Almig Air Control P Service Manual
Almig Air Control P Service Manual
Almig Air Control P Service Manual
&RQWURO
AC P
1 SAFETY MESSAGE 1
AIRCONTROL P
Note:
All information provided corresponds with the current state of development (dated October 15, 2012) Changes may occur
at any time without notice. Printing errors excepted. This document supersedes all previous versions.
Content
1 Safety message
The ALMiG AirControl P is equipped with a colour graphic display with touch user interface.
1. Commissioning, parametrisation and maintenance of the control may only be performed by trained
qualified personnel.
2. Ambient conditions for storing:
Ambient temperature range (storage) -25 .. 75°C
humidity (storage) max. 90%; no condensation
3. Ambient condition during operation:
Ambient temperature range (operation) -5 .. 55°C
humidity (operation) max. 90%; no condensation
4. ALMiG reserves the right of changes, additions or improvements on this product (hardware and
software). Hence, no obligation to update any already delivered devices.
5. Display: The life of the display depends strongly on the environmental conditions. Protect the
controller from direct sunlight and high temperatures in order to benefit from the high quality of the
display as long as possible!
2.1 Function
Fig. 1: ALMiG AirControl P. Actual design of the membrane keypad may differ from this image.
The AirControl Premium is an intelligent compressor control system with flexible expansion options.
It can be used for oil-lubricated screw compressors with fixed speed and inverter machines. With a plug-
in/expansion module that expands the input / output level it is also possible to control Lento type compressors
(oil-free).
In addition, the ACP has a primary load functionality to evenly utilise up to five compressors (ACP as LLC
master with up to 4 slaves).
All settings can be adjusted using the graphical interface in the code-protected menu system. The basic
display provides a quick overview of the system type and condition.
Additional information such as flow charts and summaries of all the pressure and temperature values can be
reached quickly with a single tap.
40 - Analogue output 1
At start-up, the controller displays for about three seconds, a splash screen as shown in Illustration 3. The
display will automatically switch to the basic display.
The control unit has a solution of 480x272 on a resistive coloured touch screen. It features the necessary
robustness for industrial use and is comfortable to use. A light tap of the respective control element - with a
finger or stylus - is enough to perform the desired input. A glove operation is also possible.
Illustration 4: Basic display (Note: This illustration comprises a combination of symbols for illustrative purposes, which in
a real system is not possible).
If the smiley face is displayed, then there are no messages. The system works
flawlessly.
When a warning message or service message is present, the smiley face is replaced by
a warning triangle.
Below the system diagram is a status bar, which provides continuous information about the systems operating
status. The following symbols are used:
Frost protection
Heating On
Fan active
Motor running
SD card
Language selection:
Via the button the language of the display can be selected in the basic display. In this version this
button has no function.
Navigation:
Navigation is done via the following buttons of the title bar.
The "Home" button leads back to the basic display (not available in the basic display)
from any display page. Any previously entered code is discarded.
The arrow to the left leads back a page or level, depending on the context.
The right arrow leads, depending on the context, a page or level further.
Here, the current measured value of the network pressure sensor is displayed. One tap
leads to a graphic representation of the network pressure course. On the other pages
(scroll using the arrow key) all pressure values for the complete system are compiled.
Temperatur (Temperature):
Here, the current measured value of the final compressor temperature is displayed. One
tap leads to a graphic representation of the mains temperature course. On the other
pages (scroll using the arrow key) all temperature values for the complete system are
compiled.
Status: The current compressor status is displayed. Tapping leads to a schematic representation
of air circulation, and the oil circuit.
Grafiken (Graphics):
This button initially leads to an overview of all available graphic evaluations. Network
pressure, temperature, maintenance intervals, and capacity utilisation as well as LLC
(only during use of LLC function) are available.
Menü (Menu): The "Menu" button provides access into the menu system. Here is where all setting
parameters are located.
Graphs
The measured values for the network pressure and final compressor temperatures are saved regularly (save
interval see 4.5.3 ). The collected data is graphically displayed (compare error: reference not found).
Within the graph interface the display range can be limited (zoom in) by pulling the square with one finger.
