Catalog

HA 35.11 ·
2023

MEDIUM-VOLTAGE SWITCHGEAR

Types 8DA10 and 8DB10 up to 40.5 kV


and 8DAB 24 blue GIS up to 24 kV,
­Gas-Insulated
siemens.com/medium-voltage-switchgear
Application
Typical uses
R-HG11-0805 tif

Typical uses
­(examples):

Public power supply


system

Industry

R-HA35-132c tif
R-HA3511-015 jpg
R-HA3511-016 jpg

Typical uses
­(examples):

Offshore

Traction power
supply
R-HA3511-017 jpg

2 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
ContentsPage

MEDIUM-VOLTAGE SWITCHGEAR Application

Types 8DA10
Versions 4

Requirements
and 8DB10 Features, Safety
Technology
6
7
up to 40.5 kV Digitalization, condition monitoring

and 8DAB 24 blue GIS Siemens Xcelerator, available monitoring functionalities


Digitalization solutions from a single source
8
9

up to 24 kV, Sustainability 10

Gas-Insulated Room planning


Single-busbar switchgear and double busbar switchgear  12
Transport and packing 14
Catalog HA 35.11 · 2023 Classification 15
Invalid: Catalog HA 35.11 · 2021 Product range
siemens.com/medium-voltage-switchgear Single-busbar switchgear 8DA10 and 8DAB 24 SBB 16
Double-busbar switchgear 8DB10 and 8DAB 24 DBB 17

Dimensions
Typicals, single-busbar switchgear (examples) 19
Typicals, double-busbar switchgear (examples) 20
Typicals, traction power supply switchgear (examples) 23

Design
Panel design, single-busbar switchgear (example) 24
Panel design, double-busbar switchgear (example) 25

Components
Vacuum circuit-breaker 26
Three-position disconnector 28
Current transformers 30
Voltage transformers 31
Panel connection 32
Panel connection (commercially available cable plugs
and bar connections) 34

Standards
Standards, specifications, guidelines 36

The products and systems described in this catalog


are manufactured and sold according to a certified
management system (acc. to ISO 9001, ISO 14001
and BS OHSAS 18001).

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 3
Application
Versions

8DA10 and 8DB10 – SF₆ version

Example: Version with mechanical gas pressure manometers for feeders and busbar

R-HA3511-024 png
R-HA3511-023 tif

Single busbar type 8DA10 and double busbar type 8DB10

8DAB 24 blue GIS – Clean Air version

Example: Version with digital gas pressure monitoring for feeders and busbar
R-HA3511-026 tif
8DAB24-SBB-LS-open tif
R-HA3511-025 tif

Single busbar type 8DAB 24 SBB and double busbar type 8DAB 24 DBB

4 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Application
Versions

Medium-voltage switchgear 8DA/B Electrical data (maximum values) according to IEC


is indoor, factory-assembled, Single-busbar and double-busbar switchgear

­type-tested, single-pole Rated voltage


­metal-enclosed, gas-insulated – SF6kV 12 24 36 40.5
switchgear, for single-busbar and – Clean AirkV 12 24
double-busbar applications, as well Rated frequency Hz 50 / 60 50 / 60 50 / 60 50 / 60
Rated short-duration power-frequency
as for traction power supply systems.
withstand voltage kV 28 1) 50 1) 70 1) 85 1)
Rated lightning impulse
It is used in transformer and
withstand voltage kV 75 125 170 185 1)
switching substations, e.g., in:
Rated peak withstand current up to kA 100 / 104 100 / 104 100 / 104 100 / 104
• Power supply companies Rated short-circuit making current up to kA 100 / 104 100 / 104 100 / 104 100 / 104
Rated short-time withstand current 3 s up to kA 40 40 40 40
• Power stations
Rated short-circuit breaking current up to kA 40 40 40 40
• Cement industry Rated continuous current of the busbar
• Automobile industry – SF6 up to A 5000 5000 5000 5000
– Clean Air up to A 2500 1) 2500 1)
• Iron and steel works Rated continuous current of feeders
• Rolling mills – SF6 up to A 3150 2) 3150 2) 3150 2) 3150 2)
• Mining industry – Clean Air up to A 2500 1) 2500 1)
• Textile, paper and food industries
Electrical data (maximum values) according to ANSI
• Chemical industry
Single-busbar and double-busbar switchgear
• Petroleum industry
Rated voltage
• Pipeline installations – SF6 kV 4.76 8.25 15 27 38
• Offshore installations – Clean Air kV 4.76 8.25 15 27
• Electrochemical plants Rated frequency Hz 60 60 60 60 60
Rated short-duration power-frequency
• Petrochemical plants
withstand voltage kV 19 36 36 50 70
• Shipbuilding industry Rated lightning impulse
• Diesel power plants withstand voltage kV 60 95 95 125 150
Rated peak withstand current up to kA 104 104 104 104 104
• Emergency power supply
­installations Rated short-circuit making current up to kA 104 104 104 104 104
Rated short-time withstand current 3 s up to kA 40 40 40 40 40
• Lignite open-cast mines
Rated short-circuit breaking current up to kA 40 40 40 40 40
• Traction power supply systems. Rated continuous current of the busbar
– SF6 up to A 5000 5000 5000 5000 5000
– Clean Air up to A 2500 1) 2500 1) 2500 1) 2500 1)
Rated continuous current of feeders
– SF6 up to A 3000 2) 3000 2) 3000 2) 3000 2) 3000 2)
– Clean Air up to A 2500 1) 2500 1) 2500 1) 2500 1)

Electrical data (maximum values)


Single-pole and double-pole traction power supply switchgear
Rated voltage kV 17.25 27.5
Rated frequency Hz 16.7 50 / 60
Rated short-duration power-frequency
withstand voltage kV 50 95
Rated lightning impulse
withstand voltage kV 125 200
Rated peak withstand current up to kA 80 80
Rated short-circuit making current up to kA 80 80
Rated short-time withstand current 3 s up to kA 31.5 31.5
Rated short-circuit breaking current up to kA 31.5 31.5
Rated continuous current of the busbar up to A 3150 3150
Rated continuous current of feeders up to A 2500 2500

1) Higher values on request


2) With forced ventilation

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 5
Requirements
Features Safety

Protection against environmental influences Personal safety


The single-pole enclosed high-voltage part of the switchgear • Safe-to-touch and hermetically sealed primary enclosure
is suitable for applications under aggressive ambient condi- • All high-voltage parts including the cable terminations,
tions, such as: busbars and voltage transformers are metal-enclosed
• Saline air • Capacitive voltage detecting system to verify safe
• Air humidity isolation from supply
• Dust • Operation is only possible with closed switchgear enclosure
• Condensation. • Standard degree of protection IP65 for all high-voltage
parts of the primary circuit, IP3XD for the switchgear enclo-
It is tight to ingress of foreign objects, such as sure according to IEC 60529
• Dust • High resistance to internal arcs by single-pole enclosure
• Pollution of the primary circuit
• Small animals. • Panels tested for resistance to internal faults up to 40 kA
• Logical mechanical interlocks prevent maloperation
The application is independent of the site altitude. • Make-proof earthing by means of the vacuum circuit-
breaker.
Compact design
Thanks to the use of gas insulation, compact dimensions Security of operation
are possible. • Hermetically sealed primary enclosure protects against
Thus: environmental effects (pollution, humidity and small
• Existing switchgear rooms can be used effectively animals)
• New constructions cost little • Maintenance-free in an indoor environment according
• Costly city-area space is saved. to IEC 62271‑1
• Two-phase and three-phase short-circuits between the
Maintenance-free design primary conductors are excluded by the single-pole
Switchgear housings designed as sealed pressure systems, primary enclosure
maintenance-free switching devices and enclosed cable plugs • In isolated or compensated systems, low-current
ensure: earth-fault currents are self-extinguishing
• M
 aximum supply reliability • Operating mechanisms of switching devices accessible
• Personnel safety outside the primary enclosure (switchgear housings)
• Sealed-for-life design according to IEC 62271‑200 • Metal-enclosed, plug-in inductive voltage transformers
(sealed pressure system) mounted outside the primary enclosure
• Reduced operating costs • Ring-core current transformers, mounted outside the
• Cost-efficient investment. primary enclosure, not subjected to dielectric stress
• Complete switchgear interlocking system with logical
Innovation mechanical interlocks
The use of digital secondary systems and combined • Bolted switchgear housings sealed for life
­protection and control devices ensures: • Minimum fire load
• C
 lear integration in process control systems • Option: Aseismic design.
• Flexible and highly simplified adaptation to new system
conditions and thus to cost-efficient operation. Reliability
• Type and routine-tested
• Standardized, NC production processes
Service life
• Quality assurance in accordance with DIN EN ISO 9001,
Under normal operating conditions, the expected service life
DIN EN ISO 14001 and BS OHSAS 18001
of gas-insulated switchgear 8DA/B is at least 40 years, taking
• More than 150,000 switchgear panels of Siemens in opera-
the tightness of the enclosed high-voltage part into account.
tion worldwide.
The service life is limited by the maximum number of oper-
ating cycles of the switching devices installed:
• For circuit-breakers, according to the endurance class
defined in IEC 62271‑100
• For three-position disconnectors and earthing switches,
according to the endurance class defined in IEC 62271‑102.

