3. If the
The run current should not exceed 14.5 amps. start or run currents are very uneven, go to the
start or run capacitor checks in the
The current should not vary more than 10%
Troubleshooting Chart.
between wires.
NOTE: Wire L1A should be connected to the
transformer voltage tap that matches the line
voltage of the power source. High voltage on the
208 volt tap will cause high run currents.
96
Electrical Maintenance
Test 3. The unit Starts but does not shift to the run
system.
If the motor starts correctly but the current
remains at approximately 20 amps after 3
seconds, the start system is not being
de-energized. Use the following procedure.
1. Locate the current relay in the main control
panel.
2. Disconnect the 7EA and 7EB wires.
3. Install a switch between the 7EA and 7EB
wires.
4. Close the switch between the 7EA and 7EB
wires and start the motor.
5. Wait 3 seconds and then open the switch
between the 7EA and 7EB wires.
c. If the motor does not shift to run, check for
a faulty motor start relay or a faulty motor
start contactor.
d. If the motor shifts to run, check for a
faulty current relay or an overload on the
motor.
e. If the motor shifts to run but then slows
down or stops, check for a faulty
transformer or faulty run capacitors.
See the Troubleshooting Chart for the individual
component tests.
97
Electrical Maintenance
Troubleshooting Chart
NOTE: All amperage and voltage measurements
should be taken with the unit turned On and the
motor running or attempting to start. Most of the
voltage measurements can be taken inside the
unit control box, from the components in the
high voltage tray and from the test point strip.
The voltage measurements associated with the
components under the motor pedestal should be
taken at the test point strip before checking the
components and connections under the pedestal.
The overload relay will trip if the motor does not
start shortly after the motor contactor is
energized.
98
Electrical Maintenance
99
Electrical Maintenance
100
Electrical Maintenance
101
Electrical Maintenance
Parts List for the MD-II MAX Single-Phase Electric Motor System
Quantity Description Part Number
1 Electric Motor 104-466
1 Electric Motor Pulley 77-1980
1 Motor Contactor 44-2853
1 Overload Relay 44-6662
1 Current Relay 44-8755
1 Motor Start Relay 44-5837
1 Motor Start Contactor 44-2853
1 Transformer 44-8756
2 Start Capacitors 44-8758
2 Run Capacitors 44-8757
1 Filter Capacitor 44-8759
2 Run Capacitor Resistors 44-8760
2 Start Capacitor Resistors 44-8761
102
Electrical Maintenance
In-Cab TG-V Controller The same interconnecting harness is used for the
Single Temperature In-Cab TG-V and the
Multi-Temp In-Cab TG-V.
A stand alone tester is available as P/N 204-831. It
will test all In-Cab TG-V Controllers.
103
Electrical Maintenance
104
Electrical Maintenance
105
Electrical Maintenance
106
Engine Maintenance
107
Engine Maintenance
108
Engine Maintenance
109
Engine Maintenance
Engine Cooling System All water-cooled engines are shipped from the
factory with a mixture of 50% permanent type
General Description antifreeze concentrate and 50% water in the
engine cooling system.
The engine employs a closed, circulating type,
pressurized cooling system. Correct engine This provides the following:
temperatures are controlled and maintained by a 1. Prevents freezing down to -30 F (-34 C).
radiator, fan and thermostat. The coolant is
circulated through the system by a belt-driven 2. Retards rust and mineral scale that can cause
centrifugal pump. The pump draws the coolant engine overheating.
from the side of the radiator (large header), 3. Retards corrosion (acid) that can attack
circulates it through the cylinder block and head, accumulator tanks, water tubes, radiators and
then back to the radiator. A thermostat mounted in core plugs.
the water outlet from the cylinder head to the
radiator automatically maintains coolant 4. Provides lubrication for the water pump seal.
temperature within the specified temperature
range.
3
2
1 4
6
7
8
AJA590
110
Engine Maintenance
Antifreeze Maintenance Procedure a. Run clear water into radiator and allow it
to drain out of the drain cock until it is
As with all equipment containing antifreeze,
clear.
periodic inspection on a regular basis is required
to verify the condition of the antifreeze. Inhibitors b. Close the block drain and install a
become worn out and must be replaced by commercially available radiator and block
changing the antifreeze. Change green or flushing agent, and operate the unit in
blue-green engine coolant every two years. accordance with instructions of the
flushing agent manufacturer.
Do not mix green or blue-green engine coolant
with ELC (red) engine coolant. c. Open the engine block and accumulator to
drain water and flushing solution.
The factory recommends the use of a 50/50%
antifreeze mixture in all units even if they are not
exposed to freezing temperatures. This antifreeze CAUTION: Avoid direct contact with hot
mixture will provide the required corrosion coolant.
protection and lubrication for the water pump.
3. Run clear water into the radiator, and allow it
to drain out of the drain cock until it is clear.
Checking the Antifreeze When water has finished draining, close drain
Check the solution concentration by using a cock.
temperature compensated antifreeze hydrometer
4. Inspect all the hoses for deterioration and the
or a refractometer designed for testing antifreeze.
hose clamp tightness. Replace if necessary.
Maintain a minimum of 50% permanent type
antifreeze concentrate and 50% water solution to 5. Loosen the water pump belt. Check the water
provide protection to -30 F (-34 C). Do not mix pump bearing for looseness.
antifreeze stronger than 68% permanent type
6. Inspect the radiator cap. Replace the cap if the
coolant concentrate and 32% water for use in
gasket shows any signs of deterioration.
extreme temperatures.
7. Mix one gallon of the appropriate permanent
Changing the Antifreeze type antifreeze concentrate and one gallon
clean water in a container to make a 50/50
1. Run the engine until it is up to operating
mixture. (Do not add antifreeze and then add
temperature. Stop the unit.
water to the unit. This procedure may not give
2. Open the engine block and completely drain a true 50/50 mixture because the exact cooling
coolant. Observe coolant color. If the coolant system capacity may not always be known).
is dirty, proceed with a, b, and c. Otherwise go
8. Refill the radiator with the 50/50 mixture.
to step 3.
CAUTION: Avoid direct contact with hot Bleeding Cooling System
coolant.
After filling the radiator, run the unit up to
operating temperature to check for overheating
and coolant level and allow the air to be purged
for a few minutes.
111
Engine Maintenance
112
Engine Maintenance
113
Engine Maintenance
Thermo King recommends that any major 4. Crank the engine until fuel appears at the
injection pump or nozzle repairs be done by a nozzles. Tighten the injector lines, and start
quality diesel injection service specialty shop. The the engine.
investment in equipment and facilities to service
NOTE: Fuel will not appear at the nozzles by
these components is quite high. Therefore, this
merely running the electric pump. The
equipment is not found in most repair shops.
engine must be cranked.