The following options are available in the X direction:
Max All available data points are displayed. Both axis are ideally adjusted
10 min, 30 min, 1h A corresponding section is shown. The arrow keys scroll in the X direction by a
quarter of the selected interval.
X Auto values from the display parameter menu → graphs → X auto are adopted.
Manuell (Manual) With this option the date and time can be selected and set to the desired values.
The y-axis is first scaled by the values from the display parameter menu → graphs. Both upper and lower
limits can be changed. Input is via a numeric keypad. Tapping the double arrow on the y-axis the limits are
reset to the values from the menu.
3.2 Messages
A flashing warning triangle (Warning/maintenance) or a tool symbol (fault) appears at the upper left of the
basic display, if a new message is present. Moreover, in a message pop-up at the bottom of the screen a
message is displayed in plain text. The message window can be closed with the Quit button. The fault icon in
the title bar flashes, but continues until the cause of the fault has been corrected. By pressing the warning or
fault icon in the title bar, the plain text message can be opened again.
An overview of all possible messages can be found in 5 .
After touching the menu buttons in the button bar the code input page appears.
A numeric keypad appears to enter an access code or a function code.
With the enter button the code digit is confirmed; the home button in the title bar aborts the entry.
The display switched in the menu level or the associated function is performed once the correct code has
been confirmed. There are codes with different functionalities:
After entering the menu code the display switches to the main menu. Depending on code level, the access is
connected to different authorisations. Thus, parameters are only displayed or can also be changed. The more
critical the setting value is for the safety of the system the higher is the associated code level (also see table
1).
After commissioning or after reaching ten operating hours the set service code is deactivated and replaced by
a dynamically assigned 24h code. Here, the control itself generates a random number and shows it in the
display. If this number is provided to the Almig service, then it will assign to this code a daily code that is valid
for 24h.
Specific codes are for specific deactivation of the fixed factory codes, regardless of the operating hours meter.
Besides the classical default setting which resets the settings to their respective default values there are other
functions for resetting of operating hour meters, error memory, graphics and operating cycles.
This code provides the possibility to set the branding from Almig (default) to Dalva or Kraftmann brand. The
functionality of the control stays identical. However, the welcome screen and screen saver are shown with the
respective logos and the selection of system types is adjusted accordingly.
The menus are all changeable parameters highlighted with a button (see Illustration 8). If a value is released
only for display, then a light blue field appears instead of the button.
Illustration 8: Examples for a menu. Here, all visible parameters can also be changed.
A numeric keypad (see Illustration 9) is available to enter or to change a numeric parameter. It appears as
soon as the value is taped. Left from it the possible setting range, default setting and a brief text of
explanation is displayed.
After the entry a new value can be adopted or discarded.
Correct entry
4 Menu system
Einschaltdruck 2 Lower limit for the pressure control when switching All Customer
(Switch-on pressure to the second range of pressure.
2)
Adjustment range: 3.5 bar – (switch-off pressure –
0.1bar)
Default setting: depending on system type
Ausschaltdruck 2 Upper limit for the pressure control when switching All Customer
(Switch-off pressure to the second range of pressure.
2)
Setting range: depending on system type but at
least 0.1 bar above switch-on pressure.
Default setting: depending on system type
Mindestdruck "Warnung Mindestdruck (Minimum pressure All Customer
(Minimum pressure) warning)" is triggered once the network pressure in (only
LLC operation (slave) falls below the minimum during LLC
pressure. As long as the warning is present or is slave
not acknowledged, the compressor switches to operation)
internal pressure control.
Adjustment range: 3.5 bar – (switch-off pressure –
0.1bar)
Default setting: 0 bar (no min. pressure
monitoring)
Prozentualer Sollwert Only for frequency converters: Position of the FU Customer
(Target value pressure setpoint within the current range of
percentage) pressure. On the "0%" setting the target value is in
the switch-on pressure, on the "100%" setting it is
at the switch-off pressure, otherwise suitably
between.
