01cda01 GCP V4.02
01cda01 GCP V4.02
01cda01 GCP V4.02
www.mandieselturbo.com
Revision History
Rev. Written Checked Released Release Date Status / Edition Issued for Remark
This wiring diagram applies for different types of voltages, engines, auxiliaries, etc. and is based on the maximum After the panel has been moved, all screw joints have to be checked and tightened, if necessary.
configuration of the default panel. At least every part of this wiring diagram marked by the exclamation mark shown in
illustration 1 has to be checked before manufacturing. The special project requirements can be found in the technical The settings of CBs, time relays, monitors and protection devices have to be checked.
specification, electrical control guide, measuring-, and consumer lists and have to be adapted by the E-Supplier. In
spite of the greatest care MAN Diesel & Turbo does not assume any liability or guarantee for the completeness or A phase-sequence test for determining the appropriate connection of the phases has to be performed for all incoming
quality of the provided wiring diagram or the fulfillment of the functional scope for the appropriate panel. three-phase voltages.
The eyebolts and/or combination angles used for transportation have to be replaced by the supplied roof fastening
During installation: screws (Rittal PS 4198.000).
All parts that could be live, although the panel voltages have been switched off (e. g. by external voltage), have to be Every cable requires a permanent label with the entire identification tag on both ends.
marked accordingly.
Every device (or terminal strip) must bear, legibly and indelibly, a label with the entire device tag itself, as well as on
the mounting plate or the panel door, respectively. The same applies to terminals, they have to be marked unique and
distinctive.
Installation material such as cable ducts, copper rails, mounting parts, etc. is part of the E-Supplier's delivery scope and
not mentioned in the parts list.
For mounting of cable ducts only non-metal and non-conductive screws or bolts are permissible. The maximum filling
range of the ducts is 80%. The electrical lines for drives and sensors have to be separated, as well as internal and
external cables or wires. Wire ends have to be equipped with appropriate ferrules, except of wires that are connected
to cage clamp terminals.
Every analog signal cable has to be shielded. The shielding for each signal pair has to be connected to an insulated
shield terminal and to be earthed at the signal processing end. The wiring has to be performed in accordance to the 1. Cable Lug
Electromagnetic Compatibility Regulations (EMC). 2. Contact Washer
3. Nut
When positioning the mounting plate and using spacer bolts for the cable clamp rail a linear routing of the cables has to 4. TS-Cabinet
be ensured. The cables have to be inserted from the bottom of the panel and firmly mounted by retainer brackets. 5. Washer
6. Bolt
Each mechanical part of the Panel (side walls, back wall, roof, bottom plates, etc.) shall be earthed in a star-shaped
form, even if there's no electrical equipment installed. The number of necessary Earthing Straps can be found in the
Earthing Connections Overview.
Earthing bolts have to be fixed with locking washers for the bolt itself and the nut. A permanent electrical connection to
the mounting plate has to be ensured, in case of painted surfaces the paint has to be removed, or contact washers
used instead. Next to the cable lug washers shall be placed to avoid twisting while tightening the screw, an example for
correct assembly is shown in illustration 2:
At every earthing connection point a corresponding label with an earthing symbol has to be attached.
1. Nut
2. Contact Washer
3. Bolt
4. Cable Lug
5. Washer
6. Spring or Lock Washer
7. Mounting Plate
Purpose: To the second part (page 200 to 298) belong the PLC and other digital logic units like Profibus DP and Ethernet
connection and the Panel PC as the Human-Machine-Interface. Digital In- and Outputs are drawn on one page per
The purpose of this Documentation is to describe the Layout and Wiring of the MDT GCP (Genset Control Panel). byte, linked to the corresponding Overviews which are arranged right behind the Rack assembly. Pages 300 to 498 are
reserved for part three, the Control Voltage area. It contains the Common Control, Voltage Regulation, Synchronization,
Measuring/Supervising, Speed and CB Control. The safety related circuits are located in part four, in particular the
Properties: Protection Relay, Emergency Stop Safety Chains for Engine, Alternator CB and auxiliary drives' loops and the voltage
Current Path
Drawing Number
Last Page Editor
Project Number
Page Number
Project Name
Page Content
Page Verifier
Panel Name
System
Wiring (shown once on each page per potential): Abbreviations of electrical links (arrow direction symbolizes signal flow):
Wire definition (e. G. 1,5mm² BU) = hard-wired connection H05V-K, H07V-K I = Current
NSGAFÖU = Short-Circuit proof wiring V = Voltage
Ringline = hard-wired connection arranged as a ring (cross-section reduction)
Cross Connection (CC due to lack of space) = Pluggable cross-connection for terminals Annex:
Integrated Cross Connection = Terminals including electrical connection
Comb Busbar = Screwable comb-type busbar for MCBs AUX = Auxiliary
Cu Busbar = copper rail system BF = Breaker Failure
DIF = Differential
EF = Earth Fault
Color definition (IEC 60575): M = Measuring
NE = Neutral Earthing
BK = Black GY = Grey OD = Open Delta
BN = Brown WH = White P = Protection
RD = Red PK = Pink PS = Power Supply
OG = Orange GD = Gold SV = Supervision
YE = Yellow TQ = Turquoise SYN = Synchronization
GN = Green SR = Silver
BU = Blue TR = Transparent (applies to Marine Cables) [DOT] Index:
LBU = Light Blue GNYE = Green-Yellow
VT = Violet A = Alternator
AUT = Automatic
BB = Busbar
Color codes of wiring: BSD = Blackstart Diesel
C = Common
Black: Three-Phase and AC control wiring, secondary winding of Voltage Transformer CHK = Check
Light Blue: Neutral Wiring HV = High Voltage
Green-Yellow: Protective Earth Wiring LV = Low Voltage
Red: DC Wiring +Pole <40V MV = Medium Voltage
Blue: DC Wiring -Pole <40V RED = Redundant
Brown: DC Wiring +Pole >40V ST = Station Transformer
Violet: DC Wiring -Pole >40V SUT = Step-Up Transformer
Grey: Secondary Winding of Current Transformer UPS = Uninterruptible Power Supply
White: Wiring for voltage free contacts
[Hyphen] Number:
Color code of Multi-Core Cables according to DIN 47100
L1 = Phase L1
Color code of Ethernet CAT5e Patch Cables: L2 = Phase L2
L3 = Phase L3
Standard: Grey N = Neutral Conductor
Cross Over: Red PEN = Protective Earth and Neutral Conductor (TN-System)
Specials:
Labeling of devices:
24VDC = DC 24V +Potential
+LIC-EIC (-subEIC) M24 = DC 24V M-Potential
LED-T = LED Test Potential
Composition of Equipment Identification Code (EIC): [Page number] [Code letter] [Consecutive number] PB = Profibus DP Connection
FO = Fiber Optic Connection
Exception 1 PLC: [Code Letter A] [Rack Number] [Consecutive two-digit number] ETH = Ethernet Connection
Exception 2 Cables: [Code Letter W] [MAN Cable Tag numbering System] RS = Serial Interface Connection
Exception 3 Terminal Strips: [Code Letter X] [Special numbering, check Page 600] EIC:xx = Connection Terminal (Source or Target)
KKS Overview
Location
Designation of KKS Identification Code
Identification Code
+00BBA01 MV Busbar
+00BBA01.02 MV Busbar
+01MKA01 Alternator
+LVD
+PLG
Contents
+01CDA01/030 Construction Layout Transport Units/Panel Groups Floor Opening Rev.C 24.10.2014 E. Simon
+01CDA01/032 Construction Layout Side, Top and Bottom Views Rev.C 24.10.2014 E. Simon
+01CDA01/033 Construction Layout Internal Layout Door, Side and Back Walls, Roof Rev.C 24.10.2014 E. Simon
+01CDA01/034 Construction Layout Internal Layout Mounting Plate Rev.C 24.10.2014 E. Simon
+01CDA01/040 PowerPS Overview Safety Chain Engine Shutdown Rev.C 24.10.2014 E. Simon
+01CDA01/041 PowerPS Overview Emergency Stop Loop for Engine Auxiliary Drives Rev.C 24.10.2014 E. Simon
+01CDA01/045 PowerPS Overview Protection and Measuring Scheme GCP Version C (ABB Alternator) Rev.C 24.10.2014 E. Simon
+01CDA01/046 PowerCS Overview GCP internal Bus Overview Profibus DP Rev.C 24.10.2014 E. Simon
+01CDA01/047 PowerCS Overview GCP internal Bus Overview Ethernet Rev.C 24.10.2014 E. Simon
+01CDA01/100 Wiring Diagram Power Supply AC 230V Panel Equipment Rev.C 24.10.2014 E. Simon
+01CDA01/102 Wiring Diagram UPS Power Supply AC 230V Rev.C 24.10.2014 E. Simon
Contents
+01CDA01/104 Wiring Diagram Power Supply Unit DC 24V Rev.C 24.10.2014 E. Simon
+01CDA01/160 Wiring Diagram Panel Equipment Illumination, Ventilation, Door Supervision Rev.C 24.10.2014 E. Simon
+01CDA01/200 PowerCS Wiring Diagram Optical Link Module Unit Profibus DP Rev.C 24.10.2014 E. Simon
+01CDA01/202 PowerCS Wiring Diagram PLC Rack 1 Assembly Rev.C 24.10.2014 E. Simon
+01CDA01/204 PowerCS Wiring Diagram PLC Rack 1 -A105 Overview Rev.C 24.10.2014 E. Simon
+01CDA01/206 PowerCS Wiring Diagram PLC Rack 1 -A106 Overview Rev.C 24.10.2014 E. Simon
+01CDA01/208 PowerCS Wiring Diagram PLC Rack 1 -A107 Overview Rev.C 24.10.2014 E. Simon
+01CDA01/210 PowerCS Wiring Diagram PLC Rack 1 -A108 Overview Rev.C 24.10.2014 E. Simon
+01CDA01/212 PowerCS Wiring Diagram PLC Rack 1 -A101 Power Supply Rev.C 24.10.2014 E. Simon
+01CDA01/214 PowerCS Wiring Diagram PLC Rack 1 -A103 CPU Rev.C 24.10.2014 E. Simon
+01CDA01/216 PowerCS Wiring Diagram PLC Rack 1 -A104 Communication Processor/Panel PC Rev.C 24.10.2014 E. Simon
+01CDA01/218 PowerCS Wiring Diagram PLC Rack 1 -A105 Digital Input Byte 0 MCB OFF Signals Rev.C 24.10.2014 E. Simon
+01CDA01/220 PowerCS Wiring Diagram PLC Rack 1 -A105 Digital Input Byte 1 MCB OFF Signals/GCP internal Signals Rev.C 24.10.2014 E. Simon
+01CDA01/222 PowerCS Wiring Diagram PLC Rack 1 -A105 Digital Input Byte 2 OLM Fault/Alternator Protection Signals Rev.C 24.10.2014 E. Simon
+01CDA01/224 PowerCS Wiring Diagram PLC Rack 1 -A105 Digital Input Byte 3 Control Switches/Buttons Rev.C 24.10.2014 E. Simon
+01CDA01/226 PowerCS Wiring Diagram PLC Rack 1 -A106 Digital Input Byte 4 Voltage, cosφ, Load, Speed, Frequency Set. Rev.C 24.10.2014 E. Simon
+01CDA01/228 PowerCS Wiring Diagram PLC Rack 1 -A106 Digital Input Byte 5 CCP Signals Rev.C 24.10.2014 E. Simon
+01CDA01/230 PowerCS Wiring Diagram PLC Rack 1 -A106 Digital Input Byte 6 Alternator MV Busbar Signals Rev.C 24.10.2014 E. Simon
+01CDA01/232 PowerCS Wiring Diagram PLC Rack 1 -A106 Digital Input Byte 7 Alternator MV Busbar Signals Rev.C 24.10.2014 E. Simon
+01CDA01/234 PowerCS Wiring Diagram PLC Rack 1 -A107 Digital Input Byte 8 Spare Rev.C 24.10.2014 E. Simon
+01CDA01/236 PowerCS Wiring Diagram PLC Rack 1 -A107 Digital Input Byte 9 Spare Rev.C 24.10.2014 E. Simon
+01CDA01/238 PowerCS Wiring Diagram PLC Rack 1 -A107 Digital Input Byte 10 Spare Rev.C 24.10.2014 E. Simon
+01CDA01/240 PowerCS Wiring Diagram PLC Rack 1 -A107 Digital Input Byte 11 Spare Rev.C 24.10.2014 E. Simon
+01CDA01/242 PowerCS Wiring Diagram PLC Rack 1 -A108 Digital Output Byte 0 Signaling Column/Position Indication Rev.C 24.10.2014 E. Simon
Contents
+01CDA01/244 PowerCS Wiring Diagram PLC Rack 1 -A108 Digital Output Byte 1 Synchronization/Alternator 1 CB Rev.C 24.10.2014 E. Simon
+01CDA01/246 PowerCS Wiring Diagram PLC Rack 1 -A108 Digital Output Byte 2 Earthing, Protection Rev.C 24.10.2014 E. Simon
+01CDA01/248 PowerCS Wiring Diagram PLC Rack 1 -A108 Digital Output Byte 3 Spare Rev.C 24.10.2014 E. Simon
+01CDA01/300 Wiring Diagram Alternator Incoming Protection Current Core 2 Rev.C 24.10.2014 E. Simon
+01CDA01/302 Wiring Diagram Alternator Incoming Protection Current Core 1 Rev.C 24.10.2014 E. Simon
+01CDA01/304 Wiring Diagram MV Busbar Incoming Measuring Voltage Rev.C 24.10.2014 E. Simon
+01CDA01/306 Wiring Diagram MV Busbar Incoming Protection + Measuring Current Rev.C 24.10.2014 E. Simon
+01CDA01/308 Wiring Diagram MV Busbar Alternator Circuit Breaker Rev.C 24.10.2014 E. Simon
+01CDA01/310 Wiring Diagram MV Busbar Incoming Measuring Voltage Rev.C 24.10.2014 E. Simon
+01CDA01/314 Wiring Diagram Synchronization Indication Voltmeter/Frequency Meter/Synchronoscope Rev.C 24.10.2014 E. Simon
+01CDA01/316 Wiring Diagram Synchrocheck Relay Automatic Synchronization Unit Rev.C 24.10.2014 E. Simon
+01CDA01/322 Wiring Diagram Alternator CB Control + Open/Trip Loop Rev.C 24.10.2014 E. Simon
+01CDA01/500 PowerPS Wiring Diagram Alternator Protection Relay Rev.C 24.10.2014 E. Simon
+01CDA01/508 PowerPS Wiring Diagram Safety Chain Engine Shutdown Rev.C 24.10.2014 E. Simon
+01CDA01/510 PowerPS Wiring Diagram Emergency Stop Loop for Engine Aux. Drives GCP via GIP to EAP + ERP (+ EVP) Rev.C 24.10.2014 E. Simon
+01CDA01/512 PowerPS Wiring Diagram Alternator CB Closed Signals to AVR and SaCoS Rev.C 24.10.2014 E. Simon
+01CDA01/514 PowerPS Wiring Diagram Alternator CB Signals and Connection to GIP Rev.C 24.10.2014 E. Simon
+01CDA01/516 PowerPS Wiring Diagram Breaker Failure from/to MV Busbar 1 Rev.C 24.10.2014 E. Simon
Contents
Contents
+01CDA01/901 Verification of Panel Protection Degree Protection Degree Certificate TS8 Series Rev.C 24.10.2014 E. Simon
+01CDA01/902 Verification of Panel Protection Degree List of surface mounted Devices Rev.C 24.10.2014 E. Simon
+01CDA01/910 Verification and Calculation of Panel Consumption per Voltage Rev.C 24.10.2014 E. Simon
+01CDA01/911 Verification and Calculation of Panel Consumption per Voltage AC 230V - Panel Equipment Rev.C 24.10.2014 E. Simon
+01CDA01/912 Verification and Calculation of Panel Consumption per Voltage AC 230V UPS - Control Voltage Rev.C 24.10.2014 E. Simon
+01CDA01/913 Verification and Calculation of Panel Consumption per Voltage DC 24V Rev.C 24.10.2014 E. Simon
+01CDA01/914 Verification and Calculation of Panel Consumption per Voltage DC 24V Rev.C 24.10.2014 E. Simon
+01CDA01/920 Verification and Calculation of Panel Heating and Cooling Rev.C 24.10.2014 E. Simon
+01CDA01/921 Verification and Calculation of Panel Heating and Cooling Calculation of Power Dissipation Rev.C 24.10.2014 E. Simon
+01CDA01/922 Verification and Calculation of Panel Heating and Cooling Calculation of Power Dissipation Rev.C 24.10.2014 E. Simon
Contents
+01CDA01/923 Verification and Calculation of Panel Heating and Cooling Climate Control Calculation Rev.C 24.10.2014 E. Simon
+01CDA01/930 Verification and Calculation of CBs, MCBs and Fuses including Settings Rev.C 24.10.2014 E. Simon
+01CDA01/931 Verification and Calculation of CBs, MCBs and Fuses including Settings Verification of CBs, MCBs and Fuses Rev.C 24.10.2014 E. Simon
+01CDA01/932 Verification and Calculation of CBs, MCBs and Fuses including Settings Calculation of Cable Length 2A (A) DC 24V Rev.C 24.10.2014 E. Simon
+01CDA01/933 Verification and Calculation of CBs, MCBs and Fuses including Settings Calculation of Cable Length 6A (B) DC 24V Rev.C 24.10.2014 E. Simon
+01CDA01/934 Verification and Calculation of CBs, MCBs and Fuses including Settings Calculation of Cable Length 10A (B) DC 24V Rev.C 24.10.2014 E. Simon
+01CDA01/935 Verification and Calculation of CBs, MCBs and Fuses including Settings Calculation of Cable Length 2A (A) AC 110V Rev.C 24.10.2014 E. Simon
+01CDA01/936 Verification and Calculation of CBs, MCBs and Fuses including Settings Calculation of Cable Length 10A (B) AC 230V Rev.C 24.10.2014 E. Simon
+01CDA01/937 Verification and Calculation of CBs, MCBs and Fuses including Settings Calculation of Cable Length 10A (C) AC 230V Rev.C 24.10.2014 E. Simon
+01CDA01/938 Verification and Calculation of CBs, MCBs and Fuses including Settings Calculation of Cable Length 1,4-2A 3AC 110V Rev.C 24.10.2014 E. Simon
+01CDA01/939 Verification and Calculation of CBs, MCBs and Fuses including Settings List of max. Cable Length Rev.C 24.10.2014 E. Simon
+01CDA01/940 Verification and Calculation of CBs, MCBs and Fuses including Settings Calculation of Voltage Drop by Cable Rev.C 24.10.2014 E. Simon