The following procedures can be done under field
conditions: Draining Water from Fuel Tank
• Bleeding air from the fuel system. Water run through the system may damage the
injection pump or nozzles. Damage to the fuel
• Maintenance involving the fuel tank and filter
system will subsequently cause more expensive
system.
damage to the engine. A large accumulation of
• Speed and governor adjustments. water in the bottom of the fuel tank will stop a
diesel engine. Water should be drained off during
• Electric transfer pump replacement or repair
scheduled maintenance inspections to prevent
(10 psig [69 kPa] pump with diesel filter).
breakdowns. Drain the water off after the fuel
• Injection line replacement. tank and unit have remained idle for an hour.
• Pump timing. 1. Place a container under the fuel tank to catch
the draining water and fuel.
• Nozzle spray pattern testing and adjustment.
2. Remove the drain plug from the bottom of the
• Minor rebuilding of nozzles.
fuel tank.
Bleeding the Fuel System NOTE: Some fuel tanks have a check valve
in the drain plug fitting. Push the check
The fuel system will have to have the air bled out valve open with a small screw driver to drain
if the engine runs out of fuel, if repairs are made the tank.
to the fuel system, or air gets into the system for
any other reason. 3. Let the water and fuel drain into the container
until no water is visible in the fuel draining
NOTE: MAKE SURE to keep the fuel tank vent from the tank. If the water and fuel do not
open. If the vent becomes clogged, a partial drain freely, the vent may be plugged. If so,
vacuum develops in the tank, and this increases clean or replace the vent.
the tendency for air to enter the system.
4. Install the drain plug.
Proceed as follows:
1. Loosen the bleeder screw on the inlet fuel Fuel Filter Replacement
fitting of the injection pump. Replace the fuel filter at intervals according to the
2. Turn On the electric fuel pump. The electric Maintenance Inspection Schedule.
fuel pump is energized when the ON key is 1. Remove the filter and discard.
pushed. Tighten the bleeder screw on the
injection pump when clear flow of fuel 2. Lubricate rubber ring of new filter with fuel.
appears. 3. Install the filter and tighten until the filter is
NOTE: At initial start-up, open the bleeder slightly loose (rubber ring not making
screw at the injection pump and bleed fuel contact).
until a clear flow is noted. 4. Bleed the air from the filter by operating the
3. Loosen the injector lines on the injection electric pump until fuel bubbles appear at the
nozzles. top of filter.
114
Engine Maintenance
Injection Pump
Injection Pump Adjustments
When the diesel engine fails to maintain the
correct engine speed, check the following before
adjusting the speed:
1. Filter
1. Check the prefilter screen. Recheck the speed.
2. Gasket
2. Bleed air out of the fuel system. Recheck the
3. Cover
speed.
4. Screw (3)
3. Bleed air out of the nozzles. Recheck the
5. Magnet
speed.
Figure 32: Electric Fuel Pump
4. Operation of electric transfer pump.
Maintenance Make the engine speed adjustments with the
Field service is limited to cleaning the bottom engine fully warmed up.
cover and filter. The filter and cover gasket are The unit has one solenoid to control the high
replaceable. speed function. The speed of the engine should be
checked with the use of a stroboscope tachometer
(see Tool Catalog).
115
Engine Maintenance
Timing the Injection Pump to the Engine repaired recently, it may be beneficial to check
individual cylinder timing. Because the possibility
There are two different types of timing procedures
of incorrect individual cylinder timing is so
used on the engine. One procedure involves
minimal, the procedure for timing the pump to the
checking to make sure the cylinders are timed
engine will be covered first. The procedure for
correctly to each other, and the second procedure
individual cylinder timing is very similar to
times the injection pump correctly to the engine.
timing the injection pump so it will be covered
If the cylinders are not timed correctly to each
last.
other, it is of no value to time the injection pump
to the engine because one or two of the three
cylinders would be out of time. The individual CAUTION: The cylinders on the engine
plungers in the injection pump are timed to each are numbered from the flywheel end to the
other by the use of spacers in the pump plunger water pump end. The number 1 cylinder is
base. It is rare that an injection pump would next to the flywheel. The number 2
change individual cylinder timing unless it had cylinder is the center cylinder. The
been through some type of repair process, but if number 3 cylinder is next to the water
all other possible problems with a rough running pump. The timing marks on the flywheel
engine have been checked, and especially if the are matched to this system.
engine’s injection pump has been replaced or
1. Rotate the engine in the direction of rotation that the number 1 cylinder top dead center
(clockwise as viewed from the water pump mark on the flywheel is aligned with the
end) until the number 1 cylinder (closest to timing mark on the starter mounting plate.
flywheel) is at approximately top dead center
of the compression stroke. The valve cover
should be removed to identify the
compression stroke. Both rocker arms of the
number 1 cylinder will be loose. Check to see
116
Engine Maintenance
NOTE: The timing marks for each of the 6. Turn the engine backwards past the injection
three cylinders are stamped 120 degrees timing mark until fuel flows from the drip
apart. Top dead center marks are identified tube.
by the number of the cylinder stamped next
7. Slowly rotate the engine in the direction of
to them. Injection timing marks are
rotation while watching the drip tube. When
unmarked. The timing marks on the engine
the fuel flow slows to approximately one drip
can be difficult to align. This is because the
every 10 to 15 seconds, check the timing
timing mark on the starter mounting plate is
marks. They should be lined up.
near the air cleaner, on the side of the plates
that faces the flywheel. It cannot be seen 8. If the timing marks did not line up, a shim or
when looking through the engine side door shims will have to be added or subtracted
opening unless you use a mirror. from the injection pump. Adding shims will
retard the injection timing, subtracting shims
The timing mark on the starter mounting
will advance the timing. Increasing or
plate is a line stamped on the side of the plate
decreasing shim thickness by 0.004 in.
facing the flywheel. To locate the timing
(0.1 mm) will change the timing by 1 degree.
mark, feel the back side of the plate 0.4 in.
(10 mm) below the center of round notch in 9. After shims have been added or subtracted,
the edge of the plate. To make it easier to recheck the timing.
align the timing marks, file a V-notch in the
10. When the injection pump has been correctly
edge of the plate in line with the timing mark
timed to the engine, remove the pump and put
on the plate.
a light coat of silicone gasket sealer on the
2. Remove the injection line from the number 1 shim pack and the pump, or dip the new shims
injector and the injection pump. Remove the in lacquer thinner to activate the sealer.
delivery valve holder, delivery valve and
11. Reinstall the pump, and torque the nuts to
spring. Care must be taken to prevent dirt
18 to 20 ft-lb (24 to 27 N•m).
from entering the fuel injection system.
