Line Impedance Calculation : Name of The Feeder

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 22
At a glance
Powered by AI
The document discusses line parameters, impedances, relay settings and calculations for different types of feeders and lines.

The different types of conductors mentioned are Panther, Leopard, Zebra, Kundah and Dog.

The primary positive sequence impedance of the longest feeder line (110kv Gobi - Barrage III) is 3.19 Ω and the secondary positive sequence impedance is 1.91 Ω.

Line Impedance calculation ( GRID FEEDERS )

Name of the Feeder 110 Kv P' Kodiveri - Gobi #


Line Lenth Total = 13.8 kM
Name of the Conductor Zebra = 0 kM
Kundah = 0 kM
Panther = 2.42 kM
Leopard = 11.38 kM
Dog = 0 kM
Name of Shortest Feeder from other end 110 kv Gobi - KVPADI #
Line Lenth Total = 2.564 kM
Name of the Conductor Zebra = 0 kM
Kundah = 0 kM
Panther = 2.564 kM
Leopard = 0 kM
Dog = 0 kM
PRIMARY IMPEDANCE of shortest line R X Z ANGLE
Positive Seq Imp of shortest line (100 %) 0.4 0.99 1.07 68.0
Zero Seq Imp of shortest line (100 %) 0.78 3.62 3.7 77.8

Name of Longest Feeder from other end 110 kv Gobi - Barrage III #
Line Lenth Total = 68.951 kM
Name of the Conductor Zebra = 0 kM
Kundah = 0 kM
Panther = 68.951 kM
Leopard = 0 kM
Dog = 0 kM
CT ratio 600 1 Amp
Pt Ratio 110000 110 volt

PRIMARY IMPEDANCE R X Z ANGLE


Positive Sequen Impedance of the 100 % line 3.19 5.73 6.56 60.9
Zero Sequence Impedance of the 100 % line 5.23 19.45 20.14 74.9
Zone 1 primary Impedance of line= 80% of full
line 2.55 4.58 5.24 60.9
Zone 2 primary Impedance of line= 100% of
full line + 50 % of Shortest line 3.39 6.23 7.09 61.4
Zone 3 primary Impedance of line= 100% of
full line + 110 % of Longest line 14.95 35.08 38.13 66.9
SECONDARY IMPEDANCE R X Z ANGLE
Positive Sequen Impedance of the 100 % line 1.91 3.44 3.93 61.0
Zero Sequence Impedance of the 100 % line 3.14 11.67 12.09 74.9
Zone 1 Secondary Impedance of line= 80% of
full line 1.53 2.75 3.15 60.9
Zone 2 Secondary Impedance of line= 100% of
full line + 50 % of Shortest line 2.03 3.74 4.26 61.5

grterode Page 1 06/17/2020


Zone 3 Secondary Impedance of line= 100% of
full line + 110 % of Longest line 8.97 21.05 22.88 66.9

MICOM P 430 C SETTING


REACH
R1 PG = (12 Pri + R1 ) Rx PG Rx PP Xx
R1 PP = ( R1 + 6 Pri )
Zone -1 8.73 5.13 2.75 Ω
Zone - 2 9.23 5.63 3.74 Ω
Zone - 3 16.17 12.57 21.05 Ω
Zone - 4 = ( 10 % OF R3 ) 1.62 1.26

Load Angle B = COS 0.9 0.95 18.19 °


Z FW PG = 1.1* Z3 29.20 52.47 °
Z FW PP = 1.1* Z3 26.97 59.16 °
ZBW / Z FW
R fw PP
R fw PG
X fw

grterode Page 2 06/17/2020


RELAY SETTING CALCULATION 0F MICOM P 442
Zone IV Reverse 20 % of Zone I = 0.63 60.9
RESIDUAL COMPENSATION FOR EARTH FAULT
Kzo = (Zo - Z1) / 3Z1 = 0.71 20.5
Maximum Load Impedance=(V ph / In) Sec = 63.51 Ohm
Phase Fault Magin is 40 %
Earth Fault Margin is 20 % with Z load =
Maximum Resistive Reach for Phase Fault = 38.11
Maxium Resistive Reach for Earth Fault = 50.81
Fault MVA of 230 kv Bus = 1000 MVA
Maximum Fault Current at Ingur SS = Fault
MVA / 1.732*KV = 2510.29 Amps
Arc Resistance ( Ra)

