01-MCC400 Single Line Diagram For TWPS MCC of TLM Plant

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

1 2 3 4 5 6 7 8

A A
THE REPUBLIC OF INDONESIA

MEDAN CITY
B B

TLM EXTENSION PROJECT

C Single Line Diagram for TWPS MCC of TLM Plant C


01-MCC400

6
5
D 4 D
3
2
1
0 2018/8/21 FIRST ISSUE
DESIGNER CHKD APP. BY
REV. ISSUE DATE COMMENTARY
(mm/dd/yy)

DRAWING:
GOOD FOR EXECUTION STUDIES

DOCUMENT STATUS
E E
Single Line Diagram GOOD FOR INQUIRY

CLIENT: FOR APPROVAL

ALL RIGHTS RESERVED FOR ALL COUNTRIES


FOR INFORMATION AND COMMENT
31st Floor,Taikang Finance Building,
Building1,Yard 38 ,DongSanHuan North Road INTERNAL ISSUE VERSION
F Chaoyang District, Beijing 100020 F

Project Number Drawing Number


A3 B-001423 01-DGT-EL-934-DI-004

1 2 3 6 7 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CATALOG F06_003_2-EN
Table name

A Sheet Drawing name Equipment name Equipment NO. REV. REMARK A

/1 COVER A
/2 CATALOG A
/3 ELECTRICAL DATA A
/4 CUBICLE DATA A
/5 DESIGN LABEL A
/6 DESIGN LABEL A
B /7 CIVIL GUIDE A B
/8 SYMBOL TABLE A
/9 SYMBOL INSTRUCTION A
/12 FRONT VIEW A
/13 ARRANGEMENT A
/15 SINGLE LINE DIAGRAM A
/16 SINGLE LINE DIAGRAM A

C C
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

D D
BOER and may neither be used nor disclosed without its prior

E E

F F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
CATALOG Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 2 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

GENERAL DATA
A
ELECTRICAL DATA
A
LOCATION OUTDOOR INDOOR
1 - NETWORK
SITUATION ROOM VENTILATED NOT VENTILATED ROOM
RATED SERVICE VOLTAGE = 380 V
AIR CONDITIONNED PRESSURISED
RATED POWER = KVA
ALTITUDE =< 2000 M > 2000 M
RATED CURRENT = 1600 A
B AVERAGE AMBIENT AIR TEMPERATURE FOR 24H MAX : 40 °C MIN : 0 °C B
RATED FREQUENCY = 50 HZ
MAXIMUM RELATIVE HUMIDITY 80 % AT °C SIMULTANEOUS NO
NUMBER OF SOURCE = 1
HEATING COLUMNS : WITHOUT WITH YES
RATED SHORT-CIRCUIT CURRENT = KA RMS

RATED PEAK WITHSTAND CURRENT = KA


CLIMATIC CONDITIONS T1 TEMPERATE CLIMATE
C EARTHING SYSTEM N OR PEN TT IT TN-S TNC C
T2 ALL CLIMATES
ACCORDING TO IEC 364
WITHOUT
T3 CORROSIVE ATMOSPHERE
= PHASE

TECHNICAL DATA < PHASE


All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

INCOMING POWER 2 - SWITCHBOARD


CONTROL
D D
INCOMER FEEDERS
SHORT CIRCUIT CURRENT = 50 KA RMS
TOP
RATED PEAK WITHSTAND CURRENT = 110 KA
BOER and may neither be used nor disclosed without its prior

BOTTOM
LESS C.B. ULTIMATE BREAKING CAPACITY

VOLTAGE TYPE FREQUENCY SOURCE NG125L 50KA


AUXILIARY CIRCUITS
(V) AC DC (HZ) IN OUT NSX**N 50KA
E
MT**H1 65KA
INCOMING CONTROL 220 MT**N2 50KA E

OTHER DATA
FEEDERS CONTROL 220
WIRING COLOR FOR AUXILIARY CIRCUIT
RELAYS 220 AC220V(L,N):L BLACK N BLUE
AC220V:A01,A03 BLACK A02,A04 BLACK
SIGNAL 220 DC24V:+ RED - DARKBLUE
DI: RED
MEASUREMENT 380 50 DO: GYAY