Replace the delivery valve holder and delivery 12. Reinstall the delivery valve and spring.
valve. Torque the delivery valve holder to 30 ft-lb
(41 N•m).
3. Install a drip valve on the nozzle holder.
13. Reinstall the injector lines, bleed the air from
4. Activate the run solenoid and the fuel pump
the nozzles, and test run the engine.
by pushing the ON key. Make sure the
Diesel/Electric switch is in the Diesel
Timing Individual Cylinder Injection
position.
This procedure should be used when a poor
CAUTION: The 8S wire on the starter running engine has had all possible problems
motor should be disconnected. checked but continues to run badly. If the
injection pump has been repaired or replaced, the
chance of individual cylinder timing problems has
CAUTION: Loosen the injection lines on a greater possibility of occurring.
the injection nozzles of the number 2 and
3 cylinders to prevent any possibility of the To check individual cylinder timing, follow the
engine firing. pump timing procedure but instead of changing
shims to adjust pump timing, check the timing of
5. The engine should be close to the top dead number 2 and number 3 injector to the engine
center position with the plunger port in the after checking number 1. The cylinders should
pump closed. No fuel should flow from the time on their respective flywheel timing marks.
drip tube.
117
Engine Maintenance
If the injection pump plungers are not correctly Turn the engine by using the belt on the
timed to each other, the pump must be removed crankshaft pulley. Rotate the engine in the
and sent to a diesel injection equipment repair direction of rotation (clockwise as viewed
shop for calibration. next to the flywheel) from the water pump
end.
NOTE: The order of the flywheel timing marks
is 1, 2, 3, but the firing order is 1, 3, 2. This is
because the engine fires every 240 degrees of CAUTION: Make sure the fuel rack is off
crankshaft rotation. Therefore, when checking to prevent the engine from starting.
individual cylinder timing check number 1 first
a. Turn the engine so number 1 cylinder is on
then rotate the engine past number 2 to number
compression with piston to TDC. Both
3 and check number 3. Then rotate the engine
push rods should turn freely. Adjust both
past number 1 to number 2 and check number 2.
valves on number 1 cylinder.
b. Revolve the crankshaft 240 degrees to
TDC mark on number 3 cylinder, and
adjust both valves.
c. Turn the crankshaft 240 degrees to align
TDC mark of number 2 cylinder, and
adjust both valves.
d. Be sure to tighten locking nut while
holding the ball head screw in position.
3. Install the valve cover making sure that the
gasket is in position.
118
Engine Maintenance
119
Engine Maintenance
Figure 38: Wiring Diagram of Fuel Solenoid Timer Starting 4th Quarter 97
120
Engine Maintenance
Troubleshooting the Integral Fuel 5. Check the CH pin in the fuel solenoid wire
Solenoid System connector for continuity to a good chassis
ground.
NOTE: The fuel solenoid pull-in coil will
require 30 to 40 amps to turn on the fuel. The a. If there is no continuity between the CH
unit’s battery must be in good condition. If the pin in the fuel solenoid wire connector and
battery has enough power to crank the engine a good chassis ground, check the black
over, it has enough power to energize the fuel (CH) wire that goes from the fuel solenoid
solenoid pull-in coil. connector to the CH terminal on the
throttle solenoid for an open circuit.
If you suspect that the engine does not run
because the fuel solenoid is not operating b. If this black (CH) wire is not open, check
correctly, use the following procedure: the other CH wire connected to the CH
terminal on the throttle solenoid for an
1. Disconnect the 20 wire from the reset switch
open circuit.
so the reset switch will not trip.
c. If there is continuity between the CH pin
2. Disconnect the 8S wire from the starter
in the fuel solenoid connector and a good
solenoid.
chassis ground, go to step 6.
3. Disconnect the fuel solenoid wire connector
6. Place a jumper wire between the CH pin in the
from the fuel solenoid.
fuel solenoid and a good chassis ground.
4. Turn the unit ON and check the voltage on the
7. Test the pull-in coil by momentarily placing a
8D pin in the fuel solenoid wire connector
jumper between the 8DP pin in the fuel
from the main wire harness. Refer to the
solenoid and the 2 terminal at the control
following illustration to identify the pins in
circuit. The fuel solenoid should make a
the wire connector and in the fuel solenoid.
definite click when the pull-in coil is
energized and should click again when the
pull-in coil is de-energized.
NOTE: The pull-in coil will draw 18 to 25
amps so do not leave the jumper connected to
the 8DP pin for more than a few seconds.
a. If the pull-in coil does not energize, check
the resistance of the pull-in coil by placing
an ohmmeter between the 8DP pin and the
CH pin in the fuel solenoid. The resistance
of the pull-in coil should be -3 to -4 ohms.
If the resistance of the pull-in coil is not in
1. Pull Coil 8DP Color: White this range, replace the fuel solenoid.
2. 8D Hold Coil Color: Red
NOTE: If the pull-in coil fails, make sure to
3. Common—Ground Color: Black CH replace the fuel solenoid relay with a
Figure 39: Fuel Solenoid Pin Identification Potter-Brumfield relay P/N 44-9111.
b. If the pull-in coil does energize, go to step
a. If battery voltage is not present on the 8D
8.
circuit, check the 8D circuit for an open or
a short. 8. Test the hold-in coil.
b. If battery voltage is present on the 8D a. Energize the hold-in coil by placing a
circuit, go to step 5. jumper between the 8D pin in the fuel
solenoid and the 2 terminal at the control
circuit.
121
Engine Maintenance
b. Momentarily energize the pull-in coil by 12. Check the voltage on the 2B circuit at the 30
placing a jumper between the 8DP pin in terminal in the fuel solenoid relay socket.
the fuel solenoid and the 2 terminal at the
a. If battery voltage is not present on the 2B
control circuit. The fuel solenoid should
circuit, check the 2B circuit for an open or
make a definite click when the pull-in coil
a short.
is energized, but should not click when the
pull-in coil is de-energized. b. If battery voltage is present on the 2B
circuit, go to step 13.
c. De-energize the hold-in coil by removing
the jumper from the 8D terminal. The fuel
solenoid should make a definite click
when the hold-in coil is de-energized.
d. If the hold-in coil does not function
properly, check the resistance of the
hold-in coil by placing an ohmmeter
between the 8D pin and the CH pin in the
fuel solenoid. The resistance of the hold-in 1. 86 Terminal—8DC Circuit
coil should be approximately 24 ohms. If
2. 30 Terminal—2B Circuit
the resistance of the hold-in coil is not in
this range, replace the fuel solenoid. 3. 85 Terminal—8D Circuit
4. 87 Terminal—8DP Circuit
e. If the hold-in coil does function properly,
go to step 9. Figure 40: Relay Socket Terminal Identification
9. Reconnect the fuel solenoid wire connector to 13. Test the relay.
the fuel solenoid.
a. Use a jumper to connect the 85 terminal
10. Remove the fuel solenoid relay from its socket on the relay to the 2 terminal at the control
and make sure the unit is turned On. circuit.