grterode Page 3 06/17/2020


THR3PE1 RELAY SETTING
ZONE REACH ( Secondary Values ) Value Angle

ZONE - 1 3.15 60.91


ZONE - 2 4.26 61.51
ZONE - 3 22.88 66.92
Choose A = B = (4,8,16,24, 32,48) the next
higher Value of Zone-1 A= 4.00
Zone - 1 = ( A * G ) …… G= 0.79
Zone - 1 = ( A * G * H ) …… H= 1.4 M= 2
Zone - 1 = ( A * G * K * M ) …… K= 3.6
k = (Z 0 - Z 1) / 3*Z 1 k= 0.69
F = k*G F= 0.55

grterode Page 4 06/17/2020


8.00 24.00 24.00 32.00

grterode Page 5 06/17/2020


DIRECTIONAL BACK UP OVER CURRENT RELAY SETTING CALCULATION
ALL ZONE VALUES ARE PRIMARY
Name of the Feeder 110 kv P' kodveri - Gobi#

CT Ratio = 600 A

Plug Setting Multiplier of Over Current Relay = 1 pu

Fault MVA of 110 kV Bus of station A p' kveri = 2265 MVA

Fault MVA contributed by other End Station BGobi = 408 MVA

Source MVA = 1857 MVA

Source Impedance = 6.52 Ohms

Line Impedance up to the end of Z1 reach Z1 = 5.24 Ohms


Short Circuit MVA contributed by Station A p' kveri
for a fault at Z1 end ( say MVA 1 ) = 1028.91 MVA

Fault current on CT sec to Relay = 9A

Time from the 3 Sec Curve = 3.14 Sec

TMS to required for clear the fault at Z1 end = 0.191

Line Impedance up to the end of Z2 reach Z2 = 7.09 Ohms


Short Circuit MVA contributed by the Station A p' kveri
for a fault at Z 2 end ( say MVA 2 ) = 889.05 MVA

Fault current on CT sec to Relay = 7.78 A

Time from the 3 Sec Curve = 3.37 Sec

TMS to required for clear the fault at Z 2 end = 0.297

HIGHER OF THE TMS 1 & 2 = 0.297

TMS to be Adopted for O / C = 0.297

grterode Page 6 06/17/2020


grterode Page 7 06/17/2020
DIRECTIONAL BACK UP EATH FAULT RELAY SETTING CALCULATION
DIRECTIONAL EARTH FAULT RELAY SETTING CALCULATION
R X Z

Possitive Seq Impe of the Line(100 %) 3.19 5.73 6.56 Ohms

Zero Seq. Impe. of the Line (100 % ) 5.23 19.45 20.14 Ohms

Plug Setting Multiplier = 0.4 pu


Total fault Impe.up to the end of Z1 reach =
Source Impe + ((2 Z 1 *0.8+ Z O *0.8)/3) Z1 + ZF = 15.32 Ohms
Short Circuit MVA contributed by Station A for p' kveri
a fault at Z1 end ( say MVA 1 ) 63.5^2 / Z tot = 263.2 MVA

Fault current on CT sec to Relay = 17.27 A

Time from the 3 Sec Curve = 2.42 Sec

TMS to required for clear the fault at Z1 end = 0.248


Positive Sequence Impedance of Shortest
Line of other end ( 100 % ) 0.4 0.99 1.07 Ohms
Zero Sequ. Impe of Shortest Line of other End
( 100 % ) 0.78 3.62 3.7 Ohms
Total fault Impedance up to the end of Z 2 reach
= Source Impe + ((2 Z 1 + Z O )/3) Z2 + ZF = 18.49 Ohms
Short Circuit MVA contributed by Station A for p' kveri
a fault at Z 2 end ( say MVA 2 ) 63.5^2 / Z tot = 218.08 MVA