Adjustment range: 0 – 100%
Default setting: 20%
Taupunkt min. Minimum permissible dewpoint temperature Lento Customer
(Dewpoint min.) setting range: -10°C – 50°C
default setting: -4°C
Taupunkt max. (Dew Maximum permissible dewpoint temperature Lento Customer
point max.)
Adjustment range: 0°C – 50°C
Default setting: 12°C
The dewpoint temperature monitoring is
deactivated, if the "Taupunkt max. (Dew point
max.)" threshold is set to 0°C
!
4.4.1 Date/time
In this menu the date and time can be set. The weekday for the date is automatically calculated and
displayed.
In addition, it is also possible to activate the automatic daylight saving time here. This takes into account the
conversion rules for the CET (Central European Time).
The timer can be fully activated/deactivated. The compressor is only released at the programmed time, if the
"Schaltzeiten Kompressor (Compressor switching times)" is on "Ein (ON)". Eight (8) switching times (channel
1 - 8) are available for programming. These channels are connected with a disjunction, meaning that the
compressor can operate, if at least one channel permits this.
Is the "Schaltzeiten Kompressor (Switching times Compressor)" set to "Aus (Off)", then any time restriction
has been lifted.
Individual channels can be switched on or off. Is a programmed channel set to "Inactive", then it is not
considered in the evaluation of the time switch. The set times are retained and can be activated when
required.
In the example below, the compressor would be operating from Monday to Friday from 13:00 hours to 22:30
hours.
To switch on a compressor for one or more days continuously, the corresponding day must be selected and
the switching times must be entered with 00.00.
The timer can be fully activated/deactivated. Is "Druckzeiten Kompressor (Compressor pressure times)" set to
"Ein (ON)", then the compressor runs at the programmed times with each set pressure band. Eight (8)
channels are available for programming. The range of pressure of the first active channel that programmed a
currently active time is valid.
The compressor move in the pressure range set in the "Regelung (Control)" menu, if the "Schaltzeiten
Kompressor (Compressor switching times)" is set to "Aus (Off)" or if no channel is programmed at the current
time.
Individual channels can be switched on or off. Is a programmed channel set to "inaktiv (Inactive)", then it is not
considered in the evaluation of the time switch. The set times and pressures are retained and can be
activated when required.
In the example shown below the pressure range of the compressor is set to weekend between 10:15 hours
and 22.30 hours and to 8.5-9.5 bar.
To switch on a pressure range for the compressor for one or more days continuously, the corresponding day
must be selected and the switching times must be entered with 00.00.
Programming of the time schedule for the digital output is done analogous to the compressors switching
times. Four schedule are available. These can be assigned to the digital output, if required ( also see Chapter
4.6.3 )
4.5.2 Texts
Using the QWERT keyboard text for the system pass can be entered in this menu.
Fabrik-Nr. (Serial Here, free text with up to 10 characters can be stored. All Plant
no.) Display is via the system pass.
Default setting: no text stored
EDV-Nr. (EDV Here, free text with up to 16 characters can be stored. All Plant
no.) Display is via the system pass.
Default setting: no text stored
Kommissions-Nr. Here, free text with up to 10 characters can be stored. All Plant
(Commission no.) Display is via the system pass.
Default setting: no text stored
Schaltplan-Nr. Here, free text with up to 16 characters can be stored. All Service
(Circuit diagram Display is via the system pass.
no.)
Default setting: no text stored
4.5.3 Diagrams
This function can be used to clean the display to prevent accidental operation. After starting this function, the
control cannot be operated for a minute.
The function is available independent of code level.
4.6 Configuration
4.6.1 Communication
RS-485 Zugriff Determines the right/authorisation for changes via the All Service/pl
(Access) RS-485 interface. Depending on setting, either no ant
parameter or only parameter of the respective code
level can be changed.
Depending on the entered code, not all settings are
available
Adjustment range: Nur Lesen (Read only)
Lesen / Schreiben Kunde (Read / write customer)
Lesen / Schreiben Service (Read / write service)
Lesen / Schreiben Werk (Read / write plant)
Default setting: Lesen / Schreiben Service (Read/write
service)
Different MK200 modules can be connected to the RS-485 bus. In doing this, the module must have its own
address and each address can only occur once. In principle, up to 32 participants are possible. Whether the
ACP establishes the communication to a module and monitors a fault of a module depends on the settings in
this menu.