11. Check the voltage on the 8D circuit at the 85 b. Use another jumper to connect the 85
terminal in the fuel solenoid relay socket. terminal on the relay to the 2 terminal at
Refer to the following illustration to identify the control circuit.
the terminals in the relay socket.
c. If the relay does not energize, it is
a. If battery voltage is not present on the 8D defective. Replace the relay.
circuit, check the 8D circuit for an open or
a short (minimum voltage is 10 volts). d. If the relay does energize, the timer is
defective. Replace the fuel solenoid timer
b. If battery voltage is present on the 8D PC board.
circuit, go to step 12.
14. Remember to reconnect the 20 wire to the
reset switch.
122
Engine Maintenance
Fuel Stop Solenoid Replacement NOTE: The fuel stop solenoid must be
energized when it is being installed. If it is
1. Disconnect the 20 wire from the reset switch
not, the plunger and the linkage may not line
to prevent the reset switch from tripping.
up correctly and the fuel solenoid will not
2. Disconnect the fuel stop solenoid wire function properly.
connector and remove the old fuel solenoid.
5. Place the o-ring in the groove in the end of the
3. Connect the fuel stop solenoid wire connector fuel injection pump. Make sure that the o-ring
to the new fuel solenoid. is positioned correctly during installation to
avoid damage and leaks.
4. Turn the unit on to energize the fuel stop
solenoid. 6. Install the new fuel stop solenoid.
7. Turn the unit Off and make sure to connect the
20 wire to the reset switch.
1. O-ring
2. Fuel Stop Solenoid
3. Fuel Injection Pump Groove
123
Engine Maintenance
AMA414
124
Engine Maintenance
125
Engine Maintenance
126
Engine Maintenance
127
Engine Maintenance
128
Refrigeration Maintenance
129
Refrigeration Maintenance
1 2
9 5
AGA654 6
130
Refrigeration Maintenance
1. 100 Microns
2. 500 Microns
3. 1000 Microns
4. 2500 Microns
5. 5000 Microns
6. 20,000 Microns
7. Atmospheric Pressure
8. Calibration Adjustment Screw
9. Example: Meter needle shown at calibration position
when Calibration Standard specifies 0.15 mm Hg.
131
Refrigeration Maintenance
Set Up and Test of Evacuation • Isolate the pump from the system by closing
Equipment the proper valve. Watch the movement of the
vacuum gauge needle. If the needle continues
NOTE: See the previous two pages for the
to rise, this is an indication that a leak exists in
following discussion.
the unit or the connecting line. The leak must
1. Connect the evacuation system to a 110 Vac then be located and eliminated.
power supply. Connect a gauge manifold and
refrigerant supply to the fitting above valve
V-4. Turn the micron gauge On.
2. Close valves V-1, V-3 and V-4. Valve V-2 is
open.
Pressure Rise
3. Turn the vacuum pump On. Levels Off
4. Open valve V-1 at the pump. The micron
e
gauge needle will move to the left. (See
is
R
re
micron gauge scale diagram—previous page). Moisture
su
es
Pr
NOTE: If the vacuum pump is okay, and
there are no leaks between V-1 and V-3, the
micron gauge should show less than 500
microns. If not, locate and correct the Time
problem. Figure 48: Moisture
5. With the pump still operating, open valve V-3. • Should the needle show a pressure rise but
If the micron reading does not return to a level finally level off to practically a constant mark,
of less than 500 microns, locate and correct this is an indication that the system is vacuum
the problem before continuing. tight but is still too wet, requiring additional
dehydration and pumping time.
6. With the vacuum pump still operating, open
valve V-4. The micron level will rise 7. Evacuate hoses to 100 microns or lowest
momentarily. If the micron reading does not achievable level below 500 microns.
return to a level of less than 500 microns, 8. Once 100 microns is reached, close valve V-1
locate and correct the problem before at the pump. Turn the vacuum pump Off.
continuing.
9. Observe the micron gauge reading. The
vacuum rise should not exceed 1500 microns
in 5 minutes.
10. If the rise is above 1500 microns in 5 minutes,
check all hoses and connections for leaks.
e
Pressure Rise
is
R
satisfactory results.
tP
an
Leak
st
Time
Figure 47: Leak
132
Refrigeration Maintenance
133
Refrigeration Maintenance
134
Refrigeration Maintenance
135
Refrigeration Maintenance
136
Refrigeration Maintenance
AEA05
137
Refrigeration Maintenance
4. Failure of the HPCO system to stop 4. Front seat discharge service valve, and
compressor operation should be investigated equalize the compressor to slightly positive.
first by checking the control circuit operation Disassemble and inspect the discharge valve
and secondly by HPCO switch replacement. plates.
3. Close (front seat) the suction service valve. CAUTION: Do not run scroll compressor
Pump the compressor down into a deep in a vacuum for more than a few seconds.
vacuum (25 in.). Stop the unit. If the suction
5. Turn the unit Off.
pressure does not rise above 10 psig (69 kPa)
in 2 minutes, perform check procedures on the 6. Prepare to perform service on the low side by
three-way valve and the bypass check valve. If equalizing the high side and low side
the pressure does not rise, go to step 4. pressures through the gauge manifold.
138
Refrigeration Maintenance
7. Equalize low side pressure to 1 to 2 psig (7 to 5. Operate the unit on Cool, and pump down the
14 kPa). low side to 0 in. (0 kPa) of vacuum.
NOTE: Repeat the pump down procedure if 6. Stop the unit. The condenser and suction
the pressures equalize above 20 psig pressures should remain stable, indicating no
(138 kPa). If acceptable low pressures leaks.
cannot be achieved after the third pump
7. Shift the three-way valve to heat position
down, the refrigerant must be recovered to
using relay board test. Low side gauge will
perform service on the low side.
raise slightly. High side gauge will drop to
NOTE: Valve stem MUST be back seated approximately 30 to 50 psig (207 to 345 kPa).
during normal unit operation. Gauges will equalize.
8. Plug in the hot gas bypass solenoid.
9. Open the receiver tank return outlet valve,
remove the gauges and return the unit to
normal operation.
139
Refrigeration Maintenance
140
Refrigeration Service Operations
NOTE: It is generally good practice to replace Compressor
the filter-drier whenever the high side is opened
or when the low side is opened for an extended Removal
period of time.
