MEDIUM-VOLTAGE SWITCHGEAR
Typical uses
(examples):
Industry
R-HA35-132c tif
R-HA3511-015 jpg
R-HA3511-016 jpg
Typical uses
(examples):
Offshore
Traction power
supply
R-HA3511-017 jpg
2 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
ContentsPage
Types 8DA10
Versions 4
Requirements
and 8DB10 Features, Safety
Technology
6
7
up to 40.5 kV Digitalization, condition monitoring
up to 24 kV, Sustainability 10
Dimensions
Typicals, single-busbar switchgear (examples) 19
Typicals, double-busbar switchgear (examples) 20
Typicals, traction power supply switchgear (examples) 23
Design
Panel design, single-busbar switchgear (example) 24
Panel design, double-busbar switchgear (example) 25
Components
Vacuum circuit-breaker 26
Three-position disconnector 28
Current transformers 30
Voltage transformers 31
Panel connection 32
Panel connection (commercially available cable plugs
and bar connections) 34
Standards
Standards, specifications, guidelines 36
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 3
Application
Versions
Example: Version with mechanical gas pressure manometers for feeders and busbar
R-HA3511-024 png
R-HA3511-023 tif
Example: Version with digital gas pressure monitoring for feeders and busbar
R-HA3511-026 tif
8DAB24-SBB-LS-open tif
R-HA3511-025 tif
Single busbar type 8DAB 24 SBB and double busbar type 8DAB 24 DBB
4 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Application
Versions
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 5
Requirements
Features Safety
6 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Requirements
Technology
Modular design
• Replacement of the panel connection housings or
the circuit-breaker possible without interrupting busbar
operation
• Low-voltage compartment removable, plug-in bus wires.
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 7
Digitalization, condition monitoring
Siemens Xcelerator, available monitoring functionalities
Circuit-breaker monitoring
Available monitoring functionalities Continuous monitoring of circuit-breaker functions enables
for gas-insulated switchgear an evaluation of the actual health status of the circuit-breaker,
based on both mechanical and electrical parameters. The
Condition monitoring
evaluation of performed mechanical and electrical switching
Condition monitoring serves to continuously improve the
operations, as well as the monitoring of other components,
resilience, reliability, and availability of maintenance-free,
allows to indicate at an early stage if servicing work is
gas-insulated medium-voltage switchgear with an expected
necessary, or if a suitable replacement switchgear should be
service life of 40 years. These values are based on the design
procured.
and empirical data for switchgear assemblies, as well as on
the intended use of the switchgear under normal service Load flow monitoring
conditions according to IEC 62271-1. Load flow monitoring provides the basis for the relation
To protect the investment (CAPEX) and reduce operational between the electrical utilization and other defined and
expenditures (OPEX), the extension of switchgear functions monitored status values. Knowing the actual utilization, for
with a condition monitoring system is the appropriate example, it is possible to determine how the temperature
way for early indication of irregularities at the switchgear characteristic will develop with increasing electrical utilization,
and its peripheral components. This is the premise for and if this leads to a possible recommended action.
condition-based inspection.
8 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Digitalization, condition monitoring
Digitalization solutions from a single source
SICAM A8000
SICAM Motor
SICAM FCM Control
Condition SIPROTEC 5 Reyrolle 5 UPS P850 plus Unit
Monitoring
Temperature
and Humidity
Partial
Discharge
Gas Density
Circuit-Breaker
Load Flow
SWITCHGEAR LEVEL
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 9
Sustainability
Siemens gas-insulated switchgear (GIS) systems have played Material efficiency: blue GIS products are designed to have
a key role over the last 40 years for a reliable and safe power a very low CO2 footprint. A prime example is SIBushing, a
distribution. The new Siemens blue GIS portfolio reflects our non-conventional instrument transformer that reduces the
commitment to 100% sustainable innovation, which integrates use of raw materials, energy consumption, and landfill waste.
both Clean Air as an insulating medium and an eco-efficient
Energy efficiency: An optimized main current path with a
design that reduces its CO2 footprint throughout the entire
low ohmic resistance reduces the power loss during opera-
life cycle. With a wide range of products covering all the
tion of the switchgear considerably, and thus increases the
needs, our blue GIS will be the core of a sustainable energy
energy efficiency.