+01CDA01/941 Verification and Calculation of Synchronization Device Settings Rev.C 24.10.2014 E. Simon
+01CDA01/942 Verification and Calculation of Synchronization Device Settings SPM-D1010B/YB Rev.C 24.10.2014 E. Simon
+01CDA01/943 Verification and Calculation of Synchronization Device Settings SPM-D1010B/YB Rev.C 24.10.2014 E. Simon
+01CDA01/944 Verification and Calculation of Synchronization Device Settings SPM-D1010B/YB Rev.C 24.10.2014 E. Simon
+01CDA01/945 Verification and Calculation of Synchronization Device Settings HAS-111 DG Rev.C 24.10.2014 E. Simon
+01CDA01/947 Verification and Calculation of MMU Settings UMG 96 RM-P Rev.C 24.10.2014 E. Simon
+01CDA01/948 Verification and Calculation of MMU Settings UMG 96 RM-P Rev.C 24.10.2014 E. Simon
Contents
≥6
≥6
≥6
≥6
≥6
0°
0°
0°
0°
0°
GENSET CONTROL PANEL 1 GENSET CONTROL PANEL 2 GENSET CONTROL PANEL 3 GENSET CONTROL PANEL 4 GENSET CONTROL PANEL 5
00BBA01 MV BUSBAR 00BBA01 MV BUSBAR 00BBA01 MV BUSBAR 00BBA01 MV BUSBAR 00BBA01 MV BUSBAR
G 01MKA01
G 02MKA01
G 03MKA01
G 04MKA01
G 05MKA01
~ ALTERNATOR
~ ALTERNATOR
~ ALTERNATOR
~ ALTERNATOR
~ ALTERNATOR
Transport Unit Transport Unit Transport Unit Transport Unit Transport Unit Loose supplied Parts
3839
215
79 640 160
2.500 LEGEND
1: Panel Label
2.400 2: -304P1 Voltmeter - Alternator Voltage
3: -306P1 Ammeter - Alternator Current
4: -314P1 Double Voltmeter - Synchronization Voltage
2.300 5: -314P2 Double Frequency Meter - Synchronization Frequency
6: -314P3 Synchronoscope
2.200
7: -304S1 Voltage Selector Switch - Alternator Voltage
8: -312P1 Multifunctional Monitoring Unit (MMU)
9: -316A2 Automatic Synchronization Unit
2.100 Front View 10: -216A1 Touch Panel PC
100 11: -224S1 Push Button Blue - Lamp Test
12: -224S2 Push Button Black - Acknowledge/Reset
2.000
13: -510S1 Push Button - Emergency Stop
GENSET CONTROL PANEL 1 23
1 14: -226S1 Control Switch - Manual Setting Voltage, Power Factor Lower/0/Higher
1.900 2 3 4 5 6 15: -226S2 Control Switch - Manual Setting Speed, Frequency, Load Lower/0/Higher
16: -224S3 Selector Switch - Local Synchronization Manual/OFF/Automatic
17: -224S4 Selector Switch - Operation Mode GCP/SCADA
1.800
7 8 9 18: -242H4 LED Position Indicator - Alternator Circuit Breaker
19: -224S6 Push Button Green - Alternator CB ON
1.700 20: -224S5 Push Button Red - Alternator CB OFF
21: -500F1 Alternator Protection Relay
10
22: -242H6 LED Position Indicator - Alternator Neutral Earthing Switch
1.600
23: -242H1 Signaling Column - Red=Engine Stopping/Standstill
-242H2 Signaling Column - Yellow=Genset Alarm
1.500 -242H3 Signaling Column - Green=Engine Starting/Running
24: -242H5 LED Position Indicator - Alternator Earthing Switch
1.400
100: -160M1.1 Top Filter
101: -160M1 Filter Ventilator
1.300
11 12
00BBA MV BUSBAR
1.200 13
14 15 16 17 19
1.100 18 20
21
1.000 24 G 01MKA01
~ ALTERNATOR
900 22
800
700
600
500
400
101
300
200
100
0
Panel Designation
Horizontally centralized black adhesive capital letters, character size 20mm:
Top View
-160E1
384
285
-160S2
600
120
160
800
2310
2000
65
145
Cable Entry
Movable Plate
Cable Clamp Rail 475
Cu Busbar 30x5
(NIEDAX)
A A
-242H3
-242H2
-242H1
-160M1.1
2.000
Back Wall
1.800 25x80
-304S1
-316A2
1.700
-312P1
1.600
1.500
-216A1
1.400
1.300
25x80
-224S2 -224S1
1.200
-224S6 -224S4 -224S3 -226S2 -226S1 -510S1
-242H4
1.100 -224S5
-242H5 -500F1
1.000 40x80
40x80
-242H6
900
Spot to fix
Tube for
Door Wiring
800
40x80
E
PL
AM
700
EX
Alternator
Rated Current: 1A
Rated Frequency: 50Hz
400
-160M1
300
200
100
Door Stay
0 100 200 300 400 500 600 700 800 900 1.000
= Earthing Strap Connection Point
Previous Page: 032 Next Page: 034
Rev.C 24.10.2014 rhoerner Edition Date 16.12.2014
Genset Control Panel GCP MAN Diesel & Turbo SE Construction Layout Drawing Number: T-06802_GCP + 01CDA01
Rev.B 24.10.2014 rhoerner Editor E. Simon
Rev.B 24.10.2014 rhoerner Checked R. Hörner
PowerES Stadtbachstr. 1 Internal Layout Page 033
Revision Date Name Edition Status Commissioning 86153 Augsburg/Germany Door, Side and Back Walls, Roof 5302272 United Cement Industrial Company Pages 175
0 1 2 3 4 5 6 7 8 9
LEGEND
Row 1 from left to right: Row 4 from left to right: Terminal Strips from bottom left
to top right:
-A100 -160K1
-A101 -244K1 -X160
Mounting Plate -A103 -244K2 -X161
-A104 -244K3 -X400
2.000
-A105 -244K4 -X401
1.900
-A106 -244K5 -X402
-A100
PS 405 10A
6ES7405-0KA02-0AA0
SIEMENS
-A101 -A103
CPU 416-2
6ES7416-2XN05-0AB0
-A104
CP 443-1
6GK7443-1EX20-0XE0
-A105
DI 32 x DC 24V
6ES7421-1BL01-0AA0
X1
-A106
DI 32 x DC 24V
6ES7421-1BL01-0AA0
X1
-A107
DI 32 x DC 24V
6ES7421-1BL01-0AA0
X1
-A108
DO 32 DC 24 V/0,5 A
6ES7422-1BL00-0AA0
X1
-A109
CP 443-1
6GK7443-1EX30-0XE0
-A107 -244K6 -X403
-A108 -244K7 -X404
INTF INTF INTF INTF -200A1
Clamping Yoke
1
EXTF EXTF EXTF
2 2 2 2
BAF BUS1F BUSF 3 3 3 3 BUSF
BATT1F BUS2F
1.800
BATT2F TXD TXD
RXD RXD
-162R1
-X149
FRCE
DC 5V MAINT MAINT MAINT
-160S1
DC 24V
RUN RUN RUN
STOP STOP STOP
-104G1 -104G2
I RUN
STOP
I
MRES
BATT.1 BATT.2
24 24 24 24
1.700
-104G1 -246K1 -X451
+ +
X1
MPI/DP
- -
BATT. INDIC 40x80
X2
DP
1.600
EXT.-BATT
5...15V DC
2
47 47 47 47
48 48 48 48
SIMATIC S7-400
1.500 60x80
-160K1 -244K1 -244K2 -244K3 -244K4 -244K5 -244K8 -246K2 -246K3 -246K4 -246K5 -246K6 -246K7 -246K8
Row 2 from left to right: -X505
1.100 60x80 Row 5 from left to right: -X506
Spot to fix
-216A2 -X507
1.000 Tube for
5
-316A1
-318K1
Door Wiring
-316A1 -X100
Row 3 from left to right: -318K1
-320K1 -320K2
900
60x80
-320K1 -X10
800 -100F1 -320K2 -X20
-X455
-104F1 -X120
700
-106F1 -X121
-X454
-X452
600
-X451
-106F2 -X123
-X450
-X450
-X100
-XPE
-106F3 -X130
-106F4 -X150
-X507
500
-X150
-106F5 -XPE
-X404
-X506
External
External
Internal
Internal
-X505
400
-X504
-106F6
-X403
-X130
300
-X402
-X503
-108F1
-X401
-X502
-X123
-108F2
200 -X400
-X161
-X501
-X121
-108F3
-X120
-X20
-108F4
100 60x80 60x80 60x80 60x80
-110F1
-X160 -X500 -X10
0
-304F1
-304Q1
-310Q1
0 100 200 300 400 500 600 700 800 900 1.000
= Earthing Strap Connection Point
Previous Page: 033 Next Page: 035
Rev.C 24.10.2014 rhoerner Edition Date 16.12.2014
Genset Control Panel GCP MAN Diesel & Turbo SE Construction Layout Drawing Number: T-06802_GCP + 01CDA01
Rev.B 24.10.2014 rhoerner Editor E. Simon
Rev.B 24.10.2014 rhoerner Checked R. Hörner
PowerES Stadtbachstr. 1 Internal Layout Mounting Plate Page 034
Revision Date Name Edition Status Commissioning 86153 Augsburg/Germany 5302272 United Cement Industrial Company Pages 175
0 1 2 3 4 5 6 7 8 9
Cu Busbar 30x5
M10 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M10
PE PE PE PE PE PE PE PE PE PE PE PE PE PE PE
min. 25mm² GNYE 16mm² Cu 16mm² Cu 16mm² Cu 16mm² Cu 16mm² Cu 16mm² GNYE 16mm² Cu 16mm² Cu 16mm² Cu 16mm² Cu 16mm² Cu 16mm² Cu 16mm² Cu 30x5mm Cu Busbar Connector
Earthing Strap Earthing Strap Earthing Strap Earthing Strap Earthing Strap Earthing Strap Earthing Strap Earthing Strap Earthing Strap Earthing Strap Earthing Strap Earthing Strap
PE PE PE PE PE PE PE PE PE PE PE PE PE
Side Wall left* Panel Frame Roof Mounting Plate Back Wall Bottom Plate 1 Bottom Plate 2 Bottom Plate 3 Door Side Wall right*
+00BAU60 +02CDA01
Equipotential Bonding
GCP
Cu Busbar 30x5
PE PE
M10
Cu Busbar
* If applicable
Previous Page: 034 Next Page: 040
Rev.C 24.10.2014 rhoerner Edition Date 16.12.2014
Genset Control Panel GCP MAN Diesel & Turbo SE Construction Layout Drawing Number: T-06802_GCP + 01CDA01
Rev.B 24.10.2014 rhoerner Editor E. Simon
Rev.B 24.10.2014 rhoerner Checked R. Hörner
PowerES Stadtbachstr. 1 Earthing Connections Overview Page 035
Revision Date Name Edition Status Commissioning 86153 Augsburg/Germany 5302272 United Cement Industrial Company Pages 175
0 1 2 3 4 5 6 7 8 9
R7 -X501 107
Option for Shutdown
-500F1 Signal by BCP
Alternator R8 -X501 207
Protection Relay
41 -X502 107 11
Option for Shutdown
-510S1 Signal by FFCP
-510S1
Emergency Stop 42 -X502 207 Emergency Stop 12
Push Button Push Button
GCP GCP
+01CDH01
Genset Interface Panel (GIP)
S11 B1 41 13 23 33
-500A1 PNOZ X3
Engine Shutdown S12 B2 42 14 24 34
23
11 -A102 51
I34.1
-500S1 ENGINE -500S1
Emergency Stop 12 SHUTDOWN Emergency Stop 52
Push Button Push Button
GIP GIP
12 14
-248K1
Engine Shutdown 11
by PLC (1) -X510 204 104 203 103
12 14
-256K1
Engine Shutdown 11
by PLC (2)
+01CDK01
SaCoS Interface Panel (SIP)
-X513 201
Option for additional
Shutdown Signal
-X513 101
DC 24V
M24-150 M24
11
-510S1
Emergency Stop 12
Push Button
GCP
-X506 102 202
+01CDH01
Genset Interface Panel (GIP)
31 24VDC-151 A2
-500S1 -502K2
Emergency Stop 32 Emergency Stop A1
Push Button from SaCoS
GIP
-X510 102 202
+01CDK01
SaCoS Interface Panel (SIP)
-X104 57 -X104 58
13 13
-502K2 -10K13
Emergency Stop 14 Safety Relay 14
from SaCoS
13
-10K17
Safety Relay 14
-X500 1 2 +.02-X501 1
+01CDC01
Engine Auxiliary Panel (EAP)
+.02-X500 1 2 +.02-X501 1
24VDC-150
Engine
Auxiliary Drives
S11 B1 41 33 13 23
+.02-500A1 PNOZ X3
Emergency Stop S12 B2 42 34 14 24
7
+.02-A103
I68.4
EMERGENCY STOP
M24-150 AUXILIARY DRIVES
+.02-X501 2
+01CDG01
Engine Radiator Panel (ERP)
+.02-X501 2
Radiator Fans
A1 12 14 22 24
+.02-500K1
A2 11 21
M24-151
24VDC-150 M24-151
41 12 14 30 24VDC-151
-500S1 -252K1
Emergency Stop 42 Alternator 11 31
Push Button Deexcitation=0
GIP
13
-500A1
PNOZ X3 14 36
Safety Chain -300T1 -A102
Engine Shutdown AVR -X1:53 55 I35.4
13 AVR WATCHDOG
A2
-502K1 DECS-200 Basler Electric ALARM -502K1
Engine Shutdown 14 Engine Shutdown A1
from SaCoS from SaCoS
MV Busbar
31 33 13 33
-224S5 -224S4 -244K7 -510S1
Alternator CB 32 Operation 34 Alternator CB 14 Emergency Stop 34
-X500 12 13 OFF Mode SCADA OFF by PLC Push Button
GCP
+00CBA01
Common Control Panel (CCP)
+.01-X501 12 13
51 13
+.01-310K5 -244K6
MV Busbar 1 52 Alternator CB 14
Breaker Failure OFF by PLC
+00BBA01.02
MV Busbar
-XDC 8 12
Alternator CB
A1 A1
Undervoltage Coil U< Tripping Coil 3
A2 A2
M110
+00BBA01.02 +00CBA01.01
MV Busbar
OFF
OFF
√3 √3 3 L2 L3 L1 L2 L3 L1
Profibus to GCP 2 to GCP 3 SUT Synchronization
Siemens
MV Busbar
* 52 A2
00BCT01GS200 38 Bearing protective device
60FL Step-Up Transformer
MV Circuit Breaker 40 Field failure (loss of excitation)
syn.
MV Busbar 00BBA01
46 Negative phase sequence current
3 +01CDA01
00BHT01GS100 49S Stator thermal protection
GCP
Station Transformer
60FL 60FL -500F1
MV Circuit Breaker 50 Instantaneous overcurrent
Alternator CB OFF by GIP Alternator K8 K7
24VDC-132 Details in Alternator CB Open/Trip Loop Protection Relay
50BF Breaker failure protection
-224S5
Alternator CB OFF
01MKY01EZ100 +00BHT01
110VDC 51 Overcurrent with time delay
14 13 32 31 62 61 K6 K5 Alternator CB
01BAC01GS001 86 Open/Trip Loop
Details
51N Ground-fault current protection
Alternator CB
14 13 Station in Protection and
syn. A1
Undervoltage
D E -224S4 Transformer Measuring Scheme 59 Overvoltage protection
U< A1 A1 SCADA Mode Station Transformer
Coil K4 K3
A2 A1 -244K7 -244K6 59N Residual voltage ground-fault protection
Tripping -306P1 34 33
Coil
Ammeter L1 Ammeter L2 Ammeter L3 Ammeter L1
A2 60FL Fuse failure monitor
Core 1: 0,5FS5 34 33 External Trip
Iprim/1A
A2 A2
K2 K1
50BF Breaker Failure +00BFA01
15VA A A A A 81 Over-, underfrequency protection
Core 2: 5P20
D 86 Lockout relay
Iprim/1A 00BHT01GS200
15VA Station Transformer 87G Differential protection
-304P1 LV Circuit Breaker
Voltmeter Voltmeter syn.
87N Earth-fault differential protection
LV Busbar 00BFA01
V V 50BF opens every Alternator CB connected to related MV Busbar
-312P1 PB DP -314P1 -314P2 -314P3 -316A1 HAS-111 -316A2 SPM-D10 (Details in Breaker Failure 50BF Scheme MV)
Multifunctional Double Double Synchrono Syn. Check Auto Syn.
11kV 110V 110V Monitoring Unit MMU Voltmeter KV/kV Frequency Hz/Hz scope Relay 25 Unit 25A
L1 L2 L3
-304S1 L1 L2 L3
OFF
OFF
01MKA01EU100 -X1 Meter
√3 √3 3 L2 L3 L1 L2 L3 L1
Deif WW
MMU Measuring
Class: 0,5 60FL 60FL Unit
Profibus -A100
Surge
01BAC01GS010 30VA
Arrester Earthing Switch DI Active Power
F3 F4 Protection Relay
* Watchdog
59N Reactive Power
24 32R 87G
Current
R5 R1
LV Part 27 40 CB Trip
Voltage
Antiparallel
Window type CT
* Damping resistor required for Open Delta VT Connection 59 46 86
1FS10
Power Factor
R2
60A/1A 87N 81 50 De-Excitation
1,25VA Frequency
+01MKA01 +01CDH01 C 51
Active Energy
Alternator
GIP
R3
Engine Shutdown
24VDC-150 B Reactive Energy
Option A1 F10
15VA 2xPT100 11 32
24
GIP Genset Interface Panel
by PLC
-502K2
3 Θ
38 14
A2
13 HV High Voltage
-256K1 -502K2 SIPROTEC 7UM621 Siemens
IEEE Institute of Electrical & Electronics Engineers, Inc.
-X1 24VDC DI
1 Unit 11 14
Profibus
Profibus DP Alternator CB Closed LV Low Voltage
ERP
Alternator 3 Alternator 2
13
-302P1 -302P1 PLC Programmable Logic Control
Details in 24VDC Multifunctional Multifunctional
110VDC SaCoS Interface Panel -10K13
-A100 Monitoring Unit -100P1 24VDC-151 Monitoring Unit -100P1 SaCoS one Safety and Control System on Engine
-X1 01CDC01EU100 01CDG01EU100
02BAU01GS001 01BAU01GS001 Redundant
NE Switch NE Switch 60FL -254K2 13 Profibus
Profibus DP
14
Voltmeter Voltmeter
DO
Y11/Y12 23 SIP SaCoS Interface Panel
-516K1 13 -516K2 13 NE Switch OFF
-10K45 13
MMU
V 33
MMU
V
ET200M Siemens Safety Relay -10K17 -X1 -X1 ST Station Transformer
14 Unit Unit
PB DP PB DP
Y10 24 Profibus Profibus
SUT Step-Up Transformer
00BAU01GL001 14 14 14
-100S1 OFF
L1 L2 L3 34 -100S1 L1 L2 L3
OFF
L2 L3 L1 L2 L3 L1
NE Resistor -516F1
25A, 10s Earth Fault Relay
-100Q1 -100Q1 VT Voltage Transformer
CB 3AC Feeder CB 3AC Feeder
MV Busbar 1 Radiator
50A/1A +01MJA01.01 Fans Electrical Connection
A1 NE Fault Current High Set
Engine
Tripping
Coil
NE Fault Current Low Set
S11 13 23 A1 14 24 Indirect Connection
A2 1SZV1012 -500A1 Option
51N Engine Shutdown PNOZ X3
-500K1
XI1-E-1 Woodward Valve Indirect Operative Connection
S12 14 24 A2 11 21
Engine from LV Busbar 00BFA01 from LV Busbar 00BFA01 Operative Connection
Auxiliary Drives
SWITCH SETTINGS
ON Terminating Resistor ON
OFF Terminating Resistor OFF
-200A1
Optical Link ON
Module -X1 A1 B1 OFF A2 B2
-W5.INT
2x0.64 GN RD
-A103
CPU 416-2 -X1 A1 B1 ON
OFF A2 B2
-W6.INT
2x0.64 GN RD
-312P1
UMG 96 RM-P -X1 A1 B1 ON
Panel Door OFF A2 B2
-W9.INT
2x0.64 GN RD
-500F1
SIPROTEC 4 -X1 A1 B1 ON
Panel Door OFF A2 B2
Ethernet Connection
-W7.INT
Patch cable RJ45 CAT.5e
3m
-216A1 -A104
Panel PC CP443-1
ETH ETH P1 P2
Panel Door
Power Supply
Panel Equipment
AC 230V
2,5mm² BK AC 230V
L1 / 160.0
N / 160.0
2 13 21
-100F1
B 10A 1 14
/218.1 22
-X10 1 2 3
+00BJB01
AC Distribution Panel (ACDP)
-W319
NYY-J
3x2.5 BN BU GNYE
-X369 1 2 4
AC 230V
16A
UPS
Power Supply
AC 230V
AC 230V
VPS.UPS-L1 / 104.0
VPS.UPS-N / 104.0
-X20 1 2 3
+00BRA01
UPS System - Distribution
-W310
NYY-J
3x2.5 BN BU GNYE
-X20.06 L2 N PE
AC 230V
16A
Cross Connection
M24-100 / 106.0
M24-100 / 110.9
1 3 13 21
-104F1
C 10A 2 4 14 22
/218.2
PE Cross Connection
6mm² GNYE
-X20 4 -X100 19 1 15 16 20 14
1,5mm² BK 1,5mm² LBU 1,5mm² GNYE 4mm² RD 4mm² BU Ringline 4mm² BU Ringline 4mm² RD 4mm² BU
PE
-104G1 -104G2
24V/20A Jump A B Buffer Module
1 120V AC 2 L1 N(L2) PE L+ L+ M M ON L+ M
OFF
INPUT OUTPUT
AC 120V - 230V 50/60Hz DC 24V 20A
ON Parallel Operation
A OFF Single Operation
ON Shut Down
B OFF Constant Current
Power Supply Power Supply Spare Digital I/Os Power Supply Power Supply
OLM, PS DI/DO Modules Internal Contacts Panel PC Internal Control Voltage
4mm² RD Ringline Comb Busbar Comb Busbar Comb Busbar Comb Busbar Comb Busbar Comb Busbar
104.9 / 24VDC-100 24VDC-100 / 108.0
1 13 21 1 13 21 1 13 21 1 13 21 1 13 21 1 13 21
-106F1 -106F2 -106F3 -106F4 -106F5 -106F6
B 6A 2 14 22 A 2A 2 14 22 A 2A 2 14 22 A 2A 2 14 22 B 10A 2 14 22 A 2A 2 14 22
/218.3
/218.5
/218.5
1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm²
RD RD RD RD RD RD RD RD RD
24VDC-124 / 216.0
Integrated Cross Connection
24VDC-123 / 160.0
24VDC-122 /
Integrated Cross Connection
24VDC-121 / 242.0
Integrated Cross Connection
24VDC-120 / 200.0
M24-122 /
Integrated Cross Connection
M24-123 / 160.0
M24-124 / 216.0
Integrated Cross Connection
M24-130 / 312.5
1,5mm² 1,5mm² BU 1,5mm² 1,5mm² BU 0,75mm² BU 1,5mm² 1,5mm² BU 1,5mm² BU 1,5mm² 1,5mm² BU