6 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Requirements
Technology

General Instrument transformers


• Single-pole enclosure of the primary part by modular • Current transformers not subjected to dielectric stress
switchgear housings made of corrosion-resistant • Metal-enclosed, plug-in and disconnectable voltage
aluminum alloy transformers.
• Insulating gas SF6 up to 40.5 kV
• Alternatively: Insulating gas Clean Air up to 24 kV Vacuum circuit-breaker
(consisting of the natural elements of the ambient air • Maintenance-free under normal ambient conditions
according to IEC 62271-4) according to IEC 62271‑1
• Three-position disconnector as busbar disconnector • No relubrication or readjustment
and feeder earthing switch • Vacuum interrupters sealed for life
• Make-proof earthing by means of the vacuum circuit‑­ • Up to 10,000 operating cycles (maintenance-free)
breaker • Option: Up to 30,000 operating cycles
• Compact dimensions due to gas insulation (maintenance required).
• Single-pole metal-enclosed, gas-insulated busbars
• Cable connection with inside-cone plug-in system, or for
Secondary systems
connection of gas-insulated and solid-insulated bars
• Protection, measuring and control equipment
• Wall-standing or free-standing arrangement
• Option: Numerical multifunction protection relay
• Installation and extension of existing switchgear at both
with ­integrated protection, control, communication,
ends without modification of existing panels.
­operating and monitoring functions
• Can be integrated in process control systems.
Interlocks
• According to IEC 62271‑200
• Three-position disconnector can only be operated with
circuit-breaker in OPEN position
• Circuit-breaker can only be operated with three-position
disconnector in end position and operating lever ­removed.

Modular design
• Replacement of the panel connection housings or
the ­circuit-breaker possible without interrupting busbar
­operation
• Low-voltage compartment removable, plug-in bus wires.

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 7
Digitalization, condition monitoring
Siemens Xcelerator, available monitoring functionalities

Siemens Xcelerator Temperature monitoring of the cable connections


Temperature monitoring of the cable connections ensures
Siemens Xcelerator is an open digital business platform that that the maximum permissible thermal service conditions of
enables customers to accelerate their digital transformation the gas-insulated switchgear and the cable connection set
more easily, quickly, and at scale. are not exceeded during operation. With the help of an
intelligent correlation between the ambient air temperature,
Addressing key challenges in the energy sector the cable connection temperature, and the switchgear
and beyond ­utilization, anomalies can already be detected and indicated
Maintaining grid stability – Increasing energy demands before the limit temperature is reached, based also on
often clash with fluctuating generation. Balancing both is low-load scenarios.
crucial for tomorrow’s grid stability. Temperature and humidity monitoring of
Our smart energy solutions simplify management, align OT the ­environment (dew-point monitoring)
and IT, and ensure a resilient, scalable, and adaptable grid. Ongoing condensation would lead to corrosion at the
­switchgear, and reduce its service life. Specific
Maximizing cyber and asset security – Power grids can ­countermeasures after strong humidity at the switchgear
be a target for cyberattacks, which may cause power outages assembly, as well as the prevention of further condensation,
and unpredictable results. can remedy the situation.
Our solutions incorporate security measures to remove
vulnerabilities in IT components, control devices, as well as Partial discharge monitoring
transformer substation and switchgear systems. Partial discharges arise if the electrical insulation is damaged
or insufficient. Partial discharge monitoring offers a
Reducing expenditures – Our solutions enhance com­ pre-alarming in case of a possibly insufficient electrical
petitiveness through optimized CAPEX and OPEX with asset ­insulation. In most cases, partial discharges are a long-term
optimization, digital planning, simulation, and flexible effect of thermal overstressing or of defective or incorrectly
financing options. installed peripheral components.
Integrating distributed energy resources (DERs) – DERs Digital gas density monitoring
are at the heart of a clean and resilient energy future. Never- For perfect operation of a gas-insulated switchgear, the correct
theless, a greater system flexibility is needed to consistently gas density inside the switchgear vessel is crucial. To maintain
balance supply and demand. the full scope of functions of the switchgear, immediate action
Our solution offering covers the entire spectrum: from is required if the gas density falls below the necessary values.
consulting through technical applications and services to Continuous monitoring with a trend analysis can provide an
tailored financing and business models. indication clearly before the operational limitations arise, and
allows the initiation of planned measures.

Circuit-breaker monitoring
Available monitoring functionalities Continuous monitoring of circuit-breaker functions enables
for gas-insulated switchgear an evaluation of the actual health status of the circuit-breaker,
based on both mechanical and electrical parameters. The
Condition monitoring
evaluation of performed mechanical and electrical switching
Condition monitoring serves to continuously improve the
operations, as well as the monitoring of other components,
resilience, reliability, and availability of maintenance-free,
allows to indicate at an early stage if servicing work is
gas-insulated medium-voltage switchgear with an expected
­necessary, or if a suitable replacement switchgear should be
service life of 40 years. These values are based on the design
procured.
and empirical data for switchgear assemblies, as well as on
the intended use of the switchgear under normal service Load flow monitoring
conditions according to IEC 62271-1. Load flow monitoring provides the basis for the relation
To protect the investment (CAPEX) and reduce operational between the electrical utilization and other defined and
expenditures (OPEX), the extension of switchgear ­functions ­monitored status values. Knowing the actual utilization, for
with a condition monitoring system is the ­appropriate example, it is possible to determine how the temperature
way for early indication of irregularities at the switchgear characteristic will develop with increasing electrical utilization,
and its peripheral components. This is the premise for and if this leads to a possible recommended action.
­condition-based inspection.

8 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Digitalization, condition monitoring
Digitalization solutions from a single source

NXpower Monitor SIPROTEC Dashboard


SICAM Navigator OT Companion

Control Center SCADA


Cloud
Spectrum Power
SICAM SCC
CONTROL LEVEL CLOUD LEVEL

RTU / Gateway SIMARIS control


End-to-End-Cybersecurity

SICAM A8000

Visualization SUBSTATION LEVEL

SICAM Motor
SICAM FCM Control
Condition SIPROTEC 5 Reyrolle 5 UPS P850 plus Unit
Monitoring

Temperature
and Humidity

Partial
Discharge

Gas Density

Circuit-Breaker

Load Flow

8DAB 24 NXPLUS C 24 8DJH 24

SWITCHGEAR LEVEL

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 9
Sustainability

Our contribution to a sustainable and cleaner planet


At Siemens, sustainability is not just a commitment, but a
core strategy deeply ingrained in our operations. Our DEGREE
framework, representing Decarbonization, Ethics, Gover-
nance, Resource Efficiency, Equity, and Employability,
guides our journey towards a sustainable future. It constitutes
a 360-degree approach for all stakeholders – our customers,
our suppliers, our investors, our people, the societies we
serve, and our planet.