transition. The following innovative solutions offer a remark-
able CO2 footprint reduction: Long service life: With the right material selection and an
innovative design, blue GIS have an expected service life of
F-gas-free insulation: Clean Air consists of natural-origin 40 years, thus extending the re-investment cycle and further
gases with a GWP < 1, which means it has virtually no nega- diminishing the CO2 footprint.
tive impact on the environment or climate change during the
Maintenance-free design: No additional maintenance is
entire life cycle. It can even be released into the atmosphere
necessary, and the CO2 footprint can be reduced further by
after reaching its end of life.
avoiding site visits during the operational phase of the
Space efficiency: Like the traditional GIS design, Siemens switchgear.
blue GIS also offer very compact solutions that save valuable
Sustainable services: The CO2 footprint can be diminished
space and additionally decrease the environmental impact of
thanks to services from predictive maintenance to condition
electrical infrastructure installations.
monitoring, remote FAT, CO2 monitoring via NXpower
monitor, the Totally Integrated Power planning tools, and
paperless documentation.
10 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Sustainability
hm
ir &
EcoDesign
b is
Reuse
Use Manufacturing
ur
R
ef
ri n
g& The exact final values depend on the used recycling processes.
R e m a n ufactu
R e c yc li n g
Extraction of
Waste
raw material
Use of environmentally safe materials
At Siemens, we are committed to the development and
The Siemens Environmental Product Declaration (EPD)
production of environmentally friendly and sustainably
adheres to ISO 14021 standards for environmental labels and
produced equipment. This includes avoiding hazardous
declarations. It is based on a comprehensive Life Cycle
substances in our products without compromising their
Assessment (LCA) study conducted in accordance with
benefits for our customers. Please visit the following website*
ISO 14040/44, incorporating Product Category Rules (PCR)
to learn more about how we comply with product-related
specified in EN 50693 for electronic and electrotechnical
environmental regulations like RoHS, REACh and others.
products and systems.
* https://www.siemens.com/global/en/products/energy/ecotransparency/
ecotransparency-downloads.html
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 11
Room planning
Single-busbar switchgear and double busbar switchgear
12 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Room planning
Single-busbar switchgear and double busbar switchgear
Door dimensions
The door dimensions depend on the dimensions of the indi-
vidual panels (see pages 19 to 23).
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 13
Room planning
Transport and packing
Dimensions, weights
14 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Room planning
Classification
Partition class PM
Loss of service continuity category
– Single-busbar switchgear LSC2
– Double-busbar switchgear LSC2A
Internal arc classification
Classification of single-busbar switchgear and double-busbar switchgear according to IEEE Std C37.20.7TM-2017
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 15
Product range
Single-busbar switchgear 8DA10 and 8DAB 24 SBB
Circuit-breaker panel
Three-position
disconnector
Vacuum circuit-breaker
Voltage transformer
without or with
disconnecting function
Current transformer
Capacitive voltage
detecting system
Bus sectionalizer
Busbars
– earthing switch
Surge arrester
Zero-sequence
current transformer
Top-mounted
bus sectionalizer
16 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Product range
Double-busbar switchgear 8DB10 and 8DAB 24 DBB
Circuit-breaker panel
Three-position
disconnector
Vacuum circuit-breaker
Voltage transformer
without or with
disconnecting function
Current transformer
Capacitive voltage
detecting system
Bus sectionalizer
Busbars
– earthing switch
Surge arrester
Zero-sequence
current transformer
Top-mounted
bus sectionalizer
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 17
Product range
Double-busbar switchgear 8DB10 and 8DAB 24 DBB
Bus coupler
Three-position
disconnector
Vacuum circuit-breaker
Voltage transformer
without or with
disconnecting function
Current transformer
Capacitive voltage
detecting system
Busbars
– earthing switch
Top-mounted
bus sectionalizer
18 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Dimensions
Typicals, single-busbar switchgear (examples)
R-HA3511-018 png
high-voltage cables
4 Area for floor openings for
control cables
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 19
Dimensions
Typicals, double-busbar switchgear (examples)
R-HA3511-019 png
20 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Dimensions
Typicals, double-busbar switchgear (examples)
R-HA3511-020 png
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 21
Dimensions
Typicals, double-busbar switchgear (examples)
R-HA3511-021 png
22 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Dimensions
Typicals, traction power supply switchgear (examples)
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 23
Design
Panel design, single-busbar switchgear (example)
• Factory-assembled, type-tested
• S ingle-pole metal enclosure
• Hermetically bolted switchgear
housings made of corrosion-resistant 1
aluminum alloy
• Switchpanel poles arranged one
behind the other 2
Legend for pages 24 and 25:
• Maintenance-free under normal
3
operating conditions according to 1 Low-voltage compartment
IEC 62271-1 4 2 Electronic control board, e.g.