BU BU BU BU
-X100 2 3 4 5 6 7
Cross Connection
104.9 / M24-100 M24-100 / 108.0
1 13 21 1 13 21 1 13 21 1 13 21
-108F1 -108F2 -108F3 -108F4
A 2A 2 14 22 A 2A 2 14 22 A 2A 2 14 22 A 2A 2 14 22
/218.6
/218.7
/220.1
/220.2
1,5mm² RD 1,5mm² RD 1,5mm² RD 1,5mm² RD
24VDC-134 / 236.0
24VDC-133 / 234.0
24VDC-132 / 230.0
24VDC-131 / 228.0
M24-132 / 320.0
1mm² BU
-X100 8 9 10 11 12
Cross Connection
106.9 / M24-100 M24-100 / 110.0
Power Supply
Alternator Protection,
CB Control
1 13 21
-110F1
A 2A 2 14 22
/220.3
1,5mm² RD
-X150 A1 B1
-X150 C1 D1
1,5mm² 1,5mm² BU
BU
-X100 13
Cross Connection
108.9 / M24-100 M24-100 / 104.9
-X160 2
1,5mm² BK
-X161 1
-W3.INT
12 14 /160.6
-160K1 ÖLFLEX CLASSIC 110
2x1 1
/160.7 11
Panel Door
Closed 1,5mm² BK
1 13 21
-160S1 -160S2
Temperature 2 Door-Operated Switch 14 22
PE PE
0-60°C
30°C
-W3.INT
1,5mm² BK /160.6 2
-X160 1 6 11 3 7 12 -X161 2
-W1.INT -W2.INT
Pre-Assembled ÖLFLEX CLASSIC 110 G
3x1.5 BN BU GNYE 3x1 1 2 GNYE 1mm² RD
-160E1
-X1 L N PE -X2 L PE N
L1 N
1 -160M1
M
Door-Operated
230V 1~
Switch
40W PE
2
183m³/h
Panel Door A1
L PE N
18W
-160K1
-160M1.1 Panel Door
Top Filter Closed
Panel Roof A2
1mm² BU
-X123 C2
01CDA01CT001-XQ01
GCP Internal Panel
Temperature
+00CBA01.01
-W1025
H05VVC4V5-K
5G1.5 WH BN GN YE PE
-X500 14 15 16 17
-W4.INT
UNITRONIC LIYCY
4x0.75 WH BN GN YE PE
-162R1 1 3 2 4
-50°C ... +100°C
PT100
-X120 A2 C2
I2.0
-X123 A3 A105:27 / 222.1
+01CDG01
-W2000
GIP
0 1 RESERVED
1 1 RED, RING ON ON A-VQ(ZN)HB2Y -202A1
2x200/230PCF
S5 S6 OUTPUT POWER CH2 / CH3 Fiber Optic Profibus
0 STANDARD Out
1 HIGH
CH2
S7 COMPATIBILITY MODE
In
0 DEFAULT
1 SINEC L2FO
-W5.INT
S8 MODE CH0 MON. SEG. UNITRONIC BUS
0 BUS ON ON 2x0.64 GN RD
1 BUS OFF OFF
-200A1
24V DC -X1 A1 B1 ON A2 B2
In Out In Out
L1+ F1 M F2 L2+ CH2 CH3
OFF -X2 -X3 -X4 -X5
S8 S0 S1 S2 S3 S4 S5 S6 S7
1
0
Fault
SWITCH SETTINGS
ON Terminating Resistor ON
OFF Terminating Resistor OFF
SIEMENS X1 X1 X1 X1
FRCE
DC 5V MAINT MAINT MAINT
DC 24V
RUN RUN RUN
STOP STOP STOP
FMR
I RUN
STOP
I
MRES
BATT.1 BATT.2
24 24 24 24
+ +
X1
MPI/DP
- -
BATT. INDIC
2 BATT.
OFF
1 BATT.
X2
DP
EXT.-BATT
5...15V DC
47 47 47 47
PE 48 48 48 48
SIMATIC S7-400
10mm² GNYE
PE
-A105
Rack 1
Slot 5
SIE.6ES7421-1BL01-0AA0
S7-400 SIEMENS
SM 421 DI 32 x DC 24V
-X1:1 -X1:25
-X1:2 -X1:26
-X1:3 -X1:27
I2.0 /222.1 -200A1:F2 01CDA01GN001-XM90 Optical Link Module (OLM) Fault
-X1:4 L+ -X1:28
01CDA01GS015-XM76 Power Supply Panel Equipment MCB OFF -100F1:14 /218.1 I0.0 I2.1 /222.2 Spare
-X1:5 -X1:29
01CDA01GS013-XM76 UPS Power Supply DC 24V PS Unit MCB OFF -104F1:14 /218.2 I0.1 I2.2 /222.3 Spare
-X1:6 -X1:30
01CDA01GW031-XM76 Power Supply DI/DO Modules MCB OFF -106F2:14 /218.3 I0.2 I2.3 /222.4 -500F1:F4 01MKY01EZ100-XM90 Alternator Protection Relay Watchdog
-X1:7 -X1:31
Spare /218.4 I0.3 I2.4 /222.5 -500F1:R1 01MKY01EZ100-XK11 Alternator Protection Relay Alternator CB Trip
-X1:8 -X1:32
01CDA01GW071-XM76 Power Supply Panel PC MCB OFF -106F5:14 /218.5 I0.4 I2.5 /222.5 -500F1:R2 01MKY01EZ100-XK12 Alternator Protection Relay Altern. De-Excitation
-X1:9 -X1:33
01CDA01GW041-XM76 Power Supply Internal Control Voltage MCB OFF -106F6:14 /218.5 I0.5 I2.6 /222.6 -500F1:R3 01MKY01EZ100-XK13 Alternator Protection Relay Engine Shutdown
-X1:10 -X1:34
01CDA01GW091-XM76 External Signals from CCP MCB OFF -108F1:14 /218.6 I0.6 I2.7 /222.7 01MKY01EZ100-XK14 Alternator Protection Relay Spare
-X1:11 -X1:35
01BAC01GS003-XM76 External Signals from Alternator CB MCB OFF -108F2:14 /218.7 I0.7
-X1:12 -X1:36
-X1:13 -X1:37
-X1:14 -X1:38
-X1:15 -X1:39
01CDA01GW093-XM76 External Signals from BCP MCB OFF -108F3:14 /220.1 I1.0 I3.0 /224.1 -224S1:14 01CDA01GH001-YA19 Lamp Test
-X1:16 -X1:40
01CDA01GW094-XM76 External Signals from FFCP MCB OFF -108F4:14 /220.2 I1.1 I3.1 /224.2 -224S2:14 01CDA01GH001-YA20 Acknowledge/Reset
-X1:17 -X1:41
01CDA01GW072-XM76 PS Altern. Protection, CB Control MCB OFF -110F1:14 /220.3 I1.2 I3.2 /224.3 -224S3:14 01CDA01GH001-YA88 Local Synchronization in Manual Position
-X1:18 -X1:42
00BBA01CE011-XM96 Measuring MV Busbar Voltage CB OFF -310Q1:14 /220.4 I1.3 I3.3 /224.4 -224S3:24 01CDA01GH001-YA89 Local Synchronization in Automatic Position
-X1:19 -X1:43
01BAC01GW001-XM86 Measuring Alternator Voltage CB OFF -304Q1:14 /220.5 I1.4 I3.4 /224.5 -224S4:12 01CDA01GH001-YA42 Selector Switch GCP / SCADA in GCP Position
-X1:20 -X1:44
01BAC01CE011D-XM76 Alternator Open Delta Voltage MCB OFF -304F1:14 /220.5 I1.5 I3.5 /224.5 -224S4:24 01CDA01GH001-YA43 Selector Switch GCP / SCADA in SCADA Position
-X1:21 -X1:45
01CDA01EZ500-XA37 Emergency Stop Push Button at GCP Pushed -510S1:24 /220.6 I1.6 I3.6 /224.6 -224S5:12 01BAC01GS003-YB12 Push Button Alternator CB OFF
-X1:22 -X1:46
01CDA01GH001-XM10 Panel Door is Opened -160K1:21 /220.7 I1.7 I3.7 /224.7 -224S6:14 01BAC01GS003-YB11 Push Button Alternator CB ON
-X1:23 -X1:47
-X1:24 M -X1:48
/224.8
M
6ES7421-1BL01-0AA0
6ES7492-1AL00-0AA0
-A106
Rack 1
Slot 6
SIE.6ES7421-1BL01-0AA0
S7-400 SIEMENS
SM 421 DI 32 x DC 24V
-X1:1 -X1:25
-X1:2 -X1:26
-X1:3 -X1:27
I6.0 /230.1 +00BBA01.02-KFA11:14 01BAC01GS003-XB41 Alternator CB in Test Position
-X1:4 L+ -X1:28
01CDA01GH001-YA76 Manual Setting Voltage, Power Factor Lower -226S1:14 /226.1 I4.0 I6.1 /230.2 +00BBA01.02-KFA12:14 01BAC01GS003-XB40 Alternator CB in Operating Position
-X1:5 -X1:29
01CDA01GH001-YA75 Manual Setting Voltage, Power Factor Higher -226S1:24 /226.2 I4.1 I6.2 /230.3 +00BBA01.02-FCM2.1:14 01BAC01GW001-XM84 Alternator Control Voltage MCB OFF
-X1:6 -X1:30
01CDA01GH001-YA78 Manual Setting Speed, Frequency, Active Power Lower -226S2:14 /226.3 I4.2 I6.3 /230.4 +00BBA01.02-FCM14.1:14 01BAC01CE011-ZM85 Alternator Voltage Measuring MCB OFF
-X1:7 -X1:31
01CDA01GH001-YA77 Manual Setting Speed, Frequency, Active Power Higher -226S2:24 /226.4 I4.3 I6.4 /230.5 +00BBA01.02-01BAC01GS008:2901BAC01GS008-XB02 Alternator Earthing Switch is Opened
-X1:8 -X1:32
01CDA01GX102-YA77 Automatic Syn. Frequency Setting Higher -316A2:9 /226.5 I4.4 I6.5 /230.5 +00BBA01.02-01BAC01GS008:4901BAC01GS008-XB01 Alternator Earthing Switch is Closed
-X1:9 -X1:33
01CDA01GX102-YA78 Automatic Syn. Frequency Setting Lower -316A2:10 /226.5 I4.5 I6.6 /230.6 +LVD-SFS1:12 01BAC01GS003-XB43 Alternator CB in Remote Position
-X1:10 -X1:34
01CDA01GX102-YA75 Automatic Syn. Voltage Setting Higher -316A2:12 /226.6 I4.6 I6.7 /230.7 -320K2:11 01BAC01GS003-XB01 Alternator CB is Closed
-X1:11 -X1:35
01CDA01GX102-YA76 Automatic Syn. Voltage Setting Lower -316A2:13 /226.7 I4.7
-X1:12 -X1:36
-X1:13 -X1:37
-X1:14 -X1:38
-X1:15 -X1:39
01CDA01GX100-YA78 MV BB 00BBA01 Frequency Setting Lower from CCP +00CBA01.01-310K1:11 /228.1 I5.0 I7.0 /232.1 Spare
-X1:16 -X1:40
01CDA01GX100-YA77 MV BB 00BBA01 Frequency Setting Higher from CCP +00CBA01.01-310K2:11 /228.2 I5.1 I7.1 /232.2 Spare
-X1:17 -X1:41
01CDA01GX100-YA76 MV BB 00BBA01 Voltage Setting Lower from CCP +00CBA01.01-310K3:11 /228.3 I5.2 I7.2 /232.3 Spare
-X1:18 -X1:42
01CDA01GX100-YA75 MV BB 00BBA01 Voltage Setting Higher from CCP +00CBA01.01-310K4:11 /228.4 I5.3 I7.3 /232.4 Spare
-X1:19 -X1:43
01CDA01GX100-YA73 Genset in Grid Parallel Operation +00CBA01.01-266K2:11 /228.5 I5.4 I7.4 /232.5 -320K1:11 01BAC01GS003-XB02 Alternator CB is Opened
-X1:20 -X1:44
01CDA01GX100-YA72 Block Synchronization from CCP +00CBA01.01-266K3:11 /228.5 I5.5 I7.5 /232.5 Spare
-X1:21 -X1:45
Spare +00CBA01.01-X501:8 /228.6 I5.6 I7.6 /232.6 Spare
-X1:22 -X1:46
Spare +00CBA01.01-X501:9 /228.7 I5.7 I7.7 /232.7 Spare
-X1:23 -X1:47
-X1:24 M -X1:48
/232.8
M
6ES7421-1BL01-0AA0
6ES7492-1AL00-0AA0
-A107
Rack 1
Slot 6
SIE.6ES7421-1BL01-0AA0
S7-400 SIEMENS
SM 421 DI 32 x DC 24V
-X1:1 -X1:25
-X1:2 -X1:26
-X1:3 -X1:27
I10.0 /238.1 Spare
-X1:4 L+ -X1:28
Spare -X501:201 /234.1 I8.0 I10.1 /238.2 Spare
-X1:5 -X1:29
Spare -X501:202 /234.2 I8.1 I10.2 /238.3 Spare
-X1:6 -X1:30
Spare -X501:203 /234.3 I8.2 I10.3 /238.4 Spare
-X1:7 -X1:31
Spare -X501:204 /234.4 I8.3 I10.4 /238.5 Spare
-X1:8 -X1:32
Spare /234.5 I8.4 I10.5 /238.5 Spare
-X1:9 -X1:33
Spare /234.5 I8.5 I10.6 /238.6 Spare
-X1:10 -X1:34
Spare /234.6 I8.6 I10.7 /238.7 Spare
-X1:11 -X1:35
Spare /234.7 I8.7
-X1:12 -X1:36
-X1:13 -X1:37
-X1:14 -X1:38
-X1:15 -X1:39
-X502:201 /236.1 I9.0 I11.0 /240.1 Spare
-X1:16 -X1:40
Spare -X502:202 /236.2 I9.1 I11.1 /240.2 Spare
-X1:17 -X1:41
Spare -X502:203 /236.3 I9.2 I11.2 /240.3 Spare
-X1:18 -X1:42
Spare -X502:204 /236.4 I9.3 I11.3 /240.4 Spare
-X1:19 -X1:43
Spare /236.5 I9.4 I11.4 /240.5 Spare
-X1:20 -X1:44
Spare /236.5 I9.5 I11.5 /240.5 Spare
-X1:21 -X1:45
Spare /236.6 I9.6 I11.6 /240.6 Spare
-X1:22 -X1:46
Spare /236.7 I9.7 I11.7 /240.7 Spare
-X1:23 -X1:47
-X1:24 M -X1:48
/240.8
M
6ES7421-1BL01-0AA0
6ES7492-1AL00-0AA0
-A108
Rack 1
Slot 8
SIE.6ES7422-1BL00-0AA0
S7-400 SIEMENS
SM 422 DO 32 DC 24 V/0,5 A
-X1:1 3L+ -X1:25
3L+
-X1:2 3L+ -X1:26
3L+
-X1:3 1L+ -X1:27
/242.1 Q2.0 /246.1 -246K1:A1 01BAC01GS008-YB15 Release Alternator Earthing Switch
1L+
-X1:4 -X1:28
01CDA01EH001-YA25 Indication Light Engine Stopping/Standstill -242H1:3 /242.1 Q0.0 Q2.1 /246.2 -246K2:A1 01MKY01EZ100-YA50 Block Voltage and Frequency Supervision
-X1:5 -X1:29
01CDA01EH001-YA26 Indication Light Genset Alarm/Shutdown -242H2:2 /242.2 Q0.1 Q2.2 /246.3 -246K3:A1 01MKY01EZ100-YA51 Block Excitation Fault
-X1:6 -X1:30
01CDA01EH001-YA27 Indication Light Engine Starting/Running -242H3:1 /242.3 Q0.2 Q2.3 /246.4 -246K4:A1 Spare Relay
-X1:7 -X1:31
01BAC01GS003-YA27 Position Indicator Alternator CB Synchronization/Closed -242H4:G /242.4 Q0.3 Q2.4 /246.5 -246K5:A1 01MKY01EZ100-YA53 Alternator CB External Trip by PLC
-X1:8 -X1:32
01BAC01GS003-YA25 Position Indicator Alternator CB Opening/Opened -242H4:R /242.5 Q0.4 Q2.5 /246.5 -246K6:A1 01MKY01EZ100 Spare for Alternator Protection Relay
-X1:9 -X1:33
01BAC01GS008-YA27 Position Indicator Alt. Earthing Switch Closed -242H5:G /242.5 Q0.5 Q2.6 /246.6 -246K7:A1 Spare Relay
-X1:10 -X1:34
01BAC01GS008-YA25 Position Indicator Alt. Earthing Switch Opened -242H5:R /242.6 Q0.6 Q2.7 /246.7 -246K8:A1 Spare Relay
-X1:11 -X1:35
01BAU01GS001-YA27 Position Indicator Alternator NE Switch Closed -242H6:G /242.7 Q0.7
-X1:12 -X1:36
-X1:16 -X1:40
01CDA01GH001-YA93 Synchronization Manual or Autom. Selected -244K2:A1 /244.2 Q1.1 Q3.1 /248.2 Spare
-X1:17 -X1:41
01CDA01GH001-YA94 Manual Synchronization Release -244K3:A1 /244.3 Q1.2 Q3.2 /248.3 Spare
-X1:18 -X1:42
01CDA01GH001-YA95 Automatic Synchronization Release -244K4:A1 /244.4 Q1.3 Q3.3 /248.4 Spare
-X1:19 -X1:43
Spare /244.5 Q1.4 Q3.4 /248.5 Spare
-X1:20 -X1:44
01BAC01GS003-YB32 Alternator CB OFF by PLC (Open/Trip Loop) -244K6:A1 /244.5 Q1.5 Q3.5 /248.5 Spare
-X1:21 -X1:45
01BAC01GS003-YB02 Alternator CB OFF Command by PLC (Tripping Coil) -244K7:A1 /244.6 Q1.6 Q3.6 /248.6 Spare
-X1:22 -X1:46
Spare Relay -244K8:A1 /244.7 Q1.7 Q3.7 /248.7 Spare
-X1:23 -X1:47
-X1:24 M -X1:48
/248.8
M
6ES7422-1BL00-0AA0
6ES7492-1AL00-0AA0
PE
-X120 C3 A3 -XPE 2
-A101
Rack 1 M L+ PE
Slot 1 -G1 -G2
Buffer Battery Buffer Battery
Central Processing
Unit
+00CBA01.04
Common Control Panel (CCP)
+00CBA01.04-W2500
UNITRONIC BUS -A103
2x0.64
Copper Profibus -X1
A1
GN
B1
RD
+02CDA01
Genset Control Panel (GCP)
-W2002
UNITRONIC BUS -A102
2x0.64
Copper Profibus -X2
A1
GN
B1
RD
-W6.INT
UNITRONIC BUS
2x0.64 GN RD
-A103
-X1 A1 B1 ON A2 B2 -X2 A1 B1 ON A2 B2
Rack 1
-D1 OFF OFF
Slot 3
Memory Card
4MB
212.9 / 24VDC-120
106.9 / 24VDC-124
212.9 / M24-120
106.9 / M24-124
-X120 A4 C4
PE
1,5mm² 1,5mm²
RD BU
-X100 17
M1
M2
L2+
F1
F2
-216A1 1
24VDC
2
PE
3
0VDC
Scalance Panel Door
N8 P5
-X6
LAN3
P1 -W3051
A-DQ(ZN)B2Y -X5 Panel PC 21,5"
1 2 3 4
P2 P5
1 2 3 4
-X4
LAN1 1 2 3 4
COM 1
RS232
1 2 3 4 1 2 3 4
P3
P6 DVG-OPC7022-059-HW PE
P4
6mm² GNYE
-W15.INT -W7.INT
Patch cable RJ45 CAT.5e -W3050 Patch cable RJ45 CAT.5e
2m Patch cable RJ45 CAT.5e 3m
4x2xAWG24 4x2xAWG24/1 4x2xAWG24/1
-A109 -A104
Rack 1 Rack 1
Slot 9 P1 P2 Slot 4 P1 P2
13 13 13 13 13 13 13
-100F1 -104F1 -106F2 -106F5 -106F6 -108F1 -108F2
/100.1 14 /104.2 14 /106.2 14 /106.5 14 /106.6 14 /108.1 14 /108.2 14
01CDA01GS015-XM76 01CDA01GS013-XM76 01CDA01GW031-XM76 01CDA01GW071-XM76 01CDA01GW041-XM76 01CDA01GW091-XM76 01BAC01GS003-XM76
Power Supply UPS Power Supply Power Supply Power Supply Power Supply External Signals External Signals from
Panel Equipment DC 24V PS Unit DI/DO Modules Panel PC Internal Control Voltage from CCP Alternator CB
MCB OFF MCB OFF MCB OFF MCB OFF MCB OFF MCB OFF MCB OFF
0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD
-A105
/204.3 -X1 4 5 6 7 8 9 10 11
Rack 1 I0.0 I0.1 I0.2 I0.3 I0.4 I0.5 I0.6 I0.7
Slot 5 /204.3 /204.3 /204.3 /204.3 /204.3 /204.3 /204.3 /204.3
MCB OFF=0 MCB OFF=0 MCB OFF=0 MCB OFF=0 MCB OFF=0 MCB OFF=0 MCB OFF=0
13 13 13 13 13 13 23 22 24
-108F3 -108F4 -110F1 -310Q1 -304Q1 -304F1 -510S1 -160K1
/108.3 14 /108.4 14 /110.1 14 /310.1 14 /304.3 14 /304.1 14 /510.2 24 /160.7 21
01CDA01GW093-XM76 01CDA01GW094-XM76 01CDA01GW072-XM76 00BBA01CE011-XM96 01BAC01GW001-XM86 01BAC01CE011D-XM76 EZ500 Panel Door
External Signals External Signals PS Altern. Protection, Measuring Measuring Alternator Emergency Stop Closed
from BCP from FFCP CB Control MV Busbar Voltage Alternator Voltage Open Delta Voltage Push Button
MCB OFF MCB OFF MCB OFF CB OFF CB OFF MCB OFF Panel Door
0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD
-A105
/204.3 -X1 15 16 17 18 19 20 21 22
Rack 1 I1.0 I1.1 I1.2 I1.3 I1.4 I1.5 I1.6 I1.7
Slot 5 /204.3 /204.3 /204.3 /204.3 /204.3 /204.3 /204.3 /204.3
MCB OFF=0 MCB OFF=0 MCB OFF=0 CB OFF=0 CB OFF=0 MCB OFF=0 Door Opened=0
A105:30 / 504.2
A105:31 / 504.5
A105:32 / 504.5
200.9 / A105:27 A105:33 / 504.5
0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD 0,75mm² RD
-A105
/204.3 -X1 27 28 29 30 31 32 33 34
Rack 1 I2.0 I2.1 I2.2 I2.3 I2.4 I2.5 I2.6 I2.7
Slot 5 /204.6 /204.6 /204.6 /204.6 /204.6 /204.6 /204.6 /204.6
Fault=0 Alarm=0
1mm² RD 0,75mm² BU
13 21 13 21 13 23 11 23 11 13 31
1 0 2
/322.2
Panel Door Panel Door Panel Door 2=SCADA
Panel Door
13 21
-224S6
Green 14 22
Panel Door
-A105 M
/204.3 -X1 39 40 41 42 43 44 45 46 48
Rack 1 I3.0 I3.1 I3.2 I3.3 I3.4 I3.5 I3.6 I3.7 /204.6
Slot 5 /204.6 /204.6 /204.6 /204.6 /204.6 /204.6 /204.6 /204.6
CB OFF=0
-X123 B5
1mm² RD
1mm² RD 1mm² RD 1mm² RD 1mm² RD 1mm² RD
13 13 8 11
1 0 2
23 1 0 2
23
-226S1 1 2 -226S2 1 2 -316A2
/316.4
1=Lower 14 24 1=Lower 14 24
2=Higher 2=Higher Automatic
Syn. Unit
Panel Door Panel Door
9 10 12 13
-A106
/206.3 -X1 4 5 6 7 8 9 10 11
Rack 1 I4.0 I4.1 I4.2 I4.3 I4.4 I4.5 I4.6 I4.7
Slot 6 /206.3 /206.3 /206.3 /206.3 /206.3 /206.3 /206.3 /206.3
-X500 1
-W1000
/228.1
H05VV5-F
12G1.5 1
+00CBA01.01
Common Control Panel (CCP)
-X501 1
12 14
-266K1
GCP 1 11
V/F Setting
Release
12 14 12 14 12 14 12 14 12 14 12 14
-310K1 -310K2 -310K3 -310K4 -266K2 -266K3
MV Busbar 1 11 MV Busbar 1 11 MV Busbar 1 11 MV Busbar 1 11 Genset 11 Block 11
Frequency Setting Frequency Setting Voltage Setting Voltage Setting in Grid Synchronization
Lower Higher Lower Higher Parallel Operation from CCP
-X501 2 3 4 5 6 7 8 9
-W1000
/228.1
300 2 3 4 5 6 7 8 9
-X500 2 3 4 5 6 7 8 9
-A106
/206.3 -X1 15 16 17 18 19 20 21 22
Rack 1 I5.0 I5.1 I5.2 I5.3 I5.4 I5.5 I5.6 I5.7
Slot 6 /206.3 /206.3 /206.3 /206.3 /206.3 /206.3 /206.3 /206.3
-X123 B6
0,75mm² RD
12 14
-W1001 -320K2
/230.1 /320.3
/320.1 01BAC01GS003-XB01 11
/320.1 -X503 101 102 103 104 105 106 107 108 Alternator CB
H05VV5-F is Closed
25G1.5 1 2 3 4 5 6 7 8
+00BBA01.02
MV Busbar
13
-FCM11.4
13 13 13 /304.3 14 28 48 11
-KFA11 -KFA12 -FCM2.1 01BAC01GS008 +LVD-SFS1
14 14 /322.1 14 13 /302.8 29 /302.9 49 12
-FCM14.1
/304.2 14
-W1001
/230.1 13 14 15 16 17 18 19 20
-A106
/206.3 -X1 27 28 29 30 31 32 33 34
Rack 1 I6.0 I6.1 I6.2 I6.3 I6.4 I6.5 I6.6 I6.7
Slot 6 /206.6 /206.6 /206.6 /206.6 /206.6 /206.6 /206.6 /206.6
-X123 B7 -X121 C3
0,75mm² RD 0,75mm² BU
12 14
-320K1
/320.1 11
01BAC01GS003-XB02
Alternator CB
is Opened
0,75mm² RD
-A106 M
/206.3 -X1 39 40 41 42 43 44 45 46 48
Rack 1 I7.0 I7.1 I7.2 I7.3 I7.4 I7.5 I7.6 I7.7 /206.6
Slot 6 /206.6 /206.6 /206.6 /206.6 /206.6 /206.6 /206.6 /206.6
1,5mm² RD
108.9 / 24VDC-133
Cross Connection
-A107
/208.3 -X1 4 5 6 7 8 9 10 11
Rack 1 I8.0 I8.1 I8.2 I8.3 I8.4 I8.5 I8.6 I8.7
Slot 7 /208.3 /208.3 /208.3 /208.3 /208.3 /208.3 /208.3 /208.3
1,5mm² RD
108.9 / 24VDC-134
Cross Connection
-A107
/208.3 -X1 15 16 17 18 19 20 21 22
Rack 1 I9.0 I9.1 I9.2 I9.3 I9.4 I9.5 I9.6 I9.7
Slot 7 /208.3 /208.3 /208.3 /208.3 /208.3 /208.3 /208.3 /208.3
-A107
/208.3 -X1 27 28 29 30 31 32 33 34
Rack 1 I10.0 I10.1 I10.2 I10.3 I10.4 I10.5 I10.6 I10.7
Slot 7 /208.6 /208.6 /208.6 /208.6 /208.6 /208.6 /208.6 /208.6
-X121 C4
0,75mm² BU
-A107 M
/208.3 -X1 39 40 41 42 43 44 45 46 48
Rack 1 I11.0 I11.1 I11.2 I11.3 I11.4 I11.5 I11.6 I11.7 /208.6
Slot 7 /208.6 /208.6 /208.6 /208.6 /208.6 /208.6 /208.6 /208.6
-X1
3 4 5 6 7 8 9 10 11
1L+
-X149 1 2 3
-W8.INT
/242.1
ÖLFLEX CLASSIC 110
4x1 1 2 3
3 2 1
-242H1 -242H2 -242H3
24V AC/DC 0 24V AC/DC 0 24V AC/DC 0
Red Yellow Green
Panel Roof Panel Roof Panel Roof
G R G R G R
-242H4 -242H5 -242H6
Panel Door GN RD Panel Door GN RD Panel Door GN RD
-X149 4
- - -
0,75mm² BU 0,75mm² BU
0,75mm² BU 0,75mm² BU
0,75mm² BU
-X121 A2
-X123
Integrated Cross Connection
C3 C4
106.9 / 24VDC-121 24VDC-121 / 244.0
Integrated Cross Connection
160.9 / M24-123 M24-123 / 244.0
Lamp Test by PLC Lamp Test by PLC Lamp Test by PLC Lamp Test by PLC Lamp Test by PLC Lamp Test by PLC Lamp Test by PLC Lamp Test by PLC
5 seconds 5 seconds 5 seconds 5 seconds 5 seconds 5 seconds 5 seconds 5 seconds
-X1
13 14 15 16 17 18 19 20 21 22
2L+ 2L+
242.9 / A108:15
42 44 42 44
-244K1 -244K4
/244.1 41 /244.4 41
A1 A1 A1 A1 A1 A1 A1 A1
-244K1 -244K2 -244K3 -244K4 -244K5 -244K6 -244K7 -244K8
Busbar Alternator Busbar Alternator U U
A2 A2 A2 A2 A2 A2 A2 A2
0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU
-X121 A3
-X123
Integrated Cross Connection
C5 C6 C7 C8 C9 C10 C11 C12
242.9 / 24VDC-121 24VDC-121 / 246.0
Integrated Cross Connection
242.9 / M24-123 M24-123 / 246.0
14 11 /314.1 14 11 /314.3 14 11 /318.2 14 11 /316.5 14 11 /316.4 13 14 /322.2 13 14 /322.6 14 11
12 12 12 12 12 21 22 21 22 12
24 21 /314.1 24 21 /314.3 24 21 24 21 /316.5 24 21 /316.4 31 32 31 32 24 21
22 22 22 22 22 43 44 43 44 22
34 31 /314.2 34 31 /314.3 34 31 34 31 /316.6 34 31 /316.4 34 31
32 32 32 32 32 32
44 41 /244.2 44 41 44 41 44 41 /244.5 44 41 /316.8 44 41
42 42 42 42 42 42
01BAC01GS008-YB15 01MKY01EZ100-YA50 01MKY01EZ100-YA51 Spare Relay 01MKY01EZ100-YA53 01MKY01EZ100 Spare Relay Spare Relay
Release Alternator Block Voltage Block Excitation Alternator CB Spare
Earthing Switch and Frequency Fault External Trip for Alternator
Supervision by PLC Protection Relay
-X1
25 26 27 28 29 30 31 32 33 34
3L+ 3L+
A1 A1 A1 A1 A1 A1 A1 A1
-246K1 -246K2 -246K3 -246K4 -246K5 -246K6 -246K7 -246K8
U
A2 A2 A2 A2 A2 A2 A2 A2
0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU 0,75mm² BU
-X121 A4
-X123
Integrated Cross Connection
C13 C14 C15 C16 C17 D2 D3 D4
244.9 / 24VDC-121 24VDC-121 / 248.0
Integrated Cross Connection
244.9 / M24-123
-X1
37 38 39 40 41 42 43 44 45 46 48
4L+ 4L+ M
0,75mm² RD 0,75mm² BU
-X121 A5 -X121 C5
Integrated CC
246.9 / 24VDC-121
Integrated Cross Connection
240.9 / M24-121
PE PE
1 2 5 1 2 3 4 5 6 7
-X400 -X401
-W1004
NYY-J
3x4 1 2 GNYE
Outside of Panel
PE
+01MKA01
Alternator
Window type CT
+CAB-BCN2 ALT1-1 / 302.1
S1 S2 PE
to NE Switch P1 P2
01BAU01GS001 ALT1-2 / 302.1
60A/1A
ALT1-3 / 302.1