Siemens aims to limit global warming to 1.5 degrees Celsius


and takes action across its operations, targeting various ESG
(Environmental, Social, and Governance) topics. We further
contribute to decarbonization by helping our customers
reduce emissions, and aim to lower our own operational
emissions significantly by 2030. Additionally, we promote
resource efficiency through recycling and a circular economy,
incorporating sustainable design criteria into our products
and increasing the use of secondary materials. Siemens
focuses on sustainable materials, energy sources, and product
service life optimization to minimize resource consumption
and waste. Ultimately, we strive to create a better future by
achieving sustainability goals and minimizing environmental
impacts.

Siemens gas-insulated switchgear (GIS) systems have played Material efficiency: blue GIS products are designed to have
a key role over the last 40 years for a reliable and safe power a very low CO2 footprint. A prime example is SIBushing, a
distribution. The new Siemens blue GIS portfolio reflects our non-conventional instrument transformer that reduces the
commitment to 100% sustainable innovation, which integrates use of raw materials, energy consumption, and landfill waste.
both Clean Air as an insulating medium and an eco-efficient
Energy efficiency: An optimized main current path with a
design that reduces its CO2 footprint throughout the entire
low ohmic resistance reduces the power loss during opera-
life cycle. With a wide range of products covering all the
tion of the switchgear considerably, and thus increases the
needs, our blue GIS will be the core of a sustainable energy
energy efficiency.
transition. The following innovative solutions offer a remark-
able CO2 footprint reduction: Long service life: With the right material selection and an
innovative design, blue GIS have an expected service life of
F-gas-free insulation: Clean Air consists of natural-origin 40 years, thus extending the re-investment cycle and further
gases with a GWP < 1, which means it has virtually no nega- diminishing the CO2 footprint.
tive impact on the environment or climate change during the
Maintenance-free design: No additional maintenance is
entire life cycle. It can even be released into the atmosphere
necessary, and the CO2 footprint can be reduced further by
after reaching its end of life.
avoiding site visits during the operational phase of the
Space efficiency: Like the traditional GIS design, Siemens switchgear.
blue GIS also offer very compact solutions that save valuable
Sustainable services: The CO2 footprint can be diminished
space and additionally decrease the environmental impact of
thanks to services from predictive maintenance to condition
electrical infra­structure installations.
monitoring, remote FAT, CO2 monitoring via NXpower
monitor, the Totally Integrated Power planning tools, and
paperless documentation.

10 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Sustainability

The complete life cycle that counts Material0.69%


composition
1.8%
In view of the global climate crisis and the necessity to reduce 0.2% 1.7% 0.1%
1.8% Ceramics
0.69%
carbon emissions and preserve natural resources, Siemens 22.9% 0.2% 0.9%1.7% Thermosets
0.1% Ceramics
aims to decrease the environmental footprint of its own Thermoplastics
22.9% 0.9% Thermosets
business operations as well as that of its customers and Rubber & Silicon
11.6% Thermoplastics
supply chains. With internationally standardized approaches, High-alloyed steel
Product weight Rubber & Silicon
we provide transparency regarding the environmental 11.6% Low-alloyed steel
High-alloyed stee
667 kg
impacts of our products, systems, solutions, and services. Copper & Alloys
Low-alloyed stee
59.8% Aluminum /
Robust Eco Design: Our blue GIS panels are designed as Copper & Alloys
Other materials
a part of the Eco Efficiency @ Siemens program, where the 59.8% Aluminum /
Clean Air
­environmental impacts to be expected in each of the prod- Other materials
uct’s life cycle phases are addressed right from the design Clean Air
phase. The switchgear is designed not only to minimize its
Resource efficiency
CO2 footprint, but also to prioritize resource efficiency and
circular economy. The end-of-life phase of an 8DAB 24 – SBB blue GIS was
Assembly
modeled with the LCA tool GaBi 9.5 by first dismantling the
equipment, followed by a shredding, sorting, and material
separation process, resulting in:
• An overall product recyclability of up to 95.3% mainly
thanks to high metal content
Re • An energy recoverability of up to 3.0% from plastic materials
ent

• A minimum disposal rate of 1.7%


pa

hm
ir &

EcoDesign
b is
Reuse

Use Manufacturing
ur

R
ef

ri n
g& The exact final values depend on the used recycling processes.
R e m a n ufactu

R e c yc li n g

Extraction of
Waste
raw material
Use of environmentally safe materials
At Siemens, we are committed to the development and
The Siemens Environmental Product Declaration (EPD)
production of environmentally friendly and sustainably
adheres to ISO 14021 standards for environmental labels and
produced equipment. This includes avoiding hazardous
declarations. It is based on a comprehensive Life Cycle
substances in our products without compromising their
Assessment (LCA) study conducted in accordance with
benefits for our customers. Please visit the following website*
ISO 14040/44, incorporating Product Category Rules (PCR)
to learn more about how we comply with product-related
specified in EN 50693 for electronic and electrotechnical
environmental regulations like RoHS, REACh and others.
products and systems.

Product 8DAB 24 – SBB – primary distribution blue GIS


Technical data Ur = 24 kV, Ik = 40 kA, Ir = 1250 A
8DAB 24 is an F-gas-free single-pole enclosed and
single-busbar (SBB) gas-insulated ­circuit-breaker
Product description switchgear with Clean Air insulation for primary
distribution grids, and available as circuit-breaker,
bus sectionalizer and d­ isconnector panels
Reference 8DAB 24 – SBB – circuit-breaker panel
– blue GIS, primary part, type-tested according to
Functional unit
IEC 62271-200. Maintenance-free, operating 24 h,
365 days/a with an expected service life of 40 years

* https://www.siemens.com/global/en/products/energy/ecotransparency/
ecotransparency-downloads.html

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 11
Room planning
Single-busbar switchgear and double busbar switchgear

Room planning for single-busbar switchgear 8DA10 and 8DAB 24 SBB


Wall-standing arrangement (top view) Free-standing arrangement (top view)





 



 

   


 
 
 

 
 

Room planning for traction power supply switchgear 8DA11


Wall-standing arrangement (top view) Free-standing arrangement (top view)




 


 


   


 
 

 
 

Room planning for traction power supply switchgear 8DA12


Wall-standing arrangement (top view) Free-standing arrangement (top view)





 



 

   




 
 


 

12 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Room planning
Single-busbar switchgear and double busbar switchgear

Room planning double busbar switchgear 8DB10 and 8DAB 24 DBB


Wall-standing arrangement (top view) Free-standing arrangement (top view)





 



 

   


 

 
 

 
  

Switchgear installation Switchgear fixing


• Wall-standing arrangement without rear wall (IAC AFL) • For floor openings and fixing points of the switchgear,
• Free-standing arrangement without rear wall (IAC AFL) see pages 19 to 23
• Free-standing arrangement with rear wall (IAC AFLR). • Foundations:
– Steel girder construction
Room dimensions
– Steel-reinforced concrete with foundation rails, welded or
See dimension drawings above.
bolted on.
Room height: ≥ switchgear height + 200 mm.
If there are any busbar components, the minimum room Panel dimensions
height may have to be higher. See pages 19 to 23.
For switchable busbar components in 8DB10, free-standing
arrangement is required.

Door dimensions
The door dimensions depend on the dimensions of the indi-
vidual panels (see pages 19 to 23).