1. Pump down the compressor and equalize the
pressure to slightly positive (1 to 2 psig
Commissioning Unit [7 to 14 kPa]).
The following procedure should be followed after 2. Loosen and remove the belts from the
any of these conditions: compressor pulley.
• The compressor has been replaced 3. Front seat the discharge and suction service
• There has been a large oil loss in the system valves. Recover the remaining refrigerant
from the compressor.
• There has been a complete clean up or flush of
the refrigeration system. 4. Unbolt the discharge valve and suction valves
from the compressor.
1. Set the thermostat to the highest setpoint.
5. Disconnect the high pressure cutout switch
If the ambient temperature is above set point wires.
range, jump power from the 2 circuit to HGS
and RHGS to allow the valves to open. 6. Remove the compressor mounting bolts.
2. Run the unit for ten minutes to allow for 7. Lift the compressor out of the unit. Keep the
wetting of the system. compressor ports covered to prevent dust, dirt,
etc., from falling into the compressor.
3. Set the thermostat for Cool (remove jumpers if
installed in the previous step). NOTE: When the compressor is removed
from the unit, the oil level should be noted,
or the oil removed from the compressor
Accumulator should be measured so that the same amount
of oil can be added before placing the
Removal replacement compressor in the unit.
1. Remove refrigerant using approved methods.
2. Unsolder the inlet and outlet refrigerant Installation
suction lines from the accumulator tank. 1. Lift the compressor into the unit and install
3. Unbolt and remove the accumulator from the the mounting bolts.
unit. 2. Install the service valves using new gaskets
soaked in refrigeration oil. Connect the high
Installation pressure cutout switch wires.
1. Place the accumulator in the unit and tighten 3. Reconnect the pilot valve and compound
the mounting bolts. pressure gauge hoses.
2. Solder the inlet and outlet suction lines to the 4. Pressurize the compressor and test for
accumulator tank. refrigerant leaks.
3. Pressurize the low side and test for refrigerant 5. If no leaks are found, evacuate the
leaks. If no leaks are found, evacuate unit. compressor. Replace the compressor/electric
motor belt and adjust the tension.
4. Charge the system with refrigerant. Check
refrigerant charge and compressor oil and add 6. Back seat the suction and discharge service
as required. valves.
141
Refrigeration Service Operations
7. Operate the unit at least 30 minutes and then Liquid Line Check Valve
inspect the oil level in the compressor. Add or
remove oil if necessary. Removal
8. Check the refrigerant charge and add 1. Remove the refrigerant charge.
refrigerant if needed.
2. Unsolder the lines and remove the check
valve.
Condenser/Radiator Coil
NOTE: Disassemble valve before unsoldering.
Removal
Installation
1. Remove the refrigerant charge by approved
methods. 1. Clean the tubes for soldering.
2. Remove the grille assembly. 2. Place the disassembled check valve in
position. Arrow on the valve body indicates
3. Drain engine coolant from the expansion tank the direction of refrigerant flow through the
and disconnect the coolant hoses from the valve.
condenser/radiator coil.
3. Solder the inlet and outlet connections. After
4. Unsolder the hot gas inlet tube and liquid the valve cools, reassemble the valve.
refrigerant line connections.
4. Pressurize the refrigeration system and test for
5. Unbolt and remove the condenser/radiator leaks.
cap.
5. If no leaks are found, evacuate the system.
Installation 6. Recharge the unit with refrigerant and check
1. Clean the tubes for soldering. the compressor oil.
2. Place the coil in the unit and install the
mounting hardware. Dehydrator (Filter-Drier)
3. Solder the inlet line and liquid line refrigerant Removal
connections.
1. Pump down the refrigeration system and
4. Pressurize the refrigeration system and test for equalize the pressure to slightly positive.
leaks. If no leaks are found, evacuate the
system. 2. Disconnect the nuts at the end of the drier.
5. Connect the coolant hoses to the radiator and 3. Loosen the mounting hardware and remove
refill the expansion tank with 50/50 ethylene the drier.
glycol/water solution.
Installation
6. Recharge the unit with refrigerant and check
the compressor oil. 1. Install the new drier and tighten the mounting
screws and nuts. Install new o-rings.
7. Reinstall the front grille.
2. Install and tighten the inlet nut to the receiver
tank outlet valve line (inlet end of drier is
labeled “IN”). Hold the drier with a back-up
wrench on the hex behind the flare fitting.
3. Release a small amount of refrigerant to purge
the air through the drier. Then tighten outlet
nut on the dehydrator to the evaporator line.
142
Refrigeration Service Operations
4. Pressurize the system and inspect for leaks. If 2. Remove the feeler bulb from the suction line
no leaks are found, open the refrigeration clamp. Note the position of the feeler bulb on
valves and place the unit in operation. the suction line.
3. Unsolder the equalizer line from the
Evaporator Coil expansion valve.
5. Disconnect the electric heaters and high 2. Solder (95-5 Solder) the inlet liquid line and
temperature cutout switch on Model 50 units. the distributor to the expansion valve.
6. Remove the mounting bolts and slide the coil 3. Solder (95-5 Solder) the equalizer line to the
from the evaporator housing. expansion valve.
4. Clean the suction line to a bright polished
Installation condition. Install the feeler bulb clamps and
1. Place the evaporator coil in the housing. the feeler bulb on the side of the suction line
in its former position. The feeler bulb must
2. Install the mounting bolts and tighten. make good contact with the suction line or the
3. Clean the tubes for soldering. operation will be faulty. Wrap with insulating
tape.
4. Solder the suction line and drain pan hot gas
line connections to the evaporator coil. 5. Pressurize the low side and test for leaks. If no
leaks are found, evacuate the low side.
5. Connect the distributor to the expansion valve
assembly.
6. Connect the air switch hoses and install the
high temperature cutout switch and electric
heaters (Model 50).
7. Pressurize the low side and test for leaks. If no
leaks are found, evacuate the unit.
1. Suction Line
8. Open the refrigeration valves and place the 2. Capillary Bulb
unit in operation. Install the refrigerant charge
and compressor oil and add as required. 3. End View
143
Refrigeration Service Operations
144
Refrigeration Service Operations
Installation Installation
1. Apply a refrigerant LoctiteTM to the threads of 1. Clean the tubes for soldering.
the high pressure relief valve.
2. Place the valve in position and solder
2. Install and tighten the high pressure relief connections.
valve.