Parameter Value range/default setting/comments System Code
types level
MK200 Profibus Determines if the Profibus module on the MK200 All Service
module has been contacted. Set address: 31.
Adjustment range: Ja / Nein (Yes/No)
Default setting: Nein (No)
MK 200 Zubehör Determines if the plug-in module on the MK200 module All Service
(Accessories) have been considered. The assignment of the digital
inputs and outputs of up to two accessory modules of
8E4RA type can be freely selected from a list of
possible functions in the submenu Configuration →
Inputs / Outputs. Addresses: 4 and 5.
Adjustment range: Ja / Nein (Yes/No)
Default setting: Nein (No)
Erweiterungsmodu Amounts of expansion modules connected to the All Service
le Anz. (Expansion MK200 module bus. Addresses 8 to 30
module amount)
Adjustment range: 0 – 23
Default setting: 0
Address assignment:
The addresses are set via the DIP switch directly on the MK200 modules. The following addresses are
intended for the modules and must be retained.
Address 0: reserved, do not use.
Address 1: MK200 4AA module to control a frequency converter. Also see 4.6.6 .
Address 2 MK200 8E4RA Module (LLC module) to control up to four LLC slaves. Also see 4.10.1 .
Address 3 do not use
Address 4-5 Up to two MK200 8E4RA modules as plug-in module 1 and 2. Inputs and outputs can be
freely configured. Also see 4.6.3 .
Address 6 MK200 8E4RA module as SWC module (Lento). The inputs and outputs are permanently
assigned. When selecting a Lento system then the module is expected and evaluated. Also
see 4.6.3 .
Address 7 do not use
Address 8-30 Up to 23 MK200 8E4RA expansion modules.
Address 31 MK200 Profibus module
4.6.3 Inputs/outputs
In this menu, the digital inputs and outputs of the AirControl P and the plug-in module functions can be
assigned.
At the AirControl P eight digital inputs and seven digital outputs are available. These are pre-assigned by
default but can be changed if needed. Outputs 1-4 of the AirControl P can be pre-assigned depending on
system type.
Digital inputs ACP default setting:
Input 1 (inverted) PTC input: E073 Motor temperature (fault over-temperature motor)
Input 2 (inverted) E074 Overcurrent
Input 3 E075 Overpressure
Input 4 E072 Direction of rotation or on Lento E099 water level
Input 5 W033 Rotation speed limit
Input 6 E071 Emergency Off
Input 7 Remote On/Off
Input 8 Remote Load/idle
Per plug-in module there are eight further inputs and 4 outputs. The assignment of the inputs / outputs can be
freely selected. For the inputs, it is possible to define the logic. Outputs can be connected to one of four time
schedules (timer; see section 4.4.4 ).
The following functions are available:
Digital inputs
Designation Function
Vorort/ Fern (On-site/remote) Switching between on-site operation and remote control is possible via
this input.
Fern Ein/Aus (Remote On/Off) Remote signal On via digital input (is only evaluated if active in menu:
compare to 4.2 )
Fern Last/Leer (Remote load/idle) Load requirement via digital input (is only evaluated if active in menu:
compare to 4.2 )
Fern GLW (Remote LLC) Only relevant for LLC master control. With this input the LLC master
can be activated/deactivated with all connected slaves. (Remote
On/Off for the whole station)
GLW – OK (LLC OK) Ok signal input for a superordinate control (valid only if the control
menu is configured as a slave GLW: compare to 4.2 )
Schaltuhr brücken (Bridge timer) The timer is ignored when a signal is at the input.
Raum-Thermostat (Room The "Ventilation flap open" and "Exhaust flap closed" outputs are
thermostat) switched when a signal is at the input.
Taupunkt Trockner (Dryer The "Dewpoint high" output is switched when a signal is at the input.
dewpoint)
W025 Öl/ Heizung (Oil/heating) Respective warning and fault messages are triggered when signal at
W033 Drehz. (Rot. speed) input.