*) Depending on national requirements


**) Lateral wall distance ≥ 500 mm
optionally required on the left or on the right
***) Lateral minimum wall distance
≥ 100 mm optionally possible on the left or on the right

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 13
Room planning
Transport and packing

Transport and packing


Means of transport: Seafreight or airfreight
Transport
• Panels on pallets
Single-busbar switchgear 8DA10 and traction power supply
• In closed crates with sealed upper and lower
switchgear 8DA11/12 is delivered in transport units
PE ­protective foil
comprising up to four panels. Double-busbar switchgear
• With desiccant bags
8DB10 is delivered in transport units comprising up to three
• With sealed wooden base
panels.
• Max. storage time: 6 months.
Please observe the following:
• Transport facilities on site Long-time packing
• Transport dimensions and transport weights • Panels on pallets
• Size of door openings in building. • In closed crates with sealed, aluminum-coated
PE ­protective foil
Packing
• With desiccant bags
Means of transport: Truck
• With sealed wooden base
• Panels on pallets
• Max. storage time: 12 months.
• Open packing with PE protective foil.

Dimensions, weights

Transport Panel spacing Transport dimensions Transport weight 1)


Width Height Depth with packing without packing
mm mm mm mm kg kg

Single-busbar switchgear 8DA10 and 8DAB 24 SBB


1 × 600 1370 2550 1888 850 750
2 × 600 1764 2550 1870 1700 1500
Truck
3 × 600 2400 2550 1870 2550 2250
4 × 600 2964 2550 1870 3400 3000
1 × 600 1388 2700 1888 850 750
Seafreight 2 × 600 1764 2700 1888 1700 1500
or
airfreight 3 × 600 2400 2700 1888 2550 2250
4 × 600 2964 2700 1888 3400 3000

Double-busbar switchgear 8DB10 and 8DAB 24 DBB


1 × 600 1370 2550 3124 1300 1200
Truck 2 × 600 1870 2550 3124 2600 2400
3 × 600 2416 2550 3124 3900 3600

Seafreight 1 × 600 1388 2850 3124 1300 1200


or 2 × 600 1888 2850 3124 2600 2400
airfreight 3 × 600 2440 2850 3124 3900 3600

Traction power supply switchgear 8DA11/12


1 × 600 1370 2550 1888 600 500
2 × 600 1764 2550 1870 1200 1000
Truck
3 × 600 2400 2550 1870 1800 1500
4 × 600 2964 2550 1870 2400 2000
1 × 600 1388 2700 1888 600 500
Seafreight 2 × 600 1764 2700 1888 1200 1000
or
airfreight 3 × 600 2400 2700 1888 1800 1500
4 × 600 2964 2700 1888 2400 2000
1) Average values based on standard subframe with LV compartment 850 mm depending on the degree to which panels are equipped

14 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Room planning
Classification

Classification of single-busbar switchgear and double-busbar switchgear according to IEC 62271-200

Design and construction

Partition class PM
Loss of service continuity category
– Single-busbar switchgear LSC2
– Double-busbar switchgear LSC2A
Internal arc classification

Wall-standing arrangement IAC AFL 40 kA, 1 s


Free-standing arrangement IAC AFLR 40 kA, 1 s
Type of accessibility A Switchgear in closed electrical service location,
access “for authorized personnel only” according to IEC 62271‑200
–F Front
–L Lateral
–R Rear (for free-standing arrangement)
Rated short-time withstand current 40 kA
Rated duration of short-circuit 1s

Classification of single-busbar switchgear and double-busbar switchgear according to IEEE Std C37.20.7TM-2017

Internal arc classification

Wall-standing arrangement Typ 1B 40 kA, 0.5 s


Free-standing arrangement Typ 2B 40 kA, 0.5 s
Type of accessibility
– Typ 1B Front
– Typ 2B Front, lateral, rear (for free-standing arrangement)
Rated short-time withstand current 40 kA
Rated duration of short-circuit 0.5 s

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 15
Product range
Single-busbar switchgear 8DA10 and 8DAB 24 SBB

Circuit-breaker panel

Three-position
disconnector

Vacuum circuit-breaker

Plug-in voltage trans-


former (directly plugged
or with cable connection)

Voltage transformer
without or with
­disconnecting function


Current transformer

Capacitive voltage
detecting system
Bus sectionalizer

Busbars
– earthing switch

Busbar connection with or


without three-position
disconnector

Surge arrester

Panel connection with


inside-cone plug or bar
connection


Zero-sequence
current transformer

Top-mounted
bus sectionalizer

Note: The 8DAB 24


product range may
contain restrictions.

16 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Product range
Double-busbar switchgear 8DB10 and 8DAB 24 DBB

Circuit-breaker panel

Three-position
disconnector

Vacuum circuit-breaker

Plug-in voltage trans-


former (directly plugged
or with cable connection)

Voltage transformer
without or with
­disconnecting function


Current transformer

Capacitive voltage
detecting system
Bus sectionalizer

Busbars
– earthing switch

Busbar connection with or


without three-position
disconnector

Surge arrester

Panel connection with


inside-cone plug or bar
connection


Zero-sequence
current transformer

Top-mounted
bus sectionalizer

Note: The 8DAB 24


product range may
contain restrictions.

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 17
Product range
Double-busbar switchgear 8DB10 and 8DAB 24 DBB

Bus coupler

Three-position
disconnector

Vacuum circuit-breaker

Voltage transformer
without or with
­disconnecting function

Current transformer


Capacitive voltage
detecting system

Busbars
– earthing switch

Busbar connection with or


without three-position
disconnector

Top-mounted
bus sectionalizer

Note: The 8DAB 24


product range may
contain restrictions.

18 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Dimensions
Typicals, single-busbar switchgear (examples)

Circuit-breaker panel up to 3150 A



R-HA3511-018 png



  


 

   








 
   

Bus sectionalizer up to 3150 A





R-HA3511-022 png

  


  

   




Legend and footnotes:








1 Fixing hole for


26 mm × 45 mm
2 Base frame


3 Floor opening for






high-voltage cables
4 Area for floor openings for
control cables


 
   

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 19
Dimensions
Typicals, double-busbar switchgear (examples)

Circuit-breaker panel up to 3150 A



R-HA3511-019 png



     


 

   








 
   

Legend and footnotes:


1 Fixing hole for
26 mm × 45 mm
2 Base frame
3 Floor opening for
high-voltage cables
4 Area for floor openings for control cables

20 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Dimensions
Typicals, double-busbar switchgear (examples)

Bus coupler up to 3150 A




R-HA3511-020 png

     


 

   








 
   

Legend and footnotes:


1 Fixing hole for
26 mm × 45 mm
2 Base frame
3 Floor opening for
high-voltage cables
4 Area for floor openings for control cables

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 21
Dimensions
Typicals, double-busbar switchgear (examples)

Bus sectionalizer up to 3150 A (busbar system 1 and 2)



R-HA3511-021 png



     


  

   














 
   

Legend and footnotes:


1 Fixing hole for
26 mm × 45 mm
2 Base frame
3 Floor opening for
high-voltage cables
4 Area for floor openings for control cables

22 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Dimensions
Typicals, traction power supply switchgear (examples)

Single-pole circuit-breaker panel up to 2500 A






 

   









 
   

Double-pole circuit-breaker panel up to 2500 A






 
 

   









Legend and footnotes:


  1 Fixing hole for
    26 mm × 45 mm
2 Base frame
3 Floor opening for
high-voltage cables
4 Area for floor openings for control cables

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 23
Design
Panel design, single-busbar switchgear (example)

Panel design Panel design (example)

• Factory-assembled, type-tested
• S ingle-pole metal enclosure
• Hermetically bolted switchgear
housings made of corrosion-resistant 1
aluminum alloy
• Switchpanel poles arranged one
behind the other 2
Legend for pages 24 and 25:
• Maintenance-free under normal
3
operating conditions according to 1 Low-voltage compartment
IEC 62271-1 4 2 Electronic control board, e.g.
• Degree of protection multifunction protection
3 Operating mechanism and
– IP65 for all high-voltage parts of
interlock for three-position
the primary circuit disconnector, as well as
– IP3XD for the switchgear enclosure 1) 5 mechanical position indicators for
• Vacuum circuit-breaker three-position disconnector and
• Three-position disconnector for circuit-breaker
4 Manometer for gas monitoring of
disconnecting and earthing

R-HA3511-023 tif
feeder gas compartments
• Make-proof earthing by means of the 6
5 Circuit-breaker operating
vacuum circuit-breaker mechanism
• Cable connection with inside-cone 6 Voltage detecting system
plug-in system according to
EN 50181
• Wall-standing or free-standing
­arrangement Panel for single-busbar switchgear
• Instrument transformers located
outside the gas compartments
• Low-voltage compartment
­removable, plug-in bus wires
• Standardized production Arrangement of gas compartments
­processes and certified quality and
­environmental management system
­according to ISO 9001, ISO 14001
and BS OHSAS 18001.