• Degree of protection multifunction protection
3 Operating mechanism and
– IP65 for all high-voltage parts of
interlock for three-position
the primary circuit disconnector, as well as
– IP3XD for the switchgear enclosure 1) 5 mechanical position indicators for
• Vacuum circuit-breaker three-position disconnector and
• Three-position disconnector for circuit-breaker
4 Manometer for gas monitoring of
disconnecting and earthing
R-HA3511-023 tif
feeder gas compartments
• Make-proof earthing by means of the 6
5 Circuit-breaker operating
vacuum circuit-breaker mechanism
• Cable connection with inside-cone 6 Voltage detecting system
plug-in system according to
EN 50181
• Wall-standing or free-standing
arrangement Panel for single-busbar switchgear
• Instrument transformers located
outside the gas compartments
• Low-voltage compartment
removable, plug-in bus wires
• Standardized production Arrangement of gas compartments
processes and certified quality and
environmental management system
according to ISO 9001, ISO 14001
and BS OHSAS 18001.
ANSI design:
Camera system
• Camera system for visual monitor-
ing of the switch positions of the
disconnectors and earthing switches.
UL certification Gas-tight
bushing
Single-busbar panel
24 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Design
Panel design, double-busbar switchgear (example)
pressure manometer.
Bushing
pervious to gas
Double-busbar panel
* Item designation
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 25
Components
Vacuum circuit-breaker
Features
R-HA3511-018 png
• V acuum circuit-breaker according to IEC 62271-100
• Application in hermetically bolted switchgear housings
in conformity with the system
• Vacuum interrupter in gas-filled switchgear housing
• Individual secondary equipment
• A metal bellows is used for gasketless separation between
the gas insulation and the vacuum.
Trip-free mechanism
The vacuum circuit-breaker is fitted with a trip-free
mechanism according to IEC 62271-100. 1
Switching duties and operating mechanisms
The switching duties of the vacuum circuit-breaker are
dependent, among other factors, on its type of operating
mechanism.
5
Motor operating mechanism 2
• Motor-operating stored-energy mechanism
4
– For auto-reclosing (K)
– For synchronization and rapid load transfer (U).
3
Further operating mechanism features
• Operating mechanism located outside the
switchgear enclosure
• Installation behind the control board Circuit-breaker operating mechanism 3AH49 for
single-busbar switchgear, double-busbar switchgear
• Stored-energy spring mechanism for and traction power supply switchgear
10,000 operating cycles
• Optional: Stored-energy spring mechanism for
1 ON pushbutton
30,000 operating cycles. 2 OFF pushbutton
3 Operations counter
Operating mechanism functions 4 Position indicator for circuit-breaker
Motor operating mechanism 5 “Closing spring charged” indicator at
In the case of motor operating mechanism, the closing spring is the operating mechanism
charged by means of a motor and latched in the charged posi-
tion (“spring charged” indication is visible). Closing is effected
either by means of an ON pushbutton or a closing solenoid.
The closing spring is recharged automatically (for auto-reclosing).
Function Class Standard Property of 8DA/B Closing time Closing solenoid < 95 ms
BREAKING M2 IEC 62271-100 10,000 times mechanically Opening time 1st shunt release < 75 ms
without maintenance 2nd shunt release < 65 ms
E2 IEC 62271-100 10,000 times rated continuous Undervoltage release < 65 ms
current without maintenance Arcing time at 50 Hz < 15 ms
50 times short-circuit breaking at 60 Hz < 12 ms
current without maintenance Break time at 50 Hz 1st shunt release < 90 ms
C2 IEC 62271-100 Very low probability of restrikes 2nd shunt release < 80 ms
Undervoltage release < 80 ms
Dead time 300 ms
Total charging time < 15 s
26 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Vacuum circuit-breaker
HA35-2678b_EN eps
requirement to be satisfied.
Closing solenoid
• Type 3AY15 10 (Y9*)
• For electrical closing.