Current Transformer
PE PE
1 2 3 4 5 6 7 3 4 6
-X402 -X400
-W1006 -W1007
NYY-J NYY-J
7x4 1 2 3 4 5 6 GNYE 3x4 1 2 GNYE
MV Busbar Connection
According to Manufacturers Wiring Diagram
+01MKA01.02 +00BBA01.02
Alternator
MV Busbar
Outside of
1 2 3 4 5 6 PE
-X? Panel
PE
PE
01BAC01GS008-K1
/322.8
Interlock Coil
PE
28 48
+01MKA01 01BAC01GS008
Window type CT 29 49
Alternator
+CAB-BCN1
/230.5
/230.5
PE S1 S2
700A / 1A P1 P2
PE
01MKA01
S1 S2
Alternator 1 60A/1A
P1 P2 13,8kV
300.8 / ALT1-1 ALT1-L1 / 304.1
S1 S2
300.8 / ALT1-2
P1 P2 G 13,8kV
ALT1-L2 / 304.1
S1 S2 3~
P1 P2 13,8kV
300.8 / ALT1-3 ALT1-L3 / 304.1
Core 1 Voltage-, Current Transformer and Exciter Field Current Transformer Alternator
connected to ECP/GIP Earthing Switch
Previous Page: 300 Next Page: 304
Rev.C 24.10.2014 rhoerner Edition Date 16.12.2014
Genset Control Panel GCP MAN Diesel & Turbo SE Wiring Diagram Drawing Number: T-06802_GCP + 01CDA01
Rev.B 24.10.2014 rhoerner Editor E. Simon
Rev.B 24.10.2014 rhoerner Checked R. Hörner
PowerES Stadtbachstr. 1 Alternator Page 302
Revision Date Name Edition Status Commissioning 86153 Augsburg/Germany Incoming Protection Current Core 1 5302272 United Cement Industrial Company Pages 175
0 1 2 3 4 5 6 7 8 9
/220.5
/220.5
Open Delta Voltage Alternator
I> I> I>
Measuring Voltage 2 4 6
-X454 1A 3A 5A -X454 1B 3B 5B
PE PE
1 2 3 1 2 3 4 5
1/L1 7/L2 5/L3
-X451 -X452 -304S1 2
1,5mm² BK
Voltage Selector
Switch L1 L2 L3
1
OFF
Panel Door L2 L3 L1
+00BBA01.02
MV Busbar
38 39 32 33 40 8 9 10 11 6
-XDV -XDV
PE
PE
2 13 13
-FCM14.1 -FCM11.4
1 14 14
PE
/230.4
/230.4
110V / 3 110V / √3
PE
PE
Uprim / √3
13,8kV 13,8kV
302.9 / ALT1-L1 ALT1-L1 / 306.1
13,8kV 13,8kV MV Busbar Connection
302.9 / ALT1-L2 ALT1-L2 / 306.1 According to Manufacturers Wiring Diagram
13,8kV 13,8kV
302.9 / ALT1-L3 ALT1-L3 / 306.1
Voltage Transformer
2,5mm² GY 2,5mm² GY 2,5mm² GY 2,5mm² GY 2,5mm² GY 2,5mm² GY 4mm² GY 4mm² GY 4mm² GY 4mm² GY 4mm² GY 4mm² GY
PE PE
1 2 3 4 5 6 7 1 2 3 4 5 6 7
-X403 -X404
-W1011 -W1012
NYY-J NYY-J
7x4 1 2 3 4 5 6 GNYE 7x4 1 2 3 4 5 6 GNYE
+00BBA01.02
MV Busbar
19 18 21 20 23 22 7 11 12 13 14 15 16 17
-XDA -XDA
PE PE
MV Busbar Connection
According to Manufacturers Wiring Diagram
700 / 1A 700 / 1A
PE S1 S2 PE S1 S2
13,8kV P1 P2 P1 P2 13,8kV
304.4 / ALT1-L1 ALT1-L1 / 308.1
S1 S2 S1 S2
13,8kV P1 P2 P1 P2 13,8kV
304.4 / ALT1-L2 ALT1-L2 / 308.1
S1 S2 S1 S2
13,8kV P1 P2 P1 P2 13,8kV
304.4 / ALT1-L3 ALT1-L3 / 308.1
Core 1 Core 2
+00BBA01.02
MV Busbar
13,8kV
01BAC01GS003-K1 U<
/322.2
Undervoltage Coil 13,8kV MV Busbar
00BBA01
01BAC01GS003-K2
/322.4 13,8kV
Closing Coil
01BAC01GS003-K3
/322.6 1 3 5
Tripping Coil
41 31
01BAC01GS003
42 32
/320.1
/320.3
2 4 6
MV Busbar Connection
13,8kV According to Manufacturers Wiring Diagram
306.8 / ALT1-L1
13,8kV
306.8 / ALT1-L2
13,8kV
306.8 / ALT1-L3
Alternator
Circuit Breaker
Previous Page: 306 Next Page: 310
Rev.C 24.10.2014 rhoerner Edition Date 16.12.2014
Genset Control Panel GCP MAN Diesel & Turbo SE Wiring Diagram Drawing Number: T-06802_GCP + 01CDA01
Rev.B 24.10.2014 rhoerner Editor E. Simon
Rev.B 24.10.2014 rhoerner Checked R. Hörner
PowerES Stadtbachstr. 1 MV Busbar Page 308
Revision Date Name Edition Status Commissioning 86153 Augsburg/Germany Alternator Circuit Breaker 5302272 United Cement Industrial Company Pages 175
0 1 2 3 4 5 6 7 8 9
00BBA01CE011A/B/C
MV Busbar
Measuring Voltage
1 3 5 13 21
-310Q1
1,4-2A 14 22
1,6A
/220.4
MV Busbar
I> I> I>
Measuring Voltage 2 4 6
2,5mm² BK
PE
1 2 3 4
-X450
-W1013
NYY-J
4x2.5 1 2 3 GNYE
+00CBA01.01
Common Control Panel (CCP)
1 2 3 4
-X451
MV Busbar 1 Voltage
3AC 110V
-W9.INT
UNITRONIC BUS
2x0.64 GN RD
-312P1
UMG 96 RM-P
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 L+ N- -X1 A1 B1 ON A2 B2
Panel Door 3 4 5 6 7 8 9 10 11 12 13 14 15 2 1 OFF
I1 I2 I3
PROFIBUS DP
SWITCH SETTINGS
ON Terminating Resistor ON
OFF Terminating Resistor OFF
12 14 22 24 32 34 12 14 22 24 32 34
-244K1 -244K2
/244.1 11 21 31 /244.2 11 21 31
Sync. Release Sync. Release
Busbar Alternator
1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm²
BK BK BK BK BK BK BK BK BK BK BK BK
-X455 2B 4B 6B 8B 6C 8C 6D 8D 2C 4C
12 14 22 24 32 34 12 14 22 24 32 34 42 44 32 34
-244K5 -244K4 -244K5 -320K1
/244.5 11 21 31 /244.4 11 21 31 /244.5 41 /320.1 31
Automatic Automatic Automatic 01BAC01GS003-XB02
Sync. Release Sync. Release Sync. Release Alternator CB
Alternator Busbar is Opened
1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1,5mm² 1mm² RD 1mm² RD
BK BK BK BK BK BK BK BK BK BK BK BK
9 10 /318.1 14 15 /318.1
8 16 17
18 19
01BAC01GS003-YB01
Alternator CB
Closing Coil
ON Command
Integrated CC
110.9 / 24VDC-150 24VDC-150 / 504.0
-X150 A2
1mm² RD
8 9
-316A1
/316.0 10
Synchrocheck Relay
CB Release 1mm² RD
1mm² RD
14 12 14
-316A2 -244K3
/316.4 15 /244.3 11
Automatic 01CDA01GH001-YA94
Synchronization Unit Manual
RD
CB ON Command 1 Synchronization
1mm² RD
Release
A1
U
-318K1
01BAC01GS003-YB01
Alternator CB
Closing Coil ON A2
Command 1mm² BU
-X150 C2
13 14 /322.4
21 22
31 32
43 44
+00BBA01.02
MV Busbar
41 31
01BAC01GS003
/308.2 42 /308.3 32
-W1001
/230.1 21 22 23 24
1mm² RD 1mm² RD
A1 A1
-320K1 -320K2
01BAC01GS003-XB02 01BAC01GS003-XB01
Alternator CB is Alternator CB is
Opened A2 Closed A2
1mm² BU 1mm² BU
108.9 / M24-132
14 11 /232.5 14 11 /230.7
12 12
24 21 /514.2 24 21 /504.4
22 22
34 31 /316.8
32
44 41
42
+01CDH01
Genset Interface Panel (GIP)
Alternator CB
OFF by GIP 1mm² WH
1mm² WH
1mm² WH 1mm² WH
1mm² WH
13
-244K6
/244.5 14
1mm² WH 1mm² WH 1mm² WH 1mm² WH 1mm² WH 1mm² WH 1mm² WH
01BAC01GS003-YB32
Alternator CB
OFF by PLC
-X504 101 (Open/Trip Loop) 201 102 202 -X503 113 213 114 214 115 215 116 216 117 217 118 218
-W1016
-W1015 H05VV5-F
H05VV5-F 12G1.5
5G1.5 1 2 3 4 110 1 2 3 4 5 6 7 8 9 10 11 12
+00BBA01.02
MV Busbar
DC 110V
L+
-XDC 7 8 1 2 11 12 17 18
13
-FCM2.1
14 Internal Interlocking
/230.3
-500F1
Alternator Protection
Panel Door
/502.3 J7 IEE1
/502.3 J8
= +
F1 /504.1
(~)
Power Supply
+ -
NC K13 TD 1 (Start-Up) F2 /504.1
=
NC K14
+
NC K15 TD 2 (Temp)
NC K16
+
NC K17 TD 3 (DC-EXC.)
NC K18 Port C
Service Interface
/506.7
RS232
/504.3 F5 BI1
/504.3 F6 BI2 Port B
/504.4 F7 BI3 -X1:A1 /506.4
/504.4 F8 BI4 -X1:B1 /506.5
PROFIBUS DP
/504.5 F9 BI5
RS485
/504.3 F10 -X1:A2 /506.6
-X1:B2 /506.6
NC K9 BI6
NC K10 Port A
NC K11 BI7 IRIG B/DCF77 /506.3
NC K12
7UM6211-2EB91-0BC0-L0A SIEMENS
AC 110V 2,5mm² BK
304.9 / VOD-2
AC 110V 2,5mm² BK
304.9 / VOD-1
-X454 2C 4C 6C 7B
1A 4mm² GY
302.9 / IEF-2
1A 4mm² GY 1,5mm² 1,5mm²
302.9 / IEF-1 BK LBU
1A 4mm² GY
302.9 / IP-1.6
1A 4mm² GY
302.9 / IP-1.5
1A 4mm² GY
302.9 / IP-1.4
1A 4mm² GY
302.9 / IP-1.3
1A 4mm² GY
302.9 / IP-1.2
1A 4mm² GY
302.9 / IP-1.1
1A 4mm² GY
306.9 / IP-2.6
1A 4mm² GY
306.9 / IP-2.5
1A 4mm² GY
306.9 / IP-2.4
1A 4mm² GY
306.9 / IP-2.3
1A 4mm² GY
306.9 / IP-2.2
1A 4mm² GY
306.9 / IP-2.1
IL1, S1 IL2, S1 IL3, S1 IEE1 IL1, S2 IL2, S2 IL3, S2 IEE2 VE VL1 VL2 VL3
7UM6211-2EB91-0BC0-L0A SIEMENS
12 14 12 14 22 24 12 14 12 14
-246K2 -246K3 -320K2 -246K5 -246K6 500F1:R7 / 508.0
/246.2 11 /246.3 11 /320.3 21 /246.5 11 /246.5 11
01MKY01 01MKY01 01BAC01 01MKY01 01MKY01 500F1:K1 / 516.0
EZ100-YA50 EZ100-YA51 GS003-XB01 EZ100-YA53 EZ100
Block Voltage Block Excitation Alternator CB Alternator CB Spare
and Frequency Fault is Closed External Trip for Alternator 500F1:K5 / 516.0
Supervision by PLC Protection Relay
1mm² RD 1mm² RD 1mm² RD 1mm² RD 1mm² RD 1mm² WH 1mm² WH 1mm² WH
-500F1 + F3 F5 F6 F7 F8 F9 R5 R7 R9 R11 K1 K3 K5 K7
Alternator Protection F1
Panel Door Power Supply
/500.3
SIEMENS
7UM6211-2EB91-0BC0-L0A
F2
-
PE F4 F10 R1 R2 R3 R4 R6 R8 R10 R12 K2 K4 K6 K8
PE
01MKY01EZ100
Alternator
Protection Relay
312.9 / PB-1
312.9 / PB-2
-500F1
Alternator Protection -X1 A1 B1 ON A2 B2
Panel Door OFF
/500.3
SWITCH SETTINGS
ON Terminating Resistor ON
OFF Terminating Resistor OFF
7UM6211-2EB91-0BC0-L0A SIEMENS
1mm² WH
504.9 / 500F1:R7
1mm² WH
504.9 / 500F1:R8
41
-510S1
/510.2 42
EZ500
Emergency Stop
Push Button
Panel Door
1mm² WH
1mm² WH 1mm² WH
-X501 107 207 108 208 -X502 107 207 108 208 -X506 101 201
-W1019
H05VV5-F
3G1.5
24 1 2
+01CDH01
Genset Interface Panel (GIP)
Engine
Shutdown Signal
to GIP
01CDC01EY100 Spare
Emergency Stop
Loop for Engine
Auxiliary Drives
11 23 33 41 51 61
-510S1
EZ500 12 24 34 42 52 62
Emergency Stop
/220.6
/322.6
/508.5
/322.2
Push Button
Panel Door
1mm² WH 1mm² WH
-W1020
H05VV5-F
5G1.5
24 1 3 2 4
+01CDH01
Genset Interface Panel (GIP)
01BAC01GS003-XB01 01BAC01GS003-XB01
Alternator CB Alternator CB
is Closed is Closed
to SaCoS
+00BBA01.02
MV Busbar
41 31
+PLG-QAB3-BB3
42 32
-W1021
H05VV5-F
4G1.5 1 3 2 4
-W1022
/514.1
H05VV5-F
18G1.5 1 9 2 10
+01CDH01
Genset Interface Panel (GIP)
Signal to Signal to
AVR SaCoS
01BAC01GS003-XB02
Alternator CB
is Opened
22 24
-320K1
/320.1 21
01BAC01GS003-XB02
Alternator CB
is Opened
1mm² WH 1mm² WH
-X506 106 206 107 207 108 208 109 209 110 210 111 211
-W1022
/512.1
24 3 11 4 12 5 13 6 14 7 15 8 16
+01CDH01
Genset Interface Panel (GIP)
-X506 106 206 107 207 108 208 109 209 110 210 111 211
01MKY01EZ100-XK58 01BAC01GS003-YB32
Breaker Failure Breaker Failure
External Trip External Trip
to CCP from CCP
1mm² WH
504.9 / 500F1:K5
1mm² WH
322.2 / X500:12
1mm² WH
504.9 / 500F1:K1
1mm² WH
504.9 / 500F1:K2
-X500 10 11 12 13
-W1023 -W1024
H05VV5-F H05VV5-F
3G1.5 1 2 3G1.5 1 2
+00CBA01.01
Common Control Panel (CCP)
-X501 10 11 12 13
51
-332K1
MV Busbar 1 52
Breaker Failure
-X504 Alternator CB Open/Trip Loop Safety Connection to MV Busbar (DC 110V) +00BBA01 101 202 0 0 4 +01CDA01/630
-X506 Connection to Genset Interface Panel (DC 24V) +01CDH01 101 211 0 0 22 +01CDA01/632
Terminal Diagram
+00BJB01-W319
Terminal Strip: =+01CDA01-X10
Cable Name
Cable Name
Power Supply AC 230V Panel Equipment
Connection Point
Connection Point
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Power Supply Panel Equipment AC 230V BN +00BJB01-X369 1 1 -100F1 1 /100.1
Power Supply Panel Equipment AC 230V BU +00BJB01-X369 2 2 -X160 6 /100.2
Power Supply Panel Equipment AC 230V GNYE +00BJB01-X369 4 3 PE /100.2
Terminal Diagram
+00BRA01-W310
Terminal Strip: =+01CDA01-X20
Cable Name
Cable Name
UPS Power Supply AC 230V
Connection Point
Connection Point
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
UPS Power Supply AC 230V BN +00BRA01-X20.06 L2 1 -104F1 1 /102.1
UPS Power Supply AC 230V BU +00BRA01-X20.06 N 2 -104F1 3 /102.1
UPS Power Supply AC 230V GNYE +00BRA01-X20.06 PE 3 PE /102.2
UPS Power Supply DC 24V Power Supply Unit PE 4 -104G1 PE /104.3
Terminal Diagram
Terminal Strip: =+01CDA01-X100
Cable Name
Cable Name
DC 24V Distribution: General
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Power Supply DC 24V (M-) 1 -104G1 M /104.5
Power Supply DC 24V (M-) -X120 D1 2 -X120 C1 /106.1
Power Supply DC 24V (M-) -X121 D1 3 -X121 C1 /106.2
Power Supply DC 24V (M-) 4 /106.3
Power Supply DC 24V (M-) -X123 D1 5 -X123 C1 /106.4
Power Supply DC 24V (M-) 6 -216A1 3 /106.5
Power Supply DC 24V (M-) -X130 D1 7 -X130 C1 /106.6
Power Supply DC 24V (M-) 8 /108.1
Power Supply DC 24V (M-) 9 -320K1 A2 /108.2
Power Supply DC 24V (M-) 10 /108.3
Power Supply DC 24V (M-) 11 /108.4
Power Supply DC 24V (M-) 12 /108.5
Power Supply DC 24V (M-) -X150 D1 13 -X150 C1 /110.1
Power Supply DC 24V (M-) 14 -104G2 M /104.9
Power Supply DC 24V (M-) -X100 16 15 -104G1 M /104.6
Power Supply DC 24V (M-) -X100 15 16 PE /104.7
Touch Panel PC PE 17 -216A1 2 /216.6
Touch Panel PC PE 18 -216A1 PE /216.9
Power Supply DC 24V (L+) -110F1 1 19 -104G1 L+ /104.5
Power Supply DC 24V (L+) 20 -104G2 L+ /104.8
Terminal Diagram
Terminal Strip: =+01CDA01-X120
Cable Name
Cable Name
Internal DC 24V Distribution: OLM, PS
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Power Supply OLM, PS A1 -106F1 2 /106.1
01CDA01GN001 Optical Link Module A2 -200A1 L1+ /200.2
Power Supply Unit A3 -A101 L+ /212.1
Communication Processor A4 -216A2 1 /216.2
A5
Power Supply OLM, PS B1 -106F1 2 /106.1
B2
B3
B4
B5
Power Supply OLM, PS C1 -X100 2 /106.1
01CDA01GN001 Optical Link Module C2 -200A1 M /200.2
Power Supply Unit C3 -A101 M /212.1
Communication Processor C4 -216A2 2 /216.2
C5
Power Supply OLM, PS D1 -X100 2 /106.1
D2
D3
D4
D5
Terminal Diagram
Terminal Strip: =+01CDA01-X121
Cable Name
Cable Name
Internal DC 24V Distribution: DI/DO Modules
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Power Supply DI/DO Modules (L+) A1 -106F2 2 /106.2
Power Supply DI/DO Modules (L+) A2 -A108-X1 -X1:3 /242.1
Power Supply DI/DO Modules (L+) A3 -A108-X1 -X1:13 /244.1
Power Supply DI/DO Modules (L+) A4 -A108-X1 -X1:25 /246.1
Power Supply DI/DO Modules (L+) A5 -A108-X1 -X1:37 /248.1
Power Supply DI/DO Modules (L+) B1 -106F2 2 /106.2
Power Supply DI/DO Modules (L+) B2
Power Supply DI/DO Modules (L+) B3
Power Supply DI/DO Modules (L+) B4
Power Supply DI/DO Modules (L+) B5
Power Supply DI/DO Modules (M-) C1 -X100 3 /106.2
Power Supply DI/DO Modules (M-) C2 -A105-X1 -X1:48 /224.8
Power Supply DI/DO Modules (M-) C3 -A106-X1 -X1:48 /232.8
Power Supply DI/DO Modules (M-) C4 -A107-X1 -X1:48 /240.8
Power Supply DI/DO Modules (M-) C5 -A108-X1 -X1:48 /248.8
Power Supply DI/DO Modules (M-) D1 -X100 3 /106.2
Power Supply DI/DO Modules (M-) D2
Power Supply DI/DO Modules (M-) D3
Power Supply DI/DO Modules (M-) D4
Power Supply DI/DO Modules (M-) D5
Terminal Diagram
Terminal Strip: =+01CDA01-X123
Cable Name
Cable Name
Internal DC 24V Distribution: Digital I/Os
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Digital I/Os Internal Contacts A1 -106F4 2 /106.4
Panel Door Closed A2 -X161 1 /160.7
01CDA01GN001-XM90 Optical Link Module OLM Fault A3 -200A1 F1 /200.2
01CDA01GS015-XM76 Power Supply Panel Equipment MCB OFF A4 -100F1 13 /218.1
01CDA01GS013-XM76 UPS Power Supply DC 24V PS Unit MCB O A5 -104F1 13 /218.2
01CDA01GW031-XM76 Power Supply DI/DO Modules MCB OFF A6 -106F2 13 /218.3
Spare A7 /218.4
01CDA01GW071-XM76 Power Supply Panel PC MCB OFF A8 -106F5 13 /218.5
01CDA01GW041-XM76 Power Supply Internal Control Voltage M A9 -106F6 13 /218.5
01CDA01GW091-XM76 External Signals from CCP MCB OFF A10 -108F1 13 /218.6
01BAC01GS003-XM76 External Signals from Alternator CB MCB A11 -108F2 13 /218.7
01CDA01GW093-XM76 External Signals from BCP MCB OFF A12 -108F3 13 /220.1
01CDA01GW094-XM76 External Signals from FFCP MCB OFF A13 -108F4 13 /220.2
01CDA01GW072-XM76 PS Altern. Protection, CB Control MCB OF A14 -110F1 13 /220.3
00BBA01CE011-XM96 Measuring MV Busbar Voltage CB OFF A15 -310Q1 13 /220.4
01BAC01GW001-XM86 Measuring Alternator Voltage CB OFF A16 -304Q1 13 /220.5
01BAC01CE011D-XM76 Alternator Open Delta Voltage MCB OFF A17 -304F1 13 /220.5
Digital I/Os Internal Contacts B1 -106F4 2 /106.4
01CDA01EZ500-XA37 Emergency Stop Push Button at GCP Push B2 -510S1 23 /220.6
01CDA01GH001-XM10 Panel Door is Opened B3 -160K1 24 /220.7
Push Buttons at Panel Door B4 -224S1 13 /224.1
Push Buttons at Panel Door B5 -226S1 13 /226.1
01BAC01GS003-XB01 Alternator CB is Closed B6 -320K2 14 /230.7
01BAC01GS003-XB02 Alternator CB is Opened B7 -320K1 14 /232.5
CE116 Optical Link Module (OLM) 1 Fault B8
B9
B10
B11
B12
B13
B14
B15
B16
B17
Digital I/Os Internal Contacts C1 -X100 5 /106.4
Terminal Diagram
Terminal Strip: =+01CDA01-X123
Cable Name
Cable Name
Internal DC 24V Distribution: Digital I/Os
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Panel Door Closed C2 -160K1 A2 /160.7
Indication Lights Panel Roof C3 -X149 4 /242.1
Position Indicator Panel Door C4 -242H4 - /242.4
01BAU01GS001-YA25 Position Indicator Alternator NE Switch Op C5 -244K1 A2 /244.1
01CDA01GH001-YA93 Synchronization Manual or Autom. Selecte C6 -244K2 A2 /244.2
01CDA01GH001-YA94 Manual Synchronization Release C7 -244K3 A2 /244.3
01CDA01GH001-YA95 Automatic Synchronization Release C8 -244K4 A2 /244.4
Spare C9 -244K5 A2 /244.5
01BAC01GS003-YB32 Alternator CB OFF by PLC (Open/Trip Loop C10 -244K6 A2 /244.5
01BAC01GS003-YB02 Alternator CB OFF Command by PLC (Trip C11 -244K7 A2 /244.6
Spare Relay C12 -244K8 A2 /244.7
01BAC01GS008-YB15 Release Alternator Earthing Switch C13 -246K1 A2 /246.1
01MKY01EZ100-YA50 Block Voltage and Frequency Supervision C14 -246K2 A2 /246.2
01MKY01EZ100-YA51 Block Excitation Fault C15 -246K3 A2 /246.3
Spare Relay C16 -246K4 A2 /246.4
01MKY01EZ100-YA53 Alternator CB External Trip by PLC C17 -246K5 A2 /246.5
Digital I/Os Internal Contacts D1 -X100 5 /106.4
01MKY01EZ100 Spare for Alternator Protection Relay D2 -246K6 A2 /246.5
Spare Relay D3 -246K7 A2 /246.6
Spare Relay D4 -246K8 A2 /246.7
D5
D6
D7
D8
D9
D10
D11
D12
D13
D14
D15
D16
D17
Terminal Diagram
Terminal Strip: =+01CDA01-X130
Cable Name
Cable Name
Internal DC 24V Distribution: Control Voltage
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Power Supply Internal Control Voltage A1 -106F6 2 /106.6
01MKA01EU100 Multifunctional Monitoring Unit (MMU) A2 -312P1 2 /312.6
Automatic Synchronization Unit A3 -316A2 53 /316.6
Automatic Synchronization Unit A4 -316A2 1 /316.7
Automatic Synchronization Unit A5 -244K5 44 /316.8
Automatic Synchronization Unit A6 -320K1 34 /316.8
A7
A8
A9
A10
Power Supply Internal Control Voltage B1 -106F6 2 /106.6
B2
B3
B4
B5
B6
B7
B8
B9
B10
Power Supply Internal Control Voltage C1 -X100 7 /106.6
01MKA01EU100 Multifunctional Monitoring Unit (MMU) C2 -312P1 1 /312.6
Automatic Synchronization Unit C3 -316A2 2 /316.7
Automatic Synchronization Unit C4 -316A2 7 /316.9
C5
C6
C7
C8
C9
C10
Power Supply Internal Control Voltage D1 -X100 7 /106.6
D2
D3
D4
D5
Terminal Diagram
Terminal Strip: =+01CDA01-X130
Cable Name
Cable Name
Internal DC 24V Distribution: Control Voltage
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
D6
D7
D8
D9
D10
Terminal Diagram
-W8.INT
Terminal Strip: =+01CDA01-X149
Cable Name
Cable Name
Signaling Column
Connection Point
Connection Point
ÖLFLEX CLASSIC 110
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01CDA01EH001-YA25 Indication Light Engine Stopping/Standstill 1 -242H1 3 1 -A108-X1 -X1:4 /242.1
01CDA01EH001-YA26 Indication Light Genset Alarm/Shutdown 2 -242H2 2 2 -A108-X1 -X1:5 /242.2
01CDA01EH001-YA27 Indication Light Engine Starting/Running 3 -242H3 1 3 -A108-X1 -X1:6 /242.3
Indication Lights Panel Roof 4 -242H1 0 4 -X123 C3 /242.1
Terminal Diagram
Terminal Strip: =+01CDA01-X150
Cable Name
Cable Name
Internal DC 24V Distribution: Safety Related Circuits
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Power Supply Alternator Protection, CB Control A1 -110F1 2 /110.1
01BAC01GS003-YB01 Alternator CB Closing Coil ON Command A2 -316A1 9 /318.1
Power Supply 01MKY01EZ100 Alternator Protection Relay A3 -500F1 F1 /504.1
01MKY01EZ100-XM90 Alternator Protection Relay Watchdog A4 -500F1 F3 /504.2
01MKY01EZ100-YA50 Block Voltage And Frequency Supervision A5 -246K2 14 /504.3
01MKY01EZ100-YA51 Block Excitation Fault A6 -246K3 14 /504.3
01BAC01GS003-XB01 Back Indication Alternator CB is Closed A7 -320K2 24 /504.4
01MKY01EZ100-YA53 Alternator CB External Trip by PLC A8 -246K5 14 /504.4
Power Supply Alternator Protection, CB Control B1 -110F1 2 /110.1
01MKY01EZ100 Spare B2 -246K6 14 /504.5
01MKY01EZ100 Spare B3 -500F1 R5 /504.5
B4
B5
B6
B7
B8
Power Supply Alternator Protection, CB Control C1 -X100 13 /110.1
01BAC01GS003-YB01 Alternator CB Closing Coil ON Command C2 -318K1 A2 /318.1
Power Supply 01MKY01EZ100 Alternator Protection Relay C3 -500F1 F2 /504.1
Alternator Protection Relay (M- for Output Relays) C4 -500F1 F10 /504.3
C5
C6
C7
C8
