Design and Use of MV Current Limiting Fuses PDF
Design and Use of MV Current Limiting Fuses PDF
Design and Use of MV Current Limiting Fuses PDF
Cahier
technique
no. 128
Design and use of MV
current-limiting fuses
O. Bouilliez
J.C. Perez Quesada
"Cahiers Techniques" is a collection of documents intended for engineers
and technicians, people in the industry who are looking for more in-depth
information in order to complement that given in product catalogues.
Foreword
The author disclaims all responsibility subsequent to incorrect use of
information or diagrams reproduced in this document, and cannot be held
responsible for any errors or oversights, or for the consequences of using
information and diagrams contained in this document.
Olivier BOUILLIEZ
Table of contents
1 Basic characteristics 1.1 Reminder p. 4
1.2 UN rated voltage p. 4
1.3 IN rated current p. 5
1.4 I3 minimum breaking current p. 5
1.5 I2 current providing the conditions affecting maximum
arc energy p. 5
1.6 I1 or maximum breaking capacity p. 6
1.7 Time/current characteristic p. 6
1.8 Limited cut-off current p. 7
1.9 Energy dissipated p. 8
1.10 Power dissipated p. 8
2 The elements of a fuse link 2.1 End caps p. 9
2.2 The tubular case p. 10
2.3 Core p. 11
2.4 Fuse element p. 11
2.5 Extinguishing agent p. 13
2.6 Striker p. 13
3 Application 3.1 General p. 14
3.2 Protecting transformers p. 14
3.3 Motor protection p. 16
3.4 Protecting capacitor banks p. 18
3.5 Summary p. 21
4 Appendices 4.1 Appendix 1: Cold resistance of FusarcCF fuses p. 23
4.2 Appendix 2: Time/current characteristics in the FusarcCF
range of fuses (Merlin Gerin) p. 24
4.3 Appendix 3: Using fuses in parallel p. 26
1.1 Reminder
Standard IEC 60282-1 defines three current- less than approximately four times the rated
limiting fuse categories based on the type of current of the fuse).
application in which the fuse is to be used:
Integral cut-out fuse
Associated fuse Recommended in particular for applications in
For applications in which the improbability of low which overcurrents may be as low as the
fault current values can be proven, either by minimum fusing current and when the fuse must
means of calculation or on the basis of past be derated in order to be used in a case.
experience. However, it must be ensured that
the minimum rated breaking current of the fuse This Cahier Technique is concerned primarily
link is less than the minimum short-circuit current with associated fuses, but also discusses
that may appear upstream of the low-voltage concepts that are applicable to all fuse
safety device. categories.
The basic definitions below can form the basis of
General purpose fuse a fuse dictionary that will facilitate discussions on
If experience or calculation indicates that there the subject between fuse manufacturers,
may be very low overcurrents on the line (i.e. installation designers and users.
Single-phase operation
Most fuses are designed for use on a three-
UN = 3.6 - 7.2 - 12 - 17.5 - 24 - 36 phase system. In this case, the recovery voltage
applied to them following a short-circuit is equal
to:
Fig. 1: list of preferential values (kV) defined by Uline
standardization bodies. x 1.5
3
The coefficient 1.5 is due to the phase-shifting of
For reasons relating to breaking, it is not the current zero points. In a three-phase system,
possible to use a fuse with a voltage rating UN this causes the neutral point to slip when the first
on a line where Uline is greater than UN. fuse blows.
Inevitably, the reverse is sometimes possible up In single-phase operation (see fig. 2 ), a fuse
to values of UN greater than that of the line. This with a rated voltage of UN is therefore tested at:
is possible thanks to certain special design
1.5
features that limit the level of the breaking UN x = 0.87 UN
overvoltage Up and enable the manufacturer 3
UN
1.5UN/e
/3
2
UN/e
/e
UN
UN/e
a
5
b
0 1 2 3
= make angle
(rd)
I
60
40 250 A
30 B 200 A
Prospective wave 160 A
I 20
(Irms = A) 15 125 A
100 A
B 10
Limited wave 8
Cut-off current 6
(peak value) 4
3
2 A
t 1 2 4 6 10 20 40 60 Isc
Fig. 7: value Ip of the limited cut-off current as a function of the prospective current.
Based on the example of a Fusarc-CF, an these elements are subject enables us to identify
examination of the various composite elements the possible choices available to the
(see fig. 8 ) and the types of stress to which manufacturer.
1. contacts 2
2. case 3
3. core
4. fuse elements 4
5. extinguishing agent
6. striker 5
6 5 4
3 2 1
2.3 Core
Serving as a spindle around which the fuse
element is coiled, the core simply supports the
fuse. Some types of fuse do not have a core.
Made of ceramic or similar material, the nature of
the core must be as similar as possible to the
extinguishing agent. It is usually cylindrical in
shape and ribbed (see fig. 10 ).
Often installed at its center, the striker, with its
control wire, is also isolated from the fuse
elements.
t (s) t (s)
P = 10
100 100
P = 20
10 10
P=5
1 1 e = 0.9
e = 0.7
0.1 0,1
e = 0.5
0.01 0.01
102 103 4
10 I (A) 102
103 104 I (A)
Effect of p (e = 0.7) Effect of e (p = 10)
e p
2.6 Striker
This is a mechanical component that indicates tripping but must ensure tripping without
that the fuse assembly has blown and is able to interfering with the breaking process.
supply a certain amount of energy stored in a Striker types are classified in several
spring in order to activate a breaking device. standardized categories (low, medium and high)
Fuses with strikers are therefore designed for according to the energy they are capable of
fuse combination units. supplying.