F F
COMMUNICATE 24

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
ELECTRICAL DATA Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 3 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CUBICLE DATA CONSTRUCTION DATA


A A
CUBICLE SYSTEM : BLOKSET NSM MB-400 POWER CABLES CONNECTION : TERMINAL BLOCKS FLAT BARS
DIRECT ON APPARATUS TERMINAL
STANDARDS : IEC 439-2
BUSBAR IDENTIFICATION :
PHASE 1 : RED PHASE 2 : YELLOW PHASE 3 : BLACK
PROTECTION DEGREE : IP 31 54 55 NEUTRAL : BLUE EARTH : PE YELLOW-GREEN
CONTROL WIRING WIRES: FLEX 500V BLACK WITH CABLE END
CONNECTION COMPARTMENT ACCESS : FRONT REAR
CONTROL CIRCUIT : 1.5 MM2 SIGNALLING CIRCUIT : 1.5 MM2
B B
VOLTAGE CIRCUIT : 1.5 MM2 CURRENT CIRCUIT : 2.5 MM2
ENCLOSURE FORM TYPE : - INCOMERS : 2 3b 4
PLC : 0.75 MM2
- OUTGOERS : 2 3b 4 CONTROL TERMINAL BLOCK MINIMUM WIDTH 6 MM

INTERNAL WIRING : CLIP SCREW


EXTERNAL WIRING : CLIP SCREW
ACCESS CLOSING : FRONT REAR FRONT DOOR
DOOR DOOR PANEL INDIVIDUAL WIRING IDENTIFICATION : WITHOUT
C
WITHOUT KEY COMMON WITH TYPE : DIRECTIONNAL C

- FULL TYPE :
WITH KEY
OTHER - TRANSPARENT LABEL : FRONT ENGRAVING : BLACK ON WHITE BACKGROUND

REAR ENGRAVING : BLACK ON WHITE BACKGROUND


PAINTING TYPE FINISH Semi-varnish.
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

ENCLOSURE EPOXY POLYESTER POWDER Non SMOOTH RAL7035

INSIDE EPOXY POLYESTER POWDER Non SMOOTH RAL7035


D
LABEL FIXATION : STICK D

INTERNAL EQUIPMENT IDENTIFICATION : STICK


COPPER BUSBAR : - HORIZONTAL : WITHOUT WITH
BOER and may neither be used nor disclosed without its prior

EQUIPMENT
TYPE OF EQUIPMENT FIXED WITHDRAWABLE
- VERTICAL : WITHOUT WITH MOUNTING
PLUG IN TRUCK
- PLATE: WITHOUT WITH TINNED INCOMING
FUTURE EXTENSION :
BUSTIE
E
LEFT SIDE WITHOUT WITH OUTGOING : .MULTI 9 E

.COMPACT =<630A
RIGHT SIDE WITHOUT WITH
.COMPACT >630A
.MASTERPACT
FREE STANDING ON FLOOR
.CONTACTOR

STICK FRONT FACE MIMIC DIAGRAM: WITHOUT WITH


OTHER DATA
F BOTTOM BASE PLATE: WITHOUT WITH F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
CUBICLE DATA Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 4 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1.Label
A A

Label description Label physical location Standard material Information written as a STANDARD Examples Additional info.that can
be included(ON REQUEST) Label size(mm)(X*Y)

Switchgear nameplate First cell in switchboard PVC Standard BOER template 100*60
..... N/A
parameters
Cabinet No. First cell in switchboard PVC According to single
line diagram MCC200-1 N/A 120*50
B B

Loop number & name On each circuit board PVC According to single AG02101A
Pre-Coagulant
CB rating 80*30
line diagram Flash Mixer KW(1) 50*20
Labels for Telemechanique
on front face of doors Device description
devices PVC according to drawings ON,OFF,TRIP N/A 27,5*13.5
...
According to single 2P 54*15
Internal label 1 on each feed circuit breaker Plastic
line diagram N/A
3P 81*15
C C