Power Supply Alternator Protection, CB Control D1 -X100 13 /110.1
D2
D3
D4
D5
D6
D7
D8
Terminal Diagram
-W2.INT
-W1.INT
Terminal Strip: =+01CDA01-X160
Cable Name
Cable Name
Panel Equipment AC 230V
Connection Point
Connection Point
ÖLFLEX CLASSIC 110 G
Pre-Assembled
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Panel Illumination BN -160E1-X1 L:L 1 -100F1 2 /160.2
Panel Ventilation 2 -160K1 14 /160.5
Panel Ventilation 1 -160M1 L1 3 -160S1 2 /160.5
4
5
Panel Illumination BU -160E1-X1 N:N 6 -X10 2 /160.2
Panel Ventilation 2 -160M1 N 7 /160.5
8
9
10
Panel Illumination GNYE -160E1-X1 PE:PE 11 PE /160.2
Panel Ventilation GNYE -160M1 PE 12 PE /160.5
13
14
15
Terminal Diagram
-W3.INT
Terminal Strip: =+01CDA01-X161
Cable Name
Cable Name
Panel Equipment DC 24V
Connection Point
Connection Point
ÖLFLEX CLASSIC 110
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Panel Door Closed 1 -160S2 13 1 -X123 A2 /160.7
Panel Door Closed 2 -160S2 14 2 -160K1 A1 /160.7
Terminal Diagram
-W1007
-W1004
Terminal Strip: =+01CDA01-X400
Cable Name
Cable Name
Earth Fault Current
Connection Point
Connection Point
NYY-J
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01BAU01CE021 Earth Fault Current Alternator Star Point 1 +CAB-BCN2 P1 1 -X400 4 /300.1
01BAU01CE021 Earth Fault Current Alternator Star Point 2 +CAB-BCN2 P2 2 /300.1
01BAC01CE021 Earth Fault Current Alternator Outlet 1 PE 3 -500F1 Q8 /302.6
1 +CAB-BCN1 P1
01BAC01CE021 Earth Fault Current Alternator Outlet 2 +CAB-BCN1 P2 4 -X400 1 /302.6
-500F1 Q7
PE GNYE PE 5 PE /300.2
PE GNYE PE 6 PE /302.7
Terminal Diagram
Terminal Strip: =+01CDA01-X401
Cable Name
Cable Name
Alternator Current for Protection Core 2
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01MKA01CE002A Altern. Current for Protection Phase U Spare 1 /300.5
01MKA01CE002A Altern. Current for Protection Phase U Spare 2 /300.5
01MKA01CE002B Altern. Current for Protection Phase V Spare 3 /300.6
01MKA01CE002B Altern. Current for Protection Phase V Spare 4 /300.6
01MKA01CE002C Altern. Current for Protection Phase W Spare 5 /300.7
01MKA01CE002C Altern. Current for Protection Phase W Spare 6 /300.7
PE 7 PE /300.7
Terminal Diagram
-W1006
Terminal Strip: =+01CDA01-X402
Cable Name
Cable Name
Alternator Current for Protection Core 1
Connection Point
Connection Point
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01MKA01CE001A Altern. Current for Protection Phase U 1 +01MKA01.02-X? 1 1 -500F1 Q1 /302.1
01MKA01CE001A Altern. Current for Protection Phase U 2 +01MKA01.02-X? 2 2 -500F1 Q2 /302.1
01MKA01CE001B Altern. Current for Protection Phase V 3 +01MKA01.02-X? 3 3 -500F1 Q3 /302.2
01MKA01CE001B Altern. Current for Protection Phase V 4 +01MKA01.02-X? 4 4 -500F1 Q4 /302.2
01MKA01CE001C Altern. Current for Protection Phase W 5 +01MKA01.02-X? 5 5 -500F1 Q5 /302.3
01MKA01CE001C Altern. Current for Protection Phase W 6 +01MKA01.02-X? 6 6 -500F1 Q6 /302.3
PE GNYE +01MKA01.02-X? PE 7 PE /302.4
Terminal Diagram
-W1011
Terminal Strip: =+01CDA01-X403
Cable Name
Cable Name
Measuring Current for Alternator Current Core 1
Connection Point
Connection Point
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01BAC01CE003A Alternator Current for Measuring Phase L1 1 +00BBA01.02-XDA 19 1 -306P1 2 /306.1
01BAC01CE003A Alternator Current for Measuring Phase L1 2 +00BBA01.02-XDA 18 2 -312P1 8 /306.1
01BAC01CE003B Alternator Current for Measuring Phase L2 3 +00BBA01.02-XDA 21 3 -312P1 9 /306.2
01BAC01CE003B Alternator Current for Measuring Phase L2 4 +00BBA01.02-XDA 20 4 -312P1 10 /306.2
01BAC01CE003C Alternator Current for Measuring Phase L3 5 +00BBA01.02-XDA 23 5 -312P1 11 /306.3
01BAC01CE003C Alternator Current for Measuring Phase L3 6 +00BBA01.02-XDA 22 6 -312P1 12 /306.3
PE GNYE +00BBA01.02-XDA 7 7 PE /306.4
Terminal Diagram
-W1012
Terminal Strip: =+01CDA01-X404
Cable Name
Cable Name
Alternator Current for Protection Core 2
Connection Point
Connection Point
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01BAC01CE001A Alternator Current for Protection Phase L1 1 +00BBA01.02-XDA 11 1 -500F1 J1 /306.5
01BAC01CE001A Alternator Current for Protection Phase L1 2 +00BBA01.02-XDA 12 2 -500F1 J2 /306.5
01BAC01CE001B Alternator Current for Protection Phase L2 3 +00BBA01.02-XDA 13 3 -500F1 J3 /306.6
01BAC01CE001B Alternator Current for Protection Phase L2 4 +00BBA01.02-XDA 14 4 -500F1 J4 /306.6
01BAC01CE001C Alternator Current for Protection Phase L3 5 +00BBA01.02-XDA 15 5 -500F1 J5 /306.7
01BAC01CE001C Alternator Current for Protection Phase L3 6 +00BBA01.02-XDA 16 6 -500F1 J6 /306.7
PE GNYE +00BBA01.02-XDA 17 7 PE /306.7
Terminal Diagram
-W1013
Terminal Strip: =+01CDA01-X450
Cable Name
Cable Name
Measuring Voltage MV Busbar
Connection Point
Connection Point
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
00BBA01CE011A MV Busbar Measuring Voltage 1 +00CBA01.01-X451 1 1 -310Q1 2 /310.1
00BBA01CE011B MV Busbar Measuring Voltage 2 +00CBA01.01-X451 2 2 -310Q1 4 /310.1
00BBA01CE011C MV Busbar Measuring Voltage 3 +00CBA01.01-X451 3 3 -310Q1 6 /310.1
00BBA01CE011A/B/C MV Busbar Measuring Voltage GNYE +00CBA01.01-X451 4 4 PE /310.2
Terminal Diagram
-W1008
Terminal Strip: =+01CDA01-X451
Cable Name
Cable Name
Alternator Open Delta Voltage
Connection Point
Connection Point
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01BAC01CE011D Alternator Open Delta Voltage 1 +00BBA01.02-XDV 38 1 -304F1 2 /304.1
01BAC01CE011D Alternator Open Delta Voltage 2 +00BBA01.02-XDV 32 2 -304F1 4 /304.1
01BAC01CE011D Alternator Open Delta Voltage GNYE +00BBA01.02-XDV 40 3 PE /304.2
Terminal Diagram
-W1009
Terminal Strip: =+01CDA01-X452
Cable Name
Cable Name
Alternator Measuring Voltage
Connection Point
Connection Point
NYY-J
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01BAC01CE011A Alternator Measuring Voltage 1 +00BBA01.02-XDV 8 1 -304Q1 2 /304.3
01BAC01CE011B Alternator Measuring Voltage 2 +00BBA01.02-XDV 9 2 -304Q1 4 /304.3
01BAC01CE011C Alternator Measuring Voltage 3 +00BBA01.02-XDV 10 3 -304Q1 6 /304.3
01BAC01CE011A/B/C Alternator Measuring Voltage 4 +00BBA01.02-XDV 11 4 -X454 7A /304.4
01BAC01CE011A/B/C Alternator Measuring Voltage GNYE +00BBA01.02-XDV 6 5 PE /304.4
Terminal Diagram
Terminal Strip: =+01CDA01-X454
Cable Name
Cable Name
Measuring Voltage 3AC 110V to Panel Door
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01MKA01CE012A/B/C Alternator Sensing Voltage to AVR Option 1A /304.5
Voltage Selector Switch 1B /304.7
1C
1D
01MKA01EU100 Multifunctional Monitoring Unit (MMU) 2A /312.1
Synchronization Release Altornator 2B /314.3
01MKY01EZ100 Alternator Protection Relay 2C /502.8
2D
01MKA01CE012A/B/C Alternator Sensing Voltage to AVR Option 3A /304.6
Voltage Selector Switch 3B /304.7
3C
3D
01MKA01EU100 Multifunctional Monitoring Unit (MMU) 4A /312.1
Synchronization Release Altornator 4B /314.3
01MKY01EZ100 Alternator Protection Relay 4C /502.8
4D
01MKA01CE012A/B/C Alternator Sensing Voltage to AVR Option 5A /304.6
Voltage Selector Switch 5B /304.7
5C
5D
01MKA01EU100 Multifunctional Monitoring Unit (MMU) 6A /312.1
Synchronization Release Altornator 6B /314.3
01MKY01EZ100 Alternator Protection Relay 6C /502.8
6D
01MKA01EU100 Multifunctional Monitoring Unit (MMU) 7A /312.1
01MKY01EZ100 Alternator Protection Relay 7B /502.8
7C
7D
Terminal Diagram
Terminal Strip: =+01CDA01-X455
Cable Name
Cable Name
Sync. Release Voltage 3AC 110V to Panel Door
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Double Voltmeter 1A /314.1
Double Frequency Meter 1B /314.4
1C
1D
LED Synchronoscope 2A /314.7
Synchrocheck Relay 2B /316.1
Automatic Sync. Release Busbar 2C /316.5
2D
Double Voltmeter 3A /314.2
Double Frequency Meter 3B /314.4
3C
3D
LED Synchronoscope 4A /314.7
Synchrocheck Relay 4B /316.1
Automatic Sync. Release Busbar 4C /316.5
4D
Double Voltmeter 5A /314.2
Double Frequency Meter 5B /314.5
5C
5D
LED Synchronoscope 6A /314.7
Synchrocheck Relay 6B /316.2
Synchrocheck Relay 6C /316.2
Automatic Sync. Release Alternator 6D /316.4
Double Voltmeter 7A /314.2
Double Frequency Meter 7B /314.5
7C
7D
LED Synchronoscope 8A /314.8
Synchrocheck Relay 8B /316.2
Synchrocheck Relay 8C /316.3
Automatic Sync. Release Alternator 8D /316.4
Terminal Diagram
-W1025
-W1024
-W1023
-W1000
-W4.INT
Terminal Strip: =+01CDA01-X500
Cable Name
Cable Name
Connection to Common Control Panel +00CBA01
Connection Point
Connection Point
H05VVC4V5-K
H05VV5-F
H05VV5-F
H05VV5-F
UNITRONIC LIYCY
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01CDA01GX100-YA78 MV BB 00BBA01 Frequency Setting Lower 1 +00CBA01.01-X501 1 1 -108F1 2 /228.1
01CDA01GX100-YA78 MV BB 00BBA01 Frequency Setting Lower 2 +00CBA01.01-X501 2 2 -A106-X1 -X1:15 /228.1
01CDA01GX100-YA77 MV BB 00BBA01 Frequency Setting Higher 3 +00CBA01.01-X501 3 3 -A106-X1 -X1:16 /228.2
01CDA01GX100-YA76 MV BB 00BBA01 Voltage Setting Lower fro 4 +00CBA01.01-X501 4 4 -A106-X1 -X1:17 /228.3
01CDA01GX100-YA75 MV BB 00BBA01 Voltage Setting Higher fr 5 +00CBA01.01-X501 5 5 -A106-X1 -X1:18 /228.4
01CDA01GX100-YA73 Genset in Grid Parallel Operation 6 +00CBA01.01-X501 6 6 -A106-X1 -X1:19 /228.5
01CDA01GX100-YA72 Block Synchronization from CCP 7 +00CBA01.01-X501 7 7 -A106-X1 -X1:20 /228.5
Spare 8 +00CBA01.01-X501 8 8 -A106-X1 -X1:21 /228.6
Spare 9 +00CBA01.01-X501 9 9 -A106-X1 -X1:22 /228.7
01MKY01EZ100-XK58 Breaker Failure External Trip to CCP 1 +00CBA01.01-X501 10 10 -500F1 K1 /516.1
01MKY01EZ100-XK58 Breaker Failure External Trip to CCP 2 +00CBA01.01-X501 11 11 -500F1 K2 /516.1
01BAC01GS003-YB32 Breaker Failure External Trip from CCP 1 +00CBA01.01-X501 12 12 -X507 201 /516.3
01BAC01GS003-YB32 Breaker Failure External Trip from CCP 2 +00CBA01.01-X501 13 13 -500F1 K5 /516.3
01CDA01CT001-XQ01 GCP Internal Panel Temperature WH +00CBA01.01-X308 101 14 -162R1 1 WH /162.4
01CDA01CT001-XQ01 GCP Internal Panel Temperature BN +00CBA01.01-X308 102 15 -162R1 3 BN /162.4
01CDA01CT001-XQ01 GCP Internal Panel Temperature GN +00CBA01.01-X308 201 16 -162R1 2 GN /162.5
01CDA01CT001-XQ01 GCP Internal Panel Temperature YE +00CBA01.01-X308 202 17 -162R1 4 YE /162.5
Terminal Diagram
Terminal Strip: =+01CDA01-X501
Cable Name
Cable Name
Spare
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Spare 101 -108F3 2 /234.1
Spare 102 /234.2
Spare 103 /234.3
Spare 104 /234.4
Spare 105 /234.4
Spare 106 /234.5
Spare 107 -500F1 R7 /508.1
Spare 108 /508.1
Spare 201 -A107-X1 -X1:4 /234.1
Spare 202 -A107-X1 -X1:5 /234.2
Spare 203 -A107-X1 -X1:6 /234.3
Spare 204 -A107-X1 -X1:7 /234.4
Spare 205 /234.4
206
Spare 207 -X502 107 /508.1
Spare 208 /508.2
Terminal Diagram
Terminal Strip: =+01CDA01-X502
Cable Name
Cable Name
Spare
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
101 -108F4 2 /236.1
Spare 102 /236.2
Spare 103 /236.3
Spare 104 /236.4
Spare 105 /236.4
Spare 106 /236.5
Spare 107 -X501 207 /508.3
Spare 108 /508.4
201 -A107-X1 -X1:15 /236.1
Spare 202 -A107-X1 -X1:16 /236.2
Spare 203 -A107-X1 -X1:17 /236.3
Spare 204 -A107-X1 -X1:18 /236.4
Spare 205 /236.4
206
Spare 207 -X506 201 /508.3
Spare 208 /508.4
Terminal Diagram
-W1021
-W1016
-W1001
Terminal Strip: =+01CDA01-X503
Cable Name
Cable Name
Connection to MV Busbar +00BBA01
Connection Point
Connection Point
H05VV5-F
H05VV5-F
H05VV5-F
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01BAC01GS003-XB41 Alternator CB in Test Position 1 +00BBA01.02-XDC 377 101 -108F2 2 /230.1
01BAC01GS003-XB40 Alternator CB in Operating Position 2 +00BBA01.02-XDC 377 102 /230.2
01BAC01GW001-XM84 Alternator Control Voltage MCB OFF 3 +00BBA01.02-XDC 356 103 /230.3
01BAC01CE011-ZM85 Alternator Voltage Measuring MCB OFF 4 +00BBA01.02-XDC 358 104 /230.4
01BAC01GS008-XB02 Alternator Earthing Switch is Opened 5 +00BBA01.02-XDC 352 105 /230.5
01BAC01GS008-XB01 Alternator Earthing Switch is Closed 6 +00BBA01.02-XDC 354 106 /230.5
01BAC01GS003-XB43 Alternator CB in Remote Position 7 +00BBA01.02-XDC 379 107 /230.6
01BAC01GS003-XB43 Alternator CB in Remote Position 108 /230.6
01BAC01GS003-XB02 Alternator CB is Opened 9 +00BBA01.02-XDC 374 109 /320.1
01BAC01GS003-XB01 Alternator CB is Closed 10 +00BBA01.02-XDC 372 110 /320.3
Spare 11 111 /320.4
Spare 12 112 /320.5
01BAC01GS003-YB01 Alternator CB Closing Coil ON Command 1 +00BBA01.02-XDC 1 113 -318K1 13 /322.4
01BAC01GS003-YB02 Alternator CB Tripping Coil OFF Command 3 +00BBA01.02-XDC 11 114 -244K7 13 /322.5
01BAC01GS008-YB15 Release Alternator Earthing Switch 5 +00BBA01.02-XDC 17 115 -246K1 13 /322.7
Spare 7 +00BBA01.02-XDC 116 /322.8
Spare 9 +00BBA01.02-XDC 117 /322.8
Spare 11 +00BBA01.02-XDC 118 /322.9
01BAC01GS003-XB01 Alternator CB is Closed 1 +00BBA01.02-XDC 340 119 -X506 104 /512.1
01BAC01GS003-XB01 Alternator CB is Closed to SaCoS 2 +00BBA01.02-XDC 342 120 -X506 105 /512.2
01BAC01GS003-XB41 Alternator CB in Test Position 13 +00BBA01.02-XDC 375 201 -A106-X1 -X1:27 /230.1
01BAC01GS003-XB40 Alternator CB in Operating Position 14 +00BBA01.02-XDC 376 202 -A106-X1 -X1:28 /230.2
01BAC01GW001-XM84 Alternator Control Voltage MCB OFF 15 +00BBA01.02-XDC 355 203 -A106-X1 -X1:29 /230.3
01BAC01CE011-ZM85 Alternator Voltage Measuring MCB OFF 16 +00BBA01.02-XDC 357 204 -A106-X1 -X1:30 /230.4
01BAC01GS008-XB02 Alternator Earthing Switch is Opened 17 +00BBA01.02-XDC 351 205 -A106-X1 -X1:31 /230.5
01BAC01GS008-XB01 Alternator Earthing Switch is Closed 18 +00BBA01.02-XDC 353 206 -A106-X1 -X1:32 /230.5
01BAC01GS003-XB43 Alternator CB in Remote Position 19 +00BBA01.02-XDC 378 207 -A106-X1 -X1:33 /230.6
01BAC01GS003-XB43 Alternator CB in Remote Position 208 /230.6
01BAC01GS003-XB02 Alternator CB is Opened 21 +00BBA01.02-XDC 373 209 -320K1 A1 /320.1
01BAC01GS003-XB01 Alternator CB is Closed 22 +00BBA01.02-XDC 371 210 -320K2 A1 /320.3
Spare 23 211 /320.4
Spare 24 212 /320.5
01BAC01GS003-YB01 Alternator CB Closing Coil ON Command 2 +00BBA01.02-XDC 2 213 -318K1 14 /322.4
01BAC01GS003-YB02 Alternator CB Tripping Coil OFF Command 4 +00BBA01.02-XDC 12 214 -244K7 14 /322.6
01BAC01GS008-YB15 Release Alternator Earthing Switch 6 +00BBA01.02-XDC 18 215 -246K1 14 /322.8
Terminal Diagram
-W1021
-W1016
Terminal Strip: =+01CDA01-X503
Cable Name
Cable Name
Connection to MV Busbar +00BBA01
Connection Point
Connection Point
H05VV5-F
H05VV5-F
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Spare 8 +00BBA01.02-XDC 216 /322.8
Spare 10 +00BBA01.02-XDC 217 /322.9
Spare 12 +00BBA01.02-XDC 218 /322.9
01BAC01GS003-XB01 Alternator CB is Closed 3 +00BBA01.02-XDC 341 219 -X506 204 /512.2
01BAC01GS003-XB01 Alternator CB is Closed to SaCoS 4 +00BBA01.02-XDC 343 220 -X506 205 /512.3
Terminal Diagram
-W1015
Terminal Strip: =+01CDA01-X504
Cable Name
Cable Name
Alternator CB Open/Trip Loop
Safety Connection to MV Busbar (DC 110V) +00BBA01
Connection Point
Connection Point
H05VV5-F
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01BAC01GS003-YB32 Alternator CB Open/Trip Loop 1 +00BBA01.02-XDC 7 101 -X507 101 /322.1
01BAC01GS003-YB32 Alternator CB Open/Trip Loop 3 +00BBA01.02-XDC 102 /322.2
01BAC01GS003-YB32 Alternator CB Open/Trip Loop 2 +00BBA01.02-XDC 8 201 -244K6 14 /322.2
01BAC01GS003-YB32 Alternator CB Open/Trip Loop 4 +00BBA01.02-XDC 202 /322.2
Terminal Diagram
Terminal Strip: =+01CDA01-X505
Cable Name
Cable Name
Spare
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
101
102
103
201
202
203
Terminal Diagram
-W1022
-W1020
-W1019
Terminal Strip: =+01CDA01-X506
Cable Name
Cable Name
Connection to Genset Interface Panel (DC 24V) +01CDH01
Connection Point
Connection Point
H05VV5-F
H05VV5-F
H05VV5-F
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01CDH01EZ100 Safety Chain Engine Shutdown Signal to GIP 1 +01CDH01-X506 101 101 -510S1 42 /508.5
01CDC01EY100 Emergency Stop Loop for Engine Auxiliary Drives 1 +01CDH01-X506 102 102 -510S1 11 /510.1
Spare 2 +01CDH01-X506 103 103 /510.3
01BAC01GS003-XB01 Alternator CB is Closed 1 +01CDH01-X506 104 104 -X503 119 /512.1
01BAC01GS003-XB01 Alternator CB is Closed to SaCoS 2 +01CDH01-X506 105 105 -X503 120 /512.2
01BAC01GS003-XB02 Alternator CB is Opened 3 +01CDH01-X506 106 106 -320K1 24 /514.1
Spare 4 +01CDH01-X506 107 107 /514.2
Spare 5 +01CDH01-X506 108 108 /514.3
Spare 6 +01CDH01-X506 109 109 /514.3
Spare 7 +01CDH01-X506 110 110 /514.4
Spare 8 +01CDH01-X506 111 111 /514.5
01CDH01EZ100 Safety Chain Engine Shutdown Signal to GIP 2 +01CDH01-X506 201 201 -X502 207 /508.5
01CDC01EY100 Emergency Stop Loop for Engine Auxiliary Drives 3 +01CDH01-X506 202 202 -510S1 12 /510.2
Spare 4 +01CDH01-X506 203 203 /510.4
01BAC01GS003-XB01 Alternator CB is Closed 9 +01CDH01-X506 204 204 -X503 219 /512.2
01BAC01GS003-XB01 Alternator CB is Closed to SaCoS 10 +01CDH01-X506 205 205 -X503 220 /512.3
01BAC01GS003-XB02 Alternator CB is Opened 11 +01CDH01-X506 206 206 -320K1 21 /514.2
Spare 12 +01CDH01-X506 207 207 /514.3
Spare 13 +01CDH01-X506 208 208 /514.3
Spare 14 +01CDH01-X506 209 209 /514.4
Spare 15 +01CDH01-X506 210 210 /514.4
Spare 16 +01CDH01-X506 211 211 /514.5
Terminal Diagram
-W1014
Terminal Strip: =+01CDA01-X507
Cable Name
Cable Name
Alternator CB Open/Trip Loop
Safety Connection to Engine Control Panel (AC 110V) +01CDB01
Connection Point
Connection Point
H05VV5-F
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
01BAC01GS003-YB32 Alternator CB Open/Trip Loop 1 +01CDH01-X507 101 101 -X504 101 /322.1
01BAC01GS003-YB32 Alternator CB Open/Trip Loop 3 +01CDH01-X507 102 102 /322.2
01BAC01GS003-YB32 Alternator CB Open/Trip Loop 2 +01CDH01-X507 201 201 -X500 12 /322.2
01BAC01GS003-YB32 Alternator CB Open/Trip Loop 4 +01CDH01-X507 202 202 /322.3
Terminal Diagram
Terminal Strip: =+01CDA01-XPE
Cable Name
Cable Name
PE Terminals
Connection Point
Connection Point
Cable Type
Cable Type
Terminal
Jumper
Function Text Target Designation Target Designation Internal Page / Path
Synchronization Voltage Busbar Alternator PE 1 -314P1 PE /314.3
Power Supply Unit PE 2 -A101 PE /212.2
01MKY01EZ100 Alternator Protection Relay PE 3 -500F1 PE /504.1
Synchronization Frequency Busbar Alternator PE 4 -314P2 PE /314.6
5
Cable Overview
Total Cross Cable
Length
Cable Name Function Text Cable Type Number of Section Diameter Source Target
[m]
Conductors [mm²] [mm]
+01CDA01
Panel Illumination Pre-Assembled 3x 1.5 7.60 3 -X160 -160E1-X1
-W1.INT
+01CDA01
Panel Ventilation ÖLFLEX CLASSIC 110 G 3x 1 6.00 1 -X160 -160M1
-W2.INT
+01CDA01
Door-Operated Switch ÖLFLEX CLASSIC 110 2x 1 5.80 3 -X161 -160S2
-W3.INT
+01CDA01
01CDA01CT001-XQ01 GCP Internal Panel Temperature UNITRONIC LIYCY 4x 0.75 7.00 -X500 -162R1
-W4.INT
+01CDA01
Profibus DP UNITRONIC BUS 2x 0.64 8.00 1 -A103-X1 -200A1-X1
-W5.INT
+01CDA01
Profibus DP UNITRONIC BUS 2x 0.64 8.00 1 -312P1-X1 -A103-X1
-W6.INT
+01CDA01
Patchcable from Com. Processor to Panel PC Patch cable RJ45 CAT.5e 4x2x AWG24/1 6.10 3 -216A1-X4 -A104
-W7.INT
+01CDA01
Signaling Column ÖLFLEX CLASSIC 110 4x 1 6.50 1 -X149 -242H1;-242H2;-242H3
-W8.INT
+01CDA01
Profibus DP UNITRONIC BUS 2x 0.64 8.00 2 -500F1-X1 -312P1-X1
-W9.INT
+01CDA01
Ethernet Connection to SCALANCE Patch cable RJ45 CAT.5e 4x2x AWG24 2 -A109 -216A2
-W15.INT
+01CDA01
Connection to CCP H05VV5-F 12G 1.5 15.30 9 -X500 +00CBA01.01-X501
-W1000
+01CDA01
Digital Signals MV Busbar +00BBA01 H05VV5-F 25G 1.5 22.70 25 -X503 +00BBA01.02-XDC
-W1001
+01CDA01
Earth Fault Current Alternator Star Point NYY-J 3x 4 11.20 25 +CAB-BCN2 -X400
-W1004
+01CDA01
Alternator Current for Protection NYY-J 7x 4 13.50 69 -X402 +01MKA01.02-X?