3. Pressurize the low side and check for leaks.
3. Pressurize the refrigeration system and test for
leaks. If no leaks are found, evacuate the 4. If no leaks are found, evacuate the low side.
system. 5. Open the refrigeration valves, and place the
4. Recharge the unit with refrigerant and check unit in operation. Check the refrigerant charge
the compressor oil. and add refrigerant as required.
145
Refrigeration Service Operations
Receiver Tank
Removal
1. Remove the refrigerant charge.
2. Unsolder the inlet tube from the receiver tank.
3. Unsolder the filter drier line from the receiver
tank outlet tube.
4. Unbolt the mounting brackets and remove the
receiver tank from the unit. 1. Teflon Check Valve 4. Cap
2. O-ring 5. Stem
Installation 3. Snap Ring 6. Spring
1. Place the receiver tank in the unit and install Figure 58: Condenser Pressure Bypass Check
the mounting bolts and nuts loosely. Position Valve
the receiver tank so the sight glass is clearly
visible and the outlet tube lines up. 5. Remove the spring and Teflon valve.
2. Solder the condenser inlet tube. 6. Inspect the check valve seat in the three-way
valve.
3. Solder the filter drier line to the receiver tank
outlet valve. 7. If replacement parts are needed, a kit must be
used which includes the Teflon valve, spring,
4. Tighten the receiver tank mounting hardware o-ring, valve stem and snap ring.
securely.
5. Pressurize the refrigeration system and check Installation
for leaks. If no leaks are found, evacuate the 1. Coat the o-ring with compressor oil (use same
system. type of oil that is used in the system) and
6. Recharge the unit with refrigerant. install it on the check valve stem.
2. Insert the spring into the hole in the check
Three-Way Valve Condenser valve stem and then install the Teflon check
Pressure Bypass Check Valve valve on the other end of the spring with the
Repair hole in the valve towards the spring.
3. Coat the entire assembly with compressor oil
Removal and install the assembly into the check valve
1. Remove the refrigerant charge. seat in the three-way valve.
2. Unscrew the condenser pressure bypass check CAUTION: The Teflon valve must be
valve cap from the check valve. inserted with the flat side against the valve
3. Remove the snap ring. seat to ensure proper sealing.
4. Unscrew the check valve stem by using a 4. Screw the check valve stem into the three-way
screwdriver in the slot provided. valve until the snap ring can be installed.
NOTE: Spring and valve are held in by the 5. Install the snap ring.
stem. While removing the stem, use care so 6. Unscrew (back seat) the check valve stem
the spring and valve are not lost. against the snap ring.
NOTE: Valve stem must be back seated
during normal unit operation.
146
Refrigeration Service Operations
7. Coat sealing area in cap with compressor oil 9. Remove the piston.
(use same type of oil that is used in the
10. Remove the center section and stem assembly.
system), install and tighten the cap on the
three-way valve. 11. Inspect the following parts for wear and
damage:
8. Pressurize the refrigeration system and test for
leaks. If no leaks are found, evacuate the a. Bottom cap sealing and support areas
system.
b. Center section, sealing surface
9. Recharge the unit.
c. Top cap, sealing and support surface
147
Refrigeration Service Operations
Installation
NOTE: Three-way valve kit is used to repair
three-way valves (see Tool Catalog).
After cleaning and inspecting all parts, reassemble
the valve. Clean solder off the condenser line and
condenser head with sandpaper and tubing brush.
1. Install the screen into the bottom cap.
2. Install new stem into the center section.
3. Install new gaskets on both sides of the valve
body. Dip gaskets in compressor oil (use same
type of oil that is used in the system) before
installing.
4. Install a new o-ring on the piston, then place
the Teflon seal over the o-ring.
5. Install the piston on the stem and attach with
spring clip.
NOTE: The Teflon seal will stretch when it is
installed. To prevent this from becoming
permanent (and possibly malfunction), the
top cap must be installed immediately.
6. Install the spring and top cap.
7. Line up the passageways in the cap and body.
Failure to line up the holes will result in
improper operation of the valve.
8. Install bolts and tighten in rotating sequence.
9. Solder condenser line to the condenser inlet.
10. Install pilot solenoid line and pressurize
system with refrigerant to check for leaks.
11. If there are no leaks, evacuate the system and
recharge with refrigerant.
12. Run the unit to check for proper three-way
valve operation.
1. Screw 8. O-ring
2. Top Cap 9. Gasket
3. Cap 10. Clip
4. Check Valve Assembly 11. Seat
5. Spring 12. Stem Assembly
6. Piston 13. Screen
7. Teflon Seal 14. Bottom Cap
148
Refrigeration Service Operations
Compressor Pulley Removal from the tapered portion of both the pulley and
and Installation hub, and the mounting screws should be torqued
to 7 to 10 ft-lb (23 to 14 N•m). Whenever the
Units with the X214 compressor will have an two-piece pulley is removed from any type of unit
anti-seize lubricant on the tapered surfaces of the service, anti-seize lubricant should be applied to
two-piece compressor pulley. The anti-seize the outside of the tapered surface on the pulley
lubricant facilitates the installation and removal of bushing. Use one of the following recommended
the two-piece pulley. To ensure correct pulley anti-seize lubricants: Fel-Pro C5-A, Loctite 767,
alignment, all rust and/or paint should be removed Never-Seez NS-12, or Never-Seez NS-160.
149
Refrigeration Service Operations
150
Refrigeration Service Operations
151
Refrigeration Service Operations
152
Hilliard Clutch Maintenance
153
Hilliard Clutch Maintenance
1 13
2 14
3 7
4 8
15
6 16
15
8
5 7
14
7
8
9 17
8
7
10 aea558
11
(3 belt grooves)
12
154
Hilliard Clutch Maintenance
Tools Required
• Internal Retaining Ring Pliers
• 7/16 in. Wrench
• 7/32 in. Allen Wrench or 7/32 x 1/2 in. Socket
Drive
• 1/2 in. Impact Tool Figure 64: Housing Removal
• Rubber or Plastic Hammer 4. Remove the nuts from six 1/4-28 link screws
and remove screws, links, and lockwashers.
• 7/16 in. Socket or Nut Driver
5. Remove the springs and shoes.
• Arbor Press with Various Sized Arbors
6. Pull oil seal and press bearings out of hub.
• Bearing Puller
• Ratchet (Optional)
• Torque Wrench
Grease
MobilTM (Synthetic) (see Tool Catalog).
Disassembly Procedure
1. Remove retaining ring.
2. Remove the 3/8-16 flat head cap screw and
washer.
Figure 65: Bearing Removal
NOTE: This screw was installed using
LoctiteTM (see Tool Catalog) and will require NOTE: Press tool should be slightly smaller
the use of an impact tool for removal. than hub bore.