Fault current on CT sec to Relay = 14.31 A

Time from the 3 Sec Curve = 2.6 Sec

TMS to required for clear the fault at Z 2 end = 0.385

HIGHER OF THE TMS 1 & 2 = 0.385

TMS to be Adopted for E / F = 0.385

grterode Page 8 06/17/2020


grterode Page 9 06/17/2020
3.1 8.24 8.8

4.13 11.24 11.97

grterode Page 10 06/17/2020


AUTO TRANSFORMER HV & LV O/C RELAYS TLS CALCULATION SETTINGS
Name of the Sub Station : 230 / 110kv GOBI SS
Name of Auto Transformer : Auto - I EMCO
3 Phase Fault Level on 230 kv Bus = 5305 MVA
3 Phase Fault level on 110 kv Bus = 3051 MVA
Name of the 110 v feeder = TLS PSM UNIT
feeder 1 = 0.25 1 pu
feeder 2 = 0.2 1 pu
feeder 3 = 0.26 1 pu
feeder 4 = 0.14 1 pu
feeder 5 = 0.2 0.75 pu
feeder 6 = 0.2 1 pu
feeder 7 = 0 0 pu
feeder 8 = 0 0 pu
Highest TLS in 110 kv feeder from the above #s = 0.26 1 pu
Fault MVA Contribution from Other End of highest TLS # = 752 MVA
Total Fault MVA in the highest TLS feeder = 2299 MVA
C.T Ratio of the Highest TLS feeder = 600 /1A
PSM of the highest TLS feeder / TLS = 1 pu 0.26
Secondary Fault Current in that feeder = 20.11 A
From the IDMT 3 SEC Curve the time to clear the fault = 2.3
Actual Relay Operating Time of the Highest TLS # with it's
TLS of = 0.6 Sec
Add Grading Timeof 0.3 sec for LV of Auto Transformer = 0.9
Therefore Time to trip the Lv breaker = 0.9
% Impedance of Auto Transformer = 11.26 %
Capacity of the Auto transformer = 100 MVA
HV side voltage = 230 kV
Per Unit Impedance of the Auto Transfomer (MVA2 /
MVA1 )*(KV1^2 / KV2^2)*Per.Impe / 100 = 5.97 pu
Fault MVA contributed by Auto Trans. To 110 kv Bus = 761.12 MVA
Primary Fault Current on LV = 3994.96 A
LV CT Ratio = 600 / 1A
PSM of LV = 1.5 pu
Secondary Fault Current on LV = 4.44
Time to clear the fault current by LV = 4.63
Actualiy required time to clear the fault = ( X + 0.3) = 0.9 sec
Therefore TLS to be set on LV = 0.19
Fault Current on H.V side of the Auto Transformer = 1910.63
CT Ratio on H.V side = 600 A
PSM of H.V = 1.4 pu
Fault current on Secondary = 2.27
Time to clear the fault current by HV = 8.43
Actualiy required time to clear the fault = ( X + 0.3) = 0.9 sec

grterode Page 11 06/17/2020


Therefore TLS to be set on HV = 0.11

TAMIL NADU ELECTICY BOARD


GRID RELAY TESTS / ERODE
AUTO TRANSFORMER DIFFERENTIAL & O / C - HIGH SET CALCULATION
Name of the Sub Station : 230 / 110kv GOBI SS
Name of the Auto Transformer : Auto - I EMCO
Fault Level on 230 kv Bus = 5305 MVA
Fault level on 110 kv Bus = 3051 MVA
% Impedance of Auto Transformer = 11.26 %
Capacity of the Auto transformer = 100 MVA
HV side voltage = 230 kV
Per Unit Impedance of the Auto Transfomer (MVA2 / = 5.97 A
MVA1 )*(KV1^2 / KV2^2)*Per.Impe / 100
Fault MVA contributed by Auto Trans. To 110 kv Bus = 761.12 MVA
Primary Fault Current on LV = 3994.96 A
LV CT Ratio = 600 / 1A
Secondary Fault Current on LV = 6.66
150 % is Recommended fdor differential High set = 9.99 A
Therefore Diff.High Set to be set = 10.0
Max through fault MVA contributed to 110 kv Bus by the
Auto = 761.12 MVA
CT Ratio on H.V side = 600 A
Fault current on H.V. C.T Secondary = 3.18
150 % is Recommended fdor differential High set = 4.77 A
Therefore H.V - O /C high set to be set on
HV Relay = 4.8