-W1006
+01CDA01
Earth Fault Current Alternator Outlet NYY-J 3x 4 11.20 69 +CAB-BCN1 -X400
-W1007
+01CDA01
Alternator Open Delta Voltage NYY-J 3x 2.5 8.10 25 -X451 +00BBA01.02-XDV
-W1008
+01CDA01
Alternator Measuring Voltage NYY-J 5x 2.5 10.00 25 -X452 +00BBA01.02-XDV
-W1009
+01CDA01
Alternator Current for Measuring NYY-J 7x 4 13.40 25 -X403 +00BBA01.02-XDA
-W1011
+01CDA01
Alternator Current for Protection ANSI 87G NYY-J 7x 4 13.40 25 -X404 +00BBA01.02-XDA
-W1012
+01CDA01
MV Busbar Measuring Voltage NYY-J 4x 2.5 8.90 9 -X450 +00CBA01.01-X451
-W1013
+01CDA01
Altern. CB Open/Trip Loop Connection to GIP H05VV5-F 5G 1.5 10.50 54 -X507 +01CDH01-X507
-W1014
+01CDA01
Altern. CB Open/Trip Loop to MV Busbar 1 H05VV5-F 5G 1.5 10.50 25 -X504 +00BBA01.02-XDC
-W1015
+01CDA01
Signals to MV Busbar +00BBA01 H05VV5-F 12G 1.5 15.30 25 -X503 +00BBA01.02-XDC
-W1016
+01CDA01
Safety Chain Engine Shutdown Signal to GIP H05VV5-F 3G 1.5 8.40 54 -X506 +01CDH01-X506
-W1019
+01CDA01
Emergency Stop Loop for Engine Auxiliary Drives H05VV5-F 5G 1.5 10.50 54 -X506 +01CDH01-X506
-W1020
+01CDA01
Altern. CB is Closed Connection to MV Busbar H05VV5-F 4G 1.5 9.50 25 -X503 +00BBA01.02-XDC
-W1021
+01CDA01
Alternator CB is Closed Connection to GIP H05VV5-F 18G 1.5 18.50 54 -X506 +01CDH01-X506
-W1022
+01CDA01
Breaker Failure External Trip to CCP H05VV5-F 3G 1.5 8.40 9 -X500 +00CBA01.01-X501
-W1023
Cable Overview
Total Cross Cable
Length
Cable Name Function Text Cable Type Number of Section Diameter Source Target
[m]
Conductors [mm²] [mm]
+01CDA01
Breaker Failure External Trip from CCP H05VV5-F 3G 1.5 8.40 9 -X500 +00CBA01.01-X501
-W1024
+01CDA01
01CDA01CT001-XQ01 GCP Internal Panel Temperature H05VVC4V5-K 5G 1.5 12.90 9 -X500 +00CBA01.01-X308
-W1025
+01CDA01
PCF Connection to GIP A-VQ(ZN)HB2Y 2x 200/230PCF 10,50 54 -200A1-X4;-200A1-X5 +01CDH01-202A1
-W2000
+01CDA01
Profibus Connection to GCP 2 UNITRONIC BUS 2x 0.64 8.00 4 -A103-X2 +02CDA01-A102-X2;+02CD
-W2002
+01CDA01
Patchcable from Com. Processor to SCADA Patch cable RJ45 CAT.5e 4x2x AWG24/1 +00CKA01-200A1 -A104
-W3050
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
1 Rittal Panel TS 8806.500 800/2000/600 TS 8806.500 Rittal TS 8806.500 031
1 Pair of Side Panels for 2.000x600mm, Screwable, RAL 7035 TS 8106.235 Rittal TS 8106.235 031
1 Wiring plan pocket of sheet steel for 800mm wide doors, RAL 7035 TS 4118.000 Rittal TS 4118.000 031
1 Door Handle: Comfort handle RAL 7035 for semi-cylinder TS 8611.070 Rittal TS 8611.070 031
1 Door Handle: Lock insert Ergoform-S, Push Button SZ 2468.000 Rittal SZ 2468.000 031
1 Door stay for escape routes TS sheet steel/stainless steel doors with tubular door frames TS 4583.500 Rittal TS 4583.500 031
4 Roof fastening screw for TS, PS, ES, DK and MC range PS 4198.000 Rittal PS 4198.000 031
1 100 pcs. Plastic cable marker, without tie, lettering field: 29x8mm KMK 2 Phoenix Contact 1005266 031
Large format insert strip, perforated, DIN A4, labeling with laser printer, M-PEN or CMS system, lettering field size: 29x8mm,
1 ESL 29X 8 Phoenix Contact 0808257 031
174-section
13 Earthing Strap M8, 16mm², Length 200mm SZ 2412.216 Rittal SZ 2412.216
-A100 1 SIMATIC S7-400, UR2 RACK, CENTRALIZED AND DISTRIBUTED WITH 9 SLOTS 2 REDUNDANT PS PLUGGABLE 6ES7400-1JA01-0AA0 Siemens 6ES7400-1JA01-0AA0 202
-A101-G1 2 Buffer Battery 3,6V 2,3Ah for S7-400, PS 405 4A/10A/20A and PS 407 4A/10A/20A 6ES7971-0BA00 Siemens 6ES7971-0BA00 212
-A101-G2 2 Buffer Battery 3,6V 2,3Ah for S7-400, PS 405 4A/10A/20A and PS 407 4A/10A/20A 6ES7971-0BA00 Siemens 6ES7971-0BA00 212
-A103-D1 1 SIMATIC S7, MEMORY CARD FOR S7-400, LONG DESIGN, 5V FLASH-EPROM, 4 MBYTE 6ES7952-1KM00-0AA0 Siemens 6ES7952-1KM00-0AA0 214
SIMATIC DP, PROFIBUS Plug up to 12 MBIT/S, 35° Cable Output, Terminating Resistor with Separating Function,
-A103-X1 1 6ES7972-0BB42-0XA0 Siemens 6ES7972-0BB42-0XA0 214
PG-Connection
SIMATIC DP, PROFIBUS Plug up to 12 MBIT/S, 35° Cable Output, Terminating Resistor with Separating Function,
-A103-X2 1 6ES7972-0BB42-0XA0 Siemens 6ES7972-0BB42-0XA0 214
PG-Connection
-A104 1 CP 443-1 Communication Processor for Industrial Ethernet 6GK7443-1EX20-0XE0 Siemens 6GK7443-1EX20-0XE0 216
-A105-X1 1 Front Connector 492 With Screw Contacts, 48-PIN, SIMATIC S7-400 6ES7492-1AL00-0AA0 Siemens 6ES7492-1AL00-0AA0 204
-A106-X1 1 Front Connector 492 With Screw Contacts, 48-PIN, SIMATIC S7-400 6ES7492-1AL00-0AA0 Siemens 6ES7492-1AL00-0AA0 206
-A107-X1 1 Front Connector 492 With Screw Contacts, 48-PIN, SIMATIC S7-400 6ES7492-1AL00-0AA0 Siemens 6ES7492-1AL00-0AA0 208
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-A108 1 SM 422, 32DO, DC 24V, 0.5A 6ES7422-1BL00-0AA0 Siemens 6ES7422-1BL00-0AA0 210
-A108-X1 1 Front Connector 492 With Screw Contacts, 48-PIN, SIMATIC S7-400 6ES7492-1AL00-0AA0 Siemens 6ES7492-1AL00-0AA0 210
PB OLM/P12 V4.0 OPTICAL LINK MODULE W. 1 RS485 AND 2 PLASTIC-FOC-INTERFACE (4 BFOC-SOCKETS), 4
-200A1 1 6GK1503-3CA00 Siemens 6GK1503-3CA00 200
BFOC-CONNECTORS INCLUDED
SIMATIC DP, PROFIBUS Plug up to 12 MBIT/S, 90° Cable Output, Terminating Resistor with Separating Function,
-200A1-X1 1 6ES7972-0BB12-0XA0 Siemens 6ES7972-0BB12-0XA0 200
PG-Connection
-200A1-X2 1 PROFIBUS PLASTIC FIBER OPTIC, BFOC CONNECTOR 6GK1900-0HB00-0AC0 Siemens 6GK1900-0HB00-0AC0 200
-200A1-X3 1 PROFIBUS PLASTIC FIBER OPTIC, BFOC CONNECTOR 6GK1900-0HB00-0AC0 Siemens 6GK1900-0HB00-0AC0 200
-200A1-X4 1 PROFIBUS PLASTIC FIBER OPTIC, BFOC CONNECTOR 6GK1900-0HB00-0AC0 Siemens 6GK1900-0HB00-0AC0 200
-200A1-X5 1 PROFIBUS PLASTIC FIBER OPTIC, BFOC CONNECTOR 6GK1900-0HB00-0AC0 Siemens 6GK1900-0HB00-0AC0 200
-216A1 1 Touch Panel PC 21,5" (1920x1080), Core2 Duo 2,26GHz, 80GB 2,5" HDD, 4GB DDR3, MDT Label OPC 7022 ads-tec DVG-OPC7022-059-HW 216
-216A2 1 SCALANCE X204-2, MANAGED IE SWITCH, 4 X 10/100MBIT/S RJ45 PORTS, 2 X 100MBIT/S MULTIMODE BFOC 6GK5204-2BB10-2AA3 SIEMENS 6GK5204-2BB10-2AA3 216
Synchrocheck Relay for Generator/Busbar Synchronization, Frequency Range 40-70Hz, Dead bus (Option B1), Continuous HAS-111DG - 110V AC - 1
-316A1 1 HAS-111 DG DEIF 316
sync. pulse (Option D) 10V AC - Option B1+D
-316A2 1 One Breaker Synchronizer 3-phase, Power Supply 24V DC, Measuring Input 100-400V AC SPM-D1010B/YB Woodward 8440-1021 316
-160E1 1 Courtesy light with door-operated switch 18W/100-240V, 50/60Hz SZ 4139.190 Rittal SZ 4139.190 160
-100F1 1 Miniature Circuit Breaker (MCB) 1-pole 10A, Tripping Characteristic B, 10kA 5SY4 110-6 Siemens 5SY4 110-6 100
-100F1 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 100
-104F1 1 Miniature Circuit Breaker (MCB) 2-pole 10A, Tripping Characteristic C, 10kA 5SY4 210-7 Siemens 5SY4 210-7 104
-104F1 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 104
-106F1 1 Miniature Circuit Breaker (MCB) 1-pole 6A, Tripping Characteristic B, 10kA 5SY4 106-6 Siemens 5SY4 106-6 106
-106F1 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 106
-106F2 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 106
-106F2 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 106
-106F3 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 106
-106F3 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 106
-106F4 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 106
-106F4 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 106
-106F5 1 Miniature Circuit Breaker (MCB) 1-pole 10A, Tripping Characteristic B, 10kA 5SY4 110-6 Siemens 5SY4 110-6 106
-106F5 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 106
-106F6 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 106
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-106F6 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 106
-108F1 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 108
-108F1 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 108
-108F2 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 108
-108F2 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 108
-108F3 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 108
-108F3 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 108
-108F4 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 108
-108F4 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 108
-110F1 1 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA 5SY4 102-5 Siemens 5SY4 102-5 110
-110F1 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 110
-304F1 1 Miniature Circuit Breaker (MCB) 2-pole 2A, Tripping Characteristic A, 10kA 5SY4 202-5 Siemens 5SY4 202-5 304
-304F1 1 Auxiliary Switch 1NO + 1NC For MCBs 5ST3010 Siemens 5ST3010 304
SIPROTEC 4 Multifunction Protection Relay for Motor, Alternator and Transformer (Function Alternator Basic), 1A, Supply 7UM6211-2EB91-0BC0-L0 7UM6211-2EB91-0BC0-L0
-500F1 1 Siemens 500
Voltage 24 to 48V DC A A
SIMATIC DP, PROFIBUS Plug up to 12 MBIT/S, 90° Cable Output, Terminating Resistor with Separating Function,
-500F1-X1 1 6ES7972-0BB12-0XA0 Siemens 6ES7972-0BB12-0XA0 506
PG-Connection
-104G1 1 SITOP Modular 20 Power Supply, Input: 120/230V AC, Output: 24V DC/20A 6EP1336-3BA00 Siemens 6EP1336-3BA00 104
-104G2 1 SITOP buffer module for 6EP1X3X-3BAX0 buffering time 100ms till 10s dependent upon load 6EP1961-3BA01 Siemens 6EP1961-3BA01 104
-242H1 1 Continuous Illuminated Element RED for Signaling Column (70mm), LED, 24V UC 8WD44-20-5AB Siemens 8WD44-20-5AB 242
-242H1 1 Connecting Element for Signaling Column (70mm), Incl. Cover for Pipe-, Basement- and Bracket Assembly 8WD44-08-0AA Siemens 8WD44-08-0AA 242
-242H1 1 Mounting base with Duct for Signaling Column (50mm/70mm), Duct length 100mm 8WD43-08-0DA Siemens 8WD43-08-0DA 242
-242H2 1 Continuous Illuminated Element YELLOW for Signaling Column (70mm), LED, 24V UC 8WD44-20-5AD Siemens 8WD44-20-5AD 242
-242H3 1 Continuous Illuminated Element GREEN for Signaling Column (70mm), LED, 24V UC 8WD44-20-5AC Siemens 8WD44-20-5AC 242
-242H4 1 LED Switch Position indicator square, 25x25mm, green/red, 24V DC SUS-01-Q Weigel SUS-01-Q-G/R-24DC 242
-242H5 1 LED Switch Position indicator round, ø25mm, green/red, 24V DC SUS-01 Weigel SUS-01-G/R-24DC 242
-242H6 1 LED Switch Position indicator round, ø25mm, green/red, 24V DC SUS-01 Weigel SUS-01-G/R-24DC 242
PR1-RSP3-LDP-24DC/2X2
-160K1 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 160
1
PR2-RSP3-LDP-24DC/4X2
-244K1 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 4 Changeover Contacts Phoenix Contact 2834766 244
1AU
PR2-RSP3-LDP-24DC/4X2
-244K2 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 4 Changeover Contacts Phoenix Contact 2834766 244
1AU
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
PR2-RSP3-LDP-24DC/4X2
-244K3 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 4 Changeover Contacts Phoenix Contact 2834766 244
1AU
PR2-RSP3-LDP-24DC/4X2
-244K4 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 4 Changeover Contacts Phoenix Contact 2834766 244
1AU
PR2-RSP3-LDP-24DC/4X2
-244K5 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 4 Changeover Contacts Phoenix Contact 2834766 244
1AU
-244K6 1 Contactor Relay, 2NC/2NO, 24V DC, Screw Connection, integrated Varistor DILA-22(24VDC) Moeller 276414 244
-244K7 1 Contactor Relay, 2NC/2NO, 24V DC, Screw Connection, integrated Varistor DILA-22(24VDC) Moeller 276414 244
PR2-RSP3-LDP-24DC/4X2
-244K8 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 4 Changeover Contacts Phoenix Contact 2834766 244
1AU
-246K1 1 Contactor Relay, 2NC/2NO, 24V DC, Screw Connection, integrated Varistor DILA-22(24VDC) Moeller 276414 246
PR1-RSP3-LDP-24DC/2X2
-246K2 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 246
1
PR1-RSP3-LDP-24DC/2X2
-246K3 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 246
1
PR1-RSP3-LDP-24DC/2X2
-246K4 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 246
1
PR1-RSP3-LDP-24DC/2X2
-246K5 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 246
1
PR1-RSP3-LDP-24DC/2X2
-246K6 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 246
1
PR1-RSP3-LDP-24DC/2X2
-246K7 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 246
1
PR1-RSP3-LDP-24DC/2X2
-246K8 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 246
1
-318K1 1 Contactor Relay, 2NC/2NO, 24V DC, Screw Connection, integrated Varistor DILA-22(24VDC) Moeller 276414 318
PR2-RSP3-LDP-24DC/4X2
-320K1 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 4 Changeover Contacts Phoenix Contact 2834766 320
1AU
PR1-RSP3-LDP-24DC/2X2
-320K2 1 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 320
1
-160M1 1 Fan and Filter Unit 230m³/h 230V, 50/60Hz, RAL 7035 SK 3241.100 Rittal SK 3241.100 160
-160M1.1 1 Roof-mounted fan, without fan motor RAL 7035 SK 3148.007 Rittal SK 3148.007 160
-304P1 1 Voltmeter, measuring range 0...110V, Scale 0...17,94kV/0...143V, 15...100Hz EQ96K WEIGEL 674.130.00 304
-306P1 1 Analog Ammeter 0-700A, 15-100Hz, for Current Transformer 700/1A, 90° Scale EQ96K WEIGEL 684.130.1000 306
Multifunctional Monitoring Unit, L-N: 0-300V AC, L-L: 0-520V AC, 45-65Hz, Profibus Interface ext. Power Supply 20-250V AC /
-312P1 1 UMG96RM-P Janitza Electronics 52.22.037 312
20-300V DC
-312P1 1 Seal to increase protection degree of MMU from IP50 to IP65 D96 Janitza Electronics 29.01.907 312
SIMATIC DP, PROFIBUS Plug up to 12 MBIT/S, 90° Cable Output, Terminating Resistor with Separating Function,
-312P1-X1 1 6ES7972-0BB12-0XA0 Siemens 6ES7972-0BB12-0XA0 312
PG-Connection
-314P1 1 Double Voltmeter, Analog 0-17,94kV, 15-100Hz, for Voltage Transformer 13,8kV/110V, Horizontal Scale WQ96/2S WEIGEL 023.130.0609 314
-314P2 1 Double Frequency Meter 2x55-65Hz, 2x21 reeds, 2x110V FQ96/2 WEIGEL 031.130.0164.00 314
-314P3 1 Read Synchroscope Type RSQ-3, Frequency Range 40-70Hz (supply), 100-127V AC, Land RSQ-3-115V DEIF RSQ-3-115V 314
-304Q1 1 LEISTUNGSSCHALTER BGR. S00, FUER DEN MOTORSCHUTZ, CLASS 10 A-AUSL. 1,4...2A, N-AUSL. 26A, SCHRAUBANSCHLUSS 3RV2011-1BA10 SIEMENS 3RV20111BA10 304
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-304Q1 1 TRANSVERSE AUX. SWITCH, 1NO+1NC, SCREW CONNECTION, FOR CIRCUIT-BREAKERS, SZ S00/S0 3RV2901-1E SIEMENS 3RV2901-1E 304
-310Q1 1 LEISTUNGSSCHALTER BGR. S00, FUER DEN MOTORSCHUTZ, CLASS 10 A-AUSL. 1,4...2A, N-AUSL. 26A, SCHRAUBANSCHLUSS 3RV2011-1BA10 SIEMENS 3RV20111BA10 310
-310Q1 1 TRANSVERSE AUX. SWITCH, 1NO+1NC, SCREW CONNECTION, FOR CIRCUIT-BREAKERS, SZ S00/S0 3RV2901-1E SIEMENS 3RV2901-1E 310
-162R1 1 SAK Series, PT100 terminal, Rated cross-section: 4mm², Screw connection, PA 66, beige DKT 4/35 PT100 Weidmüller 8014720000 162
-162R1 1 General accessories, End bracket WEW 35/2 Weidmüller 1061200000 162
-162R1 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000 162
-160S1 1 Small Thermostat KTS011, Temperature Range 0-60°C (+/- 4K) NO KTS 011 Stego 01141.0-00 160
-160S2 1 Door-operated switch, including mounting accessories SZ 4127.010 Rittal SZ 4127.010 160
-224S1 1 Push Button BLUE, 1NC+1NO, Spring-Type Terminals 3SB3201-0AA51-0CC0 SIEMENS 3SB3201-0AA51-0CC0 224
-224S1 1 Holder for Pushbutton and Switches for Snapping on 3 Blocks 3SB3901-0AB Siemens 3SB3901-0AB 224
-224S2 1 Push Button BLACK, 1NC+1NO, Spring-Type Terminals 3SB3201-0AA11-0CC0 SIEMENS 3SB3201-0AA11-0CC0 224
-224S2 1 Holder for Pushbutton and Switches for Snapping on 3 Blocks 3SB3901-0AB Siemens 3SB3901-0AB 224
-224S3 1 22mm Plastic round actuator: Selector Switch 3 Positions I-O-II, 2x50°, latching, black 3SB3000-2DA11 SIEMENS 3SB3000-2DA11 224
-224S3 2 Auxiliary Switch 1NO, Spring-Type Terminals 3SB3403-0B Siemens 3SB3403-0B 224
-224S3 1 Holder for Pushbutton and Switches for Snapping on 3 Blocks 3SB3901-0AB Siemens 3SB3901-0AB 224
-224S4 1 22mm Plastic round actuator: Selector Switch 2 Positions O-I, 90°, latching, black 3SB3000-2HA11 SIEMENS 3SB3000-2HA11 224
-224S4 2 Auxiliary Switch 1NO+1NC, Spring-Type Terminals 3SB3403-0A Siemens 3SB3403-0A 224
-224S4 1 Holder for Pushbutton and Switches for Snapping on 3 Blocks 3SB3901-0AB Siemens 3SB3901-0AB 224
-224S5 1 Push Button RED, 1NC+1NO, Spring-Type Terminals 3SB3201-0AA21-0CC0 SIEMENS 3SB3201-0AA21-0CC0 224
-224S5 1 Auxiliary Switch 1NC, Spring-Type Terminals 3SB3403-0C Siemens 3SB3403-0C 224
-224S5 1 Holder for Pushbutton and Switches for Snapping on 3 Blocks 3SB3901-0AB Siemens 3SB3901-0AB 224
-224S6 1 Push Button GREEN, 1NC+1NO, Spring-Type Terminals 3SB3201-0AA41-0CC0 SIEMENS 3SB3201-0AA41-0CC0 224
-224S6 1 Holder for Pushbutton and Switches for Snapping on 3 Blocks 3SB3901-0AB Siemens 3SB3901-0AB 224
-226S1 1 22mm Plastic round actuator: Selector Switch 3 Positions I-O-II, 2x50°, momentary contact, black 3SB3000-2EA11 SIEMENS 3SB3000-2EA11 226
-226S1 2 Auxiliary Switch 1NO, Spring-Type Terminals 3SB3403-0B Siemens 3SB3403-0B 226
-226S1 1 Holder for Pushbutton and Switches for Snapping on 3 Blocks 3SB3901-0AB Siemens 3SB3901-0AB 226
-226S2 1 22mm Plastic round actuator: Selector Switch 3 Positions I-O-II, 2x50°, momentary contact, black 3SB3000-2EA11 SIEMENS 3SB3000-2EA11 226
-226S2 2 Auxiliary Switch 1NO, Spring-Type Terminals 3SB3403-0B Siemens 3SB3403-0B 226
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-304S1 1 Voltage Selector Switch with OFF-Position, 3 phase to phase Voltages DH10 A004-614 F776 FT2 Kraus & Naimer DH10 A004-614 F776 FT2 304
-510S1 1 Emergency Stop Push Button 1NO+1NC, Spring-Type Terminals 3SB3201-1HA20-0CC0 SIEMENS 3SB3201-1HA20-0CC0 510
-510S1 1 Auxiliary Switch 1NO+1NC, Spring-Type Terminals 3SB3403-0A Siemens 3SB3403-0A 510
-510S1 1 Auxiliary Switch 2NC, Spring-Type Terminals 3SB3403-0E Siemens 3SB3403-0E 510
-510S1 1 Protective collar for Emergency Stop, yellow 3SB3921-0AK Siemens 3SB3921-0AK 510
-510S1 1 Holder for Pushbutton and Switches for Snapping on 3 Blocks 3SB3901-0AB Siemens 3SB3901-0AB 510
-W1.INT 1 Connection Cable grey, UL 3.000mm, with socket SZ 4315.150 Rittal SZ 4315.150 160
-W7.INT 1 Patch cable RJ45 CAT.5e S-FTP 3,0m grey Patch cable RJ45 LAPP CE6651 216
-X10 1 General accessories, End and intermediate plate, dark beige, 1.5mm WAP 2.5-10 Weidmüller 1050000000
-X10 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X10 1 W terminal, 2,5mm², Screw connection, Wemid, dark beige WDU 2.5 Weidmüller 1020000000 100
-X10 1 W terminal, 2,5mm², Screw connection, Wemid, blue WDU 2.5 BL Weidmüller 1020080000 100
-X10 1 W terminal, Earth terminal, 2,5mm², Screw connection, Wemid, green/yellow WPE 2.5 Weidmüller 1010000000 100
-X20 1 General accessories, End and intermediate plate, dark beige, 1.5mm WAP 2.5-10 Weidmüller 1050000000
-X20 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X20 1 W terminal, 2,5mm², Screw connection, Wemid, dark beige WDU 2.5 Weidmüller 1020000000 102
-X20 1 W terminal, 2,5mm², Screw connection, Wemid, blue WDU 2.5 BL Weidmüller 1020080000 102
-X20 2 W terminal, Earth terminal, 2,5mm², Screw connection, Wemid, green/yellow WPE 2.5 Weidmüller 1010000000 102;104
-X100 1 General accessories, End and intermediate plate, dark beige, 2mm ZAP/TW 5 Weidmüller 1608830000
-X100 15 Z terminal, 6mm², Tension clamp connection, Wemid, blue ZDU 6 BL Weidmüller 1608630000 104;106;108;110
-X100 3 Z terminal, Earth terminal, 6mm², Tension clamp connection, Wemid, green/yellow ZPE 6 Weidmüller 1608670000 104;216
-X100 2 Z terminal, 6mm², Tension clamp connection, Wemid, dark beige ZDU 6 Weidmüller 1608620000 104
-X100 1 Cross-connector / link for modular terminal, No. of poles: 2 ZQV 6/2 GE Weidmüller 1627850000
-X100 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X100 1 Cross-connector / link for modular terminal, No. of Poles: 24 ZQV 6/24 GE Weidmüller 1908990000
