IDEC Relays and Timers RTE Instruction Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

B-766(5) CONTACT RATINGS

Contact Configuration 2 Form C, DPDT (Delay output)


INSTRUCTION SHEET Allowable Voltage / Allowable Current 240V AC, 30V DC / 10A
Maximum Permissible Operating Frequency 1800 cycles per hour
ALL MULTI-TIMERS RTE-P1, -P2, -B1, -B2 Rated Load Resistive 10A 240V AC, 30V DC
Confirm that the delivered product is what you have ordered. Read this instruction Inductive 7A 240V AC, 30V DC
sheet to make sure of correct operation. Make sure that the instruction sheet is Horse Power Rating 1/6 HP 120V AC, 1/3 HP 240V AC
kept by the end user.
Conditional Short Circuit Fuse 10A, 240V
TIME RANGE Determined by Time Range Selector and Dial Selector Life Electrical 500,000 op. minimum (Resistive)
Dial Mechanical 50,000,000 op. minimum
0-1 0-3 0-10 0-30 0-60
Range
s 0.1sec - 1sec 0.1sec - 3sec 0.2sec - 10sec 0.6sec - 30sec 1.2sec - 60sec TEMPERATURE DERATING CURVES
min 1.2sec - 1min 3.6sec - 30min 12sec - 10min 36sec - 30min 1.2min - 60min Mounting A
10A
h 1.2min - 1hr 3.6min - 3hr 12min - 10hr 36min - 30hr 1.2hr - 60hr

Current
Output
10h 12min - 10hr 36min - 30hr 2hr - 100hr 6hr - 300hr 12hr - 600hr 7A
Mounting A
(hr: hours) Derating Curve
GENERAL SPECIFICATIONS
50℃ 65℃ 3
Operation System Solid-state CMOS circuit Mounting B
Ambient Temperature
Operation Type Multi-Mode
Time Range 0.1sec to 600hours 1 2
7A
Pollution Degree 2 (IE60664-1)

Current
Output
Over voltage category Ⅲ (IE60664-1) 5A ①Operation Mode
Mounting B Selector
Rated Operational AF20 100-240V AC(50/60Hz) Derating Curve
Voltage AD24 24V AC(50/60Hz)/24V DC ②Scale Selector
50℃ 65℃
D12 12V DC ③Time Range
Ambient Temperature Selector
Voltage Tolerance AF20 85-264V AC(50/60Hz)
AD24 20.4-26.4V AC(50/60Hz)/21.6-26.4V DC SWITCH SETTING
D12 10.8-13.2V DC (1) Turn the selectors securely using a flat screwdriver 4mm wide maximum.
Input off Voltage Rated Voltage ×10% minimum Note that incomplete setting may cause malfunction. The letter should be
Ambient Operating -20 to +65℃ (without freezing) centered in the display window. Do not turn the selectors beyond the limits.
(2) Since changing the setting during timer operation may cause
Temperature
malfunction, turn power off before changing the setting.
Ambient Storage and -30 to +75℃ (without freezing)
Transport Temperature DIMENSIONS RTE-P1, -P2 RTE-B1, -B2
36.0 77.9 74.9
Relative Humidity 35 to 85%RH (without condensation)
13.7 13.7
Atmospheric Pressure 80kPa to 110kPa (Operating)
70kPa to 110kPa (Transport)
Reset Time 100msec maximum
40.0