ANSI design:   

Camera system
  
• Camera system for visual monitor-
ing of the switch positions of the
­disconnectors and earthing switches.

UL certification Gas-tight
bushing


• For 8DA10 and 8DB10 ANSI design


options there is a UL or cUL certificate Bushing
available. pervious to gas

Single-busbar panel

1 Busbar L1 (manometer B11 *) 4 Circuit-breaker L1, L2, L3 (­manometer B0 *)


2 Busbar L2 (manometer B12 *)
3 Busbar L3 (manometer B13 *)

1) Other switchgear enclosure versions on request


* Item designation

24 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Design
Panel design, double-busbar switchgear (example)

Panel design (example) Insulating system

• Switchgear housing filled with gas


• Insulating gases according to
IEC 62271-4:
1 – Insulating gas SF6 up to 40.5 kV,
GWP = 24,300
– Alternatively: Insulating gas Clean Air
2
up to 24 kV (natural elements of the
4 ambient air)
• Pressure of the gases in the
­switchgear housing dependent
on the electrical ratings (relative
3
­pressure at 20 °C):
– Rated functional level (relative):
5 70 kPa to 230 kPa
– Operating pressure of bursting disc:
≥ 300 kPa
R-HA3511-024 png

– Bursting pressure: ≥ 600 kPa


6 – Gas leakage rate: < 0.1 % per year.

Legend see page 24.

Panel for double-busbar switchgear

Arrangement of gas compartments Gas compartment scheme

• Sealed pressure system according


to IEC 62271‑1
• No refilling required throughout
     
the entire service life
• Gas compartments distributed to
      several areas
• Simple, visual check of the
­gas ­pressure on the switchgear front
   • Indication of the gas pressure without
auxiliary voltage supply
• Gas filling equipment with non-­return
Gas-tight valve arranged at the switchgear
bushing front beside the associated gas


­pressure manometer.
Bushing
pervious to gas

Double-busbar panel

Legend for 8DB10:


1 Busbar system 1, L1 (manometer B11 *) 7 Three-position disconnector, busbar system 1,
2 Busbar system 1, L2 (manometer B12 *) L1, L2, L3 (manometer B1 *)
3 Busbar system 1, L3 (manometer B13 *) 8 Disconnector, busbar system 2, L1, L2, L3
4 Busbar system 2, L1 (manometer B21 *) (manometer B2 *)
5 Busbar system 2, L2 (manometer B22 *) 9 Circuit-breaker L1, L2, L3 (manometer B0 *)
6 Busbar system 2, L3 (manometer B23 *)

* Item designation

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 25
Components
Vacuum circuit-breaker

Features

R-HA3511-018 png
• V acuum circuit-breaker according to IEC 62271-100
• Application in hermetically bolted switchgear housings
in conformity with the system
• Vacuum interrupter in gas-filled switchgear housing
• Individual secondary equipment
• A metal bellows is used for gasketless separation between
the gas insulation and the vacuum.

Trip-free mechanism
The vacuum circuit-breaker is fitted with a trip-free
mechanism according to IEC 62271-100. 1
Switching duties and operating mechanisms
The switching duties of the vacuum circuit-breaker are
dependent, among other factors, on its type of operating
mechanism.
5
Motor operating mechanism 2
• Motor-operating stored-energy mechanism
4
– For auto-reclosing (K)
– For synchronization and rapid load transfer (U).
3
Further operating mechanism features
• Operating mechanism located outside the
­switchgear ­enclosure
• Installation behind the control board Circuit-breaker operating mechanism 3AH49 for
­single-busbar switchgear, double-busbar switchgear
• Stored-energy spring mechanism for and traction power supply switchgear
10,000 operating cycles
• Optional: Stored-energy spring mechanism for
1 ON pushbutton
30,000 ­operating cycles. 2 OFF pushbutton
3 Operations counter
Operating mechanism functions 4 Position indicator for circuit-breaker
Motor operating mechanism 5 “Closing spring charged” indicator at
In the case of motor operating mechanism, the closing spring is the ­operating mechanism
charged by means of a motor and latched in the charged posi-
tion (“spring charged” indication is visible). Closing is effected
either by means of an ON pushbutton or a closing solenoid.
The closing spring is recharged automatically (for auto-reclosing).

Endurance class of circuit-breaker Operating times

Function Class Standard Property of 8DA/B Closing time Closing solenoid < 95 ms
BREAKING M2 IEC 62271-100 10,000 times mechanically Opening time 1st shunt release < 75 ms
without maintenance 2nd shunt release < 65 ms
E2 IEC 62271-100 10,000 times rated continuous Undervoltage release < 65 ms
­current without maintenance Arcing time  at 50 Hz < 15 ms
50 times short-circuit breaking  at 60 Hz < 12 ms
current without maintenance Break time  at 50 Hz 1st shunt release < 90 ms
C2 IEC 62271-100 Very low probability of restrikes 2nd shunt release < 80 ms
Undervoltage release < 80 ms
Dead time 300 ms
Total charging time < 15 s

For further technical data and description of


typical applications, please refer also to Catalog HG 11.04
“3AH4 Vacuum Circuit-Breakers”

26 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Vacuum circuit-breaker

Secondary equipment Operating cycle diagram


The scope of the secondary equipment of the vacuum
­circuit-breaker depends on the type of application and offers
a wide range of possible variations, allowing almost every

HA35-2678b_EN eps
requirement to be satisfied.

Closing solenoid
• Type 3AY15 10 (Y9*)
• For electrical closing.

Shunt releases
• Types:
– Standard: 3AY15 10 (Y1*)
– Option: 3AX11 01 (Y2*), with energy store
• Tripping by protection relay or electrical actuation.

Undervoltage release
• Type 3AX11 03 (Y7*)
• Comprising:
– Energy store and unlatching mechanism
– Electromagnetic system, which is permanently connected
to voltage while the vacuum circuit-breaker is closed;
tripping is initiated when this voltage drops
• Connection to voltage transformers possible. Examples
Electrical data (curve 1)
Anti-pumping Rated short-circuit breaking current 25 kA
• F
 unction: If constant CLOSE and OPEN commands are Rated continuous current 1250 A
present at the vacuum circuit-breaker at the same time, Electrical data (curve 2)
the vacuum circuit-breaker will return to the open Rated short-circuit breaking current 31.5 kA
­position a
­ fter closing. It remains in this position until a Rated continuous current 2000 A
new CLOSE command is given. In this manner, continuous Electrical data (curve 3)
closing and opening (= pumping) is avoided. Rated short-circuit breaking current 40 kA
Rated continuous current 2500 A
Circuit-breaker tripping signal
Rated operating sequences
• F
 or electrical signaling (as pulse > 10 ms), e.g. to remote Rapid load transfer (U): O – t – CO – t’ – CO (t = 0.3 s, t’ = 3 min)
control systems, in the case of automatic tripping Auto-reclosing (K): O – t – CO – t’ – CO (t = 0.3 s, t’ = 3 min)
(e.g. protection) Auto-reclosing (K): O – t – CO – t’ – CO (t = 0.3 s, t’ = 15 s)
• Via limit switch (S6*) and cutout switch (S7*).
O = OPEN operation
Varistor module CO = CLOSE operation with subsequent OPEN operation at the ­shortest
internal close-open time of the vacuum circuit-breaker
• T
 o limit overvoltages to approx. 500 V for protection
­devices (when inductive components are mounted in
the vacuum circuit-breaker) Possible release combinations
• For auxiliary voltages ≥ 60 V DC.
Release 1 2 3 4 5
Auxiliary switch
1st shunt release type 3AY15 10 • • • • •
• Type 3SV9 (S1*) 2nd shunt release type 3AX11 01 – • • – •
• Standard: Up to 22 NO + 22 NC. – • – –
3rd shunt release type 3AX11 01 –
Position switch Undervoltage release type 3AX11 03 – – – • •
• Type 3SE4 (S4*)
• For signaling “closing spring charged“.

