SD) Relay Settings Calculations
SD) Relay Settings Calculations
SD) Relay Settings Calculations
Company Name:
FEEDER
Z1P Z1 UG +Z1A UG
Z1P 0.382 4.711 i Prepared By: MUHAMMAD SHAHID
Z1P 0.382+4.711i [email protected]
Z1P imbas 4.726 Ohm
Angle 85.364 Deg
Siemens 7SD/SA Distance Relay Settings calculation for XLPE and Oil Filled Joint Feeder
Z0P Z0 UG +Z0A UG
Z0P 1.875 1.233 i
Z0P 1.875+1.233i
Z0P imbas 2.244 Ohm
Angle 33.157 Deg
Xz1 Im (Z1Szone1)
4.184 Ohm
The standard value for the arc voltage UArc is approx. 2.5kV per meter of arc
length. For 132kV system UArc shall be as follows:
The resistance RL of the line itself can be ignored with SIPROTEC 4 devices. It is taken into account
by the shape of the polygon, provided that the inclination angle of the polygon Distance Angle (address
1211) is not set greater than the line angle Line Angle (address 1105).
The maximum arc resistance RArc must be determined for setting the distance zone in R
direction. The maximum arc fault resistance is attained when the smallest fault current at which
an arc is still present flows during an earth fault.
R Arc U Arc/(I1 + I2)
U Arc/(I1 x(1 + I2/I1))
U ArcP 2.5x(KV/m) (Per meter arc voltage)
L Arc 5m (Arc length)
U Arc L Arc x U ArcP (Total arc voltage)
12.5 KV
I1 2 KA (To cover max. fault resistance, we assume min.
fault current as 2kA.)
I2 0A
R Arc U Arc/(I1 x(1 + I2/I1))
I2/I1 I2oI1
I2oI1 3
R Arc U Arc/(I1 x(1 +I2oI1))
1.563 Ohm
R ArcS R Arc * (U sec/ U prim x Iprim/I sec)
1.633 Ohm
The following recommended setting applies for the resistance tolerance of distance zone Z1:
RE Z1 120% x ((1+I2/I1)x(RArcS+RTF/(1+RE/RL))
REoRL 1.303
RE Z1 120% x ((1+I2oI1)x(RArcS/(1+REoRL))
3.404
RE Z1S RE Z1 x (U sec/ U prim x Iprim/I sec)
3.557