Repeat Error ±0.2%, ±20msec*


Voltage Error ±0.2%, ±20msec* (UNIT: mm)
Temperature Error ±0.5%, ±20msec*
Setting Error ±10% maximum Safety Precautions
Insulation Resistance 100MΩ minimum (500V DC) Special expertise is required to use the Electronic Timer.
Dielectric Strength Between power and output terminals : 2000V AC, 1 minute ・All Electronic Timers are manufactured under IDEC's rigorous quality control
Between contacts of different poles : 2000V AC, 1 minute system, but users must add a backup or fail safe provision to the
Between contacts of the same pole : 1000V AC, 1 minute control system using the Electronic Timer in applications where heavy
damage or personal injury may be caused in case the Electronic Timer
Vibration Resistance 10 to 55Hz amplitude 0.5mm, 2hours in each of 3 axis should fail.
Shock Resistance Operating extremes: 98m/sec2 (10G) ・Install the Electronic Timer according to instructions described in this
Damage limits: 490m/sec2 (50G) instruction sheet and the catalog.
3 times in each of 3 axis ・Make sure that the operating conditions are as described in the catalog.
Degree of Protection IP40 (enclosure), IP20 (socket) (IEC60529) If you are uncertain about the specifications, contact IDEC in advance.
・In this instruction sheet, safety precautions are categorized in order of
Power TYPE RTE-P1, -B1 RTE-P2, -B2
importance to Warning and Caution.
Consum- AF20 120V AC/60Hz 6.1VA 6.2VA
ption Warning notices are used to emphasize that improper
(Approx.)
240V AC/60Hz 9.4VA 9.8VA Warning operation may cause sever personal injury or death.
AD24(AC/DC) 2.7VA/1.3W 2.8VA/1.3W
・Turn power off to the Electronic timer before starting installation, removal,
D12 1.5W 1.5W wiring, maintenance, and inspection on the Electronic Timer.
Mounting Position Free Failure to turn power off may cause electrical shocks or fire hazard.
Dimensions RTE-P1, P2 40H×36W×77.9D mm ・Do not use the Electronic Timer for an emergency stop circuit or interlocking
RTE-B1, B2 40H×36W×74.9D mm circuit. If the Electronic Timer should fail, a machine disorder, breakdown, or
Weight (Approx.) 90g accident may occur.
* For the value of the error against a preset time, whichever the largest applies. Caution notices are used where inattention might cause
Caution personal injury or damage to equipment.
APPLICABLE STANDARDS
Safety standard UL60947-1, UL60947-4-1, CSA C22.2 No.60947-1-13, ・The Electronic Timer is designed for installation in equipment.
CSA C22.2 No.60947-4-1-14, IEC61812-1, EN61812-1 Do not install the Electronic Timer outside equipment.
EMC IEC61812-1, EN61812-1 ・Install the Electronic Timer in environments described in this instruction
sheet and the catalog. If the Electronic Timer is used in places where the
Electrostatic Discharge IEC61000-4-2, EN61000-4-2 Electronic Timer is subjected to high-temperature, high-humidity,
Radiated Radio-Frequency Electromagnetic Field IEC61000-4-3, EN61000-4-3 condensation, corrosive gases, excessive vibrations, and excessive
Electrical Fast Transient/Burst IEC61000-4-4, EN61000-4-4 shocks, then electrical shocks, fire hazard, or malfunction will result.
Surges IEC61000-4-5, EN61000-4-5 ・Use an IEC60127-approved fuse and circuit breaker on the power and
Conducted Radio-Frequency IEC61000-4-6, EN61000-4-6 output line outside the Electronic Timer.
・Do not disassemble, repair, or modify the Electronic Timer.
Voltage Dips IEC61000-4-11, EN61000-4-11 ・When disposing of the Electronic Timer, do so as an industrial waste.
Voltage Interruptions IEC61000-4-11, EN61000-4-11
Radiated and Conducted Emission CISPR 11, EN55011
TYPES
RTE-P1AF20 Power Voltage
AF20: 100 to 240V AC(50/60Hz) http://www.idec.com
AD24: 24V AC(50/60Hz)/24V DC
D12: 12V DC 1175 Elko Drive Sunnyvale, CA94089, USA
Connection type Operation Mode Manufacturer, IDEC CORP.
P: Pin 1: No Control Signal 2: Control Signal 2-6-64 Nishimiyahara Yodogawa-ku, Osaka 532-0004, Japan
B: Blade A: ON Delay A: ON Delay EU Authorized Representative: APEM SAS
B: Interval ON B: Flicker 55, Avenue Edouard Herriot BP1, 82303 Caussade Cedex, France
C: Flicker C: Flicker ON
D: Flicker ON D: Signal ON/OFF Delay UK Authorized Representative: APEM COMPONENTS LIMITED
E: Signal OFF Delay Drakes Drive, Long Crendon, Buckinghamshire, HP18 9BA, UK
F: One-Shot 2021.04
OPERATION CHART
RTE-P1, -B1
A: ON-Delay 1 (power start) B: Interval (power start)
Set timer for desired delay, apply power to coil. Contacts transfer after preset Set timer for desired delay, apply power to coil. Contacts transfer immediately, and
time has elapsed, and remain in transferred position until timer is reset. Reset return to original position after preset time has elapsed. Reset occurs with removal
occurs with removal of power. of power.
Item Terminal No. Operation Item Terminal No. Operation
(1)2-7 (1)2-7
Power (2)A-B Power (2)A-B
(1)1-4, 5 - 8 (1)1-4,5-8
(NC) (NC)
Delayed (2)1-7, 3 - 9 Delayed (2)1-7,3-9
Contact (1)1-3, 6 - 8 Contact (1)1-3,6-8
(NO) (NO)
(2)4-7, 6 - 9 (2)4-7,6-9

PWR PWR
Indicator Indicator
OUT OUT

Set Time T Set Time T

C: Cycle 1 (power start, OFF first) D: Cycle 3 (power start, ON first)


Set timer for desired delay, apply power to coil. First transfer of contacts occurs Functions in same manner as Mode C, with the exception that first transfer of
after preset delay has elapsed, after the next elapse of preset delay contacts return contacts occurs as soon as power is applied. The ratio is 1:1. Time On = Time Off
to original position. The timer now cycles between on and off as long as power
is applied (duty ratio 1:1).
Item Terminal No. Operation Item Terminal No. Operation
(1)2-7 (1)2-7
Power (2)A-B Power (2)A-B
(1)1-4, 5 - 8 (1)1-4,5-8
(NC) (NC)
Delayed (2)1-7, 3 - 9 Delayed (2)1-7,3-9
Contact (1)1-3, 6 - 8 Contact (1)1-3,6-8
(NO) (NO)
(2)4-7, 6 - 9 (2)4-7,6-9