Mechanical interlock
• Mechanical interlocking to the three-position disconnector
• During operation of the three-position disconnector,
the vacuum circuit-breaker cannot be operated.

Abbreviations: NO = normally open contact, NC= normally closed contact

* Item designation

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 27
Components
Three-position disconnector

Features Position indicators, single-busbar switchgear


• Rated continuous currents up to 3150 A for three-position disconnector
• 2000 operating cycles for the disconnector * and vacuum circuit-breaker
• 1000 operating cycles for the earthing switch *
• Operating shaft and contact blades with common center
of rotation and reliable switch position up to the operating

front of the panel
• Gas-tight bushings separate the busbar and
circuit-breaker housings
• Maintenance-free under normal operating conditions 
­according to IEC 62271-1.


Switch positions
• CLOSED, OPEN, EARTHED or READY-TO-EARTH
Feeder OPEN
• CLOSED: Contact blades connected with the busbar:
Main circuit closed between busbar and circuit-breaker
• OPEN: Main circuit open between busbar and circuit-­ 
breaker: Test voltages for isolating distances are withstood
• READY-TO-EARTH: Contact blades connected with the
earthing contact 
• EARTHED: Feeder earthed and short-circuited by closing 

the circuit-breaker.

Operating mechanism
• Only permissible operations possible due to logical Feeder CLOSED
mechanical interlocks
• Mechanically coupled position indicator

• Separate operating shafts for the “DISCONNECTING”,
“EARTHING” and “READY-TO-EARTH” functions
• With manual operating mechanism
• Option: With motor operating mechanism 


• Same sense of rotation for the switching operations of


the “CLOSE” or “OPEN” functions.

Feeder READY-TO-EARTH

Endurance class of three-position disconnector 

Function Class Standard Property of 8DA/B

DISCONNECT- M1 IEC 62271-102 2000 times mechanically



ING without maintenance


READY-TO- 1000 times mechanically


EARTH without maintenance
EARTHING E2 1) IEC 62271-102 50 times rated short-circuit
making current Ima without Feeder EARTHED
maintenance

Endurance class of make-proof earthing switch

Function Class Standard Property of 8DA/B

EARTHING E1 IEC 62271-102 1000 times mechanically


without maintenance
2 times rated short-circuit
making current Ima ­without
maintenance

1) By closing the circuit-breaker


* Higher operating cycles on request

28 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Three-position disconnector

Interlocks Position indicators, double-busbar switchgear


• Selection of permissible switching for three-position disconnector
operations by means of a control and vacuum circuit-breaker
gate with mechanically interlocked
vacuum circuit-breaker
• Corresponding operating shafts are
not released at the operating front
 
until they have been pre-selected
with the control gate
• Operating lever cannot be removed
until switching operation has been 


completed
• Circuit-breaker cannot be closed until
the control gate is in neutral position
Feeder OPEN
again
• Option: Switchgear interlocking
­system with electromechanical in-
terlocks (­ mechanical interlocking for  
manual operation remains).




Feeder busbar system 1 CLOSED

 




Feeder busbar system 2 CLOSED

 




Feeder READY-TO-EARTH

 




Feeder EARTHED

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 29
Components
Current transformers

Features Current transformers


• According to IEC 61869-2
• Designed as ring-core current
transformers, single-pole
• Free of dielectrically stressed
cast-resin parts (due to design)
• Insulation class E 

• Inductive type
• Certifiable 
• Climate-independent
• Secondary connection by
means of a terminal strip in
the low-voltage compartment 
of the panel
• Cast-resin insulated.



Installation

• A
 rranged outside the primary
enclosure (switchgear housing).


B Current transformer
in bus sectionalizer and bus coupler
(type 4MC4_40)
C Feeder current transformer
(type 4MC4_90)
D Feeder current transformer
(type 4MC4_10) 
E Busbar current transformer
(type 4MC4_40)
Option:
A Feeder current transformer
between circuit-breaker and
three-position disconnector at the
busbar (type 4MC4_90)


Electrical data* for Type 4MC4


Operating voltage max. 0.8 kV
Rated short-duration p
­ ower-frequency withstand voltage Current transformer installation (examples)
3 kV
­(winding test)
Rated frequency 50 / 60 Hz
Rated continuous
max. 1.2 × rated current (primary)
thermal current
Rated thermal short-time current, max. 3 s max. 40 kA
Rated current dynamic unlimited
primary 40 A to 3150 A
secondary 1 A and 5 A
Multiratio (secondary) 200 A – 100 A up to 3150 A – 1575 A
Core data according to rated primary current max. 3 cores
Measuring core Rating 2.5 VA to 30 VA
Class 0.2 to 1
Overcurrent factor FS 5, FS 10
Protection core Rating 2.5 VA to 30 VA
Class 5 P or 10 P
Overcurrent factor 10 to 30
Permissible ambient air temperature max. 60 °C
Insulation class E
* Further electrical data on request

30 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Voltage transformers

Voltage transformers Features


• A ccording to IEC 61869‑3
• Single-pole, plug-in design

 • Connection system with plug-in
contact according to EN 50181
• Inductive type
• Safe-to-touch due to
­metal ­enclosure
• Certifiable
• Climate-independent
• Secondary connection by means
of plugs in the low-voltage
­compartment of the panel
• Cast-resin insulated.

Installation
• Arranged outside the primary
enclosure (switchgear housing).
 Mounting locations


• On the busbar



• At the panel connection housing.

Voltage transformer types


Busbar voltage transformers
Voltage transformer installation (examples) 4MT3 and 4MU4
• Pluggable on the busbar with
plug-in system according to
1  usbar voltage transformer
B 3  usbar voltage transformer 4MU4 with
B
4MU4 / 4MT3 three-position disconnector (option) EN 50181
2 Feeder voltage transformer 4 Feeder voltage transformer 4MU3 • No separate metering panel
4MT3 / 4MT7 (connection at panel (connection via flexible cable with plug required
connection housing); size S2 at the panel connection housing,
feeder voltage transformer with and metal-enclosed voltage t­ ransformer) • Option: Three-position disconnec-
disconnecting function (option) tor for busbar voltage transformer
CLOSED – OPEN – EARTHED
• Option 4MU4: Repeat test at
80 % of the rated short-duration
­power-frequency withstand ­voltage
possible with mounted voltage
transformer.
Feeder voltage transformers
4MT3 / 4MT7 and 4MU3
Electrical data for 4MT3 4MU4 4MT7 4MU3
• Pluggable at the feeder
Rated voltage  up to kV 24.0 40.5 40.5 40.5 with ­plug-in system according
Rated short-duration to EN 50181
power-frequency • Connection of 4MT3 / 4MT7
withstand voltage  up to kV 65 95 95 95 directly at the panel connection
Rated lightning impulse housing
­withstand voltage  up to kV 125 200 200 200 • Connection of 4MU3 via
Rated voltage factor Un / 8h = 1.9 Un / 8h = 1.9 Un / 8h = 1.9 Un / 8h = 1.9 ­flexible cable with plug
Un / continuous Un / continuous Un / continuous Un / continuous size S2 at the ­panel connection
= 1.2 = 1.2 = 1.2 = 1.2 housing, and metal-enclosed
Standard IEC IEC IEC IEC ­voltage transformer.
GOST GOST GOST GOST
GB GB GB GB