On control devices Device/contact name on


Yellow sticking paper Schematic diagram
Internal label 2 K1,HR,... N/A 27,5*13.5
On back face of doors

(1) These details are standard in Motor starters (MF,MW,ATV,ATS)-Written in Rated power(KW) in SLD
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

D D

2.Plastic label details

2.1 Colors
BOER and may neither be used nor disclosed without its prior

Background color Text color


Standard White Black

2.2 fixation
E E

Cabinet No
Loop number & name Screw

Internal label 1
Paste

F F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
DESIGN LABEL Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 5 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

LABEL SPECIFICATION Company LOGO


A A

MATERIAL : Plastic
COLOUR : BLACK ON WHITE

C:\Documents and Settings\Administrator\桌面\SUEZ logo_HD.jpg

91.5 mm
B Notes: B

CUBICLE LABEL 120*50mm See " Front view,General arrangement


cubicle label of Each Panel "

50
MCC200-1 210.5 mm

C C

120

CIRCUIT LOOP LABEL 80*30mm See " SINGLE LINE DIAGRAM of item equiment and
circuit description "
4kW
30
AG02101A
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

Pre-Coagulant Flash Mixer

D D
80

CIRCUIT LOOP LABEL 50*20mm


BOER and may neither be used nor disclosed without its prior

See " SINGLE LINE DIAGRAM of item equiment and


circuit description "
4kW
AG02101A
20 Pre-Coagulant Flash Mixer

50
E E

F F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
DESIGN LABEL Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 6 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A This map is 700 wide and 600 This map is 900 wide and 600
deep in the cabinet deep in the cabinet A

On the Floor and off wall installation, On the Floor and off wall installation,
cabinets after the connection cabinets after the connection

122.5 mm 455 mm 122.5 mm 655 mm

B B

600 mm
600 mm

2
2

12.
12.
30 mm 30 mm

8*∅
8*∅

25 mm
25 mm
700 mm 900 mm

C C
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

D D
600 mm

01-MCC400-1 01-MCC400-2
30 mm
BOER and may neither be used nor disclosed without its prior

700 mm 900 mm

E E

FRONT

F F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
CIVIL GUIDE Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 7 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

BASIC SYMBOLS MEASURING&SIGNALLING COMPONENTS CONTROL COMPONENTS CONTACTORS CONTROLS


A A

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION

Conductor A Ammeter Control/Potential Transformer Load Switch

Junction of Conductors V Voltmeter Current Transformer Isalator

Crossing of Conductors(connected) Wh kWh meter DC Power Circuit Breaker


Pmax

Crossing of Conductors(not connected) Pilot Light Electromagnetic Control Contactor(N/O pole)


B B

Screened Conductors BUZZER XF Closing Release Contactor(N/C pole)

Terminal Bell MX Shunt Release Change-over Contact


M MN
3~ Motor Horn Undervoltage Release Normally Open Contact
M
3~ Cooling Fan Delayed on Energisation Normally Closed Contact

Device Fitted Outside the circuit Delayed on De-energisation Delayed on Energisation


C C
Earth Fuse Delayed on De-energisation

Outside device Heater Position Switch

Mechanical Connection Thermal Over-Current Type P P Press Switch

Description Thermal Overcurrent Relay Float Switch


All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

* Startin End Switch

Capacitor Bank Mechanism Switch


D D
Reactor Thermal Overcurrent Contact

Lightning Arrester Push Button(Spring return)


BOER and may neither be used nor disclosed without its prior

Surge Protecton Device Turning Switch(Latched)

Pack&Panel Connector Emergency Stop Button(Latched)

Mechanical Interlock Change-over Switch


E E
Socket JUMP

Current Transformer 3 Positions Transfer Switch

Control/Potential Transformer

Frequency converter

F F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
SYMBOL TABLE Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 8 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
该文件中所含所有技术信息均为独家产权, 任何人未经事先书面许可不得使用和泄露其内容.
只有当执行订货合同时方可提交使用.该图中所示所有元件均处于断开或抽出位置,即处于在

Notes:
A A

1.PAGE FIELD 3.COMPONENT CROSSREFERENCE

Densadeg Clarifier MCC200 Single Line DRAWING NO.