Shunt releases
• Types:
– Standard: 3AY15 10 (Y1*)
– Option: 3AX11 01 (Y2*), with energy store
• Tripping by protection relay or electrical actuation.
Undervoltage release
• Type 3AX11 03 (Y7*)
• Comprising:
– Energy store and unlatching mechanism
– Electromagnetic system, which is permanently connected
to voltage while the vacuum circuit-breaker is closed;
tripping is initiated when this voltage drops
• Connection to voltage transformers possible. Examples
Electrical data (curve 1)
Anti-pumping Rated short-circuit breaking current 25 kA
• F
unction: If constant CLOSE and OPEN commands are Rated continuous current 1250 A
present at the vacuum circuit-breaker at the same time, Electrical data (curve 2)
the vacuum circuit-breaker will return to the open Rated short-circuit breaking current 31.5 kA
position a
fter closing. It remains in this position until a Rated continuous current 2000 A
new CLOSE command is given. In this manner, continuous Electrical data (curve 3)
closing and opening (= pumping) is avoided. Rated short-circuit breaking current 40 kA
Rated continuous current 2500 A
Circuit-breaker tripping signal
Rated operating sequences
• F
or electrical signaling (as pulse > 10 ms), e.g. to remote Rapid load transfer (U): O – t – CO – t’ – CO (t = 0.3 s, t’ = 3 min)
control systems, in the case of automatic tripping Auto-reclosing (K): O – t – CO – t’ – CO (t = 0.3 s, t’ = 3 min)
(e.g. protection) Auto-reclosing (K): O – t – CO – t’ – CO (t = 0.3 s, t’ = 15 s)
• Via limit switch (S6*) and cutout switch (S7*).
O = OPEN operation
Varistor module CO = CLOSE operation with subsequent OPEN operation at the shortest
internal close-open time of the vacuum circuit-breaker
• T
o limit overvoltages to approx. 500 V for protection
devices (when inductive components are mounted in
the vacuum circuit-breaker) Possible release combinations
• For auxiliary voltages ≥ 60 V DC.
Release 1 2 3 4 5
Auxiliary switch
1st shunt release type 3AY15 10 • • • • •
• Type 3SV9 (S1*) 2nd shunt release type 3AX11 01 – • • – •
• Standard: Up to 22 NO + 22 NC. – • – –
3rd shunt release type 3AX11 01 –
Position switch Undervoltage release type 3AX11 03 – – – • •
• Type 3SE4 (S4*)
• For signaling “closing spring charged“.
Mechanical interlock
• Mechanical interlocking to the three-position disconnector
• During operation of the three-position disconnector,
the vacuum circuit-breaker cannot be operated.
* Item designation
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 27
Components
Three-position disconnector
Switch positions
• CLOSED, OPEN, EARTHED or READY-TO-EARTH
Feeder OPEN
• CLOSED: Contact blades connected with the busbar:
Main circuit closed between busbar and circuit-breaker
• OPEN: Main circuit open between busbar and circuit-
breaker: Test voltages for isolating distances are withstood
• READY-TO-EARTH: Contact blades connected with the
earthing contact
• EARTHED: Feeder earthed and short-circuited by closing
the circuit-breaker.
Operating mechanism
• Only permissible operations possible due to logical Feeder CLOSED
mechanical interlocks
• Mechanically coupled position indicator
• Separate operating shafts for the “DISCONNECTING”,
“EARTHING” and “READY-TO-EARTH” functions
• With manual operating mechanism
• Option: With motor operating mechanism
Feeder READY-TO-EARTH
28 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Three-position disconnector
completed
• Circuit-breaker cannot be closed until
the control gate is in neutral position
Feeder OPEN
again
• Option: Switchgear interlocking
system with electromechanical in-
terlocks ( mechanical interlocking for
manual operation remains).
Feeder READY-TO-EARTH
Feeder EARTHED
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 29
Components
Current transformers
• Inductive type
• Certifiable
• Climate-independent
• Secondary connection by
means of a terminal strip in
the low-voltage compartment
of the panel
• Cast-resin insulated.
Installation
• A
rranged outside the primary
enclosure (switchgear housing).