Begrenzung (Limit)
Depending on system type, not all options mentioned are available.
W034 Trockner (Dryer)
W036 Kond. Ableiter (Cond.
Arrester)
W037 Luftfilter (Air filter)
W029 Wasserfil. (Water fil.)
W038 Ölfilter (Oil filter)
W039 Ölabscheider (Oil
precipitator)
W056 Ext.War.1
W057 Ext.War.2
W058 Ext.War.3
W059 Ext.War.4
E071 Notaus (Emergency Off)
Digital outputs
Designation Function
Lüfter ein, Klappe auf (Ventilator on Output on, if ventilator is running and flap is open.
/ flap open)
Zuluftklappe auf (Feed flap open) Output on when ventilation flap is open.
4.6.4 Heating/ventilation
Umwälzung Determines the switch-off temp. for the recirculation All Plant
Ausschalttemp. (idle run without prompt).
(Recirculation
Adjustment range: Recirculation switch-on temperature
switch-off
– 20°C
temperature)
Default setting: 15°C
The last 20 messages are saved in the message memory. In doing so, the newest message is shown in the
first place. Scroll for older messages.
4.9 Diagnosis
The current states of the AirControl P digital inputs and outputs are in this menu.
Should this page be selected using a service code, then the outputs can be switched on and off by tapping.
When doing this, only one output is activated due to safety reasons.
The settings for the priority assignments of the individual compressors are in this menu. The values set here
apply only when no timer channel on the timer LLC priorities is active.
The switch-on/off times of the LLC are defined in this menu. Applies only for the LLC master. Programming is
done analogous to the "Schaltzeiten Kompressor (Compressor switching times)" in section .
The pressure times of the LLC are defined in this menu (increase/decrease). Applies only for the LLC master.
Programming is done analogous to the "Druckzeiten Kompressor (Compressor pressure times)" in section .
The switching times of the LLC priority change are defined in this menu. Applies only for the LLC master.
Programming is done analogous to other timers such as "Schaltzeiten Kompressor (Compressor switching
times)" in section . The same priority levels as described under are available.
4.11 SD card
All functions with access to the SD card are located in this menu. The respective card must be inserted for
use.
The current parameter set is written to the SD card. An SD card must be inserted without write protection.
Warning: If data was already stored on the inserted SD card, it will be overwritten and therefore lost.
A parameter set that has been saved with this function can be read in again using the "Parameter laden (Load
parameters)" function. It does not matter with what control the data was saved. A data set can be transferred
to any number of controls (with the same software version).
Using this function a parameter set can be read from the SD card. A SD card with the "ACPParam.par" file
must be inserted.
Before actually loading the data, the storage date and system type of the data set appear. Please first check
for plausibility!
Warning: All your current settings will be overwritten by the control, to load the data from the SD card and are
thus lost.
This function starts data logging to the SD card. An SD card must be inserted without write protection. The
following data is also recorded:
Time stamp
System status
Network pressure
Final temperature
Oil temperature
Delivery amount
State of all connected compressors (only on LLC)
Pressure, delivery quantity and temperature are saved in the set display dimension at each controller(bar / psi
/ MPa m / cft, ° C / ° F / Kelvin), status in the selected language. Per calendar day a csv. format file
(separator: tab) is created. If data logging is activated, then the text of the button changes from start data
logging to sop data logging. In this case, a currently running data logging can be stopped.
5 Messages
A flashing warning triangle appears at the upper left of the basic display, if a new warning or maintenance
message is present. Moreover, in a message pop-up at the bottom of the screen a message is displayed in
plain text. The message window can be closed with the Quit button. The warning triangle in the title bar will
stop flashing but remains displayed until the cause of the alarm has been corrected. By tapping on the
warning triangle, the message appears again.
Warning message Comments System
types
W021: V-Temp. erhöht (V The max. permissible final compressor temperature All
temp. increased) (warning limit) is exceeded. See factory settings menu.