EL-934-DI-001 13 14/22.5

ARRANGEMENT Equipment Name Position in the page


B Page number B

PROJECT NO. B-000825 PAGE NO. 11

DRAWING NO.
操作机构和所有电源断点状态下.

EL-934-DI-001

Drawing number, see " Electrical Drawing List "

C C
Equipment Name AG02101A

Device number
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

2.SIGNAL CROSSREFERENCE 4.SYMBOL COMMAND

D ITEM DESCRIPTION ITEM DESCRIPTION


02/009.3 D

04/009.3 Q Circuit Breaker H Pilot Light


BOER and may neither be used nor disclosed without its prior

KM Contactor T Current Transformer


02/009.3

Position in the page F Thermal Overcurrent Relay PM Power Meter


Page number
ES Emergency Stop Button FU Fuse
Signal number
E E
S Button & Transfer switch KA Control Relay

XT Terminals

F F

DRAWING NO. 图号
TLM EXTENSION PROJECT Single Line Diagram for LVMDP of TLM Plant
01-DGT-EL-934-DI-001
CLIENT: Equipment Name
SYMBOL INSTRUCTION 设备名称
FIRST ISSUE 2018/8/21 A 博耳(无锡)电力成套有限公司
Modification 修改 Date 日期 Ver.版本 Modification 修改 Date 日期 Ver.版本 BOER (WUXI) POWER SYSTEM CO., LTD.
PROJECT NO.项目号 B-001423 PAGE NO.页号 9 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A A

01-MCC400-1 01-MCC400-2
Schneider Blokset Schneider Blokset
Electric Electric
BLOKSET
0

5
B B

DM2315 DM2315 DM2315


10

15

PM5350P
C C
2200

20

25
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

XBKH70000002M XBKH70000002M

D
30
D

35
BOER and may neither be used nor disclosed without its prior

40

E E

30 mm 700 mm 900 mm 30 mm

Depth:600mm
Only Front Access
F F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
FRONT VIEW Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 12 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A A

01-MCC400-1 01-MCC400-2
Schneider Blokset Schneider Blokset
Electric Electric
BLOKSET
0
(A) (A)

B
5 B
2000/5 DM2315 DM2315 DM2315
PM5350P

NS800N 3P F

NS800N 3P F

NS800N 3P F
CPM-R100T
RM22-TR33

MIC2.0

MIC2.0

MIC2.0
10 MT16N2 3P
D/O MIC5.0E
1000/5 1000/5 1000/5

Treated Water Pump Treated Water Pump Treated Water Pump


05-P01 05-P02 05-P03
15 INCOMING

C C
2200

20
GV2-PM32C+GV1-L3

LC1-D40AM7C+LAD4RC3U
GV2-PM08C

NG125L 2P

NG125L 3P

NG125L 2P
LC1-D09M7C+LAD4RCU

*3
C25

C80

C10

25
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

Auxiliary Power
Instrument
of 05-P01/P02/P03
Spare
15kW
1.5kW 05-P05
D 05-P04 D
30
BOER and may neither be used nor disclosed without its prior

35

40
E E

30 mm 700 mm 900 mm 30 mm

注:1,Cabinet with temperature controller and heater. Depth:600mm (PE) 1bx40x5/PH


2,Copper tin . (N) 2bx100x5/PH
F 3,Arrester,DC module, isolation transformer and hub install behind the cabinet. Only Front Access F
(A) 2bx100x5/PH 1900A
ITEM BUSBAR

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
ARRANGEMENT Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 13 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

PANEL UNMBER 01-MCC400-1


(WxHxD mm) (700mm*2200mm*600mm)
CIRCUIT NO.
A A
MAINBUA 2B*100*5
N BUS 2B*100*5

WITHSTAND CURRENT 50kA rms

SCHEMATIC OF MAIN CIRCUIT

B B

VOLTAGE 380V
PE BUS 1B*40*5

ITEM EQUIPMENT 05-P04 05-P05

Incoming Ligntning Arrester Isolation Transformer Service Water Pump Booster Pump
CIRCUIT DESCRIPTION Instrument Spare Auxiliary Power of 05-P01
C C