grterode Page 12 06/17/2020


grterode Page 13 06/17/2020
grterode Page 14 06/17/2020
grterode Page 15 06/17/2020
grterode Page 16 06/17/2020
grterode Page 17 06/17/2020
grterode Page 18 06/17/2020
RAZOA RELAY SETTING CALCULATIONS :
Name of the Sub Station : 110kv Erode SS
Name of 110 KV Feeder : 110 KV SWTP SS #
CT Ratio : 600 /1A
P.T Ratio : 110000 / 110 V
Rf = 20 Ohms Primary for Ground Fault : 20 Ω
IMPEDANCE R X Z ANGLE
Primary Positive Sequen Impedance of the 100 % line(Z 1L ) = 1.72 2.42 2.97 54.6
Primary Zero Sequence Impedance of the 100 % line ( Z O L) = 2.60 8.45 8.84 72.9
Secondary Zone 1 Impedance = 0.83 1.16 1.43 54.4
Secondary Zone 2 Impedance of line = 1.48 2.15 2.61 55.5
Secondary Zone 3 Impedance of line = 2.53 4.16 4.87 58.7
Zero Sequence Compensation K N=(XoL-X1l)/(3*X1L) = 0.8
The Total Loop Resistance (PRIMARY)
RmL ( total) =( (ROL+2R1L)/3)+Rf = 21.61
The Total Loop Resistance (SECONDARY) (= Secondary
RmL ( total) =( (ROL+2R1L)/3)+Rf = 12.97 Ω Loop Resistace)
R1 = (RmL sec / 1 + KN ) = 7.08 Ω
R3 = ( R1* X3 / X1 ) = 25.40 Ω
Z Load Minimum (Sec )= ( U^2 / Max.MVA of the Feeder) = 63.51 Ω
Z Load Minimum (Sec )= ( U^2 / Max.MVA ) / 2 = 31.76 Ω
Determination of Setting Factors ………………………..X1 =
X1 < (3.2*f / In*50 ) ……………………………………….X 1 = 3.20
R1 < (3.2 / In ) ………….………………………………..R 1 = 3.20
a' = ( X1*In*50*99)/(3.2*50) …………………………….a = 35
P 1 = ( 3.2 * f * a )/(X 1 * In * 50) ………………………..P 1 = 96.55 = 97
b = (R 1* In * P 1) / 3.2 …………………………………b = 214.71 = 215
P 2 = (3.2 * f * a ) / ( X 2 * In * 50 ) …………………….P 2 = 52.09 = 52
P 3 = (3.2 * f * a ) / ( X 3 * In * 50 ) ……………………..P 3 = 26.92 = 27
CHECK FOR CAOCULATED SETTING FACTOR
X 1 = (3.2 * f * a ) / ( In * 50 * P 1 ) / Phase = 1.16 Ω
X 2 = (3.2 * f * a ) / ( In * 50 * P 2 ) / Phase = 2.15 Ω
X 3 = (3.2 * f * a ) / ( In * 50 * P 3 ) / Phase = 4.16 Ω
Impedance Start Unit Setting
Z max = 0.5 * Z Load minimum = 31.76 Ω
Choose type of Operating Characteristic : √ (R3^2 + X3^2 ) = 4.8689
> √ (R3^2 + X3^2 )
If Z max > √ (R3^2 + X3^2 )choose CIRCULAR characteristic : Z max
CIRCULAR CHARACTERISTICS ( S3:1 on at RGZB print)
: Z ά = 1.25 * √ (R3^2 + X3^2 ) = 6.09

grterode Page 19 06/17/2020


If Z ά = 4 - 64 then C = 4 ………………………………C = 4
N ά = Z ά * In / C……………...……………………………N ά = 2

grterode Page 20 06/17/2020


>
< Please ref Page No : 12
CIRCULAR CHARACTERISTICS ( S3:1 on at RGZB print)
: Z ά = 1.25 * √ (R3^2 + X3^2 )
OVAL CHARACTERISTICS ( S3:1 off at RGZB print)
: Z ά = Z max / (0.5 * (1+ Sin 10° )

grterode Page 21 06/17/2020


grterode Page 22 06/17/2020

You might also like