W022: Netzdruck erhöht The network pressure has exceeded the limit (max. All
(Increased network permissible network pressure 0.3 bar).
pressure)
W023: Temperatur niedrig The minimum temperature required to start is too low. See All except
(Temperature low) factory settings menu. Lento
W024: Untere Minimum pressure below target. Only relevant for LLC All
Druckschwelle (Lower slave operation. See control menu.
pressure threshold)
W025: Ölstand/Heizung Warning heating limit: On an active heating the input All
prüfen (Check oil "Overpressure fault" has been triggered (delay 0.5s).
level/heating)
W026: Abgleich falsch At least one analogue input calibration value is incorrect. All
(Wrong calibration)
W029: Wasserfilter (Water Digital input water filter warning has been triggered. Lento
filter)
W030: Dif.Dru.Wasserfi. Digital input 7 "Differential pressure water filter" on module Lento
(Diff.Press.Waterfi.) address 6 open. Delay 1s
W031: Überstr. Lüfter 1 Overcurrent on fan 1 (input 1, module address 6 was Lento
(Overcurrent Fan 1) opened). Fan 2 is OK, delay 1s.
W032: Überstr. Lüfter 2 Overcurrent on fan 2 (input 2, module address 6 was Lento
(Overcurrent Fan 2) opened). Fan 1 is OK, delay 1s.
W033: Drehzahlbegrenzung The digital input programmed on "W033: speed limiter" has All
(Speed limiter) been opened. Delay 1s.
W034: Trockner (Dryer) The digital input programmed on "W034: Dryer" has been All
opened. Delay on Lento 1s otherwise without delay.
W035: Taupunkt Trockner The digital input programmed on "W035: Dewpoint dryer" Lento
(Dryer dewpoint) has been opened. Only during active dewpoint monitoring.
W036: Kondensatableiter The digital input programmed on "W036: Condensate All
(Condensate drain) drain" has been closed.
W037: Luftfilter (Air filter) The digital input programmed on "W037: Air filter" has All
been closed. Monitoring starts after 15 minutes. Triggering
of warning delayed
W038: Öl/Ölfilter (Oil/oil The digital input programmed on "W038: Oil/oil filter" has All
filter) been closed. Monitoring starts after 15 minutes. Triggering
of warning delayed
W039: Ölabscheider (Oil The digital input programmed on "W039: Oil precipitator" All
precipitator) has been closed. Monitoring starts after 15 minutes.
Triggering of warning delayed
W044: Erweiterungsmodul At least one of the configured expansion modules does not All
(Expansion module) answer (possible addresses 8 to 30).
W045: E/A module (addr.1) The analogue output module on address 1 does not All
answer. This monitoring is only active if this module has
been activated
W046: E/A module (addr.2) The LLC module on address 2 does not answer. This All
monitoring is only active in the LLC master operation on
digital control of the LLC slave,
W048: E/A module (addr.4) The plug-in module on address 4 does not answer. This All
monitoring is only active if this module has been selected.
W049: E/A module (addr.5) The plug-in module on address 5 does not answer. This All
monitoring is only active if this module has been selected.
W050: Profib. Mod.(Addr. The Profibus module on address 31 does not answer. This All
31) monitoring is only active if this module has been selected.
W055: Zugriff SD-Karte (SD During the access to the SD card a fault occurred. All
card access)
W056: Ext. War. 1 The digital input programmed on W056: Ext. War. 1 has All
been opened.
W057: Ext. War. 2 The digital input programmed on W057: Ext. War. 2 has All
been opened.
W058: Ext. War. 3 The digital input programmed on W058: Ext. War. 3 has All
been opened.
W059: Ext. War. 4 The digital input programmed on W059: Ext. War. 4 has All
been opened.
E095: E/A module (addr.4) The plug-in module on address 4 (type MK200 8E4RA) All
does not answer. This monitoring is only active if this
module has been selected (see section 4.6.2 and 4.6.3).
E096: E/A module (addr.5) The plug-in module on address 5 (type MK200 8E4RA) All
does not answer. This monitoring is only active if this
module has been selected (see section 4.6.2 and 4.6.3).
E097: E/A module (addr.6) The Lento module on address 6 (type MK200 8E4RA) Lento
does not answer. This monitoring is only active if it is a
Lento system.