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-X120 5 Initiator and actuator terminal base terminal, 1.5mm², Wemid, dark beige ZPV 1.5 Weidmüller 1676630000
-X120 2 End and intermediate plate, dark beige, 5.08 mm ZAP/TW ZPV1.5 Weidmüller 1674650000
-X120 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X120 10 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, brown ZVL 1.5 BR Weidmüller 1650370000 106;200;212;216
-X120 10 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, blue ZVL 1.5 BL Weidmüller 1650360000 106;200;212;216
-X121 5 Initiator and actuator terminal base terminal, 1.5mm², Wemid, dark beige ZPV 1.5 Weidmüller 1676630000
-X121 2 End and intermediate plate, dark beige, 5.08 mm ZAP/TW ZPV1.5 Weidmüller 1674650000
-X121 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X121 10 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, brown ZVL 1.5 BR Weidmüller 1650370000 106;242;244;246;248
-X121 10 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, blue ZVL 1.5 BL Weidmüller 1650360000 106;224;232;240;248
-X123 17 Initiator and actuator terminal base terminal, 1.5mm², Wemid, dark beige ZPV 1.5 Weidmüller 1676630000
-X123 2 End and intermediate plate, dark beige, 5.08 mm ZAP/TW ZPV1.5 Weidmüller 1674650000
-X123 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
106;160;200;218;220;224
-X123 34 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, brown ZVL 1.5 BR Weidmüller 1650370000
;226;230;232
-X123 34 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, blue ZVL 1.5 BL Weidmüller 1650360000 106;160;242;244;246
-X130 10 Initiator and actuator terminal base terminal, 1.5mm², Wemid, dark beige ZPV 1.5 Weidmüller 1676630000
-X130 2 End and intermediate plate, dark beige, 5.08 mm ZAP/TW ZPV1.5 Weidmüller 1674650000
-X130 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X130 20 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, brown ZVL 1.5 BR Weidmüller 1650370000 106;312;316
-X130 20 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, blue ZVL 1.5 BL Weidmüller 1650360000 106;312;316
-X149 1 General accessories, End and intermediate plate, dark beige, 2mm ZAP/TW 1 Weidmüller 1608740000
-X149 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X149 4 Z terminal, 2.5mm², Tension clamp connection, Wemid, dark beige ZDU 2.5 Weidmüller 1608510000 242
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-X150 8 Initiator and actuator terminal base terminal, 1.5mm², Wemid, dark beige ZPV 1.5 Weidmüller 1676630000
-X150 2 End and intermediate plate, dark beige, 5.08 mm ZAP/TW ZPV1.5 Weidmüller 1674650000
-X150 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X150 16 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, brown ZVL 1.5 BR Weidmüller 1650370000 110;318;504
-X150 16 Initiator and actuator terminal, 1.5mm², Tension clamp connection, Wemid, blue ZVL 1.5 BL Weidmüller 1650360000 110;318;504
-X160 1 General accessories, End and intermediate plate, dark beige, 2mm ZAP/TW 1 Weidmüller 1608740000
-X160 5 Z terminal, 2.5mm², Tension clamp connection, Wemid, dark beige ZDU 2.5 Weidmüller 1608510000 160
-X160 5 Z terminal, 2.5mm², Tension clamp connection, Wemid, blue ZDU 2.5 BL Weidmüller 1608520000 160
-X160 5 Z terminal, Earth terminal, 2.5mm², Tension clamp connection, Wemid, green/yellow, number of connections: 2 ZPE 2.5 Weidmüller 1608640000 160
-X160 1 Cross-connector / link for modular terminal, No. of poles: 2 ZQV 2.5/2 Weidmüller 1608860000
-X160 1 Cross-connector / link for modular terminal, No. of poles: 5 ZQV 2.5/5 Weidmüller 1608890000
-X160 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X161 1 General accessories, End and intermediate plate, dark beige, 2mm ZAP/TW 1 Weidmüller 1608740000
-X161 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X161 2 Z terminal, 2.5mm², Tension clamp connection, Wemid, dark beige ZDU 2.5 Weidmüller 1608510000 160
-X400 1 Z-series, Partition plate, dark beige, 2mm ZTW ZTL6 Weidmüller 1771870000
-X400 2 Z-series, Accessories, Cross-connector, No. of poles: 2 KSBR/2 ZTL6 Weidmüller 1771820000
-X400 2 W terminal, Earth terminal, 6mm², Screw connection, Wemid, green/yellow WPE 6 Weidmüller 1010200000 300;302
-X400 1 Cross-connector / link for modular terminal, No. of poles: 2 ZQV 6/2 GE Weidmüller 1627850000
-X400 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X400 4 Z terminal, disconnect terminal with tension spring connection 6mm², Wemid, dark beige ZTL 6 Weidmüller 1771800000 300;302
-X401 1 Z-series, Partition plate, dark beige, 2mm ZTW ZTL6 Weidmüller 1771870000
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-X401 3 Z-series, Accessories, Cross-connector, No. of poles: 2 KSBR/2 ZTL6 Weidmüller 1771820000
-X401 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X401 6 Z terminal, disconnect terminal with tension spring connection 6mm², Wemid, dark beige ZTL 6 Weidmüller 1771800000 300
-X401 1 W terminal, Earth terminal, 6mm², Screw connection, Wemid, green/yellow WPE 6 Weidmüller 1010200000 300
-X402 1 Z-series, Partition plate, dark beige, 2mm ZTW ZTL6 Weidmüller 1771870000
-X402 3 Z-series, Accessories, Cross-connector, No. of poles: 2 KSBR/2 ZTL6 Weidmüller 1771820000
-X402 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X402 6 Z terminal, disconnect terminal with tension spring connection 6mm², Wemid, dark beige ZTL 6 Weidmüller 1771800000 302
-X402 1 W terminal, Earth terminal, 6mm², Screw connection, Wemid, green/yellow WPE 6 Weidmüller 1010200000 302
-X403 1 Z-series, Partition plate, dark beige, 2mm ZTW ZTL6 Weidmüller 1771870000
-X403 3 Z-series, Accessories, Cross-connector, No. of poles: 2 KSBR/2 ZTL6 Weidmüller 1771820000
-X403 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X403 6 Z terminal, disconnect terminal with tension spring connection 6mm², Wemid, dark beige ZTL 6 Weidmüller 1771800000 306
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-X403 1 W terminal, Earth terminal, 6mm², Screw connection, Wemid, green/yellow WPE 6 Weidmüller 1010200000 306
-X404 1 Z-series, Partition plate, dark beige, 2mm ZTW ZTL6 Weidmüller 1771870000
-X404 3 Z-series, Accessories, Cross-connector, No. of poles: 2 KSBR/2 ZTL6 Weidmüller 1771820000
-X404 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X404 6 Z terminal, disconnect terminal with tension spring connection 6mm², Wemid, dark beige ZTL 6 Weidmüller 1771800000 306
-X404 1 W terminal, Earth terminal, 6mm², Screw connection, Wemid, green/yellow WPE 6 Weidmüller 1010200000 306
-X450 1 Z-series, Partition plate, dark beige, 2mm ZTW ZTL6 Weidmüller 1771870000
-X450 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X450 3 Z terminal, disconnect terminal with tension spring connection 6mm², Wemid, dark beige ZTL 6 Weidmüller 1771800000 310
-X450 1 W terminal, Earth terminal, 6mm², Screw connection, Wemid, green/yellow WPE 6 Weidmüller 1010200000 310
-X451 1 Z-series, Partition plate, dark beige, 2mm ZTW ZTL6 Weidmüller 1771870000
-X451 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X451 2 Z terminal, disconnect terminal with tension spring connection 6mm², Wemid, dark beige ZTL 6 Weidmüller 1771800000 304
-X451 1 W terminal, Earth terminal, 6mm², Screw connection, Wemid, green/yellow WPE 6 Weidmüller 1010200000 304
-X452 1 Z-series, Partition plate, dark beige, 2mm ZTW ZTL6 Weidmüller 1771870000
-X452 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X452 4 Z terminal, disconnect terminal with tension spring connection 6mm², Wemid, dark beige ZTL 6 Weidmüller 1771800000 304
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-X452 1 W terminal, Earth terminal, 6mm², Screw connection, Wemid, green/yellow WPE 6 Weidmüller 1010200000 304
-X454 1 General accessories, End and intermediate plate, blue, 2mm ZAP/TW 3 BL Weidmüller 1608810000
-X454 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X454 6 Z terminal, 2.5mm², 4 Connection Points, Tension clamp connection, Wemid, dark beige ZDU 2.5/4AN Weidmüller 1608570000 304;312
-X454 3 Cross-connector / link for modular terminal, No. of poles: 2 ZQV 2.5/2 Weidmüller 1608860000 304
-X454 1 Z terminal, 2.5mm², 4 Connection Points, Tension clamp connection, Wemid, blue ZDU 2.5/4AN BL Weidmüller 1608580000 312
-X455 1 General accessories, End and intermediate plate, dark beige, 2mm ZAP/TW 3 Weidmüller 1608800000
-X455 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X455 8 Z terminal, 2.5mm², 4 Connection Points, Tension clamp connection, Wemid, dark beige ZDU 2.5/4AN Weidmüller 1608570000 314
-X455 4 Cross-connector / link for modular terminal, No. of poles: 2 ZQV 2.5/2 Weidmüller 1608860000 314
-X500 1 General accessories, End and intermediate plate, dark beige, 2mm ZAP/TW 1 Weidmüller 1608740000
-X500 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X500 17 Z terminal, 2.5mm², Tension clamp connection, Wemid, dark beige ZDU 2.5 Weidmüller 1608510000 162;228;516
-X501 1 General accessories, End and intermediate plate, dark beige, 1.5mm ZAP/TW ZDK2.5 Weidmüller 1674730000
-X501 1 Cross-connector / link for modular terminal, No. of poles: 10 ZQV 2.5/10 Weidmüller 1608940000
-X501 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X501 8 Z terminal, Double level, 2.5mm², Tension clamp connection, Wemid, dark beige ZDK 2.5 Weidmüller 1674300000 234;508
-X502 1 General accessories, End and intermediate plate, dark beige, 1.5mm ZAP/TW ZDK2.5 Weidmüller 1674730000
-X502 1 Cross-connector / link for modular terminal, No. of poles: 10 ZQV 2.5/10 Weidmüller 1608940000
-X502 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X502 8 Z terminal, Double level, 2.5mm², Tension clamp connection, Wemid, dark beige ZDK 2.5 Weidmüller 1674300000 236;508
-X503 1 General accessories, End and intermediate plate, dark beige, 1.5mm ZAP/TW ZDK2.5 Weidmüller 1674730000
Parts List
Graphical
Supplier
Device Tag Quantity Description Type Number Manufacturer Page of
Order Number
Wiring Diagram
-X503 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X503 20 Z terminal, Double level, 2.5mm², Tension clamp connection, Wemid, dark beige ZDK 2.5 Weidmüller 1674300000 230;320;322;512
-X503 1 Cross-connector / link for modular terminal, No. of poles: 20 ZQV 2.5/20 Weidmüller 1908960000
-X504 1 General accessories, End and intermediate plate, dark beige, 1.5mm ZAP/TW ZDK2.5 Weidmüller 1674730000
-X504 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X504 2 Z terminal, Double level, 2.5mm², Tension clamp connection, Wemid, dark beige ZDK 2.5 Weidmüller 1674300000 322
-X505 1 General accessories, End and intermediate plate, dark beige, 1.5mm ZAP/TW ZDK2.5 Weidmüller 1674730000
-X505 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X505 3 Z terminal, Double level, 2.5mm², Tension clamp connection, Wemid, dark beige ZDK 2.5 Weidmüller 1674300000
-X505 1 Cross-connector / link for modular terminal, No. of poles: 3 ZQV 2.5/3 Weidmüller 1608870000
-X506 1 General accessories, End and intermediate plate, dark beige, 1.5mm ZAP/TW ZDK2.5 Weidmüller 1674730000
-X506 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X506 11 Z terminal, Double level, 2.5mm², Tension clamp connection, Wemid, dark beige ZDK 2.5 Weidmüller 1674300000 508;510;512;514
-X507 1 General accessories, End and intermediate plate, dark beige, 1.5mm ZAP/TW ZDK2.5 Weidmüller 1674730000
-X507 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-X507 2 Z terminal, Double level, 2.5mm², Tension clamp connection, Wemid, dark beige ZDK 2.5 Weidmüller 1674300000 322
-XPE 1 General accessories, End and intermediate plate, dark beige, 2mm ZAP/TW 1 Weidmüller 1608740000
-XPE 1 Terminal markers, 30x8mm, Polypropylene, transparent for WEW 35/2 and ZEW 35/2 EM 8/30 Weidmüller 1806120000
-XPE 1 Z terminal, Earth terminal, 6mm², Tension clamp connection, Wemid, green/yellow ZPE 6 Weidmüller 1608670000 314
-XPE 4 Z terminal, Earth terminal, 2.5mm², Tension clamp connection, Wemid, green/yellow, number of connections: 2 ZPE 2.5 Weidmüller 1608640000 212;314;504
The following list indicates the protection degree of the panel door, side wall or the roof-mounted parts/devices.
The protection degree of the panel itself is IP55, as indicated on the attached certificate.
A proper mounting of the Door lever doesn't decrease the Protection Degree.
For this panel a protection degree of, at least, IP41 has been specified. This protection degree is determined
by the device with the lowest protection degree mounted in the door, side walls or roof.
The protection degrees of the installed devices are indicated on the following list and the attached data sheets.
Disclaimer:
The certified protection degree only applies for the delivered panel.
Inappropriate installation or subsequent modification of the panel could affect the protection degree
and therefore releases the manufacturer from its liability
regarding the compliance with the specified protection degree.
-216A1 Touch Panel PC 21,5" (1920x1080), Core2 Duo 2,26GHz, 80GB 2,5" HDD, 4GB DDR3, MDT Label IP 65
-316A2 One Breaker Synchronizer 3-phase, Power Supply 24V DC, Measuring Input 100-400V AC IP 42
-500F1 SIPROTEC 4 Multifunction Protection Relay for Motor, Alternator and Transformer (Function Alternator Basic), 1A, Supply Voltage 24 to 48V DC IP 51
-242H1 Continuous Illuminated Element RED for Signaling Column (70mm), LED, 24V UC IP 65
-242H2 Continuous Illuminated Element YELLOW for Signaling Column (70mm), LED, 24V UC IP 65
-242H3 Continuous Illuminated Element GREEN for Signaling Column (70mm), LED, 24V UC IP 65
-160M1 Fan and Filter Unit 230m³/h 230V, 50/60Hz, RAL 7035 IP 54
-304P1 Voltmeter, measuring range 0...110V, Scale 0...17,94kV/0...143V, 15...100Hz IP 52 (65 with Seal IP 96h)
-306P1 Analog Ammeter 0-700A, 15-100Hz, for Current Transformer 700/1A, 90° Scale IP 52
-312P1 Multifunctional Monitoring Unit, L-N: 0-300V AC, L-L: 0-520V AC, 45-65Hz, Profibus Interface ext. Power Supply 20-250V AC / 20-300V DC IP 40 (65 with Seal D96)
-314P1 Double Voltmeter, Analog 0-17,94kV, 15-100Hz, for Voltage Transformer 13,8kV/110V, Horizontal Scale IP 52
-314P3 Read Synchroscope Type RSQ-3, Frequency Range 40-70Hz (supply), 100-127V AC, Land IP 52
-224S3 22mm Plastic round actuator: Selector Switch 3 Positions I-O-II, 2x50°, latching, black IP 66
-224S4 22mm Plastic round actuator: Selector Switch 2 Positions O-I, 90°, latching, black IP 66
-226S1 22mm Plastic round actuator: Selector Switch 3 Positions I-O-II, 2x50°, momentary contact, black IP 66
-226S2 22mm Plastic round actuator: Selector Switch 3 Positions I-O-II, 2x50°, momentary contact, black IP 66
The following calculation indicates the power consumption (current) for each available power supply in the panel.
The consumption values are listed for consumers inside and outside of the panel.
The basis for the calculation is the maximum load of all consumers.
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Maximum
Consumption 0,55 0,55
per Device [A]
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Maximum
Consumption 3,5 3,5
per Device [A]
Nominal Current [A] 0,2 0,030 0 0,019 3,125 0,058 6 x 0,007 = 0,042
Device Tag
Device Tag
Device Tag
Device Tag
Maximum
Consumption 4,20 0,961 0 0,285 3,125 0,474 0,042 9,087
per Device [A]
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Device Tag
Maximum
Consumption 0,106 0,014 0,007 0,633 9,847
per Device [A]
The heating and cooling calculation indicates the required cooling capacity in accordance with the power losses within the panel,
as well as the specified ambient conditions and the actual cooling capacity.
The power dissipation of the consumers installed in the panel is indicated and added in the following parts list.
The result, the total power dissipation of the installed equipment, is indicated on the last page.
The basis for the calculation is the maximum load of all consumers with a power dissipation.
-A104 1 CP 443-1 Communication Processor for Industrial Ethernet Siemens 6GK7443-1EX20-0XE0 8,6 8,6
-216A2 1 SCALANCE X204-2, MANAGED IE SWITCH, 4 X 10/100MBIT/S RJ45 PORTS, 2 X 100MBIT/S MULTIMODE BFOC SIEMENS 6GK5204-2BB10-2AA3 6,36 6,36
Synchrocheck Relay for Generator/Busbar Synchronization, Frequency Range 40-70Hz, Dead bus (Option B1), HAS-111DG - 110V AC - 110
-316A1 1 DEIF 2 2
Continuous sync. pulse (Option D) V AC - Option B1+D
-316A2 1 One Breaker Synchronizer 3-phase, Power Supply 24V DC, Measuring Input 100-400V AC Woodward 8440-1021 10 10
-100F1;-106F5 2 Miniature Circuit Breaker (MCB) 1-pole 10A, Tripping Characteristic B, 10kA Siemens 5SY4 110-6 1,3 2,6
-104F1 1 Miniature Circuit Breaker (MCB) 2-pole 10A, Tripping Characteristic C, 10kA Siemens 5SY4 210-7 2 2
-106F1 1 Miniature Circuit Breaker (MCB) 1-pole 6A, Tripping Characteristic B, 10kA Siemens 5SY4 106-6 2 2
-106F2...-106F4;-106F6;-108F1...-108F4; 9 Miniature Circuit Breaker (MCB) 1-pole 2A, Tripping Characteristic A, 10kA Siemens 5SY4 102-5 2 18
-304F1 1 Miniature Circuit Breaker (MCB) 2-pole 2A, Tripping Characteristic A, 10kA Siemens 5SY4 202-5 4 4
SIPROTEC 4 Multifunction Protection Relay for Motor, Alternator and Transformer (Function Alternator Basic), 1A,
-500F1 1 Siemens 7UM6211-2EB91-0BC0-L0A 12 12
Supply Voltage 24 to 48V DC
-104G1 1 SITOP Modular 20 Power Supply, Input: 120/230V AC, Output: 24V DC/20A Siemens 6EP1336-3BA00 59 59
-104G2 1 SITOP buffer module for 6EP1X3X-3BAX0 buffering time 100ms till 10s dependent upon load Siemens 6EP1961-3BA01 0 0
-242H4 1 LED Switch Position indicator square, 25x25mm, green/red, 24V DC Weigel SUS-01-Q-G/R-24DC 0,5 0,5
-242H5;-242H6 2 LED Switch Position indicator round, ø25mm, green/red, 24V DC Weigel SUS-01-G/R-24DC 0,5 1
-160K1;-246K2...-246K8;-320K2 9 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 2 Changeover Contacts Phoenix Contact 2834562 0,46 4,14
-244K1...-244K5;-244K8;-320K1 7 Pre-assembled coupling relay, Spring Cage Connection, LED, free-wheeling diode, 24V DC, 4 Changeover Contacts Phoenix Contact 2834766 1 7
-244K6;-244K7;-246K1;-318K1 4 Contactor Relay, 2NC/2NO, 24V DC, Screw Connection, integrated Varistor Moeller 276414 3 12
-160M1 1 Fan and Filter Unit 230m³/h 230V, 50/60Hz, RAL 7035 Rittal SK 3241.100 40 40
-304P1 1 Voltmeter, measuring range 0...110V, Scale 0...17,94kV/0...143V, 15...100Hz WEIGEL 674.130.00 4,5 4,5
-306P1 1 Analog Ammeter 0-700A, 15-100Hz, for Current Transformer 700/1A, 90° Scale WEIGEL 684.130.1000 0,4 0,4
Multifunctional Monitoring Unit, L-N: 0-300V AC, L-L: 0-520V AC, 45-65Hz, Profibus Interface ext. Power Supply
-312P1 1 Janitza Electronics 52.22.037 4,6 4,6
20-250V AC / 20-300V DC
-314P2 1 Double Frequency Meter 2x55-65Hz, 2x21 reeds, 2x110V WEIGEL 031.130.0164.00 4,1 4,1
-314P3 1 Read Synchroscope Type RSQ-3, Frequency Range 40-70Hz (supply), 100-127V AC, Land DEIF RSQ-3-115V 1 1
LEISTUNGSSCHALTER BGR. S00, FUER DEN MOTORSCHUTZ, CLASS 10 A-AUSL. 1,4...2A, N-AUSL. 26A,
-304Q1;-310Q1 2 SIEMENS 3RV20111BA10 6,3 12,6
SCHRAUBANSCHLUSS
-304Q1;-310Q1 2 TRANSVERSE AUX. SWITCH, 1NO+1NC, SCREW CONNECTION, FOR CIRCUIT-BREAKERS, SZ S00/S0 SIEMENS 3RV2901-1E 0 0
Frequency 50Hz
Enclosure Element
Panel TS 8806.500
Type of Installation Site First or Last Enclosure in a Suite for Wall Mounting
1 x Addition 335W
2. Heat Exchangers No No No
3. Cooling Units No No No
5. Heaters No No No
The following list indicates the expected current to each installed CB, MCB and fuse,
in order to show that the selected devices are suitable for the connected load.