PWR PWR
Indicator Indicator
OUT OUT

Set Time T T Set Time T T

RTE-P2, -B2
A: ON-Delay 2 (signal start) B: Cycle 2 (signal start, OFF first)
When a preset time has elapsed after the start input turned on while power is on, When the start input turns on while power is on, the output oscillates at a preset
the NO output contact goes on. cycle (duty ratio 1:1), starting while the NO contact off.
Item Terminal No. Operation Item Terminal No. Operation
(A)2-10 (A)2-10
Power (B)A-B Power (B)A-B
(A)5-6 (A)5-6
Start (B)2-5 Start (B)2-5
(A)1-4, 8 - 1 1 (A)1-4,8-11
(NC) (NC)
Delayed (B)1-7, 3 - 9 Delayed (B)1-7,3-9
Contact (A)1-3, 9 - 1 1 Contact (A)1-3,9-11
(NO) (NO)
(B)4-7, 6 - 9 (B)4-7,6-9

PWR PWR
Indicator Indicator
OUT OUT

Set Time T Set Time T T T T T T T T T Ta

C: Cycle 4 (signal start, ON first) D: Signal ON/OFF-Delay


When the start input turns on while power is on, the NO contact goes on. The When the start input turns on while power is on, the NO output contact goes on.
output oscillates at a preset cycle (duty ratio 1:1). When a preset time has elapsed while the start input remains on, the output contact
goes off. When the start input turns off, the NO contact goes on again. When a
preset time has elapsed after the start input turned off, the NO contact goes off.
Item Terminal No. Operation Item Terminal No. Operation
(A)2-10 (A)2-10
Power (B)A-B Power (B)A-B
(A)5-6 (A)5-6
Start (B)2-5 Start (B)2-5
(A)1-4, 8 - 1 1 (A)1-4,8-11
(NC) (NC)
Delayed (B)1-7, 3 - 9 Delayed (B)1-7,3-9
Contact (A)1-3, 9 - 1 1 Contact (A)1-3,9-11
(NO) (NO)
(B)4-7, 6 - 9 (B)4-7,6-9

PWR PWR
Indicator Indicator
OUT OUT

Set Time T T T T T T T T Ta Set Time T T Ta T T Ta

E: Signal OFF-Delay F: One-Shot(signal start)


When power is turned on while the start input is on, the NO output contact goes When the start input turns on while power is on, the NO output contact goes on.
on. When a preset time has elapsed after the start input turned off, the NO output When a preset time has elapsed, the NO output contact goes off.
contact goes off.
Item Terminal No. Operation Item Terminal No. Operation
(A)2-10 (A)2-10
Power (B)A-B Power (B)A-B
(A)5-6 (A)5-6
Start (B)2-5 Start (B)2-5
(A)1-4, 8 - 1 1 (A)1-4,8-11
(NC) (NC)
Delayed (B)1-7, 3 - 9 Delayed (B)1-7,3-9
Contact (A)1-3, 9 - 1 1 Contact (A)1-3,9-11
(NO) (NO)
(B)4-7, 6 - 9 (B)4-7,6-9

PWR PWR
Indicator Indicator
OUT OUT

Set Time T Ta T Ta Set Time T Ta

Note : T=Set Time, Ta=Shorter than set time, (1): RTE-P1, (2): RTE-B1, (A): RTE-P2, (B): RTE-B2

INTERNAL CONNECTIONS CAUTION: ATTENTION:


RTE-P2: Do not apply voltage to terminals #5, #6 and #7. RTE-P2: Ne pas mettre les terminaux 5, 6 et 7 sous tension.
RTE-B1, -B2: Do not apply voltage to terminals #2, #5 and #8. RTE-B1, -B2: Ne pas mettre les terminaux 2, 5 et 8 sous tension.
RTE-P1 RTE-P2 RTE-B1 RTE-B2 NOTE: RTE series are UL Listed when uesd in combination with following IDEC's sockets:
external external
control start control start RTE-P1: SR2P-06* pin type socket.
signal signal RTE-P2: SR3P-05* pin type socket.
4 5 5 6 7
1 2 3 1 2 3 RTE-B1, -B2: SR3B-05* blade type socket. (*-May be followed by A,B,C or U)
3 6 4 8 4 5 6 4 5 6 The socket to be used with these timers are rated:
3 9
2 7 7 8 9 7 8 9 -Conductor Temperature Rating 60℃min.,
1 8
2
1 11
10 -Use Copper conductors only, solid 12AWG max(3.5mm2max)
-Terminal Torque 9 to 11.5 lb-in(1.0 to 1.3 N.m)
A B A B

(~/+) (~/-) (~/+) (~/-) (~/+) (~/-) (~/+) (~/-) UL Ambient Temperature: 0 to 40℃.