E099: Wasserstand (Water Digital input water level low has been triggered. Delay Lento
level) water infeed 10s. On systems with water infeed in load run
delay by the set time "Water infeed time".
E100: Wasserstand (Water Digital input water level too high (delay water max.) has Lento
level) max. been triggered. The maximum draining time has been
exceeded. Monitoring only when motor is in operation.
E101: Dif.Drk.Wasserfi. The "Warnung Differenzdruck Wasserfilter (Warning Lento
(Diff.Press.Waterfilter) differential pressure water filter)" (Digital input module
addr. 6) is present for a longer amount of time than the
parameters in the "Max. Differenzdruck Wasserfilter
(Maximum differential pressure water filter)" (see operating
parameters).
E103: Überstrom Lüfter Both inputs "Fan 1 overcurrent" and "Fan 2 overcurrent" Lento
(Overcurrent ventilation) (inputs 1 and 2, module address 6) have been triggered.
Delay 1s.
E106: Dru.Aufb.Lagersp. Pressure build-up bearing flush fault. Digital input 8 on Lento
(Press.Buildup.bear.flush) module addr. 6 did not open after the time it was set in the
menu "Druckaufbau Lagerspülung (Pressure build-up
bearing flush)".
E108: Taupunkt Trockner The dewpoint exceeded the permitted maximum (if set in All
(Dryer dewpoint) menu) while the motor was running. Only if the heating is
not active or available.
E109: Taup. zu niedrig The dewpoint dropped short of the permitted minimum (if All
(Dewpoint too low) set in menu) while the motor was running. Only if the
heating is not active or available.
E110: Ext. Stör. (fault) 1 The digital output programmed to "Externe Störung All
(External fault) 1" has been triggered.
E111: Ext. Stör. (fault) 2 The digital output programmed to "Externe Störung All
(External fault) 2" has been triggered.
E112: Ext. Stör. (fault) 3 The digital output programmed to "Externe Störung All
(External fault) 3" has been triggered.
E113: Ext. Stör. (fault) 4 The digital output programmed to "Externe Störung All
(External fault) 4" has been triggered.
E120: FU Überstrom Only on Yaskawa converters. FU
(overcurrent) (OC,GF) FU overcurrent fault
E121: FU Überspannung Only on Yaskawa converters. FU
(Overvoltage) (OV) FU overvoltage fault
E122: FU Überlastung Only on Yaskawa converters. FU
(Overload) (OL2) FU overload fault
E123: FU Überhitzung Only on Yaskawa converters. FU
(Overheating) (OH1/2) FU overheating fault
E124: FU Motorbremse Only on Yaskawa converters. FU
(Motor brake) (RR,RH) FU motor brake fault
E125: FU Feedback Only on Yaskawa converters. FU
(FbL,FbH) FU feedback fault
E126: FU Extern (External) Only on Yaskawa converters. FU
(EF0-6) FU external fault
E127: FU Hardware (OFx) Only on Yaskawa converters. FU
FU hardware fault
E128: FU Motorüberlast Only on Yaskawa converters. FU
(Motor overload) (OL1) FU motor overload fault
E129: FU Verbindung Only on Yaskawa converters. FU
(Connection) (PGO) FU connection PGO fault
E130: FU Zw. Untersp. Only on Yaskawa converters. FU
(Interm. undervoltage) (UV) FU intermediate circuit undervoltage fault
E131: FU Only on Yaskawa converters. FU
Untersp.(Undervoltage) FU undervoltage fault
(UV1)
E132: FU Phase (LF,PF) Only on Yaskawa converters. FU
FU phase fault
E133: FU Kommunikation Only on Yaskawa converters. FU
(Communication) (CE) MEMOBUS communication fault
E134: FU Bedieneinheit Only on Yaskawa converters. FU
(Operating unit) (OPR) FU fault operating unit not connected
E135: FU Motor I2t Only on Emotron converters FU
E136: FU PTC Only on Emotron converters FU
E137: FU Motor ab (Motor Only on Emotron converters FU
off)