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 31
Components
Panel connection

Panel connection for cable plugs and bar systems

   

   













Version 1 Version 2 Version 3 Version 4

Solid-­
Solid-­
insulated
insulated
4MT7, bar
S2 S3 S2 S3 bar S2 S3
4MT3 connec-
­connection
tion up to
up to 2500 A
3150 A

1 1 1 1 4
2 5
3 6
2 4
3 1 3
1 2 1 4
2 1 2 2
1 1 2 3
2 1 3 1
1 1 3 2
2 1 4 1
1 1 1 1 1
1 1 2 1
1 1 1 1
2 1
1 1 1
1

Panel connection height h [mm]


1. Single-busbar switchgear, traction power supply switchgear
2. Double-busbar switchgear
3. Switchgear versions with higher subframe

1. 320 240 275 240.5 222 219


2. 120 40 75 40.5 22 19
3. 540 460 495 460.5 442 439

Legend: Features
1 Panel connection housing • Inside-cone plug-in system for plug sizes 2, 3 and 4 according to EN 50181
2 Subframe
h Connection height of panel
• Connection of several cables with different plug sizes possible per phase
connection versions • Connection of solid-insulated or gas-insulated bar possible
• Connection of 4MT3/4MT7 voltage transformer plugged in at the panel connection
housing versions 3 and 7
Note:
The 8DAB 24 product range
• Connection of 4MU3 voltage transformer via plug size 2 at the panel connection housing
may contain restrictions. • For rated continuous currents up to 3150 A.

32 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Panel connection

Panel connection for cable plugs and bar systems

  

  










Version 5 Version 6 Version 7

4MT7, Test
Solid-­insulated
4MU3, socket,
S2 S3 S4 bar ­c onnection S2 S3
switch- switch-
up to 2500 A
able able

1 1 1 1
1 1 2 1
2 1 1 1
1 1 2 1
1 1 1 1 1 1
2 3 1 1)
2 1 4 1 1)
3 1 1)
2 1 1 1)
1 2 1 1)
2 2 1 1)
1 3 1 1)
1 1 1) 1
1 1 1) 1
1 1 1) 1
2 1 1) 1
3 1 1) 1
1 1 1) 1
2 1 1) 1
1 1 1 1) 1
1 2 1 1) 1
Panel connection height h [mm]
1. Single-busbar switchgear, traction power supply switchgear
2. Double-busbar switchgear
3. Switchgear versions with higher subframe

1. 92 294 105
2. 108 94 –
3. 312 514 325

Surge arresters
• Pluggable via inside-cone plug-in system size 2 or 3 according to EN 50181.

Note:
The 8DAB 24 product range
1) Version with feeder voltage transformer 4MU3
may contain restrictions.

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 33
Components
Panel connection (commercially available cable plugs and bar connections)

Busbar and panel connection (commercially available cable plugs)

Cable type Cable sealing end Remark

Diameter across Conductor


cable insulation cross-section RM (RE)
Make Type Size mm mm²

Thermoplastic-insulated cables ≤ 12 kV according to IEC 60502-2


Single-core cable or NKT CPI 2 2 12.7 – 44.0 25–300 (400) Insulation material silicone rubber,
three-core cable, without metal housing, installation
CPI 3 3 21.2 – 51.0 185–630 (800)
PE and XLPE-insu- without special tools
lated, CPI 3 XL 3 34.0 – 57.8 185–630 (1000)
N2YSY (Cu) and Pfisterer CONNEX 2 13.5 – 44.0 25 – 400 Insulation material silicone rubber,
N2XSY (Cu) with metal housing
CONNEX 3 15.5 – 55.0 35 – 800
or
NA2YSY (Al) and CONNEX 4 33.0 – 78.5 95 – 1600
NA2XSY (Al) Südkabel SEIK 14 2 13.0 – 40.6 25 – 300 Insulation material silicone rubber,
with metal housing
SEIK 15 3 19.3 – 50.6 120 – 630
TE Connectivity RPIT-321x 2 19.5 – 36.0 95 – 300 Insulation material silicone rubber,
with metal housing
RPIT-331x 3 26.0 – 50.0 240-1000

Thermoplastic-insulated cables ≤ 24 kV according to IEC 60502‑2


Single-core cable or NKT CPI 2 2 17.0 – 40.0 25 – 300 (400) Insulation material silicone rubber,
three-core cable, without metal housing, installation
CPI 3 3 21.2 – 45.6 95 – 630 (800)
PE and XLPE-insu- without special tools
lated, CPI 3 XL 3 34.0 – 57.8 400 – 800 (1000)
N2YSY (Cu) and Pfisterer CONNEX 2 13.5 – 44.0 25 – 400 Insulation material silicone rubber,
N2XSY (Cu) with metal housing
CONNEX 3 15.5 – 55.0 35 – 800
or
NA2YSY (Al) and CONNEX 4 33.0 – 78.5 95 – 1600
NA2XSY (Al) Südkabel SEIK 24 2 13.0 – 40.6 25 – 300 Insulation material silicone rubber,
with metal housing
SEIK 25 3 19.3 – 50.6 50 – 630
TE Connectivity RPIT-521x 2 19.5 – 36.0 50 – 300 Insulation material silicone rubber,
with metal housing
RPIT-531x 3 26.0 – 50.0 150-1000

Thermoplastic-insulated cables ≤ 40.5 kV according to IEC 60502‑2


Single-core cable or NKT CPI 2 2 17.0 – 40.0 25 – 300 (400) Insulation material silicone rubber,
three-core cable, without metal housing, installation
CPI 3 3 21.2 – 51.0 50 – 630 (800)
PE and XLPE-insu- without special tools
lated, CPI 3 XL 3 34.0 – 57.8 400 – 800 (1000)
N2YSY (Cu) and Pfisterer CONNEX 2 13.5 – 44.0 25 – 400 Insulation material silicone rubber,
N2XSY (Cu) with metal housing
CONNEX 3 15.5 – 55.0 35 – 800
or
NA2YSY (Al) and CONNEX 4 33.0 – 78.5 95 – 1600
NA2XSY (Al) Südkabel SEIK 24 2 13.0 – 40.6 35–300 Insulation material silicone rubber,
with metal housing
SEIK 25 3 19.3 – 50.6 50 – 630
TE Connectivity RPIT-621x 2 19.5 – 36.0 50 – 185 Insulation material silicone rubber,
with metal housing
RPIT-631x 3 26.0 – 50.0 70-1000

34 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Panel connection (commercially available cable plugs and bar connections)

Busbar and panel connection (commercially available bar systems)

Bar type Bar connection Remark

Make Type Conductor ­material Max. rated current 1)


Solid-insulated bar Ritz SIS Copper, aluminum 3150 A Outer sheath made of epoxy resin
(with heat shrinkable tube, if required)
MGC Moser Glaser Duresca DE Copper, aluminum 2500 A Outer sheath made of polyamide
(polyamide tube)
Duresca DG Copper, aluminum 2500 A Outer sheath made of CrNi steel or
aluminum (metal sheath)
Tefelen Preissinger Outer sheath made of epoxy resin
ISOBUS MR Copper, aluminum 2500 A
(with heat shrinkable tube, if required)
Gas-insulated bar MGC Moser Glaser Gaslink Copper 2500 A Aluminum housing
Tefelen Preissinger ISOBUS MG Copper 2500 A Aluminum housing