RATED POWER (KW) 380V/220VAC 1000VA 1.5kW 15kW


NOMINAL CURRENT (A) 3.6A 29.4A 25A 80A 10A
MAGNETIC/THERMAL 2.5-4A 24-32A
CIRCUIT BREAKER MT16N2 3P GV2PM08C GV2PM32C NG125L 2P NG125L 3P NG125L 2P
TRIP UNIT D/O MIC5.0E C25 C80 C10
ACCESSORY GVAE20C GV1-L3+GVAE20C
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

CONTACTOR LC1D09M7C LC1D40AM7C


ACCESSORY LAD-N40C+LAD4RCU LAD-N40C+LAD4RC3U
D THERMAL RELAY D
CURRENT SETTING
CURRENT TRANSFORMER 3*LMK2-0.66/80III 2000/5
AMMETER
BOER and may neither be used nor disclosed without its prior

VOLTAGE METER
MULTI FUNCTION METER PM5350P
CAPACITOR BANK
CONTROLE
LITHTING ARRESTER CPM-R100T
VFD/SOFTSTARTER
E E
REACTOR
FUSE 2*RT18-32 2P 10A
OTHER RM22-TR33
OTHER
OTHER
CABLE CROSS SECTION
SCHEMATIC DRAWING 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004

REMARK
F F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
SINGLE LINE DIAGRAM Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 15 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

FROM PAGE 15
PANEL UNMBER 01-MCC400-1 01-MCC400-2
(WxHxD mm) (700mm*2200mm*600mm) (900mm*2200mm*600mm)
A CIRCUIT NO. A

MAINBUA 2B*100*5
N BUS 2B*100*5

WITHSTAND CURRENT 50kA rms

SCHEMATIC OF MAIN CIRCUIT

B B

VOLTAGE 380V
PE BUS 1B*40*5

ITEM EQUIPMENT 05-P01 05-P02 05-P03

C CIRCUIT DESCRIPTION Auxiliary Power of 05-P02 Auxiliary Power of 05-P03 Treated Water Pump Treated Water Pump Treated Water Pump
C

RATED POWER (KW)


NOMINAL CURRENT (A) 10A 10A 800A 800A 800A
MAGNETIC/THERMAL
CIRCUIT BREAKER NG125L 2P NG125L 2P NS800N 3P F NS800N 3P F NS800N 3P F
TRIP UNIT C10 C10 MIC2.0 MIC2.0 MIC2.0
All technical information contained in this document is the exclusive property of

written consent. Only those drawings and diagrams remitted after order booking are
binding for execution. All devices shown in this diagram are in open position,

ACCESSORY MT+OF+SDE MT+OF+SDE MT+OF+SDE


CONTACTOR
ACCESSORY
D D
THERMAL RELAY
CURRENT SETTING
CURRENT TRANSFORMER 3*LMK2-0.66/80III 1000/5 3*LMK2-0.66/80III 1000/5 3*LMK2-0.66/80III 1000/5
BOER and may neither be used nor disclosed without its prior

AMMETER DM2315 DM2315 DM2315


VOLTAGE METER
MULTI FUNCTION METER
CAPACITOR BANK
CONTROLE
LITHTING ARRESTER
E E
VFD/SOFTSTARTER
REACTOR
FUSE
OTHER
OTHER
OTHER
CABLE CROSS SECTION
SCHEMATIC DRAWING 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004 01-DGT-EL-934-DD-004

F REMARK
F

DRAWING NO.
TLM EXTENSION PROJECT Single Line Diagram for TWPS MCC of TLM Plant
01-MCC400
01-DGT-EL-934-DI-004
CLIENT:
SINGLE LINE DIAGRAM Equipment Name
FIRST ISSUE 2018/8/21 A BOER (WUXI) POWER SYSTEM CO., LTD.

Modification Date Rev. Modification Date Rev.


PROJECT NO. B-001423 PAGE NO. 16 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20