NOTE: A small amount of heat (propane or NOTE: Make sure the center of the hub is
acetylene torch with small heating tip) supported and not the outer rim of the hub,
applied to the cap screw head may be when pressing bearing out.
required to help loosen the screw.
155
Hilliard Clutch Maintenance
156
Hilliard Clutch Maintenance
157
Hilliard Clutch Maintenance
158
Structural Maintenance
Defrost Damper
Check the damper during scheduled maintenance
inspections for shaft wear, end play and sealing
AMA451
against air flow.
Position the damper so that the air flow is stopped
1. Check Mounting Bolts for Tightness
top and bottom with the solenoid plunger
bottomed.
Figure 69: Check Bolts For Tightness
1. If the damper does not close completely:
Lift Points a. Energize damper solenoid by placing a
jumper wire from 12 Vdc to No. 29 wire in
The unit lifting points are noted below. Note that
the evaporator harness.
three lift points must be used.
b. If damper blade closes, proceed to step 2.
If not, proceed to step 1.c.
c. Remove the jumper wire, loosen the
evaporator outlet adjustment angle and
move so when energized, the damper will
close.
d. Retighten the adjustment angle and repeat
Figure 70: Lift Points steps a. and b.
2. If the damper blade does not seal evenly along
Unit Inspection full width of blade:
Inspect the unit during unit pretrip inspection and a. Loosen the damper bearing blocks.
scheduled maintenance inspections for loose or
broken wires or hardware, compressor oil leaks, b. Manually close the damper so the blade
or other physical damage which might affect unit makes contact at the top and bottom of the
performance and require repair or replacement of funnel, the full width of the blade.
parts. c. Retighten damper bearing blocks.
159
Structural Maintenance
1 2 AEA924
160
Structural Maintenance
1. End Cap
2. Oil Sling Retainer
3. Tie Band
4. Air Vent (P/N 55-6417)
5. Shaft
Figure 73: Installing Oil Sling Retainer
161
Structural Maintenance
Fanshaft Assembly
The unit is equipped with a one-piece fanshaft
assembly that contains tapered roller bearings in a
sealed oil reservoir. This assembly does not
require any maintenance. There is a level plug and
a fill plug, but they are not normally utilized
except after removal and repair of the fanshaft
assembly. The condenser end oil seal and the
evaporator end oil seal should be checked during
the pre-trip inspection for oil leakage. If there is
any sign of leakage, the fanshaft assembly should
be removed and repaired.
NOTE: The fanshaft assembly requires a special Figure 75: Removing Shaft
lubricant, TK P/N 203-278.
4. Using a punch, remove the oil seal from the
Disassembly evaporator end of the assembly. With the seal
removed, clean the housing in solvent.
1. Remove the fanshaft assembly from the unit.
Remove both oil plugs and drain the oil from
the housing.
162
Structural Maintenance
Reassembly
1. Install the new bearings on the shaft with a
pipe in the same way they were removed.
163
Structural Maintenance
5. Install the retainer cap assembly over the NOTE: Use ONLY Thermo King special
shaft, and then install the bolts. fanshaft grease (P/N 203-278) in this assembly.
6. Torque the bolts in a criss-cross pattern in Lock the assembly in a vise with the vent
equal steps to 80 in-lbs (9.04 N•m). facing up. Pour grease through the top plug
until it runs out of the side hole. The assembly
holds 2.2 oz (65 ml). Check the condition of
the o-ring used on the plugs and replace if
necessary. Install top and side plugs. Clean up
any spillage.
9. Place the assembly on the workbench with the
vent up. Rotate the shaft by hand. The shaft
should be free enough to rotate without having
to hold the housing.
164
Mechanical Diagnosis
Condition Possible Cause Remedy
Unit switch On—nothing happens Dead battery Recharge or replace battery
Remote switch Off (optional) Turn On
Fuse open Replace
Corroded battery connections Clean and tighten
Main harness fuse blown Check for shorted main harness and
replace fuse
Unit switch On—indicator lights Battery low Replace or recharge battery
come On but engine does not
Fuse blown Replace
crank
Starter solenoid defective Repair or replace
Starter relay defective Replace relay
Corroded battery connections Clean and tighten
Starter clutch defective Replace
Starter defective Repair or replace
Engine cranks but fails to start Misadjusted fuel solenoid linkage Adjust
Fuel solenoid defective Replace solenoid
No fuel or wrong fuel in tank Fill fuel tank. After filling a
completely empty tank, first bleed
fuel system.
Engine too cold Use winter preheat procedure
Glow plugs defective Replace glow plugs
Air in fuel system Bleed fuel system. During this
operation, it can also be determined
if the fuel lines are tight and filters
clean.
Speed/run relay malfunction Check relay or unit thermostat
Insufficient compression Measure compression pressure. If
necessary, grind valves or replace
piston
Electric fuel pump not operating Check pump for running and 8 to
10 psig (55 to 69 kPa). Repair or
replace fuel pump
Injection pump incorrectly timed Adjust timing
Faulty injection nozzle(s) Repair injection nozzle or replace it
Faulty injection pump Have pump repaired
165
Mechanical Diagnosis
166
Mechanical Diagnosis
167
Mechanical Diagnosis
168
CYCLE-SENTRY Diagnosis
169
CYCLE-SENTRY Diagnosis
170
Electric Standby (Optional) Diagnosis
171
Electric Standby (Optional) Diagnosis
172
Refrigeration Diagnosis
Rapid cycling between Cool and Heat
Unit cools in Heat and Defrost cycle
Symptom
High suction pressure
Low suction pressure
Noisy compressor
No head pressure
Possible Causes
• • • • Overcharge of refrigerant
• • • • • • Shortage of refrigerant
• • • • • No refrigerant
• Air through condenser too hot (ambient)
• Air flow through condenser restricted
• • • Air through condenser too cold (ambient)
• • • Air in refrigerant system
• Condenser fan blades bent or broken
• Air short cycling around evaporator coil
• Air through evaporator restricted
• • • • Evaporator needs defrosting
• Compressor discharge valves leaking
• • Compressor seals leaking
• Too much compressor oil in system
• Faulty oil pump in compressor
• Loose compressor pulley
• Compressor bearing loose or burned out
• • • • • Broken discharge check valve in compressor