The striker actuator is always a resistive wire Dangerous temperatures (> 100C on the
(tungsten, Ni-Cr, etc.) installed in parallel to the contacts) for a breaking device combined with
fuse elements. At IN, an extremely low current fuses and/or fuses themselves can be invoked
flows through it. However, as soon as an by prolonged overcurrents. To suppress this risk,
overcurrent flows through the fuse assembly, this recent developments have enabled a thermal trip
current increases significantly until it melts the to be incorporated into a traditional (spring-loaded
wire and releases the spring-loaded striker. - medium type) striker system (see fig. 14 ).
Extreme care should be taken when designing This trip also acts on the striker, which invokes
the wires, as they must not cause premature the opening of the device.
A B C D E F
Fig. 14: example of a thermal trip unit incorporated into the striker system of all Merlin Gerin brand fuses.
A. striker released
B. striker in normal untripped position
C. spring
D. thermal trip for striker
E. electrical trip for striker
F. main fuse element.
This section discusses the regulations motors and capacitors. In these assemblies, the
determining the selection of the rating of the fuse fuse and the connecting device must be
link for a fuse used in good ventilation matched and, in addition to the ventilation
conditions. These rules can be used to draw up conditions, manufacturer recommendations for
usage tables for fuse ranges. the combined or associated unit must be taken
When connected to or combined with a into account when selecting the rating of the
connecting device, the fuse can also be used to fuse link.
protect various loads, in particular transformers,
3.1 General
The regulations to be observed for UN and I1 must also be observed. These are addressed in
were discussed in the first section. These subsequent sub-sections, in which the
characteristics, which are specific to the fuse, regulations are given for fuses with standard
must be greater than or equal to the line voltage ventilation. If the fuses are housed inside cases
Uline and its short-circuit current Isc. These basic with very poor ventilation, in addition to the
considerations determine the characteristics of regulations below, it must also be ensured that
the installation and in some cases exclude the any temperature rises during continuous
use of certain types of fuse. operation do not exceed standardized values. If
However, other regulations associated with the necessary, the fuse links should be derated.
specific characteristics of the protected load
0
0 0.1 0.2 0.3 0.4 0.6 0.8 1 1.1 t (s)
Fig. 17: table summarizing the possibilities of the Fusarc-CF (Merlin Gerin) range, with a short-circuit voltage of 5 %.
Is (A)
10 100 1000 10000
100 100
2 x 250 A
2 x 200 A
250 A
III
Ts (s)
Ts (s)
200 A
10 D 10
50 A
160 A
63 A
125 A
P (kW) 1650 kW 80 A
3 100 A
100 1000 10000
C
1 2 1000
10 10
11 kV x 12
10 kV x 10
6.6 kV
I II x8
In (A)
In (A)
6 kV x6
5.5 kV
100 x4 100
A B
4.16 kV 167 A
3.3 kV
3 kV
1000 1000
100 1000 10000 10 100 1000 10000
P (kW) Is (A)
Fig. 19: chart illustrating the time/current characteristics of fuses in the Fusarc-CF (source Merlin-Gerin) range.
R2
D
L
C
R
I
L1 L2 L3 Ln
R1 R2 R3 Rn
t
C1 C2 C3 Cn
2 C
v calculate IT = U x E
3 LE
LE L
v calculate T = 2 x
CE
v record the point (IT, T) on the time/current R
characteristics,
v if necessary, select a different rating, calculate
a new RE value and start the verification process
again.
If the steps are identical, a single calculation will
suffice. However, if they are not, you must
investigate several scenarios according to the L1 L2 L3
operating mode of the bank.
c Practical example for a multiple step capacitor
bank
3 banks: C1 C2 C3
UN = 10 kV
IN bank = 35 A
Fig. 23: diagram of a bank with three capacitor steps
Isc = 40 kA (cos = 0.1) protected by a single fuse.
Cables = 5 rn or Li = 2 H
3.5 Summary
The table in figure 24 contains a summary of the This diagram clearly shows the contradictory
requirements of the different types of fuse requirements of each type of load protected. It
according to the type of load. also clearly illustrates the relative insignificance
These specifications can be used to plot the of the IN value of a fuse when it is taken alone as
ideal time/current characteristic for a fuse a selection criterion (as is unfortunately too often
according to its use (see fig. 25 ). the case).
a b c
1 IN 0 to 100 A 1 1
t (s)
10 000
8
6
5
4
3
2
31.5 A
6363A A
100 A
125 A
160 A
200 A
250 A
1 000
6.3 A
10 A
16 A
20 A
25 A
40 A
50 A
80 A
4A
8
6
5
4
3
2
100
8
6
5
4
3
2
10
8
6
5
4
3
2
1
8
6
5
4
3
2
0.1
8
6 C
5 B
4
A
3
2
0.01
10 2 3 4 5 6 8 102 2 3 4 5 6 8 103 2 3 4 5 6 8 104 I (A)
1000
50 A
63 A
80 A
8
6
5
4
3
2
100
8
6
5
4
3
2
10
8
6
5
4
3
2
1
8
6
5
4
3
2
0.1
8
6
5
4
3
2
0.01
10 2 3 4 5 6 8 102 2 3 4 5 6 8 103 2 3 4 5 6 8 104 I (A)
100
9
8
7
6 2x250A
5 B 2x200A
44
4 250A
3 200A
A 160A
22 125A
2
100A
10
9
8
7
6
5
4
2
6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 Isc kA rms
1 10
Fig. 27: current limitation curves according to rating (Fusarc-CF, Merlin Gerin brand).
01-03