B Current transformer
in bus sectionalizer and bus coupler
(type 4MC4_40)
C Feeder current transformer
(type 4MC4_90)
D Feeder current transformer
(type 4MC4_10)
E Busbar current transformer
(type 4MC4_40)
Option:
A Feeder current transformer
between circuit-breaker and
three-position disconnector at the
busbar (type 4MC4_90)
30 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Voltage transformers
Installation
• Arranged outside the primary
enclosure (switchgear housing).
Mounting locations
• On the busbar
• At the panel connection housing.
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 31
Components
Panel connection
Version 1 Version 2 Version 3 Version 4
Solid-
Solid-
insulated
insulated
4MT7, bar
S2 S3 S2 S3 bar S2 S3
4MT3 connec-
connection
tion up to
up to 2500 A
3150 A
1 1 1 1 4
2 5
3 6
2 4
3 1 3
1 2 1 4
2 1 2 2
1 1 2 3
2 1 3 1
1 1 3 2
2 1 4 1
1 1 1 1 1
1 1 2 1
1 1 1 1
2 1
1 1 1
1
Legend: Features
1 Panel connection housing • Inside-cone plug-in system for plug sizes 2, 3 and 4 according to EN 50181
2 Subframe
h Connection height of panel
• Connection of several cables with different plug sizes possible per phase
connection versions • Connection of solid-insulated or gas-insulated bar possible
• Connection of 4MT3/4MT7 voltage transformer plugged in at the panel connection
housing versions 3 and 7
Note:
The 8DAB 24 product range
• Connection of 4MU3 voltage transformer via plug size 2 at the panel connection housing
may contain restrictions. • For rated continuous currents up to 3150 A.
32 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Panel connection
4MT7, Test
Solid-insulated
4MU3, socket,
S2 S3 S4 bar c onnection S2 S3
switch- switch-
up to 2500 A
able able
1 1 1 1
1 1 2 1
2 1 1 1
1 1 2 1
1 1 1 1 1 1
2 3 1 1)
2 1 4 1 1)
3 1 1)
2 1 1 1)
1 2 1 1)
2 2 1 1)
1 3 1 1)
1 1 1) 1
1 1 1) 1
1 1 1) 1
2 1 1) 1
3 1 1) 1
1 1 1) 1
2 1 1) 1
1 1 1 1) 1
1 2 1 1) 1
Panel connection height h [mm]
1. Single-busbar switchgear, traction power supply switchgear
2. Double-busbar switchgear
3. Switchgear versions with higher subframe
1. 92 294 105
2. 108 94 –
3. 312 514 325
Surge arresters
• Pluggable via inside-cone plug-in system size 2 or 3 according to EN 50181.
Note:
The 8DAB 24 product range
1) Version with feeder voltage transformer 4MU3
may contain restrictions.
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 33
Components
Panel connection (commercially available cable plugs and bar connections)
34 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Components
Panel connection (commercially available cable plugs and bar connections)
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 35
Standards
Standards, specifications, guidelines
Standards
8DA/B switchgear complies with the relevant standards and
specifications applicable at the time of type tests.
In accordance with the harmonization agreement reached
by the countries of the European Union, their national
specifications conform to the IEC standard.
36 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Standards
Standards, specifications, guidelines
Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023 37
Notes
38 Medium-Voltage Switchgear Types 8DA10 and 8DB10 up to 40,5 kV and 8DAB 24 blue GIS up to 24 kV, Gas-Insulated · Siemens HA 35.11 · 2023
Smart Infrastructure combines the real and digital worlds
across energy systems, buildings and industries, enhancing
the way people live and work and significantly improving
efficiency and sustainability.
siemens.com/smart-infrastructure
Medium-
voltage
systems
Published by
Siemens AG
Smart Infrastructure
Electrification & Automation
Mozartstrasse 31 C
91052 Erlangen, Germany
For further information, please contact
our Customer Support Center:
Phone: +49 180 524 70 00
Fax: +49 180 524 24 71
E-mail: [email protected]
siemens.com/medium-voltage-switchgear
Article No. SIEA-C10145-00-7600
VO 237889 en KG 11.23 0.0
Status 11/2023
Subject to changes and errors. The information given in this document only contains general
descriptions and/or performance features which may not always specifically reflect those
described, or which may undergo modification in the course of further development of the
products. The requested performance features are binding only when they are expressly
agreed upon in the concluded contract.
All product designations may be trademarks or other rights of Siemens AG, its affiliated
companies or other companies whose use by third parties for their own purposes could
violate the rights of the respective owner.