• • Expansion valve power element lost its charge
173
Refrigeration Diagnosis
Symptom
High suction pressure
Low suction pressure
Noisy compressor
No head pressure
Possible Causes
174
Refrigeration Diagrams
175
Refrigeration Diagrams
176
Refrigeration Diagrams
177
Refrigeration Diagrams
178
Index
A electrical components, specifications 19
accumulator 141 electrical contacts 87
after start inspection 41 electrical control system, specifications 19
air switch, specifications 19 electrical maintenance 85
alternator 85 engine air cleaner 108
antifreeze dry type 108
maintenance procedures 111 oil bath type 108
auto start diesel operation 38 engine coolant high temperature cutout 37
engine cooling system 110
B engine fuel system 112
battery 87 engine low oil pressure cutout 37
belt engine lubrication system 107
alternator/evaporator fan 126 engine maintenance 107
compressor/electric motor/jackshaft 125 engine oil change 107
compressor/evaporator/alternator 126 engine oil dipstick 36
engine/compressor 125 engine oil pressure switch 107
water pump 125 engine operation 24
belt tension, specifications 19 engine reset switch 36, 89
belt tensions 124 engine speed adjustments 127
engine thermostat 112
C engine valve clearance 118
engine, specifications 17
charging system 87
evacuation 129
clutch maintenance 153
evaporator coil 143, 159
commissioning unit 141
evaporator high temperature protection switch 37
compressor 23, 141
expansion valve 143
compressor oil 136
compressor oil sight glass 36
compressor pulley 149 F
compressor pump down 138 fanshaft 162
condenser coil 142, 159 filter-drier 142
condenser pressure bypass check valve 139, 146 fuel filter replacement 114
continuous run operation 39 fuel limit screw 118
control circuit fuse 37 fuel solenoid 119
control system circuit breaker 37 fuel stop solenoid, replacement 123
coolant tank 36 fuel system bleeding 114
crankcase breather 108 fuel tank, draining water 114
CYCLE-SENTRY diagnosis 169
CYCLE-SENTRY diesel operation 38 G
CYCLE-SENTRY operation 24, 39 general description 23
glow plugs 88
D
defrost air switch 35, 89 H
defrost damper 159 heat exchanger 144
defrost operation 25 high pressure cutout (HPCO) 137
defrost termination switch 35 high pressure cutout switch 145
dehydrator 142 high pressure relief valve 145
diagnosis, CYCLE-SENTRY 169 hourmeters 36
diagnosis, electric standby 171
diagnosis, mechanical 165 I
diagnosis, refrigeration 173 injection pump 115
digital thermometer 36 integral fuel solenoid
electrical changes 120
E troubleshooting 121
electric fuel pump 115
electric motor reset switch 36 J
electric operation 24, 40 jackshaft 160
electric standby diagnosis 171
electric standby, specifications 20
179
Index
L low voltage 16
lift points 159 microprocessor service 14
liquid line check valve 142 refrigerant 13
loading procedure 41 refrigeration oil 14
low oil pressure switch (LOP) 89 welding 15
low side pump down 138 schematic diagrams 183
serial number locations 25
M specifications 17
maintenance inspection schedule 21 air switch 19
MD-II MAX Model 30 23 belt tension 19
MD-II MAX Model 50 23 electric standby 20
mechanical diagnosis 165 electrical components 19
modes 24 electrical control system 19
mounting bolts 159 engine 17
R-134a refrigeration system 18
O R-404A refrigeration system 18
standby power requirements 20
oil change, engine 107
thermostat 20
oil filter 150
standby power requirements, specifications 20
oil filter change 107
structural maintenance 159
oil, compressor 136
operating modes 24
overload relay 36 T
TG-V 43
P alarm codes 53
connector pins 105
phase converter 91
control keys 47
pilot solenoid 145
display information 48
post load procedure 41
display symbols 45
post trip checks 41
displaying operating data 50
preheat buzzer 37, 87
electrical 103
pressure regulator valve 145
entering setpoint 52
pretrip inspection 37
Features 23
field test 103
R guarded access mode 56
R-134a 151 overview 34
R-134a refrigeration system, specifications 18 sensor test 83
R-404A 3, 151 single temp in-cab controller 44
R-404A refrigeration system, specifications 18 standard display 48
radiator coil 142 terminal identification 80
receiver tank 146 terminal voltage chart 79
receiver tank sight glass 36 testing 74
recover refrigerant 3 TherMax 90
refrigerant charge 136 thermostat, specifications 20
refrigerant high pressure cutout 37 three-phase electric motor 91
refrigerant high pressure relief valve 37 three-way valve 139, 146, 147
refrigerant leaks 133
refrigeration diagnosis 173
refrigeration maintenance 129
U
refrigeration service operations 141 unit
remote control box description 23
overview 35 features 25
remote light indicator box 36 options 25
RPM sensor 87 photographs 27
protection devices 26
unit charging 133
S unit control box
safety precautions 13 overview 33
auto start/stop 13 unit evacuation 133
electrical hazards 14 unit indicators 36
general practices 13 unit inspection 159
high voltage 15
180
Index
unit operation 37
unit protection devices 36
V
voltage, excessive 86
W
wiring 87
wiring diagrams 183
181
Index
182
Wiring and Schematic Diagrams Index
183
Wiring and Schematic Diagrams Index
184
Cab Control MD Wiring Diagram
185
MD w/o Thermostat Cab Control Schematic
186
MD Cab Box Wiring Diagram
187
MD Cab Control w/Thermostat Schematic Diagram
188
MD-II 50 STD 1-Phase Wiring Diagram—Page 1 of 2
189
MD-II 50 STD 1-Phase Wiring Diagram—Page 2 of 2
190
MD-II 50 C/S 1-Phase Wiring Diagram—Page 1 of 2
191
MD-II 50 C/S 1-Phase Wiring Diagram—Page 2 of 2
192
MD 50 STD 3-Phase Wiring Diagram—Page 1 of 2
193
MD 50 STD 3-Phase Wiring Diagram—Page 2 of 2
194
MD 50 STD 3-Phase Schematic Diagram—Page 1 of 2
195
MD 50 STD 3-Phase Schematic Diagram—Page 2 of 2
196
MD 30 STD Wiring Diagram—Page 1 of 2
197
MD 30 STD Wiring Diagram—Page 2 of 2
198
MD 30 STD Schematic Diagram—Page 1 of 2
199
MD 30 STD Schematic Diagram—Page 2 of 2
200
MD 30 C/S Wiring Diagram—Page 1 of 2
201
MD 30 C/S Wiring Diagram—Page 2 of 2
202
MD w/CYCLE-SENTRY Schematic Diagram—Page 1 of 2
203
MD w/CYCLE-SENTRY Schematic Diagram—Page 2 of 2
204
MD 50 C/S 3-Phase Wiring Diagram—Page 1 of 2
205
MD 50 C/S 3-Phase Wiring Diagram—Page 2 of 2
206
MD w/CYCLE-SENTRY Schematic Diagram—Page 1 of 2
207
MD w/CYCLE-SENTRY Schematic Diagram—Page 2 of 2
208