Another criterion, when selecting the breaking capacity of the devices,
is the cross section of the suggested external cable.
A calculation indicating the results for the suggested individual cables and data sheets for the selected MCBs are attached.
-100F1 B 10 AC 230 0,55 - 10A MCB selected because of the Service Socket in -160E1
-106F1 B 6 DC 24 4,2 -
-106F2 A 2 DC 24 0,961 -
-106F3 A 2 DC 24 0 - Spare
-106F4 A 2 DC 24 0,243 -
-106F6 A 2 DC 24 0,474 -
-108F1 A 2 DC 24 0,035 -
-108F2 A 2 DC 24 0,106 -
-108F3 A 2 DC 24 0,014 -
-108F4 A 2 DC 24 0,007 -
-110F1 A 2 DC 24 0,661 -
-304Q1 - 1,4-2 3AC 110 N/A 1,6 Depending on burdon of Voltage Transformer
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire > 0,1s Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 2 x IN x 1,4 Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm² 26,0Ω 26,0Ω x 2 / 1000m = 0,052Ω/m 2 x 2A x 1,4 = 5,6A 24V / 5,6A = 4,29Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,29Ω / 1,195 / 0,052Ω/m = 68,97m
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 2 x 2A x 1,4 = 5,6A 24V / 5,6A = 4,29Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,29Ω / 1,195 / 0,039Ω/m = 91,96m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 2 x 2A x 1,4 = 5,6A 24V / 5,6A = 4,29Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,29Ω / 1,195 / 0,0266Ω/m = 134,83m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 2 x 2A x 1,4 = 5,6A 24V / 5,6A = 4,29Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,29Ω / 1,195 / 0,01596Ω/m = 224,71m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 2 x 2A x 1,4 = 5,6A 24V / 5,6A = 4,29Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,29Ω / 1,195 / 0,0099Ω/m = 362,26m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 2 x 2A x 1,4 = 5,6A 24V / 5,6A = 4,29Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,29Ω / 1,195 / 0,0066Ω/m = 543,39m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire < 1h Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 1,45 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm² 26,0Ω 26,0Ω x 2 / 1000m = 0,052Ω/m 1,45 x 2A = 2,9A 24V / 2,9A = 8,275Ω 0,0039 x 1/K x 50K + 1 = 1,195 8,275Ω / 1,195 / 0,052Ω/m = 133,16m
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 1,45 x 2A = 2,9A 24V / 2,9A = 8,275Ω 0,0039 x 1/K x 50K + 1 = 1,195 8,275Ω / 1,195 / 0,039Ω/m = 177,55m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 1,45 x 2A = 2,9A 24V / 2,9A = 8,275Ω 0,0039 x 1/K x 50K + 1 = 1,195 8,275Ω / 1,195 / 0,0266Ω/m = 260,32m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 1,45 x 2A = 2,9A 24V / 2,9A = 8,275Ω 0,0039 x 1/K x 50K + 1 = 1,195 8,275Ω / 1,195 / 0,01596Ω/m = 433,87m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 1,45 x 2A = 2,9A 24V / 2,9A = 8,275Ω 0,0039 x 1/K x 50K + 1 = 1,195 8,275Ω / 1,195 / 0,0099Ω/m = 699,46m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 1,45 x 2A = 2,9A 24V / 2,9A = 8,275Ω 0,0039 x 1/K x 50K + 1 = 1,195 8,275Ω / 1,195 / 0,0066Ω/m = 1049,19m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire > 0,1s Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 3 x IN x 1,4 Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm² 26,0Ω 26,0Ω x 2 / 1000m = 0,052Ω/m 3 x 6A x 1,4 = 25,2A 24V / 25,2A = 0,95Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,95Ω / 1,195 / 0,052Ω/m = 15,33m
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 3 x 6A x 1,4 = 25,2A 24V / 25,2A = 0,95Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,95Ω / 1,195 / 0,039Ω/m = 20,44m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 3 x 6A x 1,4 = 25,2A 24V / 25,2A = 0,95Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,95Ω / 1,195 / 0,0266Ω/m = 29,96m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 3 x 6A x 1,4 = 25,2A 24V / 25,2A = 0,95Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,95Ω / 1,195 / 0,01596Ω/m = 49,94m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 3 x 6A x 1,4 = 25,2A 24V / 25,2A = 0,95Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,95Ω / 1,195 / 0,0099Ω/m = 80,50m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 3 x 6A x 1,4 = 25,2A 24V / 25,2A = 0,95Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,95Ω / 1,195 / 0,0066Ω/m = 120,75m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire < 1h Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 1,45 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm² 26,0Ω 26,0Ω x 2 / 1000m = 0,052Ω/m 1,45 x 6A = 8,7A 24V / 8,7A = 2,75Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,75Ω / 1,195 / 0,052Ω/m = 44,25m
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 1,45 x 6A = 8,7A 24V / 8,7A = 2,75Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,75Ω / 1,195 / 0,039Ω/m = 59,00m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 1,45 x 6A = 8,7A 24V / 8,7A = 2,75Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,75Ω / 1,195 / 0,0266Ω/m = 86,51m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 1,45 x 6A = 8,7A 24V / 8,7A = 2,75Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,75Ω / 1,195 / 0,01596Ω/m = 144,18m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 1,45 x 6A = 8,7A 24V / 8,7A = 2,75Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,75Ω / 1,195 / 0,0099Ω/m = 232,45m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 1,45 x 6A = 8,7A 24V / 8,7A = 2,75Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,75Ω / 1,195 / 0,0066Ω/m = 348,67m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire > 0,1s Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 3 x IN x 1,4 Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm²
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 3 x 10A x 1,4 = 42A 24V / 42A = 0,57Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,57Ω / 1,195 / 0,039Ω/m = 12,26m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 3 x 10A x 1,4 = 42A 24V / 42A = 0,57Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,57Ω / 1,195 / 0,0266Ω/m = 17,98m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 3 x 10A x 1,4 = 42A 24V / 42A = 0,57Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,57Ω / 1,195 / 0,01596Ω/m = 29,96m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 3 x 10A x 1,4 = 42A 24V / 42A = 0,57Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,57Ω / 1,195 / 0,0099Ω/m = 48,30m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 3 x 10A x 1,4 = 42A 24V / 42A = 0,57Ω 0,0039 x 1/K x 50K + 1 = 1,195 0,57Ω / 1,195 / 0,0066Ω/m = 72,45m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire < 1h Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 1,45 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm²
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 1,45 x 10A = 14,5A 24V / 14,5A = 1,65Ω 0,0039 x 1/K x 50K + 1 = 1,195 1,65Ω / 1,195 / 0,039Ω/m = 35,40m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 1,45 x 10A = 14,5A 24V / 14,5A = 1,65Ω 0,0039 x 1/K x 50K + 1 = 1,195 1,65Ω / 1,195 / 0,0266Ω/m = 51,90m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 1,45 x 10A = 14,5A 24V / 14,5A = 1,65Ω 0,0039 x 1/K x 50K + 1 = 1,195 1,65Ω / 1,195 / 0,01596Ω/m = 86,51m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 1,45 x 10A = 14,5A 24V / 14,5A = 1,65Ω 0,0039 x 1/K x 50K + 1 = 1,195 1,65Ω / 1,195 / 0,0099Ω/m = 139,47m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 1,45 x 10A = 14,5A 24V / 14,5A = 1,65Ω 0,0039 x 1/K x 50K + 1 = 1,195 1,65Ω / 1,195 / 0,0066Ω/m = 209,20m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire > 0,1s Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 2 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm² 26,0Ω 26,0Ω x 2 / 1000m = 0,052Ω/m 2 x 2A = 4A 110V / 4A = 27,5Ω 0,0039 x 1/K x 50K + 1 = 1,195 27,5Ω / 1,195 / 0,052Ω/m = 442,55m
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 2 x 2A = 4A 110V / 4A = 27,5Ω 0,0039 x 1/K x 50K + 1 = 1,195 27,5Ω / 1,195 / 0,039Ω/m = 590,07m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 2 x 2A = 4A 110V / 4A = 27,5Ω 0,0039 x 1/K x 50K + 1 = 1,195 27,5Ω / 1,195 / 0,0266Ω/m = 865,13m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 2 x 2A = 4A 110V / 4A = 27,5Ω 0,0039 x 1/K x 50K + 1 = 1,195 27,5Ω / 1,195 / 0,01596Ω/m = 1441,89m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 2 x 2A = 4A 110V / 4A = 27,5Ω 0,0039 x 1/K x 50K + 1 = 1,195 27,5Ω / 1,195 / 0,0099Ω/m = 2324,50m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 2 x 2A = 4A 110V / 4A = 27,5Ω 0,0039 x 1/K x 50K + 1 = 1,195 27,5Ω / 1,195 / 0,0066Ω/m = 3486,75m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire < 1h Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 1,45 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm² 26,0Ω 26,0Ω x 2 / 1000m = 0,052Ω/m 1,45 x 2A = 2,9A 110V / 2,9A = 37,93Ω 0,0039 x 1/K x 50K + 1 = 1,195 37,93Ω / 1,195 / 0,052Ω/m = 610,41m
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 1,45 x 2A = 2,9A 110V / 2,9A = 37,93Ω 0,0039 x 1/K x 50K + 1 = 1,195 37,93Ω / 1,195 / 0,039Ω/m = 813,88m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 1,45 x 2A = 2,9A 110V / 2,9A = 37,93Ω 0,0039 x 1/K x 50K + 1 = 1,195 37,93Ω / 1,195 / 0,0266Ω/m = 1193,29m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 1,45 x 2A = 2,9A 110V / 2,9A = 37,93Ω 0,0039 x 1/K x 50K + 1 = 1,195 37,93Ω / 1,195 / 0,01596Ω/m = 1988,81m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 1,45 x 2A = 2,9A 110V / 2,9A = 37,93Ω 0,0039 x 1/K x 50K + 1 = 1,195 37,93Ω / 1,195 / 0,0099Ω/m = 3206,21m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 1,45 x 2A = 2,9A 110V / 2,9A = 37,93Ω 0,0039 x 1/K x 50K + 1 = 1,195 37,93Ω / 1,195 / 0,0066Ω/m = 4809,31m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire > 0,1s Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 3 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm²
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 3 x 10A = 30A 230V / 30A = 7,66Ω 0,0039 x 1/K x 50K + 1 = 1,195 7,66Ω / 1,195 / 0,039Ω/m = 164,36m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 3 x 10A = 30A 230V / 30A = 7,66Ω 0,0039 x 1/K x 50K + 1 = 1,195 7,66Ω / 1,195 / 0,0266Ω/m = 240,97m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 3 x 10A = 30A 230V / 30A = 7,66Ω 0,0039 x 1/K x 50K + 1 = 1,195 7,66Ω / 1,195 / 0,01596Ω/m = 401,63m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 3 x 10A = 30A 230V / 30A = 7,66Ω 0,0039 x 1/K x 50K + 1 = 1,195 7,66Ω / 1,195 / 0,0099Ω/m = 647,47m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 3 x 10A = 30A 230V / 30A = 7,66Ω 0,0039 x 1/K x 50K + 1 = 1,195 7,66Ω / 1,195 / 0,0066Ω/m = 971,21m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire < 1h Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 1,45 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm²
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,039Ω/m = 340,30m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,0266Ω/m = 498,94m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,01596Ω/m = 831,57m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,0099Ω/m = 1340,60m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,0066Ω/m = 2010,90m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire > 0,1s Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 5 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm²
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 5 x 10A = 50A 230V / 50A = 4,60Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,60Ω / 1,195 / 0,039Ω/m = 98,70m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 5 x 10A = 50A 230V / 50A = 4,60Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,60Ω / 1,195 / 0,0266Ω/m = 144,71m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 5 x 10A = 50A 230V / 50A = 4,60Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,60Ω / 1,195 / 0,01596Ω/m = 241,19m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 5 x 10A = 50A 230V / 50A = 4,60Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,60Ω / 1,195 / 0,0099Ω/m = 388,83m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 5 x 10A = 50A 230V / 50A = 4,60Ω 0,0039 x 1/K x 50K + 1 = 1,195 4,60Ω / 1,195 / 0,0066Ω/m = 583,24m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire < 1h Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 1,45 x IN Rmax = U / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
0,75mm²
1,00mm² 19,5Ω 19,5Ω x 2 / 1000m = 0,039Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,039Ω/m = 340,30m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,0266Ω/m = 498,94m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,01596Ω/m = 831,57m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,0099Ω/m = 1340,60m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 1,45 x 10A = 14,5A 230V / 14,5A = 15,86Ω 0,0039 x 1/K x 50K + 1 = 1,195 15,86Ω / 1,195 / 0,0066Ω/m = 2010,90m
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire > 0,05s Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 14 x IN Rmax = U / √3 / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 14 x 2A = 28A 63,5V / 28A = 2,27Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,27Ω / 1,195 / 0,0266Ω/m = 71m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 14 x 2A = 28A 63,5V / 28A = 2,27Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,27Ω / 1,195 / 0,01596Ω/m = 119m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 14 x 2A = 28A 63,5V / 28A = 2,27Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,27Ω / 1,195 / 0,0099Ω/m = 191m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 14 x 2A = 28A 63,5V / 28A = 2,27Ω 0,0039 x 1/K x 50K + 1 = 1,195 2,27Ω / 1,195 / 0,0066Ω/m = 287m
10,00mm²
16,00mm²
Conductor Resistance Resistance / m Breaking Current Max. Perm. Resistance Max. Perm.
Cross At 20°C For 1000m Double Wire < 1h Cable Impendance Temperature Factor Cable Length
Section Class 5/6 Wire For Cu At 70°C Double Wire
(LAPPKABEL T11) R/m = R20°C x 2 / 1000m I = 1,45 x IN Rmax = U / √3 / I αCu x ΔT + 1 L = Rmax / 1,195 / R/m
1,50mm² 13,3Ω 13,3Ω x 2 / 1000m = 0,0266Ω/m 1,45 x 2A = 2,9A 63,5V / 2,9A = 21,89Ω 0,0039 x 1/K x 50K + 1 = 1,195 21,89Ω / 1,195 / 0,0266Ω/m = 688m
2,50mm² 7,98Ω 7,98Ω x 2 / 1000m = 0,01596Ω/m 1,45 x 2A = 2,9A 63,5V / 2,9A = 21,89Ω 0,0039 x 1/K x 50K + 1 = 1,195 21,89Ω / 1,195 / 0,01596Ω/m = 1147m
4,00mm² 4,95Ω 4,95Ω x 2 / 1000m = 0,0099Ω/m 1,45 x 2A = 2,9A 63,5V / 2,9A = 21,89Ω 0,0039 x 1/K x 50K + 1 = 1,195 21,89Ω / 1,195 / 0,0099Ω/m = 1850m
6,00mm² 3,30Ω 3,30Ω x 2 / 1000m = 0,0066Ω/m 1,45 x 2A = 2,9A 63,5V / 2,9A = 21,89Ω 0,0039 x 1/K x 50K + 1 = 1,195 21,89Ω / 1,195 / 0,0066Ω/m = 2775m
10,00mm²
16,00mm²
Magnetic Thermic Magnetic Thermic Magnetic Thermic Magnetic Thermic Magnetic Thermic Magnetic Thermic
-100F1 B 10 AC 230 164 340 240 498 401 831 647 1340 971 2010
-104F1 C 10 AC 230 98 340 144 498 241 831 388 1340 583 2010
-106F2 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-106F3 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-106F4 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-106F6 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-108F1 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-108F2 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-108F3 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-108F4 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-108F5 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-110F1 A 2 DC 24 68 133 91 177 134 260 224 433 362 699 543 1049
-304F1 A 2 AC 110 442 610 590 813 865 1193 1441 1988 2324 3206 3486 4809
-304Q1 - 1,4-2 3AC 110 71 688 119 1147 191 1850 287 2775
-310Q1 - 1,4-2 3AC 110 71 688 119 1147 191 1850 287 2775
The following list indicates the settings of the synchronization devices, in accordance with the system data (110V/60Hz).
In compliance with the specification the dead bus closing is activated.
For dead bands, phase angles and delta values the default values have been set.
These have to be adjusted in accordance with the utility conditions during commissioning.
Configuration measurement
Controlling configuration
Frequency Controller
Voltage controller
Synchronization configuration
39 Relay function connect 2 (16/17) OFF / asyn. only / syn. only / syn./asyn. OFF syn./asyn.
Positive 5 to 25° el 7° el
The following list indicates the settings of the multifunctional monitoring unit (MMU),
in accordance with the system data. Further settings are not required.
50 Password 0 to 999 0 -
106 Minimum pulse length, digital output 1/2 1 to 1000 5=50ms 5=50ms minimum pulse length = set value x 10ms
511 Relative voltage for THD and FFT 0/1 0 0 0=L-N, 1=L-L
600 Metering range exceedance 0 to 0xFFFFFFFF read only read only Overrange Limits: I=7Aeff, U (L-N)=520V
-106F3 Spare A 2A
Type Label
Type Label
Mains
Rated Voltage: 110V
Rated Current: 1A
Rated Frequency: 60Hz
Alternator
200
140
List of Labels
Label Size
Legend Label Type/
Device Tag Device Multilayer Label Text
Position Lettering
Formica/Glued
Remark: Device Labels shall be glued 3mm above the related device if possible, details are shown in the Panel Front View
Previous Page: 1010 Next Page: 1012
Rev.C 24.10.2014 rhoerner Edition Date 16.12.2014
Genset Control Panel GCP MAN Diesel & Turbo SE List of Labels Drawing Number: T-06802_GCP + 01CDA01
Rev.B 24.10.2014 rhoerner Editor E. Simon
Rev.B 24.10.2014 rhoerner Checked R. Hörner
PowerES Stadtbachstr. 1 Page 1011
Revision Date Name Edition Status Commissioning 86153 Augsburg/Germany 5302272 United Cement Industrial Company Pages 175
0 1 2 3 4 5 6 7 8 9
List of Labels
Label Size
Legend Label Type/
Device Tag Device Multilayer Label Text
Position Lettering
Formica/Glued
MANUAL SETTING
White with black
22mm Plastic round actuator: Selector Switch 3 Positions I-O-II, 2x50°, momentary SPEED, FREQUENCY,
15 -226S2 lettering 74x26mm
contact, black ACTIVE POWER
Arial 3mm
LOWER / 0 / HIGHER
Remark: Device Labels shall be glued 3mm above the related device if possible, details are shown in the Panel Front View
Previous Page: 1011 Next Page: 1013
Rev.C 24.10.2014 rhoerner Edition Date 16.12.2014
Genset Control Panel GCP MAN Diesel & Turbo SE List of Labels Drawing Number: T-06802_GCP + 01CDA01
Rev.B 24.10.2014 rhoerner Editor E. Simon
Rev.B 24.10.2014 rhoerner Checked R. Hörner
PowerES Stadtbachstr. 1 Page 1012
Revision Date Name Edition Status Commissioning 86153 Augsburg/Germany 5302272 United Cement Industrial Company Pages 175
0 1 2 3 4 5 6 7 8 9
List of Labels
Label Size
Legend Label Type/
Device Tag Device Multilayer Label Text
Position Lettering
Formica/Glued
Remark: Device Labels shall be glued 3mm above the related device if possible, details are shown in the Panel Front View
Previous Page: 1012 Next Page: 1014
Rev.C 24.10.2014 rhoerner Edition Date 16.12.2014
Genset Control Panel GCP MAN Diesel & Turbo SE List of Labels Drawing Number: T-06802_GCP + 01CDA01
Rev.B 24.10.2014 rhoerner Editor E. Simon
Rev.B 24.10.2014 rhoerner Checked R. Hörner
PowerES Stadtbachstr. 1 Page 1013
Revision Date Name Edition Status Commissioning 86153 Augsburg/Germany 5302272 United Cement Industrial Company Pages 175
0 1 2 3 4 5 6 7 8 9
Alternator
24 Overexcit.
27 Undervoltage
40 Field Failure
50 Inst. Overcur.
50BF Breaker F.
51 Overcurrent
59 Overvoltage
81 Overfreq.
81 Underfreq.
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
10
11
Cable Name: =+01CDA01-W1001 Cable Type: ÖLFLEX 140 G Cable Length [m]: 25
Function Text: Digital Signals MV Busbar +00BBA01 No. of Conductors: 25G Cross Section [mm²]: 1.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
20
Cable Name: =+01CDA01-W1004 Cable Type: ÖLFLEX 191 G Cable Length [m]: 25
Function Text: Earth Fault Current Alternator Star Point No. of Conductors: 3x Cross Section [mm²]: 4
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Cable Name: =+01CDA01-W1006 Cable Type: ÖLFLEX 191 G Cable Length [m]: 69
Function Text: Alternator Current for Protection No. of Conductors: 7x Cross Section [mm²]: 4
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Cable Name: =+01CDA01-W1007 Cable Type: ÖLFLEX 191 G Cable Length [m]: 69
Function Text: Earth Fault Current Alternator Outlet No. of Conductors: 3x Cross Section [mm²]: 4
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
/302.5 PE 1 -X400 3
Cable Name: =+01CDA01-W1008 Cable Type: ÖLFLEX CLASSIC 110 G Cable Length [m]: 25
Function Text: Alternator Open Delta Voltage No. of Conductors: 3x Cross Section [mm²]: 2.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Cable Name: =+01CDA01-W1009 Cable Type: ÖLFLEX CLASSIC 110 G Cable Length [m]: 25
Function Text: Alternator Measuring Voltage No. of Conductors: 5x Cross Section [mm²]: 2.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Cable Name: =+01CDA01-W1012 Cable Type: ÖLFLEX CLASSIC 110 G Cable Length [m]: 25
Function Text: Alternator Current for Protection ANSI 87G No. of Conductors: 7x Cross Section [mm²]: 4
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Cable Name: =+01CDA01-W1013 Cable Type: ÖLFLEX CLASSIC 110 G Cable Length [m]: 9
Function Text: MV Busbar Measuring Voltage No. of Conductors: 4x Cross Section [mm²]: 2.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Cable Name: =+01CDA01-W1015 Cable Type: ÖLFLEX 140 G Cable Length [m]: 25
Function Text: Altern. CB Open/Trip Loop to MV Busbar 1 No. of Conductors: 5G Cross Section [mm²]: 1.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Cable Name: =+01CDA01-W1016 Cable Type: ÖLFLEX 140 G Cable Length [m]: 25
Function Text: Signals to MV Busbar +00BBA01 No. of Conductors: 12G Cross Section [mm²]: 1.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Cable Name: =+01CDA01-W1019 Cable Type: ÖLFLEX 140 G Cable Length [m]: 54
Function Text: Safety Chain Engine Shutdown Signal to GIP No. of Conductors: 3G Cross Section [mm²]: 1.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Cable Name: =+01CDA01-W1020 Cable Type: ÖLFLEX 140 G Cable Length [m]: 54
Function Text: Emergency Stop Loop for Engine Auxiliary Drives No. of Conductors: 5G Cross Section [mm²]: 1.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Cable Name: =+01CDA01-W1021 Cable Type: ÖLFLEX 140 G Cable Length [m]: 25
Function Text: Altern. CB is Closed Connection to MV Busbar No. of Conductors: 4G Cross Section [mm²]: 1.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
17
Cable Name: =+01CDA01-W1023 Cable Type: ÖLFLEX 140 G Cable Length [m]: 9
Function Text: Breaker Failure External Trip to CCP No. of Conductors: 3G Cross Section [mm²]: 1.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Cable Name: =+01CDA01-W1025 Cable Type: ÖLFLEX 140 CY G Cable Length [m]: 9
Function Text: 01CDA01CT001-XQ01 GCP Internal Panel Temperature No. of Conductors: 5G Cross Section [mm²]: 1.5
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
GNYE
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Cable Name: =+01CDA01-W2002 Cable Type: UNITRONIC BUS Cable Length [m]: 4
Function Text: Profibus Connection to GCP 2 No. of Conductors: 2x Cross Section [mm²]: 0.64
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked
SH
Page / Path Target Designation From Connection Point Conductor Target Designation To Connection Point Connected / Checked