Busbar and panel connection (commercially available dummy plugs)

Accessories Dummy plug Remark

Fabrikat Type Size Rated voltage


Inside-cone plug-in NKT FPI 2 2 40.5 kV Insulation material silicone rubber,
system according with metal housing
FPI 3 3 40.5 kV
to EN 50181
Pfisterer 2 40.5 kV Insulation material silicone rubber,
Blindstecker with metal housing
3 40.5 kV
4 40.5 kV
Südkabel ISIK 15/25/35 2 12 / 24 / 40.5 kV Insulation material silicone rubber,
with metal housing
ISIK 15/25/35 3 12 / 24 / 40.5 kV
TE Connectivity RPIC-2 2 40.5 kV Insulation material silicone rubber,
with metal housing
RPIC-3 3 40.5 kV

1) Higher values on request

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 35
Standards
Standards, specifications, guidelines

Type of service location Terms


The switchgear can be used as indoor installation according “Make-proof earthing switches“ are earthing switches with
to IEC 61936 (Power installations exceeding 1 kV AC) short-circuit making capacity according to IEC 62271-102.
• Outside lockable electrical service locations at places which
are not accessible to the public. Enclosures of switchgear Dielectric strength
can only be removed with tools • The dielectric strength is verified by testing the switchgear
• In lockable electrical service locations. A lockable ­electrical with rated values of short-duration power-frequency
service location is a place outdoors or indoors that is ­withstand voltage and lightning impulse withstand voltage
reserved exclusively for housing electrical equipment and according to IEC 62271-1.
which is kept under lock and key. Access is restricted to • The rated values are referred to sea level and to normal
authorized personnel and persons who have been properly atmospheric conditions (1013 hPa, 20 °C, 11g/m3 humidity
instructed in electrical engineering. Untrained or according to IEC 60071).
unskilled persons may only enter under the supervision of
The gas insulation permits switchgear installation at
authorized personnel or properly instructed persons.
any ­desired altitude above sea level without the dielectric
strength being adversely affected.

Standards
8DA/B switchgear complies with the relevant standards and
specifications applicable at the time of type tests.
In accordance with the harmonization agreement reached
by the countries of the European Union, their national
­specifications conform to the IEC standard.

IEC standard / EN standard Title


Switchgear 62271-1 High-voltage switchgear and controlgear:
Common specifications for alternating current switchgear and controlgear
62271-200 High-voltage switchgear and controlgear:
AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV
and up to and including 52 kV
Switching ­devices Circuit-breakers 62271-100 High-voltage switchgear and controlgear:
Alternating-current circuit-breakers
Disconnectors and 62271-102 High-voltage switchgear and controlgear:
­earthing switches Alternating current disconnectors and earthing switches
Voltage detecting systems 62271-213 Voltage detecting and indicating system (VDIS)
62271-215 Phase comparator used with VDIS
Surge arresters 60099-4 Surge arresters
Degree of protection 60529 Degrees of protection provided by enclosures (IP code)
62262 Degrees of protection provided by enclosures (IK code)
Insulation 60071 Insulation co-ordination
Instrument transformers 61869-1 Instrument transformers
61869-2 Current transformers
61869-3 Voltage transformers
Insulating gas 62271‑4 Use and handling of SF6 and alternative gases
60376 Specification of technical grade sulphur hexafluoride (SF6) and complemen-
tary gases for use in electrical equipment
60480 Specifications for the re-use of ­sulphur hexafluoride (SF6) and its mixtures in
electrical equipment
Installation 61936-1 Power installations exceeding 1 kV a.c.
Environmental conditions 60721-3-3 Classification of environmental conditions
Operation EN 50110 Operation of electrical installations

36 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Standards
Standards, specifications, guidelines

Current carrying capacity Color of the panel front


• According to IEC 62271‑200 or IEC 62271‑1, the ­rated RAL 7035 Light grey.
­continuous current refers to the following ambient air
­temperatures: Climate and environmental influences
– Maximum of 24-hour mean + 35 °C 8DA/B switchgear is completely enclosed and insensitive to
– Maximum + 40 °C climatic influences.
• The current carrying capacity of the panels and busbars • All medium-voltage devices are installed in gas-tight and
depends on the ambient air temperature outside the bolted switchgear housings made of corrosion-resistant
­enclosure. aluminum alloy and filled with insulating gas
• Live parts are provided with single-pole enclosure
Internal arc classifications • Operating mechanism parts which are functionally
• Protection of operating personnel by means of tests for ­important are made of corrosion-resistant materials
verifying the internal arc classification • Bearings in the operating mechanism are designed as
• Internal arcing tests must be performed in accordance dry-type bearings and do not require lubrication.
with IEC 62271‑200 and IEEE Std C37.20.7™-2007
• Definition of criteria according to IEC: Recycling
– Criterion 1: Correctly secured doors and covers do not The switchgear can be recycled in ecological manner in
open, limited deformations are accepted compliance with existing legislation. Auxiliary devices such
– Criterion 2: No fragmentation of the enclosure, no as short-circuit indicators have to be recycled as electronic
­projection of small parts above 60 g scrap. Batteries have to be recycled professionally. ­Insulating
– Criterion 3: No holes in accessible sides up to a height gas SF6 has to be evacuated professionally as a reusable
of 2 m material and recycled (SF6 must not be released into the
– Criterion 4: No ignition of indicators due to hot gases environment).
– Criterion 5: The enclosure remains connected to its
­earthing point.

Resistance to internal faults


Due to the single-pole enclosure and the gas insulation of the
switchgear and the switching devices, the possibility of faults
in 8DA/B switchgear is a mere fraction of that typical of other
switchgear types:
• There are no effects due to external influences, such as
– Pollution layers
– Humidity
– Small animals and foreign objects
• Maloperation is practically excluded due to logical
arrangement of operating elements
• Short-circuit-proof feeder earthing by means of the
circuit-breaker.
In the unlikely event of a fault within the switchgear housing,
the energy conversion in the case of an internal arc fault is
minor thanks to the gas insulation and the shorter length of
the arc, approximately only ⅓ of the converted energy of an
arc in air insulation.

Resistance to short circuits and earth faults


Two-phase and three-phase short circuits between the
­primary conductors are excluded by the single-pole
­primary enclosure.

Seismic withstand capability (optional)


8DA/B switchgear can be upgraded for regions at risk from
earthquakes.
Detailed information on earthquake qualification and testing
on request.

Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 37
Notes

38 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Smart Infrastructure combines the real and digital worlds
across energy systems, buildings and industries, enhancing
the way people live and work and significantly improving
efficiency and sustainability.

We work together with customers and partners to create


an ecosystem that both intuitively responds to the needs of
people and helps customers achieve their business goals.

It helps our customers to thrive, communities to progress


and supports sustainable development to protect our planet
for the next generation.

siemens.com/smart-infrastructure

Medium-­
voltage
systems

Published by
Siemens AG
Smart Infrastructure
Electrification & Automation
Mozartstrasse 31 C
91052 Erlangen, Germany
For further information, please contact
our Customer Support Center:
Phone: +49 180 524 70 00
Fax: +49 180 524 24 71
E-mail: [email protected]
siemens.com/medium-voltage-switchgear
Article No. SIEA-C10145-00-7600
VO 237889 en KG 11.23 0.0

For the U.S. published by


Siemens Industry Inc.
100 Technology Drive
Alpharetta, GA 30005
United States

Status 11/2023
Subject to changes and errors. The information given in this document only contains general
descriptions and/or performance features which may not always specifically reflect those
described, or which may undergo modification in the course of further development of the
products. The requested performance features are binding only when they are expressly
agreed upon in the concluded contract.
All product designations may be trademarks or other rights of Siemens AG, its affiliated
companies or other companies whose use by third parties for their own purposes could
violate the rights of the respective owner.